Beruflich Dokumente
Kultur Dokumente
1 Material Specifications
2 Material Certification
Flanges shall conform to ASME B16.1, Class 125. Gaskets shall be non-asbestos compressed material in
accordance with ASME B16.21, 1.59 mm (1/16 inch) thickness, full face or self-centring flat ring type. These
gaskets shall contain aramid fibres bonded with styrene butadeine rubber (SBR) or nitrile butadeine rubber
(NBR). Bolts, nuts, and bolt patterns shall conform to ASME B16.1.
Welded valves and pipe connections (both butt-welds and socket-welds types) shall conform to ASME
B31.9. Butt-welded fittings shall conform to ASME B16.9. Socket-welded fittings shall conform to ASME
B16.11. Welded fittings shall be identified with the appropriate grade and marking symbol.
Rigid grooved mechanical connections may only be used in serviceable aboveground locations where the
temperature of the circulating medium does not exceed 110 degrees C (230 degrees F). Flexible grooved
connections shall be used only as a flexible connector with grooved pipe system. Unless otherwise specified,
grooved piping components shall meet the corresponding criteria specified for the similar welded, flanged,
or threaded component specified herein.
Each grooved mechanical joint shall be a system, including coupling housing, gasket, fasteners, all furnished
by the same manufacturer. Joint installation shall be in compliance with joint manufacturer's written
instructions.
Use fitting and coupling houses of malleable iron conforming to ASTM A47/A47M, Grade 32510; ductile iron
conforming to ASTM A536, Grade 65-45-12; or steel conforming ASTM A106/A106M, Grade B or ASTM
A53/A53M. Use gaskets of molded synthetic rubber with central cavity, pressure responsive configuration
and conforming to ASTM D2000 Grade No. 2CA615A15B44F17Z for circulating medium up to 110 degrees C
(230 degrees) For Grade No. M3BA610A15B44Z for circulating medium up to 93 degrees C (200 degrees F).
Grooved mechanical connections shall conform to AWWA C606. Coupling nuts and bolts shall be steel and
shall conform to ASTM A183. Pipe connections and fittings shall be the product of the same manufacturer.
Provide joint installation be in compliance with joint manufacturer's written instructions.
Provide dielectric waterways with a water impervious insulation barrier capable of limiting galvanic current
to 1 percent of short circuit current in a corresponding bimetallic joint. When dry, insulation barrier shall be
able to withstand a 600-volt breakdown test. Provide dielectric waterways constructed of galvanized steel
and have threaded end connections to match connecting piping. Dielectric waterways shall be suitable for
the required operating pressures and temperatures. Provide dielectric flanges with the same pressure
ratings as standard flanges and provide complete electrical isolation between connecting pipe and/or
equipment as described herein for dielectric waterways.
VALVES
Provide valves with a ANSI/ASME Class 125 service rating, which for 66 degrees C, the pressure rating is 1207
kPa (150 degrees F, the pressure rating is 175 psig).
PART 1 - GENERAL
1.2 SUMMARY
A. This Section includes piping, valves, sprinklers and devices, specialties, controls, and
wiring for the irrigation system.
2. Division 2 Section 02510 “Water Distribution” for butterfly valves and valve
chambers and related accessories.
1.3 DEFINITIONS
B. Circuit Piping: Downstream from control valves to sprinklers, specialties, and drain
valves. Piping is under pressure during flow.
C. Minimum Working Pressures: The following are minimum pressure requirements for
piping, valves, and specialties, unless otherwise indicated:
1.5 SUBMITTALS
A. Product Data: Include pressure rating, rated capacity, settings, and electrical data of
selected models for the following:
1. Water regulators.
2. Valves. Include underground; general-duty, manual control, and quick-coupler types.
3. Valve boxes.
4. Site control including remote control pressure reducing valves-RCPRV, controllers,
drip emitters, drip lines, bubbler assemblies, weather stations, sprayers and sprinklers
B. Shop Drawings: Show combined irrigation system, including plan layout and
locations, types, sizes, capacities, and flow characteristics of piping components.
Include valves, piping, irrigators, accessories, controls, and wiring. Show areas of
sprinkler spray and overspray.
G. Certificate of Compliance
B. Regulatory Requirements:
C. Piping materials shall bear label, stamp, or other markings of specified testing agency.
D. Special Tests: Whenever required by the Engineer, supply and transport to a testing
laboratory samples of materials selected by the Engineer. Number of samples is not to
be more than 0.5% of total supplied, with at least one from each class, diameter and
manufacturer. Failure of any sample is to be followed by a second and if necessary a
third test from the same batch. A third test failure will result in all material from that
manufacturer being rejected and replaced by material from a different manufacturer,
subject to approval and satisfactory tests. Provide laboratory test report in an
approved form.
1. Ensure that valves are dry and internally protected against rust and corrosion.
2. Protect valves against damage to threaded ends and flange faces.
3. Set valves in best position for handling. Set valves closed to prevent rattling.
1. Do not remove end protectors unless necessary for inspection; then, reinstall for
storage.
2. Protect from weather. Store indoors and maintain temperature higher than ambient
dew-point temperature. Support off ground or pavement in watertight enclosures
when outdoor storage is necessary.
C. Handling: Use sling to handle valves if size requires handling by crane or lift. Rig
valves to avoid damage to exposed parts. Do not use handwheels or stems as lifting
or rigging points.
D. Deliver piping with factory-applied end caps. Maintain end caps through shipping,
storage, and handling to prevent pipe-end damage and to prevent entrance of dirt,
debris, and moisture.
E. Protect stored piping from moisture and dirt. Elevate above grade. Do not exceed
structural capacity of floor when storing inside.
G. Store plastic piping protected from direct sunlight. Support to prevent sagging and
bending.
A. Perform site survey, research public utility records, and verify existing utility
locations.
B. Existing Utilities: Do not interrupt or interfere with utilities serving facilities on the
Project site or on adjoining property unless permitted by the Engineer under the
following conditions and then only after arranging to provide temporary utility
services according to requirements indicated or directed:
1. Notify the Engineer not less than 72 hours in advance of proposed utility
interruptions.
2. Do not proceed with utility interruptions without the Engineer's written permission.
PART 2 - PRODUCTS
B. Marking: Unless otherwise specified in the relevant Standards products are to have
legibly cast, stamped or indelibly painted on, the following marks, as appropriate:
1. Ductile iron pipe for water shall be to BS EN 545 or equivalent. Unless otherwise
indicated in the Bill of Quantities or the Drawings, Class K9 shall be used.
2. Spigot and socket ended pipes shall be used for straight runs and adjacent to elbows
or fittings. These joints shall be provided with rubber gaskets, and an external
thrust block is required at elbows or fittings. Anchored or self restrained joints shall
be used for sections adjacent to elbows in areas where space is restricted or indicated
on the Drawings or BOQ. Anchored joints are to be push-in, self anchored type able
to take up the axial forces thus allowing concrete thrust blocks to be dispensed with.
The Contractor shall submit calculations verifying the number of restrained joints
required noting that pipe pressure testing will be made when pipes are partially
backfilled.
3. Flanged pipes wherever specified shall have screwed-on or cast-on flanges to sustain
working pressure of NP 16 minimum.
4. Flanges shall conform to BS EN 1092, Part 2.
5. Factory protection for pipes:
IRRIGATION SYSTEM 02810 - Page 4 of 17
S08035-SPC-ENV-01 REV 1
RIYADH METRO PROJECT
CIVIL AND INFRASTRUCTURE CONSTRUCTION SPECIFICATIONS
1. PIPE, Pressure Pipe: DIN 8074 and DIN 8075, Class 10 or 16 kg/cm2 (as applicable)
or BS 3284 with straight ends for butt welding.
2. FITTINGS for PE Pipe: to be moulded and suitable for class of pipe. IN-line fittings
including couplings, unions, bushing and nipples may be extruded or machined from
extruded stock.
A. Refer to Division 2 Section "Piped Utilities – Basic Materials and Methods" for
commonly used joining materials.
B. Transition Couplings:
C. Plastic Pipe-Flange Gasket, Bolts, and Nuts: Type and material of gaskets to be as
recommended by piping system manufacturer, unless otherwise indicated. Bolts, nuts
and washer to be stainless steel grade 316.
D. Pipes utilities inside culverts should be joined using SADIP anchored standard/triduct
joints or approved equal as specified by the manufacturer.
B. Cast-Iron Gate Valves: AWWA C500, cast-iron double disc, bronze disc, and seat
rings or AWWA C509, resilient seated; bronze stem, cast-iron, or ductile-iron body
and bonnet, stem nut, 16 bar working pressure; and ends that fit HDPE pipe flanged
push-on or mechanical joint. Include elastomeric gaskets.
C. Cast-Iron, Nonrising-Stem Gate Valves: MSS SP-70, Type I, solid wedge; nonrising
stem and flanged ends. Include all bronze trim; Class 125, ASTM A 126, cast-iron
body; and handwheel. Interior and Exterior coating to be 300 microns fusion bonded
epoxy coating.
D. Cast-Iron, Rising-Stem Gate Valves: MSS SP-70, Type I, solid wedge; rising stem
and flanged ends. Include all bronze trim; Class 125, ASTM A 126, cast-iron body;
and handwheel.
E. Tapping-Sleeve Assemblies: Comply with MSS SP-60. Include sleeve and valve
compatible with drilling machine.
1. Tapping Sleeve: Ductile-iron or stainless steel, two-piece bolted sleeve with flanged
outlet for new branch connection. Include sleeve matching size and type of pipe
material being tapped and with recessed flange for branch valve.
IRRIGATION SYSTEM 02810 - Page 6 of 17
S08035-SPC-ENV-01 REV 1
RIYADH METRO PROJECT
CIVIL AND INFRASTRUCTURE CONSTRUCTION SPECIFICATIONS
F. Electric Remote Control Valves with Pressure Regulation: Heavy-duty, glass-filled, UV-
resistant, nylon body and bonnet with stainless steel studs and flange nuts, and a nylon
reinforced rubber diaphragm. Normally closed, and operated by 24 V, ac solenoid actuated
globe pattern with balanced pressure diaphragm design. Remote Control Valves shall have a
self cleaning scrubber and screen. The Solenoid shall generally be from Rainbird, Hunter,
Toro companies, or approved equal
1. Locking Top Option: Include vandal-resistant, locking feature with two matching
keys.
I. Curb-Stop Service Boxes: Cast iron with telescoping top section of length required
for depth of bury of valve, cover with lettering "IRRIGATION," bottom section with
base of size to fit over curb stop, and 75- mm diameter barrel. Include steel tee-
handle shutoff rod with one pointed end, stem of length to operate curb stop, and
slotted end fitting curb-stop head.
J. Valve Boxes for gate valves: Cast iron with top section and cover with lettering
"IRRIGATION," bottom section with base to fit over valve, 127 mm diameter barrel,
and adjustable cast-iron extension of length required for depth of bury of valve.
Include steel tee-handle, shutoff rod with one pointed end, stem of length to operate
valve, and end fitting valve operating nut.
1. Type: To BS EN 593 [27], double flange with resilient seating, for horizontal use and
suitable for NP 16.
3. Material of component parts shall be from basic materials listed in BS EN 593 [27]
Table 3.
5. Operation by hand wheel. Maximum shut off pressure against which valve is
operated is to be 15 kg/cm2.
6. Factory Protection: Casting surfaces are to be given an initial coat of protective paint
immediately after shot blasting and a second coat on assembly. Protective coating is
to be hot applied coal tar or bitumen to BS 4164 [5], or BS 3416 [4] respectively.
Thickness of coat shall be 250 microns.
M. Flap Valves
1. Type: To be flange mounted, designed for use on end closures to prevent entrance of
backwater. Seating plane is to have 10 deg. inclination.
2. Materials: Cast iron body and cover, bronze seat faces, bronze hinge pins and spring
pins, cast iron follow ring and plated steel ring draw bolts. Materials subject to de-
zincification or de-aluminuzation are not to be used.
4. Factory Protection: Casting surfaces are to be given an initial coat of protective paint
immediately after shot blasting and a second coat on assembly. Protective coating is
to be hot applied coal tar or bitumen to BS 4164 or BS 3416 respectively. Thickness
of coat shall be at least 250 microns.
2.6 IRRIGATORS
1. Type: Subsurface Root Area Watering System with associated pressure compensating
bubblers.
E. Emitters
2. Construction: emitter shall have self piercing inlet barb constructed of durable ultra-
violet resistant plastic.
3. Performance: the emitter shall have a self flushing action to minimize clogging, and
shall operate at a constant flow discharge over a pressure range specified on the
Drawings.
1. Type: fixed, non-rotating spray or stream spray adaptable for full circle, part circle, or
strip wetting pattern, suitable for installation on a pop-up mechanism. Spray head to
have built in check valve and pressure regulated stem.
2. Material: the sprinkler body, stem, nozzle, and screen shall be constructed of heavy
duty, ultra-violet resistant plastic, with a heavy-duty stainless steel retract spring.
3. Construction: spray head to retract flush with the finished ground level when not in
operation. When spraying, net pop-up height to be 150 mm from finished ground
level.
5. Tests: provide test results carried out at factory substantiating required performance
(discharge and radius of throw at prescribed operating pressure and height above
ground) and giving actual precipitation rate and its uniformity as obtained for
uniformity test carried out using catch cans.
1. Type: full or part circle pop-up rotor sprinkler, single nozzle. The part circle sprinkler
shall have adjustable arc coverage from 25° to 360°. The sprinkler shall have a built
in check valve and pressure regulated stem.
2. Material: the sprinkler body, stem, nozzle, and screen shall be constructed of heavy
duty, ultra-violet resistant plastic, with a heavy duty stainless steel retract spring.
3. Construction: sprinkler head to retract flush with the finished ground level when not
in operation. When operating, net pop-up height to be 100 mm from finished ground
level.
5. Tests: provide test results carried out at factory substantiating required performance
(discharge and radius of throw at prescribed operating pressure and height above
ground) and giving actual precipitation rate and its uniformity as obtained for
uniformity test carried out using catch cans.
2.7 SPECIALTIES
B. Drip Tubes: DN15 to DN25 flexible PE or PVC for emitters and other devices, of
length indicated, and with plugged end.
A. Check Valves:
1. Check Valves: AWWA C508, swing-check type with 16 bar working-pressure rating
and resilient seat. Include interior and exterior protection to be 300 microns fusion
bonded epoxy coating" and ends to match piping.
D. Interior and Exterior coating to be 300 microns (minimum) fusion bonded epoxy.
A. 50 mm and under to be full port of 2-piece construction, lever operated with bronze
body and stem, chrome-plated brass ball, replaceable PTFE seats and packing, plastic
coated steel handle, threaded end connection for stell piping, and copper compression
or solder end connections for copper piping.
2.11 SPECIALTIES
B. Drip Tubes: DN13 to DN18 flexible PE for emitters and other devices, of length
indicated, and with plugged end.
B. OPERATION: the controller shall have a remote pump start circuit to activate a remote
pump start relay to run the pump during the irrigation cycle.
C. OPERATION: the controller shall allow for opening the first remote control valve before
operating the pump and also for closing the last remote control valve within 15 seconds after
stopping the pump.
F. THE CONTROLLER without exception shall be of the same manufacturer as the remote
control valve.
2.13 IDENTIFICATION
1. Solid blue film with metallic core and continuously printed black-letter caption,
"CAUTION--WATER LINE BURIED BELOW."
drawings. The ladders shall be drilled for wall fixing at both ends and additional
intermediate fixing connections shall be provided at centers not greater than 1.5
meters. Rungs shall be at 300 mm centers and at a distance of not less than 150 mm
from the wall. The resins, glasses and synthetic fabrics used in the manufacture of the
ladders shall be chosen to produce a chemically resistant product with a resin-rich
surface layer suitable for use in aggressive atmospheres likely to the encountered in
sewers and sewage pumping stations. Rungs of tubular construction shall be no less
than 30 mm outer diameter and stringers shall be of a rectangular or channel section,
no less than 70 mm x 25 mm in size. The upper face of non-tubular rungs shall be
finished with a non-slip surface such as silica sand. All remaining surfaces shall be
free of sharp edges, protrusions etc. Each rung shall be able to withstand a point load
of 5000 N. When supported horizontally over a span of 1 m with the climbing face
uppermost and with a load of 1000 N applied at the centre of the span the ladder shall
not deflect more than 15 mm at the point of application of the load and shall show no
permanent deflection after removal of the load. Each ladder fixing shall be capable of
withstanding shear and pull-out loads of 5000 N. All ladders shall comply with BS
5395: Part 3. All fixings shall be stainless steel. When the height of the ladder
exceeds 6m, safety cages shall be used.
PART 3 - EXECUTION
3.1 GENERAL
A. Installation and testing shall be according to NFPA 14 and 24 and according to the
articles of this part. In case of contradiction, the most stringent standard shall apply.
3.2 PREPARATION
A. Set stakes to identify locations of proposed irrigation system components. Obtain the
Engineer's approval before excavation.
B. Install warning tape directly above pressure piping, 300 mm below finished grades,
except 150 mm below subgrade under pavement and slabs.
C. Install piping and wiring in sleeves under sidewalks, roadways, parking lots, and the
like.
D. Drain Pockets: Excavate to sizes indicated or required. Backfill with cleaned gravel
or crushed stone, graded from 75 to 19 mm minimum, to 300 mm below grade.
Cover gravel or crushed stone with sheet of asphalt-saturated felt and backfill
remainder with excavated material.
E. Provide minimum cover over top of underground piping according to the following:
A. Install components having pressure rating equal to or greater than system operating
pressure.
B. Piping in control-valve boxes and aboveground may be joined with flanges instead of
joints indicated.
1. DN65 and Smaller: PE to BS 6437 Class C or DIN 8074 and DIN 8075 Class 10 or 6
bars pipe (as applicable), PE socket or butt-fusion fittings, and heat-fusion joints.
F. Sleeves: DIN 8074/8075 Class 6 kg/cm² HDPE pipe. Straight with straight ends
suitable for heat fusion. HDPE socket fittings, and solvent-cemented joints.
1. DN80 and Larger: Gate valve, with elastomeric gaskets and stem nut, valve box, and
shutoff rod.
C. Underground, Manual Control Valves: Bronze globe valve with control-valve service
box and valve key.
A. Refer to Division 2 Section "Piped Utilities - Basic Materials and Methods" for pipe
joint construction requirements.
C. Dissimilar Piping Material Joints: Construct joints using adapters or couplings that
are compatible with both piping materials, outside diameters, and system working
pressure.
E. Install groups of pipes parallel to each other, spaced to permit valve servicing.
G. Install unions adjacent to valves and final connections to other components with
DN50 or smaller pipe connection.
H. Install flanges adjacent to valves and final connections to other components with
DN65 or larger pipe connection.
K. Install HDPE piping in dry weather when temperature is above 4.4 deg. C (40 deg. F).
Allow joints to cure at least 24 hours at temperature above 4.4 deg. C (40 deg. F)
before testing, unless otherwise recommended by the manufacturer.
A. Install anchorages for tees, plugs and caps, bends, crosses, valves, and hydrant
branches.
A. Underground Gate Valves: Install valve with stem pointing up in a valve box with
top flush with grade, comply with AWWA C600 and AWWA M44.
B. Install freestanding controllers on precast concrete bases not less than 914 by 610 by
100 mm thick, and not less than 150 mm greater in each direction than overall
dimensions of controller.
C. Install control wiring in same trench with piping. Install wiring with loops at control
valves and controllers, at intervals not greater than 30 m, and changes in direction to
allow for expansion. Bundle wiring in same trench at 3 m intervals.
3.11 CONNECTIONS
D. Arrange for electric-power connections to controllers, control valves, and devices that
require power. Electric power, wiring, and disconnect switches are specified in
Division 16 Sections.
1. Provision of test equipment: All items for test have to be provided on site before the
test i.e. pressure gages, instruments, water etc.
2. Carry out tests in the presence of the Engineer's Representative.
3. Fittings and joints: Permanently anchor fittings before testing and leave all joints
exposed for checking.
4. Test sections: Limit test sections to not more than 500 m.
5. Test sections: Test pressure lines between valve chambers whenever possible.
6. Test sections: No testing shall be carried out against or through the pressure reducing
valves. The setting of the pressure reducing valves shall not be changed for testing
purposes.
1. Fill pipe slowly with water from lowest point. Do not use power-driven pump unless
approved.
2. Fill absorbant pipes with water and allow to stand for at least 24 hours to allow
complete absorption.
3. Entrapped air is to be bled before pressurizing.
4. Pressurizing is to continue until specified test pressure is reached in lowest part of
section under test. Bleed further quantities of entrapped air while raising pressure.
5. Maintain test pressure for specified test duration with pumping stopped.
6. Repressurize to original test pressure and record respective volumes of water
pumped.
7. Failure: Pipeline will be deemed to have failed test if:
a. Visible leaks are detected, regardless of leakage being within specified limits.
b. Volume of water lost during period when pumping was stopped exceeds
allowable leakage.
8. Test pressure: Generally 1.5 times the maximum sustained pressure, minimum
12 kg/cm2 for main lines and 8 kg/cm2 for circuit piping.
9. Test period: 2 hours.
10. Allowable leakage: 0.1 liter/mm diameter/km length/day/30 m of applied pressure.
1. Timing: Carry out test after total backfilling of length under test.
2. Limit of length to be tested at one time is 3 full length pipes unless otherwise
approved.
3. Apparatus: Use rubber ty`red bogies which do not damage lining of pipe and an
adequate supply of electric lamps.
4. Check joints by means of feelers to ensure rubber rings are correctly located.
5. Check pipe barrel for visible cracks.
3.13 IDENTIFICATION
A. Flush dirt and debris from piping before installing sprinklers and other devices.
IRRIGATION SYSTEM 02810 - Page 16 of 17
S08035-SPC-ENV-01 REV 1
RIYADH METRO PROJECT
CIVIL AND INFRASTRUCTURE CONSTRUCTION SPECIFICATIONS
B. Adjust automatic control valves to provide flow rate of rated operating pressure
required for each sprinkler circuit.
C. Carefully adjust sprinklers so they will be flush with, or not more than 13 mm above,
finish grade.
3.15 COMMISSIONING
1. Verify that specialty valves and their accessories are installed and operate correctly.
2. Verify that specified tests of piping are complete.
3. Verify that sprinklers and devices are correct type.
4. Verify that damaged sprinklers and devices are replaced with new materials.
5. Energize circuits to electrical equipment and devices.
6. Adjust operating controls.
B. Operational Tests: Measure and record water flow rate and area coverage at each
sprinkler. Adjust to achieve indicated values.
3.16 DEMONSTRATION
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following basic mechanical materials and methods to complement
other Division 15 Sections.
B. Pipe and pipe fitting materials are specified in Division 15 piping system Sections.
1.3 DEFINITIONS
A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred
spaces, pipe and duct shafts, unheated spaces immediately below roof, spaces above
ceilings, unexcavated spaces, crawl spaces, and tunnels.
D. Concealed, Interior Installations: Concealed from view and protected from physical contact
by building occupants. Examples include above ceilings and in duct shafts.
E. Concealed, Exterior Installations: Concealed from view and protected from weather
conditions and physical contact by building occupants, but subject to outdoor ambient
temperatures. Examples include installations within unheated shelters.
A. In addition to the requirements shown or specified, comply with the latest current applicable
standards, specifications or codes published by the following organizations:
A. Climatic Conditions: The outdoor design conditions to be adopted for the project are as
follows:
1. Climatic Conditions:
2. Outside Temperatures:
1) Summer
2) Winter
1.6 SUBMITTALS
A. Product Data: For dielectric fittings, flexible connectors, mechanical sleeve seals, and
identification materials and devices.
B. Shop Drawings: Detail fabrication and installation for metal supports and anchorage for
mechanical materials and equipment.
1. Planned piping layout, including valve and specialty locations and valve-stem
movement.
2. Clearances for installing and maintaining insulation.
3. Clearances for servicing and maintaining equipment, accessories, and specialties,
including space for disassembly required for periodic maintenance.
4. Equipment and accessory service connections and support details.
5. Exterior wall and foundation penetrations.
6. Fire-rated wall and floor penetrations.
7. Sizes and location of required concrete pads and bases.
8. Scheduling, sequencing, movement, and positioning of large equipment into building
during construction.
9. Floor plans, elevations, and details to indicate penetrations in floors, walls, and
ceilings and their relationship to other penetrations and installations.
10. Reflected ceiling plans to coordinate and integrate installation of air outlets and inlets,
light fixtures, communication system components, sprinklers, ceiling access panels
and other ceiling-mounted items.
11. Mechanical equipment rooms.
12. Interstitial space.
E. Samples: Of color, lettering style, and other graphic representation required for each
identification material and device.
H. Where US material or reference standards are specified or indicated, compliance with the
equivalent British Standard (BS) is acceptable.
A. Comply with ASME A13.1 for lettering size, length of color field, colors, and viewing
angles of identification devices.
D. Products Criteria:
render satisfactory service to the equipment on a regular and emergency basis during
the warranty period of the contract.
3. Multiple Units: When 2 or more units of materials or equipment of the same type or
class are required, these units shall be products of one manufacturer.
4. Assembled Units: Manufacturers of equipment assemblies, which use components
made by others, assume complete responsibility for the final assembled product.
5. Nameplates: Nameplate bearing manufacturer's name or identifiable trademark shall
be securely affixed in a conspicuous place on equipment, or name or trademark cast
integrally with equipment, stamped or otherwise permanently marked on each item of
equipment.
6. Asbestos products or equipment or materials containing asbestos shall not be used.
F. Provide copies of approved equipment submittals to the Testing, Adjusting and Balancing
Subcontractor.
G. Electrical Requirements: Furnish motors, controllers, disconnects and contactors with their
respective pieces of equipment. Motors, controllers, disconnects and contactors shall
conform to and have electrical connections provided under division 16. Furnish internal
wiring for components of packaged equipment as an integral part of the equipment.
Extended voltage range motors will not be permitted. Controllers and contactors shall have
a maximum of 220-volt control circuits, and shall have auxiliary contacts for use with the
controls furnished. Electrical installations shall conform to IEEE C2, NFPA 70 and
requirements specified herein.
1.8 WELDING
A. The Contractor is entirely responsible for the quality of the welding and shall:
1. Conduct tests of the welding procedures used by his organization, determine the
suitability of the procedures used, determine that the welds made will meet the
required tests, and also determine that the welding operators have the ability to make
sound welds under standard conditions.
B. Qualification of Welders: Rules of procedure for qualification of all welders and general
requirements for fusion welding shall conform with the applicable portions of ASME B31.1,
Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel
Code: Section IX, "Welding and Brazing Qualifications, and AWS B2.1, and / or, as
approved by the Qualifications."
C. Examining Welder: Examine each welder at job site, in the presence of the Resident
Engineer, to determine the ability of the welder to meet the qualifications required. Test
welders for piping for all positions, including welds with the axis horizontal (not rolled) and
with the axis vertical. Each welder shall be allowed to weld only in the position in which he
has qualified and shall be required to identify his welds with his specific code marking
signifying his name and number assigned.
D. Examination Results: Provide the Resident Engineer with a list of names and corresponding
code markings. Retest welders who fail to meet the prescribed welding qualifications.
Disqualify welders, who fail the second test, for work on the project.
E. Beveling: Field bevels and shop bevels shall be done by mechanical means or by flame
cutting. Where beveling is done by flame cutting, surfaces shall be thoroughly cleaned of
scale and oxidation just prior to welding. Conform to specified standards.
F. Alignment: Utilize split welding rings or approved alternate method for joints on all pipes
above 50 mm to assure proper alignment, complete weld penetration, and prevention of
weld spatter reaching the interior of the pipe.
G. Erection: Piping shall not be split, bent, flattened, or otherwise damaged either before,
during, or after installation.
H. Defective Welds: Replace and re-inspect defective welds. Repairing defective welds by
adding weld material over the defect or by peening will not be permitted. Welders
responsible for defective welds must be re-qualified.
I. Electrodes: Electrodes shall be stored in a dry heated area, and be kept free of moisture and
dampness during the fabrication operations. Discard electrodes that have lost part of their
coating.
A. Metallic materials shall be protected against corrosion. Equipment enclosures shall be given
rust-inhibiting treatment and standard finish by the manufacturer. Aluminum shall not be
used in contact with earth, and where connected to dissimilar metal, shall be protected by
approved fittings, barrier material, or treatment. Ferrous parts such as anchors, bolts,
braces, boxes, bodies, clamps, fittings, guards, nuts, pins, rods, shims, thimbles, washers,
and miscellaneous parts not of corrosion-resistant steel or nonferrous materials shall be hot-
dip galvanized in accordance with ASTM A 123/A 123M for exterior locations and
cadmium-plated in conformance with ASTM B 766 for interior locations.
A. The equipment supplied shall be packed for protection against damage during handling,
transport, warehousing and installation. The efficiency of the packing shall be the
responsibility of the Contractor. The Contractor shall repair or replace any damaged items,
at no additional cost, as instructed by the Engineer even after delivery of the equipment, if it
is proven that the damage was caused by packing, storage, or handling deficiencies.
B. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through shipping,
storage, and handling to prevent pipe end damage and prevent entrance of dirt, debris, and
moisture.
C. Protect stored pipes and tubes from moisture and dirt. Elevate above grade. Do not exceed
structural capacity of floor, if stored inside.
D. Protect flanges, fittings, and piping specialties from moisture and dirt.
E. Store plastic pipes protected from direct sunlight. Support to prevent sagging and bending.
F. The following markings shall be factory applied using indelible ink on the external part of
each volume:
A. Coordinate mechanical equipment installation with other trades and building components.
B. Arrange for pipe spaces, chases, slots, and openings in building structure during progress of
construction to allow for mechanical installations.
D. Sequence, coordinate, and integrate installations of mechanical materials and equipment for
efficient flow of the Work. Coordinate installation of large equipment requiring positioning
before closing in building.
F. Coordinate requirements for access panels and doors if mechanical items requiring access
are concealed behind finished surfaces. Access panels and doors are specified in Division 8
Section "Access Doors and Frames."
PART 2 - PRODUCTS
A. Refer to individual Division 15 piping Sections for pipe and fitting materials and joining
methods.
B. Pipe Threads: ASME B1.20.1 or British Standard for factory-threaded pipe and pipe
fittings.
A. Refer to individual Division 15 piping Sections for special joining materials not listed
below.
B. Pipe-Flange Gasket Materials: Suitable for chemical and thermal conditions of piping
system contents.
a. Full-Face Type: For flat-face, Class 125, cast-iron and cast-bronze flanges.
b. Narrow-Face Type: For raised-face, Class 250, cast-iron and steel flanges.
2. AWWA C110, rubber, flat face, 3.2 mm thick, unless otherwise indicated; and full-
face or ring type, unless otherwise indicated.
C. Flange: ASME B18.2.1, carbon steel, unless otherwise indicated; Bolts, Nuts and washers,
stainless steel for potable/domestic water piping, galvanized for other piping systems.
D. Plastic, Pipe-Flange Gasket, Bolts, and Nuts: Type and material recommended by piping
system manufacturer, unless otherwise indicated.
1. Alloy Sn95: Approximately 95 percent tin and 5 percent silver, with 0.10 percent
lead content.
2. Alloy E: Approximately 95 percent tin and 5 percent copper, with 0.10 percent
maximum lead content.
3. Alloy HA: Tin-antimony-silver-copper zinc, with 0.10 percent maximum lead
content.
4. Alloy HB: Tin-antimony-silver-copper nickel, with 0.10 percent maximum lead
content.
5. Alloy Sb5: 95 percent tin and 5 percent antimony, with 0.20 percent maximum lead
content.
G. Welding Filler Metals: Comply with AWS D10.12 for welding materials appropriate for
wall thickness and chemical analysis of steel pipe being welded.
J. Flanged, Ductile-Iron Pipe Gasket, Bolts, and Nuts: AWWA C110, rubber gasket, carbon-
steel bolts and nuts.
A. General: Assembly or fitting with insulating material isolating joined dissimilar metals, to
prevent galvanic action and stop corrosion.
B. Description: Combination of copper alloy and ferrous; threaded, solder, plain, and weld-
neck end types and matching piping system materials.
D. Dielectric Unions: Factory-fabricated, union assembly, for 1725 kPa minimum working
pressure at 82 deg. C.
1. Provide separate companion flanges and steel bolts and nuts for 1035 or 2070 kPa
minimum working pressure as required to suit system pressures.
H. Dielectric Nipples: Electroplated steel nipple with inert and noncorrosive, thermoplastic
lining; plain, threaded, or grooved ends; and 2070 kPa minimum working pressure at
107 deg. C.
A. General: Fabricated from materials suitable for system fluid and that will provide flexible
pipe connections. Include 860 kPa minimum working-pressure rating, unless higher
working pressure is indicated, and ends according to the following:
B. Bronze-Hose, Flexible Connectors: Corrugated, bronze, inner tubing covered with bronze
wire braid. Include copper-tube ends or bronze flanged ends, braze welded to hose.
A. Description: Modular design, with interlocking rubber links shaped to continuously fill
annular space between pipe and sleeve. Include connecting bolts and pressure plates.
A. Sleeves: The following materials are for wall, floor, slab, and roof penetrations:
1. Steel Sheet Metal: 0.6 mm minimum thickness, galvanized, round tube closed with
welded longitudinal joint.
2. Steel Pipe: ASTM A 53, Type E, Grade A, Schedule 40, galvanized, plain ends.
3. Stack Sleeve Fittings: Manufactured, cast-iron sleeve with integral clamping flange.
Include clamping ring and bolts and nuts for membrane flashing.
B. Escutcheons: Manufactured wall, ceiling, and floor plates; deep-pattern type if required to
conceal protruding fittings and sleeves.
1. ID: Closely fit around pipe, tube, and insulation of insulated piping.
2. OD: Completely cover opening.
3. Cast Brass: One piece, with set screw and polished chrome-plated finish.
4. Cast Brass: Split casting, with concealed hinge, set screw and polished chrome-
plated finish.
5. Stamped Steel: One piece, with set screw and chrome-plated finish.
6. Stamped Steel: One piece, with spring clips and chrome-plated finish.
7. Stamped Steel: Split plate, with concealed hinge, set screw, and chrome-plated
finish.
8. Stamped Steel: Split plate, with concealed hinge, spring clips, and chrome-plated
finish.
9. Cast-Iron Floor Plate: One-piece casting.
C. Screws: Provide Stainless Steel screws for outdoor and wet applications
2.7 GROUT
PART 3 - EXECUTION
A. General: Install piping as described below, unless piping Sections specify otherwise.
Individual Division 15 piping Sections specify unique piping installation requirements.
B. General Locations and Arrangements: Drawing plans, schematics, and diagrams indicate
general location and arrangement of piping systems. Indicated locations and arrangements
were used to size pipe and calculate friction loss, expansion, pump sizing, and other design
considerations. Install piping as indicated, unless deviations to layout are approved on
Coordination Drawings.
D. Install components with pressure rating equal to or greater than system operating pressure.
E. Install piping in concealed interior and exterior locations, except in equipment rooms and
service areas.
G. Install exposed interior and exterior piping at right angles or parallel to building walls.
Diagonal runs are prohibited, unless otherwise indicated.
H. Install piping tight to slabs, beams, joists, columns, walls, and other building elements.
Allow sufficient space above removable ceiling panels to allow for ceiling panel removal.
J. Locate groups of pipes parallel to each other, spaced to permit valve servicing.
M. Install pipe escutcheons for pipe penetrations of concrete and masonry walls, wall board
partitions, and suspended ceilings according to the following:
1. Chrome-Plated Piping: Cast brass, one piece, with set screw, and polished chrome-
plated finish. Use split-casting escutcheons if required, for existing piping.
2. Uninsulated Piping Wall Escutcheons: Cast brass or stamped steel, with set screw.
3. Uninsulated Piping Floor Plates in Utility Areas: Cast-iron floor plates.
4. Insulated Piping: Cast brass or stamped steel; with concealed hinge, spring clips, and
chrome-plated finish.
5. Piping in Utility Areas: Cast brass or stamped steel, with set-screw or spring clips.
N. Install sleeves for pipes passing through concrete and masonry walls, and concrete floor and
roof slabs.
O. Install sleeves for pipes passing through concrete and masonry walls, gypsum-board
partitions, and concrete floor and roof slabs.
4. Except for underground wall penetrations, seal annular space between sleeve and pipe
or pipe insulation, using elastomeric joint sealants. Refer to Division 7 Section "Joint
Sealants" for materials.
5. Use Type S, Grade NS, Class 25, Use O, neutral-curing silicone sealant, unless
otherwise indicated.
Q. Underground, Exterior-Wall, Pipe Penetrations: Install Steel Pipe for sleeves. Seal pipe
penetrations using mechanical sleeve seals. Size sleeve for 25 mm annular clear space
between pipe and sleeve for installing mechanical sleeve seals.
R. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and
floors at pipe penetrations. Seal pipe penetrations with firestopping materials. Refer to
Division 7 Section "Through-Penetration Firestop Systems" for materials.
U. Piping Joint Construction: Join pipe and fittings as follows and as specifically required in
individual piping Specification Sections:
1. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
2. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings
before assembly.
3. Soldered Joints: Construct joints according to AWS' "Soldering Manual," Chapter
"The Soldering of Pipe and Tube"; or CDA's "Copper Tube Handbook."
4. Brazed Joints: Construct joints according to AWS' "Brazing Handbook," Chapter
"Pipe and Tube."
5. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1.
Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs
and restore full ID. Join pipe fittings and valves as follows:
a. Comply with ASTM F 402 for safe-handling practice of cleaners, primers, and
solvent cements.
b. CPVC Piping: ASTM D 2846 and ASTM F 493.
c. PVC Pressure Piping: ASTM D 2672.
d. PVC Nonpressure Piping: ASTM D 2855.
9. Plastic Piping Heat-Fusion Joints: Clean and dry joining surfaces by wiping with
clean cloth or paper towels. Join according to ASTM D 2657 procedures and
manufacturer's written instructions.
1. Install unions, in piping DN50 and smaller, adjacent to each valve and at final
connection to each piece of equipment with DN50 or smaller threaded pipe
connection.
2. Install flanges, in piping DN65 and larger, adjacent to flanged valves and at final
connection to each piece of equipment with flanged pipe connection.
3. Dry Piping Systems: Install dielectric unions and flanges to connect piping materials
of dissimilar metals.
4. Wet Piping Systems: Install dielectric coupling and nipple fittings to connect piping
materials of dissimilar metals.
A. Install equipment to provide maximum possible headroom, if mounting heights are not
indicated.
B. Install equipment according to approved submittal data. Portions of the Work are shown
only in diagrammatic form. Refer conflicts to the Engineer.
C. Install equipment level and plumb, parallel and perpendicular to other building systems and
components in exposed interior spaces, unless otherwise indicated.
F. Install flexible connectors on equipment side of shutoff valves, horizontally and parallel to
equipment shafts if possible.
A. Piping Systems: Install pipe markers on each system. Include arrows showing normal
direction of flow.
d. At access doors, manholes, and similar access points that permit view of
concealed piping.
e. Near major equipment items and other points of origination and termination.
f. Spaced at maximum of 15 m intervals along each run. Reduce intervals to
7.5 m in congested areas of piping and equipment.
g. On piping above removable acoustical ceilings, except omit intermediately
spaced markers.
1. Lettering Size: Minimum 6 mm high lettering for name of unit if viewing distance is
less than 600 mm, 13 mm high lettering for distances up to 1800 mm, and
proportionately larger lettering for greater distances. Provide secondary lettering
two-thirds to three-fourths of size of principal lettering.
2. Text of Signs: Provide name of identified unit. Include text to distinguish between
multiple units, inform user of operational requirements, indicate safety and
emergency precautions, and warn of hazards and improper operations.
C. Duct Systems: Identify air supply, return, exhaust, intake, and relief ducts with duct
markers; or provide stenciled signs and arrows, showing duct system service and direction
of flow.
A. Refer to Division 9 Section "Painting" for paint materials, surface preparation, and
application of paint.
B. Apply paint to exposed piping according to the following, unless otherwise indicated:
1. Interior, Ferrous Piping: Use semigloss, acrylic-enamel finish. Include finish coat
over enamel undercoat and primer.
2. Interior, Galvanized-Steel Piping: Use semigloss, acrylic-enamel finish. Include 2
finish coats over galvanized metal primer.
3. Interior, Ferrous Supports: Use semigloss, acrylic-enamel finish. Include finish coat
over enamel undercoat and primer.
4. Exterior, Ferrous Piping: Use semigloss, acrylic-enamel finish. Include 2 finish
coats over rust-inhibitive metal primer.
5. Exterior, Galvanized-Steel Piping: Use semigloss, acrylic-enamel finish. Include 2
finish coats over galvanized metal primer.
6. Exterior, Ferrous Supports: Use semigloss, acrylic-enamel finish. Include 2 finish
coats over rust-inhibitive metal primer.
D. Damage and Touchup: Repair marred and damaged factory-painted finishes with materials
and procedures to match original factory finish.
A. Construct concrete bases of dimensions indicated or otherwise required, but not less than
100 mm larger in both directions than supported unit. Follow supported equipment
manufacturer's setting templates for anchor bolt and tie locations. Use 21 MPa, 28-day
compressive-strength concrete and reinforcement as specified in Division 3 Section "Cast-
in-Place Concrete."
A. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and
elevation to support and anchor mechanical materials and equipment.
C. Floor Mounted Support: Provide base plate and concrete plinths beneath each floor mounted
metallic supports.
3.7 DEMOLITION
C. Accessible Work: Remove indicated exposed pipe and ductwork in its entirety.
F. Temporary Disconnection: Remove, store, clean, reinstall, reconnect, and make operational
equipment indicated for relocation.
A. Contractor shall install his work in such a manner and at such time as will require a
minimum of cutting and patching of the building structure. Holes in exposed locations, in or
through existing floors, shall be drilled and smoothed by sanding. Use of a jackhammer will
be permitted only where specifically approved. Holes through masonry walls to
accommodate sleeves shall be made with an iron pipe masonry core saw.
B. Cut, channel, chase, and drill floors, walls, partitions, ceilings, and other surfaces necessary
for mechanical installations. Perform cutting by skilled mechanics of trades involved.
3.9 GROUTING
A. Install nonmetallic, nonshrink, grout for mechanical equipment base bearing surfaces, pump
and other equipment base plates, and anchors. Mix grout according to manufacturer's
written instructions.
F. Place grout on concrete bases to provide smooth bearing surface for equipment.
3.10 INSTALLATION
A. Materials and equipment shall be installed in accordance with the requirements of the
contract drawings and approved recommendations of the manufacturers. Installation shall
be accomplished by workers skilled in this type of work. Installation shall be made so that
there is no degradation of the designed fire ratings of walls, partitions, ceilings, and floors.
B. No installation shall be permitted which blocks or otherwise impedes access to any existing
machine or system.
C. All hinged doors shall swing open a minimum of 120 degrees. The area in front of all
access doors shall be clear a minimum of one meter.
3.11 CLEANING
A. Exposed surfaces of piping and equipment that have become covered with dirt, plaster, or
other material during handling and construction shall be thoroughly cleaned before such
surfaces are prepared for final finish painting or are enclosed within the building structure.
B. Before final acceptance, mechanical equipment, including piping, ducting, and fixtures,
shall be clean and free from dirt, grease, and finger marks.
GASKET
YES
CNAF AFM 37