INSTALLER
MANUAL
WATER PURIFICATION
Installer Manual 255-LOGIX 740-760 - Table of content
Table of content
1. Generalities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1. Scope of the documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2. Release management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3. Manufacturer identifier, product . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4. Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5. Abbreviations used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.6. Norms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.6.1. Applicable norms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.6.2. Available certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.7. Procedure for technical support . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.8. Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.9. Limitation of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.10. Scan & Service application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2. Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1. Safety pictograms definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2. Serial and safety tags location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3. Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.1. Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.2. Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4. Hygiene and sanitization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4.1. Sanitary issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4.2. Hygiene measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1. Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.1. Performance flow rate characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2. Outline drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3. Description and components location . . . . . . . . . . . . . . . . . . . . . . . 16
3.4. System regeneration cycle (8-cycles operation) . . . . . . . . . . . . . . . 17
4. System sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1. Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1.1. Injector/DLFC/Refill flow controler-Valve configuration . . . . . . . . . . . 19
4.2. Cycle time calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3. Injector flow rates (tables) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.4. Salt amount definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.1. Safety notices for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.2. Installation environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.2.1. General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.2.2. Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.2.3. Mechanical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.2.4. Outdoor Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.3. Integration constraints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.4. Block diagram and configuration example . . . . . . . . . . . . . . . . . . 26
5.5. Valve connection to piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.5.1. Top-mounted valve installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.6. Connections (electrical) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.7. Bypassing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.8. Drain line connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.9. Overflow line connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.10. Brine line connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6. Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.1. Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.2. Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.3. Basic programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.3.1. Basic programming mode chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.3.2. Program system size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.3.3. Time setting and winter time - summer time change . . . . . . . . . . . . . 37
6.3.4. Day of week . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.3.5. Regeneration time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.3.6. Days to regenerate (740 time-clock controller only) . . . . . . . . . . . . . . 38
6.3.7. Calendar override (760 on-demand controller only) . . . . . . . . . . . . . . 39
6.3.8. Amount of brine used per regeneration . . . . . . . . . . . . . . . . . . . . . . . . 39
6.3.9. Estimated capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.3.10. Hardness (760 on-demand controller only) . . . . . . . . . . . . . . . . . . . . . 40
6.4. Advanced programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.4.1. Master setting reference chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.4.2. Cycle time programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.4.3. Diagnostic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.4.4. Resetting the controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
7. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
7.1. Water filling, draining and waterproofness inspection . . . . . . . . . 45
7.1.1. Activating the softener . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
7.1.2. Additional tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.2. Sanitization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.2.1. Disinfection of water softeners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.2.2. Sodium or calcium hypochlorite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.2.3. Electro chlorination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
8. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8.1. Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8.2. Manual regeneration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8.3. To advance regeneration cycles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
8.4. To cancel a regeneration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
9. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.1. General system inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.1.1. Water quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.1.2. Mechanical Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.1.3. Regeneration test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
9.2. Recommended maintenance plan . . . . . . . . . . . . . . . . . . . . . . . . . . 52
9.3. Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
9.3.1. Use original spare parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
9.3.2. Use original approved lubricants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
9.3.3. Maintenance instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
9.4. Cleaning and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
9.4.1. First steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
9.4.2. Injector cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
9.4.3. Refill controller cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
9.4.4. Injector screen cap cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
9.4.5. Backwash controller cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
9.4.6. Air check valve cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
9.4.7. Valve from tank disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
9.4.8. Motor and camshaft replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
9.4.9. Optical sensor and controller replacement . . . . . . . . . . . . . . . . . . . . . . 60
9.4.10. Top plate and disc valve replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . 61
9.4.11. Valve on tank assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
10. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
12. Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
1. Generalities
1.1. Scope of the documentation
The documentation provides the necessary information for appropriate use of the product. It informs
the user to ensure efficient execution of the installation, operation or maintenance procedures.
The content of this document is based on the information available at the time of publication. The
original version of the document was written in English.
For safety and environmental protection reasons, the safety instructions given in this documentation
must be strictly followed.
This manual is a reference and will not include every system installation situation. The person
installing this equipment should have:
• training in the 700 Logix series controllers and water softener installation;
• knowledge of water conditioning and how to determine proper controller settings;
• basic plumbing skills.
This document is available in other languages on https://www.pentairaquaeurope.com/product-
finder/product-type/control-valves.
1.6. Norms
1.6.1. Applicable norms
Comply with the following guidelines:
• 2006/42/EC: Machinery Directive;
• 2014/35/UE: Low Voltage Directive;
• 2014/30/UE: Electromagnetic compatibility;
• 2011/65/EC: Restriction of use of certain hazardous substances in electrical and electronic
equipment (RoHS).
• UNI EN ISO9001.
1.8. Copyright
© 2019 Pentair International Sàrl All rights reserved.
Any warranty provided by Pentair regarding the product will become invalid in case of:
• improper installation, improper programming, improper use, improper operation and/or
maintenance leading to any kind of product damages;
• improper or unauthorized intervention on the controller or components;
• incorrect, improper or wrong connection/assembly of systems or products with this product and
vice versa;
• use of a non-compatible lubricant, grease or chemicals of any type and not listed by the
manufacturer as compatible for the product;
• failure due to wrong configuration and/or sizing.
Pentair accepts no liability for equipment installed by the user upstream or downstream of Pentair
products, as well as for process/production processes which are installed and connected around or
even related to the installation. Disturbances, failures, direct or indirect damages that are caused by
such equipment or processes are also excluded from the warranty. Pentair shall not accept any
liability for any loss or damage of profits, revenues, use, production, or contracts, or for any indirect,
special or consequential loss or damage whatsoever. Please refer to the Pentair List Price to know
more about terms and conditions applicable to this product.
No. Operation
2. Safety
2.1. Safety pictograms definition
Caution Warning
Warns of a risk of minor injury or major Warns against serious personal injury
material damage to the device or and damage to health.
environment.
Danger Mandatory
Warns against serious personal injury or Standard or measure to apply.
death.
Note Prohibition
Comment. Restriction to be observed.
Part number
Electrical rating
Production date
Production order
Serial number
Note
Ensure that the serial label and the safety tags on the device are completely legible and
clean. If necessary, replace them with new tags and put them in the same places.
2.3. Hazards
All the safety and protection instructions contained in this document must be observed in order to
avoid temporary or permanent injury, damage to property or environmental pollution.
At the same time, any other legal regulations, accident prevention and environmental protection
measures, as well as any recognized technical regulations relating to appropriate and risk-free
methods of working which apply in the country and place of use of the device must be adhered to.
Any non-observation of the safety and protection rules, as well as any existing legal and technical
regulations, will result in a risk of temporary or permanent injury, damage to property or
environmental pollution.
2.3.1. Personnel
Caution
Only qualified and professional personnel, based on their training, experience and
instruction as well as their knowledge of the regulations, the safety rules and operations
performed, are authorized to carry out necessary work.
2.3.2. Material
The following points must be observed to ensure proper operation of the system and the safety of
user:
• do not remove the locking bar;
• be careful of high voltages present on the transformer (230V);
• do not put your fingers in the system (risk of injuries with moving parts and shock due to electric
voltage).
Assembly
• Assemble only with components which are in accordance with DM 174 and ACS;
• after installation and before use, perform one or more manual regenerations in order to clean
the media bed. During such operations, do not use the water for human consumption. Perform a
disinfection of the system in the case of installations for treatment of drinking water for human
use.
Note
This operation must be repeated in the case of ordinary and extraordinary maintenance. It
should also be repeated whenever the system remains idle for a significant time.
Note
Valid only for Italy: In case of equipment used in accordance with the DM25, apply all the
signs and obligations arising from the DM25.
3. Description
3.1. Technical specifications
Design specifications/ratings
Valve body ......................................................................... Glass-filled Noryl® - NSF listed material
Rubber components ......................................................... Compounded for cold water - NSF listed
material
Valve material certification .............................................. WQA Gold Seal Certified to ORD 0902, NSF/
ANSI 44, CE, ACS
Weight (valve with controller)........................................... 1.8 kg
Recommended operating pressure ................................. 1.4 - 8.6 bar
Hydrostatic test pressure................................................. 20.69 bar
Water temperature ........................................................... 1 - 38°C
Ambient temperature ....................................................... 2 - 50°C
Valve connections
Tank Adapter Thread ........................................................ 63.5 mm (2½") - 8, male
Inlet/Outlet Maniflold ....................................................... 25.4 mm (1") NPT or BSPT, female (brass or
thermoplastic) 19 mm (¾") NPT or BSPT,
male (thermoplastic) 2.7 (½") NPT or BSPT,
male (thermoplastic)
Drain line 12.7 mm (½") (manifold
dependent)
Brine line .......................................................................... 9.5 mm (⅜") NPT as standard, 6.35 mm (¼")
NPT optional; air check built onto valve
Riser tube [Ø].................................................................... 27 mm (1.050") standard, or 20.6 mm
(0.8125") optional with extra insert
Riser tube [length]............................................................ 29 mm ± 3 mm (1⅛ ± ⅛") above top of tank
Electrical
Controller Operating Voltage ........................................... 12 VAC (requires use of Pentair Water
supplied transformer)
Input Supply Frequency.................................................... 50 or 60 Hz (controller configuration
dependent)
Motor Input Voltage .......................................................... 12 VAC
Controller Power Consumption ....................................... 3 W average
Protection rating............................................................... IP23
Service
Flow rate (m3/h)
Backwash
Manifold
connection
LCD display
BLFC / Refill
controller
Brine tank tube
Check ball connection
Air check
UP button
SET button
DOWN button
Valve discs
Camshaft
Motor
Outlet
Injector screen
Locking bar
Drain
Inlet
Manifold
Backwash flow drain controller
Note
For illustration purpose only. Always verify inlet and outlet marking on the valve.
SERVICE BACKWASH
C0 C1 and C6
Inlet Outlet Inlet Outlet
Drain
Valve Valve
Drain
Valve Valve
From brine
tank
Drain
Valve Valve
To brine
Tank
4. System sizing
4.1. Recommendations
4.1.1. Injector/DLFC/Refill flow controler-Valve configuration
Backwash flow
Vessel diameter Media volume Injector Flow Refill flow control
control
[In] [L] control [gpm]
[gpm]
6 5/10 E [yellow] 0.33 0.9
7 15 F [peach] 0.33 1.2
8 20 G [tan] 0.33 1.6
9 30 H [lt purple] 0.33 2.0
10 35 J [lt blue] 0.33 2.5
12 40 K [pink] 0.33 3.5
13 50 L [orange] 0.33 4.1
14 80 L [orange] 0.33 4.8
5. Installation
5.1. Safety notices for installation
• Observe all warnings that appear in this manual;
• only qualified and professional personnel are authorized to carry out installation work.
5.2.2. Electrical
There are no user-serviceable parts in the AC transformer, motor, or controller. In the event of a
failure, these should be replaced.
• All electrical connections must be completed according to local codes;
• use only the power AC transformer that is supplied;
Mandatory
The use of any other power transformer than the one supplied void the warranty of all
electronic parts of the valve.
5.2.3. Mechanical
• Do not use petroleum-based lubricants such as vaseline, oils, or hydrocarbon-based lubricants.
Use only 100% silicone lubricants;
• all plastic connections should be hand tightened. PTFE (plumber’s tape) may be used on
connections that do not use an O-ring seal. Do not use pliers or pipe wrenches;
• all plumbing must be completed according to local codes;
• soldering near the drain line should be done before connecting the drain line to the valve.
Excessive heat will cause interior damage to the valve;
• If the backwash flow rate exceeds 22.7 lpm or if the unit is located 6.1-12.2 m from the drain, use
19 mm (3/4") tubing. Use appropriate fittings to connect the 19 mm (3/4") tubing to the 19 mm
(3/4") NPT drain connection on the valve;
• do not use lead-based solder for sweat solder connections;
• the drain line must be a minimum of 12.7 mm (½") in diameter. Use 19 mm (¾") pipe if the
backwash flow rate is greater than 26.5 lpm or the pipe length is greater than 6 m;
• do not support the weight of the system on the control valve fittings, plumbing, or the bypass;
• it is not recommended to use sealants on the threads. Use PTFE (plumber’s tape) on the threads
of the 25.4 mm (1") NPT elbow, the drain line connections, and other NPT/BSP threads.
User’s line
Meter
Suggested options
Mixing device
Can be integrated in the Drain line
valve
Brine line
Valve
Drain
Configuration example
MS-4564PO
1009116
AV140
MS-506PO
MS-R13460
AV090
Note
See chapter 3.3. Description and components location, page 16 to identify the connections.
200 mm flexible
• The diagrams above illustrate how the flexible piping connection should be mounted;
• in order to adequately compensate the tank elongation the flexible tubes must be installed
horizontally;
• should the flexible piping connection be installed in vertical position, instead of compensating
the elongation, it will create additional stresses on the valve & tank assembly. Therefore this is
to be avoided;
• the flexible piping connection must be also be installed stretched, avoiding excessive length. For
instance 20 - 40 cm is enough;
• excessively long and non-stretched flexible piping connection will create stresses on the valve
and tank assembly when the system is pressurized, as illustrated in the below picture: on the left
the assembly when the system is unpressurised, on the right the flexible piping connection when
put under pressure tends to lift up the valve when stretching up. This configuration is even more
dramatic when using semi-flexible piping;
• failure to provide enough vertical compensation may lead to different kinds of damage, either on
the valve thread which connects to the tank, or on the female thread connection of the tank that
connects to the valve. In some cases, damage may also be seen on the valve inlet and outlet
connections;
• in any case, any failure caused by improper installation and/or piping connections may void the
warranty of Pentair products;
• in the same way, using lubricant* on the valve thread is not allowed and will void the warranty for
the valve and tank. Indeed using lubricant there will cause the valve to be over-torqued, which
may lead to valve thread or tank thread damage even if the connection to piping has been done
following the above procedure.
*Note: Use of petroleum-based grease and mineral based lubricant is totally forbidden, not only on the valve thread, since
plastics (especially Noryl) will highly suffer from contact with this type of grease, leading into structural damage hence to
potential failures.
5.7. Bypassing
A bypass valve system should be installed on all water conditioning systems. Bypass valves isolate the
softener from the water system and allow unconditioned water to be used. Service or routine
maintenance procedures may also require that the system is bypassed.
In Out In Out
Caution
Do not solder pipes with lead-based solder.
Caution
Do not use tools to tighten plastic fittings. Over time, stress may break the connections.
When the 256 bypass valve is used, only hand tighten the plastic nuts.
Caution
Do not use petroleum grease on gaskets when connecting bypass plumbing. Use only 100%
silicone grease products when installing any plastic valve. Non-silicone grease may cause
plastic components to fail over time.
Note
Standard commercial practices are expressed here. Local codes may require changes to
the following suggestions. Check with local authorities before installing a system.
The unit should not be more than 6.1 m from the drain. Use an appropriate adapter fitting to connect
12.7 mm plastic tubing to the drain line connection of the control valve.
If the backwash flow rate exceeds 22.7 lpm or if the unit is located 6.1-12.2 m from the drain, use
19 mm (3/4") tubing. Use appropriate fittings to connect the 19 mm (3/4") tubing to the 19 mm (3/4")
NPT drain connection on the valve.
The drain line may be elevated up to 1.8 m providing the run does not exceed 4.6 m and water pressure
at the softener is not less than 2.76 bar. Elevation can increase by 61 cm for each additional 0.69 bar
of water pressure at the drain connector.
Where the drain line is elevated but empties into a drain below the level of the valve, form a 18 cm loop
at the far end of the line so that the bottom of the loop is level with the drain line connection. This will
provide an adequate siphon trap.
Where the drain empties into an overhead sewer line, a sink-type trap must be used.
Secure the end of the drain line to prevent it from moving.
Note
Waste connections or the drain outlet shall be designed and constructed to provide
connection to the sanitary waste system through an air-gap of 2 pipe diameters or 25.4 mm
(1"), whichever is larger.
Caution
Never insert the drain line directly into a drain, sewer line or trap. Always allow an air gap
between the drain line and the wastewater to prevent the possibility of sewage being back-
siphoned into the softener.
Air gap
Drain
Overflow fitting
Drain tubing
Air gap
Drain
Caution
Floor drain is always recommended to avoid flooding in case of overflow.
6. Programming
6.1. Display
1. Hourglass Displayed when the motor is running. The camshaft should be turning.
2. Cursor These cursors appear next to the item that is currently displayed.
3. Days of the week Displayed days of the week. The flag below the day appears when that
day has been programmed as a day the system should regenerate
(used with 7-day timer programming, 740 only).
4. Locked/unlocked This symbol is displayed in basic programming when the current
indicator parameter is locked-out.
It is also used in advanced programming to indicate if the displayed
parameter is locked when the controller is in basic programming (the
icon flashes).
5. Colon Colon flashes as part of the time display.
It also indicates normal operation (740 only).
6. Days between
Days between regeneration programming / day override setting.
regenerations
7. Cursor This cursor is displayed when the days between regeneration / day
override are being programmed.
8. Cursor One of these cursor is displayed to indicate which day is programmed
into the controller.
9. "PM" Indicates that the time displayed is between 12:00 noon and 12:00
midnight (there is no AM indicator).
"PM" indicator is not used if the clock mode is set to 24-hour.
10. "MIN" Indicates that the value entered/displayed is in minute increments.
11. "g/L" Indicates that the value entered/displayed for salt amount is in grams/
Liter of resin.
12. "KG" Indicates that the value entered/displayed is in kilograms or kilograins.
13. "x100" x100 multiplier for large values.
14. "Lbs/ft3" Indicates that the value entered/displayed for salt amount is in pounds
per cubic foot.
15. Faucet Appears when the current flow rate is displayed.
The controller may show the faucet and "0", indicating no flow.
16. Maintenance interval Displayed when the months in service exceed the value programmed in
parameter P11.
17. Digits Four digits used to display the time, flow rate, volume capacity,
program value or error codes.
18. Number Used with #19, #20 and #21.
Displays a sequence numbers or values.
19. History values (H) The number displayed by #18 identifies which history value is currently
displayed.
20. Parameter (P) Displayed only in advanced programming.
The number displayed by #18 identifies which parameter is currently
displayed.
21. Cycle (C) The number displayed by #18 is the current cycle in the regeneration
sequence.
22. Hardness Hardness setting - only used with 760 controller for 8-cycles softening
system.
23. Capacity Shows estimated system capacity.
24. "x2" Indicates a second regeneration has been called for.
25. Regeneration sign Flashes when a regeneration at the next time of regeneration has been
called for.
Also displayed (continuously) when in regeneration.
26. Salt Salt amount for each regeneration setting.
If the controller is on a 3-cycles filter then the backwash time is
displayed.
27. Regeneration time Time of regeneration and days of regeneration setting.
Days of regeneration setting is only available on 740 controller.
28. Time and day Current time and day setting.
6.2. Commands
Note
Menus are displayed in a defined and incremental order.
Note
The system capacity is displayed in kilograms equivalent CaCO3 of hardness removed
before a regeneration is necessary.
Note
Value is derived from the system’s resin volume input and salt amount input.
Note
The capacity is displayed for information purposes on the 740 controller. It cannot be
changed.
Note
If using the 740 controller, programming is complete. The controller will return you to the
normal operation mode.
Note
Press and hold + for 5 seconds to access advance programming. A "P" symbol is
displayed on the bottom left of screen.
The 740/760 features an advanced programming level that allows the installing dealer to make
changes to the controller for more demanding applications. The homeowner/end user should never
have to access this level.
* Calculated by software.
** Pre-selected by World model (i.e. 230 Vac, 50 Hz, metrics unit).
* Calculated depending on salt setting and resin volume. The capacity may be manually adjusted.
** Factory default value is "0" for North America Made and "1" for European Made.
Note
See chapter 3.4. System regeneration cycle (8-cycles operation), page 17 for more
information about cycles.
6.4.3. Diagnostic
To access diagnostic values, press and hold and for 5 seconds to view the "H" levels.
Diagnostic
Description Unit Range
Code
H0 Resin volume l /
H1 Day since last regeneration l/min 0 - 255
H2 Current flow rate day 0 - 177
H3 Water used today (since time of regeneration) l/min 0 - 6553.6
H4 Water used since last regeneration m3 0 - 6553.6
H5 Total water used (less significant digit) 3 0 - 9999
m
H6 Total water used (most significant digit) m3 0 - 4264 x104
H7 Average usage for Sunday m3 0 - 6553.6
H8 Average usage for Monday m3 0 - 6553.6
H9 Average usage for Tuesday 3 0 - 6553.6
m
H10 Average usage for Wednesday m3 0 - 6553.6
H11 Average usage for Thursday m3 0 - 6553.6
H12 Average usage for Friday m3 0 - 6553.6
H13 Average usage for Saturday 3 0 - 6553.6
m
Note
Diagnostic code H2 to H13 are only available on 760 controller.
Caution
Resetting the controller will delete all information stored in its memory, except the time and
day. This will require you to reprogram the controller completely from the initial power-up
mode.
7. Commissioning
Note
This chapter is available for standard regeneration types. Contact your supplier if the actual
regeneration is not standard and if you need assistance.
Caution
Do not rotate the camshaft by hand or damage to the unit may occur. Use the controller to
take the camshaft electronically through the cycles.
Caution
If opened too rapidly or too far, media may be lost out of the tank into the valve or the
plumbing. In the ¼ open position, you should hear air slowly escaping from the valve drain
line.
→ When all of the air has been purged from the media tank (water begins to flow steadily from
the drain line), open the main supply valve all of the way. This will purge the final air from the
tank.
→ Allow water to drain out until the water runs clear from the drain line. This purges any refuse
from the media bed.
→ Turn off the water supply and let the system stand for about 5 minutes. This will allow any
trapped air to escape from the tank.
Note
We recommend that you do not put salt into the tank before the control valve has been
started up. With no salt in the tank, it is much easier to view water flow and motion.
6. Engage the refill cycle to prime the line between the brine tank and the valve (softener only).
→ Slowly open the main water supply valve again, to the fully open position. Be sure not to open
too rapidly as that would push the media out of the media tank.
→ Advance the controller to the Refill (C8) position. From cycle C1 (Backwash), press and hold
. This will display the current cycle.
While pressing , press to advance to the next cycle. Continue to advance through
each cycle until you have reached cycle C8 (Refill).
Note
As you advance through each cycle there will be a slight delay before you can advance to the
next cycle. The hourglass icon will be lit while the camshaft is indexing. There may be a
pause at cycle C4 (System Pause). This cycle allows the water/air pressure to equalize on
each side of the valve discs before moving on. The hourglass will not be visible indicating
that the system is paused.
→ With the water supply completely open, when the valve reaches C8 (Refill), the controller will
direct water down through the line to the brine tank. Let the water flow through the line until
all air bubbles have been purged from the line.
→ Do not let the water flow down the line to the tank for more than 1 to 2 minutes, or the tank
may overfill.
→ Once the air is purged from the line, press and simultaneously to advance to cycle C0
(Treated Water) position.
7. Draw water from the brine tank.
→ From the treated water position (cycle C0), advance the valve to the draw brine position. Press
for 5 seconds.
The controller will begin a manual regen, and advance the control valve to the cycle C1
(Backwash). Press and to advance to cycle C2 (Draw).
→ With the controller in this position, check to see that the water in the brine tank is being drawn
out of the tank. The water level in the tank should recede very slowly.
→ Observe the water being drawn from the brine tank for at least 3 minutes. If the water level
does not recede, or goes up, check all hose connections. C2 should be displayed.
8. If the water level is receding from the brine tank you can then advance the controller back to the
treated water (C0) position by pressing and simultaneously to advance the controller to
the C0 position.
9. Finally, turn on a faucet plumbed after the water softener. Run the faucet until the water runs
clear. Add salt to the brine tank.
7.2. Sanitization
7.2.1. Disinfection of water softeners
The construction materials of the modern water softener will not support bacterial growth, nor will
these materials contaminate a water supply. During normal use, a softener may become fouled with
organic matter, or in some cases with bacteria from the water supply. This may result in an off-taste
or odour in the water.
Some softeners may need to be disinfected after installation and some softeners will require periodic
disinfection during their normal lifetime.
Depending on the conditions of use, the softener type, the type of ion exchanger, and the disinfectant
available, a choice can be made among the following methods.
Dosage
Polystyrene resin: set 1.25 mL fluid per 1 L of resin.
Non-resinous exchangers: set 0.85 mL fluid per 1 L.
Calcium hypochlorite
Calcium hypochlorite, 70% available chlorine, is available in several forms including tablets and
granules. These solid materials may be used directly without dissolving before use.
Dosage
Measure two grains ~ 0.11 mL 1 L.
8. Operation
During a regeneration:
• A "C#" is displayed to show the current cycle;
• total regen time remaining is displayed on screen;
• you can press and hold to show current cycle time remaining.
8.1. Recommendations
• Use only regeneration salts designed for water softening EN973;
• for optimal system operation, the use of clean salt and impurities free is recommended (for
example salt pellets);
• do not use ice melt salt, block, or rock salts;
• the sanitizing process (both with liquid and electrochlorination) may introduce chlorine
compounds which may reduce the lifetime of the ion exchange resins. Refer to media
manufacturer specifications sheet for more information.
Mandatory
The controller must be in service in order to enable this procedure.
Note
The unit returns to normal operation if no buttons are pressed within 30 seconds.
Note
To cancel: press again. The regen symbol disappears.
Immediate regeneration
A Press and hold for 5 seconds to initiate immediate manual regeneration.
→ A solid regeneration icon will be displayed.
→ Camshaft starts rotating to cycle C1.
Double regeneration
A After an immediate regeneration has begun, press again to plan a second manual
regeneration.
→ A flashing "x2" symbol indicates the second regeneration will start at the programmed
delayed regeneration time.
9. Maintenance
Mandatory
Cleaning and maintenance shall take place at regular intervals in order to guarantee the
proper functioning of the complete system, and be documented in the Maintenance chapter
in the User Guide document.
Mandatory
The maintenance and service operation must be done by qualified personnel only. Failure in
respecting this may void the warranty.
Mandatory
Has to be done once a year at minimum.
* Electronic parts – durability strongly affected by power source quality and stability.
** Elastomer durability is strongly affected by raw water concentration in chlorine and its derivatives.
*** 255 being already equipped with an aircheck, the safety brine valve should not be equipped with an aircheck too otherwise
this may create hydraulic interferences and cause brine draw malfunction due to safety brine valve aircheck not opening.
**** Wear part.
9.3. Recommendations
9.3.1. Use original spare parts
Caution
To ensure correct operation and safety of the device, only use original spare parts and
accessories recommended by the manufacturer.
Parts to keep in stock for potential replacements are motor and optical sensor, controller,
transformer, injectors, flapper kit, O-ring kit, refill and DLFC.
No. Operation
Tip
Depending on the maintenance required, it may be useful to disassemble the valve from the
tank in order to have easier access.
A Unlock the cover (1) from the slide clips (2) (one on each side of the valve).
B Lift the cover (1).
Using a Phillips screwdriver unscrew the screw (7) from the locking bar (6), so that the
C
locking bar (6) can be slid out of its position.
You can now lift the top of the valve body (3) from the tank adapter (5), so as to perform all
D required maintenance operations with the upper valve body (3) part on a workbench.
Take care with the seals (4) on the valve body bosses.
¼ turn
10. Troubleshooting
Assembly
Item Part number Description
quantity
1 1244650 255 valve assembly, without flow controls 1
2 1033784 255 tank adapter new style 1
3 1010154 O-ring EP 1
4 1232370 O-ring EP 1
5 1235340 Top plate, 255 valve, 700/860 series controller 1
6 1235341 Spring, one-piece, 255 valve 1
7 1236246 Cover,valve, 255/Performa, 700/860 1
* 1267672 Slim line cover 255 700/800 1
8 1001404 O-ring group: tank adapter 4
9 1040459 O-ring group: piping boss 1
10 1001986 13/16" rubber insert (optional) 1
* 1000250 Valve disk kit - standard/sev 1
* 1239760 Blending valve kit 900/700 series top plate 1
11 - Locking bar 1
* 1031402 Multilingual locking bar 1
* 1234170 Locking bar screw no. 8-9/16" 1
12 - Camshaft options 1
* 1235353 Cam 255/700-860 series valve, STD, black 1
13 1238861 Motor + cable 700 series controller 1
14 1000226 Screen/cap assembly with o-ring 1
15 - Injector (high efficiency) options 1
* 1035730 “E” Inj (high efficiency) - yellow (6" diameter vessels) 1
* 1035731 “F” Injector (high efficiency) - peach (7" diameter vessels) 1
* 1035732 “G” Inj (high efficiency) - tan (8" diameter vessels) 1
* 1035733 “H” Inj (high efficiency) - lt purple (9" diameter vessels) 1
* 1035734 “J” Inj (high efficiency) - lt blue (10" diameter vessels) 1
* 1035735 “K” Inj (high efficiency) - pink (12" diameter vessels) 1
* 1035736 “L” Inj (high efficiency) - orange (13-14" diameter vessels) 1
16 1000269 Injector cap with o-ring 1
Assembly
Item Part number Description
quantity
17 - Drain control assembly with o-ring 1
* 1000208 N°6 1
* 1000209 No.7 (1.2 gpm; 4.5 Lpm) 1
* 1000210 No.8 (1.6 gpm; 6.1 Lpm) 1
* 1000211 No.9 (2.0 gpm; 7.6 Lpm) 1
* 1000212 No.10 (2.5 gpm; 9.5 Lpm) 1
* 1000213 No.12 (3.5 gpm; 13.2 Lpm) 1
* 1000214 No.13 (4.1 gpm; 15.5 Lpm) no ball 1
* 1000215 No.14 (4.8 gpm; 18.2 Lpm) no ball 1
18A 1243510 Brine refill controller,.33 gpm, no ball 1
19 - Air check kit 1
* 1032416 Air check kit 3/8" male 1
* 1032417 Air check kit 1/4" male (Std) 1
20 1235373 Module, sensor, photo interrupter 1
Motor with spacer pinion, cable, 700 series controller, 12V, 50/
21 1238861 1
60 Hz
* 3029962 Motor locking pin (white) 1
22 1030502 Ball, flow control internal up to no.12 inclusive 1
* 1033066 New to old style air check adapter 1
* 1244336 Chlorine generator kit, 0.33 gpm 1
* 1266065 Cord, long, chlorine generator 1
Extension cord 50 cm for cabinets (motor, opt. sens., turbine
* 1242411 1
wires)
* 1235446 Turbine cable, Logix, short 1
* 1239711 Switch kit, front mount, 0.1 amp 1
* 1239752 Switch kit, front mount, 5 amp 1
* 1239753 Switch kit, top plate mount, 0.1 amp 1
* Not shown
Assembly
Item Part number Description
quantity
1 - Electronics modules/controllers 1
Logix 740 controller - picto diode/picto without diode/picto
* 1242147 1
filter
Logix 760 controller - picto diode/picto without diode/picto
* 1242165 1
filter
2 - Transformer 1
* 1000813 British 1
* 1000814 European 1
* 1030234 Transformer extension cord 4.5 m (15 ft) 1
* Not shown
Meter adapter
Assembly
Item Part number Description
quantity
1 1032350 Meter adapter kit 1
2 1040524 Piping boss/meter install kit 1
* 1234259 Male plastic piping boss 1" BSP + int. turbine 1
* 1234260 Male plastic piping boss 3/4" BSP + int. turbine 1
* Not shown
Assembly
Item Part number Description
quantity
1 3023761 Piping boss 3/4" BSPT stainless steel 3/8" BSPT drain 1
* 3023747 Piping boss 1" BSPT stainless steel 1/2" BSPT drain 1
* 1040283 Piping boss 3/4" BSPT Noryl 1/2" BSPT drain 1
2 1040524 Piping boss/meter install kit 1
* 3028275 3/8" drain elbow for manifold 1
* E01220 3/8" drain connector 1
* 3028272 1/2" drain elbow for manifold 1
* 1036988 1/2" drain connector for manifold 1
* 1234255 Male plastic piping boss 1" BSP 1
* 1234256 Male plastic piping boss 3/4" BSP 1
* Not shown
Assembly
Item Part number Description
quantity
1 1040769 Bypass body assy (includes bypass installation kit) 1
2 1040524 Bypass installation kit 1
* 1034302 Bypass repair kit (rotor seals & clips) 1
* 3028264 Drain elbow for bypass 256 1
* 3023824 3/4" BSPT stainless steel pipe adapter kit 1
* 3023807 1" BSPT stainless steel pipe adapter kit 1
* 1001608 22 mm copper tube adapter kit 1
* 1001615 32 mm PVC tube adapter kit 1
* 1001614 1" PVC tube adapter kit 1
* 1001613 3/4" PVC tube adapter kit 1
* 1030541 Gasket for 1" pipe or tube 4
* 1034385 Adapter nut 1-1 1/4" bakelite 4
* 1030540 Plumbing adapter 3/4" copper tube 1
* 1030545 Plumbing adapter 1" copper tube 1
* 3014557 Plumbing adapter for 1" NPT stainless steel 1
* 3013737 Plumbing adapter for 3/4" BSPT stainless steel (replaces 1
* 1030574 Plumbing adapter for 22 mm copper tube 1
* 1030578 Plumbing adapter for 3/4" CPVC pipe 1
* 1030579 Plumbing adapter for 1" CPVC pipe 1
* 1000982 Plumbing adapter for 3/4" BSPT plastic male thread 1
* 1001422 Plumbing adapter for 1" BSPT plastic male thread 1
* Not shown
Part Assembly
Item Description
number quantity
Kit-255/1 3029815 Comprises MS-4564PO; CC-D1203; MS-RI3460; AV090 1
MS-
E01240 Air check elbow (CA40) 1/4" FNPT- 3/8" T 1
4564PO
* 1009116 Upper screen 1
MS-
3028263 Riser tube 1.050" 1
RI3460
AV090 3028267 Brine tube 3/8" with screen 1
MS-
E01140 Union elbow 3/8" T - 3/8" T 1
506PO
AV140 E01480 Tubing 3/8" roll of 30 m 1
* 3029860 Kit mounting 255-1" 35" L without tubing 1
* Not shown
12. Disposal
The device must be scrapped in accordance with directive 2012/19/EU or the environmental standards
in force in the country of installation. The components included in the system must be separated and
recycled in a waste recycling center that conforms with the legislation in force in the country of
installation. This will help to reduce the impact on the environment, health, safety and help to promote
recycling. Pentair does not collect used product for recycling. Contact your local recycling center for
more information.