Sie sind auf Seite 1von 2

Document Title Document Number Issue Rev Date Approval Status

ET-Foundation Layout Plan WAHADLND-C-15-661 4 1 01/18/20

Category

SR. Description Dewa Specification/ DEWA Applicable Reference Complied with


Practice/ Guidelines/ Tender
document
1 Prerequisites documents/ requirements
1.1 Engineering design drawing is prepared, signed and endorsed by approved consultant. Dewa Practice Noted

1.2 Engineering design drawing is complete, dimensionally correct, readable and in compliance with other disciplines Dewa Practice Complied

1.3 Engineering design drawing is as per priority highlighted in DDCMS list . Dewa Practice Noted

1.4 DEWA approved title Block is used. Dewa Practice Complied

1.5 Engineering design drawing number and title are same as indicated in DDCMS. Dewa Practice Noted

1.6 Engineering design drawing is provided with List of required legends and references of related drawings.DEWA approval status of reference drawings with Dewa Practice Complied
revision number to be provided.
1.7 Compliance statement for the previous comments (if any) is enclosed and all the comments are complied. Dewa Practice Complied

1.8 Copy of approved Architectural Drawing No's 479, 281 & 282 is attached as a reference Dewa Practice Complied

1.9 Copy of approved Soil Report is attached as a reference Dewa Practice Complied
2 Confirmation List
2.1 Drawings are in compliance with calculations. Dewa Practice Complied

2.2 Detailing of Reinforcement is in line with standard detailing practices as per applicable DEWA specification. Dewa Practice Complied

3 Technical detailed Check points


3.1 Engineering
3.1.1 Gate level of +0.00 with Reference to DMD is incorporated in the drawing. Dewa Practice Complied
3.1.2 The main reinforcement mesh provided and the extra top & bottom bars for the Raft are as per calculation requirement . Standard Complied
3.1.3 Extra reinforcement provided are marked by symbols and given in a tabular form. Standard Complied
3.1.4 Size and spacing of starter bars for staircase and basement walls are checked. Dewa Practice N/A
3.1.5 Anchorage length of the reinforcement is checked. Minimum lap/anchorage length is 50 times the smaller bar dia. Standard Complied
3.1.6 Screed above the Raft is provided with reinforcement to reduce crack formation on surface calculated based on screed thickness. Standard Complied
3.1.7 Steel with yield strength fy=460N/mm2 and Concrete with Characteristic compressive strength Fcu= 40N/mm2 are consistant with DEWA specification. Dewa Specification Complied
3.1.8 Punching Shear reinforcement under the columns ( if required) are indicated with the spacing of the links as per the approved calculations. Standard Complied
3.1.9 Drain Pipe sleeves, drain channels, slope direction inside the drain channel & sand trap pit details are as per Approved Drainage drawings. Dewa Specification Clause No.3.4.4.1 Para (920) Rev.15 Complied
3.1.10 Local thicknening is provided under the sand trap pit in the Raft depending on the pit level. Standard Complied

3.1.11 Water proofing membrane for all concrete faces in contact with soil is as per DEWA 132/11kV specification Dewa Specification Clause No.3.3 .48.1 Para 727 Complied
3.1.12 Distance of IDT/ET trench walls from the respective grids is checked . Dewa Practice Complied

3.1.13 Sectional elevation drawings which indicates the bottom and top levels of Raft, top of screed & top of RC wall is checked and verified with DMD level. Dewa Practice Complied

3.1.14 Extension of Raft from Building footprint is done after coordination with underground services. Dewa Specification Clause No.3.2.4 Para( 45) N/A

3.1.15 Cover to the reinforcement for the face of Raft in contact with soil is minm.75 mm. Standard Clause No.3.3.42.Para (546) Table 3.7 Complied
3.1.16 Column locations and their axis orientation are inline with approved Architechtural drawings. Dewa Practice Complied
3.1.17 The safe bearing capacity and water table level are as per the Soil Report and is mentioned in the notes on the drawing. Dewa Practice Complied
3.1.18 Screed depth at junction of drain trench and cable sleeves are checked. Dewa Practice Complied

All rights reserved © TED-2016 1 CL-issue-4, Rev.0


Document Title Document Number Issue Rev Date Approval Status
ET-Foundation Layout Plan WAHADLND-C-15-661 4 1 01/18/20

Category
3.1.19 Cables are marked inside screed as per approved cable route layout to check the screed depth. Complied
SR. Description Applicable Reference Complied with
RAFT ON PILE CHECK
N The Pile layout and Type of the pile (Tension or compression) are based on the approved Design Calculation. Dewa Practice N/A
3.1.20 Working Pile load Capacities (Compression, tension/uplift and lateral ) is inline with the approved soil report. Dewa Practice N/A

3.1.21 Diameter and total number of piles are provided in a tabular form Dewa Practice N/A

3.1.22 Section and plan showing reinforcement details for pile caps ( with single, double,three or more pile groups) are provided. Dewa Practice N/A

3.1.23 Diameter, spacing and depth of the piles are mentioned in the notes on the drawing. Standard N/A

3.1.24 Reinforcement details of Pile cap is inline with the approved Design calculation. Standard N/A

3.1.25 Side face reinforcementis is provided for the pile caps to control temperature and shrinkage cracks. Standard N/A

3.2 Inspection
3.2.1 Cables arrangement to be as per approved cable route layout, copy to be attached for referance Complied
3.2.2

3.3 Construction & Installation


3.3.1
3.3.2

3.4 Testing & Commissioning


3.4.1
3.4.2

3.5 Maintenance
3.5.1
3.5.2

Prepared By: LEAD Checked By: KEC Approved By:

DEPARTMENT HEAD

All rights reserved © TED-2016 2 CL-issue-4, Rev.0