LIGHTS 0.75
SOCKETS 0.5
FCU 0.9
WASHING MACHINE 0.5
DISH WASHING 0.5
WATER HEATER 0.5
MOTOR 0.5
COOKER 0.5
AIR CONDITION 0.9
SPARE 0
BLANK 0
Project/Building Name: Main breaker type & rating: 63A ISOLATOR
Address/Location: FLAT No.1 corridor Incomminig cable size/ type: 4C 16 MM2 XLPE/SWA/PVC
Distribution Board No./Ref: DB-F11
Fed from: SMDB-11
Connecte circuit
Incomer
TYPICAL TO DB-21, DB-31, DB-41, DB,51, DB-61, DB-71, DB-81, DB-91, DB-101, DB-111, DB-121, DB-131, DB-141, DB-151, DB-161, DB171, DB-181, DB-191, DB-201
Project/Building Name: Main breaker type & rating: 40A ISOLATOR
Address/Location: FLAT No.2 corridor Incomminig cable size/ type: 4C 16 MM2 XLPE/SWA/PVC
Distribution Board No./Ref: DB-F12
Fed from: SMDB-1
circuit
Incomer
TYPICAL TO DB-15, DB-22, DB-25, DB,32, DB-35, DB-42, DB-45, DB-52, DB-55, DB-62, DB-65,DB-72, DB-75, DB-82, DB-85, DB-92, DB-95, DB-102, DB-105,
DB-112, DB-115, DB-122, DB-125, DB-132, DB-135, DB-142, DB-145, DB-152, DB-155, DB-162, DB-165, DB-172, DB-175, DB-182, DB-185, DB-192, DB-195, DB-202, DB-205
Project/Building Name: Main breaker type & rating: 63A ISOLATOR
Address/Location: FLAT No.3 corridor Incomminig cable size/ type: 4C 16 MM2 XLPE/SWA/PVC
Distribution Board No./Ref: DB-F13
Fed from: SMDB-1
circuit
Incomer
B3 16 SPARE 0 0 0
R4 20 4 2.5 WATER HEATER KITCHEN 1 1.5 1.5 0.5 0.75
Y4 20 4 2.5 WATER HEATER BATH ROOM 1 1.5 1.5 0.5 0.75
B4 20 4 2.5 WATER HEATER BATH ROOM 1 1.5 1.5 0.5 0.75
R5 30 4 2.5 SOCKETS LIVING ROOM (RING) 7 0.2 2.2 0.5 1.1
Y5 20 4 2.5 SOCKETS BED ROOMS 3 0.2 1.4 0.5 0.7
B5 32 4 2.5 SOCKETS BED ROOMS (RING) 5 0.2 1.8 0.5 0.9
40A RCD
WITH 30mA R6 32 4 2.5 WASHING MACHINE KITCHEN 1 1.5 1.5 0.5 0.75
EARTH Y6 20 4 2.5 DISH WASHING KITCHEN 1 1.5 1.5 0.5 0.75
LEAKAGE B6 32 4 2.5 SOCKETS BED ROOM (RING) 5 0.2 1.8 0.5 0.9
SENSETIVITY R7 32 4 2.5 5 0.2 1.8 0.5 0.9
SOCKETS KITCHEN (RING)
Y7 20 SPARE 0 0 0
B7 20 SPARE 0 0 0
R8 32 SPARE 0 0 0
Y8 20 SPARE 0 0 0
B8 20 SPARE 0 0 0
TOTAL CONNECTED LOAD= 21 Kw 8.6 6.1 6.3
TOTAL DIVERSIFIDE LOAD= 8.7 Kw 41.43% 8.7
TYPICAL TO DB-14, DB-23, DB-24, DB,33, DB-34, DB-43, DB-44, DB-53, DB-54, DB-63, DB-64,DB-73, DB-74, DB-83, DB-84, DB-93, DB-94, DB-103, DB-104,
DB-113, DB-114, DB-123, DB-124, DB-133, DB-134, DB-143, DB-144, DB-153, DB-154, DB-163, DB-164, DB-173, DB-174, DB-183, DB-184, DB-193, DB-194, DB-203, DB-204
Project/Building Name: Main breaker type & rating: 63A ISOLATOR
Address/Location: GROUND FLOOR Elect. Room Incomminig cable size/ type: 4C 16 MM2 XLPE/SWA/PVC
Distribution Board No./Ref: DB-G
Fed from: SMDB-EG
circuit
Incomer
Y5 20 SPARE
B5 20 4 2.5 FCU GARBAGE ROOM 1 0.5 0.5 0.9 0.45
R6 32 4 2.5 SOCKETS TRANS. & H.V. RM.(RING) 4s 1.0/0.2 1.6 0.5 0.8
Y6 32 4 2.5 SOCKETS ELECT. RM. & LOBBY(RING) 4s 1.0/0.2 1.6 0.5 0.8
B6 32 4 2.5 SOCKETS BMS,LOBBY(EXTERNAL)(RING) 4s 1.0/0.2 1.6 0.5 0.8
R7 32 4 2.5 SOCKETS LIFT LOBBY (RING) 2s 1.0/0.2 1.2 0.5 0.6
GEN. RM. GARBAGE RM.
Y7 32 4 2.5 SOCKETS 4s 1.0/0.2 1.6 0.5 0.8
(RING)
40A RCD
WITH 30mA B7 32 4 2.5 ICP MAIN ENTRANCE 1 0.2 0.2 0.9 0.18
EARTH R8 32 4 2.5 GCP MAIN ENTRANCE 1 0.2 0.2 0.9 0.18
LEAKAGE
Y8 32 4 2.5 FACP MAIN ENTRANCE 1 0.2 0.2 0.9 0.18
SENSETIVITY
B8 32 SPARE
R9 32 SPARE
Y9 32 SPARE
B9 32 SPARE
R10 SPACE
Y10 SPACE
B10 SPACE
TOTAL CONNECTED LOAD= 19.9 kW 6.8 6.8 6.3
TOTAL DIVERSIFIED LOAD= 13.49 kW 67.79% 13.49
Project/Building Name: Main breaker type & rating: 80A ISOLATOR
Address/Location: FLAT No.2 corridor Incomminig cable size/ type: 4C 25 MM2 XLPE/SWA/PVC
Distribution Board No./Ref: DB-F212
Fed from: SMDB-21
Connecte Circuit Load in Watts circuit
Incomer
R6 BLANK 0 0 0
Y6 BLANK 0 0 0
B6 BLANK 0 0 0
R7 30 4 2.5 SOCKETS FAMILY SITTING (RING) 7 0.2 2.2 0.5 1.1
Y7 20 4 2.5 WATER HEATER KITCHEN 1 1.5 1.5 0.5 0.75
B7 20 4 2.5 WATER HEATER KITCHEN 1 1.5 1.5 0.5 0.75
R8 30 4 2.5 SOCKETS BED ROOM (RING) 5 0.2 1.8 0.5 0.9
Y8 20 4 2.5 WASHING MACHINE KITCHEN 1 1.5 1.5 0.5 0.75
B8 30 4 2.5 SOCKETS BED ROOM (RING) 5 0.2 1.8 0.5 0.9
R9 20 4 2.5 WATER HEATER BATH ROOM 1 1.5 1.5 0.5 0.75
Y9 20 4 2.5 DISH WASHING KITCHEN 1 1.5 1.5 0.5 0.75
60A RCD
B9 30 4 2.5 SOCKETS FAMILY ROOM (RING) 5 0.2 1.8 0.5 0.9
WITH 30mA
EARTH ENTRANCE LOBBY &
LEAKAGE SOCKETS 3 0.2 1.4 0.5 0.7
R10 20 4 2.5 STORE
SENSETIVITY Y10 30 4 2.5 SOCKETS LIVING ROOM (RING) 7 0.2 2.2 0.5 1.1
B10 30 4 2.5 SOCKETS BED ROOM (RING) 5 0.2 1.8 0.5 0.9
R11 30 SPARE 0 0 0
Y11 30 4 2.5 SOCKETS KITCHEN (RING) 6 0.2 2 0.5 1
B11 30 SPARE 0 0 0
R12 20 SPARE 0 0 0
Y12 20 SPARE 0 0 0
B12 30 SPARE 0 0 0
TOTAL CONNECTED LOAD= 30.9 Kw 10.8 10.7 9.4
TOTAL DIVERSIFIDE LOAD= 11.975 Kw 38.75% 11.975
TYPICAL TO DB-213
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 1st BASEMENT Elect. Rm. Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-B1
Fed from: MDB-EG
circuit
Incomer
40A RCD B6 32 4 2.5 SOCKETS ETS ROOM (RING) 4s 1.0/0.2 1.6 0.5 0.8
WITH 30mA R7 32 4 2.5 SOCKETS PARKING (RING) 4s 1.0/0.2 1.6 0.5 0.8
EARTH Y7 32 4 2.5 SOCKETS PUMP ROOM (RING) 2s 1.0/0.2 1.2 0.5 0.6
LEAKAGE
SENSETIVITY B7 32 SPARE
R8 32 SPARE
Y8 32 SPARE
B8 32 SPARE
TOTAL CONNECTED LOAD= 18.9 kW 6.4 6.4 6.1
TOTAL DIVERSIFIED LOAD= 13.695 kW 72.46% 13.695
Project/Building Name: Main breaker type & rating: 32A TP ISOLATOR
Address/Location: 2nd BASEMENT Elect. Rm. Incomminig cable size/ type: 4C,10mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-B2
Fed from: SMDB-EG
circuit
Incomer
SENSETIVITY Y3 16 2.5 2.5 FCU LIFT LOBBY 1 0.5 0.5 0.9 0.45
B3 20 4 2.5 FCU SERVICE 1 0.5 0.5 0.9 0.45
R4 16 SPARE
Y4 20 SPARE
B4 20 SPARE
R5 20 4 2.5 SOCKETS LIFT LOBBY (RING) 4s 1.0/0.2 1.6 0.5 0.8
40A RCD Y5 20 4 2.5 SOCKETS PARKING (RING) 4s 1.0/0.2 1.6 0.5 0.8
WITH 30mA B5 20 4 2.5 SOCKETS SERVICE (RING) 5s 1.0/0.2 1.8 0.5 0.9
EARTH R6 32 SPARE
LEAKAGE
SENSETIVITY Y6 32 SPARE
B6 32 SPARE
TOTAL CONNECTED LOAD= 13.4 kW 4.9 4.1 4.4
TOTAL DIVERSIFIED LOAD= 9.955 kW 74.29% 9.955
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 3rd Fl Elect. Room Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-EM1
Fed from: SMDB-EG
Connecte circuit
Incomer
R4 20 4 2.5 SOCKETS Elec./Tel. Rm. (1st Fl) 2 0.2 1.2 0.5 0.6
Y4 20 4 2.5 SOCKETS Elec./Tel.Rm (2nd Fl) 2 0.2 1.2 0.5 0.6
B4 20 4 2.5 SOCKETS Elec./Tel.Rm (3rd Fl) 2 0.2 1.2 0.5 0.6
R5 20 4 2.5 SOCKETS Elec./Tel.Rm (4th Fl) 2 0.2 1.2 0.5 0.6
Y5 20 4 2.5 SOCKETS Elec./Tel.Rm (5th Fl) 2 0.2 1.2 0.5 0.6
B5 20 4 2.5 SOCKETS Elec./Tel.Rm (6th Fl) 2 0.2 1.2 0.5 0.6
32A RCD
WITH 30mA R6 20 SPARE 0 0 0
EARTH Y6 20 SPARE 0 0 0
LEAKAGE B6 20 SPARE 0 0 0
SENSETIVITY R7 20 SPARE 0 0 0
Y7 20 SPARE 0 0 0
B7 20 SPARE 0 0 0
R8 20 BLANK 0 0 0
Y8 20 BLANK 0 0 0
B8 20 BLANK 0 0 0
TOTAL CONNECTED LOAD= 15.6 Kw 5.6 4.6 5.4
TOTAL DIVERSIFIDE LOAD= 9.9 Kw 63.46% 9.9
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 9th Fl Elect. Room Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-EM2
Fed from: SMDB-EG
Connecte circuit
Incomer
R4 16 SPARE 0 0 0
Y4 16 SPARE 0 0 0
B4 16 4 2.5 FCU BTH ROOM 1 1.5 1.5 0.9 1.35
R5 20 4 2.5 SOCKETS LIFTS MACHINE ROOM 2 0.2 1.2 0.5 0.6
Y5 20 4 2.5 SOCKETS PUMP ROOMS 2 0.2 1.2 0.5 0.6
B5 30 4 2.5 SOCKETS GUARD ROOM 4 0.2 1.6 0.5 0.8
R6 SPARE 0 0 0
Y6 20 4 2.5 SOCKETS FILTERATION ROOM 2 0.2 1.2 0.5 0.6
32A RCD
WITH 30mA B6 20 4 2.5 ISOLATOR CRADLE 1 1.5 1.5 1 1.5
EARTH R7 30 SPARE 0 0 0
LEAKAGE Y7 30 SPARE 0 0 0
SENSETIVITY B7 20 SPARE 0 0 0
R8 BLANK 0 0 0
Y8 BLANK 0 0 0
B8 BLANK 0 0 0
TOTAL CONNECTED LOAD= 11 Kw 1.7 3.5 5.8
TOTAL DIVERSIFIDE LOAD= 7.775 Kw 70.68% 7.775
Project/Building Name: Main breaker type & rating: 32A TP ISOLATOR
Address/Location: ROOF ELECTRICAL ROOM Incomminig cable size/ type: 4C,10mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-ER1
Fed from: SMDB-EG
Connecte circuit
Incomer
4C 16MM2
1RYB 63 1C 16 DB-F11 19.7 6.4 8.6 4.7 58.25% 11.475
XLPE/SWA/PVC
MM2 PVC
4C 16MM2
2RYB 40 1C 16 DB-F12 14.8 4.7 5.5 4.6 57.26% 8.475
XLPE/SWA/PVC
MM2 PVC
4C 16MM2
3RYB 63 1C 16 DB-F13 21 8.6 6.1 6.3 41.43% 8.7
XLPE/SWA/PVC
MM2 PVC
4C 16MM2
4RYB 63 1C 16 DB-F14 21 6.3 6.1 8.6 41.43% 8.7
XLPE/SWA/PVC
MM2 PVC
100A
4C 16MM2
5RYB 40 1C 16 DB-F15 14.8 4.7 4.6 5.5 57.26% 8.475
XLPE/SWA/PVC
MM2 PVC
6RYB 40 SPARE
7RYB 63 SPARE
8RYB BLANK
TYPICAL TO SMDB-21, SMDB-31, SMDB-41, SMDB-51, SMDB-61, SMDB-71, SMDB-81, SMDB-91, SMDB-101, SMD-111, SMDB-121, SMDB-131, SMDB-141,
SMDB-151, SMDB-161, SMDB171, SMDB-181, SMDB-191, SMDB-201
Project/Building Name: Main breaker type & rating: 100A TP MCCB MAIN
Address/Location: 21TH FLOOR ELECTRICAL ROOM Incoming cable size/ type: 4C,35mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: SMDB-211
Fed from: BUSBAR - 2
circuit
Incomer
4C 16MM2 1C 16
1RYB 60 DB-F211 21 6.1 8.6 6.3 41.43% 8.7
XLPE/SWA/PVC MM2 PVC
4C 25MM2 1C 16
2RYB 80 DB-F212 30.9 10.8 10.7 9.4 38.75% 11.975
XLPE/SWA/PVC MM2 PVC
4C 25MM2 1C 16
3RYB 80 DB-F213 30.9 10.8 10.7 9.4 38.75% 11.975
XLPE/SWA/PVC MM2 PVC
100A
4C 16MM2 1C 16
4RYB 60 DB-F214 21 6.3 6.1 8.6 41.43% 8.7
XLPE/SWA/PVC MM2 PVC
5RYB 80 SPARE
6RYB 60 SPARE
TYPICAL TO SMDB-21, SMDB-31, SMDB-41, SMDB-51, SMDB-61, SMDB-71, SMDB-81, SMDB-91, SMDB-101, SMD-111, SMDB-121, SMDB-131, SMDB-141,
SMDB-151, SMDB-161, SMDB171, SMDB-181, SMDB-191, SMDB-201
Project/Building Name: Main breaker type & rating: 40A TP MCCB MAIN
Address/Location: 22TH FLOOR ELECTRICAL ROOM Incoming cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: SMDB-1
Fed from: BUSBAR - 2
circuit
Incomer
4C 16MM2
1RYB 60 1C 16 DB-F221 21 8.6 6.1 6.3 41.43% 8.7
XLPE/SWA/PVC
MM2 PVC
4C 16MM2
2RYB 60 1C 16 DB-F224 21 8.6 6.1 6.3 41.43% 8.7
XLPE/SWA/PVC
MM2 PVC
40A
3RYB 80 SPARE
4RYB 60 SPARE
TYPICAL TO SMDB-21, SMDB-31, SMDB-41, SMDB-51, SMDB-61, SMDB-71, SMDB-81, SMDB-91, SMDB-101, SMD-111, SMDB-121, SMDB-131, SMDB-141,
SMDB-151, SMDB-161, SMDB171, SMDB-181, SMDB-191, SMDB-201
Project/Building Name: Main breaker type & rating: 150A TP MCCB MAIN
Address/Location: ROOF FLOOR ELECTRICAL ROOM Incoming cable size/ type: 4C,50mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: SMDB-ER1
Fed from: SMDB-EG
circuit
Incomer
4C 16MM2
1RYB 60 1C 16 FAHU 20 6.7 6.6667 6.6667 100.00% 20
XLPE/SWA/PVC
MM2 PVC
4C 16MM2
2RYB 60 1C 16 FAHU 20 6.7 6.6667 6.6667 100.00% 20
XLPE/SWA/PVC
MM2 PVC
4C 16MM2
3RYB 40 1C 16 PRESSURIZED FAN 15 5.0 5 5 100.00% 15
XLPE/SWA/PVC
MM2 PVC
150A
4C 16MM2
4RYB 40 1C 16 PRESSURIZED FAN 15 5.0 5 5 100.00% 15
XLPE/SWA/PVC
MM2 PVC
5RYB 60 SPARE
6RYB 40 SPARE
TYPICAL TO SMDB-21, SMDB-31, SMDB-41, SMDB-51, SMDB-61, SMDB-71, SMDB-81, SMDB-91, SMDB-101, SMD-111, SMDB-121, SMDB-131, SMDB-141,
SMDB-151, SMDB-161, SMDB171, SMDB-181, SMDB-191, SMDB-201
Project/Building Name: Main breaker type & rating: 600A TP MCCB MAIN
Address/Location: ELECTRICAL ROOM GROUND FLOOR Incoming cable size/ type: 2X4C 150mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: SMDB-EG
Fed from: MDB-GSR
circuit
Incomer
1C
4C 16MM2
9RYB 40 16MM2 DB-EM4 10.9 4.7 3.4 2.8 61.2% 6.7
XLPE/SWA/PVC
PVC
1C
4C 16MM2
10RYB 60 16MM2 LIFT-1 25 8.3 8.3 8.3 100.0% 25
XLPE/SWA/PVC
PVC
1C
4C 16MM2
11RYB 60 16MM2 LIFT-2 25 8.3 8.3 8.3 100.0% 25
XLPE/SWA/PVC
PVC
1C
4C 16MM2
12RYB 60 16MM2 LIFT-3 25 8.3 8.3 8.3 100.0% 25
XLPE/SWA/PVC
PVC
1C
4C 10MM2
13RYB 30 10MM2 DB-ER1 7.1 3.2 1.2 2.7 57.04% 4.05
XLPE/SWA/PVC
PVC
1C
4C 50MM2
14RYB 150 25MM2 SMDB-ER1 70 23.3 23.3 23.3 90.00% 63
XLPE/SWA/PVC
PVC
15RYB 40 SPARE
16RYB BLANK
1C
4C 16MM2
5RYB 40 16MM2 DB-R1 11 1.7 3.5 5.8 70.7% 7.8
XLPE/SWA/PVC
PVC
1C
4C 240MM2
6RYB 400 120MM2 SMDB-EG 314 108.567 101.57 103.87 75.8% 238.0
XLPE/SWA/PVC
PVC
7RYB 40 SPARE
8RYB 30 SPARE
Neutral rating A
No. rating (A) mm² reference per point R Y B factors diversity
size mm² (kW)
(kW) (kW)
1RYB 1000 1000A BUS BAR 913 307.0 309.0 297.0 45.2% 412.4
2X4C
2C
150MM2
2RYB 600 75MM2 MDB-SER 383.5 130.7 124.5 128.4 67.2% 257.7
XLPE/SW
1250A
PVC
A/PVC
4RYB BLANK
3RYB 1000 1000A BUS BAR 876.2 296.8 295.5 283.9 53.1% 465.3
600A
1C
4C 95MM2
4RYB 200 50MM2 FIRE FIGHTING PUMP 75 25 25 25 100.0% 75.0
XLPE/SWA/PVC
PVC