Sie sind auf Seite 1von 66

Standard Design Document

Clearguard ACM 200


Axle Counting System

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 1 of 66
The contents of this translation correspond to the German document with the number
A6Z00033086139/A.

Document history
Version Release Sections Reason
date changed
- 2013-07-08 All First issue

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited.
Offenders will be held liable for payment of damages. All rights created by patent grant or
registration of a utility model or design patent are reserved.

Siemens AG
Postfach 33 27
38023 Braunschweig
Germany
www.siemens.com
rail-automation.mobility@siemens.com

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 2 of 66
Contents
1 Information for the user.................................................................................................... 5
About this document ........................................................................................................... 5

2 Functional overview.......................................................................................................... 9
Structure of axle counting system....................................................................................... 9
Indoor equipment .............................................................................................................. 10
Outdoor equipment ........................................................................................................... 14

3 Indoor equipment............................................................................................................ 16
3.1 ACM .................................................................................................................................. 16
One module for all track vacancy detection tasks ............................................................ 16
3.2 ACM interfaces ................................................................................................................ 18
Interfaces of ACM ............................................................................................................. 18
3.3 Power supply................................................................................................................... 20
Optional power supply module.......................................................................................... 20
3.4 Switches........................................................................................................................... 21
Switch: selection criteria and connection of power supply................................................ 21
3.5 Pin assignment................................................................................................................ 23
Connections of ACM ......................................................................................................... 23
3.6 Cables of indoor equipment .......................................................................................... 31
Properties, wiring and cable laying ................................................................................... 31

4 Outdoor equipment......................................................................................................... 33
4.1 Structure of outdoor equipment.................................................................................... 33
Information about structure of outdoor equipment............................................................ 33
4.2 Cables of outdoor equipment ........................................................................................ 34
Properties, wiring and requirements ................................................................................. 34
4.3 Control distance restrictions ......................................................................................... 35
Interference voltage, armoring, and loop resistance......................................................... 35
4.4 Connection of wheel detection equipment................................................................... 37
Signaling cable to be used and connection ...................................................................... 37

5 Earthing and protective measures ................................................................................ 38


5.1 Earthing and protective measures: concepts .............................................................. 38
Agreement on earthing and protective measures with rail operator ................................. 38
Concepts for earthing and protective measures ............................................................... 38
5.2 Operator safety................................................................................................................ 39
Earthed or earth-free installation....................................................................................... 39
5.3 Earthing and protective measures for DB AG's alternating current traction systems40
Design examples of earthing and shielding concept ........................................................ 40
5.4 Earthing and protective measures for DB AG's direct current traction systems .... 43
Earthing and shielding concept......................................................................................... 43

6 Interface to higher-level system .................................................................................... 45


6.1 Relay outputs .................................................................................................................. 45
Mode of operation and connection examples of relay outputs ......................................... 45
6.2 AZGT/AZGH inputs on process connector................................................................... 50

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 3 of 66
Inputs................................................................................................................................. 50
6.3 Ethernet interface............................................................................................................ 53
Data transmission via public telephone networks............................................................. 53
6.4 Response times............................................................................................................... 53
Track occupied indication delay........................................................................................ 53

7 Installation, acceptance and commissioning .............................................................. 56


Installation, acceptance and commissioning .................................................................... 56
Insulation measurement.................................................................................................... 57
Checks upon acceptance and commissioning ................................................................. 57

8 Parts list ........................................................................................................................... 58


Parts list ............................................................................................................................ 58

9 Technical data ................................................................................................................. 62


Technical data................................................................................................................... 62

10 Indices .............................................................................................................................. 65
List of abbreviations .......................................................................................................... 65
List of figures ..................................................................................................................... 66
List of tables ...................................................................................................................... 66

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 4 of 66
Information for the user

1 Information for the user

About this document

Scope
This document applies to the Clearguard ACM 200 axle counting system in equipment
revision level 1. The Clearguard ACM 200 axle counting system is referred to below sim-
ply as axle counting system.

Purpose
This document supports the following staff in their work:
• technical sales staff
• configuring engineers
• project staff
• commissioning staff
This document describes the system design for planning an axle counting system with
wheel detection equipment. This document does not claim to supply all the information
required for projects. No country- or project-specific conditions are described. More de-
tailed information can be found in the referenced documents.
Below a section heading or safety information box within this document, reference is
made to safety-related requirements from the SAV-B. The notation in use is:
SAV-B <identifier_1>, …, <identifier_n>
Only one identifier can be specified.

This documentation is part of the equipment described.


This documentation is part of the equipment described. It must be kept in a safe place
throughout the lifetime of the equipment described. Make this documentation available to
the personnel responsible for the activities described. If you receive any additions from
Siemens at a later date, insert them in the documentation.

Supplementary documents
The following documents are also important as supplementary documents:

Reference ID Title Document number


[SD] System Description A6Z00034296029
Clearguard ACM 200 Axle Counting System
[MI] Maintenance Instructions A6Z00034296081
Clearguard ACM 200 Axle Counting System
[CI] Configuration Instructions A6Z00034626179
Clearguard ACM 200 Axle Counting System

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 5 of 66
Information for the user

Reference ID Title Document number


[SAV-B] Safety-related Application Conditions for Operators A6Z00034626218
Clearguard ACM 200 Axle Counting System
[ZPD] Operating and Service Manual ZP D 43 Wheel Detec- A6Z00001887496
tion Equipment
[ZPE] Operating and Service Manual ZP 43 E Wheel Detection A6Z08110055889
Equipment
[ZPV] Operating and Service Manual ZP 43 V Wheel Detection A6Z08110055839
Equipment
[EC] Earthing Concept A6Z08110042822, as
Earthing and Protective Measures for Indoor Equipment from 2006
of Siemens Interlockings
[EC-AC] Earthing Concept (AC Variant) A6Z08110458576, as
Earthing and Protective Measures in Outdoor Equip- from 2005
ment of AC-electrified Railways for Siemens Interlock-
ings
[EC-DCSE] Earthing Concept (DC SE Variant) A6Z08110470932, as
Earthing and Protective Measures in the Outdoor Equip- from 2005
ment of DC-electrified Railways with Structural Earthing
(SE) for Siemens Interlockings
[EC-DCRS] Earthing Concept (DC RS Variant) A6Z08110470986, as
Earthing and Protective Measures in the Outdoor Equip- from 2005
ment of DC-electrified Railways (DC) with Earthing to
the Return System (RS) for Siemens Interlockings
[EC-ACDC] Earthing Concept (AC/DC Variant) A6Z08110030436, as
Earthing and Protective Measures in the Outdoor Equip- from 2005
ment of AC/DC Mixed Operation (AC and DC Traction
on the Same Track) for Siemens Interlockings
[EC-NER] Earthing Concept (NER Variant) A6Z08110030558, as
Earthing and Protective Measures in Outdoor Equip- from 2005
ment of Non-electrified Railways for Siemens Interlock-
ings
[OI-Scalance] Operating Instructions Scalance X208, Industrial A5E00349864
Ethernet
[OI-S7_2A] Operating Instructions Simatic S7-300, AC/DC Power C98130-A7535-A1-*-19
Supply
Power Rating of 2 A
[OI-S7_5A] Operating Instructions Simatic S7-300, AC/DC Power C98130-A7537-A1-01-
Supply 19
Power Rating of 5 A

Table 1 Supplementary documents

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 6 of 66
Information for the user

Standards and guidelines


The following standards and guidelines must be observed when setting up the axle count-
ing system:

German standards
DIN VDE 0100-410:2007-06 Low-voltage electrical installations, Part 4-41: Protection for
safety – Protection against electric shock (IEC 60364-4-41:2005,
modified); German implementation of HD 60364-4-41:2007
DIN VDE 0100-520:2003-06 Electrical installations of buildings, Part 5: Selection and erection
of electrical equipment; Chapter 52: Wiring systems
DIN VDE 0100-600:2008-06 Low-voltage electrical installations, Part 6: Verification (IEC 60364-
6:2006, modified); German implementation of HD 60364-6:2007
DIN VDE 0105-100:2009-10 Operation of electrical installations, Part 100: General require-
ments; German implementation of Chapter 62 of HD 60364-6:2007
DIN VDE 0228-1:1987-12 Proceedings in the case of interference on telecommunication in-
stallations by electric power installations; general
DIN VDE 0228-3:1988-09 Proceedings in the case of interference on telecommunication in-
stallations by electric power installations; interference by alternat-
ing current traction systems
DIN VDE 0228-4:1987-12 Proceedings in the case of interference on telecommunication in-
stallations by electric power installations; interference by d.c. trac-
tion systems
DIN VDE 0816-2:1988-02 External cables for telecommunication and data processing sys-
tems; signal and measuring cables, mining cables
DIN VDE 0831:2006-04 Electric signaling systems for railways
European standards
DIN EN 50085-1:2006-03-01 Cable trunking systems and cable ducting systems for electrical
installations
EN 50121-4:2006-07-01 Railway applications – Electromagnetic compatibility, Part 4:
Emission and immunity of the signaling and telecommunications
apparatus / Corrected and reprinted in 2008-05 / Applies in con-
junction with EN 50121-1:2006-07
EN 50159:2010-09-01 Railway applications – Communication, signaling and processing
systems – Safety-related communication in transmission systems
EN 50178:1997-10-01 Electronic equipment for use in power installations
DIN EN 60529:2000 Degrees of protection provided by enclosures (IP code)
(IEC 60529:1989 + A1:1999)
DIN EN 60721-3-1:1997 Classification of environmental conditions – Part 3: Classification
of groups of environmental parameters and their severities; Main
section 1: Storage
(IEC 60721-3-1:1997); German version of EN 60721-3-1:1997
DIN EN 60721-3-2:1997 Classification of environmental conditions – Part 3: Classification
of groups of environmental parameters and their severities; Main
section 2: Transportation
(IEC 60721-3-2:1997); German version of EN 60721-3-2:1997
DIN EN 60721-3-3:1995 Classification of environmental conditions – Part 3: Classification
of groups of environmental parameters and their severities; Main
section 3: Stationary use at weather-protected locations
(IEC 60721-3-3:1994); German version of EN 60721-3-3:1995

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 7 of 66
Information for the user

EN 60950-1:2010-03-01 Information technology equipment – Safety, Part 1: General re-


quirements (IEC 60950-1:2005, modified + Cor.:2006 + A1:2009,
modified); German version of EN 60950-1:2006 + A11:2009 +
A1:2010
EN 61000-6-2:2005-08-01 Electromagnetic compatibility (EMC), Part 6-2: Generic stan-
dards – Immunity for industrial environments (IEC 61000-6-
2:2005)
EN 61000-6-4:2007-01-01 Electromagnetic compatibility (EMC), Part 6-4: Generic stan-
dards – Emission standard for industrial environments (IEC 61000-
6-4:2006); German version of EN 61000-6-4:2007
DIN EN 61386-21:2004-08-01 Conduit systems for cable management
+ A11:2010-12-01
DIN EN 61386-23:2004-08-01
+ A11:2010-12-01
International standards
IEC 61084-1:1991-06-01 Cable trunking and ducting systems for electrical installations
IEC 61084-2-1:1996-01-01
IEC 61084-2-2:2003-05-01
IEC 60364-4-41:2005-12-01 Low-voltage electrical installations, Part 4-41: Protection for
safety – Protection against electric shock
IEC 60364-6:2006-02-01 Low-voltage electrical installations, Part 6: Verification
DB AG guidelines
Dlk 1.013.109y Signalkabel in Sternviererverseilung mit PE-Isolierung und PE-
Mantel – Pflichtenheft (Star-quad signaling cables with PE insula-
tion and PE jacket – system design specifications)
Dlk 1.013.110, 09/99 Signalkabel in adriger Verseilung und in Sternviererverseilung mit
PE-Isolierung und PE-Mantel – Technisches Kennblatt der DB AG
(Star-quad and core-stranded signaling cables with PE insulation
and PE jacket – engineering specifications of DB AG)
Dlk 1.013.201y, 09/91; Pflichtenheft für Eisenbahn-Signalkabel in Sternviererverseilung
DB AG mit PE-Isolierung und PE-Mantel (System design specifications for
star-quad signaling cables with PE insulation and PE jacket)
Dlk 1.013.990t, 10/99 Technische Anweisung für die Errichtung von Sicherungskabelan-
lagen, Technische Anweisungen der DB AG (Technical instructi-
ons for the installation of signaling cable systems, technical in-
structions of DB AG)
Guideline 819.0802 (DB) DB-Richtlinie, LST-Anlagen planen; Beeinflussung und Schutz-
maßnahmen, Starkstrombeeinflussung, Induktive Beeinflussung,
Übersicht (DB guideline, planning of signaling and control sys-
tems, interference and protective measures, exposure to power
lines, inductive interference, overview)
Guideline 892.9320.50 (DB) Prüfungsnachweis für elektrische Energieanlagen bis 1000 V
inklusive Messprotokoll (Test verification for electrical energy sup-
ply systems up to 1000 V including test record)
Guideline 997.02 Oberleitungsanlagen: Rückstromführung, Bahnerdung, Potenzia-
lausgleich (Overhead contact line systems: traction current return,
railway earth connection, potential equalization)
Guideline 997.0204 Bahnerdung planen (Planning of railway earth connection)

Table 2 Standards and guidelines

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 8 of 66
Functional overview

2 Functional overview

Structure of axle counting system

Axle counting system

Figure 1 Schematic representation of an axle counting system

The axle counting system consists of two parts:


• indoor equipment
• outdoor equipment

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 9 of 66
Functional overview

Indoor equipment

Modular design
The indoor equipment of the axle counting system comprises individual modules (ACMs),
a cable termination rack and connecting cables, permitting an axle counting system of
any size to be implemented. A number of ACMs can be installed directly side by side on a
122 mm mounting rail in a space-saving arrangement since all interfaces are located in
the lower section of the ACM housing.

Functions of axle counting system


The axle counting system has the following functions:
• evaluation of the audio-frequency signals transmitted by the wheel detection equip-
ment
• comparison of the number of axles counted into a track vacancy detection section
(TVDS) with the number of axles counted out
• monitoring of the track vacancy detection sections and output of the clear and occu-
pied indications
• transmission of operator-specific safety-related information (SRI) via the floating re-
lay interface of the axle counting system to any interlocking or subsystem

Inputs and outputs of axle counting system


In addition to the fail-safe relay output of clear and occupied indications for two track va-
cancy detection sections, it is possible, for each track vacancy detection section, to out-
put a single-channel reset restriction (RR) and reset acknowledgment (RA). Instead of
clear and occupied indications, it is also possible to output safety-related information (SRI)
of a different ACM or the "pulse detected" indication of the locally connected wheel detec-
tion equipment. Operability of the ACM (BOK) can be output on a single channel.
Axle count reset operations (AZG, VAZG) are evaluated via fail-safe optocoupler inputs.
Via an optional dual-channel auxiliary axle count reset operation (AZGH), the RR can be
canceled or a commissioning operation be performed or safety-related information be
read in and transmitted to a partner ACM.
As an alternative to the auxiliary axle count reset operation, a secondary axle count reset
procedure can be executed via the AZGH inputs.

Ordering information
Ordering information about the components of the indoor equipment can be found in the
parts list (see “Parts list” on page 58).

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 10 of 66
Functional overview

Design example of indoor equipment

1 122 mm mounting rail 7 System cable


2 Power supply module (optional) 8 Power supply terminal strip
3 Switch 9 Cable duct
4a Socket for ID plug 10 Process connection terminal strip
4b ID plug for ACM 200 11 Retaining rail
5 ACM (axle counter module) 12 WDE terminal strip
6 Ethernet socket 13 Block varistor

Figure 2 Design example of the indoor equipment

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 11 of 66
Functional overview

Power supply for ACMs


The power supply for the ACMs permits variable adaptation to available supply networks.
If a mains supply at 24 V DC is not available for the power supply, different power supply
modules are available for optimal adaptation. The power is fed into the ACM via the proc-
ess connector.

Connection of ACMs via switches to set up network


For connecting a number of ACMs, switches are mounted on the mounting rail. The
ACMs are interconnected via the switches to form an Ethernet network using IE FC TP
(CAT5 or higher) Ethernet cables.

System cable
The ACM is connected to control elements, an interlocking or the wheel detection equip-
ment via its process connector. The system cable is used to connect the process connec-
tor of the ACM to all cables from these elements. It is mechanically secured by means of
clamps.

Overvoltage protection
We recommend protecting the outdoor cables connected in the cable termination
rack/cabinet by means of additional overvoltage protection elements (type 4 lightning pro-
tection module on the basic terminal block and overvoltage arrester (block varistor)).
More detailed information relating to overvoltage protection can be found in [EC].

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 12 of 66
Functional overview

Installation space for ACM


Minimum clearances between the components (installation space for the ACM) must be
observed when setting up an axle counting system by means of ACM levels arranged
underneath each other. The figure below shows the required clearances of an ACM level:

1 Rack or cabinet 3 ACM


2 122 mm mounting rail 4 System cable

Figure 3 Clearances for the ACM installation space

Installation in racks or cabinets


A number of mounting rails, shield buses, terminal strips and cable ducts can be installed
underneath each other in racks or cabinets.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 13 of 66
Functional overview

Outdoor equipment

Part of outdoor equipment – type ZP wheel detection equipment


The outdoor equipment comprises the following components:
• wheel detection equipment (consisting of DEK double wheel detector and trackside
connection box with electronic unit)
• cables from the DEK double wheel detector to the trackside connection box
• cables from the cable termination rack in the interlocking to the trackside connection
boxes and cable distribution boxes
The wheel detection equipment is installed at the limits of a track vacancy detection sec-
tion.

1 DEK receiver
2 DEK transmitter
3 Trackside connection box with evaluation electronics
4 Signaling cable

Figure 4 Type ZP wheel detection equipment on the track

The axle counting system is combined with type ZP wheel detection equipment (ZP 43 E,
ZP 43 V or ZP D 43) with audio-frequency interface. The system parts are interconnected
by means of cables from the cable termination rack/cabinet in the interlocking to the
trackside connection boxes and cable distribution boxes. The wheel detection equipment
is powered as follows:
• directly via the axle counting system; in this case, the power supply is isolated to
earth potential
• from a separate power supply (external supply)

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 14 of 66
Functional overview

The earth-free supply of the wheel detection equipment can be monitored using auto-
matic earth leakage detectors (to be ordered and installed separately). When not using
this automatic earth leakage detectors, insulation measurement must be performed
manually. Manual insulation measurement must be performed before commissioning and
then cyclically. We recommend performing cyclic measurement every 24 months.

Components of wheel detection equipment


Wheel detector: type ZP wheel detection equipment (ZP 43 E, ZP 43 V and ZP D 43)
uses the DEK electronic double wheel detector. It consists of a separate transmitter and
receiver with an operating frequency of 43 kHz. The transmitter and receiver are installed
opposite each other on either side of a rail, the transmitter on the outer side and the re-
ceiver on the gage side.
Trackside connection box: the evaluation electronics of the wheel detection equipment
are accommodated in the trackside connection box. The two connecting cables of the
wheel detector and the trackside cable enter the box through cable glands. Rubber gas-
kets in the cable glands ensure that the box is hermetically tight. This design of the track-
side connection box provides, on the one hand, protection as per IP67 and, on the other,
adequate access to the electrical equipment. A climate lock on the underside permits a
slow pressure equalization with the environment. This lock has a semi-permeable mem-
brane which allows moisture to leave the box but prevents water from entering it.

Ordering information
Ordering information about the components of the outdoor equipment can be found in the
Operating and Service Manuals of the wheel detection equipment.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 15 of 66
Indoor equipment
3.1 ACM

3 Indoor equipment

3.1 ACM

One module for all track vacancy detection tasks

ACM applications
The ACM is the main component of the axle counting system. The ACM is suitable for
connecting two sets of wheel detection equipment and monitoring two track vacancy de-
tection sections. The integral control and display unit on the front panel of the ACM per-
mits direct input to the ACM (reset button, cancelation of reset restriction, initiation of
calibration, and direction reversal). For diagnostic purposes, LEDs on the front panel are
provided which show a steady or flashing green, yellow or red light.

Figure 5 ACM dimensions

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 16 of 66
Indoor equipment
3.1 ACM

Elements on ACM front panel


Element Meaning
A Socket for ID For inserting the configuring connec-
plug tor with lettering field
B RST button Reset button (resets the ACM)
1 OK LED ACM board is OK (BOK)
2 TVDS1 LED Track vacancy detection section 1
(TVDS 1)
3 TVDS2 LED Track vacancy detection section 2
(TVDS 2)
4 DS1.1 LED Double wheel detector 1 (channel 1)
5 DS1.2 LED Double wheel detector 1 (channel 2)
6 DS2.1 LED Double wheel detector 2 (channel 1)
7 DS2.2 LED Double wheel detector 2 (channel 2)
8 RR1 LED Reset restriction 1 (RR indication for
TVDS 1)
9 RR2 LED Reset restriction 2 (RR indication for
TVDS 2)
10 COM LED All fail-safe connections are OK
C RST-RR1 Reset button for reset restriction 1
button Cancelation of RR for TVDS 1
(AZGH)
D RST-RR2 Reset button for reset restriction 2
button Cancelation of RR for TVDS 2
(AZGH)
E RJ45 socket Ethernet interface
11 CAL LED Indication of calibration
F CAL button Button for calibration
12 DIR1 LED Indication of direction reversal for
double wheel detector 1
G DIR1 button Button for direction reversal for dou-
ble wheel detector 1
13 DIR2 LED Indication of direction reversal for
double wheel detector 2
H DIR2 button Button for direction reversal for dou-
ble wheel detector 2
I SIM1 socket No function
L SIM2 socket No function
M F1 fuse Fuse for double wheel detector 1
N F2 fuse Fuse for double wheel detector 2

Figure 6 Front panel of the ACM

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 17 of 66
Indoor equipment
3.2 ACM interfaces

3.2 ACM interfaces

Interfaces of ACM

Overview of interfaces
The ACM provides the following interfaces:
• ID plug
• Ethernet
• process connector
• SIM1, SIM2 sockets

ID plug socket
A 9-pin socket for a programmable configuring connector (ID plug) is located in the upper
front section of the ACM. The ID plug has a non-volatile memory. The configuration data
specific to each ACM is loaded onto the ID plug. The associated track vacancy detection
section can be written on the front of the ID plug. The ID plug can be removed and in-
serted without a tool.
The 9-pin socket of the ACM is exclusively used for the ID plug.
SAV-B <IO5>

Ethernet interface
An Ethernet interface is available in the lower front section of the ACM. The RJ45 socket
is used for connection to a network. An ACM network can be set up in this way. Switches
are used for interconnecting a number of ACMs.
Using the Ethernet interface, configuration data can be loaded via the ACM onto the ID
plug. The interface can also be used to output diagnostic data.
For the optional connection of a local diagnostic PC, one RJ45 socket per cabinet or rack
should be kept free on a switch.
When using two ACMs, a direct connection without a switch can be set up between the
ACMs. A diagnostic interface is not available when using this type of connection.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 18 of 66
Indoor equipment
3.2 ACM interfaces

Process connector
On the underside of the ACM, there is a 96-pin male connector for connecting a system
cable.
The following connections are combined on the process connector:
• Two dual-channel relay outputs for track vacancy detection sections 1 and 2:
− The clear and occupied indications are transmitted via floating relay contacts.
For the relay output, either an equivalent or a non-equivalent connection can be
used.
− The outputs can alternatively be used to output safety-related information (SRI)
or the "pulse detected" indication of locally connected wheel detection equip-
ment.
• Four dual-channel floating inputs:
− AZGT inputs for:
1. Axle count reset (AZGT) per TVDS
or
2. Read-in of safety-related information (SRI) if the associated TVDS is not
used
− AZGH inputs for:
1. Auxiliary axle count reset (AZGH) per TVDS (can be optionally used; there
are also buttons on the front panel of the ACM for AZGH)
or
2. Secondary axle count reset (AZG) per TVDS
or
3. Commissioning operation for manually setting a track vacancy detection sec-
tion to the occupied state
or
4. Read-in of safety-related information (SRI) if the associated TVDS is not
used
• Five single-channel relay outputs:
− Reset restriction (RR) per TVDS
− Reset acknowledgment (RA) per TVDS
− Operability of the ACM (BOK relay)
• Two interfaces for wheel detection equipment
• 24 V DC power supply interface and two terminals for potential equalization (earth or
rack potential)
SAV-B <IO1>, <IO2>, <IO3>, <IO6>, <PS32>

SIM1, SIM2 sockets


The SIM1 and SIM2 sockets are available on the front panel of the ACM. These sockets
must not be used.
SAV-B <IO8>

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 19 of 66
Indoor equipment
3.3 Power supply

3.3 Power supply

Optional power supply module

SAV-B <PS32>

Application of optional power supply module


If a 24 V DC power supply is available, a separate power supply may not be necessary
for the axle counting system.
In all other cases, we recommend using a power supply module from the Simatic S7-300
product line. These power supply modules can be used to power the ACMs and switches
without further checking the technical properties.

Requirements for supply voltage


The supply voltage must be between 21.6 V and 31.2 V DC.
Note: The ACM features reversible protection against overvoltage in the 24 V supply.
The ACM is switched off if the supply voltage exceeds 31.2 V. To put the ACM into op-
eration again, the supply must be disconnected briefly.
The supply voltage for the axle counting system must not permanently exceed 60 V DC
even in the event of a fault. 120 V DC are permissible for max. 200 ms.
Note: Commercial off-the-shelf power supplies designed in accordance with the SELV
principle as per EN 60950-1 meet the stated requirements (e.g. Sitop PS 307).
The ACM produces a maximum inrush current of 2.4 A.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 20 of 66
Indoor equipment
3.4 Switches

Recommended power supply modules


The selection of the desired power supply modules depends on the following parameters:
• climatic conditions
• available input voltage
• required output current
The following power supply modules are available (see “Parts list” on page 58):

Temperature range, Power supply modules


input voltage
0 °C to +60 °C, Sitop PS 307, output current of 2 A
120/230 V AC Sitop PS 307, output current of 5 A
Sitop PS 307, output current of 10 A
-25 °C to +60 °C, Siplus PS 305, output current of 2 A
120/230 V AC Siplus PS 305, output current of 5 A
-25 °C to +60 °C, Siplus PS 305, output current of 2 A
24/110 V DC
-40 °C to +60 °C, Sicas Sitop PS 305, output current of 5 A
120/230 V AC

Table 3 Temperature ranges and input voltages

Note relating to temperature range:


Some of the power supply modules can also be used at a temperature of 70 °C with a
reduced power – see data sheet of the power supply module.

3.4 Switches

Switch: selection criteria and connection of power supply

Switch applications
Switches are required for the Ethernet connection of the ACMs. We recommend using
the Scalance product family.
The use of network hubs is not permitted for the Ethernet connection of the ACMs.

Applications:
• for interconnecting ACMs to form networks
• for connection of a standard PC for configuration and diagnostic purposes

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 21 of 66
Indoor equipment
3.4 Switches

Figure 7 Switch (example: Scalance X108)

Selection criteria
The selection of the switch depends on the following parameters:
• climatic conditions
• number of connection options via RJ45 sockets
The following switches are available:

Temperature range Description


0 °C to +60 °C Scalance X005, unmanaged switch,
without in-situ switch diagnostics, connection via max. five
RJ45 sockets
-20 °C to +70 °C Scalance X108, unmanaged switch,
without in-situ switch diagnostics, connection via max. eight
RJ45 sockets
Scalance X208, managed switch,
with in-situ switch diagnostics, connection via max. eight RJ45
sockets

Table 4 Switch temperature ranges

Connection of power supply, indication contact


In the lower section of the switch housing, there is a four-pin pluggable terminal block for
connection of the 24 V DC power supply (18 V to 32 V DC). Next to it, the Scalance X108
and X208 switches have a two-pin terminal block for connection of an indication contact
(relay contact for the indication of fault conditions through contact separation).

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 22 of 66
Indoor equipment
3.5 Pin assignment

3.5 Pin assignment

Connections of ACM

ACM Ethernet socket


The Ethernet socket is implemented as an RJ45 socket.

Pin Assignment
1 TD+ (Transmit Data +)
2 TD- (Transmit Data -)
3 RD+ (Receive Data +)
4 -
5 -
6 RD- (Receive Data -)
7 -
8 -

Table 5 Pin assignment of the ACM Ethernet socket

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 23 of 66
Indoor equipment
3.5 Pin assignment

ACM 200 process connector


The ACM process connector is a 96-pin male connector on the underside of the ACM.

Pin a b c
1 GFM1-A2 GFM1-A1 GFM1-A3
2 GFM2-A2 GFM2-A1 GFM2-A3
3 GE1-2 GE1-1 GE1-3
4 GT1-2 GT1-1 GT1-3
5 AZGT1-A2 (-) AZGT2-A2 (-) AZGT2-A1 (+)
6 AZGT1-A1 (+) AZGH1-A2 (-) AZGH1-A1 (+)
7 - AZGH2-A2 (-) AZGH2-A1 (+)
8 - - -
9 - - -
10 - - -
11 DS2 (+) - DS2 (-)
12 - - -
13 - - -
14 - - -
15 DS1 (+) - DS1 (-)
16 - - -
17 - - -
18 - - -
19 - AZGH2-B2 (-) AZGH2-B1 (+)
20 AZGT1-B1 (+) AZGH1-B2 (-) AZGH1-B1 (+)
21 AZGT1-B2 (-) AZGT2-B2 (-) AZGT2-B1 (+)
22 BOK-2 BOK-1 BOK-3
23 GT2-2 GT2-1 GT2-3
24 GE2-2 GE2-1 GE2-3
25 GFM2-B2 GFM2-B1 GFM2-B3
26 GFM1-B2 GFM1-B1 GFM1-B3
27 - - -
28 - - -
29 - - -
30 - - -
31 V-24SV G-24SV PE
32 V-24SV G-24SV PE

Table 6 Pin assignment of the ACM process connector

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 24 of 66
Indoor equipment
3.5 Pin assignment

Key Function
GFMx-yz Output for track vacancy detection section
x: section (1/2)
y: channel (A/B) z: contact (1 – changeover contact; 2 – NC contact; 3 –
NO contact)

GEx-z Output for reset restriction


x: section (1/2)
z: contact (1 – changeover contact; 2 – NC contact; 3 – NO contact)

GTx-z Output for reset acknowledgment


x: section (1/2)
z: contact (1 – changeover contact; 2 – NC contact; 3 – NO contact)

BOK-z Output for status relay: ACM is OK (BOK)


z: contact (1 – changeover contact; 2 – NC contact; 3 – NO contact)

AZGTx-yz Input for axle count reset operation


x: section (1/2)
y: channel (A/B)
z: polarity (1 = +; 2 = -)
AZGHx-yz Input for auxiliary axle count reset operation
x: section (1/2)
y: channel (A/B)
z: polarity (1 = +; 2 = -)
DSx (z) wheel detector interface to wheel detection equipment
x: double wheel detector (1/2)
z: polarity (+/-)

Table 7 Key, function

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 25 of 66
Indoor equipment
3.5 Pin assignment

ACM 200 system cable

Figure 8 ACM 200 system cable

wh (1) +24 V
wh (2) +24 V
wh (3) -24 V
wh (4) -24 V
gnye (5) PE
gnye (6) PE

Table 8 Core assignment of the power supply cables

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 26 of 66
Indoor equipment
3.5 Pin assignment

gy DS2 (+)
pk DS2 (-)
ye DS1 (+)
gn DS1 (-)

Table 9 Core assignment of cable 7

Contents of connection set

Figure 9 Contents of the connection set

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 27 of 66
Indoor equipment
3.5 Pin assignment

Optional components
• Jumpers for connecting the two-tier terminals in the ACM process connection termi-
nal strip (see the figure below)
• Vertical jumpers for connecting the upper and lower levels

Figure 10 FBS2-3.5 jumper for process connection terminals

• Component connectors with jumper wire for the WDE terminals (see the figure below)
• We recommend protecting the outdoor cables connected in the cable termination
rack/cabinet by means of additional overvoltage protection elements (type 4 lightning
protection module on the basic terminal block, overvoltage arrester (block varistor)).
Alternatively, lightning protection can also be implemented in the ACM cabinet. In
this case, the component connectors for the WDE terminals are replaced by a type 4
lightning protection module.

Figure 11 Component connector with jumper wire for the WDE terminals (part of
the connection set)

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 28 of 66
Indoor equipment
3.5 Pin assignment

Terminal assignment of recommended power supply module


The power supply module is connected via screw terminals (terminal assignment exam-
ple applies to a Sitop PS 307, 2 A).

Terminal Assignment
L1 Mains voltage
N Neutral
PE Protective earth conductor
L+ 24 V DC output voltage
M 24 V DC output voltage
L+ 24 V DC output voltage
M 24 V DC output voltage

Table 10 Terminal assignment of the Sitop PS 307, 2 A

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 29 of 66
Indoor equipment
3.5 Pin assignment

Switch
Further ACMs are connected to the switch via the RJ45 sockets (pin assignment example
applies to the Scalance X108 switch).

Pin Assignment
1 RD+ (Receive Data +)
2 RD- (Receive Data -)
3 TD+ (Transmit Data +)
4 -
5 -
6 TD- (Transmit Data -)
7 -
8 -

Table 11 Pin assignment of the Scalance X108 switch

The switch power supply is connected via the 4-pin pluggable terminal block.

Pin Assignment
1 L1+ (24 V DC + power supply)
2 M1 (ground connection)
3 M2 (ground connection)
4 L2+ (24 V DC + power supply)

Table 12 Pin assignment of the switch power supply

The indication contact is connected via the 2-pin pluggable terminal block (Scalance
X108, X208 only).

Pin Assignment
1 F1
2 F2

Table 13 Pin assignment of the switch indication contact

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 30 of 66
Indoor equipment
3.6 Cables of indoor equipment

3.6 Cables of indoor equipment

Properties, wiring and cable laying

SAV-B <CI1>, <CI3>, <CI4>, <CI5>, <CI6>, <CIO1>

Properties of indoor cables on process connector


This section deals with all cables whose cores are electrically connected to the process
connector of the ACM and are laid in the indoor equipment. The cable termination rack
provides electrical isolation between the indoor and outdoor equipment.
• The length of the connecting cable must not exceed 100 m.
• The cable capacitance of the connecting cable must not exceed 10 nF.
• The cable must have a rated voltage of min. 300 V.
• The cable must be able to withstand a core-to-core and core-to-shield AC test volt-
age of 1 kVrms. If cores of the outdoor equipment (e.g. from the wheel detection
equipment) are routed together with indoor cores, the cable must be able to with-
stand a core-to-core and core-to-shield AC test voltage of 1.875 kVrms. The same
applies to cores within a connector or cable duct.
• The cables must have a robust shield, e.g. of wire mesh. (Does not apply to power
supply cables.)
• Cores must not be connected in parallel. (Does not apply to power supply cables.)
• The terminals used must have a rated voltage of min. 300 V and a rated impulse
voltage of min. 2.4 kV. If outdoor and indoor cores are routed together in a cable
duct, the terminals used must have a rated voltage of min. 300 V and a rated im-
pulse voltage of min. 4.96 kV.

Properties of Ethernet cables


• Ethernet cables must at least meet the requirements of Category 5 as per
EIA/TIA 568-TSB 36.

Wiring of cores
The following signals must be assigned to one pair of cores each determined by twisting
if star-quad or paired cables are used:
• signals of a set of wheel detection equipment
• signals for controlling an optocoupler input
• signals for interrogating a relay contact

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 31 of 66
Indoor equipment
3.6 Cables of indoor equipment

Laying of power supply cables (part of ACM 200 system cable)


The power supply cables of the individual ACMs must be routed from the star point as an
Y configuration (separate cable to each ACM). The power supply cables may only be laid
indoors. The negative pole of the power supply must be earthed or, in an earth-free ar-
rangement, connected to rack potential.
The requirements relating to operator safety stipulated by national standards and regula-
tions must be complied with for laying.

Shielding
All cables to be connected to the ACM must be shielded up to the cable termination
rack/cabinet and up to the terminal strip.
If the cables are longer than 0.5 m, the shield must be terminated at one end when the
relevant cable is routed within an apparatus cabinet.
The shield must be terminated at both ends when the cable is used for connection with
other apparatus cabinets. When doing so, it must be ensured that the shield is not over-
loaded by equalizing currents. If excessive equalizing currents cannot be ruled out, addi-
tional earthing cables must be connected in parallel with the shield.

Cables leaving indoor area


If cables that are not used to connect wheel detection equipment leave the indoor area,
electrical isolation with basic insulation for a rated impact voltage VNI of 3.1 kV as per
EN 50124-1 must be implemented for these connections.
If the AZGT or AZGH inputs are used to transmit operator-specific safety-related informa-
tion (SRI) and it is necessary to have electrical isolation, the hazard resulting from the
connection must be determined and checked to ensure it is tolerable.
The electrical isolation for the digital inputs and outputs on the process connector of the
ACM can be implemented by means of relays with the appropriate dielectric properties.
For Ethernet connections, a changeover to, for example, optical fibers or modems with
the appropriate dielectric properties can be used.
The interference voltage on outdoor cables must not exceed the following limits:
• the maximum permissible interference voltage defined by the relevant railway opera-
tor
• a continuous interference voltage of 250 V AC
• a transient interference voltage of 1.5 kV AC (e.g. in the case of catenary contact
with the track or its equipment)
SAV-B <CIO1>

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 32 of 66
Outdoor equipment
4.1 Structure of outdoor equipment

4 Outdoor equipment

4.1 Structure of outdoor equipment

Information about structure of outdoor equipment

Information about the structure of the outdoor equipment can be found in the Operating
and Service Manuals of the wheel detection equipment.

Cable distribution boxes and cabinets


If cable distribution boxes or cabinets are used outdoors, they must have an IP rating of
min. IP54 as per DIN EN 60529. Cable termination racks must have an IP rating of min.
IP20 as per DIN EN 60529.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 33 of 66
Outdoor equipment
4.2 Cables of outdoor equipment

4.2 Cables of outdoor equipment

Properties, wiring and requirements

SAV-B <CO1>, <CO2>, <CO3>

Properties of wheel detection equipment cable


• Outdoor cables must be able to withstand a core-to-core and core-to-shield AC test
voltage of min. 2.5 kVrms.
• The terminals used must have a rated voltage of min. 300 V and a rated impulse
voltage of min. 4.96 kV.
• All cables must have a shield.
• The shield must be connected to earth at one end at least. If the shield of a cable is
terminated more than once, overloading of the shield by equalizing currents must be
prevented. If excessive equalizing currents cannot be ruled out, additional earthing
cables must be connected in parallel with the shield.
The connection between shield bus and the the main potential equalization bar must
not be longer than 5 m, and the cross-section of the connecting cable must be min.
2
16 mm .
• The cable must have a rated voltage of min. 300 V.
• Information lines: cores must not be connected in parallel.
External supply cables: cores may be connected in parallel.
• Information lines must be star-quad or paired.
External supply cables may be core-stranded.

Requirements for cable laying


The cables must be laid as usual, e.g. underground or in cable troughs. The requirements
relating to operator safety stipulated by national standards and regulations must be com-
plied with.

Permissible other signals in main cable


In cables in which axle counting signals of type ZP wheel detection equipment are routed
may also transmit the following signals (in another star-quad of the cable):
• 230 Vrms or 100 V DC external supply of type ZP wheel detection equipment
• ISDN signals
• axle counting signals of Clearguard WSD wheel detectors
Further signals may be routed in one and the same cable with the axle counting signals
of type ZP wheel detection equipment if their non-critical nature has been demonstrated.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 34 of 66
Outdoor equipment
4.3 Control distance restrictions

4.3 Control distance restrictions

Interference voltage, armoring, and loop resistance

SAV-B <CS1>, <CV1>

Control distance between axle counting system and wheel detection equipment
The maximum permissible control distance between the axle counting system and con-
nected type ZP wheel detection equipment is restricted by the following:
• interference voltage
• loop resistance and cable capacitance
• attenuation of the signaling cable

Interference voltage
The interference voltage must not exceed the following limits:
• the maximum permissible interference voltage defined by the relevant railway opera-
tor
• a continuous interference voltage of 250 V AC
• a transient interference voltage of 1.5 kV AC (e.g. in the case of catenary contact
with the track or its equipment)
When determining the interference voltage, account must be taken of the fact that the
wheel detector cables attached to an ACM are galvanically connected inside the ACM.
Thus, unless the two wheel detector cables are routed along the same cable trough, cal-
culation must be based on the overall length of the two cables. A broadband transformer
(BBT) galvanically subdivides the cable lengths to be considered into separate lengths to
be considered.

Figure 12 Interference situation for an axle counting system, a broadband trans-


former and two sets of wheel detection equipment

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 35 of 66
Outdoor equipment
4.3 Control distance restrictions

Loop resistance and cable capacitance


The loop resistance must be less than 412 if the wheel detection equipment is supplied
via the ACM.
The cable capacitance of a separate information line must not be more than 325 nF. The
following line sections are separate information lines:
• between the ACM and a BBT
• between two BBTs
• between a BBT and wheel detection equipment
• between the ACM and wheel detection equipment

Notes
In cable data sheets, the resistance is generally indicated at 20 °C. Copper and aluminum
cables have a 10% higher cable resistance at a cable temperature which is 25 °C higher.
The resistance is 20% higher at a 50 °C higher cable temperature.

Example
The cable system between the ACM and wheel detection equipment comprises three dif-
ferent cable types with the following properties:
• 80 m of process cable, DC resistance of 140 /km at 20 °C, cable capacitance of
75 nF/km
• 4 km of main cable, nx4x0.9 signaling cable, loop resistance of 56.6 /km at 20 °C,
cable capacitance of 45.4 nF/km
• 0.25 km of tail cable, 1x4x0.8 signaling cable, loop resistance of 73.2 /km at 20 °C,
cable capacitance of 30 nF/km
The indoor area is air-conditioned to < 45 °C; thus, a 10 % higher cable resistance is
used. The outdoor cables are laid in an overground cable trough; thus, a 20 % higher ca-
ble resistance is used.
Verification:
The loop resistance must be less than 412 :
• 0.08 km * 2 * 140 /km * 1.1 + 4 km * 56.6 /km * 1.2 + 0.25 km * 73.2 /km * 1.2
= 318.28 < 412
The cable capacitance must be less than 325 nF:
• 0.08 km * 75 nF/km + 4 km * 45.4 nF/km + 0.25 km * 30 nF/km = 195.1 nF < 325 nF
Result:
The cable system can be used provided that the maximum permissible interference volt-
age is not exceeded.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 36 of 66
Outdoor equipment
4.4 Connection of wheel detection equipment

4.4 Connection of wheel detection equipment

Signaling cable to be used and connection

SAV-B <IO6>, <CS3>, <C1>

Connection
Max. two sets of wheel detection equipment can be connected to an ACM. The wheel
detection equipment must be connected in accordance with the figure below.

Figure 13 Connection of two sets of wheel detection equipment to an ACM

Wiring
The signals of a set of wheel detection equipment must each be assigned to one pair of
cores determined by twisting.

External supply
External supply means that the wheel detection equipment is powered via two additional
cores. When using the external supply option, the fuses for the relevant wheel detection
equipment must be removed in the axle counting system.

Double usage
Double usage means that a set of wheel detection equipment is used by two different
ACMs, i.e. is operated as double-usage wheel detection equipment. When using the
double-usage option, one ACM must be connected as usual to the wheel detection
equipment, i.e. with fuse. The other ACM is connected via the double-usage output or
the double-usage board (depending on the type of wheel detection equipment) without
fuse.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 37 of 66
Earthing and protective measures
5.1 Earthing and protective measures: concepts

5 Earthing and protective measures

5.1 Earthing and protective measures: concepts

Agreement on earthing and protective measures with rail operator

The earthing and protective measures concept for indoor and outdoor equipment must be
agreed on with the relevant rail operator (overall earthing system). Special measures in
accordance with customer specifications must be considered individually and dealt with in
a separate document on a project-specific basis.

Concepts for earthing and protective measures

The following concepts deal with earthing and protective measures for different operating
modes (outdoor equipment):
• Earthing Concept (AC Variant)
Earthing and Protective Measures in Outdoor Equipment of AC-electrified Railways
for Siemens Interlockings [EC-AC]
• Earthing Concept (DC SE Variant)
Earthing and Protective Measures in the Outdoor Equipment of DC-electrified Rail-
ways with Structural Earthing (SE) for Siemens Interlockings [EC-DCSE]
• Earthing Concept (DC RS Variant)
Earthing and Protective Measures in the Outdoor Equipment of DC-electrified Rail-
ways (DC) with Earthing to the Return System (RS) for Siemens Interlockings [EC-
DCRS]
• Earthing Concept (AC/DC Variant)
Earthing and Protective Measures in the Outdoor Equipment of AC/DC Mixed Op-
eration (AC and DC Traction on the Same Track) for Siemens Interlockings [EC-
ACDC]
• Earthing Concept (NER Variant)
Earthing and Protective Measures in the Outdoor Equipment of Non-electrified Rail-
ways for Siemens Interlockings [EC-NER]
This concept deals with earthing and protective measures for indoor equipment:
• Earthing Concept
Earthing and Protective Measures for Indoor Equipment of Siemens Interlockings
[EC]

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 38 of 66
Earthing and protective measures
5.2 Operator safety

5.2 Operator safety

Earthed or earth-free installation

The axle counting system must be installed in cabinets or buildings which can only be
accessed by authorized staff (SAV-B <OP4>). The ACM can be used in an earthed or
earth-free arrangement.
The operating ground (GND, pins B31 and B32) provided via the process connector and
the protective earth conductor contacts (PE, pins C31 and C32) are connected within the
axle counting system both to each other and to the housing.
The potentials connected to the outdoor equipment (wheel detector interface) are earth-
free. The switching voltages of the optocoupler inputs and relay outputs can be either
earthed or earth-free.

Earthed installation – all conductive parts are earthed


For earthed installation of the axle counting system, all the conductive parts must be
earthed via reliable connections. The conductive parts include, for example, the ACM, the
122 mm mounting rail, the shield bus and the TS 35 mounting rail. The ACM housing is
earthed via the process connector (pins C31 and C32).

Earth-free installation – requires additional measures


For earth-free installation of the axle counting system, a non-conductive environment
must be created and protective measures for electrical equipment in a non-conductive
environment as per DIN VDE 0100-410, IEC 60364-4-41 or a comparable standard must
be taken:
• Floors and walls must be insulating.
• No protective earth conductor must be present in the non-conductive environment.
• Minimum distances must be observed between persons and external conductive
parts.
• Effective obstacles must be provided between persons and external conductive parts.
• The implemented conditions must be permanent and must not be capable of being
made ineffective.
For earth-free installation of the ACM, pins C31 and C32 of the process connector must
be connected to rack potential. No earth potential must be connected to the housing of
the ACM.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 39 of 66
Earthing and protective measures
5.3 Earthing and protective measures for DB AG's alternating current traction systems

5.3 Earthing and protective measures for DB AG's


alternating current traction systems

Design examples of earthing and shielding concept

The figures below show examples of possible designs for the connection of cable shields
to railway earth. An exception is the connection in the trackside connection box (TCB). In
the TCB, the shield and armoring are isolated because the tail cable to the TCB is shorter
than 250 m.
The tail cables to the wheel detection equipment must not be longer than 250 m. If a tail
cable is longer than 250 m, the cable shield must be terminated at both ends, i.e. it must
also be connected to the earth terminal in the TCB.
The following applies to DB AG (see Earthing Concept [EC-AC]): Anti-rodent protec-
tion armoring has no guaranteed electrical properties and must thus not be electrically
connected at the ends and in cable joints. The ends must be insulated thoroughly.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 40 of 66
Earthing and protective measures
5.3 Earthing and protective measures for DB AG's alternating current traction systems

Note: observe the conditions for induction protection earthing (see Earthing Concept [EC-
AC] and DS 997.0204).
Figure 14 Earthing and shielding concept for use of the axle counting system in
electronic interlockings or type WSSB relay interlockings (German
State Railway type)

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 41 of 66
Earthing and protective measures
5.3 Earthing and protective measures for DB AG's alternating current traction systems

The example below shows the additional use of an insulating joint at the point of entry
into the interlocking. The shields of the indoor equipment are connected to the local
earth-free potential equalization facility of the interlocking.

Note: observe the conditions for induction protection earthing (see Earthing Concept [EC-
AC] and DS 997.0204).
Figure 15 Earthing and shielding concept for use of the axle counting system in
type Siemens relay interlockings (German Federal Railway type)

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 42 of 66
Earthing and protective measures
5.4 Earthing and protective measures for DB AG's direct current traction systems

5.4 Earthing and protective measures for DB AG's


direct current traction systems

Earthing and shielding concept

In DC traction systems, all shields are terminated at one end in the cable termination
rack/cabinet of the indoor equipment. The shield and armoring are isolated in the track-
side connection box (TCB). This may reduce availability. For reasons of stray-current pro-
tection, equipment connected to the track must be installed isolated from earth/structure.
The tail cables to the wheel detection equipment must not be longer than 250 m. If a tail
cable is longer than 250 m, no cable shield and no armoring must be connected to the
earth terminal in the TCB in the case of DC traction systems.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 43 of 66
Earthing and protective measures
5.4 Earthing and protective measures for DB AG's direct current traction systems

Note: protective measures in accordance with Earthing Concepts [EC-DCSE], [EC-DCRS]


and [EC-ACDC].
Figure 16 Earthing and shielding concept for use of the axle counting system in
electronic interlockings or type WSSB relay interlockings (German
State Railway type) for DC traction systems

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 44 of 66
Interface to higher-level system
6.1 Relay outputs

6 Interface to higher-level system

6.1 Relay outputs

Mode of operation and connection examples of relay outputs

SAV-B <INT1>, <INT2>, <IO1>

Fail-safe and non-fail-safe relay outputs


Two dual-channel relay outputs are available at the process connector of the ACM:
• TVDS 1 A and TVDS 1 B
• TVDS 2 A and TVDS 2 B
All other relay outputs are single-channel.

Mode of operation of fail-safe relay outputs (dual-channel)


The ACM can output two safety-related items of information via floating relay contacts
implemented as changeover contacts. Thanks to the use of positively driven contacts, the
ACM is able to check the switching capability of the normally open contacts. The ACM
does not support the detection of intercore contacts.
If a normally open contact remains closed due to a failure, a safety shutdown of the ACM
is performed. The safety shutdown rules out a hazard due to a second failure within the
ACM. The safety shutdown has no influence on the invalid relay output which continues
to exist.
The hazard rate resulting from multiple failures strongly depends on the connection of the
relay outputs and the response of the higher-level system to invalid relay outputs and
must be established as part of a safety assessment of the interface between the axle
counting system and the higher-level system. Any necessary information on the ACM for
a safety assessment can be found in the “Safety-related Application Conditions for Op-
erators”.

Application conditions for fail-safe relay outputs


In the case of an equivalent connection, normally open contacts shall be used.
The higher-level system only shall interpret the equivalent and non-equivalent safety-
related relay outputs as valid information if the relay contacts of both channels indicate
the same logical state.

Contact bounce for relay output


When states switch over, the contacts of the relevant relay may bounce for up to 100 ms;
this behavior may result in invalid states. The higher-level system must be able to handle
this behavior (e.g. though multiple evaluation).

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 45 of 66
Interface to higher-level system
6.1 Relay outputs

RR and RA outputs
The RR is output in accordance with the reset restriction of the configured primary reset
procedure. The reset acknowledgment is output by both configured reset procedures.

Connection examples
The figures below show connection examples of relay outputs.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 46 of 66
Interface to higher-level system
6.1 Relay outputs

Figure 17 Connection example of relay output with gravity control relays and
free-wheeling diodes (zero-current)

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 47 of 66
Interface to higher-level system
6.1 Relay outputs

Figure 18 Connection example of relay output (non-equivalent) with free-


wheeling diodes (zero-current)

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 48 of 66
Interface to higher-level system
6.1 Relay outputs

Figure 19 Connection example of relay output (equivalent) with free-wheeling di-


odes (zero-current)

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 49 of 66
Interface to higher-level system
6.2 AZGT/AZGH inputs on process connector

6.2 AZGT/AZGH inputs on process connector

Inputs

SAV-B <IO2>, <IO3>


The axle count reset information (AZGT), auxiliary axle count reset information (AZGH) or
secondary axle count reset information (via AZGH inputs) and operator-specific safety-
related information (SRI) must be applied in dual-channel mode to the AZGT or AZGH
inputs on the process connector of the ACM.

Maximum current/voltage
The optocoupler inputs may be directly operated at a voltage of 21.6 V DC to 72 V DC. In
the passive state, the current through the optocoupler inputs may be max. 200 µA. The
control of the inputs must be able to drive min. 3.5 mA per input. The inputs are polarized.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 50 of 66
Interface to higher-level system
6.2 AZGT/AZGH inputs on process connector

Monitoring and response to button inputs


The response to button inputs, both for an axle count reset and safety-related information,
is slightly delayed. The figure below shows the relationships for the default configuration
value for RA pulse expansion (P_TVDS#_RATi = 3 s), where
• tf = front offset of dual-channel button input
• tc = common time of dual-channel button input
• tr = rear offset of dual-channel button input

Figure 20 Monitoring and response to button inputs

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 51 of 66
Interface to higher-level system
6.2 AZGT/AZGH inputs on process connector

Connection example
The figure below shows a connection example of safety-related optocoupler inputs.

Figure 21 Connection example of optocoupler inputs

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 52 of 66
Interface to higher-level system
6.3 Ethernet interface

6.3 Ethernet interface

Data transmission via public telephone networks

SAV-B <IO4>

Measures against unauthorized access


If data is to be transmitted via public networks (transmission system in accordance with
EN 50159, Category 3, e.g. telephone networks, internet), additional measures against
unauthorized access are required. These measures are described in EN 50159 (Category
3).
Note: the ACM uses a non-linear safety code for its fail-safe communication connections.

6.4 Response times

Track occupied indication delay

SAV-B <INT3>, <INT4>, <INT5>, <INT6>

Local wheel detection equipment and track vacancy detection sections


When using locally connected wheel detection equipment, the axle counting system indi-
cates a train at its relay output within 150 ms if the train travels at max. 80 km/h. If the
train travels at a speed of more than 80 km/h, it is indicated at the relay output within
1.15 s.

Wheel detection equipment or track vacancy detection sections connected via Ethernet
If the wheel detection information or the state of a track vacancy detection section is re-
ceived via Ethernet, the track occupied indication delay may be increased by the config-
ured connection failure detection time in the event of faulty data transmission.
Note 1: in the event of fault-free communication, the delay through Ethernet communica-
tion is typically 200 ms as long as the transmit rate is set to 50 ms. Due to a disruption in
communications, the default connection failure detection time of 700 ms can result in a
track occupied indication delay of 1.85 s in the case of trains traveling at a speed of more
than 80 km/h.
Note 2: if both wheel detection information and the state of the track vacancy detection
section are transmitted via Ethernet, both configured connection failure detection times
must be taken into account. The relevant default setting is 700 ms, resulting in a track
clear indication delay of 2.55 s.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 53 of 66
Interface to higher-level system
6.4 Response times

Detailed analysis of track occupied indication delay


If the time of 1.15 s until occupied indication at the relay outputs is too long, a detailed
analysis can be performed. This analysis must be performed for all trains traveling in the
track vacancy detection section concerned.
The track clear indication delay depends on the diameter of the first wheel, the axle spac-
ing between the first and second wheels and the train speed. The figures below show the
delays for different diameters of the first wheel. The next-smaller wheel diameter must be
used for wheel diameters which are not indicated.

Figure 22 Key

Figure 23 Track clear indication delay (Ø first wheel = 330 mm)

Figure 24 Track clear indication delay (Ø first wheel = 600 mm)

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 54 of 66
Interface to higher-level system
6.4 Response times

Figure 25 Track clear indication delay (Ø first wheel = 830 mm)

Note: the possible delays for any SLC connections via Ethernet used for the relevant
track vacancy detection section must be taken into account in addition to the delays de-
rived from the diagrams.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 55 of 66
Installation, acceptance and commissioning

7 Installation, acceptance and commissioning

Installation, acceptance and commissioning

WARNING
Dangerous operating conditions and risk of accidents due to improper work!
Improper work may cause serious personal injury.
Observe all regulations and work rules to avoid any risk of injury or damage.

DANGER
Danger due to interference voltage!
All boards, components and cables may be subject to interference voltage.
In order to avoid accidental contact with parts subject to interference voltage (also in
the switched-off state), the protective provisions for work on live parts must be ob-
served.

CAUTION
Hot components! Danger of burning!
Especially in non-air-conditioned rooms or apparatus cabinets, the ACM can become
very hot.
Use gloves when replacing the ACM.

NOTICE
Electrostatic sensitive components!
Touching circuit boards causes your body to discharge its static charge. This may de-
stroy electronic components.
Do not touch any board connections or plug connectors.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 56 of 66
Installation, acceptance and commissioning

Insulation measurement

SAV-B <OP7>
When commissioning the system for the first time, an insulation measurement in accor-
dance with IEC 60364-6:2006 must be performed on the signaling cable between the
evaluation computer and core/earth of the type ZP wheel detection equipment.
Note: the following is defined in accordance with IEC 60364-6:2006, Section 62.2.1, Note
1: the maximum interval between periodic verifications may be laid down by legal or other
national regulations.
Insulation measurement must also be performed during normal operation. Automatic
earth leakage detectors can be used for this purpose to monitor adherence to the re-
quired leakage/insulation resistance. If monitoring by means of automatic earth leakage
detectors is not possible, core-to-earth insulation measurements can also be performed
manually. A test cycle of 24 months is recommended.

Checks upon acceptance and commissioning

Rules CAL1, CHK1, CHK2, CHK3, PV4, ZP41 and ZP14 from the Safety-related Applica-
tions Conditions for Operators (SAV-B) must be observed during acceptance and com-
missioning.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 57 of 66
Parts list

8 Parts list

Parts list

No. Designation Order number Comment

1 ACM 200 A2V00002047556 Board width: 63 mm


2 ID plug for ACM 200 A2V00002222533 Configuring connector
3 122 mm mounting rail A2V00002172330 Simatic S7-300
Length: 530 mm
4 35 mm mounting rail A2V00000518566 TH35 as per EN 60715
Latching of terminal strip (480 mm
long)
5 Power supply terminal strip:
Two-tier terminal A2V00000315073
PE terminal A2V00001073875
Cross-connect jumper A2V00000314980
End cover plate A2V00000315074
6 Power supply modules for temperature range of 0 °C to +60 °C
Sitop PS 307, 2 A; A2V00002024693 Board width: 40 mm
Vi = 120/230 V AC
Sitop PS 307, 5 A; A2V00002024749 Board width: 60 mm
Vi = 120/230 V AC
Sitop PS 307, 10 A; A2V00002024752 Board width: 80 mm
Vi = 120/230 V AC

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 58 of 66
Parts list

No. Designation Order number Comment


Power supply modules for temperature range of -25 °C to +60 °C
Siplus PS 305, 2 A; A2V00002025184 Board width: 80 mm
Vi = 120/230 V AC
Siplus PS 305, 5 A; A2V00002025331 Board width: 80 mm
Vi = 120/230 V AC
Siplus PS 305, 2 A; Vi = 24 V to A2V00002025087 Board width: 80 mm
110 V DC
Power supply modules for temperature range of -40 °C to +60 °C
Sicas Sitop PS 305, 5 A; A2V00082037669 Board width: 80 mm
Vi = 120/230 V AC
7 Switch for temperature range of 0 °C to +65 °C
Scalance X005 A2V00002024180 Board width: 40 mm
Switches for temperature range of -20 °C to +70 °C
Scalance X108 A2V00001959376 Board width: 60 mm
Scalance X208 A2V00002025181 Board width: 60 mm
8 Ethernet connecting cable comprising:
Ethernet cable IE FC TP, flexible A2V00001961338 State the required cable length.
cable GP 2 × 2 (type A)
Ethernet connector, IE FC RJ45 A2V00001961130 For connection to ACM, switch
9 ACM 200 system cable
System cable V25132-M1416-A1 Cut lengths:
• Cable 1: 380 mm
• Cable 2: 370 mm
• Cables 3 – 5: 340 mm
• Cable 6: 310 mm
• Cable 7: 1910 mm
• PS cores: 620 mm
System cable V25132-M1416-A2 Cut lengths:
• Cables 1 – 6: as for -A1
• Cable 7: 1600 mm
• PS cores: 620 mm
System cable V25132-M1416-A3 Cut lengths:
• Cables 1 – 6: as for -A1
• Cable 7: 1300 mm
• PS cores: 620 mm
System cable V25132-M1416-A4 Cut lengths:
• Cable 1: 1280 mm
• Cable 2: 1270 mm
• Cables 3 – 5: 1240 mm
• Cable 6: 1210 mm
• Cable 7: 2500 mm
• PS cores: 620 mm

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 59 of 66
Parts list

No. Designation Order number Comment


System cable V25132-M1416-A5 Cut lengths:
• Cable 1: 1480 mm
• Cable 2: 1470 mm
• Cables 3 – 5: 1440 mm
• Cable 6: 1410 mm
• Cable 7: 2500 mm
• PS cores: 620 mm
System cable V25132-M1416-A6 Cut lengths:
• Cable 1: 2180 mm
• Cable 2: 2170 mm
• Cables 3 – 5: 2140 mm
• Cable 6: 2110 mm
• Cable 7: 3000 mm
• PS cores: 620 mm
System cable V25132-M1416-A7 Cut lengths:
• Cable 1: 2380 mm
• Cable 2: 2370 mm
• Cables 3 – 5: 2340 mm
• Cable 6: 2310 mm
• Cable 7: 3000 mm
• PS cores: 620 mm
System cable V25132-M1416-A8 Cut lengths:
• Cables 1 – 7: as for -A7
• PS cores: 2500 mm
System cable V25132-M1416-A9 Cut lengths:
• Cable 1: 2580 mm
• Cable 2: 2570 mm
• Cables 3 – 5: 2540 mm
• Cable 6: 2510 mm
• Cable 7: 3500 mm
• PS cores: 3000 mm
10 Connection set, complete A2V00002232010
Individual parts of connection set:
End clamp A2V00000314945
Designation plate holder for end A2V00001100137
clamps
Designation plate for end clamps A2V00082027601
2
Two-tier terminal, 1.5 mm A2V00002219503 ACM process connection
D-PTTB end cover plate A2V00002219504
UCT-TMF 3.5 marker, blank A2V00002219505
Coding star A2V00002219695
PP-H connector, 5-pin A2V00002219687

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 60 of 66
Parts list

No. Designation Order number Comment


PP-H connector, 8-pin A2V00002219688
PRZ strain relief and latching de- A2V00002219689
vice
Basic terminal A2V00000315155 Wheel detection equipment con-
nection
PE terminal A2V00001063620
280-317 end cover plate A2V00000315163
Component connector with A2V00001069462
jumper wire
11 Overvoltage protection set comprising:
Type 4 lightning protection mod- A2V00000519340 One per set of wheel detection
ule equipment
Overvoltage arrester (block varis- A2V00000399792 One per cabinet
tor)
12 Jumpers
FBS, 2-pin A2V00002219691 For connecting 2, 3, 4, 5 or 10
adjacent terminals (upper or lower
level)
FBS, 3-pin A2V00002219692
FBS, 4-pin A2V00002219693
FBS, 5-pin A2V00002219694
FBS, 10-pin A2V00002226122
FBS, 1.5/S-PV (vertical jumper) A2V00002226307 For connecting the upper and
lower levels

Table 14 Parts list

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 61 of 66
Technical data

9 Technical data

Technical data

SAV-B <IO1>, <IO3>, <EC1>, <EC2>, <CS1>, <HR1>

Physical data of ACM • High-grade steel housing, IP20


• Installation by latching onto 122 mm mounting rail
• Weight: 1675 g
• H × W × D: 151 × 63 × 222 mm
Counting capacity 32,767 axles per track vacancy detection section
Permanently 20 axles per second and set of wheel detection
equipment
Number of max. connectable 2 sets of type ZP wheel detection equipment (ZP 43 E, ZP 43 V,
sets of wheel detection equip- ZP D 43)
ment per ACM
Max. number of track vacancy 2 track vacancy detection sections
detection sections per ACM
Max. number of sets of wheel Total of 10 sets of wheel detection equipment:
detection equipment per ACM • 2 sets of wheel detection equipment directly to ACM
• 8 sets of wheel detection equipment to four adjacent ACMs
(transmission of information via Ethernet using SLC)
Output information (via floating 2 dual-channel outputs for clear/occupied indication or operator-
relay contacts) specific safety-related information (SRI) or "pulse detected" indi-
cation of wheel detection equipment with non-equivalent or
equivalent connection
Reset restriction (RR), single-channel output
Reset acknowledgment (RA), single-channel output
ACM is not faulty (BOK), single-channel output
Outputs: Relay contacts for DC:
switching currents, relays • switching voltage: 10 V to 72 V DC
• switching current: 2 mA to 250 mA
• switching power: max. 15 W
Relay contacts for AC:
• switching voltage: 10 V to 150 V AC
• switching current: 2 mA to 1 A
• switching power: max. 15 W
Inputs: 4 dual-channel optocoupler inputs:
voltages, switching currents, signal voltage of 21.6 V to 72 V DC
optocouplers Input voltage range:
Active: 3.5 mA to 8 mA
Passive: < 200 µA
System start-up < 30 s (fully operational)

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 62 of 66
Technical data

Modular system Modules installed by latching onto mounting rail: mounting of


mounting rail possible in racks and cabinets
Power consumption (ACM) Typically 10 W + 4 W per set of wheel detection equipment
Max. 12 W + 5 W per set of wheel detection equipment
Supply voltage (ACM) In normal operation:
• 21.6 V to 31.2 V DC
• residual ripple max. 100 mVrms
In the event of a fault:
• max. 60 V DC permanently
• max. 120 V DC for max. 200 ms
Maximum cable length in indoor 100 m
equipment
Ambient temperature range -40 °C to +70 °C
(ACM) Category 3K7 as per DIN EN 60721-3-3
Installation site of ACM Next to track – outside ballast with spacing of > 1 m from track
Altitude: max. 2000 m
Ambient temperature range (PS Depending on recommended model up to -40 °C to +60 °C
for ACM) (+70 °C with reduced power)
Ambient temperature range Depending on recommended model -20 °C to +70 °C
(switch)
Ambient temperature range -40 °C to +85 °C
(wheel detection equipment) Temperature, humidity, air pressure 4K4 as per EN 60721-3-4
but with temperature range of -40 °C to +85 °C and max. altitude
above mean sea level of 3000 m
Transportation (ACM) -40 °C to +55 °C as per IEC 60068
(2K2, 2M2, 2B2, 2S2 and 2C2 as per DIN EN 60721-3-2)
Storage (ACM) +5 °C to +40 °C
(1K2, 1M3, 1B2, 1S2 and 1C2 as per DIN EN 60721-3-1)
Wheel detection equipment (in- Connection via audio-frequency interface (two cores)
terface to ACM)
Maximum control distance Examples of cable at 45 °C Standard With additional
measures
A-2Y (St)YbY3x4x0.9S (1B 7.1 km 14 km
0.3)
A-2Y (St)YbY5x4x1.4S (1B 6.5 km 21 km
0.3)

The maximum signaling cable length must be calculated on a


system-specific basis. The following values must not be ex-
ceeded:
continuous interference voltage Vint = 250 Vrms 16 ⅔ to 50 Hz
transient interference voltage Vcatenary contact = 1500 Vrms (0.1 s)
The attenuation per unit length of the cable must not exceed
20.1 dB at the operating frequencies of 3.5 kHz and 6.5 kHz.
Max. 23.57 dB are permissible with external supply.
Type of connecting cable Star-quad or paired signaling cable

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 63 of 66
Technical data

Max. permissible total capaci- 325 nF for electrically continuous cable


tance of WDE cable
Max. permissible total loop re- 412
sistance of WDE cable with di-
rect supply
Attachment of DEK wheel de- Rail web
tector
Required traversal cycle • ZP 43 E/ZP 43 V: every 30 days; once a year with reduced
safety
• ZP D 43: once a year
Hazard rate SIL 4 as per EN 50129 with respect to the hazards listed below
The following hazard is controlled with a hazard rate of < 6.1 E-
-1
10 h :
The indication that there is no train in a section (“clear”) although
there is at least part of a train in the section, or the status transi-
tion indications “clear” – “occupied” – “clear” (corresponds to a
passing train) although the relevant track vacancy detection sec-
tion has not been traversed.
The stated hazard rate applies to the ZP D 43 when it is used
with a traversal cycle of once a year, and to the ZP 43 E/V when
it is used with a traversal cycle of 30 days.
Note: if the ZP 43 E/V is used with a traversal cycle of once a
year, the hazard rate is 2.1 E-9 /h per track vacancy detection
section.
The following hazard is controlled with a hazard rate of < 2 E-
-1
10 h per TVDS output relay:
The untimely dual-channel energization of the TVDS output relay
(contact not in the release state) for the output of binary safety-
related information (SRI).
Note: when quantifying this hazard, it has been assumed on a
plausibility basis that the binary information to be transmitted
changes its state at least twice a year.

Table 15 Technical data

Reliability and maintainability


Unit to be re- MTBF at 25 °C MTBF at 40 °C Mean time to repair
paired
ACM 200 31 years 24 years 0.5 h
ID plug for 4230 years 2640 years 0.5 h if programmed spare
ACM 200 parts are available
ZP 43 E/ZP 43 V - 180 years 0.5 h
ZP D 43 - 133 years 0.5 h

Table 16 Mean time between failures and mean time to repair for different units

The indicated mean time to repair begins when the maintenance engineer arrives with the
spare parts at the site of repair and ends after successful start-up of the unit concerned
with confirmation of proper operation of the axle counting system.

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 64 of 66
Indices

10 Indices

List of abbreviations

Abbreviation Meaning
ACM axle counter module
AZG (Achszählgrundstellung) axle count reset operation
AZGH (Achszählgrundstellungshilfsbedienung) auxiliary axle count reset op-
eration
AZGT (Achszählgrundstellungsbedienung) axle count reset operation
BBT broadband transformer
COM communication
DEK (doppelter elektronischer Kontakt) double electronic contact
GND ground
IP ingress protection
LED light-emitting diode
MTBF mean time between failures
NER non-electrified railway
PE protective earth
PS power supply
RA reset acknowledgment
RR reset restriction
SAV-B safety-related application rules for operators
SE structural earthing (grounding)
SIL safety integrity level
Simatic Siemens automation system
SLC safety layer cyclic
SRI safety-relevant information
TCB trackside connection box
TVDS track vacancy detection section
VAZG (vorbereitende Achszählgrundstellung) preparatory axle count reset
operation
WSD wheel sensor double
ZP 43 E electronic wheel detection equipment, 43 kHz with aluminum housing
ZP 43 V electronic wheel detection equipment, 43 kHz with plastic housing
ZP D 43 electronic wheel detection equipment, 43 kHz, digital signal process-
ing, analog interface

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 65 of 66
Indices

List of figures

Figure 1 Schematic representation of an axle counting system ....................................................... 9


Figure 2 Design example of the indoor equipment ......................................................................... 11
Figure 3 Clearances for the ACM installation space ....................................................................... 13
Figure 4 Type ZP wheel detection equipment on the track............................................................. 14
Figure 5 ACM dimensions ............................................................................................................... 16
Figure 6 Front panel of the ACM ..................................................................................................... 17
Figure 7 Switch (example: Scalance X108) .................................................................................... 22
Figure 8 ACM 200 system cable ..................................................................................................... 26
Figure 9 Contents of the connection set ......................................................................................... 27
Figure 10 FBS2-3.5 jumper for process connection terminals .......................................................... 28
Figure 11 Component connector with jumper wire for the WDE terminals (part of the connection set)28
Figure 12 Interference situation for an axle counting system, a broadband transformer and two sets
of wheel detection equipment ........................................................................................... 35
Figure 13 Connection of two sets of wheel detection equipment to an ACM ................................... 37
Figure 14 Earthing and shielding concept for use of the axle counting system in electronic
interlockings or type WSSB relay interlockings (German State Railway type) ................. 41
Figure 15 Earthing and shielding concept for use of the axle counting system in type Siemens relay
interlockings (German Federal Railway type) ................................................................... 42
Figure 16 Earthing and shielding concept for use of the axle counting system in electronic
interlockings or type WSSB relay interlockings (German State Railway type) for DC
traction systems ................................................................................................................ 44
Figure 17 Connection example of relay output with gravity control relays and free-wheeling diodes
(zero-current) .................................................................................................................... 47
Figure 18 Connection example of relay output (non-equivalent) with free-wheeling diodes (zero-
current) .............................................................................................................................. 48
Figure 19 Connection example of relay output (equivalent) with free-wheeling diodes (zero-current)49
Figure 20 Monitoring and response to button inputs......................................................................... 51
Figure 21 Connection example of optocoupler inputs....................................................................... 52
Figure 22 Key .................................................................................................................................... 54
Figure 23 Track clear indication delay (Ø first wheel = 330 mm)...................................................... 54
Figure 24 Track clear indication delay (Ø first wheel = 600 mm)...................................................... 54
Figure 25 Track clear indication delay (Ø first wheel = 830 mm)...................................................... 55

List of tables

Table 1 Supplementary documents ................................................................................................. 6


Table 2 Standards and guidelines ................................................................................................... 8
Table 3 Temperature ranges and input voltages ........................................................................... 21
Table 4 Switch temperature ranges ............................................................................................... 22
Table 5 Pin assignment of the ACM Ethernet socket .................................................................... 23
Table 6 Pin assignment of the ACM process connector ................................................................ 24
Table 7 Key, function ..................................................................................................................... 25
Table 8 Core assignment of the power supply cables ................................................................... 26
Table 9 Core assignment of cable 7 .............................................................................................. 27
Table 10 Terminal assignment of the Sitop PS 307, 2 A ................................................................. 29
Table 11 Pin assignment of the Scalance X108 switch ................................................................... 30
Table 12 Pin assignment of the switch power supply ...................................................................... 30
Table 13 Pin assignment of the switch indication contact ............................................................... 30
Table 14 Parts list ............................................................................................................................ 61
Table 15 Technical data................................................................................................................... 64
Table 16 Mean time between failures and mean time to repair for different units........................... 64

A6Z00034296050/- Standard Design Document


2013-07-08 Clearguard ACM 200 Axle Counting System
© Siemens AG, 2013 All rights reserved Page 66 of 66

Das könnte Ihnen auch gefallen