Sie sind auf Seite 1von 28

DIVERSITY FACTOR

LIGHTS 0.75
SOCKETS 0.5
FCU 0.9
WASHING MACHINE 0.5
DISH WASHING 0.5
WATER HEATER 0.5
MOTOR 0.5
COOKER 0.5
AIR CONDITION 0.9
SPARE 0
BLANK 0
Project/Building Name: Main breaker type & rating: 63A ISOLATOR
Address/Location: FLAT No.1 corridor Incomminig cable size/ type: 4C 16 MM2 XLPE/SWA/PVC
Distribution Board No./Ref: DB-F11
Fed from: SMDB-11
Connecte circuit
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)
R1 10 2.5 2.5 LIGHTS LIVING ROOM & KITCHEN 6 0.1 0.6 0.75 0.45
ENTRANCE, BATH ROOM,
LIGHTS 10 0.1 1 0.75 0.75
Y1 10 2.5 2.5 STORE & TOILETS
16A RCD
B1 10 2.5 2.5 LIGHTS BED ROOM, BATH ROOM 9 0.1 0.9 0.75 0.675
WITH 100mA
EARTH R2 10 4 2.5 FCU BATHROOM 1 0.5 0.5 0.9 0.45
LEAKAGE Y2 32 4 2.5 FCU BATHROOM 1 0.5 0.5 0.9 0.45
SENSETIVITY
FCU BATHROOM 1 0.5 0.5 0.9 0.45
B2 32 4 2.5
R3 32 4 2.5 SOCKETS KITCHEN 5 0.2 1.8 0.5 0.9
ENTRANCE & STORE ROOM
SOCKETS 4 0.2 1.6 0.5 0.8
Y3 32 4 2.5 (RING)
63A ISOLATOR

B3 20 4 2.5 FCU BATHROOM 1 0.5 0.5 0.9 0.45


R4 20 4 2.5 DISH WASHING KITCHEN 1 1.5 1.5 0.5 0.75
Y4 20 4 2.5 WATER HEATER BATH ROOM 1 1.5 1.5 0.5 0.75
B4 32 4 2.5 SOCKETS BED ROOM (RING) 5 0.2 1.8 0.5 0.9
32A RCD R5 20 SPARE 0 0 0
WITH 30mA Y5 32 4 2.5 SOCKETS BEDROOM (RING) 5 0.2 1.8 0.5 0.9
EARTH B5 16 SPARE 0 0 0
LEAKAGE R6 16 4 2.5 FCU KITCHEN 1 0.5 0.5 0.9 0.45
SENSETIVITY Y6 32 SPARE 0 0 0
B6 32 4 2.5 WATER HEATER BATH ROOM 1 1 1 0.5 0.5
R7 20 4 2.5 WASHING MACHINE KITCHEN 1 1.5 1.5 0.5 0.75
Y7 16 4 2.5 SOCKETS LIVING ROOM (RING) 7 0.2 2.2 0.5 1.1
B7 16 SPARE 0 0 0
R8 BLANK 0 0 0
Y8 BLANK 0 0 0
B8 BLANK 0 0 0
TOTAL CONNECTED LOAD= 19.7 Kw 6.4 8.6 4.7
TOTAL DIVERSIFIDE LOAD= 11.475 Kw 58.25% 11.475

TYPICAL TO DB-21, DB-31, DB-41, DB,51, DB-61, DB-71, DB-81, DB-91, DB-101, DB-111, DB-121, DB-131, DB-141, DB-151, DB-161, DB171, DB-181, DB-191, DB-201
Project/Building Name: Main breaker type & rating: 40A ISOLATOR
Address/Location: FLAT No.2 corridor Incomminig cable size/ type: 4C 16 MM2 XLPE/SWA/PVC
Distribution Board No./Ref: DB-F12
Fed from: SMDB-1
circuit
Incomer

Phase & Cable Connected Circuit Load in Watts


Busbar CCT ref. MCB Earth sise No. of diversity load after
Neutral rating A circuit name / point reference Load per
section /RCD No. rating (A) mm² points R Y B factors diversity
size mm² (kW) point (kW)
(kW)
R1 10 2.5 2.5 LIGHTS LIVING ROOM & BALCONY 5 0.1 0.5 0.75 0.375
16A RCD Y1 10 2.5 2.5 LIGHTS CORRIDOR & KITCHEN 6 0.1 0.6 0.75 0.45
WITH 100mA BED, FAMILY ROOMS &
EARTH LIGHTS 8 0.1 0.8 0.75 0.6
B1 10 2.5 2.5 TOILET
LEAKAGE
SENSETIVIT R2 16 4 2.5 FCU CORRIDOR 1 0.5 0.5 0.9 0.45
Y Y2 16 4 2.5 FCU KITCHEN 1 0.5 0.5 0.9 0.45
B2 16 4 2.5 FCU KITCHEN 1 0.5 0.5 0.9 0.45
WASHING
40A ISOLATOR

KITCHEN 1 1.5 1.5 0.5 0.75


R3 20 4 2.5 MACHINE
Y3 20 4 2.5 DISH WASHING KITCHEN 1 1.5 1.5 0.5 0.75
B3 32 4 2.5 SOCKETS BEDROOM (RING) 5 0.2 1.8 0.5 0.9
32A RCD R4 32 4 2.5 SOCKETS LIVING ROOM (RING) 7 0.2 2.2 0.5 1.1
WITH 30mA Y4 20 4 2.5 WATER HEATER KITCHEN 1 1.5 1.5 0.5 0.75
EARTH B4 20 4 2.5 WATER HEATER BATH ROOM 1 1.5 1.5 0.5 0.75
LEAKAGE
SENSETIVIT R5 20 SPARE 0 0 0
Y Y5 20 4 2.5 SOCKETS FAMILY ROOM (RING) 3 0.2 1.4 0.5 0.7
B5 20 SPARE 0 0 0
R6 20 SPARE 0 0 0
Y6 32 SPARE 0 0 0
B6 32 SPARE 0 0 0
TOTAL CONNECTED LOAD= 14.8 Kw 4.7 5.5 4.6
TOTAL DIVERSIFIDE LOAD= 8.475 Kw 57.26% 8.475

TYPICAL TO DB-15, DB-22, DB-25, DB,32, DB-35, DB-42, DB-45, DB-52, DB-55, DB-62, DB-65,DB-72, DB-75, DB-82, DB-85, DB-92, DB-95, DB-102, DB-105,
DB-112, DB-115, DB-122, DB-125, DB-132, DB-135, DB-142, DB-145, DB-152, DB-155, DB-162, DB-165, DB-172, DB-175, DB-182, DB-185, DB-192, DB-195, DB-202, DB-205
Project/Building Name: Main breaker type & rating: 63A ISOLATOR
Address/Location: FLAT No.3 corridor Incomminig cable size/ type: 4C 16 MM2 XLPE/SWA/PVC
Distribution Board No./Ref: DB-F13
Fed from: SMDB-1
circuit
Incomer

Phase & Cable Connected Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of diversity load after
Neutral rating A circuit name / point reference Load per
/RCD No. rating (A) mm² points R Y B factors diversity
size mm² (kW) point (kW)
(kW)
LIGHTS LIVING ROOM, CORRIDOR &
11 0.1 1.1 0.75 0.825
R1 10 2.5 2.5 KITCHEN
LIGHTS MAID ROOM, CORIDOR &
7 0.1 0.7 0.75 0.525
Y1 10 2.5 2.5 BATH ROOM
16A RCD LIGHTS
WITH 100mA BED ROOMS & BATH ROOM 7 0.1 0.7 0.75 0.525
B1 10 2.5 2.5
EARTH R2 16 4 2.5
LEAKAGE FCU KITCHEN 1 0.5 0.5 0.9 0.45
SENSETIVITY Y2 16 4 2.5 FCU BATH ROOM 1 0.5 0.5 0.9 0.45
B2 16 4 2.5 FCU BATH ROOM 1 0.5 0.5 0.9 0.45
R3 16 SPARE 0 0 0
Y3 16 4 2.5 FCU BATH ROOM 1 0.5 0.5 0.9 0.45
63A ISOLATOR

B3 16 SPARE 0 0 0
R4 20 4 2.5 WATER HEATER KITCHEN 1 1.5 1.5 0.5 0.75
Y4 20 4 2.5 WATER HEATER BATH ROOM 1 1.5 1.5 0.5 0.75
B4 20 4 2.5 WATER HEATER BATH ROOM 1 1.5 1.5 0.5 0.75
R5 30 4 2.5 SOCKETS LIVING ROOM (RING) 7 0.2 2.2 0.5 1.1
Y5 20 4 2.5 SOCKETS BED ROOMS 3 0.2 1.4 0.5 0.7
B5 32 4 2.5 SOCKETS BED ROOMS (RING) 5 0.2 1.8 0.5 0.9
40A RCD
WITH 30mA R6 32 4 2.5 WASHING MACHINE KITCHEN 1 1.5 1.5 0.5 0.75
EARTH Y6 20 4 2.5 DISH WASHING KITCHEN 1 1.5 1.5 0.5 0.75
LEAKAGE B6 32 4 2.5 SOCKETS BED ROOM (RING) 5 0.2 1.8 0.5 0.9
SENSETIVITY R7 32 4 2.5 5 0.2 1.8 0.5 0.9
SOCKETS KITCHEN (RING)
Y7 20 SPARE 0 0 0
B7 20 SPARE 0 0 0
R8 32 SPARE 0 0 0
Y8 20 SPARE 0 0 0
B8 20 SPARE 0 0 0
TOTAL CONNECTED LOAD= 21 Kw 8.6 6.1 6.3
TOTAL DIVERSIFIDE LOAD= 8.7 Kw 41.43% 8.7

TYPICAL TO DB-14, DB-23, DB-24, DB,33, DB-34, DB-43, DB-44, DB-53, DB-54, DB-63, DB-64,DB-73, DB-74, DB-83, DB-84, DB-93, DB-94, DB-103, DB-104,
DB-113, DB-114, DB-123, DB-124, DB-133, DB-134, DB-143, DB-144, DB-153, DB-154, DB-163, DB-164, DB-173, DB-174, DB-183, DB-184, DB-193, DB-194, DB-203, DB-204
Project/Building Name: Main breaker type & rating: 63A ISOLATOR
Address/Location: GROUND FLOOR Elect. Room Incomminig cable size/ type: 4C 16 MM2 XLPE/SWA/PVC
Distribution Board No./Ref: DB-G
Fed from: SMDB-EG
circuit
Incomer

Phase & Cable Connected Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of diversity load after
Neutral rating A circuit name / point reference Load per
/RCD No. rating (A) mm² points R Y B factors diversity
size mm² (kW) point (kW)
(kW)
H.V. ROOM, TRANSFORMER &
R1 10 2.5 2.5 LIGHTS 10 0.1 1 0.75 0.75
GENERATOR RM.
Y1 16 2.5 2.5 LIGHTS MAIN ENETRANCE 11 0.1 1.1 0.75 0.825
B1 10 2.5 2.5 LIGHTS ELECT. RM., BMS 10 0.1 1 0.75 0.75
R2 16 2.5 2.5 LIGHTS LIFT LOBBY, GARBAGE RM. 11 0.1 1.1 0.75 0.825
Y2 16 2.5 2.5 LIGHTS LOBBY (EXTERNAL LIGHT) 13 0.1 1.3 0.75 0.975
40A RCD B2 16 2.5 2.5 LIGHTS LOBBY (EXTERNAL LIGHT) 13 0.1 1.3 0.75 0.975
WITH 100mA R3 16 2.5 2.5 LIGHTS LOBBY (EXTERNAL LIGHT) 12 0.1 1.2 0.75 0.9
EARTH Y3 20 4 2.5 ELECT. RM. 1 0.5 0.5 0.9 0.45
FCU
LEAKAGE
SENSETIVITY B3 16 2.5 2.5 LIGHTS LOBBY (EXTERNAL LIGHT) 12 0.1 1.2 0.9 0.9
R4 20 4 2.5 FCU H.V. ROOM 1 0.5 0.5 0.9 0.45
Y4 20 4 2.5 FCU GENERATOR ROOM 1 0.5 0.5 0.9 0.45
B4 20 4 2.5 FCU LIFT LOBBY 1 0.5 0.5 0.9 0.9
R5 20 SPARE
63A ISOLATOR

Y5 20 SPARE
B5 20 4 2.5 FCU GARBAGE ROOM 1 0.5 0.5 0.9 0.45
R6 32 4 2.5 SOCKETS TRANS. & H.V. RM.(RING) 4s 1.0/0.2 1.6 0.5 0.8
Y6 32 4 2.5 SOCKETS ELECT. RM. & LOBBY(RING) 4s 1.0/0.2 1.6 0.5 0.8
B6 32 4 2.5 SOCKETS BMS,LOBBY(EXTERNAL)(RING) 4s 1.0/0.2 1.6 0.5 0.8
R7 32 4 2.5 SOCKETS LIFT LOBBY (RING) 2s 1.0/0.2 1.2 0.5 0.6
GEN. RM. GARBAGE RM.
Y7 32 4 2.5 SOCKETS 4s 1.0/0.2 1.6 0.5 0.8
(RING)
40A RCD
WITH 30mA B7 32 4 2.5 ICP MAIN ENTRANCE 1 0.2 0.2 0.9 0.18
EARTH R8 32 4 2.5 GCP MAIN ENTRANCE 1 0.2 0.2 0.9 0.18
LEAKAGE
Y8 32 4 2.5 FACP MAIN ENTRANCE 1 0.2 0.2 0.9 0.18
SENSETIVITY
B8 32 SPARE
R9 32 SPARE
Y9 32 SPARE
B9 32 SPARE
R10 SPACE
Y10 SPACE
B10 SPACE
TOTAL CONNECTED LOAD= 19.9 kW 6.8 6.8 6.3
TOTAL DIVERSIFIED LOAD= 13.49 kW 67.79% 13.49
Project/Building Name: Main breaker type & rating: 80A ISOLATOR
Address/Location: FLAT No.2 corridor Incomminig cable size/ type: 4C 25 MM2 XLPE/SWA/PVC
Distribution Board No./Ref: DB-F212
Fed from: SMDB-21
Connecte Circuit Load in Watts circuit
Incomer

Phase & Cable


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)
ENTRANCE, KITCHEN
LIGHTS 9 0.1 0.9 0.75 0.675
R1 10 2.5 2.5 &LIVING ROOM
Y1 10 2.5 2.5 LIGHTS WC & STAIRCASE 10 0.1 1 0.75 0.75
BED, FAMILY ROOMS &
LIGHTS 10 0.1 1 0.75 0.75
B1 10 2.5 2.5 BALACONY
FAMILY SITTING &
LIGHTS 15 0.1 1.5 0.75 1.125
R2 15 2.5 2.5 BEDROOM
FAMILY SITTING &
FCU 1 0.5 0.5 0.9 0.45
Y2 15 4 BEDROOM
32A RCD
WITH 100mA B2 10 2.5 2.5 LIGHTS BEDROOM 5 0.1 0.5 0.75 0.375
EARTH R3 15 4 2.5 FCU ENTRANCE LOBBY 1 0.5 0.5 0.9 0.45
LEAKAGE B3 15 4 2.5 FCU BATH ROOM 1 0.5 0.5 0.9 0.45
SENSETIVITY R4 15 4 2.5 FCU BATH ROOM 1 0.5 0.5 0.9 0.45
Y4 15 SPARE 0 0 0
B4 15 4 2.5 FCU BTH ROOM 1 0.5 0.5 0.9 0.45
R5 15 4 2.5 FCU BTH ROOM 1 0.5 0.5 0.9 0.45
Y5 15 SPARE 0 0 0
B5 15 SPARE 0 0 0
80A ISOLATOR

R6 BLANK 0 0 0
Y6 BLANK 0 0 0
B6 BLANK 0 0 0
R7 30 4 2.5 SOCKETS FAMILY SITTING (RING) 7 0.2 2.2 0.5 1.1
Y7 20 4 2.5 WATER HEATER KITCHEN 1 1.5 1.5 0.5 0.75
B7 20 4 2.5 WATER HEATER KITCHEN 1 1.5 1.5 0.5 0.75
R8 30 4 2.5 SOCKETS BED ROOM (RING) 5 0.2 1.8 0.5 0.9
Y8 20 4 2.5 WASHING MACHINE KITCHEN 1 1.5 1.5 0.5 0.75
B8 30 4 2.5 SOCKETS BED ROOM (RING) 5 0.2 1.8 0.5 0.9
R9 20 4 2.5 WATER HEATER BATH ROOM 1 1.5 1.5 0.5 0.75
Y9 20 4 2.5 DISH WASHING KITCHEN 1 1.5 1.5 0.5 0.75
60A RCD
B9 30 4 2.5 SOCKETS FAMILY ROOM (RING) 5 0.2 1.8 0.5 0.9
WITH 30mA
EARTH ENTRANCE LOBBY &
LEAKAGE SOCKETS 3 0.2 1.4 0.5 0.7
R10 20 4 2.5 STORE
SENSETIVITY Y10 30 4 2.5 SOCKETS LIVING ROOM (RING) 7 0.2 2.2 0.5 1.1
B10 30 4 2.5 SOCKETS BED ROOM (RING) 5 0.2 1.8 0.5 0.9
R11 30 SPARE 0 0 0
Y11 30 4 2.5 SOCKETS KITCHEN (RING) 6 0.2 2 0.5 1
B11 30 SPARE 0 0 0
R12 20 SPARE 0 0 0
Y12 20 SPARE 0 0 0
B12 30 SPARE 0 0 0
TOTAL CONNECTED LOAD= 30.9 Kw 10.8 10.7 9.4
TOTAL DIVERSIFIDE LOAD= 11.975 Kw 38.75% 11.975

TYPICAL TO DB-213
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 1st BASEMENT Elect. Rm. Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-B1
Fed from: MDB-EG
circuit
Incomer

Phase & Cable Connected Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of diversity load after
Neutral rating A circuit name / point reference Load per
/RCD No. rating (A) mm² points R Y B factors diversity
size mm² (kW) point (kW)
(kW)
R1 10 2.5 2.5 LIGHTS LIFT LOBBY 8 0.1 0.8 0.9 0.72
Y1 16 2.5 2.5 LIGHTS ETS ROOM 13 0.1 1.3 0.75 0.975
B1 10 2.5 2.5 LIGHTS ELECT. RM., UPSTAND 5 0.1 0.5 0.85 0.425
R2 16 2.5 2.5 LIGHTS PUMP, TEL. RM & UPSTAND 11 0.1 1.1 0.85 0.935
Y2 16 2.5 2.5 LIGHTS PARKING 8 0.1 0.8 0.9 0.72
B2 16 2.5 2.5 LIGHTS PARKING 12 0.1 1.2 0.9 1.08
40A RCD
WITH 100mA R3 16 2.5 2.5 LIGHTS DRIVEWAY 13 0.1 1.3 0.9 1.17
EARTH Y3 20 4 2.5 FCU LIFT LOBBY 1 0.5 0.5 0.9 0.45
LEAKAGE B3 16 2.5 2.5 LIGHTS DRIVEWAY 13 0.1 1.3 0.9 1.17
SENSETIVITY R4 20
40A ISOLATOR

Y4 20 4 2.5 FCU ETS ROOM 1 1 1 0.9 0.9


B4 20 4 2.5 FCU ETS ROOM 1 1 1 0.9 0.9
R5 20 SPARE
Y5 20 SPARE
B5 20 4 2.5 FCU ELECT. ROOM 1 0.5 0.5 0.9 0.45
R6 32 4 2.5 SOCKETS LIFT LOBBY, TEL. RM.(RING) 4s 1.0/0.2 1.6 0.5 0.8
Y6 32 4 2.5 SOCKETS ELECT. RM. & UPSTAND(RING) 4s 1.0/0.2 1.6 0.5 0.8

40A RCD B6 32 4 2.5 SOCKETS ETS ROOM (RING) 4s 1.0/0.2 1.6 0.5 0.8
WITH 30mA R7 32 4 2.5 SOCKETS PARKING (RING) 4s 1.0/0.2 1.6 0.5 0.8
EARTH Y7 32 4 2.5 SOCKETS PUMP ROOM (RING) 2s 1.0/0.2 1.2 0.5 0.6
LEAKAGE
SENSETIVITY B7 32 SPARE
R8 32 SPARE
Y8 32 SPARE
B8 32 SPARE
TOTAL CONNECTED LOAD= 18.9 kW 6.4 6.4 6.1
TOTAL DIVERSIFIED LOAD= 13.695 kW 72.46% 13.695
Project/Building Name: Main breaker type & rating: 32A TP ISOLATOR
Address/Location: 2nd BASEMENT Elect. Rm. Incomminig cable size/ type: 4C,10mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-B2
Fed from: SMDB-EG
circuit
Incomer

Phase & Cable Connected Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of diversity load after
Neutral rating A circuit name / point reference Load per
/RCD No. rating (A) mm² points R Y B factors diversity
size mm² (kW) point (kW)
(kW)
R1 10 2.5 2.5 LIGHTS LIFT LOBBY 8 0.1 0.8 0.9 0.72
Y1 10 2.5 2.5 LIGHTS SERVICE 6 0.1 0.6 0.75 0.45
B1 16 2.5 2.5 LIGHTS PARKING & UPSTAND 12 0.1 1.2 0.9 1.08
R2 10 2.5 2.5 LIGHTS PARKING & UPSTAND 10 0.1 1 0.9 0.9
40A RCD Y2 10 2.5 2.5 LIGHTS PARKING 8 0.1 0.8 0.9 0.72
WITH 100mA B2 16 2.5 2.5 DRIVEWAY 13 0.1 1.3 0.9 1.17
LIGHTS
EARTH
R3 20 4 2.5 FCU LIFT LOBBY 1 0.5 0.5 0.9 0.45
LEAKAGE
32A ISOLATOR

SENSETIVITY Y3 16 2.5 2.5 LIGHTS DRIVEWAY 14 0.1 1.4 0.9 1.26


B3 20 4 2.5 FCU SERVICE 1 0.5 0.5 0.9 0.45
R4 16 SPARE
Y4 20 SPARE
B4 20 SPARE
R5 20 4 2.5 SOCKETS SERVICE (RING) 5s 1.0/0.2 1.8 0.5 0.9
Y5 20 4 2.5 SOCKETS LIFT LOBBY (RING) 4s 1.0/0.2 1.6 0.5 0.8
40A RCD
WITH 30mA B5 20 4 2.5 SOCKETS PARKING (RING) 4s 1.0/0.2 1.6 0.5 0.8
EARTH R6 32 SPARE
LEAKAGE Y6 32 SPARE
SENSETIVITY
B6 32 SPARE
TOTAL CONNECTED LOAD= 13.1 kW 4.1 4.4 4.6
TOTAL DIVERSIFIED LOAD= 9.7 kW 74.05% 9.7
Project/Building Name: Main breaker type & rating: 32A TP ISOLATOR
Address/Location: 3rd BASEMENT Elect. Rm. Incomminig cable size/ type: 4C,10mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-B3
Fed from: SMDB-EG
circuit
Incomer

Phase & Cable Connected Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of diversity load after
Neutral rating A Circuit name / Point reference Load per
/RCD No. rating (A) mm² points R Y B factors diversity
size mm² (kW) point (kW)
(kW)
R1 10 2.5 2.5 LIGHTS LIFT LOBBY 8 0.1 0.8 0.9 0.72
Y1 10 2.5 2.5 LIGHTS SERVICE 7 0.1 0.7 0.75 0.525
B1 16 2.5 2.5 LIGHTS PARKING & UPSTAND 13 0.1 1.3 0.9 1.17
R2 10 2.5 2.5 LIGHTS PARKING & UPSTAND 13 0.1 1.3 0.9 1.17
40A RCD Y2 10 2.5 2.5 LIGHTS DRIVEWAY 13 0.1 1.3 0.9 1.17
WITH 100mA B2 16 2.5 2.5 PARKING 8 0.1 0.8 0.9 0.72
LIGHTS
EARTH
R3 20 4 2.5 LIGHTS DRIVEWAY 12 0.1 1.2 0.9 1.08
LEAKAGE
32A ISOLATOR

SENSETIVITY Y3 16 2.5 2.5 FCU LIFT LOBBY 1 0.5 0.5 0.9 0.45
B3 20 4 2.5 FCU SERVICE 1 0.5 0.5 0.9 0.45
R4 16 SPARE
Y4 20 SPARE
B4 20 SPARE
R5 20 4 2.5 SOCKETS LIFT LOBBY (RING) 4s 1.0/0.2 1.6 0.5 0.8
40A RCD Y5 20 4 2.5 SOCKETS PARKING (RING) 4s 1.0/0.2 1.6 0.5 0.8
WITH 30mA B5 20 4 2.5 SOCKETS SERVICE (RING) 5s 1.0/0.2 1.8 0.5 0.9
EARTH R6 32 SPARE
LEAKAGE
SENSETIVITY Y6 32 SPARE
B6 32 SPARE
TOTAL CONNECTED LOAD= 13.4 kW 4.9 4.1 4.4
TOTAL DIVERSIFIED LOAD= 9.955 kW 74.29% 9.955
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 3rd Fl Elect. Room Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-EM1
Fed from: SMDB-EG
Connecte circuit
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)

LIGHTS 0.1 1 0.75 0.75


R1 10 2.5 2.5 Cord Elc./Tel. (1st Fl) 10
Y1 10 2.5 2.5 LIGHTS Cord Elc./Tel(2nd Fl) 10 0.1 1 0.75 0.75
32A RCD B1 10 2.5 2.5 LIGHTS Cord Elc./Tel(3rd Fl) 10 0.1 1 0.75 0.75
WITH 100mA R2 10 2.5 2.5 LIGHTS Cord Elc./Tel. (4th Fl) 10 0.1 1 0.75 0.75
EARTH Y2 10 SPARE 0 0 0
LEAKAGE
SENSETIVITY B2 10 2.5 2.5 LIGHTS Cord Elc./Tel(6th Fl) 10 0.1 1 0.75 0.75
R3 10 2.5 2.5 LIGHTS Staircase - 1 12 0.1 1.2 0.75 0.9
Y3 16 2.5 2.5 LIGHTS Staircase - 2 12 0.1 1.2 0.75 0.9
B3 10 2.5 2.5 LIGHTS Cord Elc./Tel(5th Fl) 10 0.1 1 0.75 0.75
40A ISOLATOR

R4 20 4 2.5 SOCKETS Elec./Tel. Rm. (1st Fl) 2 0.2 1.2 0.5 0.6
Y4 20 4 2.5 SOCKETS Elec./Tel.Rm (2nd Fl) 2 0.2 1.2 0.5 0.6
B4 20 4 2.5 SOCKETS Elec./Tel.Rm (3rd Fl) 2 0.2 1.2 0.5 0.6
R5 20 4 2.5 SOCKETS Elec./Tel.Rm (4th Fl) 2 0.2 1.2 0.5 0.6
Y5 20 4 2.5 SOCKETS Elec./Tel.Rm (5th Fl) 2 0.2 1.2 0.5 0.6
B5 20 4 2.5 SOCKETS Elec./Tel.Rm (6th Fl) 2 0.2 1.2 0.5 0.6
32A RCD
WITH 30mA R6 20 SPARE 0 0 0
EARTH Y6 20 SPARE 0 0 0
LEAKAGE B6 20 SPARE 0 0 0
SENSETIVITY R7 20 SPARE 0 0 0
Y7 20 SPARE 0 0 0
B7 20 SPARE 0 0 0
R8 20 BLANK 0 0 0
Y8 20 BLANK 0 0 0
B8 20 BLANK 0 0 0
TOTAL CONNECTED LOAD= 15.6 Kw 5.6 4.6 5.4
TOTAL DIVERSIFIDE LOAD= 9.9 Kw 63.46% 9.9
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 9th Fl Elect. Room Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-EM2
Fed from: SMDB-EG
Connecte circuit
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)

LIGHTS 0.1 1 0.75 0.75


R1 10 2.5 2.5 Cord Elc./Tel. (7th Fl) 10
Y1 10 2.5 2.5 LIGHTS Cord Elc./Tel(8th Fl) 10 0.1 1 0.75 0.75
32A RCD B1 10 2.5 2.5 LIGHTS Cord Elc./Tel(9th Fl) 10 0.1 1 0.75 0.75
WITH 100mA R2 10 2.5 2.5 LIGHTS Cord Elc./Tel(10th Fl) 10 0.1 1 0.75 0.75
EARTH Y2 10 SPARE 0 0 0
LEAKAGE
SENSETIVITY B2 10 2.5 2.5 LIGHTS Cord Elc./Tel(11th Fl) 10 0.1 1 0.75 0.75
40A ISOLATOR

R3 10 2.5 2.5 LIGHTS Staircase - 1(7-12) 12 0.1 1.2 0.75 0.9


Y3 16 2.5 2.5 LIGHTS Staircase - 2(7-12) 12 0.1 1.2 0.75 0.9
B3 10 2.5 2.5 LIGHTS Cord Elc./Tel(12th Fl) 10 0.1 1 0.75 0.75
R4 20 4 2.5 SOCKETS Elec./Tel. Rm. (7th Fl) 2 0.2 1.2 0.5 0.6
Y4 20 4 2.5 SOCKETS Elec./Tel.Rm (8th Fl) 2 0.2 1.2 0.5 0.6
B4 20 4 2.5 SOCKETS Elec./Tel.Rm (9th Fl) 2 0.2 1.2 0.5 0.6
32A RCD
WITH 30mA R5 20 4 2.5 SOCKETS Elec./Tel.Rm(10th Fl) 2 0.2 1.2 0.5 0.6
EARTH Y5 20 4 2.5 SOCKETS Elec./Tel.Rm(11th Fl) 2 0.2 1.2 0.5 0.6
LEAKAGE B5 20 4 2.5 SOCKETS Elec./Tel.Rm(12th Fl) 2 0.2 1.2 0.5 0.6
SENSETIVITY R6 20 SPARE 0 0 0
Y6 20 SPARE 0 0 0
B6 20 SPARE 0 0 0
TOTAL CONNECTED LOAD= 15.6 Kw 5.6 4.6 5.4
TOTAL DIVERSIFIDE LOAD= 9.9 Kw 63.46% 9.9
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 15th Fl Elect. Room Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-EM3
Fed from: SMDB-EG
Connecte circuit
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)

LIGHTS 0.1 1 0.75 0.75


R1 10 2.5 2.5 Cord Elc./Tel(13th Fl) 10
Y1 10 2.5 2.5 LIGHTS Cord Elc./Tel(14th Fl) 10 0.1 1 0.75 0.75
32A RCD
WITH 100mA B1 10 2.5 2.5 LIGHTS Cord Elc./Tel(15th Fl) 10 0.1 1 0.75 0.75
EARTH R2 10 2.5 2.5 LIGHTS Cord Elc./Tel(16th Fl) 10 0.1 1 0.75 0.75
LEAKAGE Y2 10 2.5 2.5 LIGHTS Cord Elc./Tel(17th Fl) 10 0 0.75 0
SENSETIVITY B2 2.5 2.5 LIGHTS Staircase - 1(13-18) 12 0.1 1.2 0.75 0.9
40A ISOLATOR

R3 16 2.5 2.5 LIGHTS Staircase - 2(13-18) 12 0.1 1.2 0.75 0.9


Y3 10 2.5 2.5 LIGHTS Cord Elc./Tel(18th Fl) 10 0.1 1 0.75 0.75
B3 20 4 2.5 SOCKETS Elec./Tel. Rm. (13th Fl) 2 0.1 1.1 0.5 0.55
R4 20 4 2.5 SOCKETS Elec./Tel.Rm (14th Fl) 2 0.2 1.2 0.5 0.6
Y4 20 4 2.5 SOCKETS Elec./Tel.Rm (15th Fl) 2 0.2 1.2 0.5 0.6
32A RCD B4 20 4 2.5 SOCKETS Elec./Tel.Rm(16th Fl) 2 0.2 1.2 0.5 0.6
WITH 30mA R5 20 4 2.5 SOCKETS Elec./Tel.Rm(17th Fl) 2 0.2 1.2 0.5 0.6
EARTH
Y5 20 4 2.5 SOCKETS Elec./Tel.Rm(18th Fl) 2 0.2 1.2 0.5 0.6
LEAKAGE
SENSETIVITY B5 20 SPARE 0.2 0 0 0
R6 20 SPARE 0 0 0
Y6 20 SPARE 0 0 0
B6 20 SPARE 0 0 0
TOTAL CONNECTED LOAD= 14.5 Kw 5.6 4.4 4.5
TOTAL DIVERSIFIDE LOAD= 9.1 Kw 62.76% 9.1
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 21st Fl Elect. Room Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-EM4
Fed from: SMDB-EG
Connecte circuit load
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)

LIGHTS 0.1 1 0.75 0.75


R1 10 2.5 2.5 Cord Elc./Tel(19th Fl) 10
Y1 10 2.5 2.5 LIGHTS Cord Elc./Tel(20th Fl) 10 0.1 1 0.75 0.75
32A RCD B1 10 2.5 2.5 LIGHTS Cord Elc./Tel(21st Fl) 8 0.1 0.8 0.75 0.6
WITH 100mA R2 10 2.5 2.5 LIGHTS Cord Elc./Tel(22nd Fl) 5 0.1 0.5 0.75 0.375
EARTH Y2 10 SPARE 0 0 0
LEAKAGE
SENSETIVITY B2 10 2.5 2.5 LIGHTS Stairc-1(20th To Roof) 8 0.1 0.8 0.75 0.6
R3 10 2.5 2.5 8
40A ISOLATOR

LIGHTS Stairc-2(20th To Roof) 0.1 0.8 0.75 0.6


Y3 10 2.5 2.5 SPARE 0 0 0
B3 10 SPARE 0 0 0
R4 20 4 2.5 SOCKETS Elec./Tel.Rm (19th Fl) 2 0.2 1.2 0.5 0.6
Y4 20 4 2.5 SOCKETS Elec./Tel.Rm (20th Fl) 2 0.2 1.2 0.5 0.6
B4 20 4 2.5 SOCKETS Elec./Tel.Rm(21st Fl) 2 0.2 1.2 0.5 0.6
32A RCD
WITH 30mA R5 20 4 2.5 SOCKETS Elec./Tel.Rm(22nd Fl) 2 0.2 1.2 0.5 0.6
EARTH Y5 20 4 2.5 SOCKETS Elec./Tel.Rm(18th Fl) 2 0.2 1.2 0.5 0.6
LEAKAGE B5 20 SPARE 0 0 0
SENSETIVITY
R6 20 SPARE 0 0 0
Y6 20 SPARE 0 0 0
B6 20 SPARE 0 0 0
TOTAL CONNECTED LOAD= 10.9 Kw 4.7 3.4 2.8
TOTAL DIVERSIFIDE LOAD= 6.675 Kw 61.24% 6.675
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 3rd Fl Elect. Room Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-LL1
Fed from: MDB-GSR
Connecte circuit
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)
R1 10 2.5 2.5 LIGHTS Coorridor (1st Flr.) 5 0.1 0.5 0.75 0.375
Y1 10 2.5 2.5 LIGHTS Coorridor (2nd Flr.) 5 0.1 0.5 0.75 0.375
B1 10 2.5 2.5 LIGHTS Coorridor (3rd Flr.) 5 0.1 0.5 0.75 0.375
R2 10 2.5 2.5 LIGHTS Coorridor (4th Flr.) 5 0.1 0.5 0.75 0.375
Y2 16 4 2.5 FCU Corridor (1st Fl) 1 0.5 0.5 0.9 0.45
B2 10 2.5 2.5 LIGHTS Corridor (5th Fl) 5 0.1 0.5 0.75 0.375
R3 10 2.5 2.5 LIGHTS Corridor (6th Fl) 5 0.1 0.5 0.75 0.375
Y3 16 4 2.5 FCU Corridor (2nd Fl) 1 0.5 0.5 0.9 0.45
B3 16 4 2.5 FCU Corridor (3rd Fl) 1 0.5 0.5 0.9 0.45
32A RCD
R4 16 4 2.5 FCU Corridor (4th Fl) 1 0.5 0.5 0.9 0.45
WITH 100mA
EARTH Y4 16 4 2.5 FCU Corridor (5th Fl) 1 0.5 0.5 0.9 0.45
LEAKAGE B4 16 4 2.5 FCU Corridor (6th Fl) 1 0.5 0.5 0.9 0.45
SENSETIVITY R5 16 4 2.5 FCU Corridor (2nd Fl.) 1 0.5 0.5 0.9 0.45
Y5 16 4 2.5 FCU 1 0.5 0.5 0.9 0.45
40A ISOLATOR

Corridor (3rd Fl.)


B5 16 4 2.5 FCU Corridor (4th Fl.) 1 0.5 0.5 0.9 0.45
R6 16 4 2.5 FCU Corridor (5th Fl.) 1 0.5 0.5 0.9 0.45
Y6 16 4 2.5 FCU Corridor (6th Fl.) 1 0.5 0.5 0.9 0.45
B6 16 2.5 2.5 FCU Corridor (1st Fl) 1 0.5 0.5 0.9 0.45
R7 16 SPARE 0 0 0
Y7 20 SPARE 0 0 0
B7 20 4 2.5 SOCKETS Coorridor (1st Flr.) 2 0.2 1.2 0.5 0.6
R8 20 4 2.5 SOCKETS Coorridor (2nd Flr.) 2 0.2 1.2 0.5 0.6
Y8 20 4 2.5 SOCKETS Coorridor (3rd Flr.) 2 0.2 1.2 0.5 0.6
B8 20 4 2.5 SOCKETS Coorridor (4th Flr.) 2 0.2 1.2 0.5 0.6
32A RCD R9 20 4 2.5 SOCKETS Corridor (5th Fl) 2 0.2 1.2 0.5 0.6
WITH 30mA Y9 20 4 2.5 SOCKETS Corridor (6th Fl) 2 0.2 1.2 0.5 0.6
EARTH B9 20 SPARE 0 0 0
LEAKAGE
SENSETIVITY SPARE 0 0 0
R10 20
Y10 20 SPARE 0 0 0
B10 20 SPARE 0 0 0
TOTAL CONNECTED LOAD= 16.2 Kw 5.4 5.4 5.4
TOTAL DIVERSIFIDE LOAD= 11.25 Kw 69.44% 11.25
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 9th Fl Elect. Room Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-LL2
Fed from: MDB-GSR
Connecte circuit
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)
R1 10 2.5 2.5 LIGHTS Coorridor (7th Flr.) 5 0.1 0.5 0.75 0.375
Y1 10 2.5 2.5 LIGHTS Coorridor (8th Flr.) 5 0.1 0.5 0.75 0.375
B1 10 2.5 2.5 LIGHTS Coorridor (9th Flr.) 5 0.1 0.5 0.75 0.375
R2 10 2.5 2.5 LIGHTS Coorridor (10th Flr.) 5 0.1 0.5 0.75 0.375
Y2 16 4 2.5 FCU Corridor (7th Fl) 1 0.5 0.5 0.9 0.45
B2 10 2.5 2.5 LIGHTS Corridor (11th Fl) 5 0.1 0.5 0.75 0.375
R3 10 2.5 2.5 LIGHTS Corridor (12th Fl) 5 0.1 0.5 0.75 0.375
Y3 16 4 2.5 FCU Corridor (8th Fl) 1 0.5 0.5 0.9 0.45
B3 16 4 2.5 FCU Corridor (9th Fl) 1 0.5 0.5 0.9 0.45
32A RCD
WITH 100mA R4 16 4 2.5 FCU Corridor (10th Fl) 1 0.5 0.5 0.9 0.45
EARTH Y4 16 4 2.5 FCU Corridor (11th Fl) 1 0.5 0.5 0.9 0.45
LEAKAGE B4 16 4 2.5 FCU Corridor (12th Fl) 1 0.5 0.5 0.9 0.45
SENSETIVITY R5 16 4 2.5 FCU Corridor (8th Fl.) 1 0.5 0.5 0.9 0.45
Y5 16 4 2.5 FCU Corridor (9th Fl.) 1 0.5 0.5 0.9 0.45
40A ISOLATOR

B5 16 4 2.5 FCU Corridor (10th Fl.) 1 0.5 0.5 0.9 0.45


R6 16 4 2.5 FCU Corridor (11th Fl.) 1 0.5 0.5 0.9 0.45
Y6 16 4 2.5 FCU Corridor (12th Fl.) 1 0.5 0.5 0.9 0.45
B6 16 2.5 2.5 FCU Corridor (7th Fl) 1 0.5 0.5 0.9 0.45
R7 20 SPARE 0 0 0
Y7 20 SPARE 0 0 0
B7 20 4 2.5 SOCKETS Coorridor (7th Flr.) 2 0.2 1.2 0.5 0.6
R8 20 4 2.5 SOCKETS Coorridor (8th Flr.) 2 0.2 1.2 0.5 0.6
Y8 20 4 2.5 SOCKETS Coorridor (9th Flr.) 2 0.2 1.2 0.5 0.6
B8 20 4 2.5 SOCKETS Coorridor (10th Flr.) 2 0.2 1.2 0.5 0.6
32A RCD R9 20 4 2.5 SOCKETS Corridor (11th Fl) 2 0.2 1.2 0.5 0.6
WITH 30mA Y9 20 4 2.5 SOCKETS Corridor (12th Fl) 2 0.2 1.2 0.5 0.6
EARTH B9 20 SPARE 0 0 0
LEAKAGE
SENSETIVITY SPARE 0 0 0
R10 20
Y10 20 SPARE 0 0 0
B10 20 SPARE 0 0 0
TOTAL CONNECTED LOAD= 16.2 Kw 5.4 5.4 5.4
TOTAL DIVERSIFIDE LOAD= 11.25 Kw 69.44% 11.25
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: 15th Fl Elect. Room Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-LL3
Fed from: MDB-GSR
Connecte circuit
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)
R1 10 2.5 2.5 LIGHTS Coorridor (13th Flr.) 5 0.1 0.5 0.75 0.375
Y1 10 2.5 2.5 LIGHTS Coorridor (14th Flr.) 5 0.1 0.5 0.75 0.375
B1 10 2.5 2.5 LIGHTS Coorridor (15th Flr.) 5 0.1 0.5 0.75 0.375
R2 10 2.5 2.5 LIGHTS Coorridor (16th Flr.) 5 0.1 0.5 0.75 0.375
Y2 16 4 2.5 FCU Corridor (13th Fl) 1 0.5 0.5 0.9 0.45
B2 10 2.5 2.5 LIGHTS Corridor (17th Fl) 5 0.1 0.5 0.75 0.375
R3 10 2.5 2.5 LIGHTS Corridor (18th Fl) 5 0.1 0.5 0.75 0.375
Y3 16 4 2.5 FCU Corridor (14th Fl) 1 0.5 0.5 0.9 0.45
32A RCD B3 16 4 2.5 FCU Corridor (15th Fl) 1 0.5 0.5 0.9 0.45
WITH 100mA R4 16 4 2.5 FCU Corridor (16th Fl) 1 0.5 0.5 0.9 0.45
EARTH Y4 16 4 2.5 FCU Corridor (17th Fl) 1 0.5 0.5 0.9 0.45
LEAKAGE B4 16 4 2.5 FCU Corridor (18th Fl) 1 0.5 0.5 0.9 0.45
SENSETIVITY
R5 16 4 2.5 FCU Corridor (14th Fl.) 1 0.5 0.5 0.9 0.45
40A ISOLATOR

Y5 16 4 2.5 FCU Corridor (15th Fl.) 1 0.5 0.5 0.9 0.45


B5 16 4 2.5 FCU Corridor (16th Fl.) 1 0.5 0.5 0.9 0.45
R6 16 4 2.5 FCU Corridor (17th Fl.) 1 0.5 0.5 0.9 0.45
Y6 16 4 2.5 FCU Corridor (18th Fl.) 1 0.5 0.5 0.9 0.45
B6 16 2.5 2.5 FCU Corridor (13th Fl) 1 0.5 0.5 0.9 0.45
R7 20 SPARE 0 0 0
Y7 20 SPARE 0 0 0
B7 20 4 2.5 SOCKETS Coorridor (13th Flr.) 2 0.2 1.2 0.5 0.6
R8 20 4 2.5 SOCKETS Coorridor (14th Flr.) 2 0.2 1.2 0.5 0.6
Y8 20 4 2.5 SOCKETS Coorridor (15th Flr.) 2 0.2 1.2 0.5 0.6
B8 20 4 2.5 SOCKETS Coorridor (16th Flr.) 2 0.2 1.2 0.5 0.6
32A RCD R9 20 4 2.5 SOCKETS Corridor (17th Fl) 2 0.2 1.2 0.5 0.6
WITH 30mA Y9 20 4 2.5 SOCKETS Corridor (18th Fl) 2 0.2 1.2 0.5 0.6
EARTH B9 20 SPARE 0 0 0
LEAKAGE
SENSETIVITY SPARE 0 0 0
R10 20
Y10 20 SPARE 0 0 0
B10 20 SPARE 0 0 0
TOTAL CONNECTED LOAD= 16.2 Kw 5.4 5.4 5.4
TOTAL DIVERSIFIDE LOAD= 11.25 Kw 69.44% 11.25
Project/Building Name: Main breaker type & rating: 32A TP ISOLATOR
Address/Location: 21st Fl Elect. Room Incomminig cable size/ type: 4C,10mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-LL4
Fed from: MDB-GSR
Connecte circuit
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)
R1 10 2.5 2.5 LIGHTS Coorridor (19th Flr.) 5 0.1 0.5 0.75 0.375
Y1 10 2.5 2.5 LIGHTS Coorridor (20th Flr.) 5 0.1 0.5 0.75 0.375
B1 10 2.5 2.5 LIGHTS Coorridor (21st Flr.) 3 0.1 0.3 0.75 0.225
R2 10 2.5 2.5 LIGHTS Coorridor (22nd Flr.) 3 0.1 0.3 0.75 0.225
32A RCD Y2 16 4 2.5 FCU Coorridor (19th Flr.) 1 0.5 0.5 0.9 0.45
WITH 100mA B2 10 2.5 2.5 FCU Coorridor (20th Flr.) 1 0.5 0.5 0.9 0.45
EARTH R3 10 2.5 2.5 1
FCU Coorridor (21st Flr.) 0.5 0.5 0.9 0.45
LEAKAGE
SENSETIVITY Y3 16 4 2.5 FCU Coorridor (22nd Flr.) 1 0.5 0.5 0.9 0.45
B3 16 4 2.5 FCU Coorridor (19th Flr.) 1 0.5 0.5 0.9 0.45
R4 16 4 2.5 FCU Coorridor (20th Flr.) 1 0.5 0.5 0.9 0.45
32A ISOLATOR

Y4 16 4 2.5 FCU Coorridor (21st Flr.) 1 0.5 0.5 0.9 0.45


B4 16 SPARE 0 0 0
R5 20 4 2.5 SOCKETS Coorridor (19th Flr.) 2 0.2 1.2 0.5 0.6
Y5 20 4 2.5 SOCKETS Coorridor (20th Flr.) 2 0.2 1.2 0.5 0.6
B5 20 4 2.5 SOCKETS Coorridor (21st Flr.) 2 0.2 1.2 0.5 0.6
R6 20 4 2.5 SOCKETS Coorridor (22nd Flr.) 2 0.2 1.2 0.5 0.6
32A RCD Y6 20 4 2.5 SPARE 0 0 0
WITH 30mA B6 20 4 2.5 SPARE 0 0 0
EARTH
LEAKAGE R7 2 2.5 2.5 SPARE 0 0 0
SENSETIVITY Y7 20 SPARE 0 0 0
B7 20 SPARE 0 0 0
R8 20 BLANK 0 0 0
Y8 20 BLANK 0 0 0
B8 20 BLANK 0 0 0
TOTAL CONNECTED LOAD= 9.9 Kw 4.2 3.2 2.5
TOTAL DIVERSIFIDE LOAD= 6.75 Kw 68.18% 6.75
Project/Building Name: Main breaker type & rating: 40A TP ISOLATOR
Address/Location: ELECTRICAL ROOM ON ROOF Incomminig cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-R1
Fed from: SMDB-11
Connecte circuit
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)
R1 10 SPARE 0 0 0
PUMP ROOMS &
LIGHTS 4 0.1 0.4 0.75 0.3
Y1 10 2.5 2.5 FILTERATION ROOM
B1 10 2.5 2.5 LIGHTS LIFTS LOBBY 3 0.1 0.3 0.75 0.225
R2 10 SPARE 0 0 0
16A RCD Y2 10 2.5 2.5 LIGHTS LOBBY 2 0.1 0.2 0.75 0.15
WITH 100mA B2 10 2.5 2.5 LIGHTS GUARD ROOM 4 0.1 0.4 0.75 0.3
EARTH
R3 16 4 2.5 FCU LIFTS MACHINE ROOM 1 0.5 0.5 0.9 0.45
LEAKAGE
SENSETIVITY Y3 16 4 2.5 FCU LIFTS LOBBY 1 0.5 0.5 0.9 0.45
B3 16 4 2.5 FCU LOBBY 1 0.5 0.5 0.9 0.45
40A ISOLATOR

R4 16 SPARE 0 0 0
Y4 16 SPARE 0 0 0
B4 16 4 2.5 FCU BTH ROOM 1 1.5 1.5 0.9 1.35
R5 20 4 2.5 SOCKETS LIFTS MACHINE ROOM 2 0.2 1.2 0.5 0.6
Y5 20 4 2.5 SOCKETS PUMP ROOMS 2 0.2 1.2 0.5 0.6
B5 30 4 2.5 SOCKETS GUARD ROOM 4 0.2 1.6 0.5 0.8
R6 SPARE 0 0 0
Y6 20 4 2.5 SOCKETS FILTERATION ROOM 2 0.2 1.2 0.5 0.6
32A RCD
WITH 30mA B6 20 4 2.5 ISOLATOR CRADLE 1 1.5 1.5 1 1.5
EARTH R7 30 SPARE 0 0 0
LEAKAGE Y7 30 SPARE 0 0 0
SENSETIVITY B7 20 SPARE 0 0 0
R8 BLANK 0 0 0
Y8 BLANK 0 0 0
B8 BLANK 0 0 0
TOTAL CONNECTED LOAD= 11 Kw 1.7 3.5 5.8
TOTAL DIVERSIFIDE LOAD= 7.775 Kw 70.68% 7.775
Project/Building Name: Main breaker type & rating: 32A TP ISOLATOR
Address/Location: ROOF ELECTRICAL ROOM Incomminig cable size/ type: 4C,10mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: DB-ER1
Fed from: SMDB-EG
Connecte circuit
Incomer

Phase & Cable Circuit Load in Watts


Busbar section CCT ref. MCB Earth sise No. of d Load diversity load after
Neutral rating A circuit name / point reference
/RCD No. rating (A) mm² points per point R Y B factors diversity
size mm² (kW)
(kW) (kW)
LIGHTS LIFT MACHINE, TELE &
6 0.1 0.6 0.75 0.45
R1 10 2.5 2.5 ELECTRICAL ROOMS
16A RCD
WITH 100mA Y1 10 2.5 2.5 LIGHTS LOBBY 2 0.1 0.2 0.75 0.15
EARTH B1 10 2.5 2.5 LIGHTS LIFT LOBBY 2 0.1 0.2 0.75 0.15
LEAKAGE R2 10 SPARE 0 0 0
SENSETIVITY Y2 10 SPARE 0 0 0
B2 10 SPARE 0 0 0
SOCKETS TEL. ELECTRICAL ROOM
32A ISOLATOR

4 0.2 1.6 0.5 0.8


R3 30 4 2.5 (RING)
Y3 30 SPARE 0 0 0
B3 20 4 2.5 ISOLATOR BOOSTER PUMP 1 1.5 1.5 1 1.5
R4 30 SPARE 0 0 0
32A RCD
WITH 30mA Y4 20 SPARE 0 0 0
EARTH B4 20 SPARE 0 0 0
LEAKAGE R5
SENSETIVITY Y5 16 4 2.5 ISOLATOR ETISALAT 1 3 1 1 1 1 1
B5
R6 BLANK 0 0 0
Y6 BLANK 0 0 0
B6 BLANK 0 0 0
TOTAL CONNECTED LOAD= 7.1 Kw 3.2 1.2 2.7
TOTAL DIVERSIFIDE LOAD= 4.05 Kw 57.04% 4.05
Project/Building Name: Main breaker type & rating: 100A TP MCCB MAIN
Address/Location: FIRST FLOOR ELECTRICAL ROOM Incoming cable size/ type: 4C,35mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: SMDB-1
Fed from: LV-2
circuit
Incomer

Cable Connected Circuit Load in Watts


MCCB

MCCB Phase & Neutral Earth sise diversity load after


CCT ref. No. rating A circuit name / point reference Load per
rating (A) size mm² mm² R Y B factors diversity
(kW) point (kW)
(kW)

4C 16MM2
1RYB 63 1C 16 DB-F11 19.7 6.4 8.6 4.7 58.25% 11.475
XLPE/SWA/PVC
MM2 PVC

4C 16MM2
2RYB 40 1C 16 DB-F12 14.8 4.7 5.5 4.6 57.26% 8.475
XLPE/SWA/PVC
MM2 PVC

4C 16MM2
3RYB 63 1C 16 DB-F13 21 8.6 6.1 6.3 41.43% 8.7
XLPE/SWA/PVC
MM2 PVC

4C 16MM2
4RYB 63 1C 16 DB-F14 21 6.3 6.1 8.6 41.43% 8.7
XLPE/SWA/PVC
MM2 PVC
100A

4C 16MM2
5RYB 40 1C 16 DB-F15 14.8 4.7 4.6 5.5 57.26% 8.475
XLPE/SWA/PVC
MM2 PVC

6RYB 40 SPARE

7RYB 63 SPARE

8RYB BLANK

TOTAL CONNECTED LOAD= 91.3 Kw 30.7 30.9 29.7


TOTAL DIVERSIFIDE LOAD= 41.2425 Kw 45.17% 45.825

TYPICAL TO SMDB-21, SMDB-31, SMDB-41, SMDB-51, SMDB-61, SMDB-71, SMDB-81, SMDB-91, SMDB-101, SMD-111, SMDB-121, SMDB-131, SMDB-141,
SMDB-151, SMDB-161, SMDB171, SMDB-181, SMDB-191, SMDB-201
Project/Building Name: Main breaker type & rating: 100A TP MCCB MAIN
Address/Location: 21TH FLOOR ELECTRICAL ROOM Incoming cable size/ type: 4C,35mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: SMDB-211
Fed from: BUSBAR - 2
circuit
Incomer

Cable Connected Circuit Load in Watts


MCCB

MCCB Phase & Neutral Earth sise diversity load after


CCT ref. No. rating A circuit name / point reference Load per
rating (A) size mm² mm² R Y B factors diversity
(kW) point (kW)
(kW)

4C 16MM2 1C 16
1RYB 60 DB-F211 21 6.1 8.6 6.3 41.43% 8.7
XLPE/SWA/PVC MM2 PVC

4C 25MM2 1C 16
2RYB 80 DB-F212 30.9 10.8 10.7 9.4 38.75% 11.975
XLPE/SWA/PVC MM2 PVC

4C 25MM2 1C 16
3RYB 80 DB-F213 30.9 10.8 10.7 9.4 38.75% 11.975
XLPE/SWA/PVC MM2 PVC
100A

4C 16MM2 1C 16
4RYB 60 DB-F214 21 6.3 6.1 8.6 41.43% 8.7
XLPE/SWA/PVC MM2 PVC

5RYB 80 SPARE

6RYB 60 SPARE

TOTAL CONNECTED LOAD= 103.8 Kw 34 36.1 33.7


TOTAL DIVERSIFIDE LOAD= 37.215 Kw 35.85% 41.35

TYPICAL TO SMDB-21, SMDB-31, SMDB-41, SMDB-51, SMDB-61, SMDB-71, SMDB-81, SMDB-91, SMDB-101, SMD-111, SMDB-121, SMDB-131, SMDB-141,
SMDB-151, SMDB-161, SMDB171, SMDB-181, SMDB-191, SMDB-201
Project/Building Name: Main breaker type & rating: 40A TP MCCB MAIN
Address/Location: 22TH FLOOR ELECTRICAL ROOM Incoming cable size/ type: 4C,16mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: SMDB-1
Fed from: BUSBAR - 2
circuit
Incomer

Cable Connected Circuit Load in Watts


MCCB

MCCB Phase & Neutral Earth sise diversity load after


CCT ref. No. rating A circuit name / point reference Load per
rating (A) size mm² mm² R Y B factors diversity
(kW) point (kW)
(kW)

4C 16MM2
1RYB 60 1C 16 DB-F221 21 8.6 6.1 6.3 41.43% 8.7
XLPE/SWA/PVC
MM2 PVC

4C 16MM2
2RYB 60 1C 16 DB-F224 21 8.6 6.1 6.3 41.43% 8.7
XLPE/SWA/PVC
MM2 PVC
40A

3RYB 80 SPARE

4RYB 60 SPARE

TOTAL CONNECTED LOAD= 42 Kw 17.2 12.2 12.6


TOTAL DIVERSIFIDE LOAD= 15.66 Kw 37.29% 17.4

TYPICAL TO SMDB-21, SMDB-31, SMDB-41, SMDB-51, SMDB-61, SMDB-71, SMDB-81, SMDB-91, SMDB-101, SMD-111, SMDB-121, SMDB-131, SMDB-141,
SMDB-151, SMDB-161, SMDB171, SMDB-181, SMDB-191, SMDB-201
Project/Building Name: Main breaker type & rating: 150A TP MCCB MAIN
Address/Location: ROOF FLOOR ELECTRICAL ROOM Incoming cable size/ type: 4C,50mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: SMDB-ER1
Fed from: SMDB-EG
circuit
Incomer

Cable Connected Circuit Load in Watts


MCCB

MCCB Phase & Neutral Earth sise diversity load after


CCT ref. No. rating A circuit name / point reference Load per
rating (A) size mm² mm² R Y B factors diversity
(kW) point (kW)
(kW)

4C 16MM2
1RYB 60 1C 16 FAHU 20 6.7 6.6667 6.6667 100.00% 20
XLPE/SWA/PVC
MM2 PVC

4C 16MM2
2RYB 60 1C 16 FAHU 20 6.7 6.6667 6.6667 100.00% 20
XLPE/SWA/PVC
MM2 PVC

4C 16MM2
3RYB 40 1C 16 PRESSURIZED FAN 15 5.0 5 5 100.00% 15
XLPE/SWA/PVC
MM2 PVC
150A

4C 16MM2
4RYB 40 1C 16 PRESSURIZED FAN 15 5.0 5 5 100.00% 15
XLPE/SWA/PVC
MM2 PVC

5RYB 60 SPARE

6RYB 40 SPARE

TOTAL CONNECTED LOAD= 70 Kw 23.3333 23.333 23.333


TOTAL DIVERSIFIDE LOAD= 63 Kw 90.00% 70

TYPICAL TO SMDB-21, SMDB-31, SMDB-41, SMDB-51, SMDB-61, SMDB-71, SMDB-81, SMDB-91, SMDB-101, SMD-111, SMDB-121, SMDB-131, SMDB-141,
SMDB-151, SMDB-161, SMDB171, SMDB-181, SMDB-191, SMDB-201
Project/Building Name: Main breaker type & rating: 600A TP MCCB MAIN
Address/Location: ELECTRICAL ROOM GROUND FLOOR Incoming cable size/ type: 2X4C 150mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: SMDB-EG
Fed from: MDB-GSR
circuit
Incomer

Cable Connected Circuit Load in Watts


MCCB

MCCB Phase & Neutral Earth sise diversity load after


CCT ref. No. rating A circuit name / point reference Load per
rating (A) size mm² mm² R Y B factors diversity
(kW) point (kW)
(kW)
1C
4C 35MM2
1RYB 100 25MM2 TRANS. PUMP 40 13.3 13.3 13.3 100.0% 40
XLPE/SWA/PVC
PVC
1C
4C 16MM2
2RYB 60 16MM2 DB-B1 18.9 6.4 6.4 6.1 72.5% 13.7
XLPE/SWA/PVC
PVC
1C
4C 16MM2
3RYB 40 16MM2 DB-B2 13.1 4.1 4.4 4.6 74.0% 9.7
XLPE/SWA/PVC
PVC
1C
4C 16MM2
4RYB 40 16MM2 DB-B3 13.4 4.9 4.1 4.4 74.3% 10.0
XLPE/SWA/PVC
PVC
1C
4C 16MM2
5RYB 60 16MM2 DB-GF 19.9 6.8 6.8 6.3 67.8% 13.5
XLPE/SWA/PVC
PVC
1C
4C 16MM2
6RYB 40 16MM2 DB-EM1 15.6 5.6 4.6 5.4 63.5% 9.9
XLPE/SWA/PVC
PVC
1C
4C 16MM2
7RYB 40 16MM2 DB-EM2 15.6 5.6 4.6 5.4 63.5% 9.9
XLPE/SWA/PVC
PVC
1C
4C 16MM2
8RYB 40 16MM2 DB-EM3 14.5 5.6 4.4 4.5 62.8% 9.1
XLPE/SWA/PVC
PVC
400A

1C
4C 16MM2
9RYB 40 16MM2 DB-EM4 10.9 4.7 3.4 2.8 61.2% 6.7
XLPE/SWA/PVC
PVC
1C
4C 16MM2
10RYB 60 16MM2 LIFT-1 25 8.3 8.3 8.3 100.0% 25
XLPE/SWA/PVC
PVC
1C
4C 16MM2
11RYB 60 16MM2 LIFT-2 25 8.3 8.3 8.3 100.0% 25
XLPE/SWA/PVC
PVC
1C
4C 16MM2
12RYB 60 16MM2 LIFT-3 25 8.3 8.3 8.3 100.0% 25
XLPE/SWA/PVC
PVC
1C
4C 10MM2
13RYB 30 10MM2 DB-ER1 7.1 3.2 1.2 2.7 57.04% 4.05
XLPE/SWA/PVC
PVC
1C
4C 50MM2
14RYB 150 25MM2 SMDB-ER1 70 23.3 23.3 23.3 90.00% 63
XLPE/SWA/PVC
PVC

15RYB 40 SPARE

16RYB BLANK

TOTAL CONNECTED LOAD= 314 Kw 108.567 101.57 103.87


TOTAL DIVERSIFIDE LOAD= 238.0185 Kw 75.80% 264.465
Project/Building Name: Main breaker type & rating: 600A TP MCCB MAIN
Address/Location: ELECTRICAL ROOM GROUND FLOOR Incoming cable size/ type: 2X4C,150mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: MDB-GSR
Fed from: LV
circuit
Incomer

Cable Connected Circuit Load in Watts


MCCB

MCCB Phase & Neutral Earth sise diversity load after


CCT ref. No. rating A circuit name / point reference Load per
rating (A) size mm² mm² R Y B factors diversity
(kW) point (kW)
(kW)
1C
4C 16MM2
1RYB 40 16MM2 DB-LL1 16.2 5.4 5.4 5.4 69.4% 11.25
XLPE/SWA/PVC
PVC
1C
4C 16MM2
2RYB 40 16MM2 DB-LL2 16.2 5.4 5.4 5.4 69.4% 11.3
XLPE/SWA/PVC
PVC
1C
4C 16MM2
3RYB 40 16MM2 DB-LL3 16.2 5.4 5.4 5.4 69.4% 11.3
XLPE/SWA/PVC
PVC
1C
4C 10MM2
4RYB 30 10MM2 DB-LL4 9.9 4.2 3.2 2.5 68.2% 6.8
XLPE/SWA/PVC
PVC
600A

1C
4C 16MM2
5RYB 40 16MM2 DB-R1 11 1.7 3.5 5.8 70.7% 7.8
XLPE/SWA/PVC
PVC
1C
4C 240MM2
6RYB 400 120MM2 SMDB-EG 314 108.567 101.57 103.87 75.8% 238.0
XLPE/SWA/PVC
PVC

7RYB 40 SPARE

8RYB 30 SPARE

TOTAL CONNECTED LOAD= 383.5 Kw 130.7 124.5 128.4


TOTAL DIVERSIFIDE LOAD= 257.66415 Kw 67.19% 286.2935
Project/Building Name: Main breaker type & rating: 1600A TP ACB MAIN + 500mA ELR
Address/Location: ELECTRICAL ROOM GROUND FLOOR Incoming cable size/ type: 8X1C 630 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: LV-1
Fed from: TR-1 Connecte circuit
Phase & Cable Circuit Load in Watts
CCT ref. MCCB Earth sise circuit name / point d Load diversity load after
Inco
mer
MC
CB

Neutral rating A
No. rating (A) mm² reference per point R Y B factors diversity
size mm² (kW)
(kW) (kW)
1RYB 1000 1000A BUS BAR 913 307.0 309.0 297.0 45.2% 412.4

2X4C
2C
150MM2
2RYB 600 75MM2 MDB-SER 383.5 130.7 124.5 128.4 67.2% 257.7
XLPE/SW
1250A

PVC
A/PVC

3RYB 600 SPARE

4RYB BLANK

TOTAL CONNECTED LOAD= 1296.5 Kw 437.7 433.5 425.4


TOTAL DIVERSIFIDE LOAD= 603.0802 Kw 46.52% 670.0892
Project/Building Name: Main breaker type & rating: 1600A TP ACB MAIN + 500mA ELR
Address/Location: ELECTRICAL ROOM GROUND FLOOR Incoming cable size/ type: 8X1C 630mm2 XLPE/SWA/PVC/CABLE
Distribution Board No./Ref: LV-2
Fed from: TR-2
circuit
Incomer

Cable Connected Circuit Load in Watts


MCCB

MCCB Phase & Neutral Earth sise diversity load after


CCT ref. No. rating A circuit name / point reference Load per
rating (A) size mm² mm² R Y B factors diversity
(kW) point (kW)
(kW)
1C
4C 35MM2
1RYB 100 25MM2 SMDB-1 91.3 30.7 30.9 29.7 45.2% 41.2
XLPE/SWA/PVC
PVC
1C
4C 35MM2
2RYB 100 25MM2 SMDB-2 91.3 30.7 30.9 29.7 45.2% 41.2
XLPE/SWA/PVC
PVC

3RYB 1000 1000A BUS BAR 876.2 296.8 295.5 283.9 53.1% 465.3
600A

1C
4C 95MM2
4RYB 200 50MM2 FIRE FIGHTING PUMP 75 25 25 25 100.0% 75.0
XLPE/SWA/PVC
PVC

5RYB 200 SPARE

6RYB 100 SPARE

TOTAL CONNECTED LOAD= 1133.8 Kw 383.2 382.3 368.3


TOTAL DIVERSIFIDE LOAD= 560.5065 Kw 49.44% 622.785

Das könnte Ihnen auch gefallen