Sie sind auf Seite 1von 24

CHAPTER 4

VENTILATION

User note:
About this chapter: Chapter 4 intends to provide an indoor atmosphere that protects the health and well-being of building occupants. Both
mechanical and natural ventilation are addressed. Mechanical ventilation provides what is considered to be acceptable indoor air quality.
Mechanical ventilation minimizes adverse health effects and provides an atmosphere that generally is not objectionable to occupants.

SECTION 401 1612 of the International Building Code for utilities


GENERAL and attendant equipment.
401.1 Scope. This chapter shall govern the ventilation of 401.5 Intake opening protection. Air intake openings that
spaces within a building intended to be occupied. Mechanical terminate outdoors shall be protected with corrosion-resistant
exhaust systems, including exhaust systems serving clothes screens, louvers or grilles. Openings in louvers, grilles and
dryers and cooking appliances; hazardous exhaust systems; screens shall be sized in accordance with Table 401.5, and
dust, stock and refuse conveyor systems; subslab soil exhaust shall be protected against local weather conditions. Louvers
systems; smoke control systems; energy recovery ventilation that protect air intake openings in structures located in hurri-
systems and other systems specified in Section 502 shall cane-prone regions, as defined in the International Building
comply with Chapter 5. Code, shall comply with AMCA 550. Outdoor air intake
401.2 Ventilation required. Every occupied space shall be openings located in exterior walls shall meet the provisions
ventilated by natural means in accordance with Section 402 for exterior wall opening protectives in accordance with the
or by mechanical means in accordance with Section 403. International Building Code.
Where the air infiltration rate in a dwelling unit is less than 5 TABLE 401.5
air changes per hour when tested with a blower door at a pres- OPENING SIZES IN LOUVERS, GRILLES
sure of 0.2-inch water column (50 Pa) in accordance with AND SCREENS PROTECTING AIR INTAKE OPENINGS
Section R402.4.1.2 of the International Energy Conservation MINIMUM AND MAXIMUM
OUTDOOR OPENING TYPE OPENING SIZES IN LOUVERS,
Code, the dwelling unit shall be ventilated by mechanical GRILLES AND SCREENSa
means in accordance with Section 403. Ambulatory care
Intake openings in
facilities and Group I-2 occupancies shall be ventilated by Not < 1/4 inch and not > 1/2 inch
residential occupancies
mechanical means in accordance with Section 407.
Intake openings in other
401.3 When required. Ventilation shall be provided during > 1/4 inch and not > 1 inch
than residential occupancies
the periods that the room or space is occupied.
For SI: 1 inch = 25.4 mm.
401.4 Intake opening location. Air intake openings shall a. For rectangular openings, the table requirements apply to the shortest side.
comply with all of the following: For round openings, the table requirements apply to the diameter. For
square openings, the table requirements apply to any side.
1. Intake openings shall be located not less than 10 feet
(3048 mm) from lot lines or buildings on the same lot. 401.6 Contaminant sources. Stationary local sources pro-
2. Mechanical and gravity outdoor air intake openings ducing airborne particulates, heat, odors, fumes, spray,
shall be located not less than 10 feet (3048 mm) hori- vapors, smoke or gases in such quantities as to be irritating or
zontally from any hazardous or noxious contaminant injurious to health shall be provided with an exhaust system
source, such as vents, streets, alleys, parking lots and in accordance with Chapter 5 or a means of collection and
loading docks, except as specified in Item 3 or Section removal of the contaminants. Such exhaust shall discharge
501.3.1. Outdoor air intake openings shall be permitted directly to an approved location at the exterior of the build-
to be located less than 10 feet (3048 mm) horizontally ing.
from streets, alleys, parking lots and loading docks pro-
vided that the openings are located not less than 25 feet
(7620 mm) vertically above such locations. Where SECTION 402
openings front on a street or public way, the distance NATURAL VENTILATION
shall be measured from the closest edge of the street or [BG] 402.1 Natural ventilation. Natural ventilation of an
public way. occupied space shall be through windows, doors, louvers or
3. Intake openings shall be located not less than 3 feet other openings to the outdoors. The operating mechanism for
(914 mm) below contaminant sources where such such openings shall be provided with ready access so that the
sources are located within 10 feet (3048 mm) of the openings are readily controllable by the building occupants.
opening. [BG] 402.2 Ventilation area required. The minimum open-
4. Intake openings on structures in flood hazard areas able area to the outdoors shall be 4 percent of the floor area
shall be at or above the elevation required by Section being ventilated.

2018 INTERNATIONAL MECHANICAL CODE 31


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
VENTILATION

[BG] 402.3 Adjoining spaces. Where rooms and spaces 10 percent of the resulting supply airstream consists
without openings to the outdoors are ventilated through an of air recirculated from these spaces.
adjoining room, the opening to the adjoining rooms shall be 3. Where mechanical exhaust is required by Note b in
unobstructed and shall have an area not less than 8 percent of Table 403.3.1.1, recirculation of air from such
the floor area of the interior room or space, but not less than spaces shall be prohibited. Recirculation of air that
25 square feet (2.3 m2). The minimum openable area to the is contained completely within such spaces shall not
outdoors shall be based on the total floor area being venti- be prohibited. Where recirculation of air is prohib-
lated. ited, all air supplied to such spaces shall be
Exception: Exterior openings required for ventilation exhausted, including any air in excess of that
shall be permitted to open into a thermally isolated sun- required by Table 403.3.1.1.
room addition or patio cover, provided that the openable 4. Where mechanical exhaust is required by Note g in
area between the sunroom addition or patio cover and the Table 403.3.1.1, mechanical exhaust is required and
interior room has an area of not less than 8 percent of the recirculation from such spaces is prohibited where
floor area of the interior room or space, but not less than more than 10 percent of the resulting supply air-
20 square feet (1.86 m2). The minimum openable area to stream consists of air recirculated from these spaces.
the outdoors shall be based on the total floor area being Recirculation of air that is contained completely
ventilated. within such spaces shall not be prohibited.
[BG] 402.4 Openings below grade. Where openings below
403.2.2 Transfer air. Except where recirculation from
grade provide required natural ventilation, the outdoor hori- such spaces is prohibited by Table 403.3.1.1, air trans-
zontal clear space measured perpendicular to the opening ferred from occupiable spaces is not prohibited from serv-
shall be one and one-half times the depth of the opening. The ing as makeup air for required exhaust systems in such
depth of the opening shall be measured from the average spaces as kitchens, baths, toilet rooms, elevators and
adjoining ground level to the bottom of the opening. smoking lounges. The amount of transfer air and exhaust
air shall be sufficient to provide the flow rates as specified
in Section 403.3.1.1. The required outdoor airflow rates
SECTION 403 specified in Table 403.3.1.1 shall be introduced directly
MECHANICAL VENTILATION into such spaces or into the occupied spaces from which
403.1 Ventilation system. Mechanical ventilation shall be air is transferred or a combination of both.
provided by a method of supply air and return or exhaust air
403.3 Outdoor air and local exhaust airflow rates. Group
except that mechanical ventilation air requirements for Group
R-2, R-3 and R-4 occupancies three stories and less in height
R-2, R-3 and R-4 occupancies three stories and less in height
above grade plane shall be provided with outdoor air and
above grade plane shall be provided by an exhaust system,
local exhaust in accordance with Section 403.3.2. Other
supply system or combination thereof. The amount of supply
buildings intended to be occupied shall be provided with out-
air shall be approximately equal to the amount of return and
door air and local exhaust in accordance with Section
exhaust air. The system shall not be prohibited from produc-
403.3.1.
ing negative or positive pressure. The system to convey venti-
lation air shall be designed and installed in accordance with 403.3.1 Other buildings intended to be occupied. The
Chapter 6. design of local exhaust systems and ventilation systems
403.2 Outdoor air required. The minimum outdoor airflow for outdoor air for occupancies other than Group R-2, R-3
rate shall be determined in accordance with Section 403.3. and R-4 three stories and less above grade plane shall
comply with Sections 403.3.1.1 through 403.3.1.5.
Exception: Where the registered design professional
demonstrates that an engineered ventilation system design 403.3.1.1 Outdoor airflow rate. Ventilation systems
will prevent the maximum concentration of contaminants shall be designed to have the capacity to supply the
from exceeding that obtainable by the rate of outdoor air minimum outdoor airflow rate, determined in accor-
ventilation determined in accordance with Section 403.3, dance with this section. In each occupiable space, the
the minimum required rate of outdoor air shall be reduced ventilation system shall be designed to deliver the
in accordance with such engineered system design. required rate of outdoor airflow to the breathing zone.
403.2.1 Recirculation of air. The outdoor air required by The occupant load utilized for design of the ventilation
Section 403.3 shall not be recirculated. Air in excess of system shall be not less than the number determined
that required by Section 403.3 shall not be prohibited from from the estimated maximum occupant load rate indi-
being recirculated as a component of supply air to building cated in Table 403.3.1.1. Ventilation rates for occupan-
spaces, except that: cies not represented in Table 403.3.1.1 shall be those
for a listed occupancy classification that is most similar
1. Ventilation air shall not be recirculated from one in terms of occupant density, activities and building
dwelling to another or to dissimilar occupancies. construction; or shall be determined by an approved
2. Supply air to a swimming pool and associated deck engineering analysis. The ventilation system shall be
areas shall not be recirculated unless such air is designed to supply the required rate of ventilation air
dehumidified to maintain the relative humidity of continuously during the period the building is occupied,
the area at 60 percent or less. Air from this area shall except as otherwise stated in other provisions of the
not be recirculated to other spaces where more than code.

32 2018 INTERNATIONAL MECHANICAL CODE


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
VENTILATION

With the exception of smoking lounges, the ventila- b. “Warm air” is air warmer than space temperature.
tion rates in Table 403.3.1.1 are based on the absence c. “Ceiling” includes any point above the breathing zone.
of smoking in occupiable spaces. Where smoking is d. “Floor” includes any point below the breathing zone.
anticipated in a space other than a smoking lounge, the e. Zone air distribution effectiveness of 1.2 shall be permitted for systems
with a floor supply of cool air and ceiling return, provided that low-
ventilation system serving the space shall be designed velocity displacement ventilation achieves unidirectional flow and
to provide ventilation over and above that required by thermal stratification.
Table 403.3.1.1 in accordance with accepted engineer- f. Zone air distribution effectiveness of 1.0 shall be permitted for systems
ing practice. with a ceiling supply of warm air, provided that supply air temperature is
less than 15°F above space temperature and provided that the 150-foot-
Exception: The occupant load is not required to be per-minute supply air jet reaches to within 41/2 feet of floor level.
determined based on the estimated maximum occu-
403.3.1.1.1.3 Zone outdoor airflow. The zone
pant load rate indicated in Table 403.3.1.1 where
outdoor airflow rate (Voz), shall be determined in
approved statistical data document the accuracy of
accordance with Equation 4-2.
an alternate anticipated occupant density.
403.3.1.1.1 Zone outdoor airflow. The minimum V bz
outdoor airflow required to be supplied to each zone V oz = ------- (Equation 4-2)
Ez
shall be determined as a function of occupancy clas-
sification and space air distribution effectiveness in 403.3.1.1.2 System outdoor airflow. The outdoor
accordance with Sections 403.3.1.1.1.1 through air required to be supplied by each ventilation sys-
403.3.1.1.1.3. tem shall be determined in accordance with Sections
403.3.1.1.1.1 Breathing zone outdoor airflow. 403.3.1.1.2.1 through 403.3.1.1.2.3.4 as a function
The outdoor airflow rate required in the breath- of system type and zone outdoor airflow rates.
ing zone (Vbz) of the occupiable space or spaces 403.3.1.1.2.1 Single zone systems. Where one
in a zone shall be determined in accordance with air handler supplies a mixture of outdoor air and
Equation 4-1. recirculated return air to only one zone, the sys-
tem outdoor air intake flow rate (Vot) shall be
V bz = R p P z + R a A z (Equation 4-1) determined in accordance with Equation 4-3.

where: V ot = V oz (Equation 4-3)


Az = Zone floor area: the net occupiable floor
area of the space or spaces in the zone. 403.3.1.1.2.2 100-percent outdoor air systems.
Where one air handler supplies only outdoor air
Pz = Zone population: the number of people in to one or more zones, the system outdoor air
the space or spaces in the zone. intake flow rate (Vot) shall be determined using
Rp = People outdoor air rate: the outdoor Equation 4-4.
airflow rate required per person from
Table 403.3.1.1. V ot = Σ all zones V oz (Equation 4-4)
Ra = Area outdoor air rate: the outdoor airflow
rate required per unit area from Table 403.3.1.1.2.3 Multiple zone recirculating sys-
403.3.1.1. tems. Where one air handler supplies a mixture
403.3.1.1.1.2 Zone air distribution effective- of outdoor air and recirculated return air to more
ness. The zone air distribution effectiveness (Ez) than one zone, the system outdoor air intake flow
shall be determined using Table 403.3.1.1.1.2. rate (Vot) shall be determined in accordance with
Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4.
TABLE 403.3.1.1.1.2
ZONE AIR DISTRIBUTION EFFECTIVENESSa,b,c,d 403.3.1.1.2.3.1 Primary outdoor air frac-
AIR DISTRIBUTION CONFIGURATION Ez tion. The primary outdoor air fraction (Zp)
shall be determined for each zone in accor-
Ceiling or floor supply of cool air 1.0e
dance with Equation 4-5.
Ceiling or floor supply of warm air and floor return 1.0
V oz
Ceiling supply of warm air and ceiling return 0.8f Z p = ------- (Equation 4-5)
V pz
Floor supply of warm air and ceiling return 0.7
where:
Makeup air drawn in on the opposite side of the room
from the exhaust or return
0.8 Vpz = Primary airflow: The airflow rate
supplied to the zone from the air-
Makeup air drawn in near to the exhaust or return loca- handling unit at which the outdoor air
0.5
tion intake is located. It includes outdoor
For SI: 1 foot = 304.8 mm, 1 foot per minute = 0.00506 m/s, intake air and recirculated air from that
°C = [(°F) – 32]/1.8. air-handling unit but does not include
a. “Cool air” is air cooler than space temperature. air transferred or air recirculated to the

2018 INTERNATIONAL MECHANICAL CODE 33


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
VENTILATION

zone by other means. For design 403.3.1.2 Exhaust ventilation. Exhaust airflow rate
purposes, Vpz shall be the zone design shall be provided in accordance with the requirements
primary airflow rate, except for zones of Table 403.3.1.1. Outdoor air introduced into a space
with variable air volume supply and Vpz by an exhaust system shall be considered as contribut-
shall be the lowest expected primary ing to the outdoor airflow required by Table 403.3.1.1.
airflow rate to the zone when it is fully 403.3.1.3 System operation. The minimum flow rate
occupied. of outdoor air that the ventilation system must be capa-
403.3.1.1.2.3.2 System ventilation efficiency. ble of supplying during its operation shall be permitted
The system ventilation efficiency (Ev) shall be to be based on the rate per person indicated in Table
determined using Table 403.3.1.1.2.3.2 or 403.3.1.1 and the actual number of occupants present.
Appendix A of ASHRAE 62.1.
403.3.1.4 Variable air volume system control. Vari-
TABLE 403.3.1.1.2.3.2 able air volume air distribution systems, other than
SYSTEM VENTILATION EFFICIENCYa,b
those designed to supply only 100-percent outdoor air,
Max (Zp) Ev
shall be provided with controls to regulate the flow of
0.15 1 outdoor air. Such control system shall be designed to
0.25 0.9 maintain the flow rate of outdoor air at a rate of not less
0.35 0.8 than that required by Section 403.3 over the entire
range of supply air operating rates.
0.45 0.7
403.3.1.5 Balancing. The ventilation air distribution
0.55 0.6
system shall be provided with means to adjust the sys-
0.65 0.5 tem to achieve not less than the minimum ventilation
0.75 0.4 airflow rate as required by Sections 403.3 and
> 0.75 0.3 403.3.1.2. Ventilation systems shall be balanced by an
approved method. Such balancing shall verify that the
a. Max (Zp) is the largest value of Zp calculated using Equation 4-5 among all
the zones served by the system. ventilation system is capable of supplying and exhaust-
b. Interpolating between table values shall be permitted. ing the airflow rates required by Sections 403.3 and
403.3.1.1.2.3.3 Uncorrected outdoor air 403.3.1.2.
intake. The uncorrected outdoor air intake 403.3.2 Group R-2, R-3 and R-4 occupancies, three sto-
flow rate (Vou) shall be determined in accor- ries and less. The design of local exhaust systems and
dance with Equation 4-6. ventilation systems for outdoor air in Group R-2, R-3 and
V ou = D all zones R p P z + all zones R a A z R-4 occupancies three stories and less in height above
grade plane shall comply with Sections 403.3.2.1 through
(Equation 4-6) 403.3.2.5.
403.3.2.1 Outdoor air for dwelling units. An outdoor
where: air ventilation system consisting of a mechanical
exhaust system, supply system or combination thereof
D = Occupant diversity: the ratio of the shall be installed for each dwelling unit. Local exhaust
system population to the sum of the or supply systems, including outdoor air ducts con-
zone populations, determined in nected to the return side of an air handler, are permitted
accordance with Equation 4-7. to serve as such a system. The outdoor air ventilation
Ps system shall be designed to provide the required rate of
D = -----------------------
- (Equation 4-7) outdoor air continuously during the period that the
all zones P z building is occupied. The minimum continuous outdoor
where: airflow rate shall be determined in accordance with
Ps = System population: The total number of Equation 4-9.
occupants in the area served by the
system. For design purposes, Ps shall be Q OA = 0.01A floor + 7.5 N br + 1 (Equation 4-9)
the maximum number of occupants
expected to be concurrently in all zones where:
served by the system.
QOA = outdoor airflow rate, cfm
403.3.1.1.2.3.4 Outdoor air intake flow rate.
The outdoor air intake flow rate (Vot) shall be Afloor = floor area, ft2
determined in accordance with Equation 4-8. Nbr = number of bedrooms; not to be less than one
V ou Exception: The outdoor air ventilation system is not
V ot = -------
- (Equation 4-8) required to operate continuously where the system
Ev
has controls that enable operation for not less than 1
hour of each 4-hour period. The average outdoor air-

34 2018 INTERNATIONAL MECHANICAL CODE


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
VENTILATION

flow rate over the 4-hour period shall be not less tioning systems that supply required ventilation air shall be
than that prescribed by Equation 4-9. provided with controls designed to automatically maintain
403.3.2.2 Outdoor air for other spaces. Corridors and the required outdoor air supply rate during occupancy.
other common areas within the conditioned space shall
be provided with outdoor air at a rate of not less than
0.06 cfm per square foot of floor area. SECTION 406
VENTILATION OF UNINHABITED SPACES
403.3.2.3 Local exhaust. Local exhaust systems shall
be provided in kitchens, bathrooms and toilet rooms 406.1 General. Uninhabited spaces, such as crawl spaces and
and shall have the capacity to exhaust the minimum air- attics, shall be provided with natural ventilation openings as
flow rate determined in accordance with Table required by the International Building Code or shall be pro-
403.3.2.3. vided with a mechanical exhaust and supply air system. The
mechanical exhaust rate shall be not less than 0.02 cfm per
TABLE 403.3.2.3
MINIMUM REQUIRED LOCAL EXHAUST RATES
square foot (0.00001 m3/s • m2) of horizontal area and shall be
FOR GROUP R-2, R-3, AND R-4 OCCUPANCIES automatically controlled to operate when the relative humid-
AREA TO BE EXHAUSTED EXHAUST RATE CAPACITY ity in the space served exceeds 60 percent.
100 cfm intermittent or
Kitchens
25 cfm continuous
SECTION 407
50 cfm intermittent or AMBULATORY CARE FACILITIES AND
Bathrooms and toilet rooms
20 cfm continuous GROUP I-2 OCCUPANCIES
For SI: 1 cubic foot per minute = 0.0004719 m3/s. 407.1 General. Mechanical ventilation for ambulatory care
403.3.2.4 System controls. Where provided within a facilities and Group I-2 occupancies shall be designed and
dwelling unit, controls for outdoor air ventilation sys- installed in accordance with this code and ASHRAE 170.
tems shall include text or a symbol indicating the sys-
tem’s function.
403.3.2.5 Ventilating equipment. Exhaust equipment
serving single dwelling units shall be listed and labeled
to provide the minimum required air flow in accor-
dance with ANSI/AMCA 210-ANSI/ASHRAE 51.

SECTION 404
ENCLOSED PARKING GARAGES
404.1 Enclosed parking garages. Mechanical ventilation
systems for enclosed parking garages shall operate continu-
ously or shall be automatically operated by means of carbon
monoxide detectors applied in conjunction with nitrogen
dioxide detectors. Such detectors shall be listed in accordance
with UL 2075 and installed in accordance with their listing
and the manufacturers’ instructions. Automatic operation
shall cycle the ventilation system between the following two
modes of operation:
1. Full-on at an airflow rate of not less than 0.75 cfm per
square foot [0.0038 m3/(s • m2)] of the floor area served.
2. Standby at an airflow rate of not less than 0.05 cfm per
square foot [0.00025 m3/(s • m2)] of the floor area served.

404.2 Occupied spaces accessory to public garages. Con-
necting offices, waiting rooms, ticket booths and similar uses
that are accessory to a public garage shall be maintained at a
positive pressure and shall be provided with ventilation in
accordance with Section 403.3.1.

SECTION 405
SYSTEMS CONTROL
405.1 General. Mechanical ventilation systems shall be pro-
vided with manual or automatic controls that will operate
such systems whenever the spaces are occupied. Air-condi-

2018 INTERNATIONAL MECHANICAL CODE 35


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
VENTILATION

TABLE 403.3.1.1
MINIMUM VENTILATION RATES
PEOPLE OUTDOOR AREA OUTDOOR
EXHAUST
OCCUPANT DENSITY AIRFLOW RATE IN AIRFLOW RATE IN
OCCUPANCY CLASSIFICATION AIRFLOW RATE
#/1000 FT2 a BREATHING ZONE, BREATHING ZONE,
CFM/FT2 a
Rp CFM/PERSON Ra CFM/FT2 a
Correctional facilities
Booking/waiting 50 7.5 0.06 —
Cells
without plumbing fixtures 25 5 0.12 —
with plumbing fixturesg 25 5 0.12 1.0
Day room 30 5 0.06 —
Dining halls
— — — —
(see “Food and beverage service”)
Guard stations 15 5 0.06 —
Dry cleaners, laundries
Coin-operated dry cleaner 20 15 — —
Coin-operated laundries 20 7.5 0.12 —
Commercial dry cleaner 30 30 — —
Commercial laundry 10 25 — —
Storage, pick up 30 7.5 0.12 —
Education
Art classroomg 20 10 0.18 0.7
Auditoriums 150 5 0.06 —
Classrooms (ages 5-8) 25 10 0.12 —
Classrooms (age 9 plus) 35 10 0.12 —
Computer lab 25 10 0.12 —
Corridors (see “Public spaces”) — — — —
Day care (through age 4) 25 10 0.18 —
Lecture classroom 65 7.5 0.06 —
Lecture hall (fixed seats) 150 7.5 0.06 —
Locker/dressing roomsg — — — 0.25
Media center 25 10 0.12 —
Multiuse assembly 100 7.5 0.06 —
Music/theater/dance 35 10 0.06 —
Science laboratoriesg 25 10 0.18 1.0
Smoking loungesb 70 60 — —
Sports locker roomsg — — — 0.5
Wood/metal shopsg 20 10 0.18 0.5
Food and beverage service
Bars, cocktail lounges 100 7.5 0.18 —
Cafeteria, fast food 100 7.5 0.18 —
Dining rooms 70 7.5 0.18 —
Kitchens (cooking)b 20 7.5 0.12 0.7
(continued)

36 2018 INTERNATIONAL MECHANICAL CODE


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
VENTILATION

TABLE 403.3.1.1—continued
MINIMUM VENTILATION RATES
PEOPLE OUTDOOR AREA OUTDOOR
EXHAUST
OCCUPANT DENSITY AIRFLOW RATE IN AIRFLOW RATE IN
OCCUPANCY CLASSIFICATION AIRFLOW RATE
#/1000 FT2 a BREATHING ZONE, BREATHING ZONE,
CFM/FT2 a
Rp CFM/PERSON Ra CFM/FT2 a

Hotels, motels, resorts and dormitories


Bathrooms/toilet—privateg — — — 25/50f
Bedroom/living room 10 5 0.06 —
Conference/meeting 50 5 0.06 —
Dormitory sleeping areas 20 5 0.06 —
Gambling casinos 120 7.5 0.18 —
Lobbies/prefunction 30 7.5 0.06 —
Multipurpose assembly 120 5 0.06 —
Offices
Conference rooms 50 5 0.06 —
Main entry lobbies 10 5 0.06 —
Office spaces 5 5 0.06 —
Reception areas 30 5 0.06 —
Telephone/data entry 60 5 0.06 —
Private dwellings, single and multiple
Garages, common for multiple unitsb — — — 0.75
Kitchensb — — — 25/100f
Based on number of
bedrooms. First bed- 0.35 ACH but not less
Living areasc — —
room, 2; each addi- than 15 cfm/person
tional bedroom, 1
Toilet rooms and bathroomsg — — — 20/50f
Public spaces
Corridors — — 0.06 —
Courtrooms 70 5 0.06 —
Elevator car — — — 1.0
Legislative chambers 50 5 0.06 —
Libraries 10 5 0.12 —
Museums (children’s) 40 7.5 0.12 —
Museums/galleries 40 7.5 0.06 —
Places of religious worship 120 5 0.06 —
Shower room (per shower head)g — — — 50/20f
Smoking loungesb 70 60 — —
Toilet rooms — publicg — — — 50/70e
Retail stores, sales floors and
showroom floors
Dressing rooms — — — 0.25
Mall common areas 40 7.5 0.06 —
Sales 15 7.5 0.12 —
Shipping and receiving 2 10 0.12 —
Smoking loungesb 70 60 — —
Storage rooms — — 0.12 —
Warehouses (see “Storage”) — 10 0.06 —
(continued)

2018 INTERNATIONAL MECHANICAL CODE 37


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
VENTILATION
TABLE 403.3.1.1—continued
MINIMUM VENTILATION RATES
PEOPLE OUTDOOR AREA OUTDOOR
EXHAUST
OCCUPANT DENSITY AIRFLOW RATE IN AIRFLOW RATE IN
OCCUPANCY CLASSIFICATION AIRFLOW RATE
#/1000 FT2 a BREATHING ZONE, BREATHING ZONE,
CFM/FT2 a
Rp CFM/PERSON Ra CFM/FT2 a

Specialty shops
Automotive motor-fuel dispensing stationsb — — — 1.5
Barber 25 7.5 0.06 0.5
Beauty salonsb 25 20 0.12 0.6
Nail salons b, h 25 20 0.12 0.6
Embalming roomb — — — 2.0
Pet shops (animal areas)b 10 7.5 0.18 0.9
Supermarkets 8 7.5 0.06 —
Sports and amusement
Bowling alleys (seating areas) 40 10 0.12 —
Disco/dance floors 100 20 0.06 —
Game arcades 20 7.5 0.18 —
Gym, stadium, arena (play area) 7 20 0.18 —
Health club/aerobics room 40 20 0.06 —
Health club/weight room 10 20 0.06 —
Ice arenas without combustion engines — — 0.30 0.5
Spectator areas 150 7.5 0.06 —
Swimming pools (pool and deck area) — — 0.48 —
Storage
Repair garages, enclosed parking garagesb,d — — — 0.75
Refrigerated warehouses/freezers — 10 — —
Warehouses — 10 0.06 —
Theaters
Auditoriums (see “Education”) — — — —
Lobbies 150 5 0.06 —
Stages, studios 70 10 0.06 —
Ticket booths 60 5 0.06 —
Transportation
Platforms 100 7.5 0.06 —
Transportation waiting 100 7.5 0.06 —
(continued)

38 2018 INTERNATIONAL MECHANICAL CODE


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
VENTILATION

TABLE 403.3.1.1—continued
MINIMUM VENTILATION RATES
PEOPLE OUTDOOR AREA OUTDOOR
EXHAUST
OCCUPANT DENSITY AIRFLOW RATE IN AIRFLOW RATE IN
OCCUPANCY CLASSIFICATION AIRFLOW RATE
#/1000 FT2 a BREATHING ZONE, BREATHING ZONE,
CFM/FT2 a
Rp CFM/PERSON Ra CFM/FT2 a

Workrooms
Bank vaults/safe deposit 5 5 0.06 —
Computer (without printing) 4 5 0.06 —
Copy, printing rooms 4 5 0.06 0.5
Darkrooms — — — 1.0
Meat processingc 10 15 — —
Pharmacy (prep. area) 10 5 0.18 —
Photo studios 10 5 0.12 —
For SI: 1 cubic foot per minute = 0.0004719 m3/s, 1 ton = 908 kg, 1 cubic foot per minute per square foot = 0.00508 m3/(s • m2),
°C = [(°F) - 32]/1.8, 1 square foot = 0.0929 m2.
a. Based on net occupiable floor area.
b. Mechanical exhaust required and the recirculation of air from such spaces is prohibited. Recirculation of air that is contained completely within such spaces
shall not be prohibited (see Section 403.2.1, Item 3).
c. Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous.
d. Ventilation systems in enclosed parking garages shall comply with Section 404.
e. Rates are per water closet or urinal. The higher rate shall be provided where the exhaust system is designed to operate intermittently. The lower rate shall be
permitted only where the exhaust system is designed to operate continuously while occupied.
f. Rates are per room unless otherwise indicated. The higher rate shall be provided where the exhaust system is designed to operate intermittently. The lower rate
shall be permitted only where the exhaust system is designed to operate continuously while occupied.
g. Mechanical exhaust is required and recirculation from such spaces is prohibited except that recirculation shall be permitted where the resulting supply
airstream consists of not more than 10 percent air recirculated from these spaces. Recirculation of air that is contained completely within such spaces shall not
be prohibited (see Section 403.2.1, Items 2 and 4).
h. For nail salons, each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than 50 cfm per station.
Exhaust inlets shall be located in accordance with Section 502.20. Where one or more required source capture systems operate continuously during
occupancy, the exhaust rate from such systems shall be permitted to be applied to the exhaust flow rate required by Table 403.3.1.1 for the nail salon.

2018 INTERNATIONAL MECHANICAL CODE 39


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
CHAPTER 6

DUCT SYSTEMS

User note:
About this chapter: Chapter 6 addresses duct systems used in HVAC systems and some exhaust systems. Some exhaust system ducts are
addressed in Chapter 5, such as kitchen exhaust ducts and clothes dryer exhaust ducts. This chapter addresses air plenums such as above-ceil-
®
ing and below-floor plenums. Section 607 covers fire and smoke dampers, consistent with the requirements of the International Building Code .

SECTION 601 4. The air-handling system serving the corridor is shut


GENERAL down upon detection of sprinkler waterflow where
601.1 Scope. Duct systems used for the movement of air in the building is equipped throughout with an auto-
air-conditioning, heating, ventilating and exhaust systems matic sprinkler system.
shall conform to the provisions of this chapter except as oth- 5. The space between the corridor ceiling and the floor
erwise specified in Chapters 5 and 7. or roof structure above the corridor is used as a com-
Exception: Ducts discharging combustible material ponent of an approved engineered smoke control
directly into any combustion chamber shall conform to the system.
requirements of NFPA 82. [BE] 601.3 Exits. Equipment and ductwork for exit enclosure
[BE] 601.2 Air movement in egress elements. Corridors ventilation shall comply with one of the following items:
shall not serve as supply, return, exhaust, relief or ventilation 1. Such equipment and ductwork shall be located exterior
air ducts. to the building and shall be directly connected to the
Exceptions: exit enclosure by ductwork enclosed in construction as
required by the International Building Code for shafts.
1. Use of a corridor as a source of makeup air for
2. Where such equipment and ductwork is located within
exhaust systems in rooms that open directly onto
the exit enclosure, the intake air shall be taken directly
such corridors, including toilet rooms, bathrooms,
from the outdoors and the exhaust air shall be dis-
dressing rooms, smoking lounges and janitor clos-
charged directly to the outdoors, or such air shall be
ets, shall be permitted, provided that each such cor-
conveyed through ducts enclosed in construction as
ridor is directly supplied with outdoor air at a rate
required by the International Building Code for shafts.
greater than the rate of makeup air taken from the
corridor. 3. Where located within the building, such equipment and
ductwork shall be separated from the remainder of the
2. Where located within a dwelling unit, the use of cor-
building, including other mechanical equipment, with
ridors for conveying return air shall not be prohib-
construction as required by the International Building
ited.
Code for shafts.
3. Where located within tenant spaces of 1,000 square
In each case, openings into fire-resistance-rated construc-
feet (93 m2) or less in area, use of corridors for con-
tion shall be limited to those needed for maintenance and
veying return air is permitted. operation and shall be protected by self-closing fire-resis-
4. Incidental air movement from pressurized rooms tance-rated devices in accordance with the International
within health care facilities, provided that the corri- Building Code for enclosure wall opening protectives. Exit
dor is not the primary source of supply or return to enclosure ventilation systems shall be independent of other
the room. building ventilation systems.
[BE] 601.2.1 Corridor ceiling. Use of the space between 601.4 Contamination prevention. Exhaust ducts under posi-
the corridor ceiling and the floor or roof structure above as tive pressure, chimneys and vents shall not extend into or
a return air plenum is permitted for one or more of the fol- pass through ducts or plenums.
lowing conditions: Exceptions:
1. The corridor is not required to be of fire-resistance- 1. Exhaust systems located in ceiling return air ple-
rated construction. nums over spaces that are permitted to have 10 per-
2. The corridor is separated from the plenum by fire- cent recirculation in accordance with Section
resistance-rated construction. 403.2.1, Item 4. The exhaust duct joints, seams and
3. The air-handling system serving the corridor is shut connections shall comply with Section 603.9.
down upon activation of the air-handling unit smoke 2. This section shall not apply to chimneys and vents
detectors required by this code. that pass through plenums where such venting sys-

2018 INTERNATIONAL MECHANICAL CODE 69


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

tems comply with one of the following require- 2. Dedicated forced air systems serving only the
ments: garage shall not be prohibited from obtaining return
2.1. The venting system shall be listed for posi- air from the garage.
tive pressure applications and shall be
sealed in accordance with the vent manu-
SECTION 602
facturer’s instructions.
PLENUMS
2.2. The venting system shall be installed such 602.1 General. Supply, return, exhaust, relief and ventilation
that fittings and joints between sections are air plenums shall be limited to uninhabited crawl spaces,
not installed in the above-ceiling space. areas above a ceiling or below the floor, attic spaces, mechan-
2.3. The venting system shall be installed in a ical equipment rooms and the framing cavities addressed in
conduit or enclosure with sealed joints sep- Section 602.3. Plenums shall be limited to one fire area. Air
arating the interior of the conduit or enclo- systems shall be ducted from the boundary of the fire area
sure from the ceiling space. served directly to the air-handling equipment. Fuel-fired
601.5 Return air openings. Return air openings for heating, appliances shall not be installed within a plenum.
ventilation and air-conditioning systems shall comply with all 602.2 Construction. Plenum enclosure construction materi-
of the following: als that are exposed to the airflow shall comply with the
requirements of Section 703.5 of the International Building
1. Openings shall not be located less than 10 feet (3048
Code or such materials shall have a flame spread index of not
mm) measured in any direction from an open combus-
more than 25 and a smoke-developed index of not more than
tion chamber or draft hood of another appliance located
50 when tested in accordance with ASTM E84 or UL 723.
in the same room or space.
The use of gypsum boards to form plenums shall be lim-
2. Return air shall not be taken from a hazardous or insan- ited to systems where the air temperatures do not exceed
itary location or a refrigeration room as defined in this 125ºF (52ºC) and the building and mechanical system design
code. conditions are such that the gypsum board surface tempera-
3. The amount of return air taken from any room or space ture will be maintained above the airstream dew-point tem-
shall be not greater than the flow rate of supply air perature. Air plenums formed by gypsum boards shall not be
delivered to such room or space. incorporated in air-handling systems utilizing evaporative
4. Return and transfer openings shall be sized in accor- coolers.
dance with the appliance or equipment manufacturer’s 602.2.1 Materials within plenums. Except as required by
installation instructions, ACCA Manual D or the design Sections 602.2.1.1 through 602.2.1.8, materials within ple-
of the registered design professional. nums shall be noncombustible or shall be listed and
labeled as having a flame spread index of not more than 25
5. Return air taken from one dwelling unit shall not be and a smoke-developed index of not more than 50 when
discharged into another dwelling unit. tested in accordance with ASTM E84 or UL 723.
6. Taking return air from a crawl space shall not be Exceptions:
accomplished through a direct connection to the return
side of a forced air furnace. Transfer openings in the 1. Rigid and flexible ducts and connectors shall
crawl space enclosure shall not be prohibited. conform to Section 603.
2. Duct coverings, linings, tape and connectors shall
7. Return air shall not be taken from a closet, bathroom,
conform to Sections 603 and 604.
toilet room, kitchen, garage, boiler room, furnace room
or unconditioned attic. 3. This section shall not apply to materials exposed
within plenums in one- and two-family dwell-
8. Return air shall not be taken from indoor swimming ings.
pool enclosures and associated deck areas.
4. This section shall not apply to smoke detectors.
Exceptions:
5. Combustible materials fully enclosed within one
1. Where the air from such spaces is dehumidified of the following:
in accordance with Section 403.2.1, Item 2.
5.1. Continuous noncombustible raceways or
2. Dedicated HVAC systems serving only such enclosures.
spaces.
5.2. Approved gypsum board assemblies.
Exceptions:
5.3. Materials listed and labeled for installa-
1. Taking return air from a kitchen is not prohibited tion within a plenum and listed for the
where such return air openings serve the kitchen and application.
are located not less than 10 feet (3048 mm) from the 6. Materials in Group H, Division 5 fabrication
cooking appliances. areas and the areas above and below the fabrica-

70 2018 INTERNATIONAL MECHANICAL CODE


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

tion area that share a common air recirculation accordance with Section 2603.9 of the International
path with the fabrication area. Building Code.
602.2.1.1 Wiring. Combustible electrical wires and Exceptions:
cables and optical fiber cables exposed within a plenum 1. Foam plastic in plenums used as interior wall
shall be listed and labeled as having a peak optical den- or ceiling finish or interior trim shall exhibit a
sity not greater than 0.50, an average optical density not flame spread index of 75 or less and a smoke-
greater than 0.15, and a flame spread distance not developed index of 450 or less when tested in
greater than 5 feet (1524 mm) when tested in accor- accordance with ASTM E84 or UL 723 at the
dance with NFPA 262, or shall be installed in metal maximum thickness and density intended for
raceways or metal sheathed cable. Combustible optical use, where it is separated from the airflow in
fiber and communication raceways exposed within a the plenum by a thermal barrier complying
plenum shall be listed and labeled as having a peak with Section 2603.4 of the International
optical density not greater than 0.5, an average optical Building Code.
density not greater than 0.15, and a flame spread dis-
tance not greater than 5 feet (1524 mm) when tested in 2. Foam plastic in plenums used as interior wall
accordance with UL 2024. Only plenum-rated wires or ceiling finish or interior trim, shall exhibit a
and cables shall be installed in plenum-rated raceways. flame spread index of 75 or less and a smoke-
developed index of 450 or less when tested in
602.2.1.2 Fire sprinkler piping. Plastic fire sprinkler accordance with ASTM E84 or UL 723 at the
piping exposed within a plenum shall be used only in maximum thickness and density intended for
wet pipe systems and shall be listed and labeled as hav- use, where it is separated from the airflow in
ing a peak optical density not greater than 0.50, an the plenum by corrosion-resistant steel having
average optical density not greater than 0.15, and a a base metal thickness of not less than 0.0160
flame spread distance not greater than 5 feet (1524 mm) inch (0.4 mm).
when tested in accordance with UL 1887.
3. Foam plastic in plenums used as interior wall
602.2.1.3 Pneumatic tubing. Combustible pneumatic or ceiling finish or interior trim, shall exhibit a
tubing exposed within a plenum shall be listed and flame spread index of 75 or less and a smoke-
labeled as having a peak optical density not greater than developed index of 450 or less when tested in
0.50, an average optical density not greater than 0.15, accordance with ASTM E84 or UL 723 at the
and a flame spread distance not greater than 5 feet maximum thickness and density intended for
(1524 mm) when tested in accordance with UL 1820. use, where it is separated from the airflow in
602.2.1.4 Electrical equipment in plenums. Electrical the plenum by not less than a 1-inch (25 mm)
equipment exposed within a plenum shall comply with thickness of masonry or concrete. ➡
Sections 602.2.1.4.1 and 602.2.1.4.2. 602.2.1.7 Plastic plumbing piping and tubing. Plastic
602.2.1.4.1 Equipment in metallic enclosures. piping and tubing used in plumbing systems shall be
Electrical equipment with metallic enclosures listed and labeled as having a flame spread index not
exposed within a plenum shall be permitted. greater than 25 and a smoke-developed index not
greater than 50 when tested in accordance with ASTM
602.2.1.4.2 Equipment in combustible enclosures. E84 or UL 723.
Electrical equipment with combustible enclosures
Exception: Plastic water distribution piping and
exposed within a plenum shall be listed and labeled
tubing listed and labeled in accordance with UL
for such use in accordance with UL 2043.
2846 as having a peak optical density not greater
602.2.1.5 Discrete plumbing and mechanical prod- than 0.50, an average optical density not greater than
ucts in plenums. Where discrete plumbing and 0.15, and a flame spread distance not greater than 5
mechanical products and appurtenances are located in a feet (1524 mm), and installed in accordance with its
plenum and have exposed combustible material, they listing.
shall be listed and labeled for such use in accordance
602.2.1.8 Pipe and duct insulation within plenums.
with UL 2043.
Pipe and duct insulation contained within plenums,
602.2.1.6 Foam plastic in plenums as interior finish including insulation adhesives, shall have a flame
or interior trim. Foam plastic in plenums used as inte- spread index of not more than 25 and a smoke devel-
rior wall or ceiling finish or interior trim shall exhibit a oped index of not more than 50 when tested in accor-
flame spread index of 25 or less and a smoke-devel- dance with ASTM E84 or UL 723, using the specimen
oped index of 50 or less when tested in accordance with preparation and mounting procedures of ASTM E2231.
ASTM E84 or UL 723 at the maximum thickness and Pipe and duct insulation shall not flame, glow, smolder
density intended for use, and shall be tested in accor- or smoke when tested in accordance with ASTM C411
dance with NFPA 286 and meet the acceptance criteria at the temperature to which they are exposed in service.
of Section 803.1.2 of the International Building Code. The test temperature shall not fall below 250ºF
As an alternative to testing to NFPA 286, the foam (121ºC). Pipe and duct insulation shall be listed and
plastic shall be approved based on tests conducted in labeled.

2018 INTERNATIONAL MECHANICAL CODE 71


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

602.3 Stud cavity and joist space plenums. Stud wall cavi- SECTION 603
ties and the spaces between solid floor joists to be utilized as DUCT CONSTRUCTION AND INSTALLATION
air plenums shall comply with the following conditions: 603.1 General. An air distribution system shall be designed
1. Such cavities or spaces shall not be utilized as a plenum and installed to supply the required distribution of air. The
for supply air. installation of an air distribution system shall not affect the
2. Such cavities or spaces shall not be part of a required fire protection requirements specified in the International
fire-resistance-rated assembly. Building Code. Ducts shall be constructed, braced, reinforced
and installed to provide structural strength and durability.
3. Stud wall cavities shall not convey air from more than
one floor level. 603.2 Duct sizing. Ducts installed within a single dwelling
unit shall be sized in accordance with ACCA Manual D, the
4. Stud wall cavities and joist space plenums shall comply appliance manufacturer’s installation instructions or other
with the floor penetration protection requirements of approved methods. Ducts installed within all other buildings
the International Building Code. shall be sized in accordance with the ASHRAE Handbook of
5. Stud wall cavities and joist space plenums shall be iso- Fundamentals or other equivalent computation procedure.
lated from adjacent concealed spaces by approved fire- 603.3 Duct classification. Ducts shall be classified based on
blocking as required in the International Building the maximum operating pressure of the duct at pressures of
Code. positive or negative 0.5, 1.0, 2.0, 3.0, 4.0, 6.0 or 10.0 inches
6. Stud wall cavities in the outside walls of building enve- (1 inch w.c. = 248.7 Pa) of water column. The pressure classi-
lope assemblies shall not be utilized as air plenums. fication of ducts shall equal or exceed the design pressure of
[BS] 602.4 Flood hazard. For structures located in flood the air distribution in which the ducts are utilized.
hazard areas, plenum spaces shall be located above the eleva- 603.4 Metallic ducts. Metallic ducts shall be constructed as
tion required by Section 1612 of the International Building specified in the SMACNA HVAC Duct Construction Stan-
Code for utilities and attendant equipment or shall be dards—Metal and Flexible.
designed and constructed to prevent water from entering or Exception: Ducts installed within single dwelling units
accumulating within the plenum spaces during floods up to shall have a minimum thickness as specified in Table
such elevation. If the plenum spaces are located below the 603.4.
elevation required by Section 1612 of the International 603.4.1 Minimum fasteners. Round metallic ducts shall
Building Code for utilities and attendant equipment, they be mechanically fastened by means of not less than three
shall be capable of resisting hydrostatic and hydrodynamic sheet metal screws or rivets spaced equally around the
loads and stresses, including the effects of buoyancy, during joint.
the occurrence of flooding up to such elevation.
Exception: Where a duct connection is made that is
partially inaccessible, three screws or rivets shall be

TABLE 603.4
DUCT CONSTRUCTION MINIMUM SHEET METAL THICKNESS FOR SINGLE DWELLING UNITSa
STATIC PRESSURE
1
/2-inch water gauge 1-inch water gauge

ROUND DUCT DIAMETER Thickness (inches) Thickness (inches)


(inches) Galvanized Aluminum Galvanized Aluminum
< 12 0.013 0.018 0.013 0.018
12 to14 0.013 0.018 0.016 0.023
15 to 17 0.016 0.023 0.019 0.027
18 0.016 0.023 0.024 0.034
19 to 20 0.019 0.027 0.024 0.034
STATIC PRESSURE
1
/2-inch water gauge 1-inch water gauge

RECTANGULAR DUCT DIMENSION Thickness (inches) Thickness (inches)


(inches) Galvanized Aluminum Galvanized Aluminum
≤8 0.013 0.018 0.013 0.018
9 to10 0.013 0.018 0.016 0.023
11 to 12 0.016 0.023 0.019 0.027
13 to 16 0.019 0.027 0.019 0.027
17 to 18 0.019 0.027 0.024 0.034
19 to 20 0.024 0.034 0.024 0.034
For SI: 1 inch = 25.4 mm, 1-inch water gauge = 249 Pa.
a. Ductwork that exceeds 20 inches by dimension or exceeds a pressure of 1-inch water gauge shall be constructed in accordance with SMACNA HVAC Duct
Construction Standards—Metal and Flexible.

72 2018 INTERNATIONAL MECHANICAL CODE


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

equally spaced on the exposed portion so as to prevent Section 607. Ducts in a private garage that penetrate a wall or
a hinge effect. ceiling that separates a dwelling from a private garage shall
603.4.2 Duct lap. Crimp joints for round and oval metal be continuous, shall be constructed of sheet steel having a
ducts shall be lapped not less than 1 inch (25 mm) and the thickness of not less than 0.0187 inch (0.4712 mm) (No. 26
male end of the duct shall extend into the adjoining duct in gage) and shall not have openings into the garage. Fire and
the direction of airflow. smoke dampers are not required in such ducts passing
through the wall or ceiling separating a dwelling from a pri-
603.5 Nonmetallic ducts. Nonmetallic ducts shall be con- vate garage except where required by Chapter 7 of the Inter-
structed with Class 0 or Class 1 duct material and shall com- national Building Code.
ply with UL 181. Fibrous duct construction shall conform to
the SMACNA Fibrous Glass Duct Construction Standards or 603.8 Underground ducts. Ducts shall be approved for
NAIMA Fibrous Glass Duct Construction Standards. The air underground installation. Metallic ducts not having an
temperature within nonmetallic ducts shall not exceed 250ºF approved protective coating shall be completely encased in
(121ºC). not less than 2 inches (51 mm) of concrete.
603.5.1 Gypsum ducts. The use of gypsum boards to 603.8.1 Slope. Ducts shall have a minimum slope of 1/8
form air shafts (ducts) shall be limited to return air sys- inch per foot (10.4 mm/m) to allow drainage to a point
tems where the air temperatures do not exceed 125ºF provided with access.
(52ºC) and the gypsum board surface temperature is main- 603.8.2 Sealing. Ducts shall be sealed, secured and tested
tained above the airstream dew-point temperature. Air prior to concrete encasement or direct burial. Ducts shall
ducts formed by gypsum boards shall not be incorporated be leak tested as required by Section C403 of the Interna-
in air-handling systems utilizing evaporative coolers. tional Energy Conservation Code.
603.5.2 Phenolic ducts. Nonmetallic phenolic ducts shall 603.8.3 Plastic ducts and fittings. Plastic ducts shall be
be constructed and installed in accordance with the constructed of PVC having a minimum pipe stiffness of 8
SMACNA Phenolic Duct Construction Standards. psi (55 kPa) at 5-percent deflection when tested in accor-
603.6 Flexible air ducts and flexible air connectors. Flexi- dance with ASTM D2412. Plastic duct fittings shall be
ble air ducts, both metallic and nonmetallic, shall comply constructed of either PVC or high-density polyethylene.
with Sections 603.6.1, 603.6.1.1, 603.6.3 and 603.6.4. Flexi- Plastic duct and fittings shall be utilized in underground
ble air connectors, both metallic and nonmetallic, shall com- installations only. The maximum design temperature for
ply with Sections 603.6.2 through 603.6.4. systems utilizing plastic duct and fittings shall be 150°F
(66°C).
603.6.1 Flexible air ducts. Flexible air ducts, both metal-
lic and nonmetallic, shall be tested in accordance with UL 603.9 Joints, seams and connections. Longitudinal and
181. Such ducts shall be listed and labeled as Class 0 or transverse joints, seams and connections in metallic and non-
Class 1 flexible air ducts and shall be installed in accor- metallic ducts shall be constructed as specified in SMACNA
dance with Section 304.1. HVAC Duct Construction Standards—Metal and Flexible
and NAIMA Fibrous Glass Duct Construction Standards.
603.6.1.1 Duct length. Flexible air ducts shall not be
Joints, longitudinal and transverse seams and connections in
limited in length.
ductwork shall be securely fastened and sealed with welds,
603.6.2 Flexible air connectors. Flexible air connectors, gaskets, mastics (adhesives), mastic-plus-embedded-fabric
both metallic and nonmetallic, shall be tested in accor- systems, liquid sealants or tapes. Tapes and mastics used to
dance with UL 181. Such connectors shall be listed and seal fibrous glass ductwork shall be listed and labeled in
labeled as Class 0 or Class 1 flexible air connectors and accordance with UL 181A and shall be marked “181 A-P” for
shall be installed in accordance with Section 304.1. pressure-sensitive tape, “181 A-M” for mastic or “181 A-H”
603.6.2.1 Connector length. Flexible air connectors for heat-sensitive tape. Tapes and mastics used to seal metal-
shall be limited in length to 14 feet (4267 mm). lic and flexible air ducts and flexible air connectors shall
603.6.2.2 Connector penetration limitations. Flexible comply with UL 181B and shall be marked “181 B-FX” for
air connectors shall not pass through any wall, floor or pressure-sensitive tape or “181 B-M” for mastic. Duct con-
ceiling. nections to flanges of air distribution system equipment shall
be sealed and mechanically fastened. Mechanical fasteners
603.6.3 Air temperature. The design temperature of air for use with flexible nonmetallic air ducts shall comply with
to be conveyed in flexible air ducts and flexible air con- UL 181B and shall be marked “181 B-C.” Closure systems
nectors shall be less than 250ºF (121ºC). used to seal all ductwork shall be installed in accordance with
603.6.4 Flexible air duct and air connector clearance. the manufacturer's instructions.
Flexible air ducts and air connectors shall be installed with Exception: For ducts having a static pressure classifica-
a minimum clearance to an appliance as specified in the tion of less than 2 inches of water column (500 Pa), addi-
appliance manufacturer’s installation instructions. tional closure systems shall not be required for
603.7 Rigid duct penetrations. Duct system penetrations of continuously welded joints and seams and locking-type
walls, floors, ceilings and roofs and air transfer openings in joints and seams. This exception shall not apply to snap-
such building components shall be protected as required by

2018 INTERNATIONAL MECHANICAL CODE 73


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

lock and button-lock type joints and seams located outside SECTION 604
of conditioned spaces. INSULATION
603.10 Supports. Ducts shall be supported in accordance 604.1 General. Duct insulation shall conform to the require-
with SMACNA HVAC Duct Construction Standards—Metal ments of Sections 604.2 through 604.13 and the International
and Flexible. Flexible and other factory-made ducts shall be Energy Conservation Code.
supported in accordance with the manufacturer’s instructions. 604.2 Surface temperature. Ducts that operate at tempera-
603.11 Furnace connections. Ducts connecting to a furnace tures exceeding 120°F (49°C) shall have sufficient thermal
shall have a clearance to combustibles in accordance with the insulation to limit the exposed surface temperature to 120°F
furnace manufacturer’s installation instructions. (49°C).
603.12 Condensation. Provisions shall be made to prevent 604.3 Coverings and linings. Coverings and linings, includ-
the formation of condensation on the exterior of any duct. ing adhesives where used, shall have a flame spread index not
[BS] 603.13 Flood hazard areas. For structures in flood haz- more than 25 and a smoke-developed index not more than 50,
ard areas, ducts shall be located above the elevation required when tested in accordance with ASTM E84 or UL 723, using
by Section 1612 of the International Building Code for utili- the specimen preparation and mounting procedures of ASTM
ties and attendant equipment or shall be designed and con- E2231. Duct coverings and linings shall not flame, glow,
structed to prevent water from entering or accumulating smolder or smoke when tested in accordance with ASTM
within the ducts during floods up to such elevation. If the C411 at the temperature to which they are exposed in service.
ducts are located below the elevation required by Section The test temperature shall not fall below 250°F (121°C). Cov-
1612 of the International Building Code for utilities and erings and linings shall be listed and labeled.
attendant equipment, the ducts shall be capable of resisting 604.4 Foam plastic insulation. Foam plastic used as duct
hydrostatic and hydrodynamic loads and stresses, including coverings and linings shall conform to the requirements of
the effects of buoyancy, during the occurrence of flooding up Section 604.
to such elevation. 604.5 Appliance insulation. Listed and labeled appliances
603.14 Location. Ducts shall not be installed in or within 4 that are internally insulated shall be considered as conform-
inches (102 mm) of the earth, except where such ducts com- ing to the requirements of Section 604.
ply with Section 603.8. 604.6 Penetration of assemblies. Duct coverings shall not
603.15 Mechanical protection. Ducts installed in locations penetrate a wall or floor required to have a fire-resistance rat-
where they are exposed to mechanical damage by vehicles or ing or required to be fireblocked.
from other causes shall be protected by approved barriers. 604.7 Identification. External duct insulation, except spray
603.16 Weather protection. Ducts including linings, cover- polyurethane foam, and factory-insulated flexible duct shall
ings and vibration isolation connectors installed on the exte- be legibly printed or identified at intervals not greater than 36
rior of the building shall be protected against the elements. inches (914 mm) with the name of the manufacturer, the ther-
603.17 Air dispersion systems. Air dispersion systems shall: mal resistance R-value at the specified installed thickness and
the flame spread and smoke-developed indices of the com-
1. Be installed entirely in exposed locations.
posite materials. Duct insulation product R-values shall be
2. Be utilized in systems under positive pressure. based on insulation only, excluding air films, vapor retarders
3. Not pass through or penetrate fire-resistant-rated con- or other duct components, and shall be based on tested C-val-
struction. ues at 75ºF (24ºC) mean temperature at the installed thick-
4. Be listed and labeled in compliance with UL 2518. ness, in accordance with recognized industry procedures. The
installed thickness of duct insulation used to determine its R-
603.18 Registers, grilles and diffusers. Duct registers, value shall be determined as follows:
grilles and diffusers shall be installed in accordance with the
manufacturer’s instructions. Volume dampers or other means 1. For duct board, duct liner and factory-made rigid ducts
of supply air adjustment shall be provided in the branch ducts not normally subjected to compression, the nominal
or at each individual duct register, grille or diffuser. Each vol- insulation thickness shall be used.
ume damper or other means of supply air adjustment used in 2. For duct wrap, the installed thickness shall be assumed
balancing shall be provided with access. to be 75 percent (25 percent compression) of nominal
603.18.1 Floor registers. Floor registers shall resist, with- thickness.
out structural failure, a 200-pound (90.8 kg) concentrated 3. For factory-made flexible air ducts, the installed thick-
load on a 2-inch-diameter (51 mm) disc applied to the ness shall be determined by dividing the difference
most critical area of the exposed face. between the actual outside diameter and nominal inside
603.18.2 Prohibited locations. Diffusers, registers and diameter by two.
grilles shall be prohibited in the floor or its upward exten- 4. For spray polyurethane foam, the aged R-value per
sion within toilet and bathing rooms required by the Inter- inch, measured in accordance with recognized industry
national Building Code to have smooth, hard, standards, shall be provided to the customer in writing
nonabsorbent surfaces. at the time of foam application.
Exception: Dwelling units. 604.8 Lining installation. Linings shall be interrupted at the
area of operation of a fire damper and at not less than 6 inches

74 2018 INTERNATIONAL MECHANICAL CODE


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

(152 mm) upstream of and 6 inches (152 mm) downstream of tion in air distribution systems, as required by this section.
electric-resistance and fuel-burning heaters in a duct system. Duct smoke detectors shall comply with UL 268A. Other
Metal nosings or sleeves shall be installed over exposed duct smoke detectors shall comply with UL 268.
liner edges that face opposite the direction of airflow. 606.2 Where required. Smoke detectors shall be installed
604.9 Thermal continuity. Where a duct liner has been where indicated in Sections 606.2.1 through 606.2.3.
interrupted, a duct covering of equal thermal performance Exception: Smoke detectors shall not be required where
shall be installed.
air distribution systems are incapable of spreading smoke
604.10 Service openings. Service openings shall not be con- beyond the enclosing walls, floors and ceilings of the
cealed by duct coverings unless the exact location of the room or space in which the smoke is generated.
opening is properly identified.
606.2.1 Return air systems. Smoke detectors shall be
604.11 Vapor retarders. Where ducts used for cooling are installed in return air systems with a design capacity
externally insulated, the insulation shall be covered with a greater than 2,000 cfm (0.9 m3/s), in the return air duct or
vapor retarder having a maximum permeance of 0.05 perm plenum upstream of any filters, exhaust air connections,
[2.87 ng/(Pa • s • m2)] or aluminum foil having a minimum outdoor air connections, or decontamination equipment
thickness of 2 mils (0.051 mm). Insulations having a perme- and appliances.
ance of 0.05 perm [2.87 ng/(Pa • s • m2)] or less shall not be
required to be covered. Joints and seams shall be sealed to Exception: Smoke detectors are not required in the
maintain the continuity of the vapor retarder. return air system where all portions of the building
served by the air distribution system are protected by
Exception: A vapor retarder is not required for spray poly- area smoke detectors connected to a fire alarm system
urethane foam insulation having a water vapor permeance in accordance with the International Fire Code. The
of not greater than 3 perms per inch [1722 ng/(s • m2 • Pa)]
area smoke detection system shall comply with Section
at the installed thickness.
606.4.
604.12 Weatherproof barriers. Insulated exterior ducts
shall be protected with an approved weatherproof barrier. 606.2.2 Common supply and return air systems. Where
multiple air-handling systems share common supply or
604.13 Internal insulation. Materials used as internal insula- return air ducts or plenums with a combined design capac-
tion and exposed to the airstream in ducts shall be shown to ity greater than 2,000 cfm (0.9 m3/s), the return air system
be durable when tested in accordance with UL 181. Exposed shall be provided with smoke detectors in accordance with
internal insulation that is not impermeable to water shall not Section 606.2.1.
be used to line ducts or plenums from the exit of a cooling
coil to the downstream end of the drain pan. Exception: Individual smoke detectors shall not be
required for each fan-powered terminal unit, provided
that such units do not have an individual design capac-
SECTION 605 ity greater than 2,000 cfm (0.9 m3/s) and will be shut
AIR FILTERS down by activation of one of the following:
605.1 General. Heating and air-conditioning systems shall be 1. Smoke detectors required by Sections 606.2.1
provided with approved air filters. Filters shall be installed and 606.2.3.
such that all return air, outdoor air and makeup air is filtered 2. An approved area smoke detector system located
upstream from any heat exchanger or coil. Filters shall be in the return air plenum serving such units.
installed in an approved convenient location. Liquid adhesive
coatings used on filters shall have a flash point not lower than 3. An area smoke detector system as prescribed in
325ºF (163ºC). the exception to Section 606.2.1.
605.2 Approval. Media-type and electrostatic-type air filters In all cases, the smoke detectors shall comply with Sec-
shall be listed and labeled. Media-type air filters shall comply tions 606.4 and 606.4.1.
with UL 900. High-efficiency particulate air filters shall com- 606.2.3 Return air risers. Where return air risers serve
ply with UL 586. Electrostatic-type air filters shall comply two or more stories and serve any portion of a return air
with UL 867. Air filters utilized within dwelling units shall be system having a design capacity greater than 15,000 cfm
designed for the intended application and shall not be (7.1 m3/s), smoke detectors shall be installed at each story.
required to be listed and labeled. Such smoke detectors shall be located upstream of the
605.3 Airflow over the filter. Ducts shall be constructed to connection between the return air riser and any air ducts or
allow an even distribution of air over the entire filter. plenums.
[F] 606.3 Installation. Smoke detectors required by this sec-
tion shall be installed in accordance with NFPA 72. The
SECTION 606 required smoke detectors shall be installed to monitor the
SMOKE DETECTION SYSTEMS CONTROL entire airflow conveyed by the system including return air
606.1 Controls required. Air distribution systems shall be and exhaust or relief air. Access shall be provided to smoke
equipped with smoke detectors listed and labeled for installa- detectors for inspection and maintenance.

2018 INTERNATIONAL MECHANICAL CODE 75


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

[F] 606.4 Controls operation. Upon activation, the smoke shall be installed in accordance with the requirements of this
detectors shall shut down all operational capabilities of the air section, and the manufacturer’s instructions and listing.
distribution system in accordance with the listing and label- [BF] 607.2.1 Smoke control system. Where the installa-
ing of appliances used in the system. Air distribution systems tion of a fire damper will interfere with the operation of a
that are part of a smoke control system shall switch to the required smoke control system in accordance with Section
smoke control mode upon activation of a detector. 909 of the International Building Code, approved alterna-
[F] 606.4.1 Supervision. The duct smoke detectors shall tive protection shall be used. Where mechanical systems
be connected to a fire alarm system where a fire alarm sys- including ducts and dampers used for normal building
tem is required by Section 907.2 of the International Fire ventilation serve as part of the smoke control system, the
Code. The actuation of a duct smoke detector shall acti- expected performance of these systems in smoke control
vate a visible and audible supervisory signal at a con- mode shall be addressed in the rational analysis required
stantly attended location. In facilities that are required to by Section 909.4 of the International Building Code.
be monitored by a supervising station, duct smoke detec- 607.2.2 Hazardous exhaust ducts. Fire dampers for haz-
tors shall report only as a supervisory signal, not as a fire ardous exhaust duct systems shall comply with Section
alarm. 510.
Exceptions: [BF] 607.3 Damper testing, ratings and actuation. Damper
1. The supervisory signal at a constantly attended testing, ratings and actuation shall be in accordance with Sec-
location is not required where the duct smoke tions 607.3.1 through 607.3.3.5.
detector activates the building’s alarm-indicating [BF] 607.3.1 Damper testing. Dampers shall be listed
appliances. and labeled in accordance with the standards in this sec-
2. In occupancies not required to be equipped with a tion. Fire dampers shall comply with the requirements of
fire alarm system, actuation of a smoke detector UL 555. Only fire dampers labeled for use in dynamic sys-
shall activate a visible and audible signal in an tems shall be installed in heating, ventilating and air-con-
approved location. Duct smoke detector trouble ditioning systems designed to operate with fans on during
conditions shall activate a visible or audible sig- a fire. Smoke dampers shall comply with the requirements
nal in an approved location and shall be identi- of UL 555S. Combination fire/smoke dampers shall com-
fied as air duct detector trouble. ply with the requirements of both UL 555 and UL 555S.
Ceiling radiation dampers shall comply with the require-
ments of UL 555C or shall be tested as part of a fire-resis-
SECTION 607 tance-rated floor/ceiling or roof/ceiling assembly in
DUCT AND TRANSFER OPENINGS accordance with ASTM E119 or UL 263. Only ceiling
[BF] 607.1 General. The provisions of this section shall gov- radiation dampers labeled for use in dynamic systems shall
ern the protection of duct penetrations and air transfer open- be installed in heating, ventilation and air-conditioning
ings in assemblies required to be protected. systems designed to operate with fans on during a fire.
Corridor dampers shall comply with requirements of both
[BF] 607.1.1 Ducts between shafts. Ducts transitioning
horizontally between shafts shall not require a shaft enclo- UL 555 and UL 555S. Corridor dampers shall demonstrate
acceptable closure performance when subjected to 150
sure provided that the duct penetration into each associ-
feet per minute (0.76 mps) velocity across the face of the
ated shaft is protected with dampers complying with this
section. damper using the UL 555 fire exposure test.
[BF] 607.3.2 Damper rating. Damper ratings shall be in
[BF] 607.1.2 Ducts that penetrate fire-resistance-rated
accordance with Sections 607.3.2.1 through 607.3.2.4.
assemblies without dampers. Ducts that penetrate fire-
resistance-rated walls and are not required by this section [BF] 607.3.2.1 Fire damper ratings. Fire dampers
to have fire dampers shall comply with the requirements of shall have the minimum rating specified in Table
Sections 714.3 through 714.4.3 of the International Build- 607.3.2.1.
ing Code. Ducts that penetrate horizontal assemblies not [BF] TABLE 607.3.2.1
required to be contained within a shaft and not required by FIRE DAMPER RATING
this section to have fire dampers shall comply with the MINIMUM
DAMPER
requirements of Section 714.5 of the International Build- TYPE OF PENETRATION RATING (hour)
ing Code.
Less than 3-hour fire-resistance-rated assemblies 11/2
[BF] 607.1.2.1 Ducts that penetrate nonfire-resis-
tance-rated assemblies. The space around a duct pene- 3-hour or greater fire-resistance-rated assemblies 3
trating a nonfire-resistance-rated floor assembly shall [BF] 607.3.2.2 Smoke damper ratings. Smoke
comply with Section 717.6.3 of the International Build- damper leakage ratings shall be Class I or II. Elevated
ing Code. temperature ratings shall be not less than 250°F
[BF] 607.2 Installation. Fire dampers, smoke dampers, com- (121°C).
bination fire/smoke dampers and ceiling radiation dampers [BF] 607.3.2.3 Combination fire/smoke damper rat-
located within air distribution and smoke control systems ings. Combination fire/smoke dampers shall have the

76 2018 INTERNATIONAL MECHANICAL CODE


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

minimum rating specified for fire dampers in Table 5. Where a smoke detection system is installed in all
607.3.2.1 and shall have the minimum rating specified areas served by the duct in which the damper will
for smoke dampers in Section 607.3.2.2. be located, the smoke dampers shall be permitted
[BF] 607.3.2.4 Corridor damper ratings. Corridor to be controlled by the smoke detection system.
dampers shall have the following minimum ratings. [BF] 607.3.3.3 Combination fire/smoke damper
actuation. Combination fire/smoke damper actuation
1. One-hour fire-resistance rating. shall be in accordance with Sections 607.3.3.1 and
2. Class I or II leakage rating as specified in Section 607.3.3.2. Combination fire/smoke dampers installed in
607.3.2.2. smoke control system shaft penetrations shall not be
[BF] 607.3.3 Damper actuation. Damper actuation shall activated by local area smoke detection unless it is sec-
be in accordance with Sections 607.3.3.1 through ondary to the smoke management system controls.
607.3.3.5 as applicable. [BF] 607.3.3.4 Ceiling radiation damper actuation.
The operating temperature of a ceiling radiation
[BF] 607.3.3.1 Fire damper actuation device. The
damper actuation device shall be 50°F (28°C) above the
fire damper actuation device shall meet one of the fol- normal temperature within the duct system, but not less
lowing requirements: than 160°F (71°C).
1. The operating temperature shall be approxi- [BF] 607.3.3.5 Corridor damper actuation. Corridor
mately 50°F (28°C) above the normal tempera- damper actuation shall be in accordance with Sections
ture within the duct system, but not less than 607.3.3.1 and 607.3.3.2.
160°F (71°C).
[BF] 607.4 Access and identification. Fire and smoke damp-
2. The operating temperature shall be not more than ers shall be provided with an approved means of access, large
350°F (177°C) where located in a smoke control enough to permit inspection and maintenance of the damper
system complying with Section 909 of the Inter- and its operating parts. The access shall not affect the integ-
national Building Code. rity of fire-resistance-rated assemblies. The access openings
[BF] 607.3.3.2 Smoke damper actuation. The smoke shall not reduce the fire-resistance rating of the assembly.
damper shall close upon actuation of a listed smoke Access points shall be permanently identified on the exterior
detector or detectors installed in accordance with Sec- by a label having letters not less than 0.5 inch (12.7 mm) in
tion 907.3 of the International Building Code and one height reading: FIRE/SMOKE DAMPER, SMOKE
of the following methods, as applicable: DAMPER or FIRE DAMPER. Access doors in ducts shall be
tight fitting and suitable for the required duct construction.
1. Where a smoke damper is installed within a duct,
a smoke detector shall be installed inside the duct [BF] 607.5 Where required. Fire dampers, smoke dampers,
or outside the duct with sampling tubes protrud- combination fire/smoke dampers, ceiling radiation dampers
ing into the duct. The detector or tubes within the and corridor dampers shall be provided at the locations pre-
duct shall be within 5 feet (1524 mm) of the scribed in Sections 607.5.1 through 607.5.7. Where an assem-
damper. Air outlets and inlets shall not be located bly is required to have both fire dampers and smoke dampers,
between the detector or tubes and the damper. combination fire/smoke dampers or a fire damper and smoke
The detector shall be listed for the air velocity, damper shall be provided.
temperature and humidity anticipated at the point [BF] 607.5.1 Fire walls. Ducts and air transfer openings
where it is installed. Other than in mechanical permitted in fire walls in accordance with Section 706.11
smoke control systems, dampers shall be closed of the International Building Code shall be protected with
upon fan shutdown where local smoke detectors listed fire dampers installed in accordance with their list-
require a minimum velocity to operate. ing.
2. Where a smoke damper is installed above smoke [BF] 607.5.1.1 Horizontal exits. A listed smoke
barrier doors in a smoke barrier, a spot-type damper designed to resist the passage of smoke shall be
detector shall be installed on either side of the provided at each point that a duct or air transfer open-
smoke barrier door opening. The detector shall be ing penetrates a fire wall that serves as a horizontal exit.
listed for releasing service if used for direct inter- [BF] 607.5.2 Fire barriers. Ducts and air transfer open-
face with the damper. ings that penetrate fire barriers shall be protected with
3. Where a smoke damper is installed within an listed fire dampers installed in accordance with their list-
unducted opening in a wall, a spot-type detector ing. Ducts and air transfer openings shall not penetrate
shall be installed within 5 feet (1524 mm) hori- enclosures for interior exit stairways and ramps and exit
zontally of the damper. The detector shall be passageways except as permitted by Sections 1023.5 and
listed for releasing service if used for direct inter- 1024.6, respectively, of the International Building Code.
face with the damper. Exception: Fire dampers are not required at penetra-
4. Where a smoke damper is installed in a corridor tions of fire barriers where any of the following apply:
wall or ceiling, the damper shall be permitted to 1. Penetrations are tested in accordance with ASTM
be controlled by a smoke detection system E119 or UL 263 as part of the fire-resistance-
installed in the corridor. rated assembly.

2018 INTERNATIONAL MECHANICAL CODE 77


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

2. Ducts are used as part of an approved smoke con- 3.5. The duct shall not terminate at a wall reg-
trol system in accordance with Section 513 and ister in the fire-resistance-rated wall.
where the fire damper would interfere with the 3.6. A minimum 12-inch-long (305 mm) by
operation of the smoke control system. 0.060-inch-thick (1.52 mm) steel sleeve
3. Such walls are penetrated by ducted HVAC sys- shall be centered in each duct opening.
tems, have a required fire-resistance rating of 1 The sleeve shall be secured to both sides
hour or less, are in areas of other than Group H of the wall and all four sides of the sleeve
and are in buildings equipped throughout with an with minimum 11/2-inch by 11/2-inch by
automatic sprinkler system in accordance with 0.060-inch (38 mm by 38 mm by 1.52
Section 903.3.1.1 or 903.3.1.2 of the Interna- mm) steel retaining angles. The retaining
tional Building Code. For the purposes of this angles shall be secured to the sleeve and
exception, a ducted HVAC system shall be a duct the wall with No. 10 (M5) screws. The
system for the structure’s HVAC system. Such a annular space between the steel sleeve
duct system shall be constructed of sheet steel not and the wall opening shall be filled with
less than 26 gage [0.0217 inch (0.55 mm)] thick- rock (mineral) wool batting on all sides.
ness and shall be continuous from the air-han-
4. Such walls are penetrated by ducted HVAC sys-
dling appliance or equipment to the air outlet and tems, have a required fire-resistance rating of 1
inlet terminals.
hour or less, and are in areas of other than Group
[BF] 607.5.2.1 Horizontal exits. A listed smoke H and are in buildings equipped throughout with
damper designed to resist the passage of smoke shall be an automatic sprinkler system in accordance with
provided at each point that a duct or air transfer open- Section 903.3.1.1 or 903.3.1.2 of the Interna-
ing penetrates a fire barrier that serves as a horizontal tional Building Code. For the purposes of this
exit. exception, a ducted HVAC system shall be a duct
[BF] 607.5.3 Fire partitions. Ducts and air transfer open- system for conveying supply, return or exhaust
ings that penetrate fire partitions shall be protected with air as part of the structure’s HVAC system. Such
listed fire dampers installed in accordance with their list- a duct system shall be constructed of sheet steel
ing. not less than 26 gage in thickness and shall be
continuous from the air-handling appliance or
Exception: In occupancies other than Group H, fire equipment to the air outlet and inlet terminals.
dampers are not required where any of the following
[BF] 607.5.4 Corridors/smoke barriers. A listed smoke
apply:
damper designed to resist the passage of smoke shall be
1. Corridor walls in buildings equipped throughout provided at each point a duct or air transfer opening pene-
with an automatic sprinkler system in accordance trates a smoke barrier wall or a corridor enclosure required
with Section 903.3.1.1 or 903.3.1.2 of the Inter- to have smoke and draft control doors in accordance with
national Building Code and the duct is protected the International Building Code.
as a through penetration in accordance with Sec- A corridor damper shall be provided where corridor
tion 714 of the International Building Code. ceilings, constructed as required for the corridor walls as
2. The partitions are tenant partitions in covered and permitted in Section 708.4, Exception 3, of the Interna-
open mall buildings where the walls are not tional Building Code, are penetrated.
required by provisions elsewhere in the Interna- A ceiling radiation damper shall be provided where the
tional Building Code to extend to the underside ceiling membrane of a fire-resistance-rated floor/ceiling or
of the floor or roof sheathing, slab or deck above. roof/ceiling assembly, constructed as permitted in Section
3. The duct system is constructed of approved mate- 708.4, Exception 2, of the International Building Code, is
rials in accordance with Section 603 and the duct penetrated.
penetrating the wall complies with all of the fol- Smoke dampers and smoke damper actuation methods
lowing requirements: shall comply with Section 607.5.4.1.
3.1. The duct shall not exceed 100 square Exceptions:
inches (0.06 m2). 1. Smoke dampers are not required in corridor pene-
3.2. The duct shall be constructed of steel not trations where the building is equipped through-
less than 0.0217 inch (0.55 mm) in thick- out with an approved smoke control system in
ness. accordance with Section 513 and smoke dampers
are not necessary for the operation and control of
3.3. The duct shall not have openings that the system.
communicate the corridor with adjacent
2. Smoke dampers are not required in smoke barrier
spaces or rooms.
penetrations where the openings in ducts are lim-
3.4. The duct shall be installed above a ceil- ited to a single smoke compartment and the ducts
ing. are constructed of steel.

78 2018 INTERNATIONAL MECHANICAL CODE


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

3. Smoke dampers are not required in corridor pene- 3. Smoke dampers are not required at penetrations
trations where the duct is constructed of steel not of exhaust or supply shafts in parking garages
less than 0.019 inch (0.48 mm) in thickness and that are separated from other building shafts by
there are no openings serving the corridor. not less than 2-hour fire-resistance-rated con-
struction.
4. Smoke dampers are not required in smoke barri-
ers required by Section 407.5 of the International 4. Smoke dampers are not required at penetrations
Building Code for Group I-2, Condition 2 where of shafts where ducts are used as part of an
the HVAC system is fully ducted in accordance approved mechanical smoke control system
with Section 603 and where buildings are designed in accordance with Section 909 of the
equipped throughout with an automatic sprinkler International Building Code and where the
system in accordance with Section 903.3.1.1 of smoke damper will interfere with the operation of
the International Building Code and equipped the smoke control system.
with quick-response sprinklers in accordance 5. Fire dampers and combination fire/smoke damp-
with Section 903.3.2 of the International Build- ers are not required in kitchen and clothes dryer
ing Code. exhaust systems where dampers are prohibited by
[BF] 607.5.4.1 Smoke damper. Smoke dampers shall this code.
close as required by Section 607.3.3.2. [BF] 607.5.5.1 Enclosure at the bottom. Shaft enclo-
[BF] 607.5.5 Shaft enclosures. Shaft enclosures that are sures that do not extend to the bottom of the building or
permitted to be penetrated by ducts and air transfer open- structure shall be protected in accordance with Section
ings shall be protected with listed fire and smoke dampers 713.11 of the International Building Code.
installed in accordance with their listing. [BF] 607.5.6 Exterior walls. Ducts and air transfer open-
Exceptions: ings in fire-resistance-rated exterior walls required to have
protected openings in accordance with Section 705.10 of
1. Fire dampers are not required at penetrations of the International Building Code shall be protected with
shafts where any of the following apply: listed fire dampers installed in accordance with their list-
1.1. Steel exhaust subducts extend not less ing.
than 22 inches (559 mm) vertically in [BF] 607.5.7 Smoke partitions. A listed smoke damper
exhaust shafts provided that there is a designed to resist the passage of smoke shall be provided
continuous airflow upward to the out- at each point where an air transfer opening penetrates a
doors. smoke partition. Smoke dampers and smoke damper actu-
1.2. Penetrations are tested in accordance with ation methods shall comply with Section 607.3.3.2.
ASTM E119 or UL 263 as part of the fire- Exception: Where the installation of a smoke damper
resistance-rated assembly.
will interfere with the operation of a required smoke
1.3. Ducts are used as part of an approved control system in accordance with Section 513,
smoke control system in accordance with approved alternate protection shall be used.
Section 909 of the International Building
[BF] 607.6 Horizontal assemblies. Penetrations by air ducts
Code, and where the fire damper will
of a floor, floor/ceiling assembly or the ceiling membrane of
interfere with the operation of the smoke
a roof/ceiling assembly shall be protected by a shaft enclo-
control system.
sure that complies with Section 713 and Sections 717.6.1
1.4. The penetrations are in parking garage through 717.6.3 of the International Building Code or shall
exhaust or supply shafts that are separated comply with Sections 607.6.1 through 607.6.3.
from other building shafts by not less than
2-hour fire-resistance-rated construction. [BF] 607.6.1 Through penetrations. In occupancies
other than Groups I-2 and I-3, a duct constructed of
2. In Group B and R occupancies equipped through- approved materials in accordance with Section 603 that
out with an automatic sprinkler system in accor- penetrates a fire-resistance-rated floor/ceiling assembly
dance with Section 903.3.1.1 of the International that connects not more than two stories is permitted with-
Building Code, smoke dampers are not required out shaft enclosure protection provided that a listed fire
at penetrations of shafts where kitchen, clothes damper is installed at the floor line or the duct is protected
dryer, bathroom and toilet room exhaust open- in accordance with Section 714.5 of the International
ings with steel exhaust subducts, having a mini- Building Code. For air transfer openings, see Item 6, Sec-
mum thickness of 0.0187 inch (0.4712 mm) (No. tion 712.1.9 of the International Building Code.
26 gage), extend not less than 22 inches (559
mm) vertically and the exhaust fan at the upper Exception: A duct is permitted to penetrate three floors
terminus is powered continuously in accordance or less without a fire damper at each floor provided that
with the provisions of Section 909.11 of the it meets all of the following requirements.
International Building Code, and maintains air- 1. The duct shall be contained and located within
flow upward to the outdoors. the cavity of a wall and shall be constructed of

2018 INTERNATIONAL MECHANICAL CODE 79


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
DUCT SYSTEMS

steel having a minimum thickness of 0.0187 inch penetrates the ceiling of a fire-resistance-rated floor/
(0.4712 mm) (No. 26 gage). ceiling or roof/ceiling assembly.
2. The duct shall open into only one dwelling unit or Exceptions:
sleeping unit and the duct system shall be contin- 1. A fire-resistance-rated assembly tested in
uous from the unit to the exterior of the building. accordance with ASTM E119 or UL 263
3. The duct shall not exceed a 4-inch (102 mm) showing that ceiling radiation dampers are
nominal diameter and the total area of such ducts not required in order to maintain the fire-
shall not exceed 100 square inches for any 100 resistance rating of the assembly.
square feet (64 516 mm2 per 9.3 m2) of the floor 2. Where duct and air transfer openings are
area. protected with a duct outlet penetration sys-
4. The annular space around the duct is protected tem tested as part of a fire-resistance-rated
with materials that prevent the passage of flame assembly in accordance with ASTM E119
and hot gases sufficient to ignite cotton waste or UL 263.
when subjected to ASTM E119 or UL 263 time- [BF] 607.6.2.1 Ceiling radiation dampers testing and
temperature conditions under a minimum posi- installation. Ceiling radiation dampers shall be tested
tive pressure differential of 0.01 inch (2.49 Pa) of in accordance with Section 607.3.1. Ceiling radiation
water at the location of the penetration for the dampers shall be installed in accordance with the
time period equivalent to the fire-resistance rat- details listed in the fire-resistance-rated assembly and
ing of the construction penetrated. the manufacturer’s installation instructions and the list-
5. Grille openings located in a ceiling of a fire-resis- ing.
tance-rated floor/ceiling or roof/ceiling assembly [BF] 607.6.3 Nonfire-resistance-rated floor assemblies.
shall be protected with a listed ceiling radiation Duct systems constructed of approved materials in accor-
damper installed in accordance with Section dance with Section 603 that penetrate nonfire-resistance-
607.6.2.1. rated floor assemblies shall be protected by any of the fol-
[BF] 607.6.2 Membrane penetrations. Ducts and air lowing methods:
transfer openings constructed of approved materials, in 1. A shaft enclosure in accordance with Section 713 of
accordance with Section 603, that penetrate the ceiling the International Building Code.
membrane of a fire-resistance-rated floor/ceiling or roof/
ceiling assembly shall be protected with one of the follow- 2. The duct connects not more than two stories, and the
ing: annular space around the penetrating duct is pro-
tected with an approved noncombustible material
1. A shaft enclosure in accordance with Section 713 of that resists the free passage of flame and the prod-
the International Building Code.
ucts of combustion.
2. A listed ceiling radiation damper installed at the 3. In floor assemblies composed of noncombustible
ceiling line where a duct penetrates the ceiling of a materials, a shaft shall not be required where the
fire-resistance-rated floor/ceiling or roof/ceiling
duct connects not more than three stories, and the
assembly.
annular space around the penetrating duct is pro-
Exceptions: tected with an approved noncombustible material
1. A fire-resistance-rated assembly tested in that resists the free passage of flame and the prod-
accordance with ASTM E119 or UL 263 ucts of combustion and a fire damper is installed at
showing that ceiling radiation dampers are each floor line.
not required in order to maintain the fire- Exception: Fire dampers are not required in ducts
resistance rating of the assembly. within individual residential dwelling units.
2. Where exhaust duct or outdoor air duct [BF] 607.7 Flexible ducts and air connectors. Flexible
penetrations are protected in accordance ducts and air connectors shall not pass through any fire-resis-
with Section 714.5.1.2 of the International tance-rated assembly.
Building Code, are located within the cav-
ity of a wall and do not pass through
another dwelling unit or tenant space.
3. Where duct and air transfer openings are
protected with a duct outlet penetration sys-
tem tested as part of a fire-resistance-rated
assembly in accordance with ASTM E119
or UL 263.
3. A listed ceiling radiation damper installed at the
ceiling line where a diffuser with no duct attached

80 2018 INTERNATIONAL MECHANICAL CODE


Copyright © 2017 ICC. ALL RIGHTS RESERVED. Accessed by Eric Fitch on May 15, 2018 8:17:45 AM pursuant to License Agreement with ICC. No further reproduction or
distribution authorized. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE
AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

Das könnte Ihnen auch gefallen