Sie sind auf Seite 1von 13

TIN 33251085384 DURGA SWITCHGEARS

A-Grade Contractors EA 2616


CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: Page 4A
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : durgaswitchgears@yahoo.co.in

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051
Date of test: 20th March 2012
TEST REPORT FOR HT BREAKER
TO,
Breaker Sl. No. 03906102009
Breaker Make SYSTEM CONTROL
Type SYSVAC 36125025
Rating 1250 Amps
Uv 33 KV
TITLE MAIN INCOMER

Aranvoyal,
Tiruvallur dt. M/S Goms Electricals(P) Ltd.,
DESCRIPTION Site: M/S Chennai
TYPE OFBreweries
CHECK Pvt. Ltd.,
CHECKED
S.NO. REMARKS

1 PHYSICAL INSPECTION VISUAL FOR DAMAGE OK

2 INSTALLATION/CONNECTION VISUAL/MECHANICAL FOR OK


CORRECTNESS
3 OPERATIONS
a) Manual Spring charging MECHANICAL CORRECTNESS OK
Closing / Tripping

b) Normal Closing/Tripping MECHANICAL CORRECTNESS OK

FOR
c) Tripping through RELAY ELECTRICAL PERFORMANCE OK

d) Spring Charging Motor ELECTRICAL FOR OK


PERFORMANCE

e) Closing ELECTRICAL FOR OK


PERFORMANCE

f) Opening ELECTRICAL FOR OK


PERFORMANCE
4 CONTACT PENETRATION FOR VISUAL FOR ABNORMALITY OK
VCB
5 INSULATION RESISTANCE VCB CLOSED VCB OPEN
CONDITION CONDITION

R-E > 3500 MΩ R I/C – R O/G


Y-E > 3500 MΩ  3000 M Ω
B-E > 3500 MΩ Y I/C – Y O/
R-Y > 5000 MΩ  3500 M Ω
Y-B > 4800 MΩ B I/C – B O/G
B-R > 4500 MΩ  3000 M Ω
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: Page 4B
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : durgaswitchgears@yahoo.co.in

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051

Date of test: 20th March 2012

TEST REPORT FOR HT BREAKER


TO,
Aranvoyal, Breaker Sl. No. 03906102009
Tiruvallur dt. M/S Goms Electricals(p) Ltd.,
Breaker Make SYSTEM CONTROL
Site: M/S Chennai Breweries Pvt. Ltd.,SYSVAC 36125025
Type
Rating 1250 Amps
Uv 33 KV
TITLE MAIN INCOMER

2) Contact Resistance Test:-

Phase Ref DC Current DC Volts Resistance


Applied Across
Terminal
R-Phase 100 Amps 3.6 mv 36 Micro
Ohms
Y-Phase 100 Amps 3.7 mv 37 Micro
Ohms
B-Phase 100 Amps 3.7 mv 37 Micro
Ohms

3) Breaker Timing Test:-

Ref Closing Opening


Time in milli Time in milli
secs. secs
R-Phase 173 73
Y-Phase 175 70
B-Phase 174 72

TIN 33251085384 DURGA SWITCHGEARS


A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: Page 5A
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : durgaswitchgears@yahoo.co.in

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051

Date of test: 20th March 2012


TEST REPORT FOR HT BREAKER

To Breaker Sl. No. 1291


Aranvoyal, Breaker Make Siemens
Tiruvallur dt. M/S Goms Electricals(p) Ltd.,
Type 3AF 0143
Site: M/S Chennai Breweries Pvt. Ltd.,
Rating 1600 Amps
Uv 36 KV
TITLE Tie Incomer
TYPE OF CHECK CHECKED
S.NO. DESCRIPTION REMARKS

1 PHYSICAL INSPECTION VISUAL FOR DAMAGE OK

2 INSTALLATION/CONNECTION VISUAL/MECHANICAL FOR OK


CORRECTNESS
3 OPERATIONS
a) Manual Spring charging MECHANICAL CORRECTNESS OK
Closing / Tripping

b) Normal Closing/Tripping MECHANICAL CORRECTNESS OK

FOR
c) Tripping through RELAY ELECTRICAL PERFORMANCE OK

d) Spring Charging Motor ELECTRICAL FOR OK


PERFORMANCE

e) Closing ELECTRICAL FOR OK


PERFORMANCE

f) Opening ELECTRICAL FOR OK


PERFORMANCE
4 CONTACT PENETRATION FOR
VCB VISUAL FOR ABNORMALITY

5 INSULATION RESISTANCE VCB CLOSED VCB OPEN


CONDITION CONDITION
R-E > 4500 MΩ R I/C – R O/G
Y-E > 5000 MΩ  3000 M Ω
B-E > 4000 MΩ Y I/C – Y O/
R-Y > 4000 MΩ  3000 M Ω
Y-B > 4500 MΩ B I/C – B O/G
B-R > 4500 MΩ  3000 M Ω
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: Page 5B
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : durgaswitchgears@yahoo.co.in

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051

Date of test: 20th March 2012


TEST REPORT FOR HT BREAKER

To Breaker Sl. No. 1291


Aranvoyal, Breaker Make Siemens
Tiruvallur dt. M/S Goms Electricals(p) Ltd.,
Type 3AF 0143
Site: M/S Chennai Breweries Pvt. Ltd.,
Rating 1600 Amps
Uv 36 KV
2) Contact Resistance Test:- TITLE Tie Incomer

Phase Ref DC Current DC Volts Resistance


Applied Across
Terminal
R-Phase 100 Amps 4.3 mv 43 Micro
Ohms
Y-Phase 100 Amps 4.3 mv 43 Micro
Ohms
B-Phase 100 Amps 4.2 mv 42 Micro
Ohms

3) Breaker Timing Test:-

Ref Closing Opening


Time in milli Time in milli
secs. secs
R-Phase 175 68
Y-Phase 174 67
B-Phase 176 66
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: Page 6A
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : durgaswitchgears@yahoo.co.in

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051

Date of test: 20th March 2012


TEST REPORT FOR HT BREAKER

To Breaker Sl. No. 1292


Aranvoyal, Breaker Make Siemens
Tiruvallur dt. M/S Goms Electricals(p) Ltd.,
Type 3AF 0143
Site: M/S Chennai Breweries Pvt. Ltd.,
Rating 1600 Amps
Uv 36 KV
TITLE TR. 1 Outgoing
TYPE OF CHECK CHECKED
S.NO. DESCRIPTION REMARKS

1 PHYSICAL INSPECTION VISUAL FOR DAMAGE OK

2 INSTALLATION/CONNECTION VISUAL/MECHANICAL FOR OK


CORRECTNESS
3 OPERATIONS
a) Manual Spring charging MECHANICAL CORRECTNESS OK
Closing / Tripping

b) Normal Closing/Tripping MECHANICAL CORRECTNESS OK

FOR
c) Tripping through RELAY ELECTRICAL PERFORMANCE OK

d) Spring Charging Motor ELECTRICAL FOR OK


PERFORMANCE

e) Closing ELECTRICAL FOR OK


PERFORMANCE

f) Opening ELECTRICAL FOR OK


PERFORMANCE
4 CONTACT PENETRATION FOR VISUAL FOR ABNORMALITY
VCB
VCB CLOSED VCB OPEN
INSULATION RESISTANCE CONDITION CONDITION
5
R-E > 3500 MΩ R I/C – R O/G
Y-E > 3500 MΩ  3500 M Ω
B-E > 3000 MΩ Y I/C – Y O/
R-Y > 5000 MΩ  3500 M Ω
Y-B > 5000 MΩ B I/C – B O/G
B-R > 5000 MΩ  3500 M Ω
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: Page 6B
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : durgaswitchgears@yahoo.co.in

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051

Date of test: 20th March 2012


TEST REPORT FOR HT BREAKER

To Breaker Sl. No. 1292


Aranvoyal, Breaker Make Siemens
Tiruvallur dt. M/S Goms Electricals(p) Ltd.,
Type 3AF 0143
Site: M/S Chennai Breweries Pvt. Ltd.,
Rating 1600 Amps
Uv 36 KV
2) Contact Resistance Test:- TITLE TR. 1 Outgoing

Phase Ref DC Current DC Volts Resistance


Applied Across
Terminal
R-Phase 100 Amps 4.1 mv 41 Micro
Ohms
Y-Phase 100 Amps 4.2 mv 42 Micro
Ohms
B-Phase 100 Amps 4.4 mv 44 Micro
Ohms

4) Breaker Timing Test:-

Ref Closing Opening


Time in milli Time in milli
secs. secs
R-Phase 175 73
Y-Phase 174 75
B-Phase 179 73

TIN 33251085384 DURGA SWITCHGEARS


A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: Page 7A
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : durgaswitchgears@yahoo.co.in

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051

Date of test: 20th March 2012


TEST REPORT FOR HT BREAKER

To Breaker Sl. No. 1293


Aranvoyal, Breaker Make Siemens
Tiruvallur dt. M/S Goms Electricals(p) Ltd.,
Type 3AF 0143
Site: M/S Chennai Breweries Pvt. Ltd.,
Rating 1600 Amps
Uv 36 KV
TITLE TR. 2 Outgoing
TYPE OF CHECK CHECKED
S.NO. DESCRIPTION REMARKS

1 PHYSICAL INSPECTION VISUAL FOR DAMAGE OK

2 INSTALLATION/CONNECTION VISUAL/MECHANICAL FOR OK


CORRECTNESS
3 OPERATIONS
a) Manual Spring charging MECHANICAL CORRECTNESS OK
Closing / Tripping

b) Normal Closing/Tripping MECHANICAL CORRECTNESS OK

FOR
c) Tripping through RELAY ELECTRICAL PERFORMANCE OK

d) Spring Charging Motor ELECTRICAL FOR OK


PERFORMANCE

e) Closing ELECTRICAL FOR OK


PERFORMANCE

f) Opening ELECTRICAL FOR OK


PERFORMANCE
4 CONTACT PENETRATION FOR VISUAL FOR ABNORMALITY
VCB

VCB CLOSED VCB OPEN


5 INSULATION RESISTANCE CONDITION CONDITION
R-E > 4500 MΩ R I/C – R O/G
Y-E > 4500 MΩ  3500 M Ω
B-E > 3500 MΩ Y I/C – Y O/
R-Y > 5000 MΩ  3500 M Ω
Y-B > 5000 MΩ B I/C – B O/G
B-R > 5000 MΩ  3500 M Ω

TIN 33251085384 DURGA SWITCHGEARS


A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: Page 7B
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : durgaswitchgears@yahoo.co.in

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051

Date of test: 20th March 2012


TEST REPORT FOR HT BREAKER

To Breaker Sl. No. 1293


Aranvoyal, Breaker Make Siemens
Tiruvallur dt. M/S Goms Electricals(p) Ltd.,
Type 3AF 0143
Site: M/S Chennai Breweries Pvt. Ltd.,
Rating 1600 Amps
Uv 36 KV
TITLE TR. 2 Outgoing

2) Contact Resistance Test:-

Phase Ref DC Current DC Volts Resistance


Applied Across
Terminal
R-Phase 100 Amps 4.4 mv 44 Micro
Ohms
Y-Phase 100 Amps 4.3 mv 43 Micro
Ohms
B-Phase 100 Amps 3.9 mv 39 Micro
Ohms

3) Breaker Timing Test:-

Ref Closing Opening


Time in milli Time in milli
secs. secs
R-Phase 171 73
Y-Phase 172 74
B-Phase 174 75

TIN 33251085384 DURGA SWITCHGEARS


A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: Page 8A
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : durgaswitchgears@yahoo.co.in

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051

Date of test: 20th March 2012


TEST REPORT FOR HT BREAKER
TO
Breaker Sl. No. N8 36T / 919
Breaker Make SIEMENS
Type 3AF0142
Rating 630 Amps
Uv 33 KV
TITLE Tr. 3 - Outgoing

Aranvoyal,
Tiruvallur dt. M/S Goms Electricals(p) Ltd.,
Site: M/S Chennai Breweries Pvt. Ltd.,

TYPE OF CHECK
S.NO. DESCRIPTION CHECKED REMARKS

1 PHYSICAL INSPECTION VISUAL FOR DAMAGE OK

2 INSTALLATION/CONNECTION VISUAL/MECHANICAL FOR OK


CORRECTNESS
3 OPERATIONS
a) Manual Spring charging MECHANICAL CORRECTNESS OK
Closing / Tripping

b) Normal Closing/Tripping MECHANICAL CORRECTNESS OK

FOR
c) Tripping through RELAY ELECTRICAL PERFORMANCE OK

d) Spring Charging Motor ELECTRICAL FOR OK


PERFORMANCE

e) Closing ELECTRICAL FOR OK


PERFORMANCE

f) Opening ELECTRICAL FOR OK


PERFORMANCE
4 CONTACT PENETRATION FOR VISUAL FOR ABNORMALITY OK
VCB

VCB CLOSED VCB OPEN


5 INSULATION RESISTANCE CONDITION CONDITION
R-E > 3000 MΩ R I/C – R O/G
Y-E > 3000 MΩ  4000 M Ω
B-E > 3000 MΩ Y I/C – Y O/
R-Y > 5000 MΩ  4000 M Ω
Y-B > 5000 MΩ B I/C – B O/G
B-R > 5000 MΩ  4000 M Ω
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: Page 8B
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : durgaswitchgears@yahoo.co.in

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051

Date of test: 20th March 2012


TEST REPORT FOR HT BREAKER
TO,
Aranvoyal, Breaker Sl. No. N8 36T / 919
Tiruvallur dt. M/S Goms Electricals(p) Ltd.,
Breaker Make SIEMENS
Site: M/S Chennai Breweries Pvt. Ltd.,3AF0142
Type
Rating 630 Amps
Uv 33 KV
TITLE Tr. 3 - Outgoing

2) Contact Resistance Test:-

Phase Ref DC Current DC Volts Contact


Applied Across Resistance
Terminal
R-Phase 100 Amps 4.4 mv 44 Micro
Ohms
Y-Phase 100 Amps 4.5 mv 45 Micro
Ohms
B-Phase 100 Amps 4.4 mv 44 Micro
Ohms

3) Breaker Timing Test:-

Ref Closing Opening


Time in milli Time in milli
secs. secs
R-Phase 155 71
Y-Phase 154 72
B-Phase 156 70
HT VACUUM CIRCUIT BREAKERS
TEST REPORT FOR THE MAINTENANCE TESTING OF

TRANSFORMER OIL

&

HT VACUUM CIRCUIT BREAKERS

AT

M/S CHENNAI BREWERIES PVT. LTD.,

ARANVOYAL VILLAGE

TIRUVALLUR – 602 025.

FOR:-

M/S Goms Electricals (p) Ltd.,

CHENNAI

Job Carried out by: DURGA SWITCHGEARS


EA 2616 A-Grade Contractors
No. 8/5, John Vasu Street,
Madhavaram Milk Colony,
Chennai – 600 051.

Das könnte Ihnen auch gefallen