Beruflich Dokumente
Kultur Dokumente
HKIE Transactions
Publication details, including instructions for authors and subscription information:
http://www.tandfonline.com/loi/thie20
A Study on the Energy Saving of Converting a VAV System from Inlet Guide Vane to Variable Fan Speed Control
a b a
K F Yee BEng(Hons) CEng MCIBSE MIEE MinstE MHKIE REW(CO, HO) RSO RSA , Francis W H Yik BSc MSc PhD CEng FCIBSE MIMechE MHKIE , Cary W H Chan MBA CEng MCIBSE MHKIE & Himson Y T Chan MSc BSc CEng R.P.E.
a
MIMechE MHKIE
a
Swire Properties Management Ltd
b
Department of Building Services Engineering , Hong Kong Polytechnic University
Published online: 09 Apr 2013.
To cite this article: K F Yee BEng(Hons) CEng MCIBSE MIEE MinstE MHKIE REW(CO, HO) RSO RSA , Francis W H Yik BSc MSc PhD CEng FCIBSE MIMechE MHKIE , Cary W H Chan MBA CEng MCIBSE MHKIE & Himson Y T Chan MSc BSc CEng R.P.E. MIMechE MHKIE (2002) A
Study on the Energy Saving of Converting a VAV System from Inlet Guide Vane to Variable Fan Speed Control, HKIE Transactions, 9:2, 18-24
Taylor & Francis makes every effort to ensure the accuracy of all the information (the “Content”) contained in the publications on our platform. However, Taylor & Francis, our agents, and our licensors make no representations or
warranties whatsoever as to the accuracy, completeness, or suitability for any purpose of the Content. Any opinions and views expressed in this publication are the opinions and views of the authors, and are not the views of or
endorsed by Taylor & Francis. The accuracy of the Content should not be relied upon and should be independently verified with primary sources of information. Taylor and Francis shall not be liable for any losses, actions, claims,
proceedings, demands, costs, expenses, damages, and other liabilities whatsoever or howsoever caused arising directly or indirectly in connection with, in relation to or arising out of the use of the Content.
This article may be used for research, teaching, and private study purposes. Any substantial or systematic reproduction, redistribution, reselling, loan, sub-licensing, systematic supply, or distribution in any form to anyone is
expressly forbidden. Terms & Conditions of access and use can be found at http://www.tandfonline.com/page/terms-and-conditions
A Study on the Energy Saving of Converting
a VAV System from Inlet Guide Vane to
Variable Fan Speed Control
K F Vee BEng(Hons) (Eng MCIBSE MIEE MlnstE MHKIE Cary W H Chan MSACEngMCIOSEMHKIE
REW(CO, HOI RSO RSA Swire Properties Management Ltd
Swire PropertIes Management Ltd
Hlmson Y T Chan MSe OSe CEng R.P.E. MIMeehE MHKIE
Francis W H Ylk SSe MSc PhD CEng FCIOSE MIMe<hE MHKIE Swire Properties Management Ltd
Department of Building Services EngineerIng, Hong Kong Polytechnic
University
The paper describes a stUdy on the energy saving that could be achieved by converting a variable air volume (VAVj system
from using Inlet guide vane to variable fan speed control, which was meant to inform the decision on whether to retrofit all
the VAV systems in an office building. The stUdy Involved retrOfitting one Of the 54 VAVair-hondling units (AHUs) in the
building as a pilot installation. Measurement was conducted to obtain the characteristics of the systemfollowed by a short
term monitoring of the frequency Of power supply to the AHU and the outdoor temperature. A simplified model was
establishedfrom the measured results for predicting the fan energy use Of the system. The feasible annual energy saving
was esllmated using the model, based on the monthly operating hours and the monthly mean outdoor temperatures
determinedfrom the records logged by the building management system. The pilot stUdy concluded that the conversion
would be viable, as the paybaCk period would be less than four years. Fan speed control retrOfitfor all the VAV AHUs in the
building commenced In March 1999 and was completed in June 2000. The electricity consumption Of the AHUs during the
Downloaded by [University of Connecticut] at 15:30 13 October 2014
past year has been determined from metered energy use records andfound to be reasonably close to the predictions Of the
model established in the pilat study. The procedures adapted in the pilat study may be applied In other buildingsfor
determining whether or nat to retrofit VAV systems with conventional inlet guide vane control to variable fan speed control.
Keywords: Variable Air Volume System, Inlet GUide-vane, Variabie Speed Control, RetrOfit, Fan Energy Use
Introduction the buildIng was installed with a frequency inverter (FJ) and site
measurements were conducted to evaluate the energy saving potential
A detailed energy audit stUdy had been conducted for an office building of replacing IGV control with VFS control.
(Vik et ai, 199Ba), which unveiled that the landlord's total electricity
As the local power companIes are currently offering rebates for this type
consumption in the audit year was 174 kWh per square metre of the
total gross floor area of the building. The annual eledricity consumption
of conversion in buildings as part of their demand side management
program, more buildings in Hong Kong would be considering converting
for air-conditioning In the year was 127 kWh/m 2 , out of which the airside
theIr VAV systems to using the more energy efficIent VFS control. The
eqUipment accounted for 49 kWh/m 2 • The Inlet guide vane (IGV) controlled
results of the pilot stUdy, therefore, would be a usefUl reference to this
variable air Volume NAV) air-handling units (AHUs) serving the office
type of conversion projects.
floors were responsible for about 35 kWh/m 2•
A building energy simulation stUdy showed that for a 40-storey office General Building Characteristics
building that Is eqUipped with iGV controlled VAV AHUs of an average
The stUdy was carried out In a commercial office buildIng at TaiKoQ Place,
energy efficiency (the details at which can be found in Vlk et ai, 1998bj,
Quarry Bay. The building comprises 29 above ground storeys and four
replacing the IGV control with variable fan speed (VFS) control could lead
levels of basement car parks. The total gross floor area (GFA) of the bulidlng
to a large reduction in the annual electricity consumption of the airside
Is around 74,'00 m 2, which is occupied primarily by offices. The other
eqUipment, from 47 kWh/m 2 to 23.4 kWh/m 2 or by about 50%. Energy
types of premises In the building Include one Chinese restaurant (GFA:
consumption reductions by a similar percentage are reported in the
2,050 m') and six retail shops (GFA: 250 m'l.
literature for this type of system relrofit (eg Englander 8' Norford, 1992;
Lorenzetti 8' Norlord, 199B; Shepherd, 1999). Due 10 the large energy The envelope of the buildIng Is a curtain wall construction with no external
saving potential that it promises, conversion of VAV systems in existing shading devices. The U-value of the 8 mm thick blue reflective glazing
buildings from using IGV control to VFS control is often recommended is 5.5 W/m 2K, and the shading coefficient is 0.32. The calculated overall
as an energy efficiency retrofit measure (eg Wulfinghoff, 1999). thermal transter value (OITY) of the building was 27 W/m' (Vik et ai,
199Ba).
The owner of the audited bUilding regarded the VAV system control
conversion as an energy management opportunity (CiBSE, 1991). However,
T11e Central Chilled Waler System
the actual energy saving could significantly deviate from the simulation
predidlons If the charaderlstics of the building and the VAV system designs, The building is eqUipped with a central chiller plant comprising four sets
the duratlon of the operating periods and the occupation conditions were of B50 TR and one set of 600 TR (1 TR ~ one ton 01 retrigeratlon ~
different from those assumed in the simulatlon, or if the modellll1g methods 3.517 kWI water-cooied centrifugal chillers. The 600 TR small chiller is
were not entirely appropriate for the system modelled (Kempers, 1995). used to meet the air conditioning demand outside normal office hours.
Since the conversion would "involve a substantial capital investment, It The chiller condenser heat is rejected to the atmosphere through the
was considered necessary to carry out a pilot InstallatIon before full- cooling towers Installed at the roof. Water lasses at the cooling towers
scale Implementation. For the pilot stUdy, an air-handling unit (AHUI In are replenished by seawater supply from a pump house at the sea front
v
pressure, P Fan modulation
such that, under light load conditions, chilled water can be obtained curve
from the chiller plant in the adjacent building, allowing a higher overall
energy efficiency to be achieved.
Possibl~region
~:::::--.. '. --
......:: ~ Design operating
polnl
orran operating
The AJr Side Systems points at a gi\'en
IGV closii18
Three fresh air fans were installed to supply outdoor air to various air· flow rate ' - ; r l - - - - - - :
handling units (AHUs). The outdoor air supply will mix with the returned
air and be cooled by the cooling coils within the AHUs. Each typical
office floor Is served by two variable air volume (VAV) systems. VAV Duel static
----
terminals were provided to regulate the flow rate of supply air for IndMdual "'".",
set point
spaces, in accordance with the local space air temperature. Air is returned Flow rate, V
to the AHU room through the ceiling void. The design supply airflow MinilIJJm flow De1:ign flow
rate of the AHU selected tor the pilot study Is 8,780 115. The original rat~, V_
rate, V......
IGV was retained such that the AHU could still be switched baCK to IGV
contra!.
Figure 1 - Operating Range Of the Variable Speed Fan In a VAV AHU
The BMS and the Control System
The building Is eqUipped with a building management system (8MS), 4. The operating point of a fan is fully defined when the flow rate and
which provides start/stop control for the AHUs according to a prHet the fan total pressure are both fixed. The corresponding fan efficiency,
time schedule. Direct digital control (DOQ systems are used to provide therefore, would also be fixed. It follows that the fan power demand
operational control over the AHUs and VAV terminals. Each VAV AHU can be related to the supply flow rate only, as expressed In Equation
was built-in with an IGV for modulation of the supply airflow rate. The (3).
degree of opening of the IGV is controlled by a DOC controller, according
to the lowest of the four duct static pressure signals from sensors W = P(V)Vln ~ W(VJ (3)
Installed al the four main branches of the main supply air ductlng
system.
Downloaded by [University of Connecticut] at 15:30 13 October 2014
5. Rather than the method of control, the fan total pressure required
under a specific supply flow rate Is dependent on the characteristics
Evaluation of the System Conversion of the duetlng system and the VAV terminals. Hence, the same fan
total pressure to flow rale relation (Equation (2)) applies also to the
Approach same system When VFS control Is used Instead. The fan power to
Quantification of the actual energy saving reqUires comparison of the flow rate relation f!N ~ W(V)) of the system, however, would be different
energy use of the converted system throughout a whole year against when one control method is replaced by the other, due to the difference
that of another system whIch would be identical except for the control in the fan efficiency when different control methods are used to regUlate
method used. This, however, would take at least one year to complete. the flow rate through the fan.
Furthermore, It would be impossible to ensure the operating condltlons 6. The supply flow rate demand is dependent on the total sensible cooling
of the two systems would always be identical. Due to the time and load of the air-conditioned spaces served by the system until the
resources constraints, a simplified method was devised to allow the annual VAV terminals are all closed to the preset minimum opening position.
energy saving to be quantified without the need for the year-round By making the assumption that the sensible cooling load is simply
measurement. related to the outdoor temperature (1), the supply flow rate requirement
The method employed was devised in the light of the following can be predicted from the outdoor temperature, if the relation between
considerations: the two, as expressed In Equation (4). Is known.
1. The power demand of a fan {W} is dependent on the supply flow V~V(1) (4)
rate M, the fan total pressure (P) and the efficiency of the fan and
the fan motor (n) as follows (ASHRAE, 1997): 7. It follows that if the dependence of the fan total pressure on the
flow rate and of the flow rate on the outdoor temperature can be
W = VP!n (1) made known, the annual fan eledrklty consumption can be estimated
from the outdoor temperature records throughout the year.
2. When the supply flow rate is varied In response to changes in the
sensible cooling requirement, through modulating the IGV position 8. Unfortunately, there were no flow meters available for continuous
according to a pre-set duet static pressure set point, the operating measurement of the supply airflow rate so as to allow the relation
point of the fan will shift, within a certain region, as depicted by between the flow rate and the outdoor temperature to be found from
the shaded region in Figure 1. At a particular supply flow rate, the the measured data. A further assumption was, therefore, made that
fan total pressure will not be a unique value, but can vary over a the supply flow rate demand would be simply related to the frequency
certain range, depending on the combination of the degree of opening of power supply to the fan (0 when VFS control was used, While the
frequency, obtainable from the BMS trend logs, would be simply related
of the VAV terminals.
to the outdoor air temperature, Ie:
3. However, if the assumption is made that the fan total pressure
corresponding to each supply floW rate can be represented by a V ~ V(f(1)) (S)
representative value, a unique fan total pressure to supply flow rate
relation (Equation (2)). as depicted by the fan modulation curve shown 9. The relation belween the supply flow rate and the fan power supply
in Figure 1. can be derived for the purpose of estimating the annual frequency (V = V(OI, and between the fan power demand and the
fan energy use. supply flow rate (W = W(V)), could be ascertained through a site
measurement. The relation between the power supply frequency and
P ~ P(V) (2) the outdoor temperature (f = f{Tn, however, would need to be
·--------111
TRANSACTIONS. Volume 9 Number 2
established from records logged using the BMS when the pilot system measurement points was the same, the total flow rate through each duet
with the VFS control was put Into operation. branch was determined from the average air velocity of the 12-polnt
Therefore, the method for estimatlng the annual energy saving that could measurements and the cross·sectionar area of the branch.
be achieved by converting the VAV control method from using IGV to The electrical measurements were conducted using a power analyser
VFS Involved the following steps: (Table 1). These include the three-phase voltage, current, power factor
1. To conduct site measurements to ascertain how the supply frequency and the current and voltage total harmonic distortions. Since the
(for VFS control), IGV control signal (for IGV control) and fan power measurement was made at the Incoming side of the Fl, the electric power
would vary with the total supply flow rate demand on tlie AHU. measured represented the total power demand of the FI and the fan.
2. To allow the converted system to operate for a period of time during Table 2 summarises the temperature set points set for the 31 VAV
which the frequency of the power supply to the fan motor and the terminals In the tested system during the site measurements and the
concurrent outdoor temperature would be consistently logged by the corresponding measurement results. The range of the total supply airflow
BM5. rate achieved through the VAV terminal set point adjustment was from
5.7 to 8.4 m'/s.
3. To establish a correlation between the supply frequency and the
outdoor air temperature on the basis of the logged data.
4. To estimate the annual fan energy use based on outdoor air 9.00
v = 0.211;3 f - 1.8 8
temperatures throughout the year, and on the relations ascertained
In the site measurement and from the BMS records.
IB 8.00
• I
-
Site Measurements
~ 7.00
17 V I"o VSFI
The site measurements were conducted during weekends while the office
areas were unoccupied. In order to obtain system performance data that
'E
• ". V IGV
I
,'"
can cover a sufficiently wide range of operating conditions, the supply Q. 6.00
flow rate demand at Individual VAV terminals were artificially adjusted
~
<II
~
by resetting their control set points through the BM5. Setting an 5.00
extraordinarily high set point value (32"C) for a VAV tennlnal would ensure 30 40 50 60 70 80 90
the damper in the terminal would remain at the pre-set minimum degree
VSF Freq. (Hz) IIGV Po•. (Ang.)
of opening. Conversely, an extraordinarily low set point value (12"C) would
Downloaded by [University of Connecticut] at 15:30 13 October 2014
ensure the terminal would remain fully open. Theretore, the total supply
flow rate demand could be varied in steps by setting different numbers Figure 2 - Measured Fan Power Supply Frequency (VFS Control) and lev
of terminals at the extraordinarily high, the normal and the extraordinarily Posilion (lev Controi) at Various Fiow Rates
low set point values.
Throughout the site measurements, the duct static pressure setting was 20.00
~
maintained at the original set point of 250 Pa. After the VAV terminals W = -0.234 v 2 + 4.5149 ·5.3156
were set, the system was allowed to run for some time to achieve steady
f
operation before measurements were taken. The measurements made
Include the total supply airflow rate, the electric demand of and the
15.00
... ./
i.. I" VSFI
~
differential pressure across the AHU fan, the power supply frequency 10.00
~ w=o 9715V2 ·9.9 I34V +33.• ' olGV
or the IGV position, and the power factor and the power quality. Table ,
1 summarises the characteristics of the instruments used in the site •
~
5.00
measurements.
At each of the main supply duct branch, four equally spaced holes were 0,00
available for In-duct air velocity measurement. An anemometer (Table 5.00 •.00 7.00 8.00 900
1) was Inserted into the air duct through each of these holes, at three Supply airflow I'lIts (cu.mfa)
equally spaced positions (High/Middle/Low), for measuring the air velocities
at 12 locations on a cross-sectional plane of each duct branch. Since
Figure 3 - Measured Electric Demand of AHU at Various Flow Rotes (VFS
the sub-divided cross-sectional area covered by each of the air velocity and lev Controls)
12 12
15 25 61.3 20.6 0.3547 7.32 856 6.26 15.2 6.9%
4 32
Based on the measured results, the relations between the supply airflow
00.0 '000
rate and the frequency of the power supply to the fan motor, and between
the fan power demand and the airflow rates, were established. Figure •• o. • • • 900
2 shows the relation between fhe ICV position and the supply airflow
rate, and between the fan power supply frequency and the supply airflow ."
40.0
6 4 6 .6
• 00
00• 800
700 t::::::l COunt (. rKOfds)
rate, for the two control methods tested. Rgure 3 shows the power demand e 300
00
eoo f _ I _ O.788T • 18.4n
~ . 8
•
of the fan at various supply airflow rates, when the system was put under ••
•=- 20.0
0
000
-
••
0 •
.....-g. Freq.
M8X. Freq.
the ICV and lhe VFS control.
-
~
<CO
300
0
z
0 Mft.F~q.
----------------------------ID
TRANSACTIONS' Volume 9 Number 2
room sensible load was also affected by changes in solar radiation intensity saving per hour of operation. From the data shown in Table 3, the saving
and intensities of heat gains from Internal sources, and the start·up during the overtime operation was estimated as follows:
operation. However, majority of the data clusters around the average
value for the corresponding outdoor temperature, as can be seen from 10094
Overtime Energy 5aving = 120 x ~ 406 kWh
the relatively small standard deviation (see the S1dDev curve In Figure 2987
4). Therefore, although there could be significant variations in the frequency
of the power supply to the fan motor for a given ou1door temperature, The annual total saving, therefore, would be about 10,500 kWh
the regression model relating the average frequency to the outdoor ( = 10094+406). 8ased on an electricity tariff rate of HKSO.9I1<Wh and
temperature would remain a representative model. an initial cost of HKS35,000.00 for the FI, the simple payback period
for the investment for the conversion would be 3.7 years. In this simplistic
Models Established from the Pilot Studies
estimate, inflatlon, interest on the Investment and escalation of electricity
As shown in FIgures 2, 3 a-
4, the followIng relations were established price were all Ignored.
from the data obtained from the site measurement and the BMS records:
Breakevt!n Point of the Two Methods
Yin ~ 0.215f - 1.88 (6) The site measurements show that, In general, the fan power demand
WM ~ -0.23411' + 451V - 5.32 for IGV control (7) would be smaller when the VFS control was adopted. However, because
the frequency Inverter Itself would consume electricity, the system would
WM = 0.972V' - 9.93V + 33.6 for VFS control (8) demand for a greater power than when IGV control was used while 1he
fiT) = 0.788T + 1.95 (9) system was delivering a flow rate close to the design value. The measured
results (Figure 3) show that the power demand would breakeven when
Energy SavIng Estfmate the supply airflow was at around 7.8 m1/s, Which is equivalent to 89%
Since the monitoring period lasted only for slightly longer than three of the design flow rate. This Implies that the VFS control method would
months, there were insufficient power supply frequency data for estimation bring about energy saving only When the system flow rate was lower
than 7.8 m3/s.
of the annual fan energy use. The annual fan energy use, therefore,
was simply estimated with reference to the monthly mean temperatures
Electrical Power Quality
within the 'normal' air-conditioned periods in the respective months, which
would start from 8:00 till 19:00 on a weekday, and from 8:00 till 14:00 The use of a frequency Inverter could generate considerable amount of
on every Saturday. Assuming no overtime operation, the total operating harmonic distortions to the electricity supply system (Domljan and
hours of the AHUs In each month In 1996 was estimated. The monthly Santander. 1993). According to the measured power quality reSUlts, the
Downloaded by [University of Connecticut] at 15:30 13 October 2014
operating hours, and the corresponding monthly mean outdoor frequency inverter incurred a total current hannanlc distortion (THO)
temperatures calculated from the BMS records, are summarised In by 66.8% when the inverter output was 37 Hz. This was much higher
Table 3. than When IGV control was used (THD , = 8.6%).
For Simplicity, the power supply frequency predicted using equation (9) Power quality measurement had been made subsequently, with the use
based on the monthly mean outdoor temperatures were taken as the of another make of frequency inverter, which showed a much lower TH01
monthly mean supply frequency for the respective months. The monthly of 30010 only. This experience shows that care should be exercised in
average supply flow rate for each month was then estimated using the choice of frequency inverters for application to a VAV system to ensure
Equation (6). The monthly electricity consumption of the fan, when put the power quality would not be seriously affected.
under the VFS and IGV control methods, were estimated using Equations
(7) and (8) respectively, together With the monthly operating hours. Results Fan Energy Use SUbsequent to Retrofit and
of this estimation are summarised in Table 3. Comparison with Model Predictions
The results show that the annual electricity consumption of the
VAV system, when using the ICV control would amount to about The energy metering provision in the building was upgraded
32 kWh/m' (~41,849 I 1,322 where 1,322 is the GFA of the part of since September 2000, which allowed the total electricity
the office premises served by the VAV system, in m~, which is slightiy consumption of the waterside and the airside ajr.·conditioning equipment
lower than the result found In the energy audit stUdy (35 kWh/m'). The to be more precisely determined from the meter readings. The monthly
consumptlon would drop to about 24 kWh/m 2 when the system was total fan energy consumption, for the period from October 2000 to
converted into using VFS control. The potential annual energy saving September 2001, have been determined from these metered records,
achievable would amount to about 10,100 kWh, when only the normal as summarised in Table 4. It was found from the metered records that
operating hours were considered. the annual fan energy use per square meter of the floor area in the
office floors In the building (the EUJ In Table 4) has dropped, after the
The BMS records showed that In 1996, the tested system had b~n run retrofit, to just slightly higher than 22 kWh/m'. This represents a reduction
for 120 hours outside the normal operating period. For simplicity, the in VAV AHU energy use by 37% when compared with the earlier audit
saving during the overtime period was estimated based on the average result.
Month Jan Feb Mar Apr May Jun July Aug Sep Oct Nov Dec Total
Mean T (0C) 18.8 17.4 20.5 21.6 26.2 29.6 30.9 29.5 28.3 27.1 23.7 19.6
Predicted freq (Hz) 34.3 33.2 35.6 36.5 40.1 42.8 43.8 42.7 41.8 40.8 38.1 34.9
Predicted flowrate (m'/s) 5.5 5.27 5.79 5.98 6.76 7.34 7.56 7.32 7.12 6.91 6.34 5.64
Operating Hours 226 222 261 227 277 222 277 255 249 266 261 244 2987
Fan energy (IGV) (kWh) 2816 2661 3394 3026 4025 3382 4282 3879 3730 3918 3631 3104 41849
Fan energy (VSF) (kWh) 1893 1831 2264 2033 3008 2893 3886 3304 3019 3025 2526 2073 31755
Energy saving (kWh) 924 830 1129 993 1016 489 396 575 711 893 1105 1031 10094
-t 200,000
• 3.
Institution of Bulkling services Engineers, U.K.
Domijan Jr. A, Embrlz·Santander E (1993). Measurements of electrical power
~ T".l'- .... '" inputs to varlable-speed molars and their solid-state power converters, ASHRAf
Transactions, Vol. 99, Part 1, p.241-2.58.
~
150.000 4. Englander Sl, Norford lK (1992). Save fan energy in VAV systems - Part 1:
~
, If -.-Metered
Analysis of a variable-speed drive retrofit, ASHRAf Transactions, Vol. 98, Part
- 4 - Predicted
'C
'G 100,000 " p.3-18.
-•
w
5. Kempers G (1995). DSM pitfalls for centrifugal pumps and fans, fnergy
Engineering, Vo1.92, NO.2, p.S7-80.
•
~ 50,000 6. Lorenzetti OM, Norford lK (199B). Measured energy consumption of variable-
air-volume fans under inlet-vane and variable-speed drive control, ASHRAf
Transactions, Vol. 98, Part 2, p.371-379.
a 7. Shepherd K (1999). VAV air conditioning systems, Blackwell Science ltd., UK.
B. Wulfinghoff DR (1999). fnergy efficiency manual, Energy Institute Press, US.
9. Vik FWH, Vee KF, Sat PSK, Chan (WH (1998a). A detailed energy audit for a
commercial office building in Hong Kong.. Transactions, Va1.5, No.3, p.84-BB,
The Hong Kong Institution of Engineers, HK.
10. Vik FWH, Burnett J, Jones P, Lee WL (1998b). Energy performance criteria In
Figure 5 - Comparison of the Measured and Predided Fan Energy Use in Hong Kong Building Environmental Assessmem Method. fnergy and Buildings,
Conclusion
From a pilot study conducted In 1997 in an office building, it was found
that converting the VAV systems In the building from using IGV control
to VFS control was both technically feasible and financially viable.
_ _ _ _~__:__::-------------------jm
TRANSACTIONS. Valume 9 Number 2
KFYee CaryW H Chan
IT K F Vee started his career development with Hong Ir Cary W H Chan Is a professional engineer. He is
Kong United Dockyards Ltd as an Electrical Apprentice currently the Head of Technical services Department
in 1981. At the same lime, he studied part-time for an of Swire PrOperties Ltd. overseeing the efficient operation
electrical craft certificate. He continued with his part- of all plant and equipment of the company's investment
time studies and graduated with a BEng(Hons) degree portfolio. His major interests are on energy and
in Building Services Engineering at the Hong Kong PolyU environment conservation and he has been working
in 1997. He joined Swire Properties Management ltd closely with local universities on those issues. Ir Chan
in 1991 and Is now a Bulldlng Engineer at the Pacific Is also a member of the steering committee for the
Place Management Office. Ir Vee Is a Chartered Engineer development of the Hong Kong Building Environmental
and Corporate Member of HKJE, (IBSE, lEE and loslE. Assessment Method (HK-BEAM).
He is not only a Registered Safety Officer but also a Registered Safety Auditor in
the safety industrial and Is licensed to practise as Grade CO and HO Electrical Work.
IT Vee was appointed by IVE and CltyU as a Part-tIme Lecturer since 2000 and
2001 respectively.
studies.
ml-----------------------------------------;:Th::e::-:H::o-=n-=g--:K;:o::n::g~l;:n::5t;;;it::u::tio:::n::-:;of:;;;En::g:::;;:n::ee=rs