Sie sind auf Seite 1von 49

Test Object - Device Settings

. . .
Substation/Bay:
Substation: Substation address:
Bay: Bay address:
. . .
Device:
Name/description: REF615 -DOC/DEF RELAY Manufacturer: ABB
Device type: REF615 Device address:
Serial/model number: 1VHR91403212
Additional info 1:
Additional info 2:

Hardware Configuration
.
Test Equipment
Type Serial Number
CMC356 ??????
. .
Hardware Check
Performed At Result Details
Not yet performed

RELAY METERING CHECK:


. .
Test Module
Name: OMICRON Quick CMC Version: 3.20
Test Start: 21-Nov-2018 08:04:15 Test End: 21-Nov-2018 08:05:05
User Name: Manager:
Company:

Test Results
Title: Test 1
.

Page 1 of 49
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 63.51 V 0.00 ° 50.000 Hz
V L2-E 63.51 V -120.00 ° 50.000 Hz
V L3-E 63.51 V 120.00 ° 50.000 Hz
I L1 1.000 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 63.509V 0.00° +90°
I L3
V L3-E
V L1-EI L1
180° 0°
V L2-E
I L2
80.0 V -90° 1.0 A
V L2-E 63.509V -120.00°
V L3-E 63.509V 120.00°
I L1 1.000A 0.00°
I L2 1.000A -120.00°
I L3 1.000A 120.00°

Binary Inputs
Name Slope Time
Start 0
Trip 0
Overload 0

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

Pickup & Drop test:


Test Object - Overcurrent Parameters

General - Values:
TimeTolAbs: 0.04 s VT connection: At protected object
TimeTolRel: 5.00 % CT starpoint connection: From protected object
CurrentTolAbs: 0.05 Iref

Page 2 of 49
CurrentTolRel: 5.00 %
Directional: Yes

.
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes DOCR (67) IEC Normal Inverse 1.57 Iref 1.00 0.95 Forward
.
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No DIR EF IEC Normal Inverse 0.50 Iref 0.89 0.95 Forward

Test Module
Name: OMICRON Overcurrent Version: 3.20
Test Start: 21-Nov-2018 08:19:33 Test End: 21-Nov-2018 08:19:47
User Name: Manager:
Company:

Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0.000 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 240.0 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a

Binary Inputs:
Trigger Logic: And
Name Trigger State
Start 1
Trip X
.
Pick-up / Drop-off Test:
Type Angle Resolution I Pick-up Reset Ratio
nom min max nom
L1 120.00 ° 50.00 ms 1.570 A 1.495 A 1.653 A 950.0 m
L2 120.00 ° 50.00 ms 1.570 A 1.495 A 1.653 A 950.0 m
L3 120.00 ° 50.00 ms 1.570 A 1.495 A 1.653 A 950.0 m
.
Page 3 of 49
Pick-up / Drop-off Test Results:
Type Angle I Pick-up I Drop-off Reset Ratio Result
nom act act nom act Error
L1 120.00 ° 1.570 A 1.58 A 1.507 A 950.0 m 955.0 m 526.3 m % Passed
L2 120.00 ° 1.570 A 1.58 A 1.507 A 950.0 m 955.0 m 526.3 m % Passed
L3 120.00 ° 1.570 A 1.58 A 1.507 A 950.0 m 955.0 m 526.3 m % Passed
.
State:
3 out of 3 points tested.
3 points passed.
0 points failed.

General Assessment: Test passed!

Timing test:
Test Object - Overcurrent Parameters
.
General - Values:
TimeTolAbs: 0.04 s VT connection: At protected object
TimeTolRel: 5.00 % CT starpoint connection: From protected object
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: Yes

Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes DOCR (67) IEC Normal Inverse 1.57 Iref 1.00 0.95 Forward
.
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No DIR EF IEC Normal Inverse 0.50 Iref 0.89 0.95 Forward

Test Module
Name: OMICRON Overcurrent Version: 3.20
Test Start: 21-Nov-2018 08:22:15 Test End: 21-Nov-2018 08:23:41
User Name: Manager:
Company:

Test Settings:
.
Page 4 of 49
Fault Model:
Time reference: Fault inception
Load current: 0.000 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 15.00 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a

Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1 DOCR (67) 2.000 3.140 A 120.00 ° 10.03 s 8.897 s 11.38 s
L2 DOCR (67) 2.000 3.140 A 120.00 ° 10.03 s 8.897 s 11.38 s
L3 DOCR (67) 2.000 3.140 A 120.00 ° 10.03 s 8.897 s 11.38 s
L1 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 5.730 s 6.945 s
L2 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 5.730 s 6.945 s
L3 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 5.730 s 6.945 s
L1-L2 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 5.730 s 6.945 s
L2-L3 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 5.730 s 6.945 s
L3-L1 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 5.730 s 6.945 s
L1-L2-L3 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 5.730 s 6.945 s

Binary Inputs:
Trigger Logic: Or
Name Trigger State
Start X
Trip 1
.
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1 DOCR (67) 2.000 3.140 A 120.00 ° 10.03 s 10.08 s 488.3 m % No Passed
L2 DOCR (67) 2.000 3.140 A 120.00 ° 10.03 s 10.08 s 503.3 m % No Passed
L3 DOCR (67) 2.000 3.140 A 120.00 ° 10.03 s 10.08 s 500.3 m % No Passed

Page 5 of 49
L1 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 6.330 s 439.1 m % No Passed
L2 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 6.326 s 381.9 m % No Passed
L3 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 6.329 s 431.1 m % No Passed
L1-L2 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 6.329 s 434.3 m % No Passed
L2-L3 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 6.327 s 397.8 m % No Passed
L3-L1 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 6.328 s 420.0 m % No Passed
L1-L2-L3 DOCR (67) 3.000 4.710 A 120.00 ° 6.302 s 6.329 s 429.5 m % No Passed
.

Charts for Fault


Types:
Type Angle
L1 120.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 6 of 49
+90°

180° 0°

6.0 A -90°

Charts for Fault


Types:
Type Angle
L2 120.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 7 of 49
+90°

180° 0°

6.0 A -90°

Charts for Fault


Types:
Type Angle
L3 120.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 8 of 49
+90°

180° 0°

6.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2 120.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 9 of 49
+90°

180° 0°

6.0 A -90°

Charts for Fault


Types:
Type Angle
L2-L3 120.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 10 of 49
+90°

180° 0°

6.0 A -90°

Charts for Fault


Types:
Type Angle
L3-L1 120.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 11 of 49
+90°

180° 0°

6.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2-L3 120.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 12 of 49
+90°

180° 0°

6.0 A -90°

.
State:
10 out of 10 points tested.
10 points passed.
0 points failed.

General Assessment: Test passed!

DIRECTION TEST:
Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs: 0.04 s VT connection: At protected object
TimeTolRel: 5.00 % CT starpoint connection: From protected object
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: Yes

.
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes DOCR (67) IEC Normal Inverse 1.57 Iref 1.00 0.95 Forward
.
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No DIR EF IEC Normal Inverse 0.50 Iref 0.89 0.95 Forward

Test Module
Page 13 of 49
Name: OMICRON Overcurrent Version: 3.20
Test Start: 21-Nov-2018 08:23:55 Test End: 21-Nov-2018 08:25:02
User Name: Manager:
Company:

Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0.000 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 6.000 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a

Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2-L3 DOCR (67) 4.000 6.280 A 0.00 ° No trip No trip No trip
L1-L2-L3 DOCR (67) 4.000 6.280 A 50.00 ° No trip No trip No trip
L1-L2-L3 DOCR (67) 4.000 6.280 A 57.00 ° 4.980 s 4.568 s 5.432 s
L1-L2-L3 DOCR (67) 4.000 6.280 A 90.00 ° 4.980 s 4.568 s 5.432 s
L1-L2-L3 DOCR (67) 4.000 6.280 A 135.00 ° 4.980 s 4.568 s 5.432 s
L1-L2-L3 DOCR (67) 4.000 6.280 A 180.00 ° 4.980 s 4.568 s 5.432 s
L1-L2-L3 DOCR (67) 4.000 6.280 A 213.00 ° 4.980 s 4.568 s 5.432 s
L1-L2-L3 DOCR (67) 4.000 6.280 A 220.00 ° No trip No trip No trip
L1-L2-L3 DOCR (67) 4.000 6.280 A 270.00 ° No trip No trip No trip
L1-L2-L3 DOCR (67) 4.000 6.280 A -41.00 ° No trip No trip No trip

Binary Inputs:
Trigger Logic: Or
Name Trigger State
Start X
Trip 1
.
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2-L3 DOCR (67) 4.000 6.280 A 0.00 ° No trip No trip n/a No Passed
L1-L2-L3 DOCR (67) 4.000 6.280 A 50.00 ° No trip No trip n/a No Passed
L1-L2-L3 DOCR (67) 4.000 6.280 A 57.00 ° 4.980 s 5.006 s 525.0 m % No Passed

Page 14 of 49
L1-L2-L3 DOCR (67) 4.000 6.280 A 90.00 ° 4.980 s 5.004 s 488.9 m % No Passed
L1-L2-L3 DOCR (67) 4.000 6.280 A 135.00 ° 4.980 s 5.004 s 488.9 m % No Passed
L1-L2-L3 DOCR (67) 4.000 6.280 A 180.00 ° 4.980 s 5.004 s 492.9 m % No Passed
L1-L2-L3 DOCR (67) 4.000 6.280 A 213.00 ° 4.980 s 5.004 s 486.8 m % No Passed
L1-L2-L3 DOCR (67) 4.000 6.280 A 220.00 ° No trip No trip n/a No Passed
L1-L2-L3 DOCR (67) 4.000 6.280 A 270.00 ° No trip No trip n/a No Passed
L1-L2-L3 DOCR (67) 4.000 6.280 A -41.00 ° No trip No trip n/a No Passed
.

Charts for Fault


Types:
Type Angle
L1-L2-L3 0.00 °
10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

0.010 0.100 1.000 10.000


I/A

Page 15 of 49
+90°

180° 0°

7.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2-L3 50.00 °
10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

0.010 0.100 1.000 10.000


I/A

Page 16 of 49
+90°

180° 0°

7.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2-L3 57.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 17 of 49
+90°

180° 0°

7.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2-L3 90.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 18 of 49
+90°

180° 0°

7.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2-L3 135.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 19 of 49
+90°

180° 0°

7.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2-L3 180.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 20 of 49
+90°

180° 0°

7.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2-L3 213.00 °
10000

1000

100
t/s

10

2 3 5 7 10 20 30
I/A

Page 21 of 49
+90°

180° 0°

7.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2-L3 220.00 °
10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

0.010 0.100 1.000 10.000


I/A

Page 22 of 49
+90°

180° 0°

7.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2-L3 270.00 °
10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

0.010 0.100 1.000 10.000


I/A

Page 23 of 49
+90°

180° 0°

7.0 A -90°

Charts for Fault


Types:
Type Angle
L1-L2-L3 -41.00 °
10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

0.010 0.100 1.000 10.000


I/A

Page 24 of 49
+90°

180° 0°

7.0 A -90°

.
State:
10 out of 10 points tested.
10 points passed.
0 points failed.

General Assessment: Test passed!

Pickup & Drop test:


Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs: 0.04 s VT connection: At protected object
TimeTolRel: 5.00 % CT starpoint connection: From protected object
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: Yes

.
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No DOCR (67) IEC Normal Inverse 1.57 Iref 1.00 0.95 Forward
.
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes DIR EF IEC Normal Inverse 0.50 Iref 0.89 0.95 Forward

Test Module
Name: OMICRON Overcurrent Version: 3.20
Test Start: 21-Nov-2018 08:29:22 Test End: 21-Nov-2018 08:29:36

Page 25 of 49
User Name: Manager:
Company:
Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0.000 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 8.000 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a

Binary Inputs:
Trigger Logic: Or
Name Trigger State
Start 1
Trip X
.
Pick-up / Drop-off Test:
Type Angle Resolution I Pick-up Reset Ratio
nom min max nom
L1-E 180.00 ° 50.00 ms 500.0 mA 450.0 mA 550.0 mA 950.0 m
L2-E 180.00 ° 50.00 ms 500.0 mA 450.0 mA 550.0 mA 950.0 m
L3-E 180.00 ° 50.00 ms 500.0 mA 450.0 mA 550.0 mA 950.0 m
.
Pick-up / Drop-off Test Results:
Type Angle I Pick-up I Drop-off Reset Ratio Result
nom act act nom act Error
L1-E 180.00 ° 500.0 m A 0.51 A 475.0 m A 950.0 m 940.6 m -990.1 m Passed
%
L2-E 180.00 ° 500.0 m A 0.51 A 480.0 m A 950.0 m 950.5 m 52.11 m % Passed
L3-E 180.00 ° 500.0 m A 0.51 A 480.0 m A 950.0 m 941.2 m -928.8 m Passed
%
.
State:
3 out of 3 points tested.
3 points passed.
0 points failed.

General Assessment: Test passed!

Page 26 of 49
Timing test:
Test Object - Overcurrent Parameters
.
General - Values:
TimeTolAbs: 0.04 s VT connection: At protected object
TimeTolRel: 5.00 % CT starpoint connection: From protected object
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: Yes

Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No DOCR (67) IEC Normal Inverse 1.57 Iref 1.00 0.95 Forward
.
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes DIR EF IEC Normal Inverse 0.50 Iref 0.89 0.95 Forward

Test Module
Name: OMICRON Overcurrent Version: 3.20
Test Start: 21-Nov-2018 08:30:12 Test End: 21-Nov-2018 08:30:55
User Name: Manager:
Company:

Test Settings:
.
Fault Model:
Time reference: Fault inception
Load current: 0.000 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 8.000 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms

Page 27 of 49
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a

Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-E DIR EF 2.400 1.200 A -156.00 ° 7.054 s 6.345 s 7.872 s
L2-E DIR EF 2.400 1.200 A -156.00 ° 7.054 s 6.345 s 7.872 s
L3-E DIR EF 2.400 1.200 A -156.00 ° 7.054 s 6.345 s 7.872 s
L1-E DIR EF 4.000 2.000 A -156.00 ° 4.432 s 4.065 s 4.835 s
L2-E DIR EF 4.000 2.000 A -156.00 ° 4.432 s 4.065 s 4.835 s
L3-E DIR EF 4.000 2.000 A -156.00 ° 4.432 s 4.065 s 4.835 s

Binary Inputs:
Trigger Logic: Or
Name Trigger State
Start X
Trip 1
.
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-E DIR EF 2.400 1.200 A -156.00 ° 7.054 s 7.112 s 814.1 m % No Passed
L2-E DIR EF 2.400 1.200 A -156.00 ° 7.054 s 7.115 s 866.6 m % No Passed
L3-E DIR EF 2.400 1.200 A -156.00 ° 7.054 s 7.111 s 805.6 m % No Passed
L1-E DIR EF 4.000 2.000 A -156.00 ° 4.432 s 4.461 s 652.5 m % No Passed
L2-E DIR EF 4.000 2.000 A -156.00 ° 4.432 s 4.464 s 717.9 m % No Passed
L3-E DIR EF 4.000 2.000 A -156.00 ° 4.432 s 4.463 s 697.6 m % No Passed
.

Page 28 of 49
Charts for Fault
Types:
Type Angle
L1-E -156.00 °
10000.0

1000.0

100.0
t/s

10.0

1.0
0.5 0.7 1.0 2.0 3.0 5.0 7.0
I/A

+90°

180° 0°

3.0 A -90°

Page 29 of 49
Charts for Fault
Types:
Type Angle
L2-E -156.00 °
10000.0

1000.0

100.0
t/s

10.0

1.0
0.5 0.7 1.0 2.0 3.0 5.0 7.0
I/A

+90°

180° 0°

3.0 A -90°

Page 30 of 49
Charts for Fault
Types:
Type Angle
L3-E -156.00 °
10000.0

1000.0

100.0
t/s

10.0

1.0
0.5 0.7 1.0 2.0 3.0 5.0 7.0
I/A

+90°

180° 0°

3.0 A -90°

.
State:
6 out of 6 points tested.
6 points passed.
0 points failed.

General Assessment: Test passed!

Page 31 of 49
Direction test:
Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs: 0.04 s VT connection: At protected object
TimeTolRel: 5.00 % CT starpoint connection: From protected object
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: Yes

.
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
No DOCR (67) IEC Normal Inverse 1.57 Iref 1.00 0.95 Forward
.
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes DIR EF IEC Normal Inverse 0.50 Iref 0.89 0.95 Forward

Test Module
Name: OMICRON Overcurrent Version: 3.20
Test Start: 21-Nov-2018 08:31:15 Test End: 21-Nov-2018 08:32:19
User Name: Manager:
Company:

Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0.000 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 6.000 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a

Shot Test:
Page 32 of 49
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-E DIR EF 4.000 2.000 A 0.00 ° No trip No trip No trip
L1-E DIR EF 4.000 2.000 A 60.00 ° No trip No trip No trip
L1-E DIR EF 4.000 2.000 A 90.00 ° No trip No trip No trip
L1-E DIR EF 4.000 2.000 A 109.00 ° 4.432 s 4.065 s 4.835 s
L1-E DIR EF 4.000 2.000 A 145.00 ° 4.432 s 4.065 s 4.835 s
L1-E DIR EF 4.000 2.000 A -178.00 ° 4.432 s 4.065 s 4.835 s
L1-E DIR EF 4.000 2.000 A -139.00 ° 4.432 s 4.065 s 4.835 s
L1-E DIR EF 4.000 2.000 A -110.00 ° 4.432 s 4.065 s 4.835 s
L1-E DIR EF 4.000 2.000 A -58.00 ° No trip No trip No trip
L1-E DIR EF 4.000 2.000 A -29.00 ° No trip No trip No trip

Binary Inputs:
Trigger Logic: Or
Name Trigger State
Start X
Trip 1
.
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-E DIR EF 4.000 2.000 A 0.00 ° No trip No trip n/a No Passed
L1-E DIR EF 4.000 2.000 A 60.00 ° No trip No trip n/a No Passed
L1-E DIR EF 4.000 2.000 A 90.00 ° No trip No trip n/a No Passed
L1-E DIR EF 4.000 2.000 A 109.00 ° 4.432 s 4.463 s 690.8 m % No Passed
L1-E DIR EF 4.000 2.000 A 145.00 ° 4.432 s 4.461 s 648.0 m % No Passed
L1-E DIR EF 4.000 2.000 A -178.00 ° 4.432 s 4.463 s 704.4 m % No Passed
L1-E DIR EF 4.000 2.000 A -139.00 ° 4.432 s 4.463 s 690.8 m % No Passed
L1-E DIR EF 4.000 2.000 A -110.00 ° 4.432 s 4.464 s 726.9 m % No Passed
L1-E DIR EF 4.000 2.000 A -58.00 ° No trip No trip n/a No Passed
L1-E DIR EF 4.000 2.000 A -29.00 ° No trip No trip n/a No Passed
.

Charts for Fault


Types:
Type Angle
L1-E 0.00 °

Page 33 of 49
10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

0.010 0.100 1.000 10.000


I/A

+90°

180° 0°

3.0 A -90°

Charts for Fault


Types:
Type Angle
L1-E 60.00 °

Page 34 of 49
10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

0.010 0.100 1.000 10.000


I/A

+90°

180° 0°

3.0 A -90°

Charts for Fault


Types:
Type Angle
L1-E 90.00 °

Page 35 of 49
10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

0.010 0.100 1.000 10.000


I/A

+90°

180° 0°

3.0 A -90°

Charts for Fault


Types:
Type Angle
L1-E 109.00 °

Page 36 of 49
10000.0

1000.0

100.0
t/s

10.0

1.0
0.5 0.7 1.0 2.0 3.0 5.0 7.0
I/A

+90°

180° 0°

3.0 A -90°

Charts for Fault


Types:
Type Angle
L1-E 145.00 °

Page 37 of 49
10000.0

1000.0

100.0
t/s

10.0

1.0
0.5 0.7 1.0 2.0 3.0 5.0 7.0
I/A

+90°

180° 0°

3.0 A -90°

Charts for Fault


Types:
Type Angle
L1-E -178.00 °

Page 38 of 49
10000.0

1000.0

100.0
t/s

10.0

1.0
0.5 0.7 1.0 2.0 3.0 5.0 7.0
I/A

+90°

180° 0°

3.0 A -90°

Charts for Fault


Types:
Type Angle
L1-E -139.00 °

Page 39 of 49
10000.0

1000.0

100.0
t/s

10.0

1.0
0.5 0.7 1.0 2.0 3.0 5.0 7.0
I/A

+90°

180° 0°

3.0 A -90°

Charts for Fault


Types:
Type Angle
L1-E -110.00 °

Page 40 of 49
10000.0

1000.0

100.0
t/s

10.0

1.0
0.5 0.7 1.0 2.0 3.0 5.0 7.0
I/A

+90°

180° 0°

3.0 A -90°

Charts for Fault


Types:
Type Angle
L1-E -58.00 °

Page 41 of 49
10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

0.010 0.100 1.000 10.000


I/A

+90°

180° 0°

3.0 A -90°

Charts for Fault


Types:
Type Angle
L1-E -29.00 °

Page 42 of 49
10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

0.010 0.100 1.000 10.000


I/A

+90°

180° 0°

3.0 A -90°

.
State:
10 out of 10 points tested.
10 points passed.
0 points failed.

General Assessment: Test passed!

Hardware Configuration 2
.
Test Equipment
Type Serial Number
CMC356 MC672V
. .
Hardware Check
Performed At Result Details

Page 43 of 49
11/21/2018 8:37:42 AM Passed

RYB-ph UV Pickup & Drop:

Test Settings
.
General
No. of ramp states: 2
Total steps per test: 1302
Total time per test: 130.200
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
V L1-E, L2-E, L3-E / Magnitude

.
Ramp States
Ramp Ramp 1 Ramp 2
V L1-E 64.50 V 45.00 V
0.00 ° 0.00 °
50.000 Hz 50.000 Hz
V L2-E 64.50 V 45.00 V
-120.00 ° -120.00 °
50.000 Hz 50.000 Hz
V L3-E 64.50 V 45.00 V
120.00 ° 120.00 °
50.000 Hz 50.000 Hz
Force abs. Phases No No

Page 44 of 49
Sig 1 From 64.50 V 45.00 V
Sig 1 To 45.00 V 64.50 V
Sig 1 Delta -30.00 mV 30.00 mV
Sig 1 d/dt -300.0 mV/s 300.0 mV/s
dt per Step 100.0 ms 100.0 ms
Ramp Steps 651 651
Ramp Time 65.100s 65.100s
Trigger Bin Bin
Trigger Logic AND AND
Start 1 0
Trip X X
Step back No No
Delay Time 0.000 s 0.000 s

. .
Test Module
Name: OMICRON Ramping Version: 3.20
Test Start: 21-Nov-2018 08:37:51 Test End: 21-Nov-2018 08:38:45
User Name: Manager:
Company:

Test Results
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick up Ramp 1 Start 0->1 V L1-E, 50.80 V 50.82 V 1.200 V 1.200 V 20.00 mV + 73.10 ms
L2-E, L3-
E
Drop Ramp 2 Start 1->0 V L1-E, 53.34 V 52.86 V 1.200 V 1.200 V -480.0 mV + 51.20 ms
L2-E, L3-
E
Assess: + .. Passed x .. Failed o .. Not assessed

Assessment Statistics
Name Ramp Condition Sig Nom. Act.Av. min max Std. Dev. Assess
Assess: + .. Passed x .. Failed o .. Not assessed

Calculation Results
Name/ Exec. Calc. X Y Nom. Act. Tol.- Tol.+ Dev. Assess
Drop-off/Pick-upX/Y Drop Drop 1.000 o
X/Y Drop Drop 1.000 o
X/Y Drop Drop 1.000 o
X/Y Drop Drop 1.000 o
X/Y Drop Drop 1.000 o
X/Y Drop Drop 1.000 o
X/Y Drop Drop 1.000 o
X/Y Drop Drop 1.000 o
X/Y Drop Drop 1.000 o
X/Y Drop Drop 1.000 o
Assess: + .. Passed x .. Failed o .. Not assessed

Calculation Statistics
Name Calc. X Y Nom. Act.Av. min max Std. Dev. Assess
Assess: + .. Passed x .. Failed o .. Not assessed

Page 45 of 49
Ramp 1 Ramp 2

Sig 1/V
63
62
61
60
59
58
57
56
55
54
53
52 t/s
5 10 15 20 25 30 35 40 45
51

V L1-E, L2-E, L3-E

Start
Trip

5 10 15 20 25 30 35 40 45
t/s

Cursor Data
Time Signal Value
Cursor 1 133.0 ms <none> n/a
Cursor 2 102.1 ms <none> n/a
C2 - C1 -30.90 ms n/a

Test State:
Test passed

RYB-ph UV Timing test:


.
Test Settings
State State 1 State 2
V L1-E 63.51 V 45.00 V
0.00 ° 0.00 °
50.000 Hz 50.000 Hz

Page 46 of 49
V L2-E 63.51 V 45.00 V
-120.00 ° -120.00 °
50.000 Hz 50.000 Hz
V L3-E 63.51 V 45.00 V
120.00 ° 120.00 °
50.000 Hz 50.000 Hz
Max. State Time 5.000 s 5.000 s
Trigger Logic OR
Trip 1
User interaction no no
CMGPS trigger no no
IRIG-B/PTP trigger no no
Pulses / seconds 1 1
Delay after Tr. 0.000 s 0.000 s
On trigger jump to no no
test end
Diagrams +90° +90°

180° 0° 180° 0°

230.9
-90°V 230.9
-90°V

Comment

Test Module .
Name: OMICRON State Sequencer Version: 3.20
Test Start: 21-Nov-2018 08:43:04 Test End: 21-Nov-2018 08:43:12
User Name: Manager:

Test Results
.
Time Assessment
Name Ignore Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
UV Time State 2 State 2 Trip 0>1 1.000 s 83.00 ms 83.00 ms 1.016 s 15.90 ms +
test
Assess: + .. Passed x .. Failed o .. Not assessed

State 1
State 2

Page 47 of 49
CMC356 V A/V
80
60
40
20
0
-20 1.0 2.0 3.0 4.0 5.0
t/s
-40
-60
-80

V L1-E V L2-E V L3-E

Trip

1.0 2.0 3.0 4.0 5.0


t/s

Cursor Data
Time Signal Value
Cursor 1 0.000 s <none> n/a
Cursor 2 6.016 s <none> n/a
C2 - C1 6.016 s n/a

.
Event recorder
Time Type Signal name Slope
6.016 s Input Trip 0>1

.
Test State:
Test passed

Page 48 of 49
Page 49 of 49

Das könnte Ihnen auch gefallen