Sie sind auf Seite 1von 12

I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B

FEKALNA KANALIZACIJA I VODOVOD U NOGOSTUPU ŽUPANIJSKE CESTE Z-6238,


DIONICA CAVTAT- MEČAJAC
Dio građevine:
FEKALNA KANALIZACIJA I VODOVOD
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

6. TLAČNA PROBA

INVESTITOR: KONAVOSKO KOMUNALNO DRUŠTVO


d.o.o., 20 213 Čilipi, Bistroće 70

NAZIV GRAĐEVINE: FEKALNA KANALIZACIJA I VODOVOD U NOGOSTUPU


ŽUPANIJSKE CESTE Z-6238, DIONICA CAVTAT-MEČAJAC

DIO GRAĐEVINE: FEKALNA KANALIZACIJA I VODOVOD

ZAJEDNIČKA OZNAKA: V1-7405

OZNAKA PROJEKTA: V1-7405/1

OZNAKA KNJIGE: 1

STRUKOVNA ODREDNICA: GRAĐEVINSKI PROJEKT


RAZINA OBRADE: PROJEKT IZVANREDNOG ODRŽAVANJA
PROJEKTANT: Edgard Roudnicky, dipl. ing. građ.
SURADNIK: Luka Burnać, mag. ing. aedif.

MJESTO I DATUM IZRADE: Zagreb, veljača 2016.

Tlačna proba
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

1 OPĆENITO

Tlačne cjevovode smije polagati samo stručni kadar poduzeća s iskustvom u tim radovima i s ovlaštenjem
za te radove.

Za svaki se vod zahtijeva, da svi njegovi dijelovi - tzv. cijevlje (tj. cijevi, fazoni i armature) - budu dovoljno
čvrsti i tako sastavljeni da ne dođe do nepoželjnih pomaka i da gotov vod bude potpuno nepropustan za
vodu. Nedovoljna čvrstoća i pomaci uzrokuju različite smetnje i štete, kao i slom cjevovoda. Voda koja
pod tlakom istječe na propusnim mjestima cijevi ili spoja pa ma kako neznatne bile te propusnosti u
početku, proširuje s vremenom sve više ta oštećena mjesta, a pokreće i korozivno razaranje.

Te nepoželjne pojave izbjegavamo time što sve vodove na kraju izvedbe ispitamo na čvrstoću i
nepropusnost i uklonimo sve uzroke šteta.

Nepropusnost i čvrstoću obično ispitujemo zajedno, ali se mogu ispitati i svaka za se. Tako je npr.
zavarene vodove pogodno ispitati na nepropusnost komprimiranim zrakom, a na čvrstoću vodom.

2 VRSTE TLAČNIH PROBA

Tlačna proba se može provesti:


- Višesatnim ili višednevnim ispitivanjem sa najvećim tlakom koji bi mogao nastati u pogonu. Taj
postupak dostaje kod manje važnih i kratkih vodova.
- Kraćom tlačnom probom, a probnim tlakom većim od najvećeg u pogonu. To je redovni postupak.

Tlačna proba se obavlja u slijedećim fazama:


- punjenje cjevovoda
- prethodno ispitivanje
- glavno ispitivanje
- skupno (zajedničko) ispitivanje

Pogonski tlak, trajanje probe i način ispitivanja mora odrediti naručitelj u opisu radova.

3 PROVEDBA TLAČNE PROBE

3.1 Sapinjanje i usidrenje


Prije punjenja voda vodom treba dovoljno učvrstiti i usidriti i krajeve odsjeka ispitivanja i sve horizontalne i
vertikalne zavoje kao i ogranke da bi izbjegli pomake koji su opasni za nepropusnost spojeva tijekom
ispitivanja i kasnijeg pogona. Učvršćenja i usidrenja treba dimenzionirati za probni tlak, a osloncem na
dopustivo opterećenja tla na dotičnom mjestu.
Učvršćenja krajeva ne smijemo ukloniti prije nego što smo tlak spustili do nule.

3.2 Punjenje vode


Doprema, po mogućnosti besprijekorne vode, vrši se prema mjesnim prilikama. Vod punimo tako pažljivo
da ga potpuno ispunimo vodom, a bez opasnih udara u vezi s istiskivanjem zraka.
Nakupine zraka u cjevovodu ugrožavaju cjevovod, dovode do sloma voda, a ometaju i tlačnu probu,
naročito kod većih temperaturnih promjena u tijeku probe.
Najbolje je vod puniti s njegove najniže točke i to toliko polako da sav zrak stigne mirno izaći kroz ispuste
zraka, a ti moraju biti potrebno otvoreni. Ako brtve primijenjenih spojeva upijaju vodu potrebno je to
vrijeme i za njihovo prožimanje vodom.

Tlačna proba 1
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

Pogodan dotok je za punjenje cjevovoda:

 Dotok  Dotok  Dotok


(mm) (l/s) (mm) (l/s) (mm) (l/s)
50 0.1 250 2.0 700 15.4
65 0.1 300 2.8 800 20.1
80 0.2 350 3.8 900 25.4
100 0.3 400 5.0 1000 31.4
125 0.5 450 6.5 1100 38.0
150 0.7 500 7.8 1200 45.2
200 1.3 600 11.3 1400 61.6

3.3 Zaštita protiv upliva temperature


Zbog zaštite od temperaturnih upliva moramo vod, naročito na spojevima, za vrućina zasjeniti.

3.4 Postavljanje tlačne pumpe


Tlačnu pumpu treba tako postaviti da ne dođe do nesreća.

3.5 Prethodno ispitivanje


Izvođač mora naručioca pravovremeno obavijestiti kada će vršiti predprobu.

Nakon završenog punjenja cjevovoda, počinje predproba, podizanjem tlaka u cjevovodu na ispitni tlak od
13, odnosno, 20 bara.
Smatra se da je predproba uspješno obavljena, ako se tijekom 12 satnog ispitivanja ne primijeti
propuštanje vode na spojevima i cijevima.
U slučaju da se primijeti propuštanje vode, ispitivanje se obustavlja, voda ispušta toliko, da loše mjesto
ostane suho, nedostatak se otklanja i ispitivanje se u potpunosti ponavlja.
Jedan dan nakon punjenja, izvođač provede predprobu najvećim tlakom koji bi mogao nastati u pogonu.
Trajanje predprobe (30 minuta, 6 ili 24 sati – ovisno o promjeru) određeno je u poglavlju 3.9. Na početku
tlačenja vode treba treba cjevovod još jednom dobro isprati, i to pod tlakom, a zbog boljeg odzračenja.
Ako se već kod pogonskog tlaka pokažu pomaci ili propusnosti, treba tlak, po mogućnosti, povećati do
“probnog tlaka” da bi lakše ocijenili grješke pri izvedbi. Ako naručilac dopusti popravak spojeva bez
obnavljanja, ne treba cjevovod isprazniti nego samo otpustiti tlak.

3.6 Glavno ispitivanje


Ako se kod pretprobe ne pojavi pomaci ni vidljivo istjecanje ili kapanje kroz stijenke cijevi ili na spojevima
(kod zasuna, pipa, ogranaka ili sl.) treba, na traženje naručioca, odmah provesti probu. Kod naglavnih
spojeva i spojnica treba pregledati svaki posebno.
Uvjet za glavno ispitivanje je uspješno obavljeno predhodno ispitivanje. Ono se obavlja nastavno na
prethodno ispitivanje, bez smanjivanja tlaka. Tlak kod glavnog ispitivanja je isti kao kod prethodnog
ispitivanja, tj. 1,3 puta veći od nominalnog tlaka. Trajanje ispitivanja je 30 minuta za svakih započetih 100
m duljine dionice, ali ne manje od 2 sata , bez obzira na duljinu ispitne dionice.

Tijekom glavnog ispitivanja se ne smije dodavati voda u cjevovod.


Glavno ispitivanje je zadovoljavajuće ako tlak u cjevovodu tijekom ispitivanja ne padne više 0,1 bar za
svakih započetih 100 m cjevovoda, i ako se prilikom pregleda cjevovoda ne ustanovi propuštanje vode
niti nepravilne promjene na cjevovodu. Usidrena mjesta se ne smiju pomaknuti iz prvobitnog položaja.

Tlačna proba 2
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

U slučaju da se tijekom glavnog ispitivanja primijete nedostaci na cjevovodu, ispitivanje treba


prekinuti,vodu ispustiti do te mjere da loša mjesta ostanu bez vode, nedostatke ukloniti i kompletno
ispitivanje ( i prethodno i glavno ) ponoviti.

3.7 Skupno ispitivanje


Nakon završenog glavnog ispitivanja pojedinih cjevovoda, one se međusobno spoje. Skupno ispitivanje
se provodi radi kontrole spojeva ispitanih dionica, i radi toga ovi spojevi ne smiju biti zatrpani.
Skupno ispitivanje se izvodi i radi provjere da tijekom zatrpavanja cjevovoda nije došlo do oštećenja ili
pomicanja, koja mogu rezultirati propuštanjem vode i padom tlaka.
Za skupno ispitivanje je dovoljno primijeniti nazivni tlak, a samo u posebnim okolnostima pogonski tlak.
Skupno ispitivanje traje 2 sata.
Ispitivanje zadovoljava, ako se na spojevima ispitnih dionica ne opazi propuštanje vode i ako se na
manometrima ne uoči pad tlaka.

3.8 Probni tlak


Probni tlak ne treba biti suviše velik, ali mora biti odabran ne prema redovnom opterećenju, nego prema
povišenom opterećenju voda koje može nastati u budućnosti i uz sva dodatna udarna naprezanja voda
koja u njemu mogu nastati djelovanjem automatskih zatvarača kod loma cjevovoda, prekid crpljenja
(isklop električne sklopke) i sl.
Prevelik tlak je štetan za spojeve, a naročito za naglavne spojeve, jer ih nepotrebno napreže pa može
djelovati i na nepropusnost. Nepotrebno velik tlak zahtijeva i skupa predimenzioniranja fazona,
sapinjanja, ukrućenja i usidrenja.
Kod dugih dovoda i glavnih vodova ne bi probni tlak, općenito, trebao biti veći od 5 bara povećanog
najvećeg pogonskog tlaka u budućnosti. Minimalni probni tlak je 10 (16) bara. Kod ispitivanja mreže treba
unatoč toga što normalni pogonski tlak općenito ne premašuje 8 bara ispitati kao i opskrbne vodove, zbog
teško ocjenjivih napona, u pravilu na tlak od 15, 17,5 ili 21 bara, već prema tome da li su rađeni za
nazivni tlak 10, 12,5 ili 16 bara.

3.9 Trajanje probe


Potrebno trajanje probe je ovisno o nazivnom promjeru cijevi, o važnosti voda i o dužini ispitivanog
odsjeka. Ono mora biti toliko da se pokaže i polagano puzanje cijevi zbog nedostatnog utvrđenja i
usidrenja, i istiskivanje loše izrađenih brtva kod sabirnih naglavaka, i male propusnosti kao lasaste
pukotine, porozna mjesta cijevi, greške varova, male propusnosti spojeva i slično.
Upravo male propusnosti su za cjevovod, tijekom vremena, vrlo opasne.
Često predlagano povišenje probnog tlaka sa skraćenjem trajanja probe nije dobro, pa ga ne valja
usvojiti.
Da bi se što više umanjilo upliv temperature, treba probu provesti u onom dijelu, u kom su promjene
temperature nula, a temperatura na početku probe jednaka predvidivoj temperaturi na kraju probe.
Zato je najbolje provesti 12-satnu probu od 20 h do 8 h, a 24-satnu od 8 h do 8 h.

3.10 Mjerenje tlaka, temperature i nepomičnosti


a) Za nadziranje tlačne probe potrebno je da i naručilac i izvođač imaju svaki svoj tlakomjer i na najvišoj i
na najnižoj točki ispitivanog odsjeka. Naručilac mora na svoj račun za čitavog trajanja tlačne probe držati
na njoj stručnjaka, koji je u stanju da stručno nadzore ispitivanja. Za trajanja probe nisu dozvoljeni radovi
na cjevovodu. Naročito je nedopustivo popravljanje naglavnih spojeva kao i dodavanja vode zbog
održanja tlaka.

Tlačna proba 3
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

b) Tlakomjeri (tj. manometri) za tlačnu probu moraju imati takovu skalu da u području probnog tlaka
omogućuju besprijekorno očitanje promjene tlaka od 0,1 bara. Prije tlačne probe ih treba prekontrolirati.
Najbolje je upotrijebiti tlakomjere s pisačem, tzv. manografe.

c) Vrijedi prvenstveno za novogradnje i veća proširenja vodovoda osobito glavne vodove i važne
opskrbne vodove veće duljine i većeg presjeka. Treba mjeriti i temperaturu zraka i temperaturu vode u
vodu. I za mjerenje temperature vode u cjevovodu preporučuju se uređaji s pisačem. Za utvrđenje
nepomičnosti cjevovoda treba mjeriti pomake, naročito na zavojima, na usidrenjima lukova i ogranaka, na
zatvaračima, redukcijama, svezama kao i istiskivanje brtvi pomoćnih spojeva i naglavnih spojeva, osobito
na spomenutim mjestima cjevovoda.

3.11 Nepropusnost
a) Ako se pokažu propusna mjesta na stijenkama cijevi (uslijed pukotina i sl.) ili na spoju (kapanja,
tečenje ili sl.) treba probu prekinuti i polako prazniti vod dok sva propusna mjesta ne ostanu izvan vode.
Probu se smije ponoviti tek nakon što su potpuno uklonjene te mane.

b) Prema iskustvu, tlačne probe odsjeka ograničenih zasunima mogu besprijekorno uspjeti samo ako su
zasuni ugrađeni bez otvaranja nakon otpreme iz ljevaonice. Zato treba za ograničenje probnog odsjeka
upotrijebiti završnike (prirubne, naglavne ili uglavne).

c) Kod zavarenih spojeva preporuča se prije tlačne probe vodom izvesti tlačnu probu zrakom, do 2 bara
nadtlaka, da bi se otkrile i najmanje propusnosti. Pri tome se snažno lupa po zavarima, a zatim nanese
sapunica ili drugo pjenivo sredstvo.

4 PREUZIMANJE

Smatramo da su tlačne probe prema odsjeku 3.6. i 3.11 dokazale upotrebljivost cjevovoda, ako za to
mjerodavni naručiteljev tlakomjer (po mogućnosti na najnižem mjestu voda) uzevši u obzir sve od
naručioca priznate vanjske uplive promjene temperature i sl. nije pokazao za tlačne probe veće sniženje
tlaka od 0,1 bara, a detaljni pregled voda osobito ukrućenja, usidrenja i spojeva nije pokazao ništa prema
čemu bi se dalo zaključiti da je nastao pomak ili propusnost ili da će postupno nastati.
Tlačne probe se priznaju samo, ako ih prizna, od naručioca imenovani, preuzimač.

5 ZAPISNIK O ISPITIVANJU

O izvršenju tlačne probe treba načiniti zapisnik koji ovjerava i naručilac i izvođač.
Naziv voda: ..................................................................................................................................................

Tlačna proba 4
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

Investitor: .....................................................................................................................................................

Izvođač: .......................................................................................................................................................

Projektant: ...................................................................................................................................................

Nadzorni inženjer: ........................................................................................................................................

ZAPISNIK BROJ .................

O GLAVNOJ TLAČNOJ PROBI ODSJEKA

sastavljen dana .............. u ...........................

6 PODACI O CJEVOVODU

Opis .............................................................................................................................................................
....................................................................................................................................................................
Odsjek broj ................ od km ................... do km................. ukupne duljine ................... m

Proizvođač cijevi: .........................................................................................................................................

Proizvođač fazona: ......................................................................................................................................

Proizvođač armatura: ...................................................................................................................................

Proizvođač spojnica: ....................................................................................................................................

Proizvođač gumenih brtvila: .........................................................................................................................

Proizvođač vijaka: ........................................................................................................................................

Nazivni promjer ........................................... mm Tip cijevi ............................................................

Datum proizvodnje cijevi ................................... Datum otpreme iz tvornice .................................

Debljina stijenke cijevi ................................. mm Duljina cijevi ......................................................

Vrsta i tip spojnica ............................................. Broj spojnica .....................................................

Način proizvodnje cijevi..............................................................................................................................

..................................................................................................................................................................

..................................................................................................................................................................

Za materijal i proizvode su bili obavezne HRN.

Iznimno su za bili obvezni

7 PODACI ZA TLAČNU PROBU

Najviše mjesto odsjeka je na km ......................... nadmorske visine...............................


Najniže mjesto odsjeka je na km ......................... nadmorske visine...............................

Tlačna proba 5
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

Tlačna pumpa postavljena je na km .....................nadmorske visine................................


Glavni manometar ugrađen je na km ....................nadmorske visine................................
Kontrolni manometar ugrađen je na km ................nadmorske visine................................
Propisani probni tlak na mjestu ugradbe manometra iznosi:

a) za pretprobu (toč.5.8 uputstva)

Kod glavnog manometra .................... kg/cm2

Kod kontrolnog manometra ................ kg/cm2

b) za glavnu tlačnu probu (toč.5.91)

Kod glavnog manometra .................... kg/cm2

Kod kontrolnog manometra ................ kg/cm2

Dopušteni pad manometra (toč.5.94 uputstva) ........................... kg/cm2

Dopušteno upijanje vode.................... l/m2

Glavni manometar broj ....................... tvornice...........................

Kontrolni manometar broj ................... tvornice...........................

8 PROVEDBA TLAČNE PROBE

8.1 Predproba
Provedena dana .............

Početak punjenja cjevovoda u ................. sati, kraj u ............. sati, trajanje.......................sati

Početak pretprobe cjevovoda u ............... sati, kraj u ............. sati, trajanje.......................sati

Zapažanja:

a) na manometrima: ....................................................................................................................................

....................................................................................................................................................................

b) na cjevovodu (cijevima, fazonima, armaturama, usidrenjima): .................................................................

....................................................................................................................................................................

c) na spojevima (spojnicama, gumenim prstenima, vijcima): ........................................................................

....................................................................................................................................................................

d) Odsjek je bio neispravan, te se tlačna predproba morala ponoviti nakon izvršenim popravaka.

Izvršeni popravci: .........................................................................................................................................

....................................................................................................................................................................

Tlačna proba 6
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

8.2 Ponavljanje pretprobe


Provedena dana .........................

Početak punjenja voda u ......................... sati, kraj u ............. sati, trajanje ...................... sati

Početak pretprobe voda u ....................... sati, kraj u ............. sati, trajanje ...................... sati

Zapažanja:
a) na manometrima:..................................................................................................................................

....................................................................................................................................................................

b) na cjevovodu (cijevima, fazonima, armaturama, usidrenjima): ...............................................................

....................................................................................................................................................................

c) na spojevima (spojnicama, gumenim prstenima, vijcima): .....................................................................

....................................................................................................................................................................

d) Odsjek je bio neispravan, te se tlačna predproba morala ponoviti nakon izvršenim popravaka.

Izvršeni popravci: .........................................................................................................................................

8.3 Ponavljanje pretprobe


Provedena dana .........................

Početak punjenja voda u ......................... sati, kraj u ............. sati, trajanje ...................... sati

Početak pretprobe voda u ....................... sati, kraj u ............. sati, trajanje ...................... sati

Zapažanja:
a) na manometrima:..................................................................................................................................

....................................................................................................................................................................

b) na cjevovodu (cijevima, fazonima, armaturama, usidrenjima): ...............................................................

....................................................................................................................................................................

c) na spojevima (spojnicama, gumenim prstenima, vijcima): .....................................................................

....................................................................................................................................................................

Montirani vod na predmetnom odsjeku smatra se na temelju gornjih podataka sposoban za provedbu
glavne tlačne probe.

8.4 GLAVNA TLAČNA PROBA


Provedena dana .........................

Početak probe u .......................... sati, kraj u ......................... sati, trajanje ...................... sati

Zapažanja:

Tlačna proba 7
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

a) pada tlaka i potrebne količine vode za uspostavu probnog tlaka


PAD TLAKA
PERIOD PROMATRANJA MANOMETRA DODAVANJE VODE
Trajanje Količina
Broj Od sati Do sati Glavnog Kontrolnog (min) (l)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

b) na cjevovodu (cijevima, fazonima, armaturama, usidrenjima): ...............................................................

....................................................................................................................................................................

c) na spojevima (spojnicama, gumenim prstenima, vijcima): .....................................................................

....................................................................................................................................................................

d) Odsjek je bio neispravan, te se tlačna predproba morala ponoviti nakon izvršenim popravaka.

Izvršeni popravci: .........................................................................................................................................

....................................................................................................................................................................

Tlačna proba 8
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

8.5 PONAVLJANJE GLAVNE PROBE


Provedena dana .........................

Početak probe u .......................... sati, kraj u ......................... sati, trajanje ...................... sati

Zapažanja:
a) pada tlaka i potrebne količine vode za uspostavu probnog tlaka
PAD TLAKA
PERIOD PROMATRANJA MANOMETRA DODAVANJE VODE
Trajanje Količina
Broj Od sati Do sati Glavnog Kontrolnog (min) (l)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

b) na cjevovodu (cijevima, fazonima, armaturama, usidrenjima): ...............................................................

....................................................................................................................................................................

c) na spojevima (spojnicama, gumenim prstenima, vijcima): .....................................................................

....................................................................................................................................................................

d) Odsjek je bio neispravan, te se tlačna predproba morala ponoviti nakon izvršenim popravaka.

Izvršeni popravci: .........................................................................................................................................

....................................................................................................................................................................

Tlačna proba 9
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

8.6 PONAVLJANJE GLAVNE PROBE


Provedena dana .........................

Početak probe u.......................... sati, kraj u ......................... sati, trajanje.......................sati

Zapažanja:
e) pada tlaka i potrebne količine vode za uspostavu probnog tlaka
PAD TLAKA
PERIOD PROMATRANJA MANOMETRA DODAVANJE VODE
Trajanje Količina
Broj Od sati Do sati Glavnog Kontrolnog (min) (l)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

f) na cjevovodu (cijevima, fazonima, armaturama, usidrenjima): ...............................................................

....................................................................................................................................................................

g) na spojevima (spojnicama, gumenim prstenima, vijcima): .....................................................................

....................................................................................................................................................................

9 NALAZ

Montirani odsjek br. ............................ od km ........................ do km ....................... smatra se ispravnim


na temelju gornjih podataka. Izvođač može sniziti probni tlak na nazivni i pristupiti izoliranju spojnica,
izradi posteljice ispod i oko spojeva i zatrpavanju do min. 30 cm iznad tjemena cijevi, te pažljivom
zatrpavanju preostalog dijela jarka, održavajući pri tome vod pod unutarnjim tlakom.
Prije uključenja u vodoopskrbu treba još provesti skupnu tlačnu probu dionice i dezinfekciju.

ZA INVESTITORA: ZA IZVOĐAČA:

.................................................................... ..............................................................

Tlačna proba 10
I N Ž E NJ E R S K I P R O J E K T N I Z A V O D d i o n i č k o d r u š t v o - Z A G R E B
PROJEKT IZVANREDNOG ODRŽAVANJA V1-7405/1

10 PAD TLAKA NAKON GLAVNE TLAČNE PROBE

(Kontrolna tlačna proba)


Za zatrpavanja spojeva od .................... do............................ sati glavni manometar.................... bara
Za zatrpavanja spojeva od .................... do............................ sati kontrolni manometar ............... bara
Za zatrpavanja jarka od ......................... do............................ sati glavni manometar.................... bara
Za zatrpavanja jarka od ......................... do............................ sati kontrolni manometar ............... bara
Napomena: ................................................................................................................................................

ZA INVESTITORA: ZA IZVOĐAČA:

.................................................................... ..............................................................

Prilozi :
1. Situacija odsjeka
2. Uzdužni profil dionice sa ucrtanim položajima manometra i pumpe
3. Manogrami
4. Popis osoba monterske grupe sa naznakom obavljenog rada po pojedincu.

U Zagrebu, veljača 2016. PROJEKTANT :

Edgard Roudnicky, dipl.ing.građ.

Tlačna proba 11