Beruflich Dokumente
Kultur Dokumente
Installation Instructions
Item# : 400896
2016-06-09
Contents
1 Warning........................................................................................................................................................1
2 Product information......................................................................................................................................1
2.1 General..............................................................................................................................................1
2.2 Technical data....................................................................................................................................2
2.2.1 Dimensions................................................................................................................................2
2.2.2 Weights......................................................................................................................................3
2.2.3 Space required..........................................................................................................................3
2.2.4 Electrical data............................................................................................................................4
2.3 Transport and Storage.......................................................................................................................5
3 Installation....................................................................................................................................................6
3.1 Unpacking..........................................................................................................................................6
3.2 Where/how to install...........................................................................................................................6
3.3 Ducting...............................................................................................................................................7
3.3.1 Air connection principles............................................................................................................7
3.3.2 Condensation and heat insulation.............................................................................................7
3.3.3 Silencers....................................................................................................................................8
3.4 Electric connections...........................................................................................................................8
3.4.1 Electrical connection box, components.....................................................................................9
3.5 Installing the unit..............................................................................................................................10
3.6 Supply air sensor.............................................................................................................................13
3.7 Installation of VAV models................................................................................................................13
3.8 Detailed connections, supply voltage and controller I/O (default I?O’s and options).......................14
3.9 BMS connection...............................................................................................................................18
4 Installing the control panel..........................................................................................................................19
4.1 Dimensions......................................................................................................................................19
4.2 General information..........................................................................................................................19
4.3 Installation........................................................................................................................................17
5. Additional equipment & accessories..........................................................................................................20
11Warning
Warnings
The
Thefollowing admonitions
following will be
admonitions willpresented in the in
be presented different sectionssections
the different of the document.
of the document.
Danger
Danger
• Make sure that the Main power supply to the unit is disconnected before performing any
• Make sure that
maintenance the Mains
or electrical supply to the unit is disconnected before performing any maintenance or
work!
electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local
• All electrical
rules connections must be carried out in accordance with local rules and regulations.
and regulations.
1 Warnings
Warning
Warning
• The door handles are only intended to be used during the installation. Handles must be removed
• In order for the unit to be considered safely installed the doors if equipped with handles have to be
before the unit is put into operation to ensure the required level of safety for the unit.
Thelocked withadmonitions
following a key to prevent
will beunauthorized
presented in or
theaccidental opening of the document.
different sections
• The unit must be duct connected or in some other way provided with protection so that it is not
• The unittomust
possible comebein duct connected
contact or inthrough
with the fans some the
other way
duct provided with protection so that it is not
connections.
TheDanger
• possible
unit istoheavy.
comeBe in careful
contactduring
with transport
the fans and
through the duct
mounting. Riskconnections
of injury through pinching. Use
• protective
The unit isclothing.
heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
• • Make
Bewaresure that edges
of sharp
protective the Mains
clothing. supply
during to the
mounting andunit is disconnected
maintenance. before
Make sure that performing any
a proper lifting maintenance
device is or
electrical
used. Use work!
protective clothing.
• •• Beware
All unitsof
Theelectricalsharp edges
electrical
connections
during
connection mounting
to main
must powerand
be carried
maintenance.
supply Makeby
must be preceded
out in accordance
sure that
an rules
with local all a proper
pole circuit
and
lifting device is
breaker
regulations.
used. Use protective clothing.
with a minimum 0.1” (3 mm) gap.
Warning
Important
Caution
• • In
If the unitfor
order is installed
unitintoin
abe
cold place makesafely
sure that all joints are covered with insulation, and tapehave to be
• Ifwell
the unit is the
installed considered
a cold place make sure installed
that allthe doors
joints areifcovered
equipped withwith handles
insulation, and tape well
locked with a key to prevent unauthorized or accidental opening
• • Duct connections/duct
Duct connections/duct ends
ends should
should be covered
be covered duringduring
storagestorage and installation
and installation
• The unit must be duct connected or in some other way provided with protection so that it is not
• • Do
Do not
possible connect
not connect
to cometumble
tumble dryers to
dryers
in contact the ventilation
to the fans
with system
ventilation
through system
the duct connections
• Take care not to damage the water coil when connecting water pipes to connectors. Use a spanner
• Take
The careis
unit
to tighten not
the to damage
heavy. Be careful
connection. the water
duringbattery
transportwhen
andconnecting
mounting. water
Risk ofpipes
injurytothrough
connectors. Use Use
pinching. a
spanner
protectivetoclothing.
tighten the connection.
• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
used. Use protective clothing.
2 Product Information
Caution
2.1
• IfGeneral
the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
This installation manual concerns air handling unit Topvex FR manufactured by Systemair Inc.
• DoFRnot
Topvex connect
include tumble dryers
the following to the ventilation system
model options:
• Model: FR800, FR1600, FR3800
• Take care not to damage the water battery when connecting water pipes to connectors. Use a
spanner
• Heating coil:to
ELtighten theHW
(Electric), connection.
(Water coil), None.
• Airflow control: CAV (Constant Air Volume), VAV (Variable Air Volume = Constant duct pressure control)
Water heating coil can be ordered as an accessory for units without re-heater.
This manual consists of basic information and recommendations concerning the design, installation, start-
up and operation, to ensure a proper fail-free operation of the unit.
The key to proper and safe operating of the unit is to read this manual thoroughly, use the unit according to
given guidelines and follow all safety requirements.
GG2 G1
G
H H F
H
H
F
CL
G1 G2
G
G
11.2” (285mm) FR800 = 2.4” (60mm)
FR1600 = 3.1” (80mm)
5.1” (132mm)
28.0” (712mm) FR3800 = 3” (75mm)
3.1” (80mm)
2.0” (50mm)
ØD
J
(420mm)
C
16.5”
I
L
28.0” (712mm) K
A B
Table 1: Dimensions
Model A B C ØD E F G1 G2
FR800 67.7 46.4 21.3 11.8 59.1 41.8 10.8 10.8
(1721) (1178) (540) (300) (1502) (1062) (275) (275)
FR1600 85.1 54.3 25.3 15.7 74.9 49.7 12.7 12.7
(2161) (1378) (644) (400) (1902) (1262) (323) (323)
FR3800 96.5 69.9 33.1 23.6 86.8 65.3 17.0 15.7
(2451) (1776) (840) (600) (2205) (1658) (765) (398)
Model H I J K L M
FR800 17.7 10.8 14.6 5.8 3.2 13.8
(450) (275) (370) (146) (80) (350)
FR1600 21.7 10.8 15.5 6.1 4.0 16.3
(550) (274) (394) (156) (103) (414)
FR3800 30.1 15.8 5.2 4.3 22.4
N/A
(765) (401) (132) (110) (570)
A C
D
B
Model A B* C D E
FR800 45.5 24.5 41.0 17.5 24.0
(1156) (622) (1042) (445) (610)
FR1600 58.0 32.3 49.0 21.7 24.0
(1472) (820) (1245) (550) (610)
FR3800 70.9 38.2 65.0 32.5 24.0
(1800) (970) (1652) (826) (610)
*If the sliding door option is installed, the required space corresponds to the height of the sliding door
support bars (2.0” (50 mm)).
Phase 3 3 3 1 1
Current A 5.2 16 5.2 4.4 4.4
MCA A 5.9 18.7 5.9 5 5
MOP A 15 25 15 15 15
Total Fan Power W 970 970 970 970 970
Phase 3 3 3
Current A 6 28.4 6
MCA A 6.1 33.4 6.1
MOP A 15 55 15
Total Fan Power W 1860 1860 1860
EL Preheater Power kW 9 9 9
MOP (w / EL Preheat) A 55 75 55
Phase 3 3
Current A 15.6 15.6
MCA A 17.5 17.5
MOP A 25 25
Total Fan Power W 6200 6200
Warning
Warning
The
• unit is heavy.
In order Be careful
for the unit to during transport and
be considered mounting.
safely Risk
installed of doors
the injury through pinching.
if equipped withUse
handles have to be
protective
lockedclothing.
with a key to prevent unauthorized or accidental opening
• The unit must be duct connected or in some other way provided with protection so that it is not
possible to come in contact with the fans through the duct connections
Lift should only be done from the front
• The unit is heavy. Be careful during transport and mounting. Risk
of the unit of
(orinjury through
from the pinching. Use
side using
protective clothing. extended forks).
Unit
• Beware of sharp edges during mounting and maintenance. can be
Make maneuvered
sure from lifting
that a proper the device is
side using regular length forks.
used. Use protective clothing.
Caution
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system
• Take care not to damage the water battery when connecting water pipes to connectors. Use a
spanner to tighten the connection.
Fig. 3 Transporting the unit FR800
Warning
Warning
• The door handles must be locked before the unit is put into operation to ensure the required level of
• In order for the unit to be considered safely installed the doors if equipped with handles have to be
safety for the unit. (Hex size: 5/16 in (8 mm)
locked with a key to prevent unauthorized or accidental opening
Verify
• Thethat unit
all ordered equipment
must be is delivered
duct connected or before starting
in some otherthe installation.
way providedAny discrepancies
with from
protection so theit is not
that
ordered equipment
possible must in
to come be contact
reportedwith
to the supplier
the of Systemair
fans through products.
the duct connections
• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
used. Use protective clothing.
Caution
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
Fig. 5 Opening inspection hatches with a cap key
• Do not connect tumble dryers to the ventilation system
3.2 Where/How
• Take to the
care not to damage Install
water battery when connecting water pipes to connectors. Use a
spanner to tighten the connection.
The unit is meant for indoor installation. It is important that the unit is completely level before it is put into
operation. The electronic components should not be exposed to lower temperature than 32° F (0° C) or
higher than +122° F (+50° C).
When choosing the location, keep in mind that the unit requires maintenance regularly and that the
inspection doors should be easily accessible. Leave free space for opening the doors and for taking out the
main components (Figure 2)
1 Warnings
Note:
If there is not sufficient space to open the inspection doors it is possible to unscrew the hinges to remove
the doors completely for inspection and maintenance. Another option, when installing the unit suspended
Thethe
with following admonitions
inspection door facing will be presented
downwards, in the the
is to acquire different
sliding sections of the kit.
door accessory document.
Danger
Avoid placing the appliance against a wall, as low frequency noise can cause vibrations in the wall even id
the fan noise-level is acceptable. If this is not possible it is recommended to carefully insulate the wall.
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or
electrical
The outdoor work! of the building should if possible be put in the northern or eastern side of the building
air intake
and away from other exhaust outlets like kitchen fan outcasts or laundry room outlets. The extract air
• Allideally
should electrical
be ledconnections
out via a roofmust
cowl be carried
away out outdoor
from any in accordance with
air intakes, local rules
windows, and regulations.
balconies etc.
Warning
Warning
• The unit must be duct connected or in some other way provided with protection so that it is not
• In order for the unit to be considered safely installed the doors if equipped with handles have to be
possible to come into contact with the fans through the duct connections.
locked with a key to prevent unauthorized or accidental opening
• The
Topvex unitFR1600,
FR800, must be duct
FR3800 connected or in some other way provided with protection so instructions
Installation that it is not
possible to come in contact with the fans through
6 the duct connections Systemair Inc.
• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
3.3 Ducting
2 5 1 8
B
D
C
A
3 6 7 4
Warning
Important
• • If the unit isfor
In order installed in atocold
the unit be place make sure
considered thatinstalled
safely all joints are
the covered
doors ifwith insulation,
equipped withand tape well
handles have to be
locked with a key to prevent unauthorized or accidental opening
• Duct connections/duct ends should be covered during storage and installation
• The unit must be duct connected or in some other way provided with protection so that it is not
• Dopossible to come
not connect tumbleindryers
contact with
to the the fanssystem
ventilation through the duct connections
• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
3.3.3 Silencers
• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
used.
To avoid Use protective
fan noise clothing.
being transferred via the duct system, silencers should be installed both on supply and
extract air.
Caution
To avoid noise being transferred between rooms via the duct system and also to reduce noise from the duct
system itself, installation of silencers before every inlet diffuser is recommended.
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
All external connections to possible accessories are made to terminals inside the electrical connection box
(table 8).
1 Warnings
Fig.
The7 following
Opening the electrical connection
admonitions box in the different sections of the document.
will be presented
Danger
Danger
• Make sure that the Main power supply to the unit is disconnected before performing any maintenance
• orMake surework!
electrical that the Mains supply to the unit is disconnected before performing any maintenance or
electrical work!
• • AllAll
electrical connections
electrical mustmust
connections be carried out byout
be carried an authorized installer
in accordance and
with in accordance
local rules and with local
regulations.
rules and regulations.
Warning
The
• Inunit’s electrical
order for theconnection
unit to betoconsidered
the main power supply
safely must be
installed thepreceded
doors if by an all pole
equipped circuit
with breaker
handles have to be
with locked
a minimumwith0.1” (3 mm)
a key gap. unauthorized or accidental opening
to prevent
Topvex
• The FR03,
unitFR06,
mustFR08, and FR11
be duct connected Installation
or in some other way provided with protection so that instructions
it is not
possible
206638 to come in contact with the fans through1the duct connections Systemair AB
• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
used. Use protective clothing.
Topvex FR800, FR1600, FR3800 Installation instructions
8 Systemair Inc.
Caution
3.4.1 Electrical Connection Box, Components
Topvex FR800-3800 are equipped with a built in regulator and internal wiring (figure 8)
3 1 6 13 7 11
5 2 8 9 12 10
Note:
Note:
For pre-heater components, please refer to the “Pre-Heater installation instructions (420353).
1
A
B
Warnings
Installation flat on the ground. Left and right connections are possible.
Ceiling installation. Left and right connections are possible.
Installation according to procedure below
The following admonitions will be presented in the different sections of the document.
1
Danger
Prepare the surface where the unit is to be mounted. Make sure that the surface is flat, level and that it
supports the weight of the unit. Perform the installation in accordance with local rules and regulations.
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or
2 electrical work!
• All electrical connections must be carried out in accordance with local rules and regulations.
Lift the unit in place.
Warning
Warning
Beware of sharp
• In order for edges during
the unit to bethe mounting and
considered maintenance.
safely Make
installed the sure ifthat
doors a properwith
equipped liftinghandles
device ishave to be
used. Use protective
locked with a keyclothing.
to prevent unauthorized or accidental opening
• The unit must be duct connected or in some other way provided with protection so that it is not
3 possible to come in contact with the fans through the duct connections
• The
Install unit by
the unit is using
heavy.mounting
Be careful during
brackets transport
fitted on and mounting. Risk of injury through pinching. Use
protective clothing.
the unit on delivery.
• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
Note:used. Use protective clothing.
If the unit is installed in the ceiling ensure that
the unit is pressed tightly to the mounting surface
Caution
before fastening the mounting brackets. Make
sure to use proper fastening device (screw/bolts)
• If the unit
considering is installed
the weight of theinunit
a cold place
and the make
type of sure that all joints are covered with insulation, and tape well
surface it is fitted to. The installation can only be
• Duct by
performed connections/duct ends should be covered during storage and installation
an authorized installer.
• Do not connect tumble dryers to the ventilation system
• Take care not to damage the water battery when connecting water pipes to connectors. Use a
Topvex FR800, FR1600, FR3800 Installation instructions
spanner to tighten the
connection.
10 Systemair Inc.
Double mounting brackets (pos. 1 and 2, figure 10) are used for Topvex FR1600-3800 to ensure a stable fit.
Topvex FR800 have single brackets (pos. 1).
1 Warnings
4
The following admonitions will be presented in the different sections of the document.
Connect the unit electrically to the main power
through the all pole circuit breaker (safety switch),
Danger
which is enclosed inside the unit on delivery. The
wiring is led through the side of the unit electrical
connection.
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or
electrical work!
• All electrical connections must be carried out in accordance with local rules and regulations.
Warning
Warning
The
• unit’s electrical
In order connection
for the unit to betoconsidered
the main safely installed the doors if equipped with handles have to be
powerlocked
supplywith
musta be
keypreceded by an
to prevent all pole
unauthorized or accidental opening
circuit breaker with a minimum 0.1” (3 mm) gap.
• The unit must be duct connected or in some other way provided with protection so that it is not
possible to come in contact with the fans through the duct connections
• TheDanger
unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective
• Make sure thatclothing.
the main power supply to the
•unitBeware
is disconnected
of sharpbefore
edgesperforming any
during mounting and maintenance. Make sure that a proper lifting device is
maintenance or electrical work!
used. Use protective clothing.
• All electrical connections must be carried out
by an authorized installer and in accordance
Caution
with local rules and regulations.
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system
• Take care not to damage the water battery when connecting water pipes to connectors. Use a
spanner to tighten the connection.
L1
L2
Note:
Reserved input2
35 35 AI5 Sensor CO2 (Shipped loose, mounted by
others)
Optional accessory3
40 40 Agnd UI analog reference Ground
41 41 UAI1 Differential pressure transmitter, exhaust
air VAV accessory kit
Optional accessory3
42 42 UAI2 Differential pressure transmitter, supply air
VAV accessory kit
Optional accessory3
- 43 Agnd UI analog reference
44 44 UI3 Hydronic re-heat frost protection sensor For units with hydronic or elec-
(AI) tric re-heat equipped
OR
Reserved input2
45 45 UI4 Hydronic pre-heat frost protection sensor For units with hydronic or elec-
(AI) tric re-heat equipped
OR
Reserved input2
50 B 50 B (+) BACnet MS/TP
51 A 51 A (-) BACnet MS/TP
52 N 52 N (shield) BACnet shield
53 E 53 E (earth ground) BACnet
60 B 60 B (+) EXOline expansion modules
connection (PTE & OTS)
61 A 61 A (-) EXOline expansion modules
connection (PTE & OTS)
- N 62 N (shield) EXOline expansion modules
connection (PTE & OTS)
- E 63 E (earth ground) EXOline expansion modules
connection (PTE & OTS)
Reserved input2
94 94 AO4 Free analog output (srt as “Not used” from AO4 can be field configured
factory) for different applications &
accessories.
Reserved input2
Unit control voltage Description Remark
[TB3] Expansion
[PTE]
G 1 24V+ 24 VAC
G0 2 24V- Reference
60 3 RS885-B B (+) EXOline expansion modules
connections (PTE & PTS)
61 4 RS885-A A (-) EXOline expansion modules
connections (PTE & PTS)
OR
OR
TCP/IP
E
B
Position Dimensions
A 4.5 (115.0)
B 3.7 (94.0)
C 1.0 (26.0)
D c/c 2.4 (60.0)
E 2.0 (50.5)
A set of self-adhesive magnet strips are included in the package to facilitate installation on a metal surface.
4.3 Installation
1
Find an appropriate place to install the control panel. Maximum length between control panel and unit is
32 ft. (10 m) as standard.
If needed, drill two holes in the wall to hang the control panel (center to center: 2.4” (60mm)) (pos.1, figure
17).
3 5 7
4 6
Position Description
1 Mounting holes
2 Connection block
3 Connection to yellow cable
4 Connection to orange cable
5 Connection to red cable
6 Connection to brown cable
7 Connection to black cable
For all documentation relating to accessories, please visit our website at www.systemair.net
Systemair Inc.
50 Kanalflakt Way
Bouctouche, NB
E4S3M5, Canada
Phone +1 519 915 3307
10048 Industrial Blvd
KS, 66215
United States
Phone +1 517 648 2863
www.systemair.net