Sie sind auf Seite 1von 20

Large

Diameter
Piping
Systems

⊕⊕

R
The System

The fast, easy, economical


system for joining large diameter piping.

■ Lower total ■ Utilize in-house or ■ A union at every


installed cost contracted labor joint
■ Fast, easy bolted ■ No flame or fire ■ Couplings
connection hazard as with accommodate
■ Meet project welding expansion/
deadlines and fast- ■ Less than ¹⁄₂ the contraction and
track schedules bolts of flanged deflection

■ Direct grooved systems ■ The system


products up to 42" ■ Reduced weight attenuates noise
(1050 mm); applied and assembly and vibration
Vic-Ring® products compared to flanges
up to 144"
(3600 mm)

The Victaulic® grooved method for mechanically joining pipe has been used
successfully for over 70 years to simplify design, installation, and operation
of piping systems. It combines the advantages of fast installation, design
integrity and reliable operation at lower total installed cost than other
conventional methods.
Victaulic technology for joining large diameter piping includes capabilities
for direct grooving black or galvanized steel pipe up to 42" (1050 mm). The
Vic-Ring® applied ring method accommodates odd pipe sizes up to 144"
(3600 mm).
The Victaulic system for joining large diameter pipe and piping components
are available from stocking distributors worldwide. Over 200 factory-trained
piping specialists provide on-site assistance backed by application and
product engineering support as close as your phone.

2
Diversified

Versatile and reliable


The Victaulic grooved piping system is the most
versatile, economical and reliable piping system
available. It is up to three times faster to install
than welding, easier and more reliable than
flanging, resulting in lower total installed cost.
The system is designed for roll grooved ANSI,
ISO, DIN and other black or galvanized steel pipe.
Pipe end preparation is fast and easy either in the
shop or on the job site with the variety of Victaulic
grooving tools available.
In addition to speed and ease of assembly, the
Victaulic system offers varied mechanical
benefits to the designer, installer and owner.

Economical and No fire hazard


practical As a fully mechanical, bolted
Up to three times faster to install system, Victaulic products
than welding or flanging. The present no fire hazard. It is far
Victaulic system can reduce safer and requires no shielding or
total installed costs from 20 to fire watch.
40%. Cost estimates are more
accurate; completion dates are
more predictable.

Easy system or Alignment ease


equipment access The grooved system allows full
Removal of couplings provides rotation of pipe, valves, fittings
access for cleaning, or couplings before tightening
maintenance, system expansion for easy alignment. This
or changes. compensates for some alignment
errors and eliminates the “two-
holing” required with flanges.
Fitting in tight places is eased.
Request 26.03.

Flexibility Self-restrained joint


Contraction The Victaulic system is unique The full engagement of the
in the ability to accommodate housing keys into grooves
expansion/contraction/ around the full pipe
deflection. Elimination or circumference provides
reduction of special vibration significant pressure restraint
End End
accessories, expansion loops Load Load and end load capabilities to
Deflection and settlement allowance are withstand pipe movement from
among the inherent benefits of varied internal and external
the grooved system. sources.
Request 26.01 Request 26.05.

Above drawings are exaggerated for clarity.

3
Economical

The Victaulic System vs. Flanged Systems


The Victaulic System eliminates alignment problems
Victaulic Flanged Victaulic Flanged
Rotates for Alignment Must be “two holed” 42" Typical 48" Typical

A B

■ Grooved piping can ■ Require special ■ No two-holing ■ Two-holing required


pass through wall design required ■ Side space needed
sleeves considerations
■ No side space for bolts
■ Special design ■ Flanging must be needed for bolts ■ Heavier, more costly
considerations made-on loose or
■ ¹⁄₃ the weight of to install
eliminated have coupling
flanged systems ■ More bolts, longer
adapter added to
■ Compression type
pass through a wall ■ Number of bolts installation time
couplings not
sleeve greatly reduced
required

Victaulic The Victaulic System vs. Flanged Systems


1410-1B

Saves Space… Lighter… Fewer Bolts…


Inches/millimeters Weight Number of
Nominal
Size Width A - O.D. B - O.D. Lbs./kg Bolts
Inches/mm Victaulic Flanged Victaulic Flanged Victaulic Flanged Victaulic Flanged
28 5.0 10.5 36.3 36.0 175 400
700 127 267 922 914 79.4 181.4 6 24
30 5.0 10.6 38.3 38.8 200 480
750 127 269 973 986 90.7 217.7 6 28
32 5.0 10.8 40.3 42.5 225 560
800 127 274 1022 1080 102.1 254.0 6 28
Flanged 36 5.0 11.0 44.3 46.0 250 640
900 127 279 1125 1168 113.4 290.3 6 32
42 5.8 11.5 51.5 53.0 400 830
1050 147 292 1308 1346 181.4 376.5 8 36
48 5.8 12.1 57.0 59.5 450 980
1200 147 307 1448 1511 204.1 444.5 8 44
54 5.4 12.7 70.5 66.3 470 1400
1375 137 323 1791 1684 213.2 635.0 8 44
60 5.5 13.2 74.0 73.0 570 1750
1525 140 335 1880 1854 258.6 793.8 10 48
66 6.9 14.0 82.0 80.0 750 2300
1675 175 356 2083 2032 340.2 1043.3 24 52

4
Certified

The ISO 9001 certified


piping products manufacturer.
Victaulic is committed to excellence.
Victaulic is committed to customers that all the (a subsidiary of Lloyd’s of
excellence – in our products, appropriate systems are in place London). A major factor in
people, programs and service to to assure quality as defined by maintaining ISO certification is
the industry. Indicative of this the standard. In qualifying for our continuous Quality
commitment is our certification certification, we worked through Improvement Process.
to ISO 9001 standards for our The Loss Prevention Control Establishing this management
principal U.S. and European Board (of England) and Lloyd’s direction has put into practice
locations. This confirms to our Register Quality Assurance Ltd. the corporate mission:

“We will satisfy our customers’ requirements by furnishing


defect free products and services on time, every time. We will
accomplish this to the benefit of our employees, owners and
community.”

General Code Groups, Government Agencies


Approved Associations, Bureau of Marine Inspection – Salt and
Worldwide* Laboratories and
fresh water, oil transfer
Bureau of Public Roads – Div. of Bridges –
Approval Bodies Drain lines and bridge crossings
The grooved piping system has been tested to a wide variety of (ANSI) American National Standards Canadian Coast Guard
industry standards in our own laboratories, independent laboratories Institute U.S. Coast Guard – Approves each vessel
and many agency facilities. The system has withstood the test of time (ANSI/AWWA) American Water Works individually
Association – C-606 (COE) Corps of Engineers – CEGS 15000
since 1925.
(API) American Petroleum Institute – API (FAA) Federal Aviation Administration -
*Specific approvals, listings and test data are available to meet varied Std. 5L, Sect. 7.5 HVAC, Plumbing, Fire Protection
requirements. The approvals shown here apply to Victaulic (ASHRAE) American Society of Heating, (FHA) Federal Housing Administration
Company’s standard product size range. Contact Victaulic for specific Refrigerating and Air Conditioning
Engineers (GSA) General Services Administration –
information regarding the products contained in this literature. 15000 Series
(ASME) American Society of Mechanical
Engineers Power Piping, B-31.1; (MIL) Military Specifications – MILP-
Chemical Plant and Petroleum 10388 Fittings; MIL-C-10387
Refinery Piping, B-31.3; Refrigeration Couplings;
Piping, B-31.5; Building Services MIL-P-11087A(CE) Steel Pipe, Grooved
Piping, B-31.9; Slurry Pipelines, B- MIL-I-45208 Inspection Procedure
31.11 (NASA) National Aeronautics and Space
(ASTM) American Society of Testing and Administration – 15000 Series
Materials F-1476 (NAVFAC) Naval Facilities Engineering
(BOCA) Building Officials and Code Command – NFGS 15000 Series
Administrators (NIH) National Institute of Health (Dept.
(CSA) Canadian Standards Association – of Health) – 15000 Series
B-242 (TVA) Tennessee Valley Authority – Fire
(FM) Factory Mutual Research Corp. - protection, storm drains
approved for fire protection services (VA) Veterans Affairs – 15000 Series
(IAPMO) International Association of
Plumbing & Mechanical Officials
(LLOYD'S) Lloyd's Register of Shipping
Worldwide
(LPC) Loss Prevention Council (formerly (AS) AS4041-1992 Australian Standard
F.O.C.) (3.24.10)
(NFPA) National Fire Protection (BV) Bureau Veritas
Association (DNV) Det Norske Veritas
(NY-BSA) New York Board of Standards (DVGW) Deutscher Verein des Gas-und
and Appeals Wasserfaches e.V.
(SBCCI) Southern Building Code (HDB) Singapore Housing Development
Congress International – Standard Board
Plumbing
and Mechanical Code Hong Kong Fire Services Board
(UL) Underwriter's Laboratories, Inc. – New Zealand Insurance Council
Listed for fire protection services. New Zealand Building Act. (1991)
(ULC) Underwriter's Laboratories of (SSL) Scientific Services Laboratory
Canada – Listed for fire protection Standards Australia
services.
(VdS) Verband der Schadenversicherer
e.V.
(WRC) Water Research Council – U.K.
Request 02.02 for details.

5
Applications

Water
■ Chilled
■ Heating
■ Condenser
■ Supply
■ Underground
■ Wastewater
Other
■ Compressed air
■ Slurries
■ Tailings

Galvanized steel pipe, 30 - 42" (750 - 1050 mm), was easily direct grooved and coupled with Style 770 couplings
for these condenser water lines in a large office complex in Singapore. The system was then painted to color code
and for aesthetics.

Vic®-Ring applied rings allowed easy bolted coupling assembly for these Large diameter ductile iron pipe was radius cut grooved and assembled for
power plant water supply lines. underground fire protection water supply.

Condenser, chilled and


river water supply
utilized direct roll
grooved fittings and
Style 770 couplings for
emergency repair of the
HVAC systems at the
World Trade Center in
New York City.

6
Applications

Markets
■ Heating/Air
Conditioning
■ Plumbing
■ Industrial
■ Mining
■ Power Plant
■ Marine
■ Dredging

Large mine tailings such as these lines at BP Minerals, Bingham Canyon and other abrasive services utilize the
full wall thickness and the option to rotate pipe sections available with Vic-Ring applied ring piping.

Large diameter valves are available Direct grooved pipe was easily assembled for these chilled water lines at a large hotel in Dubai, UAE.
with grooved or shouldered ends to
allow easy positioning, assembly
and future maintenance with the
Victaulic system, such as these
Style 770 grooved couplings. These
systems were installed at Prospect
Water Treatment Facility in
Sydney, Australia.

Even large diameter


stainless steel, such as
these deionized water
lines at Argonne National
Laboratories, can be direct
grooved and joined with
Victaulic couplings.

7
Grooved System

The direct grooved method


B
A B

OD C

■ ISO, DIN and other ANSI standard weight steel pipe


■ Black or galvanized
■ Stainless Steel
■ Sizes up to 42" (1050 mm)
■ Roll grooving is fast and easy

Roll Vic-Easy
A B A B
grooving tools roll a
removes groove
Hydraulic
no metal Force into pipe
Upper Roll from pipe

Pipe
Pipe

Lower
(Drive)
Roll

Above drawings are exaggerated for clarity.


The concept of rolling a groove into pipe without removing metal was developed by Victaulic in 1955. The
concept was first used for light-wall pipe which did not have sufficient wall thicknesses to permit cut
grooving. Technological developments now permit roll grooving of standard weight steel pipe, up to 42"
(1050 mm).
Victaulic Vic-Easy® roll grooving tools are designed to rotate the pipe as an upper roll is pressed into the
pipe. The lower roll, in addition to rotating the pipe, is the female die inside the pipe. Groove depth “D” is
controlled by an adjustable stop. The configuration of the rolls provides the proper “A” (gasket sealing
surface), “B” (groove width) and “C” (groove diameter) dimensions.
Standard cut grooved pipe will provide double the expansion/contraction or deflection of the same size
standard roll groove pipe. Roll grooving is applicable for both carbon steel (galvanized or black) and stainless
steel.

8
Couplings

Style 770 Style 770 couplings are Roll Grooved NOTE: Bolts and nuts
Large Diameter designed to provide a Beveled or square cut pipe must be torqued to
Pipe Coupling strong reliable component of 0.375" or 0.500" (9.5 or listed specifications
for joining large diameter 12.7 mm) wall thickness during installation.
piping systems. Style 770 can be roll grooved with This product requires
provides a joint with special Vic-Easy® roll special roll grooving
flexibility to accommodate grooving tools. Grooving equipment, pipe specifi-
settlement and alignment. must be performed by Vic- cations, and mandatory
Ranging in size from 28" taulic trained personnel. installation training.
(700 mm) to 42" (1050 mm), Contact Victaulic for details Refer to I-770 for
Style 770 is ideal for roll on other wall thicknesses. product installation
grooved black or galvanized instructions.
Cut Grooved
steel and stainless steel
Cut Grooving may be used
systems up to 330 PSI (2270
for pipe wall thickness
kPa) depending on pipe
0.625" (15.9 mm) or thicker.
size, wall thickness and
material. Contact Victaulic for
details.
Compatible roll grooved fit-
tings to ANSI B-16.9 cen-
ter-to-end dimensions are
also available.

Y Z

Y Z

X
X

28 - 36" Sizes 42" Size


06.03-1B

Max. Max. Required Nominal Range of Approx.


PIPE Work End Bolt Coupling Dimensions Linear Movement ‡ Nominal Wgt.
Inches/mm Press. Load Bolt/Nut* Torque Inches/mm Inches/mm Deflection CL ‡ Each
Nominal Actual PSI* Lbs.* No. - Size lb. ft. In./Ft. Lbs.
Size Size kPa N Inches N•m X Y Z Min. Max. Degrees mm/m kg
28 28.00 330 203199 600 31.75 36.25 5.00 0 0.38 0.16 175.0
700 711 2270 904236 6 - 1¹⁄₄ ✕ 3¹⁄₂ 815 807 921 127 0 9.7 0° - 46´ 13.3 78.0
30 30.00 300 212058 600 33.75 38.25 5.00 0 0.38 0.15 200.0
750 762 2065 943658 6 - 1¹⁄₄ ✕ 3¹⁄₂ 815 857 972 127 0 9.7 0° - 43´ 12.5 90.7
32 32.00 260 209105 600 35.75 40.25 5.00 0 0.38 0.14 225.0
800 813 1790 930517 6 - 1¹⁄₄ ✕ 4¹⁄₂ 815 908 1022 127 0 9.7 0° - 40´ 11.7 102.1
36 36.00 200 203575 600 39.75 44.25 5.00 0 0.38 0.12 250.0
900 914 1380 905909 6 - 1¹⁄₄ ✕ 3¹⁄₂ 815 1010 1124 127 0 9.7 0° - 36´ 10.0 113.4
42 42.00 145 200890 600 45.75 51.50 5.75 0.25 0.38 0.03 400.0
1050 1067 1000 893961 8 - 1¹⁄₂ ✕ 4¹⁄₂ 815 1162 1308 146 6.4 9.7 0° - 10´ 2.5 181.4
*Refer to notes below.
‡ Nominal Linear Movement and Deflection are dependent upon pipe properly roll or cut grooved to Victaulic specifications.
Contact Victaulic for information.
Maximum allowable linear movement is the difference between minimum and maximum pipe end separation subject to tolerances (see Design Data).

NOTES
* Working Pressure and End Load are total, from all internal and external loads, based on ANSI standard weight (0.375"/9.5 mm) steel pipe, standard roll grooved
in accordance with Victaulic® specifications and with bolts fully torqued to listed specifications. Contact Victaulic for performance on other pipe.
WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1¹⁄₂ times the figures shown.
‡ Pipe End Separation and Deflection figures show the nominal range of movement available at each joint for standard roll grooved pipe. For design and installation
purposes these figures should be reduced by 25% to allow for pipe groove tolerances. NOTE: Joints which are fully deflected can no longer provide linear move-
ment. Partially deflected joints will provide some portion of linear movement. Pressure thrusts will tend to straighten deflected pipe.
@ Number of bolts required equals number of housing segments.
Metric thread size bolts are available (color coded gold) for all coupling sizes upon request. Contact Victaulic for details.
WARNING: Piping systems must always be depressurized and drained before attempting disassembly and removal of any Victaulic piping products.

9
Fittings

1410-2B
PERFORMANCE PIPE
Carbon Steel Stainless Steel
PIPE ¹⁄₂"/12.7 mm ³⁄₈"/9.5 mm ¹⁄₄"/6.4 mm ¹⁄₄"/6.4 mm
Inches/mm Wall Thickness Wall Thickness Wall Thickness* Wall Thickness*
Max. Max. Max. Max. Max. Max. Max. Max.
Work End Work End Work End Work End
Nominal Actual Press. Load Press. Load Press. Load Press. Load
Size Size PSI/kPa Lbs./N PSI/kPa Lbs./N PSI/kPa Lbs./N PSI/kPa Lbs./N
28 28.00 380 233986 330 203198 132 81279 110 67733
700 711 2620 1040822 2270 903870 910 361547 760 301291
30 30.00 348 245987 300 212058 120 84823 100 70686
750 762 2400 1094205 2065 943281 826 377312 690 314427
32 32.00 300 241274 260 209104 105 84446 85 68361
800 813 2065 1073240 1790 930141 724 375635 585 304085
36 36.00 232 236147 200 203575 80 81430 75 76341
900 914 1600 1050434 1379 905547 552 362219 517 339582
42 42.00 165 228598 145 200889 55 76199 50 69272
1050 1067 1138 1016855 1000 893599 379 338950 345 308137
*Ratings are based upon pipe grooved with Victaulic R x rolls.

Direct Grooved Victaulic offers a broad line All fittings are supplied Machining for rubber lining
Fittings of fittings in sizes through with grooves to permit fast may be varied to provide
42" (1050 mm) in a variety installation without field abrasion resistance only or
of straight and reducing preparation. The grooved both abrasion and corrosion
styles. Standard fittings are design permits flexibility resistance.
steel, segmentally welded for easy alignment.
Lining may be applied on
steel or ductile iron
Fitting center-to-end the inside diameter and
depending on styles and
dimensions will vary end (abrasion resistance) or
size. Fittings are painted
depending upon type and wrap-around for corrosion
with galvanized optionally
schedule. and/or abrasion. Request
available, contact Victaulic
for details. 25.03 or contact Victaulic
Rubber or Urethane for specific details.
Victaulic fittings pressure Lining (MRL) – For severe
ratings conform to the rat- abrasive services, Victaulic
fittings may be rubber or
ings of the particular cou-
urethane lined (by others).
pling style used for
assembly.

C to E
C to E
C to E

C
to
E

Steel – 1¹⁄₂ D Radius 1410-3B

PIPE
Inches/mm No. 100 – 90° No. 110 – 45° No. 20 – Tee
Nom. Actual C-E Wgt. Ea. C-E Wgt. Ea. C-E Wgt. Ea.
Size Size In./mm Lbs./kg In./mm Lbs./kg In./mm Lbs./kg
28 28.000 42.00 626.0 17.25 312.0 24.00 790.0
700 711 1066 284 438 142 610 358
30 30.000 45.00 775.0 18.50 358.0 25.00 1000.0
750 762 1143 352 470 162 635 454
36 36.000 54.00 1170.0 22.25 583.0 30.00 1450.0
900 914 1372 531 565 265 762 658
42 42.000 63.00 1810.0 26.00 900.0 35.00 2000.0
1050 1067 1600 821 660 408 889 907
Ductile iron available. Contact Victaulic for sizes, dimensions and availability.

10
Tools

Direct Grooved
Piping from 28 - 42" the pipe wall as the pipe is Coupling weight is less
Pipe Preparation (700 - 1050 mm) can now rotated by a lower female than one-half, ranging from
be direct roll grooved to drive roll forming the 175 - 450 lbs. (79 - 204 kg)
receive new Style 770 large groove. vs. 440 - 980 lbs. (200 -
diameter couplings. This 445 kg) for flanges.
The grooved system has far
capability brings the speed
fewer bolts than flanged Victaulic shop roll groovers
and ease of bolted mechan-
systems, for example: 30" can roll groove up to ¹⁄₂"
ical assembly to large diam-
(750 mm) requires six bolts (13 mm) wall thickness car-
eter pipe assembly.
for a Victaulic coupling, bon steel pipe.
Roll grooving removes flanging requires 28 bolts;
no metal, cold forming a 42" (1050 mm) requires
groove by the action of an eight bolts, compared to
upper male roll displacing 36 bolts.

Large Diameter The Victaulic Large Diame- 0.375" (9.5 mm). The tool is grooving pipe in the follow-
Pipe Roll ter Roll Groover is a fully supplied with 4 - 24" ing sizes: 22 - 24"
motorized, automated shop (100 - 600 mm) rolls as stan- (550 - 600 mm) and 30 - 36"
Grooving Tool tool for continuous produc- dard. Optional rolls avail- (750 - 900 mm) up to maxi-
tion grooving. It is supplied able are 4 - 24" (100 - mum wall thickness of .500"
in several variations to 600 mm) lightwall stainless (12.7 mm). These rolls are
accommodate the needs of steel pipe, 4 - 12" (100 - standard supply with this
roll grooving pipe above 24" 300 mm) “ES” grooving, tool. Other roll sets can be
(600 mm). and a conversion kit for provided upon request.
grooving 26 - 36" (650 -
The VE424 is a fully auto- For roll grooving 42"
900 mm) standard wall
mated shop tool for roll (1050 mm) pipe, contact
.375" (9.5 mm) steel pipe.
grooving pipe from 4 - 36" Victaulic.
(100 - 900 mm) with a maxi- The VE436 is a fully auto-
mum wall thickness of mated shop tool for roll

1410-4B

1 2 3 5 4 6 7 8
Roll/Cut Groove Dimensions – Inches/mm
Specifications Pipe Groove Width Min. Allow. Wall
for Style 770 Large Nom. Outside Diameter O.D. Gasket “B” Groove Dia. Thickness
Inches/mm ±0.03/±0.76 “C” Grv. “T” Max.
Diameter Couplings Pipe Seat
Size “A” Tol. Depth Allow.
B
Inches +0.03/–0.06 Roll Cut +0.000 “D” Roll Cut Flare
A B T mm Basic Tolerance +0.8/–1.5 Groove Groove Basic +0.00 (Ref.) Groove Groove Dia.
28 O.D. 28.00 +0.093 –0.031 1.75 0.625 0.625 27.50 –0.063 0.250 0.250 0.625 28.20
700 711.0 +2.36 –0.79 44.45 15.88 15.88 698.50 –1.60 6.35 6.35 15.88 716.3
30 O.D. 30.00 +0.093 –0.031 1.75 0.625 0.625 29.50 –0.063 0.250 0.250 0.625 30.20
OD C 750 762.0 +2.36 –0.79 44.45 15.88 15.88 749.30 –1.60 6.35 6.35 15.88 767.1
32 O.D. 32.00 +0.093 –0.031 1.75 0.625 0.625 31.50 –0.063 0.250 0.250 0.625 32.20
800 813.0 +2.36 –0.79 44.45 15.88 15.88 800.10 –1.60 6.35 6.35 15.88 817.9
36 O.D. 36.00 +0.093 –0.031 1.75 0.625 0.625 35.50 –0.063 0.250 0.250 0.625 36.20
Exaggerated for Clarity 900 914.0 +2.36 –0.79 44.45 15.88 15.88 901.70 –1.60 6.35 6.35 15.88 919.5
D
42 O.D. 42.00 +0.093 –0.031 2.00 0.625 0.625 41.50 –0.063 0.250 0.250 0.625 42.20
1050 1067.0 +2.36 –0.79 50.80 15.88 15.88 1054.10 –1.60 6.35 6.35 15.88 1071.8
COLUMN 1: Nominal IPS Pipe size.
COLUMN 2: IPS outside diameter. The outside diameter of roll grooved pipe shall not vary more than the tolerance listed. For IPS pipe the maximum allowable tolerance from square cut ends
is 0.060" (1.5 mm) for sizes 28" (700 mm) and above measured from true square line.
COLUMN 3: Gasket seat. The pipe surface shall be free from indentations, roll marks, and projections from the end of the pipe to the groove, to provide a leaktight seal for the gasket. All loose
paint, scale, dirt, chips, grease and rust must be removed. It continues to be Victaulic Company’s first recommendation that pipe be square cut. When using beveled pipe contact Victaulic for
details. Gasket seat “A” is measured from the end of the pipe. IMPORTANT: Roll grooving of beveled end pipe may result in unacceptable pipe end flare. See column 8.
COLUMN 4: Groove width. Bottom of groove to be free of loose dirt, chips, rust and scale that may interfere with proper coupling assembly. Corners at bottom of groove must be radiused. For
IPS steel pipe, R-0.015" (0.38 mm) ±0.005 (0.13 mm).
COLUMN 5: Groove outside diameter. The groove must be of uniform depth for the entire pipe circumference. Groove must be maintained within the “C” diameter tolerance listed.
COLUMN 6: Groove depth. For reference only. Groove must conform to the groove diameter “C” listed.
COLUMN 7: Minimum allowable wall thickness. This is the minimum wall thickness which may be roll grooved.
COLUMN 8: Maximum allowable pipe end flare diameter. Measured at the most extreme pipe end diameter square cut or beveled.

11
Vic-Ring

Applied Vic-Ring ® Method


Victaulic offers the Vic-
Ring piping method for
joining large diameter pipe
which does not lend itself
to direct grooving. The
adaptation of pipe with Vic-
Ring adapters and the
selection of a suitable Vic-
taulic coupling can present
individual considerations
which are best handled by
Victaulic engineers, who
are experienced in these
applications. Contact Vic-
taulic for assistance.

Vic-Ring Configurations

Type A Vic-Ring Type B Vic-Ring Type C Vic-Ring


Standard
Vic-Ring
Configurations

Type A Type B Type C


This method is widely used for A short grooved nipple, butt- Attached with double fillet welds,
light wall pipe and tubing for welded to the pipe end. The front and rear, this is principally for
general applications. The Vic-Ring nipples may be cut from standard large diameter pipe. Coupling
adapters are slipped over the pipe pipe and joined using standard IPS Styles 41 and 44 are generally
ends and are welded in place with couplings or with Vic-Ring applied but others may be used
a single fillet end weld. couplings. depending on the Vic-Ring O.D.

Type D Vic-Ring Type E Vic-Ring Type G Vic-Ring

Type D Type E Type G


A heavy duty collar typically for Similar in application to C and D Ductile iron pipe may sometimes
large diameter pipe – 30" (750 mm) Vic-Ring adapter ends, Type E be supplied with a cast-in shoulder
and up – providing special pipe allows easier attachment while which equates to an applied ring.
end reinforcement and rigidity. providing secure coupling
Styles 41 and 44 couplings are engagement. Style 31, Style 41 and
most commonly used, however, Style 44 couplings are commonly
others may be used. used.

12
Couplings

Style 22 Style 22 couplings are Y Z Y Z


Vic-Ring® designed with cross-ribbed
Coupling construction to provide a
strong component for Vic-
Ring adapter prepared pip- X X
ing systems. Style 22 cou-
plings are designed
primarily for use with Type
“A” Vic-Ring adapters, 17 - 24" sizes 30 - 36" sizes
depending upon sizes and
pressures. 16.02-1B

Coupling Dimensions Bolt Dimensions Aprx.


Style 22 couplings are sup- Vic-Ring Inches/mm Inches/mm Weight
plied with “E” or “T” gas- Size O.D. Each
kets. FlushSeal® gaskets In. Inches Height Width Depth Lbs.
mm mm X Y Z No. Dia. ✕ Lgth. kg
are available upon request. 17 17.031 20.13 23.13 3.13 62.0
425 432.6 511 588 80 4 1 ✕ 5¹⁄₂ 28.1
All sizes are supplied
24 24.750 28.38 32.00 3.50 125.0
painted and with plated 600 628.6 721 813 89 4 1¹⁄₈ ✕ 5¹⁄₂ 56.7
nuts and bolts. 30 31.000 34.38 38.00 3.63
6 1 ✕ 5¹⁄₂
138.0
750 787.4 873 965 92 62.6
Request 16.02. 33 36.000 39.38 44.25 5.13
6 1¹⁄₄ ✕ 5¹⁄₂
195.0
832 914.4 1000 1124 130 88.5
36 38.000 42.00 47.75 4.88 250.0
900 965.2 1067 1213 124 6 1¹⁄₂ ✕ 5³⁄₄ 113.4
60 63.500 67.38 74.00 5.00 455.0
1500 1612.9 1712 1880 127 10 1⁵⁄₈ ✕ 6 206.4

Style 41 Style 41 couplings are com- Y Z


Vic-Ring® monly used with Type “E”
Coupling Vic-Ring adapters and are
designed to provide a
strong component for use X
on steel pipe with applied
Vic-Ring adapters. Many
sizes may be used on pipe
with cast shoulders. 30 - 38" sizes

Style 41 Vic-Ring cou- 16.04-1B

plings are supplied with “E” Coupling Dimensions Bolt Dimensions Aprx.
or “T” gaskets. FlushSeal® Inches/mm Inches/mm Weight
Size Each
gaskets are available upon Inches Height Width Depth Lbs.
request. mm X Y Z No. Dia. ✕ Lgth. kg
30 36.25 40.25 5.00 178.0
All sizes are supplied 750 921 1022 127 6 1¹⁄₈ ✕ 5¹⁄₂ 80.7
painted with alkyd phenolic 36 42.50 46.50 5.00
6 1¹⁄₈ ✕ 5¹⁄₂
205.0
900 1080 1181 127 93.0
primer and with plated nuts
38 44.50 48.50 5.13 220.0
and bolts. 950 1130 1232 130 6 1¹⁄₄ ✕ 5¹⁄₂ 99.8
42 49.13 55.00 5.13 270.0
Request 16.04. 1050 1248 1397 130 8 1³⁄₈ ✕ 5³⁄₄ 122.5
46 52.25 58.75 5.38 330.0
1150 1327 1492 137 8 1¹⁄₂ ✕ 5³⁄₄ 149.7
48 55.63 62.00 5.25 390.0
1225 1413 1575 133 8 1⁵⁄₈ ✕ 6 176.9
54 62.25 69.50 5.38 470.0
1350 1581 1765 137 8 1³⁄₄ ✕ 6 213.2
60 68.63 76.00 5.50 570.0
1500 1743 1930 140 10 1⁷⁄₈ ✕ 6 258.6
66 74.88 81.00 6.88 750.0
1650 1902 2057 175 24 1¹⁄₂ ✕ 5³⁄₄ 340.2

13
Couplings

Style 44
16.05-1B
Vic-Ring® Coupling Dimensions Bolt Dimensions Aprx.
Coupling Inches/millimeters Inches/millimeters Weight
Size Each
Y Z Inches Height Width Depth Lbs.
mm X Y Z No. Dia. ✕ Lgth. kg
4 6.88 9.25 2.13 8.0
100 175 235 54 2 ⁵⁄₈ ✕ 4 3.6
X
6 9.13 11.50 2.25 11.0
150 232 292 57 2 ⁵⁄₈ ✕ 4 5.0
8 11.88 14.50 2.50 17.0
200 302 368 64 2 ³⁄₄ ✕ 5 7.7
4 - 12 sizes
10 14.13 16.75 2.69 23.0
2 ³⁄₄ ✕ 5
Style 44 couplings are 250 359 425 68 10.4
Y Z
designed with cross-ribbed 12 16.63 19.50 2.81 31.0
300 422 495 71 2 ⁷⁄₈ ✕ 5¹⁄₂ 14.1
construction to provide a 14 18.75 22.50 2.75 43.0
strong component for use 350 476 572 70 4 1 ✕ 3¹⁄₂ 19.5
on steel pipe with applied 16 21.00 25.25 3.50
4 1 ✕ 3¹⁄₂
63.0
X 400 533 641 89 28.6
Vic-Ring adapters. Many
18 24.25 28.00 3.69 85.0
sizes may be used on pipe 450 616 711 94 4 1 ✕ 3¹⁄₂ 38.6
with cast shoulders. 20 26.13 30.50 3.50 90.0
500 664 775 89 4 1¹⁄₄ ✕ 5¹⁄₂ 40.8
14 - 20" sizes Style 44 couplings are sup- 24 30.13 35.00 3.50 107.0
600 765 889 89 6 1¹⁄₄ ✕ 3¹⁄₂ 48.5
plied with “E” or “T” gas-
kets. FlushSeal® gaskets 30 37.63 43.00 5.19 225.0
750 956 1092 132 6 1¹⁄₂ ✕ 5³⁄₄ 102.1
Y Z
are available upon request. 36 44.25 50.00 5.13 270.0
900 1124 1270 130 6 1¹⁄₂ ✕ 5³⁄₄ 122.5
All sizes are supplied 42 50.63 57.50 5.25 380.0
painted with alkyd phenolic 1050 1286 1461 133 8 1³⁄₄ ✕ 6 172.4
X primer and with plated nuts 48 57.63 63.00 6.50 515.0
1200 1464 1600 165 16 1³⁄₈ ✕ 5³⁄₄ 233.6
and bolts. 54 64.50 70.50 6.88 615.0
1350 1638 1791 175 16 1¹⁄₂ ✕ 5³⁄₄ 279.0
Request 16.05. 60 71.25 77.00 6.88 688.0
1500 1810 1956 175 20 1¹⁄₂ ✕ 5³⁄₄ 312.1
24 - 36" sizes

Y Z Y Z
Style 31 Style 31 couplings are com-
Vic-Ring® monly used with Type “D”
Coupling or “E” Vic-Ring adapters
and are designed to provide X X
a strong component for use
on ductile iron pipe with
applied Vic-Ring adapters.
Many sizes may be used on 14 - 20" sizes 24 - 36" size
pipe with cast shoulders.
Style 31 Vic-Ring cou- 16.03-1B

plings are supplied with Coupling Dimensions Bolt Dimensions Aprx.


Inches/millimeters Inches/millimeters Weight
“M” or “S” FlushSeal® Size Each
gaskets. Inches Height Width Depth Lbs.
mm X Y Z No. Dia. ✕ Lgth. kg
All sizes are supplied 14 17.38 21.50 2.88 40.0
350 442 546 73 4 1 ✕ 3¹⁄₂ 18.1
painted with alkyd phenolic
primer and with plated nuts 18 22.25 26.50 3.50 73.0
450 565 673 89 4 1 ✕ 3¹⁄₂ 33.1
and bolts. 20 24.38 29.00 3.50 87.0
500 619 737 89 4 1¹⁄₈ ✕ 4 39.5
Request 16.03. 24 28.38 33.00 3.50 93.0
600 721 838 89 6 1¹⁄₈ ✕ 4 42.2
30 35.13 39.38 4.38 162.0
750 892 1001 111 6 1¹⁄₈ ✕ 4 73.5
36 41.38 46.00 4.50 200.0
900 1051 1168 114 6 1¹⁄₈ ✕ 4 90.7

14
Vic-Ring

Vic-Ring System Application Data


The adaptation of pipe with Vic-Ring adapters and the selection of a
suitable Victaulic coupling present individual considerations which can
best be screened by Victaulic engineers, who are experienced in Vic-Ring
end applications. Also, space limitation in this manual prevents a listing of
all Victaulic coupling patterns available for Vic-Ring adaptations.
Before proceeding with Vic-Ring end designs, submit to us a Vic-Ring
Application Data form which is part of Section 16.01, include: pipe O.D.,
pipe wall thickness, working pressure, laying conditions and the quantity of
Victaulic couplings required. We will be glad to recommend the type of Valve
ends, the collar dimensions, and the Victaulic coupling best suited to the Ring Body/
application. Pipe Shoulder Pipe

Please send completed information to your regional branch or the


Engineered Products Department at Victaulic World Headquarters.

SELECTION CHART 16.01-1B

Pipe Max. Work. Coupling Selection Pipe Max. Work. Coupling Selection
O.D. Press.* Size Vic-Ring O.D. Press.* Size Vic-Ring
In./mm PSI/kPa Inches/mm Style Type In./mm PSI/kPa Inches/mm Style Type
14 175 14 38 90 38
350 1207 350 31 D, E 950 620 950 41 D, E
16 200 17 42 175 42
400 1380 430 22 A 1050 1207 1050 44 D, E
16 175 16 42 90 42
400 1207 400 44 D, E 1050 620 1050 41 D, E
18 175 18 46 90 46
450 1207 450 31 D, E 1175 620 1175 41 D, E
20 200 20 48 175 48
500 1380 500 22 A 1200 1207 1200 44 D, E
20 175 20 48 90 48
500 1207 500 31 D, E 1200 620 1200 41 D, E
24 200 24 54 175 54
600 1380 600 22 A 1375 1207 1375 44 D, E
24 175 24 54 90 54
600 1207 600 31 D,E 1375 620 1375 41 D, E
30 175 30 60 175 60
750 1207 750 44 D, E 1525 1207 1525 44 D, E
30 150 30 60 90 60
750 1035 750 22 A 1525 620 1525 41 D, E
30 90 30 66 90 66
750 620 750 41 D, E 1675 620 1675 41 D, E
36 175 36
900 1207 900 44 D, E
For complete Vic-Ring adapter dimensions for the above selections, as well as Victaulic couplings data, refer to Sections 16.02 through 16.06. For coupling/ring combinations not
shown, or for other applications, contact Victaulic for details.
* Working Pressures are total, from all internal and external loads, based on ANSI standard weight steel pipe, with Vic-Rings applied in accordance with Victaulic specifications.
Contact Victaulic for performance on other pipe.

15
Gasket Data

Gasket Data
Unique “C” shaped gasket Seals between the pipe ends Surrounded, reinforced and Seal is enhanced by pressure
forms a triple seal and the groove slightly compressed by the housing of vacuum in the line

The sealing efficiency of The combination of these The Victaulic gasket design (250 mm) of mercury, the use of
Victaulic gaskets is such that the characteristics creates a seals equally well under vacuum. molded FlushSeal® gaskets or
gasket forms an initial seal as it permanent, leak-tight triple seal Vacuum creates a pressure standard gaskets with metal
is stretched over the pipe ends. on a variety of piping materials differential between the inside liners is recommended.
Upon placement of the housing including carbon steel, stainless and outside of the piping FlushSeal gaskets comprised of
around the gasket and into the steel, aluminum, PVC, cast iron system. The resulting increased standard gaskets with rubber
grooves, the gasket is and copper. force from external pressure filler strip inserts are not
positioned. As the housing Line pressure serves to differential has the same seal recommended for vacuum
segments are tightened, the strengthen the seal through the strengthening effect as internal services greater than 10"
resilient elastomeric gasket combination of normal gasket pressure. (250 mm) of mercury.
conforms to the internal cavity resilience, housing Due to the forces applied at the For more details about Victaulic
of the housing and is further reinforcement and the action of center of the gasket under gasket construction and testing,
compressed, enhancing the pressure downward on the lips. vacuum service greater than 10" request 05.01.
gasket’s seal against the pipe.
The Victaulic gasket is pressure
responsive.

Gasket To assure the maximum life for


the service intended, proper
Selection gasket selection and
specification in ordering is To assure maximum life for the service intended, proper gasket selection and specifi-
cation in ordering is essential.
essential.
Failure to select the proper rubber compound may result in personal injury or property
Many factors must be damage, improper installation, joint leakage or joint failure.
considered in determining the
optimum gasket for a specific Standard Gaskets – Large Diameter
service. The foremost Temp. Com- Color
consideration is temperature, Grade Range pound Code General Service Recommendations
along with concentration of Recommended for hot water service within the speci-
–30°F (–34°C) fied temperature range plus a variety of dilute acids,
product, duration of service and
continuity of service. E to
+230°F (+110°C)
EPDM
Green
Stripe oil-free air and many chemical services. UL classified
in accordance with ANSI/NSF 61 for potable water
service. Not recommended for petroleum services.
Temperatures beyond the
Recommended for petroleum products, air with oil
recommended limits have a –20°F (–29°C) vapors, vegetable and mineral oils within the specified
degrading effect on the gasket.
Therefore, there is a direct
T to
+180°F (+82°C)
Nitrile
Orange
Stripe temperature range. Not recommended for hot water
services over +150°F (+66°C) or for hot dry air over
+140°F (+60°C).
relationship between
temperature, continuity of
service and gasket life. Standard Gaskets – Style 31 Coupling only
Contact Victaulic for specific Temp. Com- Color
Grade Range pound Code General Service Recommendations
recommendations or assitance.
Recommended for water service within the speci-
fied temperature range plus a variety of dilute ac-
–20°F (–29°C) ids, oil-free air and many chemical services.
NOTE:
Services listed are General Service Rec-
M to
+200°F (+93°C)
Halogenated
Butyl
Brown
Stripe Readily conforms to ductile pipe surfaces. UL
classified in accordance with ANSI/NSF 61 for po-
table water service. Not recommended for petro-
ommendations only. It should be noted leum services.
that there are services for which these
Specially compounded to conform to ductile pipe
gaskets are NOT recommended. Refer- surfaces. Recommended for petroleum products,
ence should always be made to the latest –20°F (–29°C)
Victaulic Gasket Selection Guide for spe-
cific recommendations.
S to
+180°F (+82°C)
Nitrile
Red
Stripe
air with oil vapors, vegetable and mineral oils
within the specified temperature range. Not rec-
ommended for hot water services over +150°F
Gasket recommendations apply only to (+66°C) or for hot dry air over +140°F (+60°C).
Victaulic gaskets. Recommendations for
a particular service do not necessarily
imply compatibility of the coupling hous-
ing, related fittings or other components
for the same service.

16
Design Data

Design Considerations
piping runs that will experience accumulated growth (∆L) as the
The Victaulic large diameter piping method may be used for joining a
system is pressurized. Note also that thermal expansion of pipes will
variety of piping systems for a variety of services. It may be utilized for
add to the total movement in these cases.
varied pipe sizes, pipe materials and wall thickness. Large diameter
products are available to provide flexible systems.
As with any piping method, the nature of the method should be
considered in designing the piping systems. This design data applies Pressure Zero
primarily to grooved end pipe, however, much of the information ∆L
applies to other Victaulic mechanical piping products used in
conjunction with grooved components.
The material presented is intended solely for piping design reference Line Pressurized
in utilization of Victaulic products for their intended application. It is
not intended as a substitute for competent, professional assistance
which is an obvious requisite to any specific application. Recommended Pipe
Hanger/Support Spacing Maximum Hanger/
PRESSURE THRUST for Flexible Systems Support Spacing
When a flexible grooved type mechanical coupling is sustaining forces Requiring Maximum Not Requiring
trying to separate the pipe ends, the shoulder of the groove is pulled Linear Movement Linear Movement
1410-5A 1410-6A
hard against the inside face of the coupling key. This is what prevents
Pipe Length
the pipes from separating. Feet/Meters
Nom.
The allowable force which a joint can sustain varies for different types 9.8 19.7 29.5 39.4
Pipe Nom. Maximum
of couplings, pipe wall thickness, types of pipes and grooving. The Size 3 6 9 12
Pipe Size Span
product data under the column “Maximum End Load” shows the Inches Hangers Per Inches Feet
maximum allowable end force that the couplings will sustain. mm Above Length mm Meters
28 28 20
700 1 2 3 3 700 6.1
30 30 20
750 1 2 3 3 750 6.1
32 32 21
800 1 2 3 3 800 6.4
36 36 21
900 1 2 3 3 900 6.4
PT D PT
42 42 21
1050 1 2 3 3 1050 6.4

USE OF HANGERS AND SUPPORTS


The use of hangers and supports offering freedom of movement in one
or more directions has to be considered to allow pipes to move freely.
Spring hangers are good practice at change of direction to allow
freedom of pipe movement.
When this end force is due to a closed end or change in direction, the
pressure thrust transmitted by the joint can be computed from the
formula:

π 2
PT = --- D p Pump
4
Oscillation

ACCOMMODATING COUPLING FLEXIBILITY


Flexible grooved type couplings allow angular flexibility and rotational
movement to take place at joints. These features provide advantages
in installing and engineering piping systems, but must be considered
when determining hanger and support requirements.
Where:
PT = Pressure thrust or end load (lbs.)
D = Outside diameter of pipe (inches)
p = Internal pressure (PSI)
Sag Due to
PIPE LINE LINEAR MOVEMENT Flexibility
Pipe will be moved to the full extent of the available pipe end gap
when pressurized. Care must be taken to ensure that the resulting
movement of randomly installed systems is not harmful to joints at
changes in directions, at branch connections, or to parts of the Front Side
structure or other equipment. This is particularly important for long Elevation View

17
Design Data

As illustrated, it is obvious that this system would require further


hangers to eliminate the deflection of the pipes that would occur.
Hanger positions must therefore be considered in relation to the
angular and rotational movement that will occur at joints.
In the system illustrated, if the joints had all been installed butted or
only partially open when pressurized, the pipe ends would all move to
the maximum extent allowed by the coupling and this movement
would accumulate at the end of the system. The offset would have to
Θ
be capable of deflecting sufficiently, otherwise harmful bending
moments would be induced in the joints of the offset. Note, if the pipes Θ
were to expand due to thermal changes, then further growth of the
pipes would also take place at the ends. ANGULAR MOVEMENT TOLERANCE

ANCHORAGE AND SUPPORT 4" (100 mm) and larger – Reduce published figures by 25%
Standard cut grooved pipe will provide double the
expansion/contraction or deflection capabilities of the same
size standard roll groove pipe.

Θ = Maximum angular deflection between center lines as shown


under Performance.
= Anchor = Lateral Resistance The angular deflection available at a Victaulic flexible grooved pipe
joint is useful in simplifying and speeding installation.
Ensure anchorage and support is adequate. Use anchors to direct
movement away from or to protect critical changes in direction, NOTE: Joints which are fully deflected can no longer provide linear
branch connections and structure. Spacing and types of supports movement. Partially deflected joints will provide some portion of linear
should consider anticipated pipe movements. movement. NOTE: Pressure thrusts will tend to straighten deflected
pipe.
Consideration must be given to use of expansion joints if thermal
movement is expected. G
Y
The supporting of fittings (elbows, tees, etc.) in this size range will
depend on the weight (wall thickness) and position (orientation) of the
Θ
fittings within the system. Fittings and other concentrated loads
should be supported by an appropriate means in order to prevent the D
buildup of stresses at the coupling. As an example, a support in the L
center of the fitting will prevent the weight of the fitting and internal
fluid from being transferred to the adjacent couplings.
Y = L SIN Θ
RULES APPLICABLE TO LONG RUNS OF PIPE
For long pipe runs it is normal practice to anchor or block all changes Θ = SIN -1 G
D
of directions to prevent pressure thrusts from expanding flexible joints G ✕ L
and causing gross movement of the pipes. Intermediate anchors could Y=
D
prevent accumulation of end pull forces on the joints due to thermal
growth. Where changes in direction of piping inside a structure (e.g., Where:
pump house) can create pressure thrusts, a main anchor could be used Y = Misalignment (Inches)
to prevent pipe being pulled into the pump house. This anchor will
also prevent harmful thermal movement of pipe. G = Maximum Allowable Pipe End Movement (Inches) as shown
under Performance Data (Published value to be reduced be
Design Tolerance.)
Θ = Maximum Deflection (Degrees) from Center Line as shown
under Performance Data (Published value to be reduced by
Design Tolerance.)
D = Pipe Outside Diameter (Inches)
L = Pipe Length (Inches)

Where lines are likely to block or plug, joints and anchors (including
intermediate anchors) should be designed to withstand the
longitudinal pressure thrust or End Load created by the blockage.
ANGULAR DEFLECTIONS
Angular deflection available at flexible grooved pipe joints is
published under Performance Data for each Victaulic coupling style.
These values are MAXIMUMS. For design and installation purposes
these figures should be reduced by the following factors to allow for
pipe grooving tolerances (Refer to Sections 26.01 & 26.02 for more
details).

18
The Company

Quality, reliability,
and innovation since 1925
Victaulic Company is the originator and developer of the grooved piping method for rapidly
joining building service pipe. Victaulic has been used for many years for HVAC, plumbing,
fire protection and many specialized building service piping applications.
The Victaulic system has been approved, specified and used for building service piping by
GSA, VA, COE, NAVFAC and other federal agencies for many years. Applications include
chilled and hot water, condenser water, plumbing services, fire protection and general util-
ity services.
Victaulic has developed many products for the building market including two and three-
way actuated valves, flange adapters, rigid couplings and field pipe preparation too. Exten-
sive in-house product development and testing capabilities assure products designed and
manufactured for life-of-the-system reliability. Look to Victaulic for the finest pipe cou-
plings, fittings, valves and piping accessories.

Victaulic World Headquarters,


located in Easton, Pennsylvania,
includes state-of-the-art design,
integrated manufacturing,
finishing and testing, all on-site.

For questions, contact us on the Internet:


www.victaulic.com

19
www.victaulic.com
Customer Inquiries: pickvic@victaulic.com
Literature Requests: victaulic@victaulic.com
R

WORLD HEADQUARTERS
P.O. Box 31 • Easton, PA 18044-0031
4901 Kesslersville Road • Easton, PA, USA 18040
Phone: 610/559-3300 • FAX: 610/250-8817

CUSTOMER CARE CENTER


Phone: 1-800-PICK-VIC (1-800-742-5842) • e-mail: pickvic@victaulic.com

VICTAULIC COMPANY OF AMERICA


P.O. Box 31 • Easton, PA 18044-0031
Phone: 610/559-3300 • Fax: 610/250-8817
Fire Protection Division Victaulic Tool Company
Customer Care Centers P.O. Box 31 • Easton, PA 18044-0031
■ SOUTHEAST FIRE PROTECTION Phone: 610/559-3300 • Fax: 610/923-3090
Phone: 877/773-8322 • Fax: 877/776-9769
Victaulic Municipal Division
■ NORTHEAST FIRE PROTECTION 1818 Vultee Street • Allentown, PA 18103
Phone: 888/265-0805 • Fax: 888/265-0918 Phone: 610/923-3158 • Fax: 610/923-3166
■ CENTRAL FIRE PROTECTION
Phone: 888/448-3534 • Fax: 888/448-3595 Victaulic Construction Piping Services
■ WESTERN FIRE PROTECTION 1818 Vultee Street • Allentown, PA 18103
Phone: 877/487-7231 • Fax: 877/487-7232 Phone: 610/559-3488 • Fax: 610/923-3170

United States Distribution Centers


■ NEW ENGLAND/NEW YORK METRO ■ PERMIAN BASIN
4901 Kesslersville Road • Easton, PA 18040 2628 Remington Road • Odessa, TX 79763
Cust.Care: 800/742-5842 • Cust. Fax: 800/437-6573 Local Tel.: 915/332-1489 • Local Fax: 915/332-4924
■ SOUTHEAST ■ ROCKY MOUNTAIN
650 Coastline Drive • Yulee, FL 32097 5045 Paris Street • Denver, CO 80239
Cust.Care: 800/742-5842 • Cust. Fax: 888/201-3468 Cust.Care: 800/742-5842 • Cust. Fax: 888/448-3528
■ MIDWEST ■ PACIFIC - NORTH
730 Thomas Drive • Bensenville, IL 60106 22633 83rd Ave. So. • Kent, WA 98032
Cust.Care: 800/742-5842 • Cust. Fax: 888/265-2018 Cust.Care: 800/742-5842 • Cust. Fax: 888/448-3530
■ GREAT LAKES ■ MID-ATLANTIC
23107 Commerce Drive • Farmington Hills, MI 48335 4901 Kesslersville Road • Easton, PA 18040
Cust.Care: 800/742-5842 • Cust. Fax: 800/564-0119 Cust.Care: 800/742-5842 • Cust. Fax: 800/696-6447
■ CENTRAL STATES ■ PACIFIC - SOUTH
5900 Deramus Avenue • Kansas City, MO 64120 20934 So. Santa Fe Ave. • Long Beach, CA 90810
Cust.Care: 800/742-5842 • Cust. Fax: 888/448-3540 Cust.Care: 800/742-5842 • Cust. Fax: 800/448-3542
■ MID-CONTINENT
7177 Railspur Street • Houston, TX 77078
Cust.Care: 800/742-5842 • Cust. Fax: 888/448-3537

VICTAULIC COMPANY OF CANADA


65 Worcester Road • Rexdale, Ontario • Canada M9W 5N7
Phone: 416/675-5575 • FAX: 416/675-5565 • e-mail: viccanada@victaulic.com
Canadian Sales Offices and Service Centers
■ EASTERN ■ ONTARIO - SOUTH
975 rue Selkirk • Pointe Claire, QC H9R 4S4 65 Worcester Road • Rexdale, ON M9W 5N7
Phone: 514/426-3500 • FAX: 514/426-2818 Phone: 416/675-5575 • FAX: 416/675-5729
■ ONTARIO - NOR TH ■ WESTERN
1070 Elisabella Street • Sudbury, ON P3A 5K2 11659 180th Street NW • Edmonton, AB T5S 2H6
Phone: 705/560-9595 • FAX: 705/560-9490 Phone: 780/452-0680 • FAX: 780/452-2430
■ PACIFIC
Unit 5, 7560 Vantage Way • Delta, BC V4G 1H1
Phone: 604/940-3301 • FAX: 604/940-3360

VICTAULIC INTERNATIONAL VICTAULIC AMERICA LATINA


P.O. Box 31 • Easton, PA, USA 18044-0031 P.O. Box 31 • Easton, PA, USA 18044-0031
4901 Kesslersville Road • Easton, PA, USA 18040 4901 Kesslersville Road • Easton, PA, USA 18040
Phone: 610/559-3300 • FAX: 610/559-3608 Phone: 610/559-3300 • FAX: 610/559-3608
e-mail: vicintl@victaulic.com e-mail: vical@victaulic.com

VICTAULIC EUROPE VICTAULIC ASIA-PACIFIC


Prijkelstraat 36 541 Orchard Road, #14-02, Liat Towers
9810 Nazareth Belgium Singapore 238881
Phone: 011-32-93-811500 • FAX: 011-32-93-804438 Phone: 011-65-6235-3035 • FAX: 011-65-6235-0535

MB-010 1410 Rev.A 1/97 10MO