Sie sind auf Seite 1von 7

Produced on 03/02/2020 with Xpress Selection V8.6.7 - database DIL 13.8.

Project name airnav tower admin


Project address Indonesia
Reference 1
Client name 12
Revision 21

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description Material cost Install. cost Subtotal
RXQ10TAY14 1 Cooling only VRV IV STD(ID)
FXAQ40AVM4 1 VRV A(AVM4) - Wall Mounted
FXAQ63AVM4 1 VRV A(AVM4) - Wall Mounted
FXFQ63AV4 2 VRV F(AV4) - Ceiling Mounted
Cassette(Round Flow)
FXFQ80AV4 1 VRV F(AV4) - Ceiling Mounted
Cassette(Round Flow)
KHRP26A22T 2 Refnet branch piping kit
KHRP26A33T 2 Refnet branch piping kit
BRC1E63 5 Wired Remote Controller (Navigation Remote
Controller)
BYCQ125EAF 3 Standard panel(Fresh white)
Total cost

2. Indoor Unit Details


2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / RH)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
2.2. Out 1 - RXQ10TAY14
Capacity data at conditions and connection ratio (123%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C BTU/h BTU/h m³/h
Ind 1 (gedung Admin lt 1) FXFQ80AV4 24,0 / 50% 18000 20301 n/a 17729 9,0 n/a n/a n/a 1350
Ind 2 (gedung tower lt 1) FXAQ40AVM4 24,0 / 50% 9000 9566 n/a 8735 9,0 n/a n/a n/a 732
Ind 3 (gedung tower lantai 5) FXAQ63AVM4 24,0 / 50% 14000 15254 n/a 13249 9,0 n/a n/a n/a 1140
Ind 4 ( Gedung Tower lantai 7) FXFQ63AV4 24,0 / 50% 14000 16036 n/a 14904 9,0 n/a n/a n/a 1260
Ind 5 (gedung tower lantai 7) FXFQ63AV4 24,0 / 50% 14000 16036 n/a 14904 9,0 n/a n/a n/a 1260

Required cooling capacity towards the outdoor unit: 69000BTU/h.


All outdoor and indoor unit capacity values are for a VRV system operating with an evaporating temperature of
9,0°C.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Ind 1 (gedung Admin lt 1) 29,5-37 230V 1ph 1 840×256×840 22
Ind 2 (gedung tower lt 1) 33,5-37 220V 1ph 0,7 1050×290×269 15
Ind 3 (gedung tower lantai 5) 38,5-46,5 220V 1ph 0,7 1050×290×269 14
Ind 4 ( Gedung Tower lantai 7) 28-36 240V 1ph 0,6 840×256×840 22
Ind 5 (gedung tower lantai 7) 28-36 240V 1ph 0,6 840×256×840 22

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C BTU/h BTU/h °C BTU/h BTU/h
Out 1 RXQ10TAY14 123 32,0 74175 69000

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
Out 1 RXQ10TAY14 7,5 R410A 6,0 n/a

Name Model PS MCA WxHxD Wght


A mm kg
Out 1 RXQ10TAY14 400V 3ph 22 930×1657×765 195

3.2.1. Out 1 - RXQ10TAY14


Model Qty Description
RXQ10TAY14 1 Cooling only VRV IV STD(ID)
FXAQ40AVM4 1 VRV A(AVM4) - Wall Mounted
FXAQ63AVM4 1 VRV A(AVM4) - Wall Mounted
FXFQ63AV4 2 VRV F(AV4) - Ceiling Mounted Cassette(Round Flow)
FXFQ80AV4 1 VRV F(AV4) - Ceiling Mounted Cassette(Round Flow)
KHRP26A22T 2 Refnet branch piping kit
KHRP26A33T 2 Refnet branch piping kit
BRC1E63 5 Wired Remote Controller (Navigation Remote Controller)
BYCQ125EAF 3 Standard panel(Fresh white)

The capacity for 14.0-15.9CWB are at VRT powerful mode.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

4.1. Piping Out 1


Out 1
RXQ10TAY14

⅜"×⅞" ⅜"×⅝"
KHRP26A33T

Ind 1 (gedung Admin lt 1)


FXFQ80AV4

⅜"×⅞" ¼"×½"
KHRP26A33T

Ind 2 (gedung tow er lt 1)


FXAQ40AVM4

⅜"×¾" ⅜"×⅝"
KHRP26A22T

Ind 3 (gedung tow er lantai 5)


FXAQ63AVM4

⅜"×⅝" ⅜"×⅝"
KHRP26A22T

Ind 4 ( Gedung Tow er lantai 7)


FXFQ63AV4

⅜"×⅝"

Ind 5 (gedung tow er lantai 7)


FXFQ63AV4

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring Out 1


P1,P2
Out 1 Ind 1 (gedung Admin lt 1) BRC1E63
RXQ10TAY14 FXFQ80AV4
IN F1,F2 F1,F2 L,N 1A 1ph
L1,L2,L3,N 22A 3ph
P1,P2
Ind 2 (gedung tow er lt 1) BRC1E63
FXAQ40AVM4
F1,F2 L,N 0,7A 1ph

P1,P2
Ind 3 (gedung tow er lantai 5) BRC1E63
FXAQ63AVM4
F1,F2 L,N 0,7A 1ph

P1,P2
Ind 4 ( Gedung Tow er lantai 7) BRC1E63
FXFQ63AV4
F1,F2 L,N 0,6A 1ph

P1,P2
Ind 5 (gedung tow er lantai 7) BRC1E63
FXFQ63AV4
F1,F2 L,N 0,6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 6
6. Device Options
6.1. Indoor Unit Options
Model Description Used by
BYCQ125EAF Standard panel(Fresh white) Ind 1 (gedung Admin lt 1) [FXFQ80AV4] Ind 4 ( Gedung Tower lantai 7) [FXFQ63AV4] Ind 5 (gedung to

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 7