Sie sind auf Seite 1von 16

Unit Report For RTU-1

Project: La Colonia Wellness Center 10/31/2019


Prepared By: Gilbert Catano 01:23PM

Unit Parameters Dimensions (ft. in.) & Weight (lb.) ***


Unit Model: 50GC-N06A2B5-0A0A0 Unit Length: 6' 2.375''
Unit Size: 06 (5 Tons) Unit Width: 3' 10.625''
Volts-Phase-Hertz: 208-3-60 Unit Height: 3' 5.375''
Heating Type: Electric *** Total Operating Weight: 752 lb
Duct Cfg: Vertical Supply / Vertical Return
No Heat *** Weights and Dimensions are approximate. Weight does
not include unit packaging. Approximate dimensions are
Two Stage Cooling With Humidi-MiZer provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters


Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2

Unit Configuration
Direct Drive - EcoBlue - Medium Static
Precoat Al/Cu - Al/Cu
Base controls set up for field installed air management device
Standard Packaging
Humidi-MiZer™ Adaptive Dehumidification System

Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)

No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quantity


50GC-N06A2B5-0A0A0 Rooftop Unit 1
Base Unit
Direct Drive - EcoBlue - Medium Static
Precoat Al/Cu - Al/Cu
None

Accessories
CRRFCURB001A01 14-inch Tall Roof Curb 1
CRTWOPOS010A00 Air Damper 1
CRHEATER326A00 Electric Heater 1
33CS2PPRH-03 Thermostats 1

Packaged Rooftop Builder 1.49w Page 1 of 16


Certified Drawing for RTU-1
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Packaged Rooftop Builder 1.49w Page 2 of 16


Certified Drawing for RTU-1
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Packaged Rooftop Builder 1.49w Page 3 of 16


Certified Drawing for RTU-1
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Packaged Rooftop Builder 1.49w Page 4 of 16


Certified Drawing for RTU-1
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

ROOFCURB NOTES: CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING POWER WIRING CONTROL WIRING ACCESSORYCONVENIENCE
ACCESSORY # A FITTING FITTING OUTLET WIRING CONNECTOR
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
14" 3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
CRRFCURB001A01 CRBTMPWR001A01 THRU THE CURB 3/4" [19] NPT
[356] 4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB). 3/4" [19] NPT 1/2" [12.7] NPT 1/2" [12.7] NPT
24" 6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
CRRFCURB002A01 CRBTMPWR003A01 THRU THE BOTTOM 1/2" [12.7] NPT
[610] 7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
1-3/4"
[44.5]

1.00"
[25.4]
5.42" 11.96" 11 3/4"[298.5] WIDE
[137.7] [303.8] INSULATED DECK PANELS

"A"

21.74"
[552.2]
8 9/16"[217.5] WIDE
INSULATED DECK PANEL
1-3/4"
[44.4]
1' 4-13/16" SEE NOTE #2
SECTION E-E [427] INSIDE
4.96" SCALE 0.250 GAS SERVICE PLATE 2-3/8"
[126.0] 70.87" THRU THE CURB
[1800.2] [61]
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
RETURN AIR
OPENING
15.19" 1/3/4"[44.5]
[385.8]
3.00" 21.84" E E
[76.2] [554.7]
32.19"
[817.6]
VIEW"B"
CORNER DETAIL
16.03" SUPPLY AIR RETURN AIR 1-3/4"
14.00" SUPPLY AIR [407.2] [44.4]
[355.6] OPENING
1-3/4"
[44.5]

1.75" 20.41" 3.00" UNIT


[44.5] [518.3] [76.2]
GASKET "A"
(SUPPLIED WITH CURB)
13.78"
[350.0] NAIL (FIELD SUPPLIED)
5' 7-3/8"
40.69" [1711.3]
[1033.5] DUCT TYPICAL (4) SIDES
(FIELD SUPPLIED) 7/16"
[11] 3'-1 3/16"
COUNTERFLASHING [944.6]
(FIELD SUPPLIED)

ROOFINGFELT SEEVIEW"B"
(FIELD SUPPLIED)
CERTIFIEDDRAWING
1/4" CANT STRIP
[7.0] (FIELD SUPPLIED)
49/16"
[115.5] ROOFINGMATERIAL
DRAWINGRELEASELEVEL: PRODUCTION INDIANAPOLIS,IN.
SYRACUSE,NY.
(FIELD SUPPLIED) UNLESSOTHERWISESPECIFIED
THIRDANGLE DIMENSIONSAREININCHES
PROJECTION TOLERANCESON: THISDOCUMENTANDTHEINFORMATIONCONTAINEDTHEREIN
1DEC 2DEC 3DEC ANG ISPROPRIETARYTOCARRIERCORPORATIONANDSHALLNOT
BEUSEDORDISCLOSEDTOOTHERS,INWHOLEORINPART,
MATERIAL - - - - WITHOUTTHEWRITTENAUTHORIZATIONOFCARRIERCORPORATION.

- AUTHORIZATIONNUMBER TITLE
SUPPLYAIR RETURNAIR RIGIDINSULATION - 1041738 CURBASY,ROOF
(FIELD SUPPLIED) - ENGINEERING MANUFACTURING (004-007)
ENGINEERINGREQUIREMENTS - - - - SIZE DRAWINGNUMBER REV
T-005, Y-002 DRAFTER CHECKER 48TC400427
A
OVERALL DIM. 5'-7 3/8" WAS 5'-7 7/8; 18GA
MATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WAS
WITH CURB
04/22/13 MMC - - 1067898 WEIGHT: - MMC 06/17/11 - - D SHEET5OF5
B
SURFACEFINISH MFG/PURCH MODEL (INTERNALUSEONLY) NEXTDRAWING SCALE DISTRIBUTION
REV REVISIONRECORD DATE BY CHK'D APP'D ECNNO. - PURCH - N/A MMC

Packaged Rooftop Builder 1.49w Page 5 of 16


Performance Summary For RTU-1
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Part Number:50GC-N06A2B5-0A0A0

ARI SEER: 16.00

Base Unit Dimensions


Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 555 lb
Two Stage Cooling With Humidi-MiZer: 33 lb
Accessories
14-inch Tall Roof Curb: 115 lb
Air Damper: 39 lb
Electric Heater: 10 lb

Total Operating Weight: 752 lb

Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct
Actual Airflow: 1500 CFM
Site Altitude: 13 ft

Cooling Performance
Condenser Entering Air DB: 91.0 F
Evaporator Entering Air DB: 76.6 F
Evaporator Entering Air WB: 63.7 F
Entering Air Enthalpy: 28.90 BTU/lb
Evaporator Leaving Air DB: 50.9 F
Evaporator Leaving Air WB: 50.2 F
Evaporator Leaving Air Enthalpy: 20.40 BTU/lb
Gross Cooling Capacity: 57.39 MBH
Gross Sensible Capacity: 41.58 MBH
Compressor Power Input: 3.85 kW
Coil Bypass Factor: 0.020

Mixed Air
Outdoor Air Airflow: 470 CFM
Outdoor Air DB: 91.0 F
Outdoor Air WB: 77.0 F
Outdoor Air Htg. Temp.: 46.0 F
Return Air DB: 70.0 F
Return Air WB: 56.0 F
Return Air Htg. Temp.: 70.0 F

Heating Performance
Heating Airflow: 1500 CFM
Entering Air Temp: 62.5 F
Leaving Air Temp: 79.1 F
Electric Heating Capacity: 7.90 kW

Supply Fan
External Static Pressure: 0.75 in wg
Options / Accessories Static Pressure
Electric Heaters: 0.16 in wg
Humidi-MiZer Dehumidification System: 0.15 in wg
Total Application Static (ESP + Unit Opts/Acc.): 1.16 in wg
Fan RPM: 1864
Fan Power: 0.70 BHP
NOTE: Selected IFM RPM Range: 239 - 2390

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 16.2
Compressor #1 LRA: 110
Actual Electric Heater kW: 7.9
Electric Heater FLA: 21.9
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA: 8.6
Power Supply MCA: 39
Power Supply MOCP (Fuse or HACR): 45
Disconnect Size FLA: 35
Disconnect Size LRA: 126
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.5
Electric Heater Part Number: 326A
Electric Heater Number of Stages: 1

Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage

Acoustics
Packaged Rooftop Builder 1.49w Page 6 of 16
Performance Summary For RTU-1
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Sound Power Levels, db re 10E-12 Watts

Discharge Inlet Outdoor


63 Hz 92.4 89.1 85.6
125 Hz 83.3 77.8 84.7
250 Hz 76.9 71.5 80.5
500 Hz 71.5 63.8 76.0
1000 Hz 67.9 66.0 72.4
2000 Hz 64.7 57.2 68.0
4000 Hz 62.0 51.1 62.8
8000 Hz 59.0 44.9 59.3

A-Weighted 75.5 70.6 79.0

Advanced Acoustics

Advanced Accoustics Parameters


1. Unit height above ground: 30.0 ft
2. Horizontal distance from unit to receiver: 50.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal distance from obstruction to receiver: 0.0 ft
6. Horizontal distance from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall


A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA

Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very
significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation
and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound
paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always
generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer
or a person with sound prediction expertise should be consulted.

Packaged Rooftop Builder 1.49w Page 7 of 16


Performance Summary For RTU-1
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Fan Curve
3.0
2.9 2400RPM 2600RPM 2800RPM 3000RPM
2000RPM 2200RPM
2.8 1800RPM
2.7
2.6 1600RPM
2.5
2.4
2.3
2.2 1400RPM
Static Pressure (in. wg.)

2.1
2.0
1.9
3.00BHP
1.8
1.7
1200RPM
1.6 SC
1.5
1.4
1.3 2.00BHP
1.2 RP
1000RPM
1.1 1.50BHP
1.0
0.9
1.00BHP
0.8 800RPM
0.7 0.75BHP
0.6
0.50BHP
0.5 600RPM
0.4
0.3
0.2
0.1
0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
Airflow(CFM-thousands)
RPM=1864 BHP=0.70 MaximumRPM=2836 MaximumBHP=3.00
SC-SystemCurve RP-RatedPoint

Packaged Rooftop Builder 1.49w Page 8 of 16


Unit Report For RTU-2
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Unit Parameters Dimensions (ft. in.) & Weight (lb.) ***


Unit Model: 50GC-M06A2B5-0A0A0 Unit Length: 6' 2.375''
Unit Size: 06 (5 Tons) Unit Width: 3' 10.625''
Volts-Phase-Hertz: 208-3-60 Unit Height: 3' 5.375''
Heating Type: Electric *** Total Operating Weight: 719 lb
Duct Cfg: Vertical Supply / Vertical Return
No Heat *** Weights and Dimensions are approximate. Weight does
not include unit packaging. Approximate dimensions are
Two Stage Cooling Models provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters


Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2

Unit Configuration
Direct Drive - EcoBlue - Medium Static
Precoat Al/Cu - Al/Cu
Base controls set up for field installed air management device
Standard Packaging

Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)

No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information

Part Number Description Quantity


50GC-M06A2B5-0A0A0 Rooftop Unit 1
Base Unit
Direct Drive - EcoBlue - Medium Static
Precoat Al/Cu - Al/Cu
None

Accessories
CRRFCURB001A01 14-inch Tall Roof Curb 1
CRTWOPOS010A00 Air Damper 1
CRHEATER326A00 Electric Heater 1
33CS2PP2S-03 Thermostat 1

Packaged Rooftop Builder 1.49w Page 9 of 16


Certified Drawing for RTU-2
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Packaged Rooftop Builder 1.49w Page 10 of 16


Certified Drawing for RTU-2
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Packaged Rooftop Builder 1.49w Page 11 of 16


Certified Drawing for RTU-2
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Packaged Rooftop Builder 1.49w Page 12 of 16


Certified Drawing for RTU-2
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

ROOFCURB NOTES: CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING POWER WIRING CONTROL WIRING ACCESSORYCONVENIENCE
ACCESSORY # A FITTING FITTING OUTLET WIRING CONNECTOR
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
14" 3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
CRRFCURB001A01 CRBTMPWR001A01 THRU THE CURB 3/4" [19] NPT
[356] 4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB). 3/4" [19] NPT 1/2" [12.7] NPT 1/2" [12.7] NPT
24" 6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
CRRFCURB002A01 CRBTMPWR003A01 THRU THE BOTTOM 1/2" [12.7] NPT
[610] 7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
1-3/4"
[44.5]

1.00"
[25.4]
5.42" 11.96" 11 3/4"[298.5] WIDE
[137.7] [303.8] INSULATED DECK PANELS

"A"

21.74"
[552.2]
8 9/16"[217.5] WIDE
INSULATED DECK PANEL
1-3/4"
[44.4]
1' 4-13/16" SEE NOTE #2
SECTION E-E [427] INSIDE
4.96" SCALE 0.250 GAS SERVICE PLATE 2-3/8"
[126.0] 70.87" THRU THE CURB
[1800.2] [61]
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
RETURN AIR
OPENING
15.19" 1/3/4"[44.5]
[385.8]
3.00" 21.84" E E
[76.2] [554.7]
32.19"
[817.6]
VIEW"B"
CORNER DETAIL
16.03" SUPPLY AIR RETURN AIR 1-3/4"
14.00" SUPPLY AIR [407.2] [44.4]
[355.6] OPENING
1-3/4"
[44.5]

1.75" 20.41" 3.00" UNIT


[44.5] [518.3] [76.2]
GASKET "A"
(SUPPLIED WITH CURB)
13.78"
[350.0] NAIL (FIELD SUPPLIED)
5' 7-3/8"
40.69" [1711.3]
[1033.5] DUCT TYPICAL (4) SIDES
(FIELD SUPPLIED) 7/16"
[11] 3'-1 3/16"
COUNTERFLASHING [944.6]
(FIELD SUPPLIED)

ROOFINGFELT SEEVIEW"B"
(FIELD SUPPLIED)
CERTIFIEDDRAWING
1/4" CANT STRIP
[7.0] (FIELD SUPPLIED)
49/16"
[115.5] ROOFINGMATERIAL
DRAWINGRELEASELEVEL: PRODUCTION INDIANAPOLIS,IN.
SYRACUSE,NY.
(FIELD SUPPLIED) UNLESSOTHERWISESPECIFIED
THIRDANGLE DIMENSIONSAREININCHES
PROJECTION TOLERANCESON: THISDOCUMENTANDTHEINFORMATIONCONTAINEDTHEREIN
1DEC 2DEC 3DEC ANG ISPROPRIETARYTOCARRIERCORPORATIONANDSHALLNOT
BEUSEDORDISCLOSEDTOOTHERS,INWHOLEORINPART,
MATERIAL - - - - WITHOUTTHEWRITTENAUTHORIZATIONOFCARRIERCORPORATION.

- AUTHORIZATIONNUMBER TITLE
SUPPLYAIR RETURNAIR RIGIDINSULATION - 1041738 CURBASY,ROOF
(FIELD SUPPLIED) - ENGINEERING MANUFACTURING (004-007)
ENGINEERINGREQUIREMENTS - - - - SIZE DRAWINGNUMBER REV
T-005, Y-002 DRAFTER CHECKER 48TC400427
A
OVERALL DIM. 5'-7 3/8" WAS 5'-7 7/8; 18GA
MATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WAS
WITH CURB
04/22/13 MMC - - 1067898 WEIGHT: - MMC 06/17/11 - - D SHEET5OF5
B
SURFACEFINISH MFG/PURCH MODEL (INTERNALUSEONLY) NEXTDRAWING SCALE DISTRIBUTION
REV REVISIONRECORD DATE BY CHK'D APP'D ECNNO. - PURCH - N/A MMC

Packaged Rooftop Builder 1.49w Page 13 of 16


Performance Summary For RTU-2
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Part Number:50GC-M06A2B5-0A0A0

ARI SEER: 16.00

Base Unit Dimensions


Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 555 lb
Accessories
14-inch Tall Roof Curb: 115 lb
Air Damper: 39 lb
Electric Heater: 10 lb

Total Operating Weight: 719 lb

Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct
Actual Airflow: 1972 CFM
Site Altitude: 13 ft

Cooling Performance
Condenser Entering Air DB: 91.0 F
Evaporator Entering Air DB: 77.6 F
Evaporator Entering Air WB: 64.7 F
Entering Air Enthalpy: 29.69 BTU/lb
Evaporator Leaving Air DB: 56.2 F
Evaporator Leaving Air WB: 54.1 F
Evaporator Leaving Air Enthalpy: 22.61 BTU/lb
Gross Cooling Capacity: 62.81 MBH
Gross Sensible Capacity: 45.64 MBH
Compressor Power Input: 3.92 kW
Coil Bypass Factor: 0.158

Mixed Air
Outdoor Air Airflow: 211 CFM
Outdoor Air DB: 91.0 F
Outdoor Air WB: 77.0 F
Outdoor Air Htg. Temp.: 46.0 F
Return Air DB: 76.0 F
Return Air WB: 63.0 F
Return Air Htg. Temp.: 70.0 F

Heating Performance
Heating Airflow: 1972 CFM
Entering Air Temp: 67.4 F
Leaving Air Temp: 80.1 F
Electric Heating Capacity: 7.90 kW

Supply Fan
External Static Pressure: 0.75 in wg
Options / Accessories Static Pressure
Electric Heaters: 0.23 in wg
Total Application Static (ESP + Unit Opts/Acc.): 1.11 in wg
Fan RPM: 2054
Fan Power: 0.94 BHP
NOTE: Selected IFM RPM Range: 239 - 2390

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 16.2
Compressor #1 LRA: 110
Actual Electric Heater kW: 7.9
Electric Heater FLA: 21.9
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA: 8.6
Power Supply MCA: 39
Power Supply MOCP (Fuse or HACR): 45
Disconnect Size FLA: 35
Disconnect Size LRA: 126
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.5
Electric Heater Part Number: 326A
Electric Heater Number of Stages: 1

Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage

Acoustics

Packaged Rooftop Builder 1.49w Page 14 of 16


Performance Summary For RTU-2
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Sound Power Levels, db re 10E-12 Watts

Discharge Inlet Outdoor


63 Hz 92.1 90.6 85.6
125 Hz 83.4 79.2 84.7
250 Hz 77.4 71.8 80.5
500 Hz 73.8 65.9 76.0
1000 Hz 70.6 68.1 72.4
2000 Hz 67.2 58.8 68.0
4000 Hz 64.1 52.7 62.8
8000 Hz 60.1 46.4 59.3

A-Weighted 77.0 72.2 79.0

Advanced Acoustics

Advanced Accoustics Parameters


1. Unit height above ground: 30.0 ft
2. Horizontal distance from unit to receiver: 50.0 ft
3. Receiver height above ground: 5.7 ft
4. Height of obstruction: 0.0 ft
5. Horizontal distance from obstruction to receiver: 0.0 ft
6. Horizontal distance from unit to obstruction: 0.0 ft

Detailed Acoustics Information

Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall


A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA

Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA

Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very
significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation
and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound
paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always
generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer
or a person with sound prediction expertise should be consulted.

Packaged Rooftop Builder 1.49w Page 15 of 16


Performance Summary For RTU-2
Project: La Colonia Wellness Center 10/31/2019
Prepared By: Gilbert Catano 01:23PM

Fan Curve
3.0
2.9 2400RPM 2600RPM 2800RPM 3000RPM
2000RPM 2200RPM
2.8 1800RPM
2.7
2.6 1600RPM
2.5
2.4
2.3
2.2 1400RPM
Static Pressure (in. wg.)

2.1
2.0
1.9
3.00BHP
1.8
1.7
1200RPM
1.6 SC
1.5
1.4
1.3 2.00BHP
1.2 1000RPM RP
1.1 1.50BHP
1.0
0.9
1.00BHP
0.8 800RPM
0.7 0.75BHP
0.6
0.50BHP
0.5 600RPM
0.4
0.3
0.2
0.1
0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
Airflow(CFM-thousands)
RPM=2054 BHP=0.94 MaximumRPM=2836 MaximumBHP=3.00
SC-SystemCurve RP-RatedPoint

Packaged Rooftop Builder 1.49w Page 16 of 16

Das könnte Ihnen auch gefallen