Beruflich Dokumente
Kultur Dokumente
subjected to soil and superimposed loads was carried out in a large laboratory
soil box. Normal and tangential soil stresses were measured by plane-stress
hansducers at the pipe-soil interface in a wide trench laying conditions. The
results were used to calculate vertical and horizontal soil loads on the pipe. It
is shown that both normal and tangential soil stresses are essential for pipe
load evaluation. Horizontal to vertical soil load ratios as well as vertical load
concentration coefficients are presented for a wide range of pipe-soil stiffness
ratios.
INTRODUCTION
481
EXPERIMENTAL PHASE
482
SURCHARGE PRESSURE
iuwuuwmuuuwiuw
483
484
RESULTS
FIG. 4.—Normal and Tangential (Shear) Soil Stresses around 1,000/60 Pipe in Clay,
90° Bedding Angle: (a) Test No. 16, 85% Standard Proctor; (b) Test No. 17, 70%
Standard Proctor
FIG. 5.—Normal and Tangential (Shear) Soil Stress around 1,000/60 Pipe in Sand,
90° Bedding Angle: (a) Test No. 15, 97% Standard Proctor; (b) Test No. 14, 85%
Standard Proctor
FIG. 6.—Normal and Tangential (Shear) Earth Stresses around 900/10 Pipe In Sand;
120° Angle: (a) Test No. 55, 85% Standard Proctor; (b) Test No. 53, 97% Standard
Proctor
486
F
H = — Zi (P-» sin 9 - Ps, cos 6) (3)
12 i=i
in which i = denotes the location of the equivalent force; P„, = the nor-
mal soil stress at the i location; Ps, = the tangential soil stress at the i
location; 6,- = IT i/12 •= the related central angle, measured from the crown
of the pipe; P„0 = the normal soil stresses at the top of the pipe; and P s6
= the tangential shear stress at the pipe spring line.
These loads (Fv and FH) were compared to vertical and horizontal loads
FV(N) and FH(N) calculated by considering the normal stresses P,„- only
in Eqs. 2 and 3. Results from 26 tests are presented in Table 4. It can
be seen that the vertical load calculated from the normal stresses only
FV(N) are up to 30% lower than those calculated from both normal and
tangential stresses Fv. On the other hand, the horizontal loads calcu-
lated from the normal stresses only FH(N) are in some cases more than
twice the FH calculated from both normal and tangential stresses. There-
fore, classical design methods that ignore shear stresses underestimate
the total vertical load and overestimate the total horizontal load. As a
result, the predicted values of ring bending moments and deflections
may be too small. This possibility should be considered, especially in
regard to engineering design methods.
Earth Load Parameters.—Two nondimensional parameters related to
earth loads on buried pipes were chosen to present the test results. One
is the vertical load concentration coefficient:
487
Fv
C <4)
--Q;
where Qv = the original vertical earth load at the pipe depth, if no pipe
is present (see Appendix I).
The second is the horizontal to vertical soil load ratio:
FH
Cu = f (5)
The values of Cv and C H as affected by soil condition, pipe stiffness
and bedding angle are presented in Table 5. Cv values increased with
pipe stiffness while CH values decreased; higher CH values were ob-
tained in sand compared to those in clay; Cv values obtained in highly
compacted clay were higher then those obtained in highly compacted
sand; and C H values increased and Cv values decreased with the in-
crease in soil compaction. An increase of the bedding angle resulted with
lower CH values in sand and with no significant changes in Cv values.
Both Cv and C H values were uneffected by the applied surcharge pres-
sure.
488
Materials
(1) (2) (3) (4) (5) (6) (7) (8)
Sand, 85% Stan- 1,000/20 1,19, 31 0.990 0.092 0.540 0.010 0.046
dard Proctor, 1,000/40 7, 35 0.827 0.029 0.420 0.046 0.271
bedding angle 800/32 26 1.090 0.040 0.368 0.033 0.305
30° 1,200/48 23 1.360 0.056 0.325 0.039 0.270
1,000/60 13 1.056 0.067 0.234 0.075 0.744
Sand, 85% Stan- 1,000/20 2, 20, 33 1.138 0.097 0.473 0.038 0.046
dard Proctor, 1,000/40 8, 37 1.180 0.028 0.308 0.051 0.271
bedding angle 800/32 25, 51 1.376 0.131 0.324 0.036 0.305
90° 1,200/48 22, 49 1.346 0.013 0.276 0.049 0.270
1,000/60 14, 44, 48 1.286 0.054 0.286 0.009 0.744
900/10" 55 1.108 0.086 0.572 0.049 0.004
Sand, 97% Stan- 1,000/20 3, 32 0.846 0.073 0.592 0.090 0.013
dard Proctor, 1,000/40 9, 38 0.964 0.112 0.338 0.034 0.077
bedding angle 800/32 24, 52 1.052 0.021 0.330 0.056 0.086
90° 1,200/48 21, 50 1.054 0.115 0.314 0.038 0.076
1,000/60 15, 45 1.024 0.054 0.284 0.076 0.210
900/10" 53 0.852 0.123 0.508 0.024 0.001
Clay, 70% Stan- 1,000/20 6 1.215 0.219 0.275 0.035 0.193
dard Proctor, 1,000/40 12, 42 1.625 0.389 0.235 0.078 1.138
bedding angle 1,000/60 18 1.707 0.271 0.123 0.021 3.119
30°
Clay, 70% Stan- 1,000/20 4 0.943 0.075 0.287 0.031 0.193
dard Proctor, 1,000/40 10, 41 0.910 0.044 0.220 0.099 1.138
bedding angle 1,000/60 * 47, 16 1.163 0.159 0.148 0.015 3.119
90°
Clay, 85% Stan- 1,000/20 5, 34 1.013 0.106 0.293 0.015 0.054
dard Proctor, 1,000/40 11, 39, 40 1.320 0.195 0.210 0.036 0.320
bedding angle 1,000/60 17, 46 1.118 0.048 0.150 0.035 0.877
90°
Sand, 91% Stan-
dard Proctor,
bedding angle
120° 900/10a 54 0.906 0.106 0.618 0.030 0.002
"Bedding angle 120°.
It is clearly shown that soil loads are affected not only by pipe stiff-
ness, but also by soil type and compaction. Thus, pipe-soil stiffness ratio
was selected for the analysis of the experimental results. Its form is
EI
(6)
of the pipe wall per unit length; R = average pipe radius; and Ms =
confined soil modulus.
The pipe-soil stiffness ratio S for each test is also listed in Table 5. The
range studied was fairly wide: from a very flexible pipe laying in well-
compacted sand (S = 0.00114) to a relatively rigid pipe laying in poorly
compacted clay (S = 3.119).
A hyperbolic type equation seems to represent the relation between
llglNP
- taddlng ••>•)•
-1 1—llll
i i 1—i i i i m i — 1 — r r r T
Pipe-Soil Stiffness Ratio S
490
where C, = the soil load parameter; and C!0o, C,„, and At = constants.
The subscript i = V denotes the vertical load concentration coefficient
Cv, while i = H denotes the horizontal to vertical load ratio CH . Cio and
C10o are the values of C, for very flexible (S -» 0) and very rigid pipes (S
—> o°), respectively. The constants A{ represents the rate of change of the
soil parameters in the intermediate range of S.
The constants of Eq. 7, as determined by least-square procedure (5),
are listed in Table 6. Curves of the load coefficients versus the pipe-soil
stiffness ratio are shown in Figs. 7 and 8 with the experimental values.
It is seen that the constants representing the Cv parameter are unaf-
fected by the bedding angle, while those representing the C H parameter
are somewhat affected. When pipe rigidity is reduced from rigid to flex-
ible condition the vertical load concentration coefficient is reduced to
one-half and the horizontal to vertical load ratio is increased by a factor
of four. This indicates the importance of the backfill material in sup-
porting flexible pipe.
CONCLUSION
ACKNOWLEDGMENTS
Qi MPo--)e<-z"> Do (8)
z
in which D 0 = external pipe diameter; P 0 = surcharge pressure; h = the
height of the soil backfill, measured from t h e crown of t h e pipe; y =
!
unit weight of backfill; and
where B, L = width and length of the soil box; 4> = angle of internal
friction of the soil backfill; and cj>' = angle of friction between the backfill
and the walls of the soil box (assumed to b e 2 / 3 of 0').
APPENDIX II.—REFERENCES
492
11. Kaufer, Z., "Experimental Study of Flexible Arches Buried in Sand," thesis
presented to the Israel Institute of Technology, at Haifa, Israel, in 1973, in
partial fulfillment of the requirements for the degree of Master of Science.
12. Rrizek, R. J., "Behaviour of Buried Concrete Pipe," Journal of the Geotechnical
Engineering Division, ASCE, Vol. 104, No. GT7, Proc. Paper 13899, July, 1978,
pp. 815-836.
13. Krizek, R. J., et al., "Structural Analysis and Design of Pipe Culverts," Na-
tional Cooperative Highway Research Program Report 116, 1971 (including Ap-
pendix N, Bibliography for 1900-1968).
14. Leonards, G. A., and Roy, M. B., "Predicting Performance of Pipe Culverts
Buried in Soil," Interim Report, Purdue Univ., W. Lafayette, Ind., May, 1976.
15. Marston, A., "The Theory of External Loads on Closed Conduits in the Light
of the Latest Experiments," Bulletin 96, Iowa State College, Ames, la., 1930.
16. Nayak, G. C , Prakash, S., and Gupta, R., "Finite Element Analysis of Ditch
Conduits," International Symposium On Soil Structure Interaction, Univ. of
Roorkee, India, Jan. 3-7, 1977.
17. Olander, H. C , "Stress Analysis of Concrete Pipe," Technical Editorial Office,
Denver Federal Center, Denver, Colo., 1950.
18. Pettibone, H. C , and Howard, A. K., "Distribution of Soil Pressure on Con-
crete Pipe," Journal of the Pipeline Division, ASCE, Vol. 93, No. PL2, Proc.
Paper 5354, July, 1967, pp. 85-102.
19. Rude, L. C , "Load Reductions on Buried Rigid Pipe," Journal of Transpor-
tation Engineering, ASCE, Vol. 109, No. TE1, Paper 17638, Jan., 1983, pp. 107-
123.
20. Shmulevich, I., "An Experimental Investigation of the Interaction between
Pipe and Soil," thesis presented to Technion, Israel Institute of Technology,
at Haifa, Israel, in 1980, in partial fulfillment of the requirements for the
degree of Doctor of Philosophy.
21. Shmulevich, I., and Galili, N., "Deflections and Bending Moments in Buried
Pipe," Journal of Transportation Engineering, ASCE, Vol. 112, No. 4, July, 1986,
pp. 345-357.
22. Spangler, M. G., and Handy, R. L., Soil Engineering, 3rd ed., Harper & Row
Publishers, New York, N.Y., 1973, pp. 658-730.
APPENDIX III.—NOTATION
At = constant;
B = width of soil-box;
CH = horizontal to vertical soil load ratio;
C, = soil load parameters;
C,0 = limit values of soil load parameters;
C,„ = limit values of soil load parameters;
Cv = vertical load concentration coefficient;
D0 = external pipe diameter;
E = elastic m o d u l u s of pipe;
e„ = measured strain in normal direction;
493
494