Chapter 4 Complete Software Tasks Required at CompactLogix 5370 Controller Installation

Change the IP Address of a You can change the IP address of a CompactLogix 5370 controller after system
operation has begun. In this case, the controller has an IP address that is assigned
Controller to it, but you must change that IP address.

You can use these tools to changethe IP address of a controller:


• RSLinx Classic software
• Studio 5000 Logix Designer application
• SD card

IMPORTANT You cannot use any of these tools to change a the IP address of a controller:
• Bootstrap Protocol (BOOTP) server
• Dynamic Host Configuration Protocol (DHCP) server

Consider these factors when you determine how to change the IP address of a
controller:
• Network isolation from, or integration into, the plant/enterprise network

• Network size - For large, isolated networks, it can be more convenient and
safer to use a BOOTP/DHCP server rather than
the Studio 5000 environment or RSLinx Classic software. A BOOTP/
DHCP server limits the possibility of duplicate IP address assignment.

However, you can only use the BOOTP/DHCP server to set the IP
address of the controller and not to change it. If you decide to change the
IP address of the controller and want to use a BOOTP/DHCP server to
limit the possibility of duplicate IP address assignment, you must first clear
the IP address.

After clearing the IP address, use the steps that are described at Use the
BOOTP Server to Set the IP Address of the Controller on page 83 or Use
the DHCP Server to Set the IP Address of the Controller on page 89 to
set the IP address of the controller.

• Company policies and procedures that deal with plant floor network
installation and maintenance

• Level of involvement by IT personnel in plant-floor network installation


and maintenance

• Type of training that is offered to control engineers and maintenance


personnel

96 Rockwell Automation Publication 1769-UM021F-EN-P - April 2015