CAPITAL CONTROLS

Chloralert™
Series T17CA4000
Chlorine Detector

The Chloralert™ Series T17CA4000 is a mounted remotely with up


low-cost, simply operated device designed to 26 feet (8 m) of sample
to detect and provide a warning of the pipe or located within the
presence of chlorine gas in air. The unit Chlorine area. The detector
is suitable for use in any location where contains a local alarm light
Chlorine is manufactured, used or stored, and electrical contacts for
provided the Chloralert™ is protected the actuation of external
from rain, snow, sleet, and subzero alarm devices in the event
temperatures. The detector may be Chlorine is sensed.
Factory set alarm levels
of 1 ppm or 3 ppm are
available, and alarm
relays can be supplied
as energized in alarm
condition (STD) or
de-energized (Fail Safe).
The Fail Safe design also
includes an optical flow
switch to detect when there
is no sample flow.

WATER MADE EASY

MARINE ENERGY MUNICIPAL INDUSTRIAL


• Simple to Operate – Self-contained test switch permits Operation
functional check of circuitry. The Chloralert™ uses glycerin-containing potassium
• Low Maintenance – Under normal operation unit needs bromide as the electrolyte in the electrode cell. Two
cleaning once a year (8 months if continuously operated platinum electrodes are partially immersed in this
at maximum temperature of 149°F (60°C). No reagent electrolyte and have a low voltage impressed across them.
bottles to refill. Plug in alarm relay. An internal blower draws an air sample into the unit
where it passes through a flow indicator to permit positive
• Sensitive – Will sense and alarm at chlorine levels below adjustment of sampling rate. From this meter the sample
the threshold of smell to conform to the OSHA Short flows to the electrode cell where an amperometric
Term Exposure Limit of 1 ppm. signal is generated by the presence of even minute
• Adaptable – Small, lightweight unit is easily wall mounted concentrations of Chlorine. This current is sensed by a
where space is available. unique self-contained electronic circuit and is used to
trigger the alarm system causing the alarm light to flash
• Convenient – Self-contained sample system permits
and the plug-in relay contacts to change state.
unit to be mounted remotely, even out of doors when
protected from inclement or subzero weather, with Because of the unique measuring cell design, the wall
sample pipe run to Chlorine area. mountable instrument will alarm within seconds for
a 1 ppm Chlorine leak, and reach equilibrium equally
Engineering Specifications fast once the leak disappears. Once actuated, the
Detection Level circuitry is specifically designed to demand the alarm be
acknowledged with the spring loaded reset switch.
Fixed at 1 ppm Chlorine by volume (3 mg/m3)
If the sample still contains Chlorine above the 1 ppm
Fixed at 3 ppm Chlorine by volume (9 mg/m3) level, the alarm contacts will transfer to their normal
Materials of Construction (non-alarm) position while the reset switch is depressed
and will immediately return to the alarm position when
Housing: ABS and polycarbonate plastic the reset switch is released. The test switch, when
Cell: ABS plastic depressed together with the reset switch, substitutes a
Electrodes: Platinum simulated measuring cell current permitting a sample
check to be made of the circuit performance.
Electrical Connections: ¾ inch NPTI for electrical
conduit on bottom of unit.
Model Number Designation
Electrolyte: Unit supplied with a bottle of premixed
T17CA4 B
electrolyte (5 year supply under normal conditions).
Basic CHLORALERT™
Electrical Requirements: 120, 220/240 Vac ±10%,
50/60 Hz, 1 ph. Alarm Design
Power Consumption: 20 W 1 - Std
Relay Contacts: DPDT relay, contacts rated 10 A 2 - Fail Safe
resistive; 240 Vac, 28 vdc Electrical Requirement
Weight: 5 lbs. (2.3 kg) Sample Tubing Kit adds 8 lbs. 10 - 120 Vac, 60 Hz
(3.6 kg).
20 - 220 Vac, 50 Hz
Mounting: Wall
30 - 110 Vac, 50 Hz
Dimensions: 8-½" H x 6-3/8" W x 9-¼" D
(216 mm x 162 mm x 235 mm) Design Level

Sampling Rate: 2 std ft3/min (0.057 m3/min) nominal Alarm Level

Cell Response Time: Instantaneous electrochemical 3 - 1 ppm, Fixed


reaction at electrodes. 4 - 3 ppm, Fixed
Ambient Temperature: -4 to 149°F (-20 to 65°C)
Sample Inlet Connection: 1 inch NPTI on bottom of unit.
Note: Since chlorine is heavier than air, the unit or the end of the sample line should be
located no more than 6 inches (152 mm) above the floor. If desired, the detector may
be mounted at a convenient height and location with 1 inch PVC pipe or 1 inch flexible
tubing [25 feet (7.6 m) maximum] run from the unit to the sample point.
Equipment Description
The Chlorine detector shall be a wall mounted device The detector shall include an alarm reset switch for alarm
suitable for monitoring the air in a Chlorine area. It shall acknowledgment and a test switch to permit simple
include a self-contained sample blower for positive air checking of the circuits. Detectors utilizing automatic reset
sampling to avoid Chlorine buildup in stagnant areas, are not acceptable because they do not provide a history
and an easy to read flowmeter to indicate the sample is of leaks and even though the circumstances causing the
reaching the measuring cell. The unit shall use a glycerin- alarm may be gone, the leak may not.
based electrolyte that shall not require replacement more
The Chlorine detector shall be a Capital Controls®
than once a year under normal operation and be supplied
Chloralert™ Series T17CA4000. It shall be supplied
with a 5-year supply of pre-mixed electrolyte. Detectors
complete with all standard accessories.
utilizing water-based electrolytes or one depending on
dispersion or convection currents to bring chlorine to the Optional Equipment
measuring cell are not acceptable. Sample tubing kit – 25 feet (7.6 m) of 1-inch (25.4 mm)
ID flexible PVC tubing and adaptor.
The detector shall contain necessary electronic circuits
to trigger an alarm condition when the Chlorine Ordering Information
concentration in the sample exceeds 1 ppm. The alarm When ordering please specify:
level shall be fixed by design to avoid unauthorized • Model Number
adjustments, that may be harmful to personnel and above
• Voltage and Frequency
the current OSHA limit. The alarm shall be evidenced by
a flashing light on the front of the unit and a change in • Optional Equipment
state of the relay contacts for actuation of remote devices.
The relay shall be of the plug-in type and shall have
double pole, double throw contacts rated at 10 amperes.

ELECTRODES
SAMPLE VENT

SAMPLE IN

MEASURING CELL

PRINTED CIRCUIT BOARD


ELECTROLYTE

BLOWER MOTOR
SAMPLE FLOW ADJUST

FLOWMETER

CELL DISCHARGE TUBING

BY-PASS VALVE

SAMPLE IN
RESET SWITCH

TEST SWITCH
BLOWER HOUSING

POWER ON/ALARM LIGHT

Functional Illustration
CAPITAL CONTROLS®
Chloralert™ Series T17CA4000

Warranty and Capability


De Nora Water Technologies warrants its gas detectors for
eighteen (18) months from the date of invoice, or twelve
(12) months from date of installation.
De Nora Water Technologies is ISO 9001 certified to
provide quality and precision materials. Disinfection
technologies, water quality monitors and instrumentation
for water and wastewater are areas of specialization. Over
35 years of industrial and municipal application experience
in the water and wastewater industries is incorporated
into the equipment design to provide high quality
comprehensive solutions for the global market.

WATER MADE EASY

MARINE ENERGY MUNICIPAL INDUSTRIAL

info.dnwt@denora.com www.denora.com

© Copyright 2018 Industrie De Nora S.p.A. - All rights reserved.


De Nora, ON circle, Our research - your future, electrochemistry at your service (and any other
trademark name) are trademarks or registered trademarks of Industrie De Nora S.p.A. in Europe and/or
other countries. Other trademarks used herein are the registered trademarks of their respective owners.
The information contained herein is offered for use by technically qualified personnel at their discretion
and risk without warranty of any kind.

DNWT - CAPITAL CONTROLS® Chloralert™ Series T17CA4000 - 325.0030.7 - 4/2018