Beruflich Dokumente
Kultur Dokumente
CONTROLLER
OPERATORS/
INSTRUCTION MANUAL
PARTS LIST
Limitation of Liability
The remedies of the Purchaser set forth herein are exclusive, and the total liability of the Company with respect to
this contract or the Equipment and services furnished hereunder, in connection with the performance or breach
thereof, or from the manufacture, sale, delivery, installation, repair or technical direction covered by or furnished
under this contract, whether passed on contract, warranty negligence, indemnity, strict liability or otherwise, shall not
exceed the purchase price of the unit of Equipment upon which such liability is based.
The Company and its suppliers shall in no event be liable to the Purchaser, any successors in interest or any ben-
eficiary or assignee of this contract for any consequential, incidental, indirect, special or punitive damages arising
out of this contract or any breach thereof, or any defect in, or failure of, or malfunction of the Equipment hereunder,
whether based upon loss of use, lost profits or revenue, interest, lost goodwill, work stoppage, impairment of other
goods, loss by reason of shutdown or non-operation, increased expenses of operation, cost of purchase of replace-
ment power or claims of Purchaser or customers of Purchaser for service interruption whether or not such loss or
damage is based on contract, warranty, negligence, indemnity, strict liability or otherwise.
©INGERSOLL-RAND COMPANY
This unit was purchased from
______________________________________________________
______________________________________________________
______________________________________________________
Serial Number:__________________________________________
Model Number:__________________________________________
INGERSOLrAND
NGERSOLrAND
INTELLISYS
• ALARM
SEQUENCE • • SEQUENCE
UNIT 5
UNIT 1
LOADED • • LOADED
SEQUENCE • • SEQUENCE
UNIT 2 UNIT 6
LOADED • POWER
SEQUENCING
• LOADED
SEQUENCE • • SEQUENCE
UNIT 3 SEQUENCER COMPRESSOR UNIT 7
LOADED • STATUS STATUS • LOADED
SEQUENCE • • SEQUENCE
UNIT 4 UNIT 8
LOADED • • LOADED
SEQUENCING
SET SEQUENCING
START STOP
NOTICE
INGERSOLL-RAND®
1
TABLE OF CONTENTS
2
Electricity and compressed air have the potential to
0.0 SAFETY AND WARNINGS cause severe personal injury or property damage.
The operator should use common sense and good work-
Before you install this Intellisys System Controller (ISC) ing practices while operating and maintaining this unit.
you should take the time to carefully read all the instruc- All applicable codes should be strictly adhered to.
tions contained in this manual, and the compressor man-
ual. Maintenance should be done by qualified personnel,
adequately equipped with proper tools.
INGERSOLrAND
NGERSOLrAND
INTELLISYS
• ALARM
SEQUENCE • • SEQUENCE
UNIT 5
UNIT 1
LOADED • • LOADED
SEQUENCE • • SEQUENCE
UNIT 2 UNIT 6
LOADED • POWER
SEQUENCING
• LOADED
SEQUENCE • • SEQUENCE
UNIT 3 SEQUENCER COMPRESSOR UNIT 7
LOADED • STATUS STATUS • LOADED
SEQUENCE • • SEQUENCE
UNIT 4 UNIT 8
LOADED • • LOADED
SEQUENCING
SET SEQUENCING
START STOP
INGERSOLrAND
NGERSOLrAND NOTICE
INTELLISYS
• ALARM
SEQUENCE • • SEQUENCE
UNIT 5
UNIT 1
LOADED • • LOADED
SEQUENCE • • SEQUENCE
UNIT 2 UNIT 6
LOADED • POWER
SEQUENCING
• LOADED
SEQUENCE • • SEQUENCE
UNIT 3 SEQUENCER COMPRESSOR UNIT 7
LOADED • STATUS STATUS • LOADED
SEQUENCE • • SEQUENCE
UNIT 4 UNIT 8
LOADED • • LOADED
SEQUENCING
SET SEQUENCING
START STOP
3
1. The ISC can manage from 2 to 8 air compressors.
1.0 INTRODUCTION
2. Compressors can be either Intellisys or preIntellisys
One Intellisys System Controller (ISC) can sequence (rotary) models.
both rotary and reciprocating compressors. To do this, it
must have software EPROM version 1.1 or higher. 3. System air pressure control is based on a single pres-
sure point, not multiple pressure bands.
1.1 APPLICATION The ISC will operate any size SSR
rotary, Sierra oilfree rotary or Intellisys equipped recipro- 4. System air pressure settings can be user programmed
cating compressor. Recip units can be two, three or five to change, based on preset time of day and day of week.
step loading, whether inlet valve or clearance pocket
controlled. 5. Load and unload delay times can be independently set
to account for air system characteristics.
Intellisys controlled compressors connect directly to the
ISC and communicate through twisted pair cable. Rotary 6. The ISC can be located remotely from the air com-
non-Intellisys controlled compressors require an pressors.
Ingersoll-Rand supplied interface device to be installed
between the compressor and the ISC. An Intellisys 7. Connection to compressors is by telephone-type wire
Retrofit Kit is available to upgrade Ingersoll-Rand recip and connectors.
PHE, LLE or XLE compressors which are not presently
equipped with Intellisys. 8. There can be up to 8 user programmable compressor
sequences.
1.2 FEATURES The ISC is capable of controlling the
loading and unloading of multiple air compressors for the 9. Rotation from one sequence to another can be user
purpose of keeping a compressed air system’s pressure programmed based on running time, time of day and day
at or near a user set value. It is a microprocessor based, of week, or manually.
self-contained unit that is mounted and powered inde-
pendently from any compressor. 10. The ISC will not start more than one compressor at a
time.
The ISC has a variety of simple, user adjustable modes
of operation that enable it to be customized for specific 11. Smooth rotation of sequences will avoid disruptions
compressed air system conditions. In response to sys- to system air pressure.
tem air pressure variations, as measured by the ISC’s
own sensor, it adds or subtracts air compressors in an 12. ISC operating parameters can be changed without
order selected by the user. stopping the system.
There are many conveniences provided by the ISC that 13. The ISC will automatically resume operation following
simplify both its set up and use. The following list outlines a power outage.
its many installation and operational features.
4
2.0 RECEIPT OF EQUIPMENT
When you receive the Intellisys System Controller (ISC)
please inspect it closely. Any indication of careless han-
dling by the carrier should be noted on the delivery receipt
especially if the ISC will not be immediately unboxed.
Obtaining the delivery man’s signed agreement to any
noted damages will facilitate any future insurance claims.
IMPORTANT
READ THIS
LOST OR DAMAGED GOODS
Ingersoll-Rand Company
Davidson, North Carolina
APODGFO-99-79
5
3.0 INSTALLATION 3.1 ISC MOUNTING
Before beginning Intellisys System Controller (ISC)
installation and system operation, the following require- 1. The ISC can be easily installed on any suitable sur-
ments and recommendations must be satisfied. face in the general vicinity of the air compressors. Refer
to the typical air system drawing (Figure 6.12) for
1. Each Intellisys compressor must have its controller requirements.
software revision at or above a certain minimum level to
work with the ISC. The machine types and the required 2. Mount the ISC and associated wiring conduits using
software EPROM minimum version levels are listed general arrangement drawing (Figure 6.10) for mounting
below. Check each machine to be controlled by the ISC dimensions.
for appropriate EPROM’s. If the EPROM is not of the
correct minimum version level, an appropriate EPROM 3.2 PRESSURE TRANSDUCER MOUNTING/PIPING
may be ordered from your local Ingersoll-Rand
Distributor or Air Center. 1. Choose one of two typical locations for the transducer.
It can be installed in a receiver tank or in a common dis-
Machine EPROM Min. charge air header, as long as either one serves all the
Type Version Level sequenced compressors. See Figure 3.2-2 for Choice A,
the tank; and Choice B, the header. The tank is the rec-
U-Series (10-40 Horsepower) 9.3 ommended location as long as it is close to the com-
15-50 Horsepower SE 1.1 pressors.
SSR 50-450 Horsepower 1.9
SSR 50-450 Horsepower 2.0 2. In either location, mount the transducer with a dripleg
Extended Memory and isolation valve to allow for calibration and repairs.
Sierra 100-200 Horsepower 2.0 Mount as shown in Figure 3.2-1, and refer to the general
Recip 1.5 arrangement drawing (Figure 6.10) for mounting dimen-
sions.
2. The Automatic Start/Stop feature is required to be
installed on each compressor to receive the full energy 3. If the transducer is to be mounted in the air header,
saving benefits of the ISC. Compressors without the Choice B, connect it to the TOP of the header to prevent
Auto Start/Stop function will continue to run after the ISC moisture accumulation in the transducer. If the header
tells them to unload. Compressors with Auto Start/Stop runs at floor level, mount the transducer to the wall
could stop themselves after their stop-time criteria are above the header and connect it to the top of the header
met. using pipe or tubing. This will prevent moisture accumu-
lation and damage to the transducer.
3. The mounting location of the ISC’s pressure transduc-
er is very important. The ISC will load and unload com- NOTE: If there are dryers or filters installed in the sys-
pressors based on the air pressure it measures at the tem between the compressors and the ISC pressure
transducer’s location. Because the transducer will typi- transducer, the ISC’s user-set TARGET PRESSURE
cally be mounted in a receiver tank or large common air must be adjusted to compensate for the pressure drop
header, it will likely be reading pressures lower than the caused by these devices. Proper adjustment must be
compressor discharge pressures. The transducer loca- done to prevent overloading the compressor main drive
tion and the user-set TARGET PRESSURE must allow motors. This procedure is described in Section 4.2.2
for these pressure differences. Be sure to follow the PRESSURE SET UP and CONTROL.
instructions for setting the TARGET PRESSURE as
detailed in Section 4.2.2 PRESSURE SET UP AND
CONTROL.
6
SAFETY
VALVE
PRESSURE PRESSURE
GAUGE TRANSDUCER
ISOLATION
A VALVE
INGERSOLL-RAND
DRIP
LEG
RECEIVER
DRIP
LEG
TRAP
ISOLATION
B VALVE
INGERSOLL-RAND
DRAIN PRESSURE
TRANSDUCER
ISOLATION
VALVE DRIP
STRAINER
LEG
DRIP
LEG
3.3 PRESSURE TRANSDUCER WIRING 1. The transducer cable assembly included in the ISC kit
comes with a preattached transducer connector. Route
Before beginning any work on the ISC, open, lock the free end of the cable from the transducer to the ISC,
and tag the electrical disconnect for the ISC. preferably in its own grounded conduit.
7
3.5 ISC COMMUNICATION WIRING 3.7 PRESSURE TRANSDUCER CALIBRATION
1. The ISC is connected to each compressor using the This should always be done after first installing the ISC,
telephone type wire supplied in the ISC kit. Cut appropri- or after servicing the ISC or pressure transducer.
ate lengths for each compressor and route the wires in
grounded electrical conduit. These wires should be the 1. Vent the transducer to atmospheric pressure by clos-
only wires in the conduit(s). ing the isolation valve and opening the dripleg valve.
2. Install one modular plug (supplied in the kit, along with 2. With the ISC stopped and the display showing
a special tool) on each end of each wire, one end in the “READY TO START”, press the Up and Down Arrow
compressor and one in the ISC enclosure. Refer to keys simultaneously to start the ISC’s autocalibrate rou-
Figure 6.7 and 6.8 for instructions on the tool, and for tine. The display will show the message “CALIBRATING”
proper wire color codes and pin numbers. Be careful to while calibration is taking place. When calibration is suc-
match color codes and pin numbers. cessful, the display will return to “READY TO START”. If
calibration is unsuccessful, the display will show “CALI-
3. Plug the compressor end of each wire into the com- BRATION FAIL”. If this occurs, refer to Trouble Shooting
munication port on the compressor’s Intellisys panel or Chart, Section 5.0.
Intellisys circuit board, whichever is appropriate.
3. Return the transducer to system air pressure .
4. Plug the ISC end of each wire into the communication
port on top of the ISC controller that corresponds to the The ISC is now ready for entering the Set Points that
channel number you choose for each compressor. configure it for specific air system requirements. Proceed
Compressors must be connected to ports in consecutive to Section 4.2 “Setting Up The ISC”, and follow the
order, starting with port number 1. For example, if there instructions there.
are five compressors, they must be plugged into ports 1
through 5, with no unused ports between the first and
the last.
8
INGERSOLrAND
INTELLISYS
• ALARM
SEQUENCE • • SEQUENCE
UNIT 5
UNIT 1
LOADED • • LOADED
SEQUENCE • • SEQUENCE
UNIT 2 UNIT 6
LOADED • POWER
SEQUENCING
• LOADED
SEQUENCE • • SEQUENCE
UNIT 3 SEQUENCER COMPRESSOR UNIT 7
LOADED • STATUS STATUS • LOADED
SEQUENCE • • SEQUENCE
UNIT 4 UNIT 8
LOADED • • LOADED
SEQUENCING
SET SEQUENCING
START STOP
4.0 OPERATION
FIGURE 4.0-1 INTELLISYS SYSTEM CONTROLLER PANEL
9
4.0 OPERATION 4.1.2 SEQUENCER STOP BUTTON
The ISC panel contains seven buttons, twenty LED (light Pressing this button while the ISC is stopped will do a
emitting diode) lamps and a sixteen character alphanu- display test by lighting all the LED’s. This will also cause
meric display. The buttons are used for operator input, the version number of the ISC’s software to be dis-
the LED’s indicate continuous status information, and the played.
display provides additional status information during the
setting of Set Points (See Figure 4.0-1). 4.1.3 SEQUENCER STATUS BUTTON
This button has numerous functions in the Set Point rou- 4.1.10 “ALARM” LED
tine. It is used to enter the routine, to step through por-
tions of the routine and to “lock in” new set point values. An alarm status from any of the compressors, a commu-
See appropriate portions of Section 4.2 for details of its nication failure detected by the ISC or a system pressure
use. transducer failure detected by the ISC will turn on this
LED. See Section 4.6 for details of each alarm condition
A failure of the ISC’s pressure sensor is one reason for and how each is cleared.
the “Alarm” LED to light up. Pressing the SET button
when the sensor failure has been corrected will clear the 4.2 SETTING UP THE ISC
alarm and turn off the LED. See Section 4.6 for details
concerning all the alarm conditions that could cause the Setting up, or programming, the ISC is done by entering
“Alarm” LED to be on, and when it will go off. chosen values for the ISC operating parameters, which
are called set points. Figure 6.1 is a map of all the ISC
4.1.6 UP AND DOWN ARROW BUTTONS set points and provides a quick reference of how to step
the display to each one. Figures 6.2 through 6.7 list the
set points, show the value limits for each one, and pro-
vide space for recording the values chosen for specific
air system requirements.
12
4.2.2 PRESSURE SET UP AND CONTROL 2. Each Setting is enabled by specifying its Target
Pressure, Day of the Week and Time of Day, or it is dis-
The ISC controls the loading and unloading of air com- abled by specifying it as “UNUSED” in place of selecting
pressors for the purpose of maintaining a steady system a Target Pressure.
air pressure at the point where the pressure transducer
is installed. The Pressure Set Up and Control Set Points 3. Target Pressure can be set to 0 (zero), any value from
enable the user to choose the desired air pressure and 30 to 225 PSI (in 1 PSI increments) or UNUSED. A zero
to adjust three operating parameters that “tune” the ISC setting will cause the ISC to unload all machines regard-
to best maintain that pressure. The Set Points for control- less of the system pressure.
ling pressure are:
4. Any Day of the Week designator can be assigned to
Pressure Settings (including Target Pressure) any number of Settings. Day of the Week can be any
Control Band one of the following choices:
Load Delay Time
Unload Delay Time MON Monday
TUE Tuesday
The Target Pressure in the first Pressure Setting set WED Wednesday
point should initially be set to match the pressure pre- THU Thursday
sent at the transducer location prior to starting the ISC. It FRI Friday
can be adjusted later, after confirming proper air system SAT Saturday
operation. With the air system operating in typical fash- SUN Sunday
ion, press the SEQUENCER STATUS button to read the DLY Daily - every day of the week
pressure currently at the transducer. Watch the pressure WD Week Day - every day Monday thru
go up and down, noting the maximum and minimum Friday
readings. Use the pressure value midway between these WE Week End - both Saturday and Sunday
readings for the Target Pressure in the first Pressure (blank) Fixed Target Pressure - This is available
Setting. only in Setting Number 1. When “blank”
is used, the Target Pressure of Setting
PRESSURE SET UP Number 1 will be used all the time, and
Setting Numbers 2 thru 9 will not be
The ISC can store up to nine user selected Pressure available.
Settings. Each Pressure Setting can be given a Target
Pressure, a day of the week and a time of day. At the 5. Any Time of Day can be assigned to any number of
instant a Pressure Setting matches the present day and Settings. Each Time of Day can be on any hour or quar-
time, the ISC will begin loading and unloading compres- ter of an hour. Time is entered using the 24-hour clock
sors based on that Pressure Setting’s Target Pressure. method. For example, four-thirty in the afternoon would
That Target Pressure will remain active until another be entered as 16:30.
Pressure Setting matches another day and time.
6. In case two or more Pressure Settings have the same
This feature enables the system air pressure to be auto- Day of the Week and Time of Day entries, the lower
matically reduced during non-operating hours to save numbered Setting will have priority.
energy and automatically returned to the operating level
when needed. 7. When the ISC leaves the Set Point routine, the
Pressure Setting assigned to the current day and time
An example of a Pressure Setting Set Point is shown in “period” will be initiated. This is done by the ISC search-
Figure 6.4. Using the following rules as guidelines, ing through all the Settings to determine which Setting
decide what Pressure Settings are needed and write (i.e.Target Pressure) is supposed to be currently active.
them in Figure 6.4. Then perform the steps that follow
these rules to access the Set Points and to enter the 8. This Pressure Settings feature is independent of the
Pressure Settings. three modes of sequence rotation. It is active regardless
of whether rotation is under Timed, Event or Manual con-
PRESSURE SETTINGS SET UP RULES: trol.
Perform the following steps to enter or change Pressure
1. Settings are numbered 1 through 9, and any number Settings, or use the Set Point Map (Figure 6.1) as a
of them can be used. quick reference of how to get to the PRESSURE SET
UP Set Points.
13
PRESSURE CONTROL
Step Action
The ISC will maintain the Target Pressure by loading
1 While not in any Set Point routine, press the compressors when the pressure is below the “lower
SET button once and observe pressure limit”, which is defined as the Target Pressure
“PRESSURE SET UP” in the display. minus one-half of the Control Band. Likewise, the ISC
will unload compressors when the pressure is above the
2 Press SET once, observe something like “upper pressure limit”, which is the Target Pressure plus
“1 100 DLY 6:45”. one-half of the Control Band. For example, if the Target
Pressure is set at 100 PSI and the Control Band is set at
(This is the place to enter the first Pressure 8 PSI, the ISC will make decisions concerning loading
Setting. This example says the first Setting compressors when the system pressure drops to 96 PSI.
(1) will operate the ISC at a Target Pressure In the same manner, it will make decisions concerning
of 100 PSI (100) beginning every day of the unloading compressors when the system pressure rises
week (DLY) at forty-five minutes past six to 104 PSI.
o’clock in the morning (6:45). If this is the
only Setting being used, the display will not When the system pressure falls below the “lower pres-
show any day nor time designators.) sure limit”, the last compressor to have been unloaded is
immediately told to load. The Load Delay Time is the
3 Press the Up or Down Arrow buttons to set length of time the ISC then waits before telling the next
the system air pressure that the ISC is to compressor to load.
maintain. If a Setting is to be unused, press
the Arrow buttons until “PRESS#________ Explanation: Once a compressor is signaled to load,
UNUSED” appears in the display. the Load Delay Timer is reset and restarted. This
process will continue until the pressure begins to rise. As
(The display shows a cursor under the long as the pressure is rising, no more compressors will
charactor position that the arrow buttons will be told to load. If the pressure stops rising but is still
affect). below the “lower pressure limit”, the Load Delay Timer
will be reset and restarted in anticipation of telling anoth-
4 Press the Right Arrow button to position the er compressor to load. The Load Delay Timer has no
cursor under the Day or Time to be entered. effect when the system pressure is above the “lower
pressure limit”.
5 Press the Up or Down Arrow button to cycle
the item to the desired value. When the system pressure rises above the “upper pres-
sure limit”, the last compressor to have been loaded is
6 If there are more items to be entered in this immediately told to unload. The Unload Delay Time is the
particular Setting, repeat steps 4 and 5 length of time the ISC then waits before telling the next
above. When there are no more items to be compressor to unload, if the pressure is still above the
entered, press the SET button to lock in the “upper pressure limit”.
Setting values and to step to the next
Setting. Explanation: After a compressor is signaled to unload,
the Unload Delay Timer is reset and restarted, and the
7 Repeat steps 3 through 6 to program all process continues until the pressure begins to drop. If
desired Settings. the pressure stops going down but remains above the
“upper pressure limit”, the timer and unloading process
8 When all Settings are entered and confirmed will resume. The Unload Delay Timer has no effect when
correct, press the SET button to step the system pressure is below the “upper pressure limit”.
through any remaining settings until the
display returns to “PRESSURE SET UP”.
14
If the system pressure should ever rise above the “maxi-
mum pressure limit”, which is defined as 5 PSI above the Step Action
“upper pressure limit”, the ISC will tell all compressors to
unload at once. If the pressure then drops to the “upper
pressure limit” within one minute, the ISC will tell all pre- 7 Press SET once, observe
viously loaded compressors, except the last one, to load “UNLOAD _______SEC”.
again. If however, it takes the pressure more than one
minute to drop to the “upper pressure limit”, the ISC will 8 With the display showing
tell only the first compressor in the sequence to load. In “UNLOAD_______SEC”, press the Up or Down
either case, since the pressure will be within the Control Arrow buttons to set the Unload Delay Time
Band, the normal sequence logic will apply. in seconds.
The Pressure Control Set Points can be accessed by 9 Press SET to step through each of the
entering the Set Point routine while ISC is either stopped PRESSURE CONTROL Set Points and
or running. Perform the following steps to access each confirm that each is correct, or change any
item, or use the Set Point Map of Figure 6.1 as a quick as necessary.
reference of how to get to the PRESSURE CONTROL
Set Points. 10 Press the SEQUENCER STATUS button to
leave the Set Points and return the display
to normal operation.
Step Action
1 While not in any Set Point routine, press the 4.2.3 SEQUENCE SET UP
SET button once and observe “PRESSURE
SET UP” in the display. The ISC can store up to eight user selected sequences,
called sequence “A” through sequence “H”, plus a ninth
(NOTE: If you press SET more than once, the called sequence “M”, which is used only when in Manual
display will cycle through the Pressure Set Up mode. A sequence is a specified numerical order of
Set Points. Continue Pressing SET compressors which the ISC will follow when loading and
and stop with the display showing unloading compressors to maintain the system air pres-
“PRESSURE SET UP”). sure at the preset Target Pressure. Each compressor’s
number corresponds to the communication channel
2 Press the Right Arrow button once, observe number it is plugged into inside the ISC enclosure. See
“PRESSURE CONTROL” in the display, or INSTALLATION Section 3.0 for details, and refer to the
continue to press the Right Arrow button until “Compressor Control” setpoints (Figure 6.2) that was
you do see it. completed as part of the installation procedure.
3 Press SET once, observe “CONTROL The same eight sequences, “A” through “H” are used by
BAND___________.” both the Timed and the Event modes of rotating from
one sequence to the next. See Section 4.2.5, Sequence
4 Press the Up or Down Arrows to set the width Rotation Mode, for setting up the modes. It is important
of the pressure band the ISC is to use for to know that the Timed mode always rotates from one
loading and unloading compressors. The sequence to the next in “alphabetical order”. This means
width is always even, with half of it above the that when Timed mode is started, sequence “A” will
Target Pressure and half below the Target always run first, followed by “B” after the Elapsed Run
Pressure. Time expires, followed by “C”, etc.
(Note: See the beginning of this section for an explana- Timed mode rotation will loop from the last sequence
tion of the Control Band, the Load Delay Time, and the entered back to “A” and continue indefinitely.
Unload Delay Time.)
Using the following rules, decide what sequences the
5 Press SET once, observe “WAIT LOAD______ ISC is to use and write them in the appropriate section
SEC”. of Figure 6.6. Then perform the steps that follow these
rules to enter the chosen sequences into the ISC.
6 With the display showing “WAIT
LOAD _____SEC”, press the UP or Down
Arrow buttons to set the Load Delay Time in
seconds.
15
SEQUENCE SET UP RULES:
Step Action
1. Compressors are numbered 1 through 8 with no gaps in
the numbering. For example, if there are five compressors, 1 While not in any Set Point routine, press
they must be connected to communication channels 1 the SET button once and observe
through 5. “PRESSURE SET UP” in the display.
2. Sequences lettered A through H are used for both (NOTE: If you press SET more than once,
Timed and Event modes. Sequence M is used only by the the display will cycle through the Pressure
Manual mode, and its set up is described in the Manual Set Up Set Points. Continue pressing SET
mode portion of Section 4.2.5. and stop with the display showing
“PRESSURE SET UP”).
3. Any number of the eight sequences can be used. All of 2 Press the Right Arrow button twice, observe
them do not need to be entered. “SEQUENCE SET UP” in the display, or
continue to press the Right Arrow button
4. Compressors can be entered in any sequence, in any until you do see it.
order.
3 Press SET once, observe something like
5. The first compressor (number) entered in any sequence “SEQ A 213”.
will be the first one to load when air is needed. It is com-
monly refered to as the “lead” compressor. Loading of the (This is the place to enter the first se-
other compressors will follow in the order in which they are quence, “A”. This example shows se-
entered in the sequence, from left to right. quence “A” with compressor number 2 as
the “lead” compressor (first to load) follow-
6. The same compressor number can not be entered into a ed by compressor 1 followed by com-
given sequence more than once. pressor 3. The display shows a cursor
under the compressor position that the ar
7. No compressor number larger than the quantity of com- row buttons will affect. In the example, the
pressors entered in the Initial Set Up can be entered in cursor position would be under 2).
any sequence. 4 Press the Up or Down Arrow button to cy-
cle the number to the compressor to be put
8. Leaving the first character position in any sequence in the first position in the sequence.
“blank” will indicate that sequence is not used.
(NOTE: When a position’s compressor
Perform the following steps to enter or change sequences, number is changed, all compressor
or use the Set Point Map (Figure 6.1) as a quick reference numbers to the right will go blank).
of how to get to the SEQUENCE SET UP Set Points.
5 Press the Right Arrow button once to step
the display cursor to the next compressor
number position to be entered.
6 Press the Up or Down Arrow button to cy-
cle the number to the compressor to be put
in this position in the sequence.
1 While not in any Set Point routine, press The Set Point Map (Figure 6.1) can be used as a quick
the SET button once and observe reference of how to get to the ROTATION SET UP Set
“PRESSURE SET UP” in the display. Points. Also, it is recommended that the ISC Set Up Log,
“Sequence Rotation Mode” Set Points, (Figure 6.7) be
(NOTE: If you press SET more than once, used for writing down the desired Set Points before
the display will cycle through the Pressure entering them into the ISC. The Log is then available to
Set Up Set Points. Continue pressing SET serve as a reference for checking what Set Points have
and stop with the display showing been entered.
“PRESSURE SET UP”).
2 Press the Right Arrow button three times, TIMED ROTATION MODE
observe “COMP CONTROL” in the display,
or continue to press the Right Arrow button In TIMED rotation mode, the ISC rotates from the cur-
until you do see it. rently running sequence to the next one every time the
accumulated compressor running hours during the cur-
3 Press SET once, observe something like rent sequence equals the “Elapsed Run Time” hours set
“#1 LOCAL”, This would indicate that point. “Compressor running hours” is defined as the time
compressor 1 is under its own (local) accumulated when at least one compressor on the ISC
control. is running and when the ISC is in TIMED mode.
4 Press the Up or Down Arrow button to The order of rotation is always sequence A followed by
toggle the compressor between LOCAL or SE- B, then C, etc. to the last sequence entered, then back
QUENCE CONTROL, leaving the display at to A. This means that when the TIMED mode is selected
the selected mode. after making any change to any sequence, the ISC will
restart sequencing with sequence A and will reset the
5 Press SET once to lock in the selected accumulated compressor running hours to zero. On the
mode for that compressor and to step to other hand, if TIMED mode was active, then replaced by
the next compressor. another mode, then reactivated with no changes having
been made to any sequences, ISC operation will resume
6 If there are more compressors to have their in the same sequence (rotating to it if necessary) and
control mode set, repeat steps 4 and 5 with the same accumulated compressor running hours
above. When the control of all compressors that were present when TIMED mode was exited.
has been set and confirmed correct, press
the SEQUENCER STATUS button to leave The only set up required that is unique to the TIMED
the Set Points and return the display to rotation mode is the entering of the Elapsed Run Time
normal operation. Set Point. Perform the following steps to enter or change
the Elapsed Run Time, or use the Set Point Map (Figure
4.2.5 SEQUENCE ROTATION MODES 6-1) as a quick reference of how to get to the TIMED
rotation mode and the Set Points.
One sequence of compressors can be replaced by
another sequence through a process called “rotation”.
Rotating from one sequence to another can be initiated
17
EVENT ROTATION MODE
Step Action
In the EVENT rotation mode, the ISC rotates from the
1 While not in any Set Point routine, press currently running sequence to the sequence specified to
the SET button once and observe be active at the moment an Event matches the present
“PRESSURE SET UP” in the display. day and time. An Event is defined as a user set day of
the week and a user set time of that day. There can be
(NOTE: If you press SET more than once, as many as nine Events entered through the Set Point
the display will cycle through the Pressure routine. Each Event can be preset to start a selected
Set Up Set Points. Continue pressing SET sequence on a selected day of the week at a selected
and stop with the display showing time of day. That sequence will remain active until
“PRESSURE SET UP”). another Event occurs.
2 Press the Right Arrow button four times, An example of an Event Set Point is shown in the ISC
observe “ROTATION SET UP” in the Set Up Log (Figure 6.7). Using the following rules as
display or continue to press the Right Arrow guidelines, decide what Events are needed and write
button until you do see it. them in the ISC Set Up Log (Figure 6.7) Then perform
the steps that follow these rules to access the Set Points
3 Press SET once and observe the presently and to enter the Events.
active Rotation Mode showing in the
display. EVENT SET UP RULES:
4 If necessary, press the Up or Down Arrow 1. Events are numbered 1 through 9, and any number of
button one or two times until them can be used.
“MODE: TIMED” is displayed.
2. Each event is enabled by specifying its Sequence,
(NOTE: The mode that was active when the Day of the Week and Time of Day, or it is disabled by
set point routine was entered will remain specifying it as “UNUSED” in place of selecting a
active even when accessing other modes Sequence.
and their set points. The mode that the ISC
is running will change only upon exiting the 3. Any of the sequences, A through H, can be assigned
set point routine). to any number of Events. However, a sequence must first
be programmed through the SEQUENCE SET UP Set
5 Press SET once, observe “SEQ CHG______ Points before it can be assigned to an Event (See
HRS”. Section 4.2.3 for Sequence Set Up).
(NOTE: The display will flash twice in- 4. Any Day of the Week designator can be assigned to
dicating the TIMED Mode has been any number of Events. Day of the Week can be any one
selected if some other mode had previously of the following choices:
been active).
MON Monday
6 Press the Up or Down Arrow buttons to set TUE Tuesday
the compressor running hours the ISC is to WED Wednesday
accumulate before rotating to the next THU Thursday
sequence. FRI Friday
7 Press SET once to lock in the selected SAT Saturday
hours and to return to “ROTATION SET SUN Sunday
UP”. DLY Daily - every day of the week
8 Press the SEQUENCER STATUS button to WD Week Day - every day Monday thru Friday
leave the Set Points and return the display WE Week End - both Saturday and Sunday
to normal operation. This will cause the
TIMED mode to immediately become active. 5. Any Time of Day can be assigned to any number of
Events. Each Time of Day can be on any hour or quarter
of an hour. Time is entered using the 24-hour clock
method. For example, four-thirty in the afternoon would
be entered as 16:30.
18
6. In case two or more Events have the same Day of the
Week and Time of Day entries, the lower numbered Event Step Action
will have priority.
5 Press SET once, observe something like
7. When Event Mode is selected to be active, the “1 A MON 6:45”.
sequence assigned to the current day and time “period”
will be initiated. This is done by the ISC searching through (NOTE: The display will flash twice in-
all the Events to determine which Event (and sequence) is dicating the EVENT Mode has been
supposed to be currently active and rotating to it. selected if some other mode has previously
been active.)
8. Remember to adjust the Day and Time Clock when
appropriate for Daylight Savings Time. (This is the place to enter the first Event.
This example says the first Event (1) will
Perform the following steps to enter or change Events, or start sequence A (A) every Monday (MON)
use the Set Point Map (Figure 6.1) as a quick reference of morning at forty-five minutes past six
how to get to the EVENT rotation mode Set Points. o’clock (6:45). If this Event has previously
been unused, the display will say “EVENT
#1 UNUSED”).
Step Action
6 Press the Up Arrow button to cycle the se-
1 While not in any Set Point routine, press quence letter to the one intended for this
the SET button once and observe Event or to “UNUSED”.
“PRESSURE SET UP” in the display.
(The display shows a cursor under the
(NOTE: If you press SET more than once, character position that the arrow buttons
the display will cycle through the Pressure will affect).
Set Up Set Points. Continue pressing SET
and stop with the display showing 7 Press the Right Arrow button to position the
“PRESSURE SET UP”). cursor under the Day or Time item to be
entered.
2 Press the Right Arrow button four times,
observe “ROTATION SET UP” in the 8 Press the Up or Down Arrow button to cy-
display, or continue to press the Right cle the item to the desired value.
Arrow button until you do see it.
9 If there are more items to be entered in this
3 Press SET once and observe the presently particular Event, repeat steps 7 and 8
active Rotation Mode showing in the above. When there are no more items to be
display. entered for this Event, press the SET but-
ton to lock in the Event values and to step
4 If necessary, press the Up or Down Arrow to the next Event.
button one or two times until “MODE:
EVENT” is displayed. 10 Repeat steps 6 through 9 to program all
desired Events.
(Note that the mode that was active when
the set point routine was entered will re- 11 When all Events are entered and confirmed
main active even when accessing other correct, press the SET button to step
modes and their set points. The mode that through any remaining Events until the
the ISC is running will change only upon display returns to “ROTATION SET UP”.
exiting the set point routine).
12 Press the SEQUENCER STATUS button to
leave the Set Points and return the display
to normal operation. This will cause the
EVENT mode to immediately become
active.
19
MANUAL ROTATION MODE
1 While not in any Set Point routine, press 6 Press the Right Arrow button to step the
the SET button once and observe display cursor to the compressor number
“PRESSURE SET UP” in the display. position to be entered.
(NOTE: If you press SET more than once, (In the example, the first position would be
the display will cycle through the Pressure under the 4).
Set Up Set Points. Continue pressing SET
and stop with the display showing 7 Press the Up or Down Arrow button to cy-
“PRESSURE SET UP”). cle the number to the compressor to be put
in this position in the sequence.
2 Press the Right Arrow button four times,
observe “ROTATION SET UP” in the 8 If there are more compressor numbers to
display or continue to press the Right Arrow be entered, repeat steps 6 and 7 above.
button until you see it.
If there are no more compressor positions
3 Press SET once and observe the presently to be entered in the Manual sequence,
active Rotation Mode showing in the press the SET button to lock in this se-
display. quence and to return to “ROTATION SET
UP”.
4 If necessary, press the Up or Down Arrow
button one or two times until “MODE: 9 Press the SEQUENCER STATUS button to
MANUAL” is displayed. leave the Set Points and return the display
to normal operation. This will cause the
(Note that the mode that was active when MANUAL mode to immediately become ac-
the set point routine was entered will re- tive, and the ISC will rotate directly to
main active even when accessing other Manual sequence M.
modes and their set points. The mode that
the ISC is running will change only upon
exiting the set point routine).
20
4.3 STARTING AND STOPPING 5. The ISC leaves the auto start/stop function to the indi-
vidual compressors. The ISC will not stop machines. A
There are general rules to keep in mind when starting an compressor will stop itself if it meets its own set point cri-
air system controlled by an ISC. However, there is not teria for doing an auto stop. It will then restart when it
one, strict way that it has to be done. Observe the follow- receives a load command from the ISC.
ing rules to ensure a smooth start up.
The ISC is stopped by pressing the SEQUENCER STOP
1. Compressors can be either started or stopped when button. This stops all sequencing of compressors, but
the ISC is started. compressor status is still available. Load and unload
control of the compressors is returned to their respective
2. Each compressor must be started at its own control local controllers. As long as the Rotation Mode set points
panel and placed in a mode able to load before the ISC are not changed, pressing the SEQUENCER START
can take control, If a compressor is stopped locally, it button will restart the ISC operation in the same mode it
must be started locally again. The following list outlines was in when stopped.
what to do for each of five types of Ingersoll-Rand
Intellisys compressors to enable them to give control to NOTE: When the ISC is stopped, each compressor
the ISC. It is recommended that all compressors have might start, stop, load or unload itself depending on its
the auto start/stop feature installed for maximum energy own local conditions and set points. For example, if the
savings. ISC is stopped while it is operating the system at a pres-
sure lower than a compressor’s on-line setting, and the
5-10 Install an ISC Interface II Kit. compressor is stopped by its Auto Restart, the compres-
Start the compressor (it auto loads). sor might immediately start.
SE Models Turn the sequence option set point 4.4 ISC STATUS
“ON”.
Start the compressor (it auto loads). Repeatedly pressing the SEQUENCER STATUS button
will step the display through the following ISC status
U-Series Start the compressor. messages.
Press the LOAD button.
System Pressure
SSR/Sierra Turn the sequence option set point Current Sequence
“ON”. Mode of Operation or Time to Next Rotation
Start the compressor. Target Pressure
Press the ON-LINE/OFF-LINE button. Clock
Recip Turn the sequence option set point System Pressure is the air pressure currently being
“ON”. measured by the ISC pressure transducer. This is the
Start the compressor. normal, or default, display message after the ISC is
Press the CONSTANT SPEED started. The display will automatically return to this mes-
CONTROL or AUTO/DUAL button. sage if no button is pressed in 30 seconds.
3. After all installation and set up instructions have been Current Sequence is the sequence of compressors cur-
completed as described earlier in this manual and the rently being followed by the ISC, showing the compres-
display shows “READY TO START”, the ISC is started by sor numbers in order from left to right.
pressing the SEQUENCER START button.
Mode of operation is “EVENT MODE” if the ISC is cur-
4. Based on the current pressure reading and the Target rently operating in Event Rotation Mode or “MANUAL
Pressure set point, the ISC will load compressors in the MODE” if currently in Manual Rotation Mode. If the ISC
order specified by the current sequence. Any compres- is currently in Timed Rotation Mode, the display will be
sor not properly started and enabled for sequencing will “SEQ CHG 125 HRS” showing how many hours (exam-
be skipped in the sequence. Each compressor’s status ple is 125) until the ISC rotates to the next sequence. If
can be observed on the ISC, refer to Section 4.5. If a the remaining time is less than two hours, it will show the
compressor is enabled after the ISC is started, it will be time in minutes.
included in the sequence in its appropriate position when
demand for air warrants it. Target Pressure is the air pressure in the Pressure
Setting that the ISC is currently using for managing the
air system.
Clock is the current day of the week and the current time
expressed in 24-hour format.
21
4.5 COMPRESSOR STATUS 4.6 ALARMS
As described in Section 4.1.9 there is a pair of front The “Alarm” LED on the ISC’s front panel will light for
panel status LED’s “Sequence” and “Loaded”, for each any one of the following three reasons.
compressor under the control of the ISC. Each
“Sequence” LED lights to indicate that compressor is in 1. Any time the ISC receives an Alarm status message
Sequence mode through the communication channel to from any compressor, it turns on the “Alarm” LED and
the ISC. Each “Loaded” Led lights to indicate that com- provides the Alarm message for that particular compres-
pressor is running loaded. sor as described in Section 4.5 . When the compressor’s
Alarm condition is cleared at the machine, the ISC auto-
In addition, there are more detailed status messages matically turns off the “Alarm” LED and changes that
available through the display. Repeatedly pressing the compressor’s status message accordingly.
COMPRESSOR STATUS button will step the display
through each compressor number (#1 through the num- 2. Any time the ISC detects a failure to communicate
ber of compressors entered during initial set up), accom- with a compressor, it turns on the “Alarm” LED and pro-
panied by a message indicating that compressor’s sta- vides the Communication Failure message for that par-
tus. There are seven different status messages that can ticular compressor as described in Section 4.5. When
be displayed for each compressor. The messages and communication is reestablished with the compressor, the
their meanings are as follows: ISC automatically turns off the “Alarm” LED and changes
that compressor’s status message accordingly.
“#1 LOCAL” Compressor number 1 is not under
sequence control. 3. If the ISC determines it is no longer receiving valid
readings from its pressure transducer, it turns on the
“#1 RUNNING Compressor number 1 is not under “Alarm” LED, displays “SENSOR FAILURE” and stops all
LOCAL” sequence control and is running. sequencing, allowing the compressors to return to their
local controls. The ISC will stay in this state until the sen-
“#1 STOPPED” Compressor number 1 is under sor problem is corrected and the alarm is manually
sequence control and is stopped in its cleared through the front panel. The alarm state is
auto restart mode. cleared by pressing the SET button. To resume sequenc-
ing, the ISC must be started by pressing the
“#1 RUNNING” Compressor number 1 is under SEQUENCER START button. This is the only alarm that
sequence control and is running. will not automatically clear when the problem is correct-
ed.
“#1 WARNING” Compressor number 1 is in a “WARN-
ING” state defined by its own controller. The “Volt-free Alarm Contacts” on connector J1 terminals
4, 5 and 6 will activate for any compressor Alarm or for
“#1 ALARM” Compressor number 1 has stopped an ISC sensor failure. The contacts reset to normal con-
itself in an “Alarm” state defined by dition when the Alarm is cleared per the above Alarm
its own controller. LED descriptions.
“#1 COMM Compressor number 1 com- The ISC software versions for which the Alarm LED and
FAILURE” munication channel has persistent the Alarm Contacts are active are summarized in the fol-
serial communication problems from lowing table:
which the ISC is unable to
automatically recover. ISC Software Alarm LED Alarm Contacts
v1.0/v1.1/v1.2 Activated Activated
22
5.0 ISC TROUBLE SHOOTING
CHART
ISC POWER light is off. No message in display, no lights on. 1. Check fuse and wiring connections.
Bad system air pressure readings. “SENSOR FAILURE” 1. Check for defective ISC air system
pressure transducer, bad connections
or broken wires.
Zero pressure reading when pressure 1. Check air system pressure transducer
is present. isolation valves to ensure system air
is getting to the transducer.
Any compressor’s (#n) “#n COMM FAILURE” 1. Check compressor to ensure power
communication problem. is on and compressor controller is
operating.
23
6.0 REFERENCE DRAWINGS
24
6.4 “PRESSURE SETTINGS” SET POINTS
25
FIGURE 6.6 “SEQUENCE SET UP ” SET POINTS
26
The following are instructions to attach 6 position modu- 5. Insert modular plug connector - TAB UP - into die set.
lar plugs to communication cable. LOCKING TAB MUST SNAP INTO CAVITY.
1. Trim cable end flush. 6. Squeeze tool handles together until movable anvil is
completely bottomed. Two “clicks” or 11 snaps” should be
2. Strip off 1/4” of cable jacket from wires. heard or felt.
3. Cut off the blue with white stripe and the white with 7. Allow tool handles to open fully, depress locking tab
blue stripe wires. on connector and remove terminated connector.
28
39842224
REV 01
29
30
GROUND CONDUIT
WITH COMMUNICATION
WIRES GOING TO AIR SYSTEM
COMPRESSOR BEING TRANSDUCER CABLE
SEQUENCED
LOCKABLE
ELECTRICAL
DISCONNECT
INGERSOLrAND
NGERSOLrAND
INTELLISYS
• ALARM
SEQUENCE • • SEQUENCE
UNIT 5
UNIT 1
LOADED • • LOADED
SEQUENCE • • SEQUENCE
UNIT 2 UNIT 6
LOADED • POWER
SEQUENCING
• LOADED
SEQUENCE • • SEQUENCE
UNIT 3 SEQUENCER COMPRESSOR UNIT 7
LOADED • STATUS STATUS • LOADED
SEQUENCE • • SEQUENCE
UNIT 4 UNIT 8
LOADED • • LOADED
SEQUENCING
SET SEQUENCING
START STOP
NOTICE
INGERSOLL-RAND®
INCOMING
INTELLISYS SYSTEM CONTROLLER
POWER
39844105
REV 01
31
7.0 PARTS LIST
39839253
REV 03
32
39839253
REV 03
33
34
39841838
REV 02
PRESSURE TRANSDUCER ASSEMBLY
ITEM PART
NO. NUMBER QTY. DESCRIPTION
1. 39841630 1 ENCLOSURE
2. 39566500 1 TRANSDUCER,PRESSURE
3. 39153861 1 BUSHING
4. 50677459 1 BULKHEAD ASSY. (3 PARTS)
5. 39131859 1 O-RING
6. 42368530 1 CABLE ASSEMBLY
7. 39173935 1 LOCKNUT
8. 39173927 1 GLAND
35
ISC KIT (PART NO. 42367813)
PART
NUMBER OTY. DESCRIPTION
36
8.0 MAINTENANCE RECORD
37
MAINTENANCE RECORD
38