Beruflich Dokumente
Kultur Dokumente
Subject Use of alarm terminals by customer for positive communication of any BBU
system faults.
Background 1. Local indicating lights are provided on the front of each BBU, to aid in
isolation and correction of any system fault by the serviceman. These
lights are summarized as follows:
, 2. Additionally, five sets of terminals are provided on the front of each BBU,
to permit alerting operating personnel of specific BBU system alarm
conditions. Three terminals are furnished for each set of Form C alarm
contacts (N.O., N.C. & COM), with contact closures indicated for the
deenergized (alarm) condition. Alarm terminals furnished are:
Customer Risk Unless the customer connects the alarm terminals to annunciating devices,
any system fault which might develop may remain undetected until: (a)
maintenance personnel discover the abnormal condition by opening cabinet
containing the BBU; or (b) a power emergency occurs, and BBU can not
functionally respond as intended. With this time lapse, serious damage to
batteries or other portions of the BBU system may occur, further extending
the vulnerability of the "protected" TDC operating system.
Examples:
1. If the AC remote sense line to the battery charger opens up for any
reason, the output of the charger can be elevated to approximately 50
Vdc, and the charger will output at its higher current of 2 to 3 amps.
Without wired alarm contacts, the fault will go unnoticed and the batteries
will be overcharged until they are destroyed.
2. If the output of the battery charger drops to 0 Vdc, the batteries will start
to discharge from their "ready" state. Without wired alarms, the batteries
will fully discharge over a period of time, thereby defeating the functional
purpose of the BBU.
With wired alarm contacts, the "Charger Failure" alarm will detect and
report the charger output voltage loss, (and the "Low Battery" alarm
would report the subsequent droop in series battery voltage).