900VPR-2-280 / 520V

OP380-V01
selec Operating Instructions
TIME SETTINGS
Power ON Delay : 2.0 - 99.9sec
Response Delay : 0 - 99.9sec
SAFETY PRECAUTIONS
All safety related codifications, symbols and
DIMENSIONS ( All dimensions in mm )
35 44
15 18 16 instructions that appear in this operating manual or
(Trip time delay) on the equipment must be strictly followed to ensure
26 28 25

Delay ON Release : 0 - 99.9sec the safety of the operating personnel as well as the
Response Time : <200ms instrument.
HYSTERESIS If the equipment is not used in a manner

67.50

45
90

90
Voltage : 1.0 – 99.9V specified by the manufacturer it might impair the
Frequency : 0.2 – 2Hz protection provided by the equipment.
Asymmetry : 2.0 – 20.0% If there is physical damage to the unit then do not
RESOLUTION use it.
Voltage : 1V Read complete instructions prior to installation
Frequency : 0.1Hz and operation of the unit.
FEATURES ACCURACY 70.50
q Under voltage, over voltage, under frequency, Voltage : ±1% of set value
WIRING GUIDELINES LED INDICATION CHART
over frequency, asymmetry, phase failure and Frequency : ±0.3Hz
Time : ±5% of setting + 200ms Various Power
phase sequence monitoring in 3Ø system WARNING ‘R1' LED ‘R2’ LED
Conditions LED
! RMS measurement (Recovery Time, Trip Delay. Power ON Delay) 1. To prevent the risk of electric shock power supply
! Power ON delay, Trip time delay and OUTPUT SPECIFICATIONS No fault ON OFF OFF
to the equipment must be kept OFF while doing the
Delay on release 2 Relays : Relay1 : 1C/O (SPDT) wiring arrangement. Trip (Relay 1) ON ON OFF
! Adjustable switching hysteresis Relay2 : 1C/O (SPDT) 2. Wiring shall be done strictly according to the
! Two separate alarm relays operation RELAY RATING terminal layout with shortest connections. Confirm Trip (Relay 2) ON OFF ON
NO (5A, 250V AC / 30V DC) that all connections are correct.
SPECIFICATIONS Trip (If programmed
NC (3A, 250V AC / 30V DC) for both relays) ON ON ON

DISPLAY LED INDICATION CAUTION


LED1 (Green) : Power ON TERMINAL CONNECTIONS
3 Digits, Liquid Crystal Display 1. To ensure the safe operation of unit, check the
ELECTRICAL CONNECTION LED2 (Red) : Relay1 wiring and connections. RELAY 1
3Ø-3 wire, 3Ø-4 wire (Continuously ON after trip)
LED3 (Red) : Relay2 15 18 16
AUXILIARY SUPPLY
Self powered (Continuously ON after trip) NO1 NC1
COM1
OPERATING RANGE ENVIRONMENTAL SPECIFICATIONS
280 – 520V AC (L-L) - Indoor use RELAY 2
160 – 300V AC (L-N) - Altitude of up to 2000 meters 26 28 25
FREQUENCY RANGE - Pollution degree II
NC2 NO2
45 - 65Hz Temperature : Operating : 0 to 55OC COM2
VA RATING Storage : - 20 to 70OC
30VA max Humidity : Up to 95% RH, non-condensing
MECHANICAL SPECIFICATIONS L2 L3
TRIP SETTINGS
Under Voltage : 280 to 520V AC (L-L) No. of Push Buttons : 3
[for 3Ø-3 wire] Size : 35mm width
Mounting : 35mm Din Rail Mount N L1
160 to 300V AC (L-N)
[for 3Ø-4 wire] Wire Size (max) : 4 sq.mm
Over Voltage : 280 to 520V AC (L-L) Screw tightening torque : 0.5 N-M
[for 3Ø-3 wire] WEIGHT
160 to 300V AC (L-N) 135 gms.
[for 3Ø-4 wire]
Under Frequency : 45 – 65Hz
Over Frequency : 45 – 65Hz
Phase Asymmetry : 5.0 – 99.9%

Doc. name : OP INST 900VPR-2-280 / 520V OP380-V01(Page 1 of 4)


CONFIGURATION MENU SUB MENU
Press + for 3sec. to enter or exit configuration menu.
Network Selection (NWK) Press to enter sub menu from main menu
MAIN MENU SUB MENU Press or to scroll
Press + or + to change parameter value
Network through sub menu
selection
DISPLAY DEFAULT
(For 1sec) DESCRIPTION RANGE CONDITION
Press Key to go to Relay 1 setting (RL1) from network selection (NWK) VALUE
Press Key to go to network selection (NWK) from Relay 1 setting (RL1)

Network
Relay 1 Set Over Set under Over Set over Under 3P3 / 3P4
selection
settings Over voltage Voltage Under voltage voltage frequency frequency frequency

Relay 1 (RL1) settings Press to enter sub menu from main menu
Press or to scroll
Phase Press + or + to change parameter value
Set under Asymmetry Phase
through sub menu
frequency Asymmetry Setting sequence Phase failure Latch DISPLAY DEFAULT
KEYS

(For 1sec) DESCRIPTION RANGE CONDITION


VALUE
<
V

Over voltage ON / OFF


+

Time Setting Trip time Recovery Power ON R1


for Relay 1 delay time delay
OR

< 280 - 520V(Default : 498)


V
This option will be
Set Over [For 3P3W system]
prompted only when OV
Voltage 160 - 300V(Default : 288)
+

R1 option is made ON
[For 3P4W system]
Relay 2 Over Set Over Under Set under Over Set over
TO SCROLL THROUGH MAIN MENU PRESS

setting voltage voltage voltage voltage frequency frequency


<V

Under voltage ON / OFF


R1

<V 280 - 520V(Default : 332)


Phase Set under This option will be
Under
[For 3P3W system]
Set under Asymmetry Phase voltage prompted only when
frequency frequency Asymmetry Setting sequence Phase failure Latch 160 - 300V(Default : 192)
R1 UV option is made ON
[For 3P4W system]
<
Over
frequency ON / OFF
Time Setting Trip time Recovery R1 Hz
for Relay 2 delay time
<
This option will be
Set over
45.0 - 65.0Hz prompted only when OF
frequency
R1 Hz option is made ON
Hysteresis Voltage Frequency Asymmetry
<
Under
frequency ON / OFF
R1 Hz

Password
Set < This option will be
Enable / Set under
Password Disble password 45.0 - 65.0Hz prompted only when
frequency
R1 Hz UF option is made ON

AS

Factory set Asymmetry ON / OFF


Factory set Yes / No R1

Phase V AS
This option will be
Asymmetry 5.0 - 99.9% prompted only when
Setting R1 AS option ismade ON
Note : Appearance of shaded menus dependant on selection of other parameters
Doc. name : OP INST 900VPR-2-280 / 520V OP380-V01(Page 2 of 4)
DISPLAY DEFAULT DISPLAY DEFAULT
(For 1sec) DESCRIPTION RANGE CONDITION (For 1sec) DESCRIPTION RANGE CONDITION
VALUE VALUE
<
Phase Over
sequence ON / OFF ON / OFF
R1
frequency
R2 Hz

Phase failure <


ON / OFF
R1
Set over 45.0 - 65.0Hz
frequency R2 Hz

If Latch is ON, user has


Latch ON / OFF to reset the unit manually <
R1 when fault is removed Under ON / OFF
frequency
Time Setting for Relay 1 (TM1) Press to enter sub menu from main menu R2 Hz

Press or to scroll
Press + or + to change parameter value < This option will be
through sub menu Set under
45.0 - 65.0Hz prompted only when UF
DISPLAY DEFAULT frequency
DESCRIPTION RANGE CONDITION R2 Hz option is made ON
(For 1sec) VALUE
S
AS

Trip time delay 0.0 - 99.9s Asymmetry ON / OFF


R1 t R2

S
Phase V AS
This option will be
Recovery time 0.0 - 99.9s Asymmetry 5.0 - 99.9% prompted only when
R1 t off Setting R2 AS option is made ON

Applicable for Phase


Power ON 2.0 - 99.9s ON / OFF
Relay 1 & Relay 2 sequence
delay R1 t on R2

Relay 2 (RL2) Press to enter sub menu from main menu


Press or to scroll Phase failure ON / OFF
Press + or + to change parameter value
through sub menu R2

DISPLAY DEFAULT
(For 1sec) DESCRIPTION RANGE CONDITION
VALUE If Latch is ON, user has
If RL1 is selected, all the Latch ON / OFF to reset the unit manually
settings done for RL1 & R2 when fault is removed
Relay RL1 / RL2 TM1 will be automatically
R2
set for RL2 and no other
parameter of RL2 & TM2 Time Setting for Relay 2 (TM2) Press to enter sub menu from main menu
will be prompted. Press or to scroll
Press + or + to change parameter value
<
V
through sub menu
Over voltage ON / OFF DISPLAY DEFAULT
(For 1sec) DESCRIPTION RANGE CONDITION
R2
VALUE
S
V <
V
280 - 520V(Default : 498) This option will be
Set Over [For 3P3W system] prompted only when Trip time delay 0.0 - 99.9s
voltage 160 - 300V(Default : 288) OV option is made ON R2 t
R2
[For 3P4W system]
S

<V
Recovery time 0.0 - 99.9s
Under voltage ON / OFF R2 t off

R2

<V 280 - 520V(Default : 332)


This option will be
Set under [For 3P3W system]
prompted only when UV
voltage 160 - 300V(Default : 192)
R2 option is made ON
[For 3P4W system]

Note : Relay 2 (RL2) Default values shown are applicable when Relay 2 (RL2) selected as Relay 1 (RL1)
Doc. name : OP INST 900VPR-2-280 / 520V OP380-V01(Page 3 of 4)
Hysteresis (HYS) Press to enter sub menu from main menu Press or to scroll
Press + or + to change parameter value
Press or to scroll through main menu
Press + or + to change parameter value DISPLAY DEFAULT
through sub menu DESCRIPTION RANGE CONDITION
(For 1sec) VALUE
DISPLAY DEFAULT
(For 1sec) DESCRIPTION RANGE CONDITION 280 - 520V(Default : 498)
VALUE Set over
<
V
[For 3P3W system]
voltage
V 160 - 300V(Default : 288)
Hysteresis for Relay 1 R1 [For 3P4W system]
for voltage 1.0 - 99.9V
H
Set under <V 280 - 520V(Default : 332)
[For 3P3W system]
voltage
160 - 300V (Default : 192)
Hysteresis for Relay 1 R1 [For 3P4W system]
for frequency 0.2 - 2Hz
H Set over
<
V 280 - 520V(Default : 498)
[For 3P3W system]
voltage
160 - 300V(Default : 288)
AS
for Relay 2 R2 [For 3P4W system]
Hysteresis for
2 - 20%
Asymmetry <V 280 - 520V(Default : 332)
H Set under
[For 3P3W system]
voltage
160 - 300V(Default : 192)
for Relay 2 [For 3P4W system]
Password (PW) Press to enter sub menu from main menu R1 R2

Press or to scroll Trip time delay


S

Press + or + to change parameter value 0.0 - 99.9s


through sub menu for Relay1
R1 t
DISPLAY DEFAULT
(For 1sec) DESCRIPTION RANGE CONDITION
VALUE S

Trip time delay


0.0 - 99.9s
Enable / Disable for Relay2
R2 t
Password ENB / DIS password protection
option YES / NO, (In this option if YES is selected by the user, then whenever
the user enters the Trip Value Setting, initially LOCK option will be
LOCK prompted. The user will have to set NO after which he can access the
Will be prompted only
Set password 000-999 trip setting menu. If the user wants to disable LOCK option, he can set
when Password option
NO when LOCK option is prompted after TR2 option.)
is enabled
NOTE : If Values are changed, the same setting in config menu will also changed and vice versa, also if RL1 is
NOTE : PW option will be asked when the user enter the config. menu if PW option is enabled in the config menu selected for RL2 in config menu no parameter of Relay 2 will be prompted in the above trip value setting.
and the user has to enter the password which he has set in the S.PW (set password) option.
ONLINE KEYS Individual parameters can be viewed with every press of keys.
Factory set (RST) Press to enter sub menu from main menu
PARAMETER SYMBOL
Press or to scroll
Press + or + to change parameter value * Average Voltage L1 L2 L3
through sub menu
DISPLAY Voltage (L1-phase) L1
DEFAULT
(For 1sec) DESCRIPTION RANGE CONDITION
VALUE Voltage (L2-phase) L2
Voltage (L3-phase) L3
Reset
YES / NO Voltage (L1-L2 phase) L1 L2
(Factory set)
Voltage (L2-L3 phase) L2 L3
Voltage (L1-L3 phase) L1 L3 * Default Page : This page is displayed after 3 sec.
from other online page.
TRIP VALUE SETTING Press key for 3 sec. to enter or exit Trip Value Setting menu : Frequency Hz For 3P4W system average of L-N voltages is shown.
Phase Asymmetry As % For 3P3W system average of L-L voltages is shown.
Press or to scroll
Press + or + to change parameter value TRIP INDICATION Trip Indication on press of key : Trip value will be displayed till the key is pressed.
through main menu
DISPLAY DEFAULT Press key for 3sec. to reset manually
DESCRIPTION RANGE CONDITION RESET
(For 1sec) VALUE
This option will Master Password : 753 ( Specifications are subject to change, since development is a
prompted first when the continuous process )
LOCK YES / NO user enters the trip In Trip value setting & configuration menu, if no key
setting menu. User has Selec Controls Pvt. Ltd.
pressed for 30 sec. then unit resumes online mode.
to set NO after which Tel. No. : +91-22-40394200 / 40394202
he can access the trip Fax No. : +91-22-28471733 I Toll free : 1800 227 353
setting menu. Website: www.selec.com I Email : sales@selec.com
Disclaimer : "This product is strictly for industrial use and for sale in non European countries only"

Doc. name : OP INST 900VPR-2-280/520V OP380-V01/d(Page 4 of 4)