Beruflich Dokumente
Kultur Dokumente
ARDETEM - TA IN/02 v.04 A 04/04 - Any data in this documentation may be modified without prior notice.
69510 - Soucieu en Jarrest
Tél. 04 72 31 31 30 - Fax 04 72 31 31 31
DIP 404
Tel. Intern. 33 4 72 31 31 30 - Fax Intern. 33 4 72 31 31 31
User handbook
Valid for instruments with version 04.xx
ARDETEM
http: //www.ardetem.com - e-mail: info@ardetem.com
Soucieu en Jarrest - FRANCE
Summary
4.7 Reading of the configuration p13
1 . PRESENTATION p2
4.8 Access code p14
4.9 Programming of a new access code p14
2 . SPACE REQUIREMENTS p3
4.10 Functions accessible in the main menu p14
3 . WIRING p4 4.10.1 - Display simulation p14
4.10.2 - Analog output simulation p15
4 . PROGRAMMING p5
4.10.3 - Menu CLEAr :
4.1 Communication with the instrument p5
4.2 Orientation through the programming p5 Deleting of recorded alarms p15
4.3 Main menu p5
5 . FUNCTIONS DIRECT FROM THE DISPLAY p15
4.4 Programming menu p6
4.4.1 - Programming of the input p6 5.1 Functions which require pressing only 1 key p15
4.4.2 - Programming of the display p7 a / Display of the minimum value p15
4.4.3 - Programming of the analog output p7 b / Display of the maximum value p15
4.4.4 - Programming of the digital output p8 c / Display switching p15
4.4.5 - Programming of the LOGIC inputs p8 d / Deleting of maximum and minimum values p15
4.4.6 - Programming of the relay outputs p8
4.4.7 - Programming of mode safety p9 5.2 Functions which require pressing several keys p16
4.4.8 - Programming of the brightness, the bargraph p9 5.2.1 - Automatic setting of the cut-offs p16
and the displays
4.4.9 - Programming exit with or without saving p10 5.2.2 - Visualisation of the measure unit p16
Latching function.
• DIP 404 Time delay and hysteresis adjustable on each setpoint.
Alarm messages
Measurement of an alternating voltage, an alternating current and of the
frequency of an alternating signal.
• 2 programmable voltage calibers : 150V and 500V Insulated digital output : N
Un = 150 VAC and 500 VAC RS 485 2 wire, protocole MODBUS-JBUS.
Overstepping 1.2 Un
• 2 programmable current calibers : 1A and 5A
In = 1.2A and 6A LOGIC input 2 insulated LOGIC inputs with programmable functions
Overstepping 1.2 In Display hold,
Automatic caliber on 0-500V, 0-5A possible Min. and max. zero reset
• Voltage overload
permanent : 750 V Bargraph : (16 led display) : B
during 10s : 1000 V Allows a quick evaluation of the measured value
• Current overload variations.
permanent : 10A Programmable scale factor
during 10s : 50A Possibility to programme 3 bargraphs (1 for each
• Frequency : 45 Hz to 65 Hz displayed parameter)
• Accuracy rating :
0.2 % voltage / current (at 25°C)
• Measure cycle
55 ms
• Display :
3 magnitudes can be programmed for a display accessible simply by
pressing 1 key.
p2
General features 2. SPACE REQUIREMENTS
• Input impedance ≥ 1 MΩ for the voltage inputs
< 0.2 VA for the current input
• Common mode rejection rate : 130 dB Case dimensions : (with terminals)
Serial mode rejection rate : 70 dB 50/60 Hz
96 x 48 x 124 mm
• Thermic drift < 200 ppm/°C
• Insulation : Input / Power supply : 2.5 kV eff. 50Hz-1min
Input / Output : 2.5 kV eff. 50Hz-1min Mounting panel
max. thickness 30
• Power supply : (specify on order) Terminals
2 Versions : High Voltage or Low Voltage
case external
High Voltage : 90...270 VAC and 88 ...350 VDC 50/60/400 Hz seal
Low Voltage : 20...53 VAC and 20...75 VDC 50/60/400 Hz tightenings
Panel mounting
• Complies with standards EN 50081-2 on emissions and EN 50082-2;
cut out 44 x 91 mm
on immunity (in industrial environment)
EN 61000-4-2 level 3, EN 61000-4-3 level 3,
EN 61000-4-4 level 4, EN 61000-4-6 level 3.
CE marking according to Directive EMC 89-336
• Environment :
Operating temperature : -5° to 55°C
Storage temperature : -30° to 80 °C
Relative dampness : 80% annual average. Protection : Connectors plug-off connectors on
Front face : IP 65 rear face for screwed connections
Case : IP20 (2.5mm², flexible or rigid)
Terminals : IP 20
Display : ±10 000 points (14 mm)
Case : Electroluminescent red (green optional)
Self-extinguishing casing of 4 alarm leds
black UL 94 V0 ABS.
-2 000 / +10 000 points (20 mm)
(consult)
p3
3. WIRING 20 23
26
27
32
33
B 21 C 24
Wiring recommendations 22 25
D
28
E
34
29 35
The input network may carry significant disturbances, and they may disturb the complete chain. In order to avoid
POWER SUPPLY
30 36
this, the disturbance immunity can be made significantly better by respecting following rules : A - inputs 31 37
- do not connect close to each other : the input network and the DIP 404 power supply wires,
1 2 3 4 5 6 7 8 9
- do not connect close to each other : the input network and all the DIP 404 output wires,
- use for all DIP 404 outputs shielded cables connected to the ground on both extremities. 1 2 3 A Location of terminals
(view of case rear side)
AC ~ ~
DC + -
INPUTS
LOGIC INPUTS
(options)
5 6 7 8 23 TOR 1 C or 32 TOR 1 E
U 24 TOR 2 33 TOR 2
0/150 VAC 34
I 25 COM COM
0/500 VAC
2 channels 2 channels
0/1 AAC
0/5 AAC
23 + C or 23 C 20 B B 28 R1 34 R3
V
24 + 24 21 A
29 T2 35 T4
-
T : ON
mA C : Common
25
Lr
25 22 COM
30 C2 36 C4 R : OFF
-
+
SEC.tc
«
enter CT secondary value
« 005.0 or current input full scale
Pri.tP
«
Note : enter VT primary value (decimal point + unit)
⇒ Press key M to revert to menu SAvE « 8.888 or full display scale for the voltage input
⇒ In mode programming, the instrument will automatically revert to SEC.tP
«
enter VT secondary value
measure with the former configuration if no key is pressed during 1min. 500.0 or voltage input full scale
Note :
Press M to revert to
menu
diSPL.
Upwards move /
M Menu exit /access
increase
Downwards move /
decrease Validation / Vertical move
p6
Option analog output
4.4.2 Programming of the display
«
diSPL. 4.4.3 Programming of the analog output
Out.MA Out.MA
dISPL. « or
diSP.2
«
choice of display parameter n°2 PArAM
«
choice of the parameter associated
with the analog output
Out.U
«
«
choice of display parameter n°3
diSP.3 d.out
analog output down scale
«
(4) 00.00 < x < 22.00 (mA)
«
current cut off (4) -88.88 00.00 < x < 11.00 (V)
Cut.I enter current cut-off from 1.0% to 15.0% in manual caliber
003.0 from 0.2% to 15.0% of caliber 5A «
analog output full scale
in auto caliber
F.out
«
«
voltage cut off
Cut.U (4) -88.88
003.0 enter voltage cut-off from 1.0% to 20.0% in manual caliber
from 0.3% to 20.0% of caliber 500V
«
« in auto caliber PAr.dS «
entering of the parameter value corresponding to the
FiLt. « « « -88.88 output down scale (decimal point + unit)
choice of the filtering
OFF 1 2 «
no filtering
PAr.FS entering of the parameter value corresponding to the
«
Out.U or rELAY or
Out.MA or JbuS or tor or SECU
according to options according to options
or tor or rELAY or
JbuS SECU
Choice of the display parameters see also the output features p11
U, I, FrE. Choice of the parameter dedicated to the analog output : U, I, FrE.
U : voltage U : voltage
I : current I : current
FrE. : network frequency FrE. : network frequency
Note : Note :
Press M to go on to next menu Move through menus / choice
Press M to go on to next menu Move through menus / choice
JBuS
«
SLAvE rEL.1 «
rELAY
active
«
must be included between 1 and de-activated
Acti.1
«
-8888 « «
255
« idem rEL.2 On OFF
transmission speed rEL.1
«
bAUd « « « « «
« PArA.1 choice of the parameter dedicated to the output
19200 9600 4800 2400 1200 idem
rEL.1 rEL.3
«
(5) mode setpoint mode window
« ModE.1
delay before any response pattern
dELAY
«
« « idem
On : delay 75ms On OFF OFF : delay 20ms rEL.1 rEL.4 «
access to SP1 access to SP1.1
if mode setpoint programmed (5) choice
tor or or SECU See also the features of the SP 1 of the relay
rELAY 02.00 (dec. point + unit) operating
digital data link p11
« mode : mode
if mode window programmed setpoint or
4.4.5 Programming of the LOGIC inputs Option LOGIC inputs SP1.1 «
window
02.00 (dec. point + unit) (see p14)
tor
tor
« «
SPI.2 must be ≥ SPI.I
tor 1 SP1.2
« « «
Pr.diS
Pr.diS
«
setting of the displays brightness
br.diG on 4 levels
1111
«
bargraph and leds brightness
br.bAr
1111 on 4 levels
«
state of the last digit (right hand side)
L.dIG « «
not enforced to 0 On OFF enforced to 0
YES no
«
SECU «
option bargraph
« state of relay 1 in case option 2 or 4 relays d.bAr1 «
value of displayed parameter 1 corresponding to
rEL.1
of error self-diagnosis 0200 0% of the bargraph (decimal point + unit)
« « « OFF : self-diagnosis
inactive on the relay
«
OFF LO HI In case of self- F.bAr1 «
diagnosis error value of displayed parameter 1 corresponding to
LO : relay de-activated 0600 100% of the bargraph (decimal point + unit)
« « state of the relay in case HI : relay active «
of error self-diagnosis
rEL.2 or rEL.4 « « « d.bAr2 «
value of displayed parameter 2 corresponding to
OFF LO HI 0200 0% of the bargraph (decimal point + unit)
«
« «
option analog output
F.bAr2 «
value of displayed parameter 2 corresponding to
out.MA or out.U « «
0600 100% of the bargraph (decimal point + unit)
«
YES no d.bAr3 «
if a return value has been entered value of displayed parameter 3 corresponding to
« 0200 0% of the bargraph (decimal point + unit)
value of the output in case of self-diagnosis error
rEPLi « «
00.00<rEPLI<22.00 (mA)
-88.88 00.00<rEPLI<11.00 (V)
F.bAr3 «
value of displayed parameter 3 corresponding to
0600 100% of the bargraph (decimal point + unit)
Pr.diS
SAvE
See also the safety features p12 p9
See also the display features p13
4.4.9 Programming exit with or without 4.5.4 Choice of the CT ratio or the current scale factor
saving Example : say an installation with a 5000 kA / 5 A CT, or a display of
5000 for 5A
SAvE
YES no SAvE Pri.tc 5000. and 10 3
revert to measure exit with con- exit without
display figuration sav- configuration
ing saving SEc.tc 005.0
Note : Exit of programming mode saving configuration (SAVE, YES) will automati- 4.5.5 Choice of the VT ratio or the voltage scale factor
cally reset to zero the tare, the min. and max. as well as the alarm recordings. Example : say an installation with a 400 kV / 110 V VT
Pri.tP 400.0 and 10 3 display 1 cipher after the decimal point
4.5 Input features and programming limits => 400.0 for 110V
SEc.tP 110.0
4.5.1 Manual or automatic caliber CAL Note concerning the entering of the Pri.tc and Pri.tP :
Auto automatic caliber The instrument will always try to display with a maximum resolution.
MAnu manual caliber eg. : for Pri.tP = 400.0, the display will be 400.0
for Pri.tP = 0400, the instrument will save the value Pri.tP = 400.0
and in measure the display will be the same 400.0
4.5.2 Choice of the current caliber CALI
likewise for Pri.tc = 0010, the instrument will save Pri.tc = 10.00 and
1A or 5A only in manual in measure the display will be
Current input features 10.00
p11
Mode alarm
• Alarm time delay tiME.x
Choice of the operating mode : ModE.x The relay time delay is adjustable from 000.0 to 025.0s. in 0.1s increases.
It is active both on switching and switching back.
• Mode setpoint
• Time delay position t.Act.X
ON ON Legend :
ON coil supplied SIMPL Time delay on switching on alarm
OFF setpoint or setpoint OFF OFF coil not supplied doubL Time delay on switching on alarm and off alarm
• Latching function MEM.x
Allows recording of the alarm after a setpoint has been passed. When
• Mode window the measure reverts below the alarm setpoint, the relay remains ON and
the led blinks to warn the user that a setpoint has been passed (to reset
ON ON ON the recording of alarms to zero see menu CLEAr p 15).
Note : An exit from mode programming with configuration saving will
OFF set- OFF or set-
OFF
set- reset the alarm recordings to zero.
point point point
• Display of alarm messages MESSx
SPX.1 SPX.2 SPX.1 SPX.2
A programmed alarm message can be made to appear alternating with
Choice of the state of the relay associated led LEdx the measure. The message will appear only during the alarm, while the
The led indicates the alarm state. associated led is lit.
On led lit when relay active (coil supplied) • Setting of the setpoints : There are 2 ways to adjust setpoints.
OFF Led still when relay active (coil supplied) - either in mode programming entering the correct access code (see p16)
- or by simultaneous pressing on M and if the access to a quick
Setting of the hysteresis in the unit of the chosen parameter entering has been authorized on the code programming
HYSt.x The hysteresis is active on switching from led lit to led
still; i.e. on switching out of alarm, as the led represents the alarm state.
4.6.4 Safeties : diAG
• Mode setpoint
led lit
• Self-diagnosis :
The self-diagnosis serves to warn the user in case of error.
led still The self-diagnosis error information can be reported :
SP.X SP.X · On the display : An error message appears alternating with the
- Hystx measure ; an error code is registered, and can be read in menu About
(see p14)
Coding :
• Mode window led lit 1 : Current caliber overstepping
2 : Voltage caliber overstepping
4 : Frequency calculation error
8 : Programming error
16 : Input calibration error
led still 32 : Output calibration error
led still
SPX.1 SPX.1 SPX.2 SPX.2 If the instrument detects for instance a current and a voltage caliber p12
-Hyst.x +Hyst.x overstepping the error code value will be 3 (1+2).
· On the relays : nuLL
• Deleting of unsignificant zeros
No influence of a self-diagnosis error on the relay
OFF nuLL = YES Suppresses the unsignificant zeros on the left hand
Relay de-activated (coil not supplied) in case of self-diagnosis side.
LO error Eg. : Display value 0015
HI Relay active (coil supplied) in case of self-diagnosis error nuLL = no Display 0015
Note : The led is either still or lit according to its programming in the Display 15
menu rELAY.
= YES
Eg. : Display value 00.15
· On the analog output
nuLL = no Display 00.15
If a return value has been entered Display 0.15
Value included between : 0 and 22 mA (current output) = YES
or 0 and 11 V (voltage output) • Bargraph display factor (option bargraph only)
4.6.5 Display features : d.bArX Value of the display parameter X corresponding to 0% of the
bargraph
diSP.1 Choice of the parameter dedicated to the display n°1
Value of the display parameter X corresponding to 100% of the
Choice of the parameter dedicated to the display n°2 F.bArXbargraph
diSP.2
Choice of the parameter dedicated to the display n°3 In case of overstepping, the bargraph starts to blink.
diSP.3
Cut.I Cut-off on the current programmable from 1.0% to 15.0% in 4.7 Reading of the configuration rEAd
manual caliber, from 0.2% to 15.0% of caliber 5A in auto caliber
Cut-off on the voltage programmable from 1.0% to 20.0% in rEAd
Cut.U manual caliber, from 0.3% to 20.0% of caliber Validation /
Vertical move
500V in auto caliber
FiLt. Choice of the digital filtering : OFF , 1 , 2 ; increase the value InPut Reading of the input parameters
in case of unsteady measures. Reading of the measure display parameters
diSPL
• Response time : Reading of the analog output parameters
Out.MA or Out.U (option analog output)
Typical response time : 110ms.
Reading of the communication parameters
Note : For the analog output response time, add 40 ms to the above JbuS (option digital output)
value. Reading of the LOGIC input parameters
For the relays : add the time delay programmed on the alarms. tor (option TOR)
• Setting of the digits brightness br.diG Reading of the alarm parameters
rELAY (option 2 or 4 relays)
1111 Lowest brightness 4444 Strongest brightness
• Setting of the brightness of the bargraph and leds br.bAr Reading of the safety parameters in case of
SECU self-diagnosis error
1111 Lowest brightness 4444 Strongest brightness
The brightness level is visualised directly on leds 5 to 8 and on the Pr.diS Reading of the display programming para-
bargraph. meters (leds, bargraph leds..)
Caution : during the setting, the 4 leds and the bargraph no longer repre- Reading of the instrument own parameters
sent the measure, including in mode reading. About
In each reading submenu, press and to move, and
to visualise parameters.
• Inhibition of the last digit (low weight) L.dIG
In the programming mode, the menu L.dIG allows deleting the display of If no key is pressed during 20s, the instrument will automatically
the last digit, enforcing it to 0 if OFF is validated. revert to measure display. p13
Sub-menu
About 4.9 Programming of a new access code
Validation /
Vertical move
P.CodE
type of instrument if code not valid
d404 (old)
Enter previ-
n0 instrument number
ous code display during 2s.
XXXXX and revert to
12345. A0123 if code correct no measure display
X1 : - : No analog output (old)
A : Analog output programme version Enter new
ProG
code
X2 X3 : - - : No relay output 01.00
r- : Output 2 relays
code of the registering of the
r4 : Output 4 relays 0Pt10. XXXXX installed options new code
12345. Revert to measure
X4 : - : No RS output Ar4--. display
n : RS output
error code in case of
X5 - : No LOGIC input Err. error self-diagnosis Reminder : If no key is pressed during 1 min, the instrument will
t : 2 LOGIC inputs automatically revert to measure display.
0000
(.) : decimal point still : CH.SUM flash memory check sum
no bagraph
“.” : decimal point lit : FC4E
option bargraph 4.10 Functions accessible in the main menu
4.10.1 Display simulation
(accessible according to the programmed access code, and if
4.8 Access code option relays or analog output)
An access code adjustable from 0000 to 9999 serves to prevent unau-
thorized programming of the meter and of its setpoints, and to lock the SIMUL
access to some functions. choice of the
diSP.1 diSP.2 diSP.3 parameter to be
0 0 0 0 Factory code simulated
x x x x
0 to 5 Access to the current and voltage automatic cut off
6 to 9 No access SIMUL
M Press Menu to
revert to meas- if
0 to 5 Access to the display and output simulations ure display.
6 to 9 No access Entering of a new dis-
Display value
play value
0 to 5 Access to a quick entering of alarm setpoints
6 to 9 No access Note : During simulation, the instrument no longer measures, the analog
and the relay outputs react according to entered display value.
If alarm messages have been programmed, they can appear p14
during simulation.
4.10.2 Simulation of the analog output
(accessible according to programmed access
code and if option analog output)
5. FUNCTIONS DIRECT FROM DISPLAY
GEnE.
5.1 Functions which require pressing only 1 key :
GEnE.
M Press Menu to
revert to meas- if a / min. value display b/ max. value display
ure display
Enter the value Measure dis- Measure dis-
Output value
to be injected play play
Note : The instrument carries on measuring during simulation. Only the
analog output no longer reacts to the measure.
InF. SUP.
4.10.3 Menu CLEAr : Deleting of recorded alarms Alternate infor- Alternate infor-
mation display mation display
If the function recording of alarms has been programmed :
The relay state is recorded after a setpoint has been passed. 02.00 Minimum value 08.00 Maximum value
If the setpoint is passed back the other way, the relay state does not
change and the corresponding led starts to blink.
To come back to the normal state (led not blinking and relay in the cor- c / Display switching (3 possible parameters)
rect state) use menu CLEAr).
A long pressing (>3 s) on or allows passing on to next or previ-
recorded alarms are not ous parameter (a led indicates which parameter is selected).
M deleted
CLEAr d / Deleting of maximum and minimum values
5.2.2 Visualisation of the measure unit Er.xxx Self-diagnosis error (see p12 )
d.bAr1 «
display of parameter 1 corresponding to 0% of bargraph Mode alarm ModE.x
display of parameter 2 corresponding to 0% of bargraph
d.bAr2 « __1-- --1__ Mode setpoints
display of parameter 3 corresponding to 0% of bargraph
d.bAr3 « _1--1_ -1__1- Mode window
F.bAr1 « display of parameter 1 corresponding to 100% of bargraph SPx Value of the setpoint in mode setpoint
F.bAr2 « display of parameter 2 corresponding to 100% of bargraph SPx.1 Value of the 1st setpoint in mode window
F.bAr3 display of parameter 3 corresponding to 100% of bargraph Value of the 2nd setpoint in mode window
SPx.2
Analog output HYSt.x Value of the hysteresis in display points
Out.U Access to the voltage output programming sub-menu tiME.x Time delay on relay X
Out.MA Acces to the current output programming sub-menu t.Act.X Time delay position
PArAM Choice of the parameter dedicated to the analog output SIMPL Time delay on switching on alarm
Analog output down scale doubL Time delay on switching on alarm and off alarm
d.out
F.out Analog output full scale Programming of the led associated with the relay
LEdx
Value of the parameter dedicated to the output corresponding On Led lit when relay active (coil supplied)
to PAr.dS output down scale Led still when relay active (coil supplied)
Value of the parameter dedicated to the output corresponding
OFF
PAr.FS MEM.x Recording of alarm X
to output full scale
YES Recording no No recording
Digital output
MESSx Alarm message
JbuS Access to the RS output programming sub-menu
YES Message no No message
SLAvE Slave number Safeties
bAud Transmission speed Access to the safeties programming submenu
SECU
1200 Minimum speed
rEL.X State of relay X in case of sensor rupture
19200 Maximum speed
OFF No sensor rupture associated with the relay
dELAY Time delay before any answer
Relay de-activated in case of sensor rupture
On Time delay 75ms OFF Time delay 20ms LO (coil not supplied)
rELAY Access to the relay outputs programming sub-menu out.U out.MA Return value on the output (or not)
or in case of error self-diagnosis
rEL.x Access to the programming of relay x
Activation of relay output x YES Return value required no No return value
Acti.x p18
On Activation OFF De-activation rEPLi Return value
Configuration saving
9. ANNEXE : MODBUS
SAvE Configuration saving
9.1 Table of the measure Modbus addresses
YES Saving no No saving
Address Measures Format nb of words
Reading of the instrument internal features 1 voltage U integer 1
2 current I integer 1
About Access to the internal features reading submenu 3 network frequency integer 1
d404 Instrument type : DIP404,
p19
Writing of n words : Function N°16 :
Further addresses
Address Value of the analog output Format nb of words Request pattern :
50 in µA (mA output) double integer 2 Nbr of Nbr of
Slave Function 1st word Value of the words
in mV (10V output) words to bytes to CRC 16
number 16 address to be enforced
52 maximum display 1 double integer 2 be enfor. be enfor.
54 maximum display 2 double integer 2 1 byte 1 byte 2 bytes 2 bytes 1 byte n bytes 2 bytes
56 maximum display 3 double integer 2
Response pattern :
58 minimum display 1 double integer 2
60 minimum display 2 double integer 2 Nbr of
Slave Function 1st word
62 minimum display 3 double integer 2 words to CRC 16
number 16 address
be enfor.
64 state of relay 1 integer 1
65 state of relay 2 integer 1 1 byte 1 byte 1 byte 2 bytes 2 bytes
66 state of relay 3 integer 1
67 state of relay 4 integer 1 9.4 Reading in double integer format :
Example : Reading of the maximum on display 1 (voltage maximum)
• State of the relays :
Request :
bit 15 bit 7 bit 6 bit 0
254 03 0 52 0 2 CRC 16
1 : Led lit Slave Reading of Address Number of words
1 : Led blinking : mode number n words
recording and measure
not in alarm • Response with a positive measure :
measure
1 : Relay ON
Alarm 254 3 4 19 136 0 0 CRC 16
recorded
byte 1 byte 2 byte 3 byte 4 2 bytes
p20
9.5 CRC16 calculation algorythm :
FFFF → CRC
n=0
no carry yes
n= n+1
no n>7 yes
next byte
no end of pattern
yes
END
p21