EE251

First Examination
October 15, 2019

The power system shown has the following electrical parameters:

G1 & G2: 100 MVA, 69 kV, X1 = X2 = 15%, X0 = 10%


G3: 50 MVA, 13.8 kV, X1 = X2 = 20%, X0 = 15%
T1 & T2: 100 MVA, 230/69 kV, X = 12%; T3: 50 MVA, 230/13.8 kV, X = 10%
L1: X1 = X2 = 0.15 p.u., X0 = 0.35 p.u.; L2: X1 = X2 = 0.05 p.u., X0 = 0.12 p.u.
L3: X1 = X2 = 0.12 p.u., X0 = 0.25 p.u.

A Fault occurred at Bus 2.

1. Draw the impedance diagrams for the positive/negative and zero Sequence networks
of the power system. Label or indicate the p.u. impedance of the components.

2. Using network reduction method, determine the thevenin equivalent for the
positive/negative and zero sequence networks.

3. Calculate the sequence and phase fault currents in per unit for (a) three-phase fault,
(b) line-to-line fault, (c) single line-to-ground fault, and (d) double line-to-ground
fault. Assume bolted bus fault.

4. For single line-to-ground fault, what are the voltages at Bus 3 and Bus 4?

5. What is the magnitude and direction of currents through line L3?