Sie sind auf Seite 1von 2

DC POWER SYSTEMS

Smart Series

Smart SYS E2121300R48 Embedded Power System

Features Introduction
19’’2U sub-rack, easy to be embedded into all Smart SYS E2121300R48 system is a compact
standard telecom equipment and intelligent power system, It can house up to
4*2KW rectifiers and 1*SC500 controller
Up to 8kW system capacity
Up to 0.99 power factor Dry contact use front access and front
operation.AC input and DC output use rear
Intelligent fan-cooling access and rear connection.
Rectifier modules hot-swap With compact design, easy installation
N+1 rectifier module redundancy Two levels Low Voltage Disconnect (LVD)
Advanced batteries monitoring and protection
management
Two battery MCBs
ECO mode
Compatible with rectifiers of the same size
High power density

Applications Applicable Standards


Fiber optic network IEC 60950-1 EN 60950-1
Electrical
Access network UL 60950-1

Satellite communication ground station EMC EN 55022 Class A

Transmission equipment ETSI EN 300 019-2


Environmental ETSI EN 300 132-2
Mobile communication RoHS
ESS

Rev 2.1, 2017.11.02 1 Beijing Dynamic Power Co., Ltd www.dpc.com.cn


DC POWER SYSTEMS
Smart Series

Input Options
LLVD:1*150A/2P
AC Input 85Vac-300Vac
BLVD:1*150A/2P
DC Distribution 2 MCBs for battery, the rating of
Input Current load MCB is 100A
≤12A (Per rectifier)
BLVD & LLVD1,
Rear operation and rear connection
Frequency 45~65Hz
Connect to backplane directly
<5%@full load AC Distribution
Rear access and rear connection
THDi <10%@half load
Rated input and output voltage
Low Voltage 150A Bi-stable contactors should
Disconnect be used as BLVD &LLVD1
Output
Output Short-circuit protection
Output Voltage -53.5V Rated output voltage Protection Overload protection

SP I 48/2000
-53.5V float voltage
Output Current -56.4V boost voltage
SP II 48/2000
≥120A Rectifier SP II 48/2000HE
SP I 48/3000
Voltage SP II 48/3000HE
Regulation ≤±1%

Current Sharing ≤±5%


Monitoring
Efficiency ≥92%

Operation information
acquirements, battery and
Ripple and Noise ≤200mV Peak-Peak Function system management,
system alarm, communicate with
Psophometric ≤2mV control center related ports
Noise

Controller SC500
Other Specifications Battery 2 x Battery mid-point
Mid-Point
Operating -40℃ to +70℃ (-40℉ to +158℉)
Temperature
Dry Contact 6 relay outputs, NO+COM
Storage -40℃ to +85℃ (-40℉ to +185℉)
Temperature Digital Input 6 DI

Operating: ≤95% non- condensing Interface LCD


Humidity
Storage: ≤99% non-condensing Temp Sensor 1

Dimensions(mm) 482.6W(19”) x 88.1 H (2U)x 395D


Weight ≤10kg(Without rectifier)

Rev 2.1, 2017.11.02 2 Beijing Dynamic Power Co., Ltd www.dpc.com.cn