Beruflich Dokumente
Kultur Dokumente
DESCRIPTION
1710±10
1 - CONNECTION BETWEEN PHASES
A 855 855 A
The information contained in this document is to be kept strictly confidential. Any unauthorized use, reproduction, distribution or disclosure is strictly forbidden. © Copyright 2015 ABB. All rights reserved.
2 - COOLING FAN
166±10 570±10 570±10
384(Ref.) 431.7(Ref.) 3 - EARTHING TERMINAL M12x30
420 420
4 - H.V. TERMINAL
n a b c 6
5 - L.V. TERMINAL
6 - RATING PLATE
5 7 - TAP CHANGER BY LINKS
A B C 8 - WHEELS D125x40
B B
1821±20
SPECIFICATION
RATED POWER 1250 kVA
22000 V
1312±20
RATED HIGH VOLT.
7
RATED LOW VOLT. 400 V
FREQUENCY 50 Hz
888
1 INSULATION SYSTEM (HV/LV) F/F
C C
VECTOR GROUP Dyn11
TOTAL WEIGHT 3150 kg
TOLERANCES ACCORDING TO ISO 2768V
8 240 3
97.5
820 820
2
920
D D
2- 18
L.V. TERMINAL n-a-b-c
a (TOP) b (TOP) c (TOP) H.V. TERMINAL A - B - C
100
n (TOP)
50 30
LV SIDE 4- 14
∅14X18
42.5 22
50
25
∅14
E E
MATERIAL: COPPER
MATERIAL: COPPER THICKNESS: 4 mm
HV SIDE THICKNESS: 12 mm
2 - COOLING FAN
225±10 620±10 620±10
420 420 3 - EARTHING TERMINAL M12x30
n a b c 6 4 - H.V. TERMINAL
5 - L.V. TERMINAL
6 - RATING PLATE
5
7 - TAP CHANGER BY LINKS
A B C
B B
2214±20
SPECIFICATION
RATED POWER 2000 kVA
RATED HIGH VOLT. 22000 V
1602±20
7
RATED LOW VOLT. 400 V
FREQUENCY 50 Hz
1
1044
INSULATION SYSTEM (HV/LV) F/F
C C
VECTOR GROUP Dyn11
TOTAL WEIGHT 4450 kg
TOLERANCES ACCORDING TO ISO 2768V
3
1070
1070
2
1170
D D
2- 18
42.5 22
∅14
40
70
E E
10
100 107.1
13 14 15 16 17 18 19 20 21 22 23 24 Unit :mm
Temperature Controller KN804
A B B- A B B- A B B-
T.MAX TRIP
A B B-
SCAN
AUTO ℃ ALARM
FAN
MAN FAULT
CH 1 CH 2 CH 3 CH 4 100 COM
CH 89.8
Pt100Ω
PRG ON FAN ON BUZZER ON
Pt100Ω Pt100Ω Pt100Ω
SENSER
MODE
▲
SENSER SENSER SENSER RES ET
TEST
PRG ▲
FAN
T.MAX
STOP MAN ENT
54 T/X-
COMMUNICATION
T/X+ RS-485
53
52 - 122
DC4~20mA
51 + PANEL CUTTING SIZE
AC100~240V
ALARM TRIP FAULT FAN 50~60Hz
OUT OUT OUT OUT DC100~300V
92
1 2 3 4 5 6 7 8 9 10 11 40 41 42
87.6 92
2 - COOLING FAN
210±10 610±10 610±10
410 410 6 3 - EARTHING TERMINAL M12x30
n a b c 4 - H.V. TERMINAL
5 - L.V. TERMINAL
5 6 - RATING PLATE
1948±20
SPECIFICATION
RATED POWER 1600 kVA
RATED HIGH VOLT. 22000 V
1357±20
7
RATED LOW VOLT. 400 V
FREQUENCY 50 Hz
930
1 INSULATION SYSTEM (HV/LV) F/F
C C
VECTOR GROUP Dyn11
TOTAL WEIGHT 3640 kg
TOLERANCES ACCORDING TO ISO 2768V
8 240 3
99.5
820 820
920 2
D D
2- 18
L.V. TERMINAL n-a-b-c H.V. TERMINAL A-B-C
a (TOP) b (TOP) c (TOP) 150 30
n (TOP) 50
6- 14
∅14X18
LV SIDE
42.5 22
∅14
40
70
E E