Sie sind auf Seite 1von 2

The importance of loop

impedance testing
Application Note

Measurement of earth loop impedance and determining the


Prospective Fault Current (PFC) are critical for safety and form
integral parts of the International Electrotechnical Commission
(IEC) guidelines. Standard IEC 60364 (and its various national
equivalent standards) specifies the requirements for fixed
electrical installations in buildings, including verification of
protection by automatic supply disconnection. The new Fluke
1650 Series Multifunction Installation Testers have a loop
impedance test function in addition to being able to measure
prospective short circuit current (PSC) and fault current (PFC).

Why measure earth loop current would take is low enough to


impedance? allow sufficient current to flow in the
event of a fault and that any installed
Earth loop impedance testing is essen-
protective device will operate within a
tial since if a live conductor is
safe time limit.
accidentally connected to an earth
conductor in a faulty appliance or
As measurement of circuit loop impe-
circuit, the resulting short-circuit
dance is made with the supply
current to earth can easily be high
normally on, precautions must be taken
enough to cause electric shock or
to avoid the possibility of electric shock
generate enough heat to start a fire.
and danger to personnel working in
Normally, the fuse will blow or another
the vicinity of the circuit under test.
circuit protection device will trip, but a
situation may arise where the actual
Verifying protection by
short-circuit current in a faulty installa-
automatic supply
tion is of insufficient level and the
disconnection
protection device would thus take too
long to activate. The delay can be In IEC 60364, fault loop testing falls
disastrous for life and property. It is under the category of ‘Verifying protec-
therefore necessary to know if the tion by automatic supply disconnection’.
impedance of the path that any fault This covers verification of the
effectiveness of protective measures,
and the test methods applied depend
on the type of system. TT systems, for
example, require measurement of the
earth electrode resistance for exposed-
conductive-parts of the installation,
whereas IT systems use calculation or
measurement of the first fault current.
This application note looks specifically
at TN systems, which require measure-
ment of the fault loop impedance and
verification of the characteristics of the
associated protective device (i.e. visual
inspection of the nominal current
setting for circuit-breakers,
the current ratings and blow charac- resistance. They also have a dedicated It can also provide a direct readout of
teristics for fuses and the correct function for carrying out basic loop the Prospective Short Circuit Current
functioning of RCDs). impedance measurements between (PSC).
line and protective earth, and can
The earth loop impedance of each directly display the results in ohms. Interpreting results and
individual circuit from the point of use Measurements should be taken at all taking remedial action
back to the incoming supply connec- outlets of the installation, including
Remember that it is not sufficient just
tion point should be measured. light fittings and all distribution
to carry out tests and record the
(sub-) panels.
results. Knowledge of local regulations
A separate measurement of the exter-
– and of how to interpret results – is
nal loop impedance of the installation The 1650 Series includes several
also required to ensure the installa-
can also be made at the incoming useful features to help with earth loop
tion’s safety characteristics are within
supply point or main distribution panel testing, including an ‘Auto-null’ to
the prescribed limits. An excessive
and this value will form part of the remove test-lead resistance from
earth loop impedance value should, for
overall loop impedance from any part measurement and Automatic overheat
example, prompt an investigation into
of the final circuit installation. protection. Loop measurements are
its cause. Remedial action should then
Knowing the earth loop impedance, it displayed with 0.01-ohm resolution.
be carried out, and the installation
is possible to calculate the value of the The instruments can also measure the
retested.
prospective fault current (PFC) at any line impedance, that is, the source
point in an installation and to ensure impedance between line and neutral
Caution!
that all installed protective devices are or the line-to-line impedance in three-
of an adequate rating to clear the phase systems, although these tests do This Application Note is not intended
potential fault current level. not form part of the loop impedance to replace or supercede the recognized
tests specified in IEC 60364. standards in IEC 60364 (or its national
Measuring earth loop equivalents), but to provide a summary
impedance Conventional techniques for measuring of the fault loop impedance testing
loop impedance can often trip RCDs, considerations. Always consult the
Since the AC impedance of a circuit
preventing further measurement. Often appropriate standards publication.
may be different from its DC resistance
the only way around this is to “bridge”
– particularly for circuits rated at over
the RCD or replace the RCD with an
100 A – the fault loop impedance is
equivalent rated MCB for the duration
measured using the same frequency as
of the test – both of which are poten-
the nominal mains frequency (50 Hz).
tially dangerous and time consuming
The earth loop impedance test meas-
practices. To overcome this in the 1650
ures the resistance of the path that a
series, Fluke has applied innovative
fault current would take between line
and patented technology to ensure Fluke. Keeping your world
and protective earth. This must be low up and running.
that both electromechanical and
enough to allow sufficient current to
electronic type RCDs do not trip during
flow to trip a circuit protection device
earth loop impedance measurements. Fluke Corporation
such as a fuse or miniature circuit PO Box 9090, Everett, WA USA 98206
This technology gives more consistent
breaker.
results and also allows a very short Fluke Europe B.V.
PO Box 1186, 5602 BD
test period, considerably less than the Eindhoven, The Netherlands
The Fluke 1650 Series testers can be
time required by most conventional
used to carry out the test at a distribu- For more information call:
installation testers. In the U.S.A. (800) 443-5853 or
tion board using the three separate Fax (425) 446-5116
test leads supplied, and at appliance In Europe/M-East/Africa (31 40) 2 675 200 or
Calculating Prospective Fax (31 40) 2 675 222
outlets using a dedicated lead fitted
Fault Current In Canada (800)-36-FLUKE or
with a mains plug. A plug of the Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
appropriate national standard is also In addition to measuring the earth loop Fax +1 (425) 446-5116
supplied with the instrument. impedance, the 1650 Series automati- Web access: http://www.fluke.com
cally calculates the Prospective Fault
Dedicated functions on the Current (PFC) and displays it in the
1650 Series lower part of the dual display. ©2003 Fluke Corporation. All rights reserved.
Printed in the Netherlands.
Determining the PFC is important to 9/2003 Pub-ID 10642-eng
The Fluke 1650 Multifunction
ensure that the capability of fuses and
Installation Testers have a dedicated
over-current circuit breakers are not
function to measure the earth resist-
exceeded.
ance component of the total loop

Das könnte Ihnen auch gefallen