Sie sind auf Seite 1von 29

ELECTRICAL BOQ FOR INTERNATIONAL WORSHIP CENTRE AT NIGERIA

25-Oct-18
SUPPLY & INSTALLATION
NO DESCRIPTION UNITS QTY
Rate INR Amount INR
NOTES
All wiring to be done in FRLS PVC MMS conduits , recessed or surface as
**
required at site. Conduits in floor shall be HMS
** All wires and cables are with copper conductor only
Modular Switch assesories shall be LEGRAND ARTEOR SQUARE
**
WHITE MECHANISM
** Contractor to approve all GA dwgs before fabrication
** Contractor to provide all shop dwgs prior to installation
Contractor to provide all as built dwgs [ 3 soft copy (cd or pen drive) & 5
**
sets of hard copies ] after completion
Contractor to execute in coordination with all vendors , consultants &
**
Architect
Any items not covered & required to be executed shall be done with prior
**
approval of PMC and shall be paid as per prevaling market rates
Vendor to maintain clean site with debris management , failing to do so
** the client shall do the same and deduct from the vendor along with
penalty.
** Contractor to certify the site by the local electrical inspector
** All '0' items to be compulsorily quoted
** Rates shall be billed as per actuals installed at site
All items are supply , install , test and commission at site unless otherwise
** mentioned and shall include all material , labour, transport , loading ,
unloading, relocations, transit and its insurance , site insurance stc.
A PANELS / MCB DB'S / SWITCHGEARS
S.I.T.C. [supply , installation, testing & commissioning ]of
14/16(2mm/1.62mm) swg CRCA fabricated & powder coated after 7 tank
process ,compartmentalised panel with air ventilation & dust/vermin proof
, free standing, floor mounted on100 mm rigid 'C' MS base supported on
concrete base with anchor fastners. Panels to be top / bottom entry &
accessible from front & rear side or as required by consultant & site
conditions. GA to be made by contractor & approved by consultant Prior
to fabrication with respect to SLD & specks. Busbar to be of electrolytic
Alu with current density of 1.0 amp per sqmm or as mentioned for copper
Panel shall confirm to all applicable IS standards. All MCCB shall be with
microprocessor based release & RHOM . Below 25 KA thermal magnetic
can be used. APFC panels to have D curve mcb All internal wiring to be
done in pvc insulated copper wires Out going from MCCB to be
terminated in bus bars/ panel connecteors in cable alley. All terminations
to have BI-Metallic strip as required . All MCCB to have spreader links
MCB DB. ALL DB's to be IP43. SITC of DB'S ready made or fabricated
as per design & site conditions or consultants requirements. TPN DB
shall have 3 nos separate neutral links / flexy DB / with internal wiring
done as required with copper wire & cable sockets Internal terminations &
wiring to be neatly dressed up in a systematic manner. All MCB to be 'C'
& 'D' curve as mentioned & indicators to be LED All MCB & DB to be
approved by consultant before procurement . DB to be fixed surface or
recessed as per requirements

All panels to have gas suppresion system with gas cylinder , piping, panel
internal piping complete in all respects as mentioned.below.This shall be
not considered as a seprate item and shall be included in the cost of all
panels. As per specifications below.

2000 A , Tp ,50 ka ,ACB with E/F, U/V, O/C, S/C , O/V, EDO,
microprocessor based releases ,data communication [ L & T - C power or
equivalent ] --- 2nos
LED ON OFF TRIP indicators with mcb protection -- 2 set
LED L1-L2-L3 indicators with mcb protection -- 2 set
Multifunction CT Meter -- 2 set
CT 2000/5, CL 1,15VA -- 2 sets [1 set for 3 Phases]
CT 2000/5, CL 1,15VA -- for apfc control
Transient voltage surge suppressor , cat c , continuous operating, 3phase
4 wire , metal oxide varistor technology , parallel connected , less than 0.5
nano second response time , surge current capacity 100 ka , 6000v ,
1 3000a, UL listing & labelled 14492 supressed voltage range of 800v peak. Nos 1 2,875,000 2,875,000
ASCO make 330SERIES or equivalent -- 1 set with Mcb Protection
ASCO make 300 series or equivalent 2000 A, 4p, ATS -- 1 Nos
4P Cu bus bar with HSS --- 1 set
microprocessor based releases mccb
800 A 4P 36 KA MCCB - 2 Nos
500 A 4P 36 KA MCCB - 2 Nos
315 A 4P 36 KA MCCB - 1 Nos
thermal magnetic releases mccb
250 A 4P 25 KA MCCB - 8 Nos
160 A 4P 16 KA MCCB - 6 Nos
125 A 4P 16 KA MCCB - 2 Nos
C 40-63A 4P 10 KA MCB -- 5 nos

2000 A , Tp ,50 ka ,ACB with E/F, U/V, O/C, S/C , O/V, EDO,
microprocessor based releases ,data communication [ L & T - C power or
equivalent ] --- 2nos
LED ON OFF TRIP indicators with mcb protection -- 6 set
LED L1-L2-L3 indicators with mcb protection -- 2 set
Multifunction CT Meter -- 2 set
CT 2000/5, CL 1,15VA -- 2 sets [1 set for 3 Phases]
CT 2000/5, CL 1,15VA -- for apfc control

Transient voltage surge suppressor , cat c , continuous operating, 3phase


4 wire , metal oxide varistor technology , parallel connected , less than 0.5
nano second response time , surge current capacity 100 ka , 6000v ,
3000a, UL listing & labelled 14492 supressed voltage range of 800v peak.
ASCO make 330SERIES or equivalent -- 1 set with Mcb Protection
2 Nos 1 2,950,000 2,950,000
ASCO make 300 series or equivalent 2000 A, 4p, ATS -- 1 Nos
Dual sensing KWH meter with mcb protection -- 6 Nos
CT 1000/5, CL 1,15VA -- 4 sets [1 set for 3 Phases]
CT 300/5, CL 1,15VA -- 1 sets [1 set for 3 Phases]
CT 500/5, CL 1,15VA -- 1 sets [1 set for 3 Phases]
4P Cu bus bar with HSS --- 1 set
microprocessor based releases mccb-
1000 A 4P 50KA, ACB with E/F, U/V, O/C, S/C , O/V, EDO - 4 Nos
500 A 4P 36 KA MCCB - 3 Nos
315 A 4P 36 KA MCCB - 1 Nos
thermal magnetic releases mccb-
250 A 4P 25 KA MCCB - 1 Nos
160 A 4P 16 KA MCCB - 3 Nos
C 40-63A 4P 10 KA MCB -- 2 nos
FIRE PUMP PANEL
250 A, 4p ,25 ka ,MCCB with (TM )--- 2 nos
LED ON OFF TRIP indicators with mcb protection -- 9 set
LED L1-L2-L3 indicators with MCB protection -- 1 set
ASCO make 230 series or equivalent 250 A, 4p, ATS -- 1 Nos
Load manager (dual sence)-- 1 set
3 CT 250/5, CL 1,15VA -- 1 sets [1 set for 3 Phases] Nos 1 520,000 520,000
4P Cu bus bar with HSS --- 1 set
Start/Stop/Trip ind with P/B sw. & STAR DELTA / DOLstarter set as
required with control logic of fire panel
thermal magnetic releases mccb-
125 A 4P 16KA MCCB -- 3 nos
80 A 4P 16KA MCCB -- 1 nos
C 32 A 4P 10 KA MCB -- 3 nos
HVAC PANEL (FOR OTHER THAN WORSHIP & UTILITY)
800 A 4P 36 KA MCCB - 1 Nos
(microprocessor based releases mccb)
LED L1-L2-L3 indicators with mcb protection -- 1 set
Load manager-- 1 set
CT 800/5, CL 1,15VA -- 1 sets [1 set for 3 Phases]
4P Cu bus bar with HSS --- 1 set
4 Nos 1 230,000 230,000
(thermal magnetic releases mccb)
160 A 4P 16 KA MCCB - 3 Nos
125 A 4P 16 KA MCCB - 1 Nos
100 A 4P 16 KA MCCB - 2 Nos
80 A 4P 16 KA MCCB - 3 Nos
C 40-63A 4P 10 KA MCB -- 5 nos
C 25A 4P 10 KA MCB -- 1 nos
RAW POWER MAIN PANEL (ALL AREA)
315 A 4P 36 KA MCCB - 1 Nos
(microprocessor based releases mccb)
LED L1-L2-L3 indicators with mcb protection -- 1 set
Load manager-- 1 set
5 CT 300/5, CL 1,15VA -- 1 sets [1 set for 3 Phases] Nos 1 155,000 155,000
4P Cu bus bar with HSS --- 1 set
(thermal magnetic releases mccb)
125 A 4P 16 KA MCCB - 2 Nos
80 A 4P 16 KA MCCB - 3 Nos
C 40-63A 4P 10 KA MCB -- 16 nos
LIGHTING MAIN PANEL (OTHER THAN WORSHIP AREA)
500 A 4P 36 KA MCCB - 1 Nos
(microprocessor based releases mccb)
LED L1-L2-L3 indicators with mcb protection -- 1 set
Load manager-- 1 set
6 Nos 1 150,000 150,000
CT 500/5, CL 1,15VA -- 1 sets [1 set for 3 Phases]
4P Cu bus bar with HSS --- 1 set
(thermal magnetic releases mccb)
125 A 4P 16 KA MCCB - 3 Nos
C 40-63A 4P 10 KA MCB -- 15 nos
LIGHTING/POWER MAIN PANEL (WORSHIP AREA)
400 A 4P 36 KA MCCB - 1 Nos
(microprocessor based releases mccb)
LED L1-L2-L3 indicators with mcb protection -- 1 set
Load manager-- 1 set
CT 400/5, CL 1,15VA -- 1 sets [1 set for 3 Phases]
7 4P Cu bus bar with HSS --- 1 set Nos 1 185,000 185,000
(microprocessor based releases mccb)
315 A 4P 36 KA MCCB - 2 Nos
(thermal magnetic releases mccb)
100 A 4P 16 KA MCCB - 1 Nos
C 25-32A 4P 10 KA MCB -- 1 nos
C 40-63A 4P 10 KA MCB -- 9 nos
UPS POWER MAIN PANEL (OTHER THAN WORSHIP AREA)
80 A 4P 16 KA MCCB - 1 Nos
thermal based releases mccb)
LED L1-L2-L3 indicators with mcb protection -- 1 set
8 Load manager-- 1 set Nos 1 85,000 85,000
CT 75/5, CL 1,15VA -- 1 sets [1 set for 3 Phases]
4P Cu bus bar with HSS --- 1 set
C 40-63A 4P 10 KA MCB -- 11 nos
C 25-32A 4P 10 KA MCB -- 4 nos
100KVA X3 UPS O/P MAIN PANEL (OTHER THAN WORSHIP AREA)
250 A 4P 25 KA MCCB -- 4 Nos
LED L1-L2-L3 indicators with mcb protection -- 4 set
4P Cu bus bar with HSS --- 1 set
9 Nos 1 240,000 240,000
(microprocessor based releases mccb)
500 A 4P 36 KA MCCB - 2 Nos
thermal magnetic releases mccb-
80 A 4P 16 KA MCCB - 2 Nos
100KVA X3 UPS O/P MAIN PANEL (WORSHIP AREA)
250 A 4P 25 KA MCCB -- 4 Nos
LED L1-L2-L3 indicators with mcb protection -- 4 set
4P Cu bus bar with HSS --- 1 set
10 Nos 1 220,000 220,000
(microprocessor based releases mccb)
400 A 4P 36 KA MCCB - 2 Nos
(thermal magnetic releases mccb)
125 A 4P 16 KA MCCB - 1 Nos
CHILLER PRI.PUMP PANEL
315 A, 4p ,36 ka ,MCCB--- 1 nos
(microprocessor based releases mccb)
LED ON OFF TRIP indicators with mcb protection -- 5 set
LED L1-L2-L3 indicators with MCB protection -- 1 set
11 4P Cu bus bar with HSS --- 1 set Nos 1 205,000 205,000
Start/Stop/trip ind with P/B sw. & STAR DELTA / DOLstarter set as
required with control logic of fire panel
thermal magnetic releases mccb-
160 A 4P 16KA MCCB -- 4 nos
100 A 4P 16KA MCCB -- 1 nos
STAGE/PODIUM AHU MAINS PANEL
160 A 4P 16 KA MCCB -- 1 Nos
LED L1-L2-L3 indicators with mcb protection -- 1 set
12 4P Cu bus bar with HSS --- 1 set Nos 1 98,000 98,000
thermal magnetic releases mccb-
80 A 4P 16 KA MCCB - 3 Nos
C 40-63A 4P 10 KA MCB -- 4 nos
SMOKE EVACU.& STAIRCASE PRESSUR. FAN DB(IP55)-Z1 & Z2
100 A 4P 16 KA MCCB -- 1 Nos
LED L1-L2-L3 indicators with mcb protection -- 1 set
13 Nos 2 73,000 146,000
4P Cu bus bar with HSS --- 1 set
C 25-32A 4P 10 KA MCB -- 9 nos
C 40-63A 4P 10 KA MCB -- 1 nos
UPS & BATTERY ROOM AC POWER DB
125 A 4P 16 KA MCCB -- 1 Nos
LED L1-L2-L3 indicators with mcb protection -- 1 set
14 4P Cu bus bar with HSS --- 1 set Nos 1 78,000 78,000
32 A 2P 30MA RCCB -- 3 Nos
C 25-32A 4P 10 KA MCB -- 2 nos
C 40-63A 4P 10 KA MCB -- 4 nos
CW.COND.PUMP & COOLING TOWER PUMP PANEL
500 A, 4p ,36 ka ,MCCB--- 1 nos
(microprocessor based releases mccb)
LED ON OFF TRIP indicators with mcb protection -- 9 set
LED L1-L2-L3 indicators with MCB protection -- 1 set
15 4P Cu bus bar with HSS --- 1 set Nos 1 300,000 300,000
Start/Stop/trip ind with P/B sw. & STAR DELTA / DOLstarter set as
required with control logic of fire panel
200 A 4P 25KA MCCB -- 4 nos
100 A 4P 16KA MCCB -- 1 nos
C 40-63A 4P 10 KA MCB -- 4 nos

500A, 4P ,36 KA ,MCCB with (microprocessor based releases mccb)--- 1


nos
Auto / manual ,APFC 10 step meter ---- 1nos
Gas filled 440 v capacitor 50 kvar X 2 steps
Gas filled 440 v capacitor 25 kvar X 3 steps
Gas filled 440 v capacitor 15 kvar X 3 steps
Gas filled 440 v capacitor 10 kvar X 2 steps

16 A/M switch , phase indication lamps with mcb tp for protection 4p Nos 1 720,000 720,000
aluminium bus bar with colour coded HSS as per capacity 30 sec delay
timing for manual operation ,power contactors ,auxiliary contactors ,
illuminated start stop push buttons with elements , TP MCB for power
contactors , phase indication lamps , Digital amp meter , with CT , digital
voltmeter with selector switch , on / off indication lamps for capacitors All
contactors to be capacitor duty.Detuned reactor filters to be used.

All 'D' curve mcb to be used Capacitors to be placed in separate


compartments with small continuous rating ventilation fans. All MCCB to
APFC PANEL links
have spreader [225 with
KVAR ] [current
RHOM & contactor
sensing CT to bebased]
included

500A, 4P ,36 KA ,MCCB with (microprocessor based releases mccb)--- 1


nos
Auto / manual ,APFC 10 step meter ---- 1nos
Gas filled 440 v capacitor 50 kvar X 1 steps
Gas filled 440 v capacitor 25 kvar X 5 steps
Gas filled 440 v capacitor 15 kvar X 2 steps
Gas filled 440 v capacitor 10 kvar X 2 steps

17 A/M switch , phase indication lamps with mcb tp for protection 4p Nos 1 675,000 675,000
aluminium bus bar with colour coded HSS as per capacity 30 sec delay
timing for manual operation ,power contactors ,auxiliary contactors ,
illuminated start stop push buttons with elements , TP MCB for power
contactors , phase indication lamps , Digital amp meter , with CT , digital
voltmeter with selector switch , on / off indication lamps for capacitors All
contactors to be capacitor duty.Detuned reactor filters to be used.

All 'D' curve mcb to be used Capacitors to be placed in separate


compartments with small continuous rating ventilation fans. All MCCB to
have spreader links with RHOM sensing CT to be included
1000A/4P/36KA/MCCB WITH CHILLER ADPT.PANEL

Supply of Adapter panel fabricated from 14/16 SWG CRCA sheet steel
and duly painted with neoprene gaskets at all cover joints, having
18 detachable gland plates and complete with 1000A 4P tinned copper Nos 3 375,000 1,125,000
busbars with HSS & mounted on insulators of non-hygroscopic material
with provision for terminating incoming cables from Main Panel and
outgoing cables to chiller circuits. 1000 A, 50ka, ACB with cable entry box
& surface enclosure with R-Y-B indicator.
BALCONY AHU MAINS DB
160A 4P 16 KA MCCB -- 1 nos
19 C 40/63A 3P 10 KA MCB -- 7 nos Nos 1 29,410 29,410
C 16/32A 3P 10 KA MCB -- 1 nos
8 WAY VTPN MCCB DB IP43 -- 1 nos
ABOVE BALCONY AHU DB-Z1 & Z2
C 63A 4P 10 KA MCB -- 1 nos
20 Nos 2 19,300 38,600
C 16 - 25A 3P 10 KA MCB -- 8 nos
8 WAY VTPN MCB DB IP43 -- 1 nos
BELOW BALCONY AHU DB-Z1 & Z2
C 63A 4P 10 KA MCB -- 1 nos
21 Nos 2 16,200 32,400
C 16 - 25A 3P 10 KA MCB -- 6 nos
6 WAY VTPN MCB DB IP43 -- 1 nos
STAGE/PODIUM AHU DB-Z1 & Z2

22 C 80A 4P 10 KA MCB -- 1 nos Nos 2 21,300 42,600


C 16 - 32A 3P 10 KA MCB -- 6 nos
6 WAY VTPN MCB DB IP43 -- 1 nos
FRESH AIR FAN DB, PRESSUERIZATION FAN DB & AIR CURTAIN
POWER DB
23 C 40 A 4P 10 KA MCB -- 1 nos Nos 3 13,700 41,100
C 16 - 32A 3P 10 KA MCB -- 4 nos
4 WAY VTPN MCB DB IP43 -- 1 nos
OTHER THAN WORSHIP AREA AHU UNIT DB-Z1 & Z2
80A 4P 16 KA MCCB -- 1 nos
24 (thermal magnetic release mccb) Nos 2 31,615 63,230
C 16/32A 3P 10 KA MCB -- 12 nos
12 WAY VTPN MCCB DB IP43 -- 1 nos
UTILITY FRESH AIR FAN DB
C 25 A 4P 10 KA MCB -- 1 nos
25 Nos 1 13,150 13,150
C 16 - 32A 3P 10 KA MCB -- 4 nos
4 WAY VTPN MCB DB IP43 -- 1 nos
UTILITY AREA VENTILATION FAN DB-1 & 2 (PARKING & DG SIDE)
C 63A 4P 10 KA MCB -- 1 nos
26 Nos 2 21,750 43,500
C 16 - 25A 3P 10 KA MCB -- 12 nos
6 WAY VTPN MCB DB IP43 -- 1 nos
LANDSCAPING PUMP& WATER FOUNTAIN POWER DB
C 40 A 4P 10 KA MCB -- 1 nos
27 Nos 1 16,200 16,200
C 16 - 25A 3P 10 KA MCB -- 6 nos
6 WAY VTPN MCB DB IP43 -- 1 nos
LIFT MAIN DB-Z1 & Z2
160A 4P 16 KA MCCB -- 1 nos
28 Nos 2 25,800 51,600
C 40/63A 3P 10 KA MCB -- 6 nos
6 WAY VTPN MCCB DB IP43 -- 1 nos
SUMP PUMP MAIN DB
C 63A 4P 10 KA MCB -- 1 nos
29 Nos 1 17,000 17,000
29 Nos 1 17,000 17,000
C 40 A 3P 10 KA MCB -- 4 nos
4 WAY VTPN MCB DB IP43 -- 1 nos
SUMP PUMP DB-1,2,3
C 40 A 4P 10 KA MCB -- 1 nos
30 C 16 - 25A 3P 10 KA MCB -- 5 nos Nos 3 16,700 50,100
C 40/63A 3P 10 KA MCB -- 1 nos
6 WAY VTPN MCB DB IP43 -- 1 nos
BALCONY(W) AREA RAW POWER DB-1,2 / PODIUM LVL(OTW)
RPDB-4,1/ / 7.85M /12M LVL RPDB-3,1 /PODIUM LVL(W) RPDB-3,1
C 40A 4P 10 KA MCB -- 1 nos
31 Over voltage module -- 1nos Nos 8 20,600 164,800
40 A 2P 30MA RCCB -- 3 Nos
C 10 - 25A SP MCB 10 KA - 18 nos
8 WAY TPN MCB DB IP43 -- 1 Nos
SUB PODIUM LVL LIGHTING DB-1,2 / BALCONY(W) AREA MAIN
LIGHTING DB-1,2 /BALCONY(OTW) AREA UPS POWER
DB/BALCONY(W) AREA LIGHTING DB-1,2 / PODIUM LVL(W)AREA
UPS POWER DB-1,2
32 C 40A 4P 10 KA MCB -- 1 nos Nos 9 26,900 242,100
Over voltage module -- 1nos
40 A 2P 30MA RCCB HPI type-- 3 Nos
C 10 - 25A SP MCB 10 KA - 18 nos
8 WAY TPN MCB DB IP43 -- 1 Nos
STAIRCASE LIGHTING DB-1,2
C 63A 4P 10 KA MCB -- 1 nos
Over voltage module -- 1nos
33 Nos 2 26,100 52,200
63 A 2P 30MA RCCB HPI type -- 3 Nos
33 Nos 2 26,100 52,200
C 10 - 25A SP MCB 10 KA - 12 nos
6 WAY TPN MCB DB IP43 -- 1 Nos
BALCONY(OTW) AREA RAW POWER DB-1,2 / PODIUM LVL(OTW)
RPDB-2,3,5,6 / 7.85M /12M LVL RPDB-4,2 / PODIUM LVL(W) RPDB-
4,2 / SUB PODIUM LVL RAW POWER DB-1,2
C 40A 4P 10 KA MCB -- 1 nos
34 Nos 12 18,900 226,800
Over voltage module -- 1nos
40 A 2P 30MA RCCB -- 3 Nos
C 10 - 25A SP MCB 10 KA - 12 nos
6 WAY TPN MCB DB IP43 -- 1 Nos

BMS / CONTROL ROOM UPS POWER DB / FACADE UPS POWER DB-


1,2 / EXTERNAL UPS POWER DB-1,2 / PODIUM LVL(OTW) UPS
PDB-1,2,3,4 / 7.85M /12M LVL LDB-1,2,3,4 / PODIUM LVL(OTW) LDB-
1,2,3,4,5,6 / PODIUM LVL(W) LDB-1,2,3,4
35 C 40A 4P 10 KA MCB -- 1 nos Nos 23 25,200 579,600
Over voltage module -- 1nos
40 A 2P 30MA RCCB HPI type-- 3 Nos
C 10 - 25A SP MCB 10 KA - 12 nos
6 WAY TPN MCB DB IP43 -- 1 Nos
EXTERNAL LDB-1,2,3,4
C 40A 4P 10 KA MCB -- 1 nos
(With 24hrs on/off based timer)
36 Over voltage module -- 1nos Nos 2 22,380 44,760
40 A 2P 100MA RCCB -- 3 Nos
C 10 - 25A SP MCB 10 KA - 12 nos
6 WAY TPN MCB DB IP43 -- 1 Nos
FACADE LDB-1,2,3,4,5,6
C 40A 4P 10 KA MCB -- 1 nos
Over voltage module -- 1nos
37 40 A 2P 100MA RCCB -- 3 Nos Nos 6 21,000 126,000
C 10 - 25A SP MCB 10 KA - 18 nos
8 WAY TPN MCB DB IP43 -- 1 Nos
SUB PODIUM LVL UPS POWER DB, 7.85M /12M LVL UPS POWER
DB, BALCONY(W) AREA UPS POWER DB
C 25A 4P 10 KA MCB -- 1 nos
38 Over voltage module -- 1nos Nos 3 26,500 79,500
25 A 2P 30MA RCCB (HPI) -- 3 Nos
C 10 - 16A SP MCB 10 KA - 18 nos
8 WAY TPN MCB DB IP43 -- 1 Nos
SERVER UPS POWER DB
C 32A 4P 10 KA MCB -- 1 nos
Over voltage module -- 1nos
39 Nos 1 18,000 18,000
32 A 2P 30MA RCCB (HPI) -- 3 Nos
39 Nos 1 18,000 18,000
C 10 - 25A SP MCB 10 KA - 12 nos
6 WAY TPN MCB DB IP43 -- 1 Nos
EXTERNAL RPDB-1,2 / LANDSCAPING RPDB-1,2
C 40A 4P 10 KA MCB -- 1 nos
Over voltage module -- 1nos
40 Nos 4 18,500 74,000
40 A 2P 100MA RCCB -- 3 Nos
C 10 - 25A SP MCB 10 KA - 12 nos
6 WAY TPN MCB DB IP43 -- 1 Nos
KITCHEN PDB
C 63A 4P 10 KA MCB -- 1 nos
Over voltage module -- 1nos
41 Nos 1 21,850 21,850
63 A 2P 30MA RCCB -- 3 Nos
C 10 - 25A SP MCB 10 KA - 18 nos
8 WAY TPN MCB DB IP43 -- 1 Nos
KITCHEN LIGHTING DB
C 25A 4P 10 KA MCB -- 1 nos
Over voltage module -- 1nos
42 Nos 1 23,100 23,100
42 Nos 1 23,100 23,100
25 A 2P 30MA RCCB -- 3 Nos
C 10 - 25A SP MCB 10 KA - 12 nos
6 WAY TPN MCB DB IP43 -- 1 Nos
PODIUM LVL(OTW)AREA MAIN LIGHTING DB-Z1,Z2
125A 4P 16 KA MCCB -- 1 nos
43 Nos 2 24,600 49,200
C 40/63A 3P 10 KA MCB -- 6 nos
6 WAY VTPN MCCB DB IP43 -- 1 nos
7.85M /12M LVL MAIN LIGHTING DB-Z1,Z2 / FACADE MAIN LIGHTING
DB-Z1,Z2 / EXTERNAL MAIN LIGHTING DB-Z1,Z2 / PODIUM
LVL(OTW)AREA MAIN UPS POWER DB-Z1, Z2 / PODIUM
LVL(W)AREA MAIN LIGHTING DB-Z1,Z2 / PODIUM LVL(W)AREA MAIN
RAW POWER DB-Z1,Z2 / 7.85M /12M LVL MAIN
44 RAW POWER DB-Z1,Z2. Nos 14 16,520 231,280
C 63A 4P 10 KA MCB -- 1 nos
C 40A 3P 10 KA MCB -- 3 nos
C 16 - 25A 3P 10 KA MCB -- 1 nos
4 WAY VTPN MCB DB IP43 -- 1 nos
PODIUM LVL(OTW)AREA MAIN RAW POWER DB-Z1,Z2
80A 4P 16 KA MCCB -- 1 nos
45 (thermal magnetic release mccb) Nos 2 20,500 41,000
C 40/63A 3P 10 KA MCB -- 4 nos
4 WAY VTPN MCCB DB IP43 -- 1 nos
7.85M /12M LVL KITCHEN MAIN DB
125A 4P 16 KA MCCB -- 1 nos
46 C 40/63A 3P 10 KA MCB -- 3 nos Nos 1 25,850 25,850
C 25 - 32A 3P 10 KA MCB -- 5 nos
8 WAY VTPN MCCB DB IP43 -- 1 nos
47 SP MCB
a C 6 - 32 A SP Mcb with enclosure Nos 0 925 -
b C 40 A SP Mcb with enclosure Nos 0 1,140 -
c C 63 A SP Mcb with enclosure Nos 0 1,140 -
48 DP MCB
a C 6 - 32 A 2 p Mcb with enclosure Nos 0 1,530 -
b C 40 A 2P Mcb with enclosure Nos 0 1,860 -
c C 63 A 2P Mcb with enclosure Nos 0 1,860 -
49 TP MCB
a C 6 - 32 A TP Mcb with enclosure Nos 0 1,875 -
b C 40 A TP Mcb with enclosure Nos 0 2,340 -
c C 63 A TP Mcb with enclosure Nos 0 2,340 -
50 FP MCB / ISOLATER
a C 6 - 32 A 4 p Mcb with enclosure Nos 0 2,190 -
b C 40 A 4P Mcb with enclosure Nos 0 2,725 -
c C 63 A 4P Mcb with enclosure Nos 0 2,725 -
d 40 A 4P Isolater with enclosure Nos 0 1,720 -
e 63 A 4P Isolater with enclosure Nos 10 1,785 17,850
51 2P RCCB / ELCB
a 16 A 2 P 30 MA RCCB/ELCB in surface enclosure Nos 0 2,775 -
b 25 A 2 P 30 MA RCCB/ELCB in surface enclosure Nos 0 2,940 -
c 32 A 2 P 30 MA RCCB/ELCB in surface enclosure Nos 0 3,120 -
d 40 A 2 P 30 MA RCCB/ELCB in surface enclosure Nos 0 3,275 -
e 63 A 2 P 30 MA RCCB/ELCB in surface enclosure Nos 0 3,725 -
52 4P RCCB / ELCB
a 16 A 4 P 100 MA RCCB/ELCB in surface enclosure Nos 50 3,675 183,750
b 25 A 4 P 100 MA RCCB/ELCB in surface enclosure Nos 35 3,800 133,000
c 32 A 4 P 100 MA RCCB/ELCB in surface enclosure Nos 10 3,900 39,000
d 40 A 4 P 100 MA RCCB/ELCB in surface enclosure Nos 0 3,925 -
e 63 A 4 P 100 MA RCCB/ELCB in surface enclosure Nos 0 4,350 -
f 16 A 4 P 30 MA RCCB/ELCB in surface enclosure Nos 0 3,550 -
g 25 A 4 P 30 MA RCCB/ELCB in surface enclosure Nos 0 3,675 -
h 32 A 4 P 30 MA RCCB/ELCB in surface enclosure Nos 0 3,585 -
i 40 A 4 P 30 MA RCCB/ELCB in surface enclosure Nos 0 3,850 -
j 63 A 4 P 30 MA RCCB/ELCB in surface enclosure Nos 0 4,070 -
53 4P RCCB / ELCB
a 25 A 4 P 100 MA RCCB/ELCB in surface enclosure (IP55) Nos 18 5,500 99,000
b 32 A 4 P 100 MA RCCB/ELCB in surface enclosure (IP55) Nos 0 5,700 -
c 40 A 4 P 100 MA RCCB/ELCB in surface enclosure (IP55) Nos 5 5,850 29,250
d 63 A 4 P 100 MA RCCB/ELCB in surface enclosure (IP55) Nos 0 6,100 -
54 MCCB
a 80 A 4P 16 KA MCCB with RHOM in enclosure Nos 0 8,300 -
b 100 A 4P 16 KA MCCB with RHOM in enclosure Nos 0 8,300 -
c 125 A 4P 16 KA MCCB with RHOM in enclosure Nos 0 8,500 -
d 160 A 4P 16 KA MCCB with RHOM in enclosure Nos 0 9,650 -
e 200 A 4P 25 KA MCCB with RHOM in enclosure Nos 0 19,100 -
f 250 A 4P 25 KA MCCB with RHOM in enclosure Nos 6 23,000 138,000
g 315 A 4P 36 KA MCCB with RHOM in enclosure Nos 0 35,400 -
h 400 A 4P 36 KA MCCB with RHOM in enclosure Nos 0 35,400 -
i 630 A 4P 36 KA MCCB with RHOM in enclosure Nos 1 41,200 41,200
56 MCCB
a 200 A/4P /25 KA MCCB with RHOM & 4P Alu busbar in enclosure Nos 0 22,750 -
b 250 A/4P /25 KA MCCB with RHOM & 4P Alu busbar in enclosure Nos 0 26,500 -
c 400 A/4P /36 KA MCCB with RHOM & 4P Alu busbar in enclosure Nos 0 39,000 -
57 MOTOR STARTERS / PARALLEL P/B STATION
a 2.0HP Motor DOL Starter Nos 24 2,500 60,000
b 3.0HP Motor DOL Starter Nos 14 2,800 39,200
c 5.0HP Motor DOL Starter Nos 1 3,500 3,500
d 7.5HP Motor DOL Starter Nos 5 8,600 43,000
e 10HP Motor Star delta Starter Nos 1 9,800 9,800
f 20HP Motor Star delta Starter Nos 1 14,000 14,000
g 25HP Motor Star delta Starter Nos 1 14,800 14,800
A TOTAL FOR PANELS / MCB DB'S / SWITCHGEARS 14,261,280
B EARTHING / PITS / L.A.
Chemical maintenance free earthing pits , high condivity carbon based
backfill compound ,18-25 mm dia 3 mts long ,high tensil low carbon steel
rod conductor with molecurly bonded 250 micron copper or clad copper
1 on the outer surface with polyplastic earth pit chamber.[extra earth pits to Nos 54 18,000 972,000
be added if required to form a grid to reduce resistivity ](suggested make
Jef Techno or equivalent) PSS-8,
LA-8,DG-20,LV - 2, BODY-10,AV-2,HT-4,

Conventional earthing pit system with 600 x 600 x 3mm copper plate , in
to 3 mts deep excavated earth , 2'' alterante layers of salt, charcoal and
2 earth, watering pipe, heavy duty chamber,all nit bolts to be in stainless Nos - 12,000 -
steel, copper braising for jointing of conductors to plates etc to be
complete in all respects and standards
3 S/F of 25 x 3 mm bare flat strip G.I. earthing Mts - 125 -
4 S/F of 25 x 6 mm bare flat strip G.I. earthing Mts - 240 -
5 S/F of 32 x 3 mm bare flat strip G.I. earthing Mts - 285 -
6 S/F of 32 x 6 mm bare flat strip G.I. Earthing Mts - 450 -
7 S/F of 50 x 3 mm bare flat strip G.I. earthing Mts - 240 -
8 S/F of 50 x 6 mm bare flat strip G.I. earthing Mts - 490 -
9 S/F of 50 x 10 mm bare flat strip G.I. earthing Mts - 590 -
10 S/F of 65 x 10 mm bare flat strip G.I. earthing Mts - 650 -
11 S/F of bare 12 swg GI earth Mts - 20 -
12 S/F of bare 8 swg GI earth Mts - 30 -
13 S/F of copper earth bus bar 50 x 6 mm G.I. with ms enclosure Nos 4 6,500 26,000
14 S/F of 25 x 3 mm bare flat strip copper earthing Mts 2,000 490 980,000
15 S/F of 50 x 3 mm bare flat strip copper earthing Mts 550 885 486,750
16 S/F of 50 x 6 mm bare flat strip copper earthing Mts 200 1,800 360,000
17 S/F of bare 8 swg CU earth Mts 1,000 65 65,000
18 S/F of copper earth bus bar 25 x 6 copper with ms enclosure Nos 6 5,500 33,000
19 S/F of 6 sqmm x1c pvc insulated green color coded wire conduit Mts 50 65 3,250
20 S/F of 10 sqmm x1c pvc insulated green color coded wire conduit Mts 50 120 6,000
21 S/F of 16 sqmm x1c pvc insulated green color coded wire conduit Mts 25 175 4,375
22 S/F of 25 sqmm x1c pvc insulated green color coded wire conduit Mts 25 265 6,625
25 LIGHTINING ARRESTOR
Supply of level one protection Early Streamer Emission type Lightning
Protection complete with the Lightning Air Terminal - Configured as a
Spheroid which is comprised of separate electrically isolated 4panels
surrounding an Earthened Central Finial. The upper section of the central
finial shall be rated to withstand 200KA. The Insulation material used to
electrically isolate the panels shall be comprised of base polymer which
shall provide high Ozone & UV resistance with a di-electric strength of 24-
38KV/mm & ESE terminal shall withstand a minimum Switching Impulse
Voltage of 500KV tested as per NFC 17-102 & IEC Test Standard - IEC60-
1:1989. Design to co ordinated with the supplying vendor . Supply of
Mounting Pole. The mounting pole used to support the lightning air
terminal shall either be a supporting mast or Free standing mast at a
a minimum height of 5 metres above to be area protected or as per required Nos 4 200,000 800,000
level of protection. The mounting pole and supports shall be securely
fixed with brackets and guy wires where it is required to withstand
maximum locally recorded wind velocity. Mounting Pole shall be non
corrosive. The down conductor shall pass through the centre of the pole
for the entire length of the pole. Supporting Guyed Mast : 5Mtr. .
Lightning Strike recorder( 6 digits Display) of non-resettable type in an IP
67 enclosure with the minimum sensitivity of 1500 A & maximum capacity
of 220 KA ( 8/20 micro sec wave form) tested as per IEC 60-1:189.
( these specks are considering a specific make, equivalent can be used)

1c X 70 SQMM , pvc insulated , multistranded, copper conductor in pvc


b Mts 200 850 170,000
conduits
SUB TOTAL FOR EARTHING / PITS / L.A. 3,913,000
C CABLING / WIRING & TERMINATIONS

SITC of Armoured aluminium , XLPE, cable to be laid in trenches , cable


trays ,walls , floor , ceiling , with labelling as required ,with saddle ,
c1 spacers , well dressed manner as required as per site conditions &
consultant / architect .All cables shall be XLPE with outer sheath FRLS .
Multistranded Wires shall be pvc insulated FRLS .

Aluminium Armoured cables


1 400 sqmm x 4 c Mts 600 1,785 1,071,000
2 300 sqmm x 4 c Mts 1,900 1,405 2,669,500
3 240 sqmm x 4 c Mts 450 1,165 524,250
4 185 sqmm x 4 c Mts 300 915 274,500
5 150 sqmm x 4 c Mts 1,600 735 1,176,000
6 120 sqmm x 4 c Mts 650 600 390,000
7 95 sqmm x 4 c Mts - 490 -
8 70 sqmm x 4 c Mts 1,625 400 650,000
9 50 sqmm x 4 c Mts 1,550 295 457,250
10 35 sqmm x 3 c Mts 225 185 162,800
11 35 sqmm x 4 c Mts 880 230
12 25 sqmm x 3 c Mts 100 155 15,500
13 25 sqmm x 4 c Mts 6,800 190 1,292,000
14 16 sqmm x 3 c Mts 250 115 28,750
15 16 sqmm x 4 c Mts 15,000 140 2,100,000
SITC of Armoured copper , XLPE, cable to be laid in trenches , cable
trays ,walls , floor , ceiling , with labelling as required ,with saddle ,
c2 spacers , well dressed manner as required as per site conditions &
consultant / architect .All cables shall be XLPE with outer sheath FRLS .
Multistranded Wires shall be pvc insulated FRLS .
1 10 sqmm x 3 c Mts - 340 -
2 10sqmm x 4 c Mts - 430 -
3 6sqmm x 3 c Mts - 210 -
4 6sqmm x 4 c Mts 550 270 148,500
5 4sqmm x 3 c Mts - 155 -
6 4sqmm x 4 c Mts 2,800 195 546,000
7 2.5sqmm x 3 c Mts - 115 -
8 2.5sqmm x 4 c Mts 3,900 140 546,000
9 6sqmm x 1 c Mts - 60 -
10 10sqmm x 1 c Mts - 100 -
11 16sqmm x 1 c Mts - 165 -
12 25sqmm x 1 c Mts - 265 -
13 50sqmm x 1 c Mts - 520 -
14 70sqmm x 1 c Mts - 720 -
15 95sqmm x 1 c Mts - 995 -
16 120sqmm x 1 c Mts 650 1,270 825,500
17 240sqmm x 1 c Mts 850 2,530 2,150,500
Terminations with double commpression
1 400 sqmm x 4 c Nos 7,900 -
2 300 sqmm x 4 c Nos 6,600 -
3 240 sqmm x 4 c Nos 5,200 -
4 185 sqmm x 4 c Nos 4,300 -
5 150 sqmm x 4 c Nos 3,400 -
6 120 sqmm x 4 c Nos 2,800 -
7 95 sqmm x 4 c Nos 2,400 -
8 70 sqmm x 4 c Nos 2,100 -
9 50 sqmm x 4 c Nos 1,750 -
10 35 sqmm x 4 c Nos 1,350 -
11 25 sqmm x 3 c Nos 1,200 -
12 25 sqmm x 4 c Nos 1,200 -
13 16 sqmm x 3 c Nos 900 -
14 16 sqmm x 4 c Nos 900 -
15 10 sqmm x 3 c Nos 850 -
16 10sqmm x 4 c Nos 850 -
17 6sqmm x 3 c Nos - 600 -
18 6sqmm x 4 c Nos 38 600 22,800
19 4sqmm x 3 c Nos - 480 -
20 4sqmm x 4 c Nos 196 480 94,080
21 2.5sqmm x 3 c Nos - 450 -
22 2.5sqmm x 4 c Nos - 450 -
23 6sqmm x 1 c Nos - 450 -
24 10sqmm x 1 c Nos - 450 -
25 16sqmm x 1 c Nos - 450 -
26 25sqmm x 1 c Nos - 450 -
27 50sqmm x 1 c Nos - 425 -
28 70sqmm x 1 c Nos - 425 -
29 95sqmm x 1 c Nos - 550 -
30 120sqmm x 1 c Nos 96 700 67,200
31 240sqmm x 1 c Nos 72 1,200 86,400
TOTAL FOR CABLING / WIRING & TERMINATIONS 15,298,530
D LIFT ROOM & SHAFT WIRING
1 way Light point wiring with 1.5Sqmm X 3 wire with Conduits from MCB
1 DB as required for internal lift room wiring along with modular switch Pts 16 1,200 19,200
boards
Secondary Light point wiring with 1.5Sqmm X 3 wire with Conduits
2 Pts 32 650 20,800
looped from above primary point wiring
S/F of 2.5 sqmm x 3 wire circuit in conduits for power point primary wiring
3 Pts 8 1,000 8,000
in lift room
S/F of 2.5 sqmm x 3 wire circuit in conduits for power point secondary
4 Pts 8 550 4,400
wiring in lift room
S/F of 4 sqmm x 3 wire circuit in conduits for power point primary wiring in
5 Pts 8 1,500 12,000
lift room
S/F of 4 sqmm x 3 wire circuit in conduits for power point secondary wiring
6 Pts 8 750 6,000
in lift room
7 S/F of 6 a switch socket with face plate and enclosure Nos 16 650 10,400
S/F of 13 a universal multi socket with switch with face plate and
8 Nos 56 1,100 61,600
enclosure
9 Supply and Fixing of bulkhead fitting with LED lamps in lift shaft. Nos 40 1,250 50,000
10 S/F of 20 watts batten type LED light fixtures Nos 20 750 15,000
S/F of 4 sqmm x 3 c copper armoured cable in shaft for shaft utility power
11 Mts 200 155 31,000
points
S/F of terminations to 4 sqmm x 3 c copper armoured cable with double
12 Nos 80 480 38,400
compression brass glands

TOTAL LIFT ROOM AND SHAFT WIRING 276,800


E TEMPORARY POWER ARRANGEMENT FOR CONSTRUCTION

S/F of 70 sqmm x 4 c copper armoured cable with terminations ( main


1 Mts 150 2,750 412,500
cable )
MCCB DB consisting of the following
250A 36 KA MCCB --- 1 nos
2 C 63 a 3 p mcb -- 6 nos Nos 1 49,500 49,500
C 40 a 3 p mcb -- 6 nos
12 WAY VTPN MCCB DB, IP43 - 1nos
S/F of 16 sqmm x 4 c copper armoured cable ( per area cable from mccb
3 Mts 500 620 310,000
db )
S/F of 20 a 3 pin and earth metal clad plug socket with spmcb and metal
4 Nos 20 1,750 35,000
enclosure
S/F of 13 a universal multi socket with switch with face plate and
5 Nos 150 1,100 165,000
enclosure
MCB DB consisting of the following
63 a 4 p mcb -- 1nos
63 a 2 p 100ma rccb --- 3 nos
6 Nos 4 23,500 94,000
25 a spmcb ---------- 18 nos
25 a 4 p mcb ---- 1nos
8 way tpn db, ip43. --- 1nos
S/F of 1.5 SQMMX 3 C pvc sheathed and pvc insulated , multistranded
7 Mts 1,200 65 78,000
copper cable for interconnections
S/F of 2.5 SQMMX 3 C pvc sheathed and pvc insulated , multistranded
8 Mts 1,200 100 120,000
copper cable for interconnections
9 S/F of 1.5 sqmm x 3 c submersible cable Mts 500 75 37,500
10 S/F of 2.5 sqmm x 3 c submersible cable Mts 500 110 55,000
11 S/F of 4.0 sqmm x 3 c submersible cable Mts 200 165 33,000
12 S.F of 2.5 sqmm x 3c copper armoured cable Mts 300 115 34,500
13 S.F of 4 sqmm x 3c copper armoured cable Mts 200 155 31,000
14 S/F of 1 x 20 w LED batten light fixture Nos 200 650 130,000
15 S/F of 100 w LED flood light IP65 Nos 50 6,500 325,000
TOTAL FOR TEMPORARY POWER ARRANGEMENT FOR CONSTRUCTION 1,910,000
FIXING LIGHT FIXTURES [ owner supplied unless otherwise
F
mentioned]
Fixing of owner supplied light with all connectors , connecting wires,
required supports , brackets , terminations , suspension arrangements
etc. To be picked up from stores and installed at the required location
.This item also includes some basic items to be supplied and installed.
INTERNAL LIGHTING
1 recess / surface spots of all types Nos 325 100 32,500
2 LED profile with required drivers at specific length Mts 2,300 75 172,500
3 Linear light ptofile Mts 750 100 75,000
4 suspendant lights Nos 150 200 30,000
5 supply and fixing 20 W LED batten type tube lights for service areas etc Nos 100 550 55,000
6 supply and fixing 48'' ceiling fan , 3 leaf white colour for service areas etc Nos 25 1,650 41,250
7 S/F of ceiling fan hooks with dual anchor expansion fastners Nos 25 150 3,750
EXTERIOR LIGHTING
8 Exterior spike lights Nos 400 125 50,000
9 Exterior post top lights average 3 mts high Nos 250 1,200 300,000
External linear LED profile for floor, benches etc including fixing of drivers
10 Mts 2,000 100 200,000
as required by vendor / architect
11 External wall recess small LED fixture Nos 30 125 3,750
12 External wall recess big LED fixture Nos 50 125 6,250
13 External underwater fountain light Nos 60 150 9,000
14 External Flood Lights Nos 50 150 7,500

TOTAL FOR FIXING LIGHT FIXTURES 986,500

G STAIRCASE WIRING

1 way Light point wiring with all circuits from MCB DB and modular
1 switches as required for staircase wiring - for primary points using 1.5 Pts 8 1,800 14,400
sqmm x 3 wire from db / switch boards.To be connected to emergency db

same as above - for secondary points using 1.5 sqmm x 3 wire from db /
2 Pts 40 850 34,000
switch boards.To be connected to emergency db
TOTAL FOR STAIRCASE WIRING 48,400

LIGHTING & POWER WIRING FOR TOILETS , COMMON , BALCONY


H
AREAS ETC

SITC of light / fan point / circuit wiring direct to mcb db or switch board as
mentioned in respective drawings including circuits from switch board &
lights to mcb db with 1.5 / 2.5 / 4 sqmm or as mentioned with FRLS
copper wires in conduits with all terminations in copper cable sockets/
lugs, using modular switch accessories including chasing & recementing
for recess boxes & conduiting as required. Modular switches for quote to
be considered. Wiring to be done in if already laid ceiling cable trays
and to be extended with conduits to the exact location of point. Switch
board to switch board looping & sub circuit from DB shall be 2.5 sqmm x
3 wire. Switch board to primary & secondary point wiring shall be 1.5
sqmm x 3 wire, DB to direct primary & secondary point wiring shall be
2.5 sqmm x 3 wire

Primary point wiring in conduits with 1.5 sqmm x 3 wire controlled through
1 switch board including ciruit to DB with 2.5 sqmm x 3 wire .Shall include Pts 225 1,250 281,250
modular switches
Secondary point wiring in conduits with 1.5 sqmm x 3 wire looped to the
2 Pts 400 750 300,000
above primary point wiring
3 S/F of ceiling fan step regulator with face plate and enclosure. Nos 25 1,200 30,000
Primary point wiring in conduits with 2.5 sqmm x 3 wire controlled directly
4 Pts 60 2,250 135,000
through MCB DB .
Secondary point wiring in conduits with 2.5 sqmm x 3 wire looped to the
5 Pts 225 750 168,750
above primary point wiring
6 S/F of 6 a switch socket with face plate and enclosure Nos 70 650 45,500
S/F of 13 a universal multi socket with switch with face plate and
7 Nos 120 1,100 132,000
enclosure
S/F of 2.5 sqmm x 3 wire circuits in conduits for power wiring from DB to
8 Pts 20 2,500 50,000
socket outlets for primary power points
S/F of 2.5 sqmm x 3 wire circuits in conduits for power wiring from DB to
9 Pts 40 1,500 60,000
socket outlets for secondary power pints looped to primary points
S/F of 4 sqmm x 3 wire circuits in conduits for power wiring from DB to
10 Pts 40 3,400 136,000
socket outlets for primary power points
S/F of 4 sqmm x 3 wire circuits in conduits for power wiring from DB to
11 Pts 80 2,100 168,000
socket outlets for secondary power points looped to primary points
SUB TOTAL FOR LIGHTING & POWER WIRING FOR TOILETS ,
12 1,506,500
COMMON , BALCONY AREAS ETC

I MAIN WORSHIP AREA LIGHTING WIRING

S/F of 1.5 sqmm x 3 wire circuits in conduits for lighting wiring from DB to
1 Mts 100 125 12,500
light points
S/F of 2.5 sqmm x 3 wire circuits in conduits for lighting wiring from DB to
2 Mts 9,800 155 1,519,000
light points
S/F of 4 sqmm x 3 wire circuits in conduits for lighting wiring from DB to
3 Mts 1,000 185 185,000
light points
S/F of 2 core x 1.5 sqmm copper multistranded , pvc insulated , pvc
4 Mts 100 60 6,000
sheathed
S/F of 3 core x 1.5 sqmm copper multistranded , pvc insulated , pvc
5 Mts 100 65 6,500
sheathed
S/F of 2 core x 2.5 sqmm copper multistranded , pvc insulated , pvc
6 Mts 100 90 9,000
sheathed
S/F of 3 core x 2.5 sqmm copper multistranded , pvc insulated , pvc
7 Mts 100 100 10,000
sheathed

SUB TOTAL FOR MAIN WORSHIP AREA LIGHTING WIRING 1,748,000

J MAIN WORSHIP AREA POWER WIRING

1 S/F of 6 a switch socket with face plate and enclosure Nos 25 650 16,250
S/F of 13 a universal multi socket with switch with face plate and
2 Nos 80 1,100 88,000
enclosure
S/F of 2.5 sqmm x 3 wire circuits in conduits for power wiring from DB to
3 Mts 200 155 31,000
socket outlets for power points
S/F of 4 sqmm x 3 wire circuits in conduits for power wiring from DB to
4 Mts 1,500 185 277,500
socket outlets for power points
S/F of 2.5 sqmm x 5 wire circuits in conduits for power wiring from DB to
5 Mts 200 265 53,000
socket outlets for power points
S/F of 4 sqmm x 5 wire circuits in conduits for power wiring from DB to
6 Mts 200 310 62,000
socket outlets for power points
7 20 A 4 pin and earth metal clad plug socket with 4 pole mcb in enclosure Nos 10 5,500 55,000
8 32 A 4 pin and earth metal clad plug socket with 4 pole mcb in enclosure Nos 10 6,500 65,000

SUB TOTAL FOR MAIN WORSHIP AREA POWER WIRING 647,750

K EXTERNAL / LAND SCAPING, FAÇADE LIGHTING & POWER

S/F of building external lighting to be done in armoured cabling with IP65


terminating enclosures. Cables to be buried in ground at least 700 mm
deep. All water proof JB shall also be buried in ground or as directed.
S/F of 2.5 sqmm x 3 c copper armoured XPLE cable to be fixed on
1 Mts 15,000 115 1,725,000
exterior walls for lighting and power etc
S/F of 2.5 sqmm x 4 c copper armoured XPLE cable to be fixed on
2 Mts 100 140 14,000
exterior walls for lighting and power etc
S/F of 4 sqmm x 3 c copper armoured XPLE cable to be fixed on exterior
3 Mts 5,000 155 775,000
walls for lighting and power etc
S/F of 4 sqmm x 4 c copper armoured XPLE cable to be fixed on exterior
4 Mts 100 195 19,500
walls for lighting and power etc
SITC of IP66 cable junction box for outdoor application. Connectors for
5 terminations to be included within the box as per average dimensions
mentioned below
a 88 mm x 88 mm x 53 mm Nos 250 575 143,750
b 98 mm x 98 mm x 61 mm Nos 225 685 154,125
c 139 mm x 119 mm x 70 mm Nos 150 1,050 157,500
d 167 mm x 125 mm x 82 mm Nos 125 1,350 168,750
e 200 mmx 160 mm x 98 mm Nos 20 2,250 45,000
S/F terminations to cable with water proof cable compression glands as
6
follows
a 2-6mm Nos 250 130 32,500
b 3-6.5mm Nos 550 150 82,500
c 4-8mm Nos 650 175 113,750
d 5-10mm Nos 750 250 187,500
e 6-12mm Nos 300 300 90,000
f 10-14mm Nos 100 390 39,000
S/F of 1.5 sqmm x 3 c pvc insulated & pvc sheathed cable from
7 Mts 500 65 32,500
terminating enclosure to light fixture with all terminations.
S/F of 2.5 sqmm x 3 c pvc insulated & pvc sheathed cable from
8 Mts 650 100 65,000
terminating enclosure to light fixture with all terminations.
S/F of 4sqmm x 3 c pvc insulated & pvc sheathed cable from terminating
9 Mts 200 150 30,000
enclosure to light fixture with all terminations.
S/F of 1 mts long , 25mm dia GI pipe earthing for individual pole lights
with 2 nos of 8 swg bare GI earth connected to poles earth terminal. To
10 Nos 340 850 289,000
buried in to soft ground about 2 mts deep to achive good earth
connectivity
11 S/F of 16 a / 6a switch socket in outdoor application IP55 enclosure Nos 25 1,500 37,500
12 S/F of bare GI, 8 SWG , earth condutor Mts 1,000 25 25,000
13 S/F of bare GI, 12 SWG , earth condutor Mts 1,000 20 20,000

SUB TOTAL FOR EXTERNAL / LAND SCAPING, FAÇADE LIGHTING &


4,246,875
POWER
L TRUNKING / CABLE TRAYS / CONDUITS

S/F of ladder type , bolted type ,cable tray ,with hanger support , tee,
1 bends, coupler ,cross pieces ,reducers ,Z section all accessories etc
complete in all respects . Pre galvanized .
a 1000mm wide x 50mm deep Mts 5 1,250 6,250
b 750mm wide x 50 mm deep Mts 5 1,000 5,000
c 600mm wide x 50 mm deep Mts 5 950 4,750
d 450mm wide x 50 mm deep Mts 5 850 4,250
e 300mm wide x 40 mm deep Mts 5 740 3,700
f 200mm wide x 25 mm deep Mts - 650 -
g 150mm wide x 25 mm deep Mts - 600 -
h 100mm wide x 25 mm deep Mts - 550 -
S/F of perforated cable trays, without cover,16 SWG, bolted type ,cable
2 tray ,with hanger support , tee, bends, coupler ,cross pieces ,reducers ,Z
section all accessories etc complete in all respects . Pre galvanized .
a 1000mm wide x 50mm deep Mts 200 2,200 440,000
b 750mm wide x 50 mm deep Mts 400 1,800 720,000
c 600mm wide x 50 mm deep Mts 1,600 1,500 2,400,000
d 450mm wide x 50 mm deep Mts 400 1,100 440,000
e 300mm wide x 40 mm deep Mts 700 900 630,000
f 200mm wide x 25 mm deep Mts 400 550 220,000
g 150mm wide x 25 mm deep Mts 400 450 180,000
h 100mm wide x 25 mm deep Mts 400 400 160,000
S/F of trunking , with cover,16 SWG, bolted type , ,with hanger support ,
3 tee, bends, coupler ,cross pieces ,reducers ,Z section all accessories etc
complete in all respects . Pre galvanized .
a 600mm wide Mts 10 1,600 16,000
b 450mm wide Mts 10 1,200 12,000
c 300mm wide Mts 10 1,000 10,000
d 200mm wide Mts 10 650 6,500
e 150mm wide Mts 10 550 5,500
f 100 mm wide Mts 10 500 5,000
S/F of ALU 16 swg box section to be laid on floor with all excavation ,
recementing & refinishing civil works to make good in line with the
3
existing floor level . Respective junction box to be fabricated in 16 swg GI
sheet with cut out as required for terminating the box sections
a 65 x 40 mm Mts 50 550 27,500
b 100 x 40 mm Mts 35 765 26,775
c 150 x 150 x 50 mm MS Junction box with cover & cut outs Nos 10 350 3,500
d 200 x 150 x 50 mm MS Junction box with cover & cut outs Nos 5 450 2,250
e 250 x 150 x 50 mm MS Junction box with cover & cut outs Nos 5 600 3,000
S/F of heavy duty PVC conduits to be laid on floor with all excavation ,
recementing & refinishing civil works to make good in line with the
existing floor level . Respective junction box to be fabricated in 16 swg GI
4
sheet with cut out as required for terminating the box sections. This item
to be used other all the above items where pvc conduits are already
included
a 1 x 25mm Mts 700 65 45,500
b 1 x 32mm Mts 600 75 45,000
c 1 x 40mm Mts 500 95 47,500
d 1 x 50mm Mts 500 120 60,000
e 150 x 150 x 50 mm MS Junction box with cover & cut outs Nos 20 350 7,000
f 200 x 200 x 50 mm MS Junction box with cover & cut outs Nos 50 450 22,500
g 250 x 250 x 50 mm MS Junction box with cover & cut outs Nos 50 650 32,500
h 300 x 300 x 50 mm MS Junction box with cover & cut outs Nos 10 850 8,500
i 400 x 400 x 50 mm MS Junction box with cover & cut outs Nos 5 1,150 5,750
S/F of heavy duty UPVC trunking with cover and all accessories to
5
complete in all respects
a 75 x 75 mm Mts 80 590 47,200
b 100 x 75 mm Mts 70 735 51,450
c 100 x 100 mm Mts 60 875 52,500

SUB TOTAL TRUNKING / CABLE TRAYS / CONDUITS 5,757,375

M MISC ITEMS
Supplying & Laying of rubber matting of 6 mm thickness of required length
1 and breadth with good insulation property for 33 kV. sq mts 30 1,200 36,000

Supply & Installation of floor mounting stand approximately 1500mm long,


for keeping 4Nos of FIRE buckets, 900 mm in height frame made out of
2 30 x 30 x 6mm angle iron with cross supports, welded with 4 hooks and set 6 12,500 75,000
duly painted with one coat of red lead and two coats of silver paint.

Providing round bottom FIRE bucket of 9 Liters capacity made out of 24


gauge GI sheet with extra handle at bottom duly painted white inside and
3 red outside with FIRE Mark, filled with dry sand on provided sand/wall Nos 4 900 3,600
hook.

Supplying and erecting wall hook 225 mm projection for keeping fire
4 buckets, made out of 15mm dia M.S Rod grouted in wall to a depth of Nos 16 550 8,800
minimum 150mm.

Supply a pair of duly tested rubber hand gloves suitable for working on
5 11kV grade supply. each 4 900 3,600

Providing printed instruction chart for treating persons suffering from


6 electric shock, in English, Hindi & Local language and duly framed with each 4 1,500 6,000
front glasses.(Each set consist of 1 printed chart of all above languages)
7 Supplying and standard first aid box with all the standard contents. Nos 12 3,500 42,000
CO2 fire extinguisher, 5Kgs, of zenith,fire fight,minimax make or
8 equivalent in HT metering kiosk room Nos 4 8,500 34,000

Supply, Fixing of Danger Boards for HT metering room, Substation room,


having size not less than 250mm x 250mm x 2mm thick marked with red
9 colour danger sign & supply voltage indication in white colour. Complete Job 6 550 3,300
as per clients/consultants approval.

Laisioning work for getting permanent power for entire premises for 2 nos
x 1500 kva from local supply electricity board, this also includes liasioning
work with all other related authorities, submission of application forms to
get sanctioned Load as per load sheet, Charges of Electrical Inspectors
approval, Local authorities approval, Testing of Equipment at site etc. The
10 charges required to pay legal fees shall be scope of electrical contractor & Job 1 600,000 600,000
the same will get reimbursed as per actual fees only after production of
original receipt from electricity board duly stamped & signed by electricity
board authority.

SUB TOTAL FOR MISC ITEMS 812,300

SUMMARY TOTAL
A SUB TOTAL FOR PANELS / MCB DB'S / SWITCHGEARS 14,261,280
B SUB TOTAL FOR EARTHING / PITS / L.A. 3,913,000
C SUB TOTAL FOR CABLING / WIRING & TERMINATIONS 15,298,530
D SUB TOTAL LIFT ROOM AND SHAFT WIRING 276,800
TOTAL FOR TEMPORARY POWER ARRANGEMENT FOR
E 1,910,000
CONSTRUCTION
F SUB TOTAL FOR FIXING LIGHT FIXTURES 986,500
G SUB TOTAL FOR STAIRCASE WIRING 48,400
SUB TOTAL FOR LIGHTING & POWER WIRING FOR TOILETS ,
H 1,506,500
COMMON , BALCONY AREAS ETC
I SUB TOTAL FOR MAIN WORSHIP AREA LIGHTING WIRING 1,748,000
J SUB TOTAL FOR MAIN WORSHIP AREA POWER WIRING 647,750
SUB TOTAL FOR EXTERNAL / LAND SCAPING, FAÇADE LIGHTING &
K 4,246,875
POWER
L SUB TOTAL TRUNKING / CABLE TRAYS / CONDUITS 5,757,375
M SUB TOTAL FOR MISC ITEMS 812,300
SUB TOTAL 51,413,310

EXCLUSIONS
1 IT active components
2 service providers for internet, TV etc
3 light fixtures , façade lights , gysers, exhaust
phone hand sets , TV ,electrical and electronic gadgets , coffee
4
makers, minibar ,etc
5 Lifts , stack park, EPBAX , Racks, Switches
6 scanner, x ray, boom barrier, body scanner, gaurd tour management
etc
7 civil works and foundation for MEP
8 AV system
9 Automation
10 civil Trenches

Das könnte Ihnen auch gefallen