Abstract—Voltage and current unbalance problems of traction substations are designed so that that when loads
power networks due to AC electrified railway systems on the zones of a traction substations are the same and
are studied and their influences such as the voltage equal i.e. when I1=I2 as shown in Fig. 2, the unbalance
unbalance factor and the current negative sequence impact injected to the utility grid will be minimized
contribution factor injected to the network are calculated. except for the low-cost configuration case in which the
Several methods can be used for reducing the power zones are of the same phase. A typical load profile of a
quality unbalance problems which have been proposed high-speed railway is also shown in Fig. 3.
and the best of them is chosen by comparing the results
of their unbalance and current negative sequence
contribution factors.
Index Terms— Electrified railway, Power distribution
system, Voltage unbalance, Current negative sequence.
1. Introduction
a)
7. Conclusion
Fig. 10. Single line diagram of the power distribution In this paper, the unbalanced power quality problems of
system feeding the traction system the AC electrified railway systems including the voltage
unbalance factor and the current negative sequence
Two parallel transformers are used in the main traction distribution factor injected to the AC network were
substations, each with the rating of 15 MW. The studied. Different applicable solutions are utilized for
transformers are fed from two-phase source and a single reducing these problems which have been proposed and
studied. Comparing the unbalanced factor and current Voltage unbalance is due to the voltage negative
negative sequence contribution factor for each of the sequence which can be calculated by dividing the
solutions, the best way of limiting the unbalance power negative sequence of voltage to its positive sequence as
quality problems of the AC network is chosen. shown by 2.
V−
%ε v = (3)
References V+
The currents Ia, Ib and Ic as the unbalanced feeding
[1] B. Bhargava, Railway electrification systems and currents of the traction substation can be converted to
configurations, IEEE Power Engineering Society three balanced currents of I+, I- and I0 based on the
Summer Meeting, Vol. 1, pp. 445-450, July 1999. theory of symmetrical component analysis with their
[2] T.H. Chen, Simplified models of electric railway equivalent balanced Z+, Z- and Z0 as the positive,
substation for three-phase power-flow studies, IEEE negative and zero sequence impedance of the Thevenin
Conf. on Industry Applications, Vol. 3, pp. 2245-2248, equivalent and E+ as the open-circuit voltage at the
October 1994. input, respectively as determined by 3 and shown in Fig.
[3] A.F. Imece, Utility impact and power quality issues, 5.
IEEE Power Engineering Society Summer Meeting,
pp. 434–438, Canada, July 1999.
[4] S.L. Chen, R.J. Li, P.H. His, Traction system
unbalance problem, Analysis methodologies, IEEE
Trans. on Power Delivery, Vol. 19, No. 4, pp. 1877-
1883, October 2004.
[5] G.R. Zaker, S.H. Hosseini, Controlling the
unbalance of electrified railways and buses in Fig. 12. Electrical circuit equivalent of the power
distribution networks, in Persian, 3rd Iranian Int. Conf. network feeding the traction system
on Electrical Engineering, Tehran, May 1995.
⎡I + ⎤ ⎡1 1 1 ⎤⎡I a ⎤
Appendix ⎢ ⎥ 1⎢ ⎥⎢ ⎥
⎢ ⎥ 3 ⎢1 a
I − = a 2 ⎥ ⎢ I b ⎥ , a = 1e j120° (4)
⎢⎣ I 0 ⎥⎦ ⎢⎣1 a 2 a ⎥⎦ ⎢⎣ I c ⎥⎦
For a balanced power network, the three phases of the
current and voltage waveforms have equal magnitudes
with an exact phase difference of 120 degrees.
Connecting a single-phase or an unbalanced three-phase
load to the network, the current and voltage waveforms
would be unbalanced. The voltage unbalanced factor of a
single phase load with the power rating of Sn and the
short circuit rating of Scc is equal to:
Sn
%ε v = (2)
SS
For example, the unbalanced voltage factor of an AC
Fig. 13. Sequence network of the grid utility feeding the
electrified railway system considered as an unbalanced
traction substation
single-phase load, with the power rating of 10 MVA and
the short circuit rating of 1000 MVA, is about 1%.