Beruflich Dokumente
Kultur Dokumente
TRANSMISSION
SYSTEM STUDY IN
ATP-EMTP
Power System Protection Lab Work
High Voltage and High Current Laboratory
Institut Teknologi Bandung
MODULE 3-3
TRANSMISSION SYSTEM STUDY
IN ATP-EMTP
A. Experiment
A lightning strikes over the insulation of a transmission line causing an
overvoltage that depends mainly on the magnitude of the discharge and the
ground resistance. The parameter that has traditionally measured this behavior
is the number of line outputs per 100 km in length and per year, a parameter
that constitutes an insulation design criterion, or a measure of performance for
a line that is already built. Lightning is a phenomenon that causes an
overvoltage of external origin or simply of atmospheric origin. Atmospheric-
based overvoltage is independent of the operating voltages of the power
systems as opposed to those that occur by maneuver, depending on the
nominal voltage level of the systems. The relative importance of atmospheric
surges increases as the voltage level of the systems decreases. Transmission
systems are usually designed with a shield of a very small failure probability.
Lightning strikes that would fall directly would be very unlikely. The inverse
flare caused by a discharge that falls on the tower or on the guard wire is the
most common cause of line output. It is called inverse flame because it is from
the neutral to the phase, due to the increase in voltage is the same.
𝑅𝑖 =
∆𝑅𝑖 . 𝑥𝑖 ……………………………………………(3.1)
𝐿𝑖 =
2𝜏𝑅𝑖 ……………………………………………....(3.2)
∆𝑅1 = ∆𝑅2 = ∆𝑅3 =
2𝑍𝑡1 1
(ℎ−𝑥4 )
. ln (𝛼1)…………………….........................(3.3)
∆𝑅4 =
2𝑍𝑡4 1
. ln (𝛼4).............................................................(3.4)
ℎ
where
𝜏 = ℎ/𝑐0 – traveling time along the tower;
𝑎1 = 𝛼4 = 0.89 – attenuation along the tower;
ℎ – tower height
where
ℎ is height of the cross-arms, m
𝑟𝐴 is radius of the cross-arms, m
2. Lightning Source
Impulse-current magnitude due to lightning charge is a
probability function. Low discharge levels of lightning current (about
5-22 kA) may increase the tendency for lightning-strike to pass by
shield wires (ground wires), instead of striking a phase-conductor.
Lightning impulse currents of large magnitudes will strike a tower top
or overhead ground wire, causing back flashover across insulator
string.
In ATP- EMTP software, lightning-strike model is represented
by a current source with parallel resistance. The parallel resistance is
actually lightning-path impedance. The model used in this study is the
Heidler current model, where four characteristics of lightning current
quantities at striking point must be considered: lightning-current peak,
maximum of current-steepness, rise time, and decay time. Fig. 3.2 (a)
shows the Heidler model in ATP- EMTP. Fig. 3.2 (b) below shows the
(a) (b)
Figure 3.2 (a) Lightning Strike, Heidler Model; (b) Lightning-Strike Waveform
where
𝑛=
1
𝜏 𝑛𝜏
[−[ 1 ][ 2 ]𝑛 ]
𝜏2 𝜏1
𝑒 .................................................................. (3.9)
and
𝐼0 lightning current peak,
𝜏1 time constant determining current rise-time;
𝜏2 time constant determining current decay-time;
𝑛 current steepness factor
You can give data to objects at any time during the building
process. If you right click on the AC source icon, a window as
shown in Figure 3.5 appears. Choose the radio button Amplitude-
RMS L-G to specify the rms value. ATPDraw will then multiply with
2 internally (the RMS L-L option will also divide by √3). To use a
Variable for the AmplitudeA value the Peak L-G (standard, no
scaling) option is required. A negative value for StartA parameter
means that the source is active during steady-state initialization.
2. Lines/Cables
The Lines/Cables menu in ATPDraw has several sub-
menus for different types of line models. Available line models are:
Lumped parameter models (RLC π, RL coupled), distributed parameter
lines with constant (i.e. frequency independent) parameters, lines and
cables with constant or frequency dependent parameters (Bergeron,
PI, JMarti, Noda or Semlyen), calculated by means of the LINE
CONSTANTS, CABLE CONSTANTS or CABLE PARAMETERS
supporting routine of ATP-EMTP.
Power System Protection Lab Work – Module 3-3 8
Module 3-3: Transmission System Study in ATP-EMTP
To use the built-in line/cable module of ATPDraw the user must first select a
line/cable component under Lines/Cables | LCC item in the selection menu, as
shown in Fig. 3.6. This will display a component in the circuit window that is
connected to the circuit as any other component.
(a) (b)
Figure 3.8 (a) Standard data for all line/cable models; (b) System type options for
overhead lines.
Jmarti
Figure 3.13 Line Data dialog box of a 3-phase line (3 conductors/phase + 1 ground
wires)
E. Procedure
1. Modification exa_9.acp for Study Case Simulation
In this section, we will modification exa_9.acp to make it
suitable for study case. First thing to do is open exa_9.acp which
the step was demonstrated in previous module.
Figure 3.18 Save as File can be chosen directly from the menu
Note : If you want to change file name, do not use only number or number at the first and do not use
space for the file name.
After you save as the file, now we can modify it. Exa_9.acp
is a circuit model of electrical system in ATPDraw which drawn for
transmission system 400 kV, so we must modify it to become
transmission system 500 kV. Now, right-clicking on the source
component will bring up a special input dialog box called the
Component: AC3PH|Attributes dialog as shown in Fig. 3.20.
Figure 3.20 Component Source dialog box of the three-phase sinusoidal source
After pop-up dialog is opened, change value Amplitude from
-330000 Volt/Amps to -500000 Volt/Amps. Click Ok.
Note : The source must declaration by minus because the influence of the power frequency voltage
on the back-flashover probability can't be neglected either at this voltage level. So, it was
considered by a Thevenin equivalent 3-phase source connected to the remote end of
Line2.
Note : You must change the #Ph first before you add Node. If you don’t do that, it will show up
an error code.
Figure 3.23 Line Data and View Model dialog box of overhead transmission
lines
If the result is the same as shown in Fig. 3.23, close the View
Model dialog box by left-clicking on the icon close (X). The next
step is generating this design placement conductor overhead
transmission lines 500 kV by left-clicking in box Run ATP. After
program has run completely, hit any key to close that pop up dialog. If
program show another pop up dialog e.g. Information pop up
dialog box, click OK.
Note : in Lines box, length was defined by m. But only in this example of LINEZT_1
(Exa_9.acp) the length was defined as km in lines box, as shown in Figure 3.34. So, the
parameter for this example must change from m to km.
Figure 3.30 LINEZT_1 for structure upper tower has changed value
Figure 3.31 LINEZT_1 for structure middle tower has changed value
Figure 3.32 LINEZT_1 for structure lower tower has changed value
Figure 3.35 Modified Node dialog box for structure tower of Exa_9.acp
Figure 3.36 Structure tower of Exa_9.acp after modified Node dialog box
Figure 3.37 Structure tower after place all RLC and Resistance component in free
space
Fill the blank space with the parameter as written in Table 3.8.
Please read and fill it carefully because if you type it wrong then the
program would not running.
Figure 3.44 ATP program will perform the simulation directly from the menu
See Fig. 3.48, the green line is the voltage stress appearing at
the transformer terminal, the red line shows the incoming surge
measured at the voltage transformer of Line1 (node PT1 of the
circuit). The discharge current of the gapped arrester is drawn at the
bottom if the Fig. 3.49. As it shown, the instantaneous value of the
power frequency voltage is set opposed to the polarity of the lightning
surge in the simulation.
30 120
32 120
34 120
36 120
38 120
40 120