Beruflich Dokumente
Kultur Dokumente
25-Oct-18
SUPPLY & INSTALLATION
NO DESCRIPTION UNITS QTY
Rate INR Amount INR
NOTES
All wiring to be done in FRLS PVC MMS conduits , recessed or surface as
**
required at site. Conduits in floor shall be HMS
** All wires and cables are with copper conductor only
Modular Switch assesories shall be LEGRAND ARTEOR SQUARE
**
WHITE MECHANISM
** Contractor to approve all GA dwgs before fabrication
** Contractor to provide all shop dwgs prior to installation
Contractor to provide all as built dwgs [ 3 soft copy (cd or pen drive) & 5
**
sets of hard copies ] after completion
Contractor to execute in coordination with all vendors , consultants &
**
Architect
Any items not covered & required to be executed shall be done with prior
**
approval of PMC and shall be paid as per prevaling market rates
Vendor to maintain clean site with debris management , failing to do so
** the client shall do the same and deduct from the vendor along with
penalty.
** Contractor to certify the site by the local electrical inspector
** All '0' items to be compulsorily quoted
** Rates shall be billed as per actuals installed at site
All items are supply , install , test and commission at site unless otherwise
** mentioned and shall include all material , labour, transport , loading ,
unloading, relocations, transit and its insurance , site insurance stc.
A PANELS / MCB DB'S / SWITCHGEARS
S.I.T.C. [supply , installation, testing & commissioning ]of
14/16(2mm/1.62mm) swg CRCA fabricated & powder coated after 7 tank
process ,compartmentalised panel with air ventilation & dust/vermin proof
, free standing, floor mounted on100 mm rigid 'C' MS base supported on
concrete base with anchor fastners. Panels to be top / bottom entry &
accessible from front & rear side or as required by consultant & site
conditions. GA to be made by contractor & approved by consultant Prior
to fabrication with respect to SLD & specks. Busbar to be of electrolytic
Alu with current density of 1.0 amp per sqmm or as mentioned for copper
Panel shall confirm to all applicable IS standards. All MCCB shall be with
microprocessor based release & RHOM . Below 25 KA thermal magnetic
can be used. APFC panels to have D curve mcb All internal wiring to be
done in pvc insulated copper wires Out going from MCCB to be
terminated in bus bars/ panel connecteors in cable alley. All terminations
to have BI-Metallic strip as required . All MCCB to have spreader links
MCB DB. ALL DB's to be IP43. SITC of DB'S ready made or fabricated
as per design & site conditions or consultants requirements. TPN DB
shall have 3 nos separate neutral links / flexy DB / with internal wiring
done as required with copper wire & cable sockets Internal terminations &
wiring to be neatly dressed up in a systematic manner. All MCB to be 'C'
& 'D' curve as mentioned & indicators to be LED All MCB & DB to be
approved by consultant before procurement . DB to be fixed surface or
recessed as per requirements
All panels to have gas suppresion system with gas cylinder , piping, panel
internal piping complete in all respects as mentioned.below.This shall be
not considered as a seprate item and shall be included in the cost of all
panels. As per specifications below.
2000 A , Tp ,50 ka ,ACB with E/F, U/V, O/C, S/C , O/V, EDO,
microprocessor based releases ,data communication [ L & T - C power or
equivalent ] --- 2nos
LED ON OFF TRIP indicators with mcb protection -- 2 set
LED L1-L2-L3 indicators with mcb protection -- 2 set
Multifunction CT Meter -- 2 set
CT 2000/5, CL 1,15VA -- 2 sets [1 set for 3 Phases]
CT 2000/5, CL 1,15VA -- for apfc control
Transient voltage surge suppressor , cat c , continuous operating, 3phase
4 wire , metal oxide varistor technology , parallel connected , less than 0.5
nano second response time , surge current capacity 100 ka , 6000v ,
1 3000a, UL listing & labelled 14492 supressed voltage range of 800v peak. Nos 1 2,875,000 2,875,000
ASCO make 330SERIES or equivalent -- 1 set with Mcb Protection
ASCO make 300 series or equivalent 2000 A, 4p, ATS -- 1 Nos
4P Cu bus bar with HSS --- 1 set
microprocessor based releases mccb
800 A 4P 36 KA MCCB - 2 Nos
500 A 4P 36 KA MCCB - 2 Nos
315 A 4P 36 KA MCCB - 1 Nos
thermal magnetic releases mccb
250 A 4P 25 KA MCCB - 8 Nos
160 A 4P 16 KA MCCB - 6 Nos
125 A 4P 16 KA MCCB - 2 Nos
C 40-63A 4P 10 KA MCB -- 5 nos
2000 A , Tp ,50 ka ,ACB with E/F, U/V, O/C, S/C , O/V, EDO,
microprocessor based releases ,data communication [ L & T - C power or
equivalent ] --- 2nos
LED ON OFF TRIP indicators with mcb protection -- 6 set
LED L1-L2-L3 indicators with mcb protection -- 2 set
Multifunction CT Meter -- 2 set
CT 2000/5, CL 1,15VA -- 2 sets [1 set for 3 Phases]
CT 2000/5, CL 1,15VA -- for apfc control
16 A/M switch , phase indication lamps with mcb tp for protection 4p Nos 1 720,000 720,000
aluminium bus bar with colour coded HSS as per capacity 30 sec delay
timing for manual operation ,power contactors ,auxiliary contactors ,
illuminated start stop push buttons with elements , TP MCB for power
contactors , phase indication lamps , Digital amp meter , with CT , digital
voltmeter with selector switch , on / off indication lamps for capacitors All
contactors to be capacitor duty.Detuned reactor filters to be used.
17 A/M switch , phase indication lamps with mcb tp for protection 4p Nos 1 675,000 675,000
aluminium bus bar with colour coded HSS as per capacity 30 sec delay
timing for manual operation ,power contactors ,auxiliary contactors ,
illuminated start stop push buttons with elements , TP MCB for power
contactors , phase indication lamps , Digital amp meter , with CT , digital
voltmeter with selector switch , on / off indication lamps for capacitors All
contactors to be capacitor duty.Detuned reactor filters to be used.
Supply of Adapter panel fabricated from 14/16 SWG CRCA sheet steel
and duly painted with neoprene gaskets at all cover joints, having
18 detachable gland plates and complete with 1000A 4P tinned copper Nos 3 375,000 1,125,000
busbars with HSS & mounted on insulators of non-hygroscopic material
with provision for terminating incoming cables from Main Panel and
outgoing cables to chiller circuits. 1000 A, 50ka, ACB with cable entry box
& surface enclosure with R-Y-B indicator.
BALCONY AHU MAINS DB
160A 4P 16 KA MCCB -- 1 nos
19 C 40/63A 3P 10 KA MCB -- 7 nos Nos 1 29,410 29,410
C 16/32A 3P 10 KA MCB -- 1 nos
8 WAY VTPN MCCB DB IP43 -- 1 nos
ABOVE BALCONY AHU DB-Z1 & Z2
C 63A 4P 10 KA MCB -- 1 nos
20 Nos 2 19,300 38,600
C 16 - 25A 3P 10 KA MCB -- 8 nos
8 WAY VTPN MCB DB IP43 -- 1 nos
BELOW BALCONY AHU DB-Z1 & Z2
C 63A 4P 10 KA MCB -- 1 nos
21 Nos 2 16,200 32,400
C 16 - 25A 3P 10 KA MCB -- 6 nos
6 WAY VTPN MCB DB IP43 -- 1 nos
STAGE/PODIUM AHU DB-Z1 & Z2
Conventional earthing pit system with 600 x 600 x 3mm copper plate , in
to 3 mts deep excavated earth , 2'' alterante layers of salt, charcoal and
2 earth, watering pipe, heavy duty chamber,all nit bolts to be in stainless Nos - 12,000 -
steel, copper braising for jointing of conductors to plates etc to be
complete in all respects and standards
3 S/F of 25 x 3 mm bare flat strip G.I. earthing Mts - 125 -
4 S/F of 25 x 6 mm bare flat strip G.I. earthing Mts - 240 -
5 S/F of 32 x 3 mm bare flat strip G.I. earthing Mts - 285 -
6 S/F of 32 x 6 mm bare flat strip G.I. Earthing Mts - 450 -
7 S/F of 50 x 3 mm bare flat strip G.I. earthing Mts - 240 -
8 S/F of 50 x 6 mm bare flat strip G.I. earthing Mts - 490 -
9 S/F of 50 x 10 mm bare flat strip G.I. earthing Mts - 590 -
10 S/F of 65 x 10 mm bare flat strip G.I. earthing Mts - 650 -
11 S/F of bare 12 swg GI earth Mts - 20 -
12 S/F of bare 8 swg GI earth Mts - 30 -
13 S/F of copper earth bus bar 50 x 6 mm G.I. with ms enclosure Nos 4 6,500 26,000
14 S/F of 25 x 3 mm bare flat strip copper earthing Mts 2,000 490 980,000
15 S/F of 50 x 3 mm bare flat strip copper earthing Mts 550 885 486,750
16 S/F of 50 x 6 mm bare flat strip copper earthing Mts 200 1,800 360,000
17 S/F of bare 8 swg CU earth Mts 1,000 65 65,000
18 S/F of copper earth bus bar 25 x 6 copper with ms enclosure Nos 6 5,500 33,000
19 S/F of 6 sqmm x1c pvc insulated green color coded wire conduit Mts 50 65 3,250
20 S/F of 10 sqmm x1c pvc insulated green color coded wire conduit Mts 50 120 6,000
21 S/F of 16 sqmm x1c pvc insulated green color coded wire conduit Mts 25 175 4,375
22 S/F of 25 sqmm x1c pvc insulated green color coded wire conduit Mts 25 265 6,625
25 LIGHTINING ARRESTOR
Supply of level one protection Early Streamer Emission type Lightning
Protection complete with the Lightning Air Terminal - Configured as a
Spheroid which is comprised of separate electrically isolated 4panels
surrounding an Earthened Central Finial. The upper section of the central
finial shall be rated to withstand 200KA. The Insulation material used to
electrically isolate the panels shall be comprised of base polymer which
shall provide high Ozone & UV resistance with a di-electric strength of 24-
38KV/mm & ESE terminal shall withstand a minimum Switching Impulse
Voltage of 500KV tested as per NFC 17-102 & IEC Test Standard - IEC60-
1:1989. Design to co ordinated with the supplying vendor . Supply of
Mounting Pole. The mounting pole used to support the lightning air
terminal shall either be a supporting mast or Free standing mast at a
a minimum height of 5 metres above to be area protected or as per required Nos 4 200,000 800,000
level of protection. The mounting pole and supports shall be securely
fixed with brackets and guy wires where it is required to withstand
maximum locally recorded wind velocity. Mounting Pole shall be non
corrosive. The down conductor shall pass through the centre of the pole
for the entire length of the pole. Supporting Guyed Mast : 5Mtr. .
Lightning Strike recorder( 6 digits Display) of non-resettable type in an IP
67 enclosure with the minimum sensitivity of 1500 A & maximum capacity
of 220 KA ( 8/20 micro sec wave form) tested as per IEC 60-1:189.
( these specks are considering a specific make, equivalent can be used)
G STAIRCASE WIRING
1 way Light point wiring with all circuits from MCB DB and modular
1 switches as required for staircase wiring - for primary points using 1.5 Pts 8 1,800 14,400
sqmm x 3 wire from db / switch boards.To be connected to emergency db
same as above - for secondary points using 1.5 sqmm x 3 wire from db /
2 Pts 40 850 34,000
switch boards.To be connected to emergency db
TOTAL FOR STAIRCASE WIRING 48,400
SITC of light / fan point / circuit wiring direct to mcb db or switch board as
mentioned in respective drawings including circuits from switch board &
lights to mcb db with 1.5 / 2.5 / 4 sqmm or as mentioned with FRLS
copper wires in conduits with all terminations in copper cable sockets/
lugs, using modular switch accessories including chasing & recementing
for recess boxes & conduiting as required. Modular switches for quote to
be considered. Wiring to be done in if already laid ceiling cable trays
and to be extended with conduits to the exact location of point. Switch
board to switch board looping & sub circuit from DB shall be 2.5 sqmm x
3 wire. Switch board to primary & secondary point wiring shall be 1.5
sqmm x 3 wire, DB to direct primary & secondary point wiring shall be
2.5 sqmm x 3 wire
Primary point wiring in conduits with 1.5 sqmm x 3 wire controlled through
1 switch board including ciruit to DB with 2.5 sqmm x 3 wire .Shall include Pts 225 1,250 281,250
modular switches
Secondary point wiring in conduits with 1.5 sqmm x 3 wire looped to the
2 Pts 400 750 300,000
above primary point wiring
3 S/F of ceiling fan step regulator with face plate and enclosure. Nos 25 1,200 30,000
Primary point wiring in conduits with 2.5 sqmm x 3 wire controlled directly
4 Pts 60 2,250 135,000
through MCB DB .
Secondary point wiring in conduits with 2.5 sqmm x 3 wire looped to the
5 Pts 225 750 168,750
above primary point wiring
6 S/F of 6 a switch socket with face plate and enclosure Nos 70 650 45,500
S/F of 13 a universal multi socket with switch with face plate and
7 Nos 120 1,100 132,000
enclosure
S/F of 2.5 sqmm x 3 wire circuits in conduits for power wiring from DB to
8 Pts 20 2,500 50,000
socket outlets for primary power points
S/F of 2.5 sqmm x 3 wire circuits in conduits for power wiring from DB to
9 Pts 40 1,500 60,000
socket outlets for secondary power pints looped to primary points
S/F of 4 sqmm x 3 wire circuits in conduits for power wiring from DB to
10 Pts 40 3,400 136,000
socket outlets for primary power points
S/F of 4 sqmm x 3 wire circuits in conduits for power wiring from DB to
11 Pts 80 2,100 168,000
socket outlets for secondary power points looped to primary points
SUB TOTAL FOR LIGHTING & POWER WIRING FOR TOILETS ,
12 1,506,500
COMMON , BALCONY AREAS ETC
S/F of 1.5 sqmm x 3 wire circuits in conduits for lighting wiring from DB to
1 Mts 100 125 12,500
light points
S/F of 2.5 sqmm x 3 wire circuits in conduits for lighting wiring from DB to
2 Mts 9,800 155 1,519,000
light points
S/F of 4 sqmm x 3 wire circuits in conduits for lighting wiring from DB to
3 Mts 1,000 185 185,000
light points
S/F of 2 core x 1.5 sqmm copper multistranded , pvc insulated , pvc
4 Mts 100 60 6,000
sheathed
S/F of 3 core x 1.5 sqmm copper multistranded , pvc insulated , pvc
5 Mts 100 65 6,500
sheathed
S/F of 2 core x 2.5 sqmm copper multistranded , pvc insulated , pvc
6 Mts 100 90 9,000
sheathed
S/F of 3 core x 2.5 sqmm copper multistranded , pvc insulated , pvc
7 Mts 100 100 10,000
sheathed
1 S/F of 6 a switch socket with face plate and enclosure Nos 25 650 16,250
S/F of 13 a universal multi socket with switch with face plate and
2 Nos 80 1,100 88,000
enclosure
S/F of 2.5 sqmm x 3 wire circuits in conduits for power wiring from DB to
3 Mts 200 155 31,000
socket outlets for power points
S/F of 4 sqmm x 3 wire circuits in conduits for power wiring from DB to
4 Mts 1,500 185 277,500
socket outlets for power points
S/F of 2.5 sqmm x 5 wire circuits in conduits for power wiring from DB to
5 Mts 200 265 53,000
socket outlets for power points
S/F of 4 sqmm x 5 wire circuits in conduits for power wiring from DB to
6 Mts 200 310 62,000
socket outlets for power points
7 20 A 4 pin and earth metal clad plug socket with 4 pole mcb in enclosure Nos 10 5,500 55,000
8 32 A 4 pin and earth metal clad plug socket with 4 pole mcb in enclosure Nos 10 6,500 65,000
S/F of ladder type , bolted type ,cable tray ,with hanger support , tee,
1 bends, coupler ,cross pieces ,reducers ,Z section all accessories etc
complete in all respects . Pre galvanized .
a 1000mm wide x 50mm deep Mts 5 1,250 6,250
b 750mm wide x 50 mm deep Mts 5 1,000 5,000
c 600mm wide x 50 mm deep Mts 5 950 4,750
d 450mm wide x 50 mm deep Mts 5 850 4,250
e 300mm wide x 40 mm deep Mts 5 740 3,700
f 200mm wide x 25 mm deep Mts - 650 -
g 150mm wide x 25 mm deep Mts - 600 -
h 100mm wide x 25 mm deep Mts - 550 -
S/F of perforated cable trays, without cover,16 SWG, bolted type ,cable
2 tray ,with hanger support , tee, bends, coupler ,cross pieces ,reducers ,Z
section all accessories etc complete in all respects . Pre galvanized .
a 1000mm wide x 50mm deep Mts 200 2,200 440,000
b 750mm wide x 50 mm deep Mts 400 1,800 720,000
c 600mm wide x 50 mm deep Mts 1,600 1,500 2,400,000
d 450mm wide x 50 mm deep Mts 400 1,100 440,000
e 300mm wide x 40 mm deep Mts 700 900 630,000
f 200mm wide x 25 mm deep Mts 400 550 220,000
g 150mm wide x 25 mm deep Mts 400 450 180,000
h 100mm wide x 25 mm deep Mts 400 400 160,000
S/F of trunking , with cover,16 SWG, bolted type , ,with hanger support ,
3 tee, bends, coupler ,cross pieces ,reducers ,Z section all accessories etc
complete in all respects . Pre galvanized .
a 600mm wide Mts 10 1,600 16,000
b 450mm wide Mts 10 1,200 12,000
c 300mm wide Mts 10 1,000 10,000
d 200mm wide Mts 10 650 6,500
e 150mm wide Mts 10 550 5,500
f 100 mm wide Mts 10 500 5,000
S/F of ALU 16 swg box section to be laid on floor with all excavation ,
recementing & refinishing civil works to make good in line with the
3
existing floor level . Respective junction box to be fabricated in 16 swg GI
sheet with cut out as required for terminating the box sections
a 65 x 40 mm Mts 50 550 27,500
b 100 x 40 mm Mts 35 765 26,775
c 150 x 150 x 50 mm MS Junction box with cover & cut outs Nos 10 350 3,500
d 200 x 150 x 50 mm MS Junction box with cover & cut outs Nos 5 450 2,250
e 250 x 150 x 50 mm MS Junction box with cover & cut outs Nos 5 600 3,000
S/F of heavy duty PVC conduits to be laid on floor with all excavation ,
recementing & refinishing civil works to make good in line with the
existing floor level . Respective junction box to be fabricated in 16 swg GI
4
sheet with cut out as required for terminating the box sections. This item
to be used other all the above items where pvc conduits are already
included
a 1 x 25mm Mts 700 65 45,500
b 1 x 32mm Mts 600 75 45,000
c 1 x 40mm Mts 500 95 47,500
d 1 x 50mm Mts 500 120 60,000
e 150 x 150 x 50 mm MS Junction box with cover & cut outs Nos 20 350 7,000
f 200 x 200 x 50 mm MS Junction box with cover & cut outs Nos 50 450 22,500
g 250 x 250 x 50 mm MS Junction box with cover & cut outs Nos 50 650 32,500
h 300 x 300 x 50 mm MS Junction box with cover & cut outs Nos 10 850 8,500
i 400 x 400 x 50 mm MS Junction box with cover & cut outs Nos 5 1,150 5,750
S/F of heavy duty UPVC trunking with cover and all accessories to
5
complete in all respects
a 75 x 75 mm Mts 80 590 47,200
b 100 x 75 mm Mts 70 735 51,450
c 100 x 100 mm Mts 60 875 52,500
M MISC ITEMS
Supplying & Laying of rubber matting of 6 mm thickness of required length
1 and breadth with good insulation property for 33 kV. sq mts 30 1,200 36,000
Supplying and erecting wall hook 225 mm projection for keeping fire
4 buckets, made out of 15mm dia M.S Rod grouted in wall to a depth of Nos 16 550 8,800
minimum 150mm.
Supply a pair of duly tested rubber hand gloves suitable for working on
5 11kV grade supply. each 4 900 3,600
Laisioning work for getting permanent power for entire premises for 2 nos
x 1500 kva from local supply electricity board, this also includes liasioning
work with all other related authorities, submission of application forms to
get sanctioned Load as per load sheet, Charges of Electrical Inspectors
approval, Local authorities approval, Testing of Equipment at site etc. The
10 charges required to pay legal fees shall be scope of electrical contractor & Job 1 600,000 600,000
the same will get reimbursed as per actual fees only after production of
original receipt from electricity board duly stamped & signed by electricity
board authority.
SUMMARY TOTAL
A SUB TOTAL FOR PANELS / MCB DB'S / SWITCHGEARS 14,261,280
B SUB TOTAL FOR EARTHING / PITS / L.A. 3,913,000
C SUB TOTAL FOR CABLING / WIRING & TERMINATIONS 15,298,530
D SUB TOTAL LIFT ROOM AND SHAFT WIRING 276,800
TOTAL FOR TEMPORARY POWER ARRANGEMENT FOR
E 1,910,000
CONSTRUCTION
F SUB TOTAL FOR FIXING LIGHT FIXTURES 986,500
G SUB TOTAL FOR STAIRCASE WIRING 48,400
SUB TOTAL FOR LIGHTING & POWER WIRING FOR TOILETS ,
H 1,506,500
COMMON , BALCONY AREAS ETC
I SUB TOTAL FOR MAIN WORSHIP AREA LIGHTING WIRING 1,748,000
J SUB TOTAL FOR MAIN WORSHIP AREA POWER WIRING 647,750
SUB TOTAL FOR EXTERNAL / LAND SCAPING, FAÇADE LIGHTING &
K 4,246,875
POWER
L SUB TOTAL TRUNKING / CABLE TRAYS / CONDUITS 5,757,375
M SUB TOTAL FOR MISC ITEMS 812,300
SUB TOTAL 51,413,310
EXCLUSIONS
1 IT active components
2 service providers for internet, TV etc
3 light fixtures , façade lights , gysers, exhaust
phone hand sets , TV ,electrical and electronic gadgets , coffee
4
makers, minibar ,etc
5 Lifts , stack park, EPBAX , Racks, Switches
6 scanner, x ray, boom barrier, body scanner, gaurd tour management
etc
7 civil works and foundation for MEP
8 AV system
9 Automation
10 civil Trenches