Sie sind auf Seite 1von 2

59 1/2 MIN ELECTRICAL REQUIREMENTS CUSTOMER CONNECTIONS

74 3/4 MAX VOLTAGE OPERATING FLA ITEM DESCRIPTION SIZE TYPE


(SEE NOTE 12) 240/60/1 15 AMPS A FEED WATER INLET 1" N.P.T.
32 1/2 (MIN WIDTH)
460/60/3 8 AMPS B BLOWDOWN OUTLET 1 1/4" N.P.T.
NOTE: OPERATING FULL LOAD AMPERAGE (FLA) C STEAM OUTLET 2" N.P.T.
REFERS TO THE BOILER'S RATED CURRENT DRAW D EXHAUST STACK 8" ---
SEE AT HIGH FIRE. E SAFETY RELIEF VALVE* 1" N.P.T.
NOTE F FUEL INLET 1 1/4" N.P.T.
9 G WATER COLUMN DRAIN 1" N.P.T.
H SIGHT GLASS DRAIN 1/4" N.P.T.
J WATER SAMPLE PORT 1/4" N.P.T.
K STEAM SAMPLE PORT 1/4" N.P.T.
L SURFACE BLOWDOWN 3/4" N.P.T.
M HIGH WATER PROTECTION (CAPPED) 3/4" N.P.T.
N PANEL BOX --- N.P.T.
P COMBUSTION AIR INLET 6" ---
7 1/8 AUXILIARY WATER COLUMN (CAPPED)
R 1" N.P.T.

11 3/4
E
EQUIPMENT SPECIFICATION CHART
MAX ALLOWABLE WORKING PRESSURE: 150 PSI
BOILER INPUT: 1,200,000 BTU/HR
P C
MIN: 62 1/16 BOILER INPUT: (NATURAL GAS) 1,200 CU FT/HR
MAX: 67 3/8 BOILER INPUT: (PROPANE) 480 CU FT/HR
(SEE NOTE 12) BOILER OUTPUT: 1,005,000 BTU/HR
24 1/8
STEAM OUTPUT/MIN. SRV CAPACITY: 1,035 LBS/HR
NET EFFECTIVE HEATING SURFACE: 65 SQ. FT.
WATER CAPACITY (OPERATING): 112 GAL.
APPROXIMATE DRY WEIGHT: 3,100 LBS.
APPROXIMATE OPERATING WEIGHT: 4,100 LBS.
APPROXIMATE SHIPPING WEIGHT: 3,400 LBS.
APPROXIMATE FLOODED WEIGHT: 4,400 LBS.
F BURNER TURNDOWN: 6:1
MINIMUM DRAFT REQUIREMENT: -0.25" W.C.
MINIMUM INCOMING GAS PRESSURE: 3" W.C.

NOTES:

1. STEAM OUTPUT LB/HR: FROM 0 PSIG AT 212 F (0 KG/CM AT


K 100 C)
SEE NOTES 3 AND 10
2. ALL CLEARANCES ARE FACTORY RECOMMENDATIONS. CONSULT
LOCAL JURISDICTION FOR EXACT CODE COMPLIANCE.
110
CLEARANCE M 3. FULTON RECOMMENDS MINIMUM CLEARANCE OF 36" IN FRONT
REQUIRED OF ELECTRICAL PANELS.
FOR BURNER
REMOVAL 4. FULTON RECOMMENDS 36" CLEARANCE BETWEEN INSPECTION
H OPENINGS OF ALL BOILERS, 18" CLEARANCE OF HANDHOLES,
85 9/16 AND 14" FROM EXHAUST STACK.
85 9/16
J D 5. PLEASE REFER TO THE O&M MANUAL FOR ADDITIONAL
82 3/4 INFORMATION REGARDING CLEARANCES AND INSTALLATION
79 1/8 80 13/16* INSTRUCTIONS.
L
(MINIMUM HEIGHT)
6. ALL DIMENSIONS INSIDE ( ) DENOTE REFERENCE DIMENSIONS.
R

G 7. ALL DIMENSIONS INSIDE DENOTE OVERALL DIMENSIONS.


A
51 8. WE RESERVE THE RIGHT TO CHANGE SPECIFICATIONS
AND/OR DIMENSIONS. ALL INFORMATION IS SUBJECT
49 1/8
TO CHANGE BASED ON ADDITION OF ANY OPTIONAL
EQUIPMENT AND/OR ACCESSORIES. PLEASE CONSULT THE
N FACTORY FOR PROJECT SPECIFIC ESTIMATES IF
ADDITIONAL OPTIONS OR ACCESSORIES ARE REQUIRED.

B 9. RECOMMEND STACK RUN IS MINIMUM 24" STRAIGHT OFF


THE REAR OF THE BOILER, PRIOR TO MAKING A
22 5/16
DIRECTIONAL CHANGE.

10. LOCAL CODES CAN SUPERCEDE FULTON RECOMMENDED


CLEARANCE.

11. *SIZE DEPENDS ON TRIM PRESSURE.


5
FRONT VIEW RIGHT SIDE VIEW 12. OVERALL SIZE MAY VARY BASED ON TRIM AND OPTIONS.
UNLESS OTHERWISE NOTED This design and drawings are The items shown in this DRAWN BY: MECHANICAL REVIEW: JOB NUMBER: DESCRIPTION:

Fulo
t n
DIMENSIONS ARE IN INCHES
TOLERANCES
FRACTION & 1/8
proprietary and are the
exclusive property of The
drawing may be covered by
one or more patents of The
S. WOODS 4/11/2018 W..W 7/23/2018 VSRT-30 GAS FIRED MODULATING STEAM BOILER
- INITIAL RELEASE - - - - - WHOLE VALUE
Fulton Companies. The Fulton Companies.
(1) PLACE DEC. 0.03 CHECKED BY: ELECTRICAL REVIEW: PROJECT NAME:
corporation does not permit 7/25/2018 N/A
(2) PLACE DEC.
(3) PLACE DEC.
0.015
0.005
J.F. Fulton Steam Solutions, Inc.
their use except with prior
ANGLE 0.5 DEG DRAWING NUMBER REVISION
SURFACE FINISH written consent.
REV REVISION DESCRIPTION B.O.M. ELEC. ENG. MECH. ENG CHECKED APPROVED
-
B.O.M. REVIEW: APPROVED BY: PROJECT MANAGER:

REVISION HISTORY
250 MICRO-INCHES
N/A E.B.W. 7/26/2018 6-91-290030 - PDS
THIRD ANGLE PROJECTION SHEET 1 OF 2
BURNER AND BLOWER
FUEL TRAIN

TRIM KIT

INSULATED BOILER

HIGH WATER PROTECTION


(OPTIONAL)

WATER COLUMN

SURFACE BLOWDOWN
(OPTIONAL)

CYCLONE AND COLLECTION CHAMBER

FEEDWATER

BOTTOM
BLOWDOWN

PANEL BOX
NOTES:
1. CUSTOMERS MAY REFER TO ORDER FORM FOR THE LIST OF
FEATURES AND OPTIONS RELEVENT TO THEIR CONFIGURATION.
EXPLODED VIEW 2. SOME OPTIONAL COMPONENTS SHOWN ON THIS PAGE.

UNLESS OTHERWISE NOTED This design and drawings are The items shown in this DRAWN BY: MECHANICAL REVIEW: JOB NUMBER: DESCRIPTION:

Fulo
t n
DIMENSIONS ARE IN INCHES
TOLERANCES
FRACTION & 1/8
proprietary and are the
exclusive property of The
drawing may be covered by
one or more patents of The
S. WOODS 4/11/2018 W..W 7/23/2018 VSRT-30 GAS FIRED MODULATING STEAM BOILER
- INITIAL RELEASE - - - - - WHOLE VALUE
Fulton Companies. The Fulton Companies.
(1) PLACE DEC. 0.03 CHECKED BY: ELECTRICAL REVIEW: PROJECT NAME:
corporation does not permit 7/25/2018 N/A
(2) PLACE DEC.
(3) PLACE DEC.
0.015
0.005
J.F. Fulton Steam Solutions, Inc.
their use except with prior
ANGLE 0.5 DEG DRAWING NUMBER REVISION
SURFACE FINISH written consent.
REV REVISION DESCRIPTION B.O.M. ELEC. ENG. MECH. ENG CHECKED APPROVED
-
B.O.M. REVIEW: APPROVED BY: PROJECT MANAGER:

REVISION HISTORY
250 MICRO-INCHES
N/A E.B.W. 7/26/2018 6-91-290030 - PDS
THIRD ANGLE PROJECTION SHEET 2 OF 2

Das könnte Ihnen auch gefallen