Single Type Protective Relays

July, 2011

TN5A0498c
Table of Contents

Protective relays are designed DUT series single type digital protective relays ................................................................. 2
to detect electrical faults,  Definition of terms used .................................................................................................. 7
abnormal running conditions  Identifications .................................................................................................................. 8
and other troubles in the system  Previous and new type list ............................................................................................ 10
and to isolate defective circuits DRAW series protective relays ......................................................................................... 17
and equipment before the TELR series control relays ............................................................................................... 18

possibilities of damage occurs. DUT series protective relays


 Digital type ground overcurrent relay ......................................................................... 1−1
For this purpose, relays
  DUT□EH, DUT□ET, DUT□EN, DUT□EM
generally work in combination
 Digital type overcurrent relay ...................................................................................... 1−2
with automatic circuit breakers
  DUT□AH, DUT□AT, DUT□AN, DUT□AM
and other protective devices. It
 Digital type overcurrent relay (A wide frequency band) ............................................. 1−3
is therefore important to select   DUT□AF, DUT□AG
protective relays that are  Digitai type ground overcurrent relay for non-ground line .......................................... 1−9
capable of closely monitoring   DUT□C
the actual state of the  Digital type DC current relay .................................................................................... 1−11
equipment with which they are   Overcurrent relay DUT□AD, Undercurrent relay DUT□BD
associated and that will quickly  Digital type field ground overcurrent relay ............................................................... 1−13
respond in the face of trouble.   DUT□F
Fuji produces a wide range of  Digital type ground overvoltage relay ......................................................................... 2−1
sensitive and highly dependble   DUT□GH, DUT□GT, DUT□GN, DUT□GM
protective relays from which the  Digital type overvoltage relay ...................................................................................... 2−2

customer can select a type that   DUT□VH, DUT□VT, DUT□VN, DUT□VM


 Digital type undervoltage relay .................................................................................. 2−3
will accurately match your
  DUT□UH, DUT□UT, DUT□UN, DUT□UM
requirements.
 Digital type voltage relay (A wide frequency band) ................................................... 2−4
  Overvoltage relay DUT□VG, Undervoltage relay DUT□UG
 Digital type DC voltage relay ...................................................................................... 2−9
  Overvoltage relay DUT□VD, Undervoltage relay DUT□UD
 Digital type ground directional relay ........................................................................... 3−1
How to use this catalog
  DUT□D
 This
● catalog describes Fuji's single
type relays which are housed in a  Digital type ground directional relay for resistance grounded neutral system ........... 3−3
relay-case.   DUT□J
 Relays
● in this catalog are listed  Digital type phase directional relay ............................................................................. 3−5
according to model identification   DUT□K
number and type.  Digital type reverse power relay ................................................................................. 3−7
 When
● ordering or enquiring, please
  DUT□L
supply us with the necessary informa-
tion in cases where items are marked  DUT series protective relays testing tool .................................................................... 4−1
thus (★) in the specifications.   DUTT1
 The
● characteristic curves given in  Digital type complex-element relay ............................................................................. 5−1
this catalog are typical and are given   DUTS
for your planning purpose only.
 DRAW series static type undercurrent relay, current-limit relay ................................. 6−1
 Note
● that part of the figures in the
 TELR series control relays
code symbols are subject to change
without notice for continued improve-   Auxiliary relay .......................................................................................................... 7−1
ment.   Keep relay ................................................................................................................ 7−3
 The
● catalog and operation manual for   Time-lag relay .......................................................................................................... 7−4
the DUT series are available on our  Outline drawings
company’s website as follows:
  Fig. DUT1 ............................................................................................................ Fig−1
 Web page for our protective relays
and related control devices:   Fig. DUT2 ............................................................................................................ Fig−2
 URL http://www.fujielectric.co.jp/   Fig. DUT3 ............................................................................................................ Fig−3
products/protection_relay/   Fig. DRAW1 ......................................................................................................... Fig−4
  Fig. TELR1, 2, 3 ................................................................................................... Fig−5

1
DUT Series
Single Type Digital Protective Relays

The conventional single type F series protective these parts has made it easier to obtain the
relay (accommodated in a vertically rectangular relay protective relay characteristics suited for the object
case) was commercialized at the beginning of year of protection, for example. Thus, hardware
1955. And the static type protective relay equipment technologies have advanced and optimization of the
(accommodated as a PC board in a horizontally relay standards concerning protective relays has
case) was commercialized in 1961 along with progressed. In electric power companies, the
practical application of transistorized protective relay. protective relaying scheme and protective relay
Since then, these relays have been used extensively characteristics have been positively standardized.
in the electric power and other industrial fields while In response to the above trends, the DQ series
receiving modifications. protective relays (in a vertical, rectangular case) and
In this time period, an increase in the demand for DRH series auxiliary relays have been developed
electric power has been remarkable. This has made and marketed since 1977. Since then, however, old
power systems larger in scale and more models of electronic circuit parts and mechanical
complicated. Also, the demand for power has parts have been increasingly discontinued, and the
concentrated in urban area and more stable power discontinuance of mechanical parts in particular has
supply has been requested. However, due to made it difficult to continue manufacturing the DQ
present day's social background such as difficulty of series protective relays.
acquiring a lot for power supply facility construction, In parallel with the above, our product lineup has
power plants have been far from demand site and included since 1982 the equipment type as a top-end
transmission cables have been extended long. In product that incorporates digital technologies, the
the demand site, use of ultrahigh voltage unit type as a mid-range product, etc. Since 2000,
underground cable systems have increased and the DUT series digital protective relay has been
more loads have now been based on marketed as a modified version of the induction or
semiconductors. These tendencies have been rectifier type DQ series protective relay, featuring
requiring the protective relay equipment for system digital technologies developed through previous
protection to incorporate new and sophisticated types. The DUT series is outlined here.
technologies for enhancing speed and reliability.
On the other hand, the electronic circuit parts used
for protective relays, in particular semiconductors
have been upgraded significantly. Application of

Fig.1 DUT series protective relay DQ series protective relay

Induction disk type Rectifier type Static type

A9252-25-01 310-8-250 N61-137-17 N99-2261-103

2
DUT series protective relay
DUT series single type digital protective plate structure with external dimensions • Characteristic influenced by frequency:
relays have been developed to replace equivalent to the conventional DQ-series ±5% of rated frequency, and -20 to +50%
the induction type, rectifier type, and static complex-function relays. of rated frequency in the version for broad
type conventional DQ series relays. frequency band
■Performance
■Features DUT series relays comply with the • Characteristic influenced by ambient
temperature: 0 to +40˚C
• This single type digital protective relay requirements of JEC-2500 (Protective
has a single protection function relays for Electric Power Systems), JEC- • Characteristic influenced by wave
distortion: 3rd harmonics 30% in current
incorporating with a 16-bit CPU and 2510 (Overcurrent relays), JEC-2511
relay, 90% in voltage relay
output circuit. (Voltage relays), and JEC-2512
• A variety of models and specifications (Directional earth fault relays). This relay, • Vibration resistance: 9.8m/s2
are available to suit various purposes. in particular, can be used under severe • Mechanical shock resistance: 294m/s2
• The operation of overcurrent relay can environment condition concerning ■Construction
be selected from 6 kinds of inverse time- vibration and noise. Fig.2 shows the internal element of the
lag characteristics. The outputs from DUT series are all relay relay that has been drawn out from the
• It continuously monitors the CPU and contacts; trip, alarm output for continuous relay case. There is a square hole on the
the power supply, and is activated when a monitoring, and external output. The front cover to operate the "INDICATION
defective condition is detected. contact capacity is good enough as RESET" switch so that resetting the
• The mass has been reduced by using follows: display LED can be easily made by
molded plastic resin for the relay-case • Limiting making capacity: 15A (0.5s, R- pressing this switch. The external terminal
and the front cover of the relay. load) screws (M4 x 8) at the back of the relay
• Forced operation function can be • Continuous current carrying capacity: are made of brass (nickel-plated). A
executed by switching, which facilitates 5A testing tool is available to facilitate the test
sequence checking. Forced reset function • Limiting breaking capacity: 10VA DC (L/ of the relay.
facilitates periodical inspection. R=40ms)
• It has the same appearance and In addition, DUT relay has the following
mounting size as the existing DQ series, performance, which satisfies required
for easy replacement. The exterior standards.
terminal numbers and locations of the • Characteristic influenced by auxiliary
standard type of unit are somewhat energizing source voltage: 80 to 130% of
different from those of the DQ series DC rated voltage, 85 to 115% of AC rated
protective relay. However, DQ series voltage
replacement relays having the same
terminal arrangement are also available.
• The internal element of the relay can be
drawn out at which time the CT circuit is Fig. 2 Construction of relay, type DUT□A
automatically short-circuited, so
inspection is simple.
• The setting modes can be set by
operating the setting control switches on
the front setting panel while checking the
value on the setting indicator (7
segments) and LED.
• The operation indicator is available in
two types: with or without display hold
function.
• Types complying with the B-402
standard in immunity to noise (Digital
Protective Relays and Protective
Equipment) are available.
• In overcurrent, overvoltage and
undervoltage relays that meet the JEC-
2500 standard, products having enhanced
frequency characteristics for a broad
frequency band are also available.
• The complex-element relay series are
also available as successor models to the
Front cover Relay-case Draw-out type relay element
conventional DQ-series complex-function
relays.
Unlike DUT-series models, the case for
the complex-element relay is of an iron
A9252-25-04

3
■Operation and display
Fig. 3 Setting panel, type DUT□A
The operation procedure and the display
on the setting panel in the setting change
mode are shown below.
• Power, alarm, and start display LED
The "POWER" LED remains illuminated
when the auxiliary energizing source is
being normally applied, and the "ALARM"
LED illuminates when a defective Power, alarm, and start
display LED
condition is detected by the continuous
monitoring function. The "START" LED Setting and operation
display LED
illuminates when the time lag element is
actuated. Setting indicator
(7 segments)
• Setting and operation display LED
"SETTING" illuminates when the operate
value, time setting, and time characteristics
are being set. The instantaneous Setting control switch
element "INST" and time lag element
"INV" illuminate when the relay is
activated, and blink while the element to
be set is being selected and the operation
setting is being made. "TIME" blinks
while the time setting is being made.
Time characteristics "CHAR" blinks while
the operate time characteristics are
being set.
• Setting indicator (7 segments) A9252-25-07
When the element to be set has been
selected, the setting of that element is
displayed and illuminated on the setting ■Monitoring function Er7) of each monitored section are
indicator. The setting on the indicator When a defective condition occurs in the displayed on the setting indicator.
blinks while the setting is being changed, monitored sections, the relay functions to Monitoring function is effective during
and remains on when the changing lock the trip output, activate the alarm forced reset operation.
operation has been ended. When the relay, and illuminate the "ALARM" LED. It
relay is activated, "On" is displayed on does not continuously monitor analog
the setting indicator, and when a input circuits and output relays.
defective condition of the relay is Monitoring alarm (error) codes (Er1 to
detected, the alarm (error) codes (Er1 to
Er7) are displayed on the setting Table 1 Continuous monitoring function
indicator.
Monitored Target of monitoring External operational processing Internal operational
• Setting control switches section
Trip relay Alarm Alarm LED Setting
processing
The "SELECT/SETTING" switch is used relay display indicator
(7 segments)
to select the element to be set and
CPU Halt or runaway of Output is Activated Illuminates Er1 Protection function is
change the setting. Pressing the "∧/∨" processing the program locked. stopped.
switch allows the setting to be scrolled unit
Processing function Er2
Reset not possible.
up and down, and pressing the "SET/ Er3
ROM Failure
END" switch implements and ends the RAM Er4
setting. The "SHIFT" switch provides Setting Failure Output is Er5 Operation is continued.
expansion functions, and the "OPERATE" memory (compare check) not locked. Protecting operation.
*1 Reset possible.
switch allows forced operation and/or
Failure (sum check) Output is Er6 Protection function is
forced reset operation. The "INDICATION locked. stopped.
RESET" switch resets the operation Reset not possible.

display. A-D Accuracy Er7 Operation is continued.


converter Protection function is
• Operation indicator locked.
Reset possible.
The operation indicator having a magnetic
inversion function is provided only when Power Voltage Output is Extinguishes − −
supply locked *2 *3
an AC auxiliary energizing source is used
(when symbols other than "A" are Notes *1:Output is locked during forced reset operation.
*2:When the relay is failure at +24V, output is not
selected for the 8th digit of the code locked. The trip relay cannot be activated.
*3:Illuminates when the relay is failure at ±15V.
symbol).

4
■Precautions on replacement
As mentioned on the DUT series protective relays in page 3, this If the power LEDs on the setting panel are extinguished despite
series offers the digital protective relays with a single protection that the auxiliary energizing source is provided, the internal power
function, which have been commercialized as replacement types supply of the relay may be abnormal.
for the DQ series analog protective relays. • Preparation for withstand voltage test
For replacing the DQ series with the DUT series, change of cables External terminal 18 (B18 in DQ series replacement type) should
inside the panel, etc. are required. Therefore, the following be grounded without fail. One cable needs to be added inside the
precautions shall be observed. panel. This test can be carried out in the grounded status.
• External dimensions • Independent test method
The DQ series replacement type has a depth 26mm longer than For testing the relay independently, turn off the auxiliary energizing
that of the DQ series. If the depth dimension is restricted due to source. Then, draw out the relay element from the panel and
mounting of the door to the cubicle panel, a panel mounting insert it into the testing tool (available at option; type DUTT1) for
adapter for matching the depth dimension with that of the DQ test. The testing plug STT5–Y2 cannot be used in this case.
series can be manufactured. For details, refer to Fuji Electric • Check of outdoor installation conditions
systems. The normal operating conditions given in JEC–2500 (temperature:
• External terminals 0 to +40˚C, though operation at –10 to +50˚C allowed for a few
Due to a difference in the external terminal structure, the terminal hours in a day, relative humidity: 30 to 80%) should be followed.
locations and terminal numbers are different between the DQ and Because the relay case is not enclosed completely, it should be
DUT series. The DQ series replacement type has the same protected carefully from undesirable ambient conditions such as
terminal arrangement with that of the DQ series. The terminals harmful gas and excessive dust, and excessive surge and noise
numbers are 1 to 18 in the standard unit structure type, and A1 to due to outdoor installation.
A10 and B9 to B18 in the DQ series replacement type. • Noise and surge measures
• Auxiliary energizing source If any noise may be generated by auxiliary relays inside the power
For replacement of an induction or rectifier type relay, 2 cables distribution panel, mount the surge absorber etc.
need to be added inside the panel for connecting an auxiliary Particularly, be sure to pay attention when upgrading
energizing source. Supply an auxiliary energizing source between electromechanical type relay to this relay in the existing panel.
the external terminals 9 and 10 (between B9 and B10 in the DQ • Reliability
series replacement type). An AC auxiliary energizing source is In the DUT series, the CPU, output circuit and other internal
assured for a power interruption time of 2 seconds. If a time circuits are not duplicated. When a higher reliability is desired as
period longer than 2 seconds is needed, a power supply unit free a measure against troubles in a relay alone, it is requested to
from voltage drop at occurrence of a system failure should be adopt a due measure such as series duplication by preparing
prepared outside the relay. Line voltage should be used for another relay of the same specifications externally at option.
ground relays and use of capacitor trip method or the like should • Others
be examined for phase fault relays. Rearrangement of the DUT series is allowed relay by relay. For
• Operation indicator inserting a relay element, it is required to confirm that the terminal
A drop-type operation indicator is not provided. An LED operation card on the left side of the inner face of relay case coincides with
indicator is used for a DC auxiliary energizing source, and a that on the rear face relay element in advance. Also, mounting
magnetic inversion operation indicator for an AC auxiliary and wiring work should be carried out carefully not to allow
energizing source (when symbols other than "A" are selected for entrance of foreign materials to enter the relay.
the 8th digit of the code symbol). Select "S" for the 8th digit of the
code symbol when that of the DQ-series relay was G, H, J, or P
(operation indicator with seal-in contact). Select "K" when symbols
other than the above were selected for the 8th digit of the code
symbol of the DQ-series relay (without seal-in contact). Select "A"
when a DQ-series relay without operation indicator was used
(when "A" was selected for the 8th digit of the code symbol).
• Trip, monitoring and alarm output terminals
The DUT series has each output for trip, alarm (continuous
monitoring error) and external alarm indication. When auxiliary
energizing source is turned off, the alarm contact and LED display
momentarily turns on and lights, respectively, but this
phenomenon is not abnormal. For avoiding the momentary alarm
contact output, an on-delay timer should be connected externally.
Refer to the application circuit example of overcurrent relay shown
in Fig. 4.
• Continuous monitoring functions
The continuous monitoring output (external terminals 14-15) is
important to check the relay abnormality earlier. Install and use
the alarm output externally. (Refer to Fig.4 application circuit
example of overcurrent relay).
If the alarm circuit can not be installed, check the display status of
the relay setting panel.

5
Fig. 4 Application circuit example of overcurrent relay, types DUT□AHA□ー2, DUT□ANA□ー2, DUT□AFA□ー2

R S T

3 4
50/51R

3 4
50/51T

CT

CB

P (or R)

11 14 16 9

I 3
SO.
H*
1
H*
1
AL
L
L
4 RST
12 13 15 17 10 18

LX
Connect with
terminals having
HX the same number
in other phases

AX

Trip display On-delay


timer

0.3s or more External


52a
output
Alarm display display
(to annunciator
TC relay etc.)

N (or T)

Note *1:DUT□ATA□-2, DUT□AMA□-2 and DUT□AGA□-2 type relays are not provided with
an instantaneous element output relay (H).
*2:If AC power has to be used as auxiliary energizing source, externally
provide an AC auxiliary energizing source whose voltage does not
drop even in case of an accident.

6
Definition of Terms Used

■Output duration ■Symbols (conforming to JIS C-0301)


This refers to the time required for the trip and external output • Explanatory diagram
contacts to switch from make to break (resetting time) when the
input is changed from operation to resetting.
Time-lag Instantaneous
One of the following specifications is specified in the 8th digit of element contact element contact
the code symbols: Current Alarm contact
circuit (continuous
「S」in the 8th digit of the code symbol: Slow reset 1±0.1 s H AL
H monitoring)
L L
「K」or
「A」in its 8th digit: Instantaneous reset 0.2±0.1 s
Short-circuiting Draw-out
bar of paired device
■Operate value accuracy terminals
This value is calculated as follows : External
terminal No. 3 4 11 12 13 14 15 16 17 9 10 18
Operate value accuracy
Measured value – Setting value Polarity of
= ×100 [%] relay input + −
Setting value or Specially set value I Trip Alarm External output SO.
Input current Auxiliary
■Holding factor (V: input voltage) energizing
source and
polarity
This factor is calculated as follows :
Holding factor
Operate value – Resetting value • Contacts
= ×100 [%]
Operate value
Name Symbols Remarks
■Expressing contact capacity NO contact
(Make contact)
Contact capacity refers to limiting making capacity, limiting ("a"contact)
breaking capacity and current carrying capacity.
• Limiting making capacity NC contact
This value is the limit of load which can be carried by the closed (Break contact)
("b"contact)
contacts, repeatedly in safe and dependable operation. The value
is expressed by the conditions to be guaranteed and the voltage
and its corresponding current. R-load current carring time 0.5s, PDT contact
(Change-over
and 110V DC are used unless otherwise designated. contact)
Example : 110V DC 15A
• Limiting breaking capacity Time-lag contact NO NC
This value is the limit of the load which can be carried by the in closed circuit contact contact
contacts in the open position. It is expressed by the conditions to
be guaranteed and the voltage and its corresponding current, or
volt-ampere and permissible voltage/current range. Time-lag contact NO NC
in open circuit contact contact
The load is L/R = 40ms unless otherwise specified.
Example :
In case of 110V DC, 10VA DC
For 10VA, the relationship between the circuit voltage and the Time-lag contact NO NC
in both closed and contact contact
breaking current is ; 0.09A at 110V DC
open circuit
• Current carrying capacity
This value is the limit of the current that can be carried by the For UVR NO Closed at input OFF This contact closes
current carrying part without exceeding the temperature rise limit and UCR contact when input is zero
and only auxiliary
under the guaranteed conditions. Two values may be given
energizing source is
according to carrying conditions i.e. continuous current carrying applied. (It opens
capacity and intermittent current carrying capacity. The continuous when both input and
auxiliary energizing
current carrying capacity is given unless specified otherwise.
source are zero.)
■Expressing burden NC Open at input OFF This contact opens
contact when input is zero
• Burden and only auxiliary
This is called the impedance of the relay input circuit, and is energizing source is
applied. (It closes
expressed in volt-ampere (VA), watt (W) or impedance (Ω). when both input and
• Rated burden auxiliary energizing
source are zero.)
This indicates the consumption VA when the relay is drawing its
Others Changeover PDT These contacts are
rated input. However, in case this value varies due to the setting based on NO and
at input OFF contact
value and other inputs, etc. the maximum value is used unless NC contacts.
otherwise specified.
Closed at input NO
OFF contact

7
Identifications

DUT series protective relays Example D U T U A H A S – 2 –


1 2 3 4 5 6 7 8 9 10 11
 Basic
1 type  Characteristics
4  Development
7 order
DUT : Single type digital protective relay H : Inverse time-lag  Rated
8 frequency
 Construction
2 T : Independent time-lag 5 : 50Hz
U : Unit standard structure type, DC auxiliary energizing source N : Inverse time-lag 6 : 60Hz
A : Unit standard structure type, AC auxiliary energizing source (Noise immunity conforming to standard of B-402) 1 : DC rating
R : DQ series replacement type, DC auxiliary energizing source M : Independent time-lag
B : DQ series replacement type, AC auxiliary energizing source (Noise immunity conforming to standard of B-402)
T : Testing tool D : Independent time-lag (DC input)
 Name
3 (Function) F : Inverse time-lag (A wind frequency band)
A : Overcurrent relay G : Ground overvoltage relay G : Independent time-lag (A wind frequency band)
B : Undercurrent relay J : Ground directional relay for  No.
5 of input
C : Ground overcurrent relay resistance A : One input
for non-ground line grounded neutral sysytem B : Two inputs (Directional relay etc. : one input in the current, one input in the voltage)
D : Ground directional relay K : Phase directional relay C : Three inputs
E : Ground overcurrent relay L : Reverse power relay  Output
6 duration and operation display hold function
F : Field ground overcurrent U : Undervoltage relay S: Slow reset (1±0.1s), Display hold function: Provided
relay V : Overvoltage relay K: Instantaneous reset (0.2±0.1s), Display hold function: Provided
A: Instantaneous reset (0.2±0.1s), Display hold function: Not provided
9 Rating and setting range
Name Code Inverse time-lag Instantaneous Independent time-lag Name Code Rated voltage Rated current Operate Operate Max. sensitivity Operate
symbol
Rated current 5A symbol (3Vo) (3Io) voltage current phase angle(θ) time
Overcurrent CC 1 to 6A 5 to 40A Reverse FS 110V 5A 5.5V(fixed) 15 to 0°(fixed) 0 to 30s
relay DD 2 to 12A 10 to 80A power FT 115V 5.8V(fixed) 100mA
CE 1 to 6A relay GS 110V 5.5V(fixed) 100 to
DE 2 to 12A GT 115V 5.8V(fixed) 500mA
Rated current 1A HS 110V 1A 5.5V(fixed) 15 to
HH 0.2 to 1.2A 1 to 8A HT 115V 5.8V(fixed) 100mA
JJ 0.4 to 2.4A 2 to 16A Name Code Rated current Operation setting
HK 0.2 to 1.2A symbol
JK 0.4 to 2.4A Ground overcurrent AL 2A 1.5 to 15mA
Ground Rated current 5A relay for non-ground BL 10 to 100mA
overcurrent AA 0.1 to 0.8A 0.5 to 4A line CL 40 to 400mA
relay BB 0.5 to 4A 2.5 to 20A
Name Code Rated current DC Operation setting DC
AE 0.1 to 0.8A
symbol
BE 0.5 to 4A
DC overcurrent AN 50mA 5 to 12mA
Rated current 1A
and undercurrent BN 100mA 10 to 80mA
FF 0.02 to 0.16A 0.1 to 0.8A
relay CN 2A 0.08 to 1A
GG 0.1 to 0.8A 0.5 to 4A
DN 10A 1 to 6A
FK 0.02 to 0.16A
GK 0.1 to 0.8A Name Code Rated voltage DC Operation setting
symbol DC
Name Code Rated voltage Operation setting
DC over voltage and AP 110V 10 to 100V
symbol
under voltage BP 220V 10 to 120V
Overvoltage GD 110V 60 to 150V
relay CP 500V 40 to 250V
relay
MP 100%=300mV 20 to 150%
Ground GA 110V 5 to 50V
overvoltage NP 100%=150mV 40 to 200%
GB 5 to 70V
relay PP 100%=100mV 60 to 300%
DA 190V 5 to 50V
RP 100%=60mV 100 to 500%
DB 5 to 70V
Undervoltage JG 63.5V 10 to 60V Note) One external resistor (type: YZ3) meeting various specifications is attached
to a DC overvoltage and undervoltage relay.
relay GH 110V 15 to 100V
Name Code Rated voltage Rated current Operate Operate Max. sensitivity Operate Name Code Ratings Operation External auxiliary power source box
symbol (3Vo) (3Io) voltage current phase angle(θ) time symbol setting DC Auxiliary energizing source voltage
Ground AA 110V 2A 5 to 30V 1 to 10mA 45 to 75° 0 to 3s (50/60 Hz)
directional AB 190V * Power output: 50V DC
relay BA 110V 10 to 100mA Field ground AR Applicable 5 to 8mA 100V AC
BB 190V overcurrent relay AS field voltage: 110V AC
AT 500V DC or 120V AC
Name Code Rated voltage Rated current Operate Operate Max. sensitivity Operate
AR less 200V AC
symbol (3Vo) (3Io,lo) voltage current phase angle(θ) time
AV 220V AC
Ground CD 110V 5A 5 to 20V 0.1 to 0.8A 0 to 30° 0 to 30s
directional CE 190V  Reted
10 auxiliary energizing source voltage
relay for DD 110V 0.5 to 3.0A
Code Rated voltage Code Rated voltage Code Rated voltage
resistance DE 190V
symbol symbol symbol
grounded ED 110V 1A 0.02 to 0.16A
C 100V DC J 100V AC, 50Hz R 200V AC, 50Hz
neutral EE 190V
D 110V DC K 100V AC, 60Hz S 200V AC, 60Hz
system FD 110V 0.1 to 0.6A
E 125V DC L 110V AC, 50Hz T 220V AC, 50Hz
FE 190V
F 200V DC M 110V AC, 60Hz U 220V AC, 60Hz
Name Code Rated voltage Rated current Operate Operate Max. sensitivity Operate G 220V DC N 127V AC, 50Hz V 250V AC, 50Hz
symbol (3Vo) (3Io) voltage current phase angle(θ) time H 250V DC P 127V AC, 60Hz W 250V AC, 60Hz
Phase AN 110V 5A 2.2V 0.1 to 1.0A 45°(fixed) 0 to 3s
 Special
11 specifications
directional BN (fixed) 1 to 8A For standard products with English nameplate, black (Munsell code N1.5)
relay CN 2 to 12A frame of the relay case, and without special processing for tropical use, this
DN 1A 0.2 to 1.6A need not be specified. For details, contact Fuji.
EN 0.4 to 2.4A
8
Complex-element relay D U T S A S S S – 1 –
1 2 3 4 5 6 7 8 9 10 11
 Basic
1 type  Characteristics
4  Development
7 order
DUT : Single type digital protective relay S: Complex-element structure  Rated
8 frequency
 Construction
2  No.
5 of input 5: 50Hz
S : Comprex-element relay S: Complex-element structure 6: 60Hz
DC auxiliary energizing source  Output
6 duration and operation display hold function
(Case and cover made of iron plate) S : Slow reset (1s±0.1s), with indication holding function
 Name
3 (Function) K : Instantaneous reset (0.2s±0.1s), without indication holding function
A : 3OCR
E : 3OCR+EFR
D: 2OCR+DGR

9 Rating and setting range


• 3OCR  Rated
10 auxiliary energizing source voltage
Code Ratings Setting range Code Rated voltage
symbol Overcurrent element : 3OCR symbol
Inverce time element Instantaneous element C 100V DC
CC 5A 1 to 6A 5 to 40A D 110V DC
DD 2 to 12A 10 to 80A E 125V DC
HH 1A 0.2 to 1.2A 1 to 8A
 Special
11 specifications
JJ 0.4 to 2.4A 2 to 16A For standard products with English nameplate, black (Munsell code N1.5)
• 3OCR+EFR frame of the relay case, and without special processing for tropical use, this
need not be specified. For details, contact Fuji.
Code Ratings Setting range
symbol Overcurrent Earth-fault overcurrent
element : 3OCR element : EFR
Inverce time element Instantaneous element Inverce time element
CA 5A 1 to 6A 5 to 40A 0.1 to 0.8A
DA 2 to 12A 10 to 80A 0.1 to 0.8A
CB 1 to 6A 5 to 40A 0.5 to 4.0A
DB 2 to 12A 10 to 80A 0.5 to 4.0A
HF 1A 0.2 to 1.2A 1 to 8A 0.02 to 0.16A
JF 0.4 to 2.4A 2 to 16A 0.02 to 0.16A
HG 0.2 to 1.2A 1 to 8A 0.1 to 0.8A
JG 0.4 to 2.4A 2 to 16A 0.1 to 0.8A

• 2OCR+DGR
Code Setting range
symbol Overcurrent element : 2OCR Earth-fault directional element : DGR
Ratings Inverce time element Instantaneous element Ratings Operation voltage setting : 5 to 30V
Max. sensitivity phase angle setting : 45 to 75˚
Operation time setting : 0 to 3s
3lo 3Vo Operation current setting
CK 5A 1 to 6A 5 to 40A 2A 110V 1 to 10mA
DL 2 to 12A 10 to 80A 10 to 100mA
CM 1 to 6A 5 to 40A 190V 1 to 10mA
DN 2 to 12A 10 to 80A 10 to 100mA
CL 1 to 6A 5 to 40A 110V 10 to 100mA
DK 2 to 12A 10 to 80A 1 to 10mA
CN 1 to 6A 5 to 40A 190V 10 to 100mA
DM 2 to 12A 10 to 80A 1 to 10mA
HK 1A 0.2 to 1.2A 1 to 8A 2A 110V 1 to 10mA
JL 0.4 to 2.4A 2 to 16A 10 to 100mA
HM 0.2 to 1.2A 1 to 8A 190V 1 to 10mA
JN 0.4 to 2.4A 2 to 16A 10 to 100mA
HL 0.2 to 1.2A 1 to 8A 110V 10 to 100mA
JK 0.4 to 2.4A 2 to 16A 1 to 10mA
HN 0.2 to 1.2A 1 to 8A 190V 10 to 100mA
JM 0.4 to 2.4A 2 to 16A 1 to 10mA

9
Previous and New Type List

Note) This list shows only those models that can be replaced with the DUT series.
■Current relay Please contact Fuji for previous models not listed here.
Previous type New type:DUT series Instructions for replacement with
Name PF series DQ series Auxiliary ①Standard type ②Noise immunity ③A wide DUT series
energizing Unit standard DQ series conforming to frequency band
source structure type replacement type standard of B-402
Low energy AI2PFー□ DQAJA1HA DC DUTUEHAAー2 DUTREHAAー2 DUTUENAAー2 − ・Select normal inverse time-lag
induction AC DUTAEHAAー2 DUTBEHAAー2 DUTAENAAー2 (C1) for operate time
disk type characteristic of inverse time-
ground AI2PFーO□ DQAJA1HB DC DUTUEHAKー2 DUTREHAKー2 DUTUENAKー2 − lag element.
overcurrent AC DUTAEHAKー2 DUTBEHAKー2 DUTAENAKー2 ・As an instantaneous element is
relay not required, select the lock
AI2PFーMO□ DQAJA1HH DC DUTUEHASー2 DUTREHASー2 DUTUENASー2 − setting for operation setting of
AC DUTAEHASー2 DUTBEHASー2 DUTAENASー2 instantaneous element.
Induction AI3PFー□ DQAJB1HA DC DUTUAHAAー2 DUTRAHAAー2 DUTUANAAー2 DUTUAFAAー2 ・Select normal inverse time-lag
disk type (C1) for operate time
AC DUTAAHAAー2 DUTBAHAAー2 DUTAANAAー2 DUTAAFAAー2
overcurrent characteristic of inverse time-
relay AI3PFーO□ DQAJB1HB DC DUTUAHAKー2 DUTRAHAKー2 DUTUANAKー2 DUTUAFAKー2 lag element.
AC DUTAAHAKー2 DUTBAHAKー2 DUTAANAKー2 DUTAAFAKー2 ・As an instantaneous element is
not required, select the lock
AI3PFーMO□ DQAJB1HH DC DUTUAHASー2 DUTRAHASー2 DUTUANASー2 DUTUAFASー2 setting for operation setting of
AC DUTAAHASー2 DUTBAHASー2 DUTAANASー2 DUTAAFASー2 instantaneous element.
Induction AI31PFー□ − DC DUTUAHAAー2 DUTRAHAAー2 DUTUANAAー2 DUTUAFAAー2 ・Select normal inverse time-lag
disk type AC DUTAAHAAー2 DUTBAHAAー2 DUTAANAAー2 DUTAAFAAー2 (C1) for operate time
overcurrent characteristic of inverse time-
relay with AI31PFーO□ DQAJB1HC DC DUTUAHAKー2 DUTRAHAKー2 DUTUANAKー2 DUTUAFAKー2 lag element.
instantaneous AC DUTAAHAKー2 DUTBAHAKー2 DUTAANAKー2 DUTAAFAKー2
element
AI31PFーMO□ DQAJB1HJ DC DUTUAHASー2 DUTRAHASー2 DUTUANASー2 DUTUAFASー2
AC DUTAAHASー2 DUTBAHASー2 DUTAANASー2 DUTAAFASー2
− DQAJE1HJ DC DUTUAHASー2 DUTRAHASー2 DUTUANASー2 DUTUAFASー2
(E, P) AC DUTAAHASー2 DUTBAHASー2 DUTAANASー2 DUTAAFASー2
Long time AI5PFー□ DQAJD1HA DC DUTUAHAAー2 DUTRAHAAー2 DUTUANAAー2 DUTUAFAAー2 ・Select long inverse time-lag
induction AC DUTAAHAAー2 DUTBAHAAー2 DUTAANAAー2 DUTAAFAAー2 (C3) for the operate time
disk type characteristic of the inverse
overcurrent AI5PFーO□ DQAJD1HB DC DUTUAHAKー2 DUTRAHAKー2 DUTUANAKー2 DUTUAFAKー2 time-lag element.
relay AC DUTAAHAKー2 DUTBAHAKー2 DUTAANAKー2 DUTAAFAKー2 ・As an instantaneous element is
not required, select the lock
AI5PFーMO□ DQAJD1HH DC DUTUAHASー2 DUTRAHASー2 DUTUANASー2 DUTUAFASー2 setting for operation setting of
AC DUTAAHASー2 DUTBAHASー2 DUTAANASー2 DUTAAFASー2 instantaneous element.
Long time AI51PFー□ − DC DUTUAHAAー2 DUTRAHAAー2 DUTUANAAー2 DUTUAFAAー2 ・Select long inverse time-lag
induction disk AC DUTAAHAAー2 DUTBAHAAー2 DUTAANAAー2 DUTAAFAAー2 (C3) for the operate time
type characteristic of the inverse
overcurrent AI51PFーO□ DQAJD1HC DC DUTUAHAKー2 DUTRAHAKー2 DUTUANAKー2 DUTUAFAKー2 time-lag element.
relay with AC DUTAAHAKー2 DUTBAHAKー2 DUTAANAKー2 DUTAAFAKー2
instantaneous
element AI51PFーMO□ DQAJD1HJ DC DUTUAHASー2 DUTRAHASー2 DUTUANASー2 DUTUAFASー2
AC DUTAAHASー2 DUTBAHASー2 DUTAANASー2 DUTAAFASー2
Sort time AI6PFー□ DQAJC1HA DC DUTUAHAAー2 DUTRAHAAー2 DUTUANAAー2 DUTUAFAAー2 ・Select short inverse time-lag
induction (C2) for the operate time
AC DUTAAHAAー2 DUTBAHAAー2 DUTAANAAー2 DUTAAFAAー2
disk type characteristic of the inverse
overcurrent AI6PFーO□ DQAJC1HB DC DUTUAHAKー2 DUTRAHAKー2 DUTUANAKー2 DUTUAFAKー2 time-lag element.
relay AC DUTAAHAKー2 DUTBAHAKー2 DUTAANAKー2 DUTAAFAKー2 ・As an instantaneous element is
not required, select the lock
AI6PFーMO□ DQAJC1HH DC DUTUAHASー2 DUTRAHASー2 DUTUANASー2 DUTUAFASー2 setting for operation setting of
AC DUTAAHASー2 DUTBAHASー2 DUTAANASー2 DUTAAFASー2 instantaneous element.
Sort time − DQAJC1HC DC DUTUAHAKー2 DUTRAHAKー2 DUTUANAKー2 DUTUAFAKー2 ・Select short inverse time-lag
induction disk (C2) for the operate time
type overcurrent AC DUTAAHAKー2 DUTBAHAKー2 DUTAANAKー2 DUTAAFAKー2
characteristic of the inverse
relay with − DQAJC1HJ DC DUTUAHASー2 DUTRAHASー2 DUTUANASー2 DUTUAFASー2
instantaneous time-lag element.
element AC DUTAAHASー2 DUTBAHASー2 DUTAANASー2 DUTAAFASー2
Rectifier AR3PFー□ DQARA1HA DC DUTUATAAー2 DUTRATAAー2 DUTUAMAAー2 DUTUAGAAー2 ・Operate time setting: 0 to 3s
type (0s setting: 50ms or less)
AC DUTAATAAー2 DUTBATAAー2 DUTAAMAAー2 DUTAAGAAー2
overcurrent
relay AR3PFーO□ DQARA1HB DC DUTUATAKー2 DUTRATAKー2 DUTUAMAKー2 DUTUAGAKー2
① AC DUTAATAKー2 DUTBATAKー2 DUTAAMAKー2 DUTAAGAKー2
Overcurrent
detection − DQARA1HH DC DUTUATASー2 DUTRATASー2 DUTUAMASー2 DUTUAGASー2
AC DUTAATASー2 DUTBATASー2 DUTAAMASー2 DUTAAGASー2
Rectifier AR3PFー□ DQARA1HA DC DUTUETAAー2 DUTRETAAー2 DUTUEMAAー2 − ・Operate time setting: 0 to 3s
type AC DUTAETAAー2 DUTBETAAー2 DUTAEMAAー2 − (0s setting: 80ms or less)
overcurrent
relay AR3PFーO□ DQARA1HB DC DUTUETAKー2 DUTRETAKー2 DUTUEMAKー2 −
② AC DUTAETAKー2 DUTBETAKー2 DUTAEMAKー2 −
Ground-fault
overcurrent − DQARA1HH DC DUTUETASー2 DUTRETASー2 DUTUEMASー2 −
detection AC DUTAETASー2 DUTBETASー2 DUTAEMASー2 −

10
Previous type New type:DUT series Instructions for replacement with
Name PF series DQ series Auxiliary ①standard type ②Noise immunity ③A wide DUT series
energizing Unit standard DQ series conforming to frequency band
source structure type replacement type standard of B-402
Moving-iron AA7PFー□ DQAWA□HA DC DUTUATAAー2 DUTRATAAー2 DUTUAMAAー2 DUTUAGAAー2 ・Operate time setting: 0 to 3s
type overcurrent (N) AC DUTAATAAー2 DUTBATAAー2 DUTAAMAAー2 DUTAAGAAー2 (0s setting: 50ms or less)
relay(PF series)
Static type AA7PFーO□ DQAWA□HB DC DUTUATAKー2 DUTRATAKー2 DUTUAMAKー2 DUTUAGAKー2
overcurrent (D) AC DUTAATAKー2 DUTBATAKー2 DUTAAMAKー2 DUTAAGAKー2
relay(DQ series)
①Overcurrent − DQAWA□HH DC DUTUATASー2 DUTRATASー2 DUTUAMASー2 DUTUAGASー2
detection (G) AC DUTAATASー2 DUTBATASー2 DUTAAMASー2 DUTAAGASー2
Moving-iron type AA7PFー□ DQAWC□HA DC DUTUAHAAー2 DUTRAHAAー2 DUTUANAAー2 DUTUAFAAー2 ・Select lock setting for operation
overcurrent relay setting of the inverse time-lag
(PF series) Static *8ー24A,12ー36ASpec. (N) AC DUTAAHAAー2 DUTBAHAAー2 DUTAANAAー2 DUTAAFAAー2
element and operate only with
type overcurrent AA7PFーO□ DQAWC□HB DC DUTUAHAKー2 DUTRAHAKー2 DUTUANAKー2 DUTUAFAKー2 the instantaneous element.
relay(DQ series)
②With specifications *8ー24A,12ー36ASpec. (D) AC DUTAAHAKー2 DUTBAHAKー2 DUTAANAKー2 DUTAAFAKー2 ・Operate time setting: 0 to 3s
for high setting (0s setting: 50ms or less)
− DQAWC□HH DC DUTUAHASー2 DUTRAHASー2 DUTUANASー2 DUTUAFASー2
overcurrent
detection (G) AC DUTAAHASー2 DUTBAHASー2 DUTAANASー2 DUTAAFASー2
Moving-iron AA7PFー□ DQAWA□HA DC DUTUETAAー2 DUTRETAAー2 DUTUEMAAー2 − ・Operate time setting: 0 to 3s
type overcurrent (0s setting: 80ms or less)
relay(PF series) (N) AC DUTAETAAー2 DUTBETAAー2 DUTAEMAAー2 −
Static type AA7PFーO□ DQAWA□HB DC DUTUETAKー2 DUTRETAKー2 DUTUEMAKー2 −
overcurrent
relay(DQ series) (D) AC DUTAETAKー2 DUTBETAKー2 DUTAEMAKー2 −
③Ground-fault − DQAWA□HH DC DUTUETASー2 DUTRETASー2 DUTUEMASー2 −
overcurrent
detection (G) AC DUTAETASー2 DUTBETASー2 DUTAEMASー2 −
Static type − DQAWE□HA DC DUTUATAAー2 DUTRATAAー2 DUTUAMAAー2 − ・Operate time setting: 0 to 3s
overcurrent AC DUTAATAAー2 DUTBATAAー2 DUTAAMAAー2 − (0s setting: 50ms or less)
relay with
DC portion − DQAWE□HB DC DUTUATAKー2 DUTRATAKー2 DUTUAMAKー2 −
countermeasure AC DUTAATAKー2 DUTBATAKー2 DUTAAMAKー2 −
①Overcurrent
− DQAWE□HH DC DUTUATASー2 DUTRATASー2 DUTUAMASー2 −
detection
AC DUTAATASー2 DUTBATASー2 DUTAAMASー2 −
Static type − DQAWE□HA DC DUTUETAAー2 DUTRETAAー2 DUTUEMAAー2 − ・Operate time setting: 0 to 3s
overcurrent AC DUTAETAAー2 DUTBETAAー2 DUTAEMAAー2 − (0s setting: 80ms or less)
relay with
DC portion − DQAWE□HB DC DUTUETAKー2 DUTRETAKー2 DUTUEMAKー2 −
countermeasure AC DUTAETAKー2 DUTBETAKー2 DUTAEMAKー2 −
②Ground-fault
overcurrent − DQAWE□HH DC DUTUETASー2 DUTRETASー2 DUTUEMASー2 −
detection AC DUTAETASー2 DUTBETASー2 DUTAEMASー2 −
Static type − DQAWF1HA DC DUTUATAAー2 DUTRATAAー2 DUTUAMAAー2 − ・Operate time setting: 0 to 3s
overcurrent AC DUTAATAAー2 DUTBATAAー2 DUTAAMAAー2 − (0s setting: 50ms or less)
relay
①Overcurrent − DQAWF1HB DC DUTUATAKー2 DUTRATAKー2 DUTUAMAKー2 −
detection AC DUTAATAKー2 DUTBATAKー2 DUTAAMAKー2 −
− DQAWF1HH DC DUTUATASー2 DUTRATASー2 DUTUAMASー2 −
AC DUTAATASー2 DUTBATASー2 DUTAAMASー2 −
Static type − DQAWF1HA DC DUTUETAAー2 DUTRETAAー2 DUTUEMAAー2 − ・Operate time setting: 0 to 3s
overcurrent AC DUTAETAAー2 DUTBETAAー2 DUTAEMAAー2 − (0s setting: 80ms or less)
relay
②Ground-fault − DQAWF1HB DC DUTUETAKー2 DUTRETAKー2 DUTUEMAKー2 −
overcurrent AC DUTAETAKー2 DUTBETAKー2 DUTAEMAKー2 −
detection
− DQAWF1HH DC DUTUETASー2 DUTRETASー2 DUTUEMASー2 −
AC DUTAETASー2 DUTBETASー2 DUTAEMASー2 −
Static type − DQAWG1PN DC DUTUATCAー2 − − − ・The appearance of the case,
overcurrent AC DUTAATCAー2 − − − panel cutout size, configuration of
relay trip output circuit, etc. are different.
(3-phase − DQAWG1PG DC DUTUATCKー2 − − − ・Operate time setting: 0 to 3s (0s
type) AC DUTAATCKー2 − − − setting: 50ms or less)
Static type − DQAWJ□HA DC DUTUATAAー2 DUTRATAAー2 DUTUAMAAー2 − ・Operate time setting: 0 to 3s
independent (N) AC DUTAATAAー2 DUTBATAAー2 DUTAAMAAー2 − (0s setting: 50ms or less)
time-lag
overcurrent − DQAWJ□HB DC DUTUATAKー2 DUTRATAKー2 DUTUAMAKー2 −
relay (D) AC DUTAATAKー2 DUTBATAKー2 DUTAAMAKー2 −
①Overcurrent
detection − DQAWJ□HH DC DUTUATASー2 DUTRATASー2 DUTUAMASー2 −
(G) AC DUTAATASー2 DUTBATASー2 DUTAAMASー2 −

11
Previous type New type:DUT series Instructions for replacement with
Name PF series DQ series Auxiliary ①standard type ②Noise immunity ③A wide DUT series
energizing Unit standard DQ series conforming to frequency band
source structure type replacement type standard of B-402
Static type − DQAWJ□HA DC DUTUETAAー2 DUTRETAAー2 DUTUEMAAー2 − ・Operate time setting: 0 to 3s
independent (0s setting: 50ms or less)
(N) AC DUTAETAAー2 DUTBETAAー2 DUTAEMAAー2 −
time-lag
overcurrent − DQAWJ□HB DC DUTUETAKー2 DUTRETAKー2 DUTUEMAKー2 −
relay (D) AC DUTAETAKー2 DUTBETAKー2 DUTAEMAKー2 −
②Ground-fault
overcurrent − DQAWJ□HH DC DUTUETASー2 DUTRETASー2 DUTUEMASー2 −
detection (G) AC DUTAETASー2 DUTBETASー2 DUTAEMASー2 −
Static type − DRAWP□SA DC DUTUATAAー2 − − DUTUAGAAー2 ・Operate time setting: 0 to 3s
AC current (0s setting: 50ms or less)
(N)
relay ・There are differences in the appearance
AC DUTAETAAー2 − − DUTAAGAAー2 of the case, panel mounting,
configuration of trip output circuit, etc.
Static type − DQAWD□HA DC DUTUCTAAー1 DUTRCTAAー1 − − ・Operate time setting: 0 to 3s
ground
(N) AC DUTACTAAー1 DUTBCTAAー1 − − (0s setting: within 0.2 ± 0.05s)
overcurrent ・The standard model complies
relay for AS5PFーO□ DQAWD□HB DC DUTUCTAKー1 DUTRCTAKー1 − − with the power standard in
non-ground (D, Z) AC DUTACTAKー1 DUTBCTAKー1 − − immunity to noise.
line
− DQAWD□HH DC DUTUCTASー1 DUTRCTASー1 − −
(G) AC DUTACTASー1 DUTBCTASー1 − −
Moving-coil AC3PFー□ DQACA1HA DC DUTUADAAー1 DUTRADAAー1 − − ・Operate time setting: 0 to 30s
type DC
(DQACA2HA) AC DUTAADAAー1 DUTBADAAー1 − − (0s setting: within 0.1 ± 0.05s)
overcurrent ・Trip output of DUT series is "a"
relay AC3PFーO□ DQACA1HB DC DUTUADAKー1 DUTRADAKー1 − − contact.
(DQACA2HB) AC DUTAADAKー1 DUTBADAKー1 − −
− DQACA1HH DC DUTUADASー1 DUTRADASー1 − −
(DQACA2HH) AC DUTAADASー1 DUTBADASー1 − −
Moving-coil UAC3PFー□ DQACB1HA DC DUTUBDAAー1 DUTRBDAAー1 − − ・Operatie time setting: 0 to 30s
type DC
(DQACB2HA) AC DUTABDAAー1 DUTBBDAAー1 − − (0s setting: within 0.1 ± 0.05s)
undercurrent ・Trip output of DUT series is "a"
relay UAC3PFーO□ DQACB1HB DC DUTUBDAKー1 DUTRBDAKー1 − − contact.
(DQACB2HB) AC DUTABDAKー1 DUTBBDAKー1 − −
− DQACB1HH DC DUTUBDASー1 DUTRBDASー1 − −
(DQACB2HH) AC DUTABDASー1 DUTBBDASー1 − −
Moving-iron AA5PFー□ − DC DUTUADAAー1 DUTRADAAー1 − − ・Operate time setting: 0 to 30s
type DC
AC DUTAADAAー1 DUTBADAAー1 − − (0s setting: within 0.1 ± 0.05s)
overcurrent ・Trip output of DUT series is "a"
relay AA5PFーO□ − DC DUTUADAKー1 DUTRADAKー1 − − contact.
AC DUTAADAKー1 DUTBADAKー1 − −
Moving-iron UAA5PFー□ − DC DUTUBDAAー1 DUTRBDAAー1 − − ・Operate time setting: 0 to 30s
type DC (0s setting: within 0.1 ± 0.05s)
AC DUTABDAAー1 DUTBBDAAー1 − −
undercurrent ・Trip output of DUT series is "a"
relay UAA5PFーO□ − DC DUTUBDAKー1 DUTRBDAKー1 − − contact.
AC DUTABDAKー1 DUTBBDAKー1 − −

■Field ground overcurrent relay


Previous type New type:DUT series Instructions for replacement with
Name PF series DQ series Auxiliary ①Standard type ②Noise immunity ③A wide DUT series
energizing Unit standard DQ series conforming to frequency band
source structure type replacement type standard of B-402
Moving-coil AC3PFー□ DQACD□NA DC DUTUFDAAー1 − − − • Since the outside dimension of
type field the relay case does not fit the
+YZ14
ground conventional DQ series, and
overcurrent
thus external conection of the
relay − DQACD□NB DC DUTUFDAKー1 − − −
external auxiliary power source
box (type : YZ14-2) is required,
modifcation of the distribution
− DQACD□NH DC DUTUFDASー1 − − − board is required when a
conventional item is to be
updated.
• Operate time setting : 0 to 30s
• The standard model complies
with the power standard in
immunity to noise.

12
■Voltage relay
Previous type New type:DUT series Instructions for replacement with
Name PF series DQ series Auxiliary ①standard type ②Noise immunity ③A wide DUT series
energizing Unit standard DQ series conforming to frequency band
source structure type replacement type standard of B-402
Induction VI2PFー□ DQVJA1HA DC DUTUGHAAー2 DUTRGHAAー2 DUTUGNAAー2 −
disk type
AC DUTAGHAAー2 DUTBGHAAー2 DUTAGNAAー2
ground
overvoltage VI2PFーO□ DQVJA1HB DC DUTUGHAKー2 DUTRGHAKー2 DUTUGNAKー2 −
relay AC DUTAGHAKー2 DUTBGHAKー2 DUTAGNAKー2
VI2PFーMO□ DQVJA1HH DC DUTUGHASー2 DUTRGHASー2 DUTUGNASー2 −
AC DUTAGHASー2 DUTBGHASー2 DUTAGNASー2
Induction VI3PFー□ DQVJC1HA DC DUTUVHAAー2 DUTRVHAAー2 DUTUVNAAー2 −
disk type
AC DUTAVHAAー2 DUTBVHAAー2 DUTAVNAAー2 −
overvoltage
relay VI3PFーO□ DQVJC1HB DC DUTUVHAKー2 DUTRVHAKー2 DUTUVNAKー2 −
AC DUTAVHAKー2 DUTBVHAKー2 DUTAVNAKー2 −
VI3PFーMO□ DQVJC1HH DC DUTUVHASー2 DUTRVHASー2 DUTUVNASー2 −
AC DUTAVHASー2 DUTBVHASー2 DUTAVNASー2 −
Induction UVI3PFー□ DQVJD1HA DC DUTUUHAAー2 DUTRUHAAー2 DUTUUNAAー2 − ・Operate time setting: 0 to 5s
disk type (0s setting: 70ms or less)
AC DUTAUHAAー2 DUTBUHAAー2 DUTAUNAAー2 −
undervoltage
relay UVI31PFーO□ DQVJD1HB DC DUTUUHAKー2 DUTRUHAKー2 DUTUUNAKー2 −
AC DUTAUHAKー2 DUTBUHAKー2 DUTAUNAKー2 −
UVI3PFーMO□ DQVJD1HH DC DUTUUHASー2 DUTRUHASー2 DUTUUNASー2 −
AC DUTAUHASー2 DUTBUHASー2 DUTAUNASー2 −
Rectifier type VR3PFー□ DQVRA1HA DC DUTUVTAAー2 DUTRVTAAー2 DUTUVMAAー2 DUTUVGAAー2 ・Operate time setting: 0 to 30s
overvoltage AC DUTAVTAAー2 DUTBVTAAー2 DUTAVMAAー2 DUTAVGAAー2 (0s setting: 70ms or less)
relay
①Overvoltage VR3PFーO□ DQVRA1HB DC DUTUVTAKー2 DUTRVTAKー2 DUTUVMAKー2 DUTUVGAKー2
detection AC DUTAVTAKー2 DUTBVTAKー2 DUTAVMAKー2 DUTAVGAKー2
VR3PFーMO□ DQVRA1HH DC DUTUVTASー2 DUTRVTASー2 DUTUVMASー2 DUTUVGASー2
AC DUTAVTASー2 DUTBVTASー2 DUTAVMASー2 DUTAVGASー2
Rectifier type VR3PFー□ DQVRA1HA DC DUTUGTAAー2 DUTRGTAAー2 DUTUGMAAー2 − ・Operate time setting: 0 to 30s
overvoltage AC DUTAGTAAー2 DUTBGTAAー2 DUTAGMAAー2 − (0s setting: 70ms or less)
relay
②Ground-fault VR3PFーO□ DQVRA1HB DC DUTUGTAKー2 DUTRGTAKー2 DUTUGMAKー2 −
overrvoltage AC DUTAGTAKー2 DUTBGTAKー2 DUTAGMAKー2 −
detection
VR3PFーMO□ DQVRA1HH DC DUTUGTASー2 DUTRGTASー2 DUTUGMASー2 −
AC DUTAGTASー2 DUTBGTASー2 DUTAGMASー2 −
Rectifier type UVR3PFー□ DQVRB1HA DC DUTUUTAAー2 DUTRUTAAー2 DUTUUMAAー2 DUTUUGAAー2 ・Operate time setting: 0 to 5s
undervoltage (0s setting: 70ms or less)
AC DUTAUTAAー2 DUTBUTAAー2 DUTAUMAAー2 DUTAUGAAー2
relay
UVR3PFーO□ DQVRB1HB DC DUTUUTAKー2 DUTRUTAKー2 DUTUUMAKー2 DUTUUGAKー2
AC DUTAUTAKー2 DUTBUTAKー2 DUTAUMAKー2 DUTAUGAKー2
− DQVRB1HH DC DUTUUTASー2 DUTRUTASー2 DUTUUMASー2 DUTUUGASー2
AC DUTAUTASー2 DUTBUTASー2 DUTAUMASー2 DUTAUGASー2
Moving-iron VA7PFー□ DQVWA□HA DC DUTUVTAAー2 DUTRVTAAー2 DUTUVMAAー2 DUTUVGAAー2 ・Operate time setting: 0 to 30s
type overvoltage (N) AC DUTAVTAAー2 DUTBVTAAー2 DUTAVMAAー2 DUTAVGAAー2 (0s setting: 70ms or less)
relay(PF series)
Static type VA7PFーO□ DQVWA□HB DC DUTUVTAKー2 DUTRVTAKー2 DUTUVMAKー2 DUTUVGAKー2
overvoltage (D) AC DUTAVTAKー2 DUTBVTAKー2 DUTAVMAKー2 DUTAVGAKー2
relay(DQ series)
①Overvoltage − DQVWA□HH DC DUTUVTASー2 DUTRVTASー2 DUTUVMASー2 DUTUVGASー2
detection (G) AC DUTAVTASー2 DUTBVTASー2 DUTAVMASー2 DUTAVGASー2
Moving-iron type VA7PFー□ DQVWA□HA DC DUTUGTAAー2 DUTRGTAAー2 DUTUGMAAー2 − ・Operate time setting: 0 to 30s
overvoltage relay(PF
(N) AC DUTAGTAAー2 DUTBGTAAー2 DUTAGMAAー2 − (0s setting: 70ms or less)
series)Static type
overvoltage relay(DQ VA7PFーO□ DQVWA□HB DC DUTUGTAKー2 DUTRGTAKー2 DUTUGMAKー2 −
series) (D) AC DUTAGTAKー2 DUTBGTAKー2 DUTAGMAKー2 −
②Ground-fault
overrvoltage − DQVWA□HH DC DUTUGTASー2 DUTRGTASー2 DUTUGMASー2 −
detection (G) AC DUTAGTASー2 DUTBGTASー2 DUTAGMASー2 −
Moving-iron UVA7PFー□ DQVWB□HA DC DUTUUTAAー2 DUTRUTAAー2 DUTUUMAAー2 DUTUUGAAー2 ・Operate time setting: 0 to 5s
type (0s setting: 70ms or less)
(N) AC DUTAUTAAー2 DUTBUTAAー2 DUTAUMAAー2 DUTAUGAAー2
undervoltage
relay(PF series) UVA7PFーO□ DQVWB□HB DC DUTUUTAKー2 DUTRUTAKー2 DUTUUMAKー2 DUTUUGAKー2
Static type (D) AC DUTAUTAKー2 DUTBUTAKー2 DUTAUMAKー2 DUTAUGAKー2
undervoltage
relay(DQ − DQVWB□HH DC DUTUUTASー2 DUTRUTASー2 DUTUUMASー2 DUTUUGASー2
series) (G) AC DUTAUTASー2 DUTBUTASー2 DUTAUMASー2 DUTAUGASー2

13
Previous type New type:DUT series Instructions for replacement with
DUT series
Name PF series DQ series Auxiliary ①standard type ②Noise immunity ③A wide
energizing Unit standard DQ series conforming to frequency band
source structure type replacement type standard of B-402
Static type − DQVWF1HA DC DUTUVTAAー2 DUTRVTAAー2 DUTUVMAAー2 − ・Operate time setting: 0 to 30s
overvoltage relay (0s setting: 70ms or less)
with high- AC DUTAVTAAー2 DUTBVTAAー2 DUTAVMAAー2 −
harmonic − DQVWF1HB DC DUTUVTAKー2 DUTRVTAKー2 DUTUVMAKー2 −
countermeasure AC DUTAVTAKー2 DUTBVTAKー2 DUTAVMAKー2 −
①Overvoltage
detection − DQVWF1HH DC DUTUVTASー2 DUTRVTASー2 DUTUVMASー2 −
AC DUTAVTASー2 DUTBVTASー2 DUTAVMASー2 −
Static type − DQVWF1HA DC DUTUGTAAー2 DUTRGTAAー2 DUTUGMAAー2 −
overvoltage relay
with high- AC DUTAGTAAー2 DUTBGTAAー2 DUTAGMAAー2 −
harmonic − DQVWF1HB DC DUTUGTAKー2 DUTRGTAKー2 DUTUGMAKー2 −
countermeasure
AC DUTAGTAKー2 DUTBGTAKー2 DUTAGMAKー2 −
②Ground-fault
overrvoltage − DQVWF1HH DC DUTUGTASー2 DUTRGTASー2 DUTUGMASー2 −
detection AC DUTAGTASー2 DUTBGTASー2 DUTAGMASー2 −
Moving-coil VC3PFー□ DQVCA1(A2)HA DC DUTUVDAAー1 DUTRVDAAー1 − − ・Operate time setting: 0 to 30s
type DC (0s setting: within 0.15 ± 0.05s)
(DQVCA3HA) AC DUTAVDAAー1 DUTBVDAAー1 − − ・An external resistor (type: YZ3)
overvoltage
relay VC3PFーO□ DQVCA1(A2)HB DC DUTUVDAKー1 DUTRVDAKー1 − − is attached.
・Trip output of DUT series is "a"
(DQVCA3HB) AC DUTAVDAKー1 DUTBVDAKー1 − −
contact.
− DQVCA1(A2)HH DC DUTUVDASー1 DUTRVDASー1 − −
(DQVCA3HH) AC DUTAVDASー1 DUTBVDASー1 − −
Moving-coil UVC3PFー□ DQVCB1(B2)HA DC DUTUUDAAー1 DUTRUDAAー1 − − ・Operate time setting: 0 to 30s
type DC (0s setting: within 0.2 ± 0.05s)
(DQVCB3HA) AC DUTAUDAAー1 DUTBUDAAー1 − −
undervoltage ・An external resistor (type: YZ3)
relay UVC3PFーO□ DQVCB1(B2)HB DC DUTUUDAKー1 DUTRUDAKー1 − − is attached.
(DQVCB3HB) AC DUTAUDAKー1 DUTBUDAKー1 − − ・Trip output of DUT series is "a"
contact.
− DQVCB1(B2)HH DC DUTUUDASー1 DUTRUDASー1 − −
(DQVCB3HH) AC DUTAUDASー1 DUTBUDASー1 − −
Moving-iron VA5PFー□ − DC DUTUVDAAー1 DUTRVDAAー1 − − ・Operate time setting: 0 to 30s
type DC (0s setting: within 0.15 ± 0.05s)
AC DUTAVDAAー1 DUTBVDAAー1 − −
overvoltage ・An external resistor (type: YZ3)
relay VA5PFーO□ − DC DUTUVDAKー1 DUTRVDAKー1 − − is attached.
AC DUTAVDAKー1 DUTBVDAKー1 − − ・Trip output of DUT series is "a" contact.

Moving-iron UVA5PFー□ − DC DUTUUDAAー1 DUTRUDAAー1 − − ・Operate time setting: 0 to 30s


type DC (0s setting: within 0.2 ± 0.05s)
AC DUTAUDAAー1 DUTBUDAAー1 − −
undervoltage ・An external resistor (type: YZ3)
relay UVA5PFーO□ − DC DUTUUDAKー1 DUTRUDAKー1 − − is attached.
AC DUTAUDAKー1 DUTBUDAKー1 − − ・Trip output of DUT series is "a" contact.

■Directional relay
Previous type New type:DUT series Instructions for replacement with
DUT series
Name PF series DQ series Auxiliary ①standard type ②Noise immunity ③A wide
energizing Unit standard DQ series conforming to frequency band
source structure type replacement type standard of B-402
Static type SWP4PFー1 DQWPA□HA(N) DC DUTUDTBAー3 DUTRDTBAー3 − − ・Setting of maximum sensitivity phase
ground angle:θ= 45 to 75˚ settable (SWP4PF
DQWPF□HA(N) AC DUTADTBAー3 DUTBDTBAー3 − − type:θ= 45˚ fixed, DQWPA, DQWPF
directional
relay for non- SWP4PFーO1 DQWPA□HB(D) DC DUTUDTBKー3 DUTRDTBKー3 − − types: θ= 60˚ fixed)
ground line ・Operate time setting: 0 to 3s (0s
DQWPF□HB(D) AC DUTADTBKー3 DUTBDTBKー3 − − setting: within 0.2 ± 0.05s)
− DQWPA□HH(G) DC DUTUDTBSー3 DUTRDTBSー3 − − ・The standard model complies with the
power standard in immunity to noise.
DQWPF□HH(G) AC DUTADTBSー3 DUTBDTBSー3 − −
Induction disk WJ9PFーA□ DQWJA1HA DC DUTUDTBAー3 DUTRDTBAー3 − − ・The induction disk type ground directional
type ground relay can be replaced by the DUT ground
*θ=45°Spec. *θ=45, 60°Spec. AC DUTADTBAー3 DUTBDTBAー3 − − directional relay only in the case when
directional
relay WJ9PFーAO□ DQWJA1HB DC DUTUDTBKー3 DUTRDTBKー3 − − ground fault protection is specified for a non-
*For non- grounded line (maximum sensitivity phase
*θ=45°Spec. *θ=45, 60°Spec. AC DUTADTBKー3 DUTBDTBKー3 − − angle tapθ= 45, 60˚ current advance)
ground line − DQWJA1HH DC DUTUDTBSー3 DUTRDTBSー3 − − ・Operate time setting: 0 to 3s (0s setting:
within 0.2 ± 0.05s)
*θ=45, 60°Spec. AC DUTADTBSー3 DUTBDTBSー3 − −
・The standard model complies with the power
standard in immunity to noise.
Rectifier, WR2PF-□ DQWPB□HA(N) DC DUTUJTBAー1 DUTRJTBAー1 − − ・Setting of maximum sensitivity phase
static type angle:θ= 0 to 30˚ settable (WR2PF
*ground directional type, DQWPB type standard spec.: θ
ground
directional Spec. = 0˚ fixed,
relay for DQWPB2, 4 type : θ= 10˚ current
WR2PF-0(L)□ DQWPB□HB(D) DC DUTUJTBKー1 DUTRJTBKー1 − − advance fixed)
resistance *ground directional ・Operate time setting: 0 to 30s (0s
grounded setting: within 50ms)
neutral Spec. ・The standard model complies with the
sysytem − DQWPB□HH(G) DC DUTUJTBSー1 DUTRJTBSー1 − − power standard in immunity to noise.

14
Previous type New type:DUT series Instructions for replacement with
DUT series
Name PF series DQ series Auxiliary ①standard type ②Noise immunity ③A wide
energizing Unit standard DQ series conforming to frequency band
source structure type replacement type standard of B-402
Rectifier, WR2PF-□ DQWPC□HA(N) DC DUTUKTBAー1 DUTRKTBAー1 − − ・An operating voltage is fixed to 2.2V
static type (corresponding to 2% of a rated
*phase directional voltage). Internal processing of a
phase
directional Spec. voltage memory function is adopted
relay for a voltage input section. If
WR2PF-0(L)□ DQWPC□HB(D) DC DUTUKTBKー1 DUTRKTBKー1 − − considering short circuit of three
*phase directional phase of a nearest end, select "output
duration specification: Slow reset type
Spec. (8th digits of the type: S)." It is
recommended to select "Operating
− DQWPC□HH(G) DC DUTUKTBSー1 DUTRKTBSー1 − −
time setting: 0s" for operation.
・Operate time setting: 0 to 3s (0s
setting: within 50ms)
・The standard model complies with the
power standard in immunity to noise.
Rectifier, WR2PFー□ DQWPD□HA(N) DC DUTULTBAー1 DUTRLTBAー1 − − ・Operate time setting: 0 to 3s (0s
static type setting: within 50ms)
Reverse power − − ・The standard model complies with the
phase
directional Spec. power standard in immunity to noise.
relay WR2PFー0(L)□ DQWPD□HB(D) DC DUTULTBKー1 DUTRLTBKー1
Reverse power
Spec.
− DQWPD□HH(G) DC DUTULTBSー1 DUTRLTBSー1

■Complex-function relay
Configuration of Previous type : DQ series comprex-function relay New type : DUT series
protective function 1st generation 2nd generation 3rd generation 4th generation 5th generation comprex element relay
element Note) Discontinued in 1984 *6 Discontinued in 1990 Discontinued in 1994 Discontinued in 1995 Discontinued in 2007 *1, 2
1OCR(N) DQASA3H□ DQASA6M□ DQASA7M□ DQASH3M□ DQASF7M□ DUTSASS□-1
DQASD3H□ DQASD6M□ : 3OCR *3
2OCR(N) DQASA2H□ DQASA5M□ DQASA8M□ DQASH4M□ DQASF8M□ DUTSASS□-1
DQASD2H□ DQASD5M□ : 3OCR *3
3OCR(N) DQASA1H□ DQASA4M□ DQASA9M□ DQASH5M□ DQASF9M□ DUTSASS□-1
DQASD1H□ DQASD4M□ : 3OCR
2OCR(N)+EFR(N) DQASB2N□ DQASB4M□ DQASB8M□ DQASL1M□ DQASS1M□ DUTSESS□-1
DQASE2N□ DQASE4M□ : 3OCR+EFR *3
3OCR(N)+EFR(N) DQASB1N□ DQASB3M□ DQASB9M□ DQASL3M□ DQASS2M□ DUTSESS□-1
DQASE1N□ DQASE3M□ : 3OCR+EFR
2OCR(N)+DGR DQASC1N□ DQASC2M□ DQASC8M□ DQASU1M□ DQASU5M□ DUTSDSS□-1
DQASF1N□ DQASF2M□ : 2OCR+DGR
1OCR(L) DQASD9M□ DQASH6M□ DQAST4M□ DUTSASS□-1
: 3OCR *1
2OCR(L)+EFR(N) DQASB6M□ DQASE6M□ DQASJ9M□ DQASN9M□ DUTSESS□-1
: 3OCR+EFR *3
3OCR(L)+EFR(N) DQASB5M□ DQASE5M□ DQASL9M□ DQASS7M□ DUTSESS□-1
: 3OCR+EFR
EFR(N), without DQASG1M□ DQASG7M□ DQASW1M□ DQASW3M□ DUTSASS□-1
instantaneous element DQASH1M□ : 3OCR *4
EFR(N), with DQASG2M□ DQASG8M□ DQASW2M□ DQASW4M□ DUTSESS□-1
instantaneous element DQASH2M□ : 3OCR+EFR *5
1OCR(V) DQASJ1M□ DQASE7M□ DQAST1M□ DUTSASS□-1
: 3OCR *3
2OCR(V) DQASJ2M□ DQASE8M□ DQAST2M□ DUTSASS□-1
: 3OCR *3
3OCR(V) DQASJ3M□ DQASE9M□ DQAST3M□ DUTSASS□-1
: 3OCR
2OCR(V)+DGR DQASJ4M□ DQASU2M□ DQASU6M□ DUTSDSS□-1
: 2OCR+DGR
1OCR(E) DQASK1M□ DQASF4M□ DQASH7M□ DUTSASS□-1
: 3OCR *3
2OCR(E) DQASK2M□ DQASF5M□ DQASH8M□ DUTSASS□-1
: 3OCR *3

15
Configuration of Previous type : DQ series comprex-function relay New type : DUT series
protective function 1st generation 2st generation 3st generation 4st generation 5st generation comprex element relay
element Note) Discontinued in 1984 *6 Discontinued in 1990 Discontinued in 1994 Discontinued in 1995 Discontinued in 2007 *1, 2
3OCR(E) DQASK3M□ DQASF6M□ DQASH9M□ DUTSASS□-1
: 3OCR
2OCR(E)+DGR DQASK4M□ DQASU3M□ DQASU7M□ DUTSDSS□-1
: 2OCR+DGR
2OCR(L) DQASD7M□ DQASL2M□ DQASD8M□ DQAST5M□ DUTSASS□-1
: 3OCR *3
2OCR(L)+DGR DQASF3M□ DQASL4M□ DQASU4M□ DQASU8M□ DUTSDSS□-1
: 2OCR+DGR
2OCR(V)+EFR(N) DQASM1M□ DQASJ5M□ DQASN5M□ DUTSESS□-1
: 3OCR+EFR *3
2OCR(E)+EFR(N) DQASM2M□ DQASJ7M□ DQASN7M□ DUTSESS□-1
: 3OCR+EFR *3
3OCR(E)+EFR(N) DQASM3M□ DQASJ6M□ DQASN6M□ DUTSESS□-1
: 3OCR+EFR
3OCR(E)+EFR(N) DQASM4M□ DQASJ8M□ DQASN8M□ DUTSESS□-1
: 3OCR+EFR
2OCR(V)+EFR(E) DQASN1M□ DQASM5M□ DQASR5M□ DUTSESS□-1
: 3OCR+EFR *3
2OCR(E)+EFR(V) DQASN2M□ DQASM7M□ DQASR7M□ DUTSESS□-1
: 3OCR+EFR *3
3OCR(V)+EFR(E) DQASN3M□ DQASM6M□ DQASR6M□ DUTSESS□-1
: 3OCR+EFR
3OCR(E)+EFR(V) DQASN4M□ DQASM8M□ DQASR8M□ DUTSESS□-1
: 3OCR+EFR
2OCR(N)+EFR(V) DQASP1M□ DQASL5M□ DQASS3M□ DUTSESS□-1
: 3OCR+EFR *3
2OCR(N)+EFR(E) DQASP2M□ DQASL7M□ DQASS5M□ DUTSESS□-1
: 3OCR+EFR *3
3OCR(N)+EFR(V) DQASP3M□ DQASL6M□ DQASS4M□ DUTSESS□-1
: 3OCR+EFR
3OCR(N)+EFR(E) DQASP4M□ DQASL8M□ DQASS6M□ DUTSESS□-1
: 3OCR+EFR
2OCR(V)+EFR(V) DQASR1M□ DQASK5M□ DQASP5M□ DUTSESS□-1
: 3OCR+EFR *3
2OCR(E)+EFR(E) DQASR2M□ DQASK7M□ DQASP7M□ DUTSESS□-1
: 3OCR+EFR *3
3OCR(V)+EFR(V) DQASR3M□ DQASK6M□ DQASP6M□ DUTSESS□-1
: 3OCR+EFR
3OCR(E)+EFR(E) DQASR4M□ DQASK8M□ DQASP8M□ DUTSESS□-1
: 3OCR+EFR
Note: The alphabets in parentheses ( ) following OCR/EFR represents inverse time characteristics.
(N): Normal inverse time characteristics (V): Strong inverse time characteristics
(E): Extremely inverse time characteristics (L): Long inverse time characteristics

<Cautions in selecting a model succeeding conventional ones>


Notes *1:Since the number of external terminals of the control circuit of the case is different from that of conventional models
(Conventional models: 10, this model: 12), the relay element cannot be mounted to the case of conventional models. When updating conventional models,
replace them along with the case.
*2:The rating of the control power supply of this relay: 100V, 110V, and 125V DC
*3:When selecting a model succeeding conventional 1OCR or 2OCR model, connect the input phase required for this model, 3OCR or 2OCR, to the external
terminal.
(Since the trip output of this model is “OR output of each phase”, 1 or 2 input only is applicable.)
*4:For conventional “EFR without instantaneous element” model, select “DUTSESS□-1 (3OCR+EFR)”, set the inverse time and instantaneous elements of
3OCR to “Lock setting”, and operate the relay with EFR only.
*5:For conventional “EFR with instantaneous element” model, select “DUTSESS□-1 (3OCR+EFR), set the inverse time element of 3OCR to “Lock setting”,
and operate the relay with OCR instantaneous element and EFR only.
*6:The outside dimensions of the case of conventional 2nd to 5th generation models and those of the case of this relay are the same. The outside dimensions
of the case of the 1st generation model only are different.

16
DRAW Series
Protective relays

DRAW Series is made up of two types: undercurrent relays and (5) The auxiliary energizing source can be selected from 100 to
current-limiting relays. 110 V/200 to 220 V AC using an external terminal connection.
These electrical relays are the alternating current electrical relays (Input frequency for AC control power supply uses 50/60 Hz in
applicable to analog static principles. common.)
The DRAW Series has the following features. (6) The series uses the structure that allows surface-mounting on
the panel by adopting the same main unit case outer shape as
■Features
the previous models. The external terminal arrangement is also
(1) It uses basic circuitry based on analog static principles the same, so that it is easy to make exchanges using existing
successfully used with previous models. Since this series does parts.
not use electronic parts such as semiconductor ICs, which are (7) Since the internal circuitry has a static and simple interior
sensitive to external surge noise voltage, it ensures sufficiently structure excluding the output relay, no dimensional error will
stable performance against disturbance. be created by mounting angle. As a result, it can be installed
(2) The alternating current input frequency is a common value of inside of the switchboard at an arbitrary angle when being
50/60 Hz so that it can detect operating current with high mounted to the main unit.
sensitivity. (8) These relays conform to standard of JEC-2500-1987 (Protective
(3) The current-limiting relay has a performance level suitable for Relays for Electric Power Systems.). The immunity to square
starting control operations, such as alternating AC would-rotor wave impulse noise (high frequency noise), radio wave noise
type electrical motors. and electrostatic discharge noise conforms to standard of B-
(4) Since the series uses a stabilization method using a dial, it can 402 (Digital Protective Relays and Protective Equipment).
stabilize the load continuously and easily.

The DRAW Series protective relays are standardized as the following two models.
Name Application Type
Static type undercurrent relay Undercurrent or disconnection detection in AC circuit DRAWN5SA
Static type current-limit relay Current-limit starting of AC wound-rotor motor DRAWN6SA
* Previously, there were several models with separated stabilization section (no stabilization dial provided but external support is required) in the DRAW Series, but now only the
integrated stabilization models (stabilization dial provided as standard) are currently commercialized.

DRAW series protective relays Example D R A W N 6 S A – 7 M S Y Q –


1 2 3 4 5 6 7 8
 Basic
1 type 5 Rated current and operation setting:
DRAW: Static type undercurrent relay (Surface mounting type, crest value Rated value 5 A, Stabilizing range 1 to 5 A.
detection type) 6 Rated auxiliary energizing source voltage:
 Construction
2 100/110 to 200/220V AC (50/60 Hz common)
N5: Undercurrent relay (Holding factor: 5%) 7 Power supply specifications for appendages:
N6: Current-limit relay (Holding factor: 25%) Q: No appendages
3 External form, structure, output circuit configuration: 8 Special specification:
SA: Covered structure with dedicated case, configuration with no external Not required for standard product (standard case, transparent cover, English
appendages. nameplate, no tropical zone processing)(Contact us for details.)
4 Rated frequency: 7: 50/60 Hz common

17
TELR series
Control relay

The TELR control relay series, a successor to the conventional • Since the plug-in structure and terminals of the conventional
DRHH-series assembly plug-in units, include auxiliary relays, a DRHH-series relays are adopted, the relay can be stored in a
keep relay, and time-lag relays. case for the conventional DRHH-series assembly plug-in relays
Since this relay has an external shape and terminal socket (DQBA2, DQBD1, etc.)
equivalent to those of the conventional DRHH-series assembly • The relay has performance equivalent to that of conventional
plug-in units, replacement is easy. DRHH-series relays, conforming to the JEC-2500 (1987) power
Since the TELR series keep relay has a different internal circuit relay, JEC-174D (1979) power auxiliary relay, and JEC-174E
structure than the conventional DRKH series models, refer to the (1980) power time-lag relay standards.
updating notes described below. • The TELR-series control relays are manufactured by Fuji Electric
Industry Co., Ltd., and sold and delivered by Fuji Electric Systems
■Features
Co., Ltd. You cannot place orders directly with Fuji Electric
• Select applicable succeeding models (specifications) to your Industry Co., Ltd.
conventional DRHH-series assembly plug-in units. (See the
following table and each specification of the TELR-series control
relays for details.)

TELR-series control relay Corresponding conventional models


Model Type Specifications
Auxiliary relay TELR-HHB5CA-DC110V Coil rating : 100/110V DC DRHHB1CA
(Single coil (DC)) DRHHB5CA
Auxiliary relay TELR-HHB5VA-DC110V Coil rating : 100/110V DC DRHHB5VA
(Single coil (DC)/high speed type)
Auxiliary relay TELR-HHB1UA-DC0.3A Coil rating : 0.3A DC DRHHB1UA
(Double coil (DC)) TELR-HHB1UA-DC0.8A Coil rating : 0.8A DC
TELR-HHB1UA-DC1.0A Coil rating : 1A DC
Keep relay TELR-KHB5AB-DC110V Coil rating : 100/110V DC DRKHB1AB
DRKHB5AB
Time-lag relay TELR-TK1PA-100/220-A Setting : 0.5 to 3s DRTKA1PA
TELR-TK1PA-100/220-B Setting : 1 to 30s
TELR-TK1PA-100/220-C Setting : 30 to 180s
* The time-lag relay allows free input voltage between 100 to 200V AC/DC at 50/60Hz DC.

■Notes for updating to the TELR series keep relay


The input terminals of the operating (first) coil and resetting (second) coil of the TELR series keep relay are polarized and feature a
terminal structure that is common with the Nos. 2 to 4 input terminals (negative polarity). For this reason, these TELR series characteristics
are different from those of the conventional DRKH series models.
When updating the conventional DRKHB series models, pay particular attention to the polarity of the input terminals of these coils. If the
No. 2 and No. 4 input terminals are used as + polarity in the conventional model wiring, be sure to change the wiring.

18
Digital Type Ground Overcurrent Relay
DUT □ EH, DUT □ ET
DUT □ EN, DUT □ EM(Noise immunity conforming to standard of B-402)

★Information required with your inquiry or order. The pitch in parentheses and lock setting "L" need not be specified.
Application Detection of ground fault (Mainly resistance grounded line system)
Principle and name Digital type ground overcurrent relay
Classification Auxiliary energizing source Input ★Type *11
Unit standard DC 1 DUTUEHAS−2 DUTUEHAK−2 DUTUEHAA−2 DUTUETAS−2 DUTUETAK−2 DUTUETAA−2
structure type AC DUTAEHAS−2 DUTAEHAK−2 DUTAEHAA−2 DUTAETAS−2 DUTAETAK−2 DUTAETAA−2
DQ series DC 1 DUTREHAS−2 DUTREHAK−2 DUTREHAA−2 DUTRETAS−2 DUTRETAK−2 DUTRETAA−2
replacement
type *1 AC DUTBEHAS−2 DUTBEHAK−2 DUTBEHAA−2 DUTBETAS−2 DUTBETAK−2 DUTBETAA−2
Unit standard DC 1 DUTUENAS−2 DUTUENAK−2 DUTUENAA−2 DUTUEMAS−2 DUTUEMAK−2 DUTUEMAA−2
structure type *10 AC DUTAENAS−2 DUTAENAK−2 DUTAENAA−2 DUTAEMAS−2 DUTAEMAK−2 DUTAEMAA−2
Ratings ★Frequency [Hz] 50, 60
★Current [A] AC 1, 5
Element Inverse time−lag Instantaneous Independent time−lag
Setting ★Setting value 1A 0.02 to 0.16(0.01)−L 0.1 to 0.8(0.01)−L 0.02 to 0.16(0.01)
range *2 [A] AC 0.1 to 0.8(0.01)−L 0.5 to 4(0.1)−L 0.1 to 0.8(0.01)
5A 0.1 to 0.8(0.01)−L 0.5 to 4(0.1)−L 0.1 to 0.8(0.01)
0.5 to 4(0.1)−L 2.5 to 20(0.1)−L 0.5 to 4(0.1)
Time setting n=0.5 to 50(n=0.1) 0 to 3s(0.1s)*3 0 to 3s(0.1s)*3
Output duration *4 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Rated burden [VA] 0.4
Continuous withstand current 100% of rated value
Auxiliary ★Voltage [V] DC 100, 110, 125, 200, 220, 250
energizing
source *5 AC 100, 110, 127, 200, 220, 250 50, 60Hz
Rated burden DC 100, 110, 125V rated : 6.5W 200, 220, 250V rated : 8.5W
AC 100, 110, 127V rated : 15VA 200, 220, 250V rated : 20VA
Operation Display hold function *12 With With – With With –
indicators DC auxiliary LED: Time lag x 1, Instantaneous x 1 LED: Operation x 1
energizing source
AC auxiliary 1 input LED: Time lag x 1, Instantaneous x 1 LED: Operation x 1 LED: Operation x 1
energizing source Magnetic inversion: – Magnetic inversion: Operation x 1
Time lag x 1, Instantaneous x 1
2 inputs – –

3 inputs – –
Contacts Arrangement Trip: Time lag 1NO ("a" make contact), Instantaneous: 1NO, Trip: 1NO, Alarm: 1NC
Alarm: 1NC ("b" break contact), External output: 1NO External output: 1NO
Limiting making capacity [A] 15 (R-load, 0.5s, 110V DC)
Continuous current carrying [A] 5
capacity
Limiting breaking capacity [VA] DC 10 (L-load, L/R=0.04, 110V DC)
Characteristics Operate time *6 *6, *7 *6, *8
Operate value accuracy [%] *9 ±5 *9
f2 locking function (f2/f1) [%] – 15 or more 15 or more
Holding factor [%] 5
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2
Previous relay type DQAJA1HH DQAJA1HB DQAJA1HA DQARA1HH, DQARA1HB, DQARA1HA,
DQAWA2HH,G DQAWA2HB,D DQAWA2HA,N
Notes
*1:DQ series replacement relay having the same external terminal arrangement with DQ series relay. DQ series replacement relay with panel mounting
adapter that has the same depth with DQ series relay, is also available. For details, contact Fuji. 
*2:The value in parentheses indicates the pitch, and "L" indicates that the setting is locked. *3:Zero represents instantaneous operate time (80ms max.).
*4:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of 0.2±0.1s is used on other occasions.
*5:Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*6:Refer to "Operate time characteristics".
*7:±5% of max. time setting, or for min. time setting, 80ms max. when 200% input current of operate setting value.
*8:±5% of max. time setting, or for min. time setting, 80ms max. when 300% input current of operate setting value.
*9:±5% in accuracy guaranteed setting range (three times min. of min. operate setting value to max. operate setting value), ±15% for outside the accuracy
guaranteed setting range.
*10:Noise immunity per B-402 (Digital Protective Relays and Protective Equipment).
*11:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*12:If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold function.
If "A" is selected, the LED indicator has no display hold function.

1ー 1
Digital Type Overcurrent Relay
DUT □ AH, DUT □ AT
DUT □ AN, DUT □ AM(Noise immunity conforming to standard of B-402)

★Information required with your inquiry or order. The pitch in parentheses and lock setting "L" need not be specified.
Application Detection of overload, short-circuit, and ground fault of directly grounded line system
Principle and name Digital type overcurrent relay
Classification Auxiliary energizing source Input ★Type *33
Unit standard DC 1 DUTUAHAS−2 DUTUAHAK−2 DUTUAHAA−2 DUTUATAS−2 DUTUATAK−2 DUTUATAA−2
structure type AC DUTAAHAS−2 DUTAAHAK−2 DUTAAHAA−2 DUTAATAS−2 DUTAATAK−2 DUTAATAA−2
DQ series DC 1 DUTRAHAS−2 DUTRAHAK−2 DUTRAHAA−2 DUTRATAS−2 DUTRATAK−2 DUTRATAA−2
replacement
type *21 AC DUTBAHAS−2 DUTBAHAK−2 DUTBAHAA−2 DUTBATAS−2 DUTBATAK−2 DUTBATAA−2
Unit standard DC 2 DUTUAHBS−2 DUTUAHBK−2 – DUTUATBS−2 DUTUATBK−2 –
structure type AC DUTAAHBS−2 DUTAAHBK−2 – DUTAATBS−2 DUTAATBK−2 –
Unit standard DC 3 DUTUAHCS−2 DUTUAHCK−2 – DUTUATCS−2 DUTUATCK−2 –
structure type AC DUTAAHCS−2 DUTAAHCK−2 – DUTAATCS−2 DUTAATCK−2 –
Unit standard DC 1 DUTUANAS−2 DUTUANAK−2 DUTUANAA−2 DUTUAMAS−2 DUTUAMAK−2 DUTUAMAA−2
structure type *32 AC DUTAANAS−2 DUTAANAK−2 DUTAANAA−2 DUTAAMAS−2 DUTAAMAK−2 DUTAAMAA−2
Ratings ★Frequency [Hz] 50, 60
★Current [A] AC 1, 5
Element Inverse time−lag Instantaneous ndependent time−lag
Setting ★Setting value 1A 0.2 to1.2 (0.1)−L 1 to 8 (0.1)−L 0.2 to 1.2 (0.1)
range *22 [A] AC 0.4 to 2.4 (0.1)−L 2 to 16 (0.1)−L 0.4 to 2.4 (0.1)
5A 1 to 6 (0.1)−L 5 to 40 (0.1)−L 1 to 6 (0.1)
2 to 12 (0.1)−L 10 to 80 (1)−L 2 to 12 (0.1)
Time setting n=0.5 to 50 (n=0.1) 0 to 3s (0.1s)*26 0 to 3s (0.1s)*27
Output duration *23 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Rated burden [VA] 0.4
Continuous withstand current 100% of rated value
Auxiliary ★Voltage [V] DC 100, 110, 125, 200, 220, 250
energizing
source *24 AC 100, 110, 127, 200, 220, 250 50, 60Hz
Rated burden DC 100, 110, 125V rated : 6.5W 200, 220, 250V rated : 8.5W
AC 100, 110, 127V rated : 15VA 200, 220, 250V rated : 20VA
Operation Display hold function *34 With With – With With –
indicators *31 DC auxiliary energizing source LED: Time lag x 1, Instantaneous x 1 LED: Operation x 1
AC auxiliary 1 input LED: Time lag x 1, Instantaneous x1 LED: Operation x 1 LED: Operation x 1
energizing source Magnetic inversion: Time lag x 1, Instantaneous x 1 – Magnetic inversion: Operation x 1
2 inputs LED: Time lag x 1, Instantaneous x 1 – LED: Operation x 1 –
Magnetic inversion: Phase display x 2, Instantaneous x 1 Magnetic inversion: Phase display x 2
3 inputs LED: Time lag x 1, Instantaneous x 1 – LED: Operation x 1 –
Magnetic inversion: Phase display x 3, Instantaneous x 1 Magnetic inversion: Phase display x 3
Contacts Arrangement Trip: Time lag 1NO ("a" make contact), Instantaneous 1NO, Trip: 1NO, Alarm: 1NC
Alarm: 1NC ("b" break contact), External output: 1NO External output: 1NO
Limiting making capacity [A] 15 (R-load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10 (L–load, L/R=0.04, 110V DC)
Characteristics Operate time *25 *25, *28 *25, *29
Operate value accuracy [%] *30 ±5 *30
f2 locking function (f2/f1) [%] – – –
Holding factor [%] 5
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2
Previous relay 1 input DQAJB1,C1,D1HJ DQAJB1,C1,D1HC DQAJB1HA, DQARA1HH,DQAWA2 DQARA1HB,DQAWA2 DQARA1HA,DQAWA2
type (DQAJB1,C1,D1HH) (DQAJB1,C1,D1HB) DQAJD1HA (C2,E2,F1,J2)HH,G (C2,E2,F1,J2)HB,D (C2,E2,F1,J2)HA,N
2 inputs, 3 inputs – – – DQAWG1P□ –
Notes
*21:DQ series replacement relay having the same external terminal arrangement with DQ *30:±5% in accuracy guaranteed setting range (1.5 times min. of min. operate setting value to
series relay. DQ series replacement relay with panel mounting adapter that has the same max. operate setting value), ±10% for outside the accuracy guaranteed setting range.
depth with DQ series relay, is also available. For details, contact Fuji.  *31:Display by phase (R, S, and T) is as follows.
*22:The value in parentheses indicates the pitch, and "L" indicates that the setting is locked. DC auxiliary energizing source: Numbers 1 and 3 appear on the setting display (7
*23:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of segments) when the number of inputs is 2 ("2" is not displayed for (S) phase), and 1, 2, and
0.2±0.1s is used on other occasions. 3 appear when the number of inputs is 3.
*24:Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may AC auxiliary energizing source: Numeric values that appear on the setting display (7
exceed 2s depending on input or operating conditions. segments) are the same as the case of a DC auxiliary energizing source. Characters "R"
*25:Refer to "Operate time characteristics". and "T" appear on the magnetic inversion operation indicator when the number of inputs is
*26:Zero represents instantaneous operate time (40ms max.). 2 ((S) phase is not displayed), and "R", "(S)" and "T" appear when the number of inputs is 3.
*27:Zero represents instantaneous operate time (50ms max.). *32:Noise immunity per B-402 (Digital Protective Relays and Protective Equipment) .
*28:±5% of max. time setting, or for min. time setting, 40ms max. when 200% input current of *33:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
operate setting value. *34:If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic
*29:±5% of max. time setting, or for min. time setting, 50ms max. when 300% input current of inversion operation indicators are provided with a display hold function.
operate setting value. If "A" is selected, the LED indicator has no display hold function.

1ー 2
Digital Type Overcurrent Relay(A Wide Frequency Band )
DUT □ AF, DUT □ AG

★Information required with your inquiry or order. The pitch in parentheses and lock setting "L" need not be specified.
Application Detection of overload, short-circuit, and ground fault of directly grounded line system
Principle and name Digital type overcurrent relay (A wide frequency band)
Classification Auxiliary energizing source Input ★Type *43,*44
Unit standard DC 1 DUTUAFASー2 DUTUAFAKー2 DUTUAFAAー2 DUTUAGASー2 DUTUAGAKー2 DUTUAGAAー2
structure type AC DUTAAFASー2 DUTAAFAKー2 DUTAAFAAー2 DUTAAGASー2 DUTAAGAKー2 DUTAAGAAー2
Ratings ★Frequency [Hz] 50, 60
★Current AC [A] 1, 5
Element Inverse time-lag Instantaneous Independent time-lag
Setting ★Setting value 1A 0.2 to1.2 (0.1)ーL 1 to 8 (0.1)ーL 0.2 to 1.2 (0.1)
range *41 [A] AC 0.4 to 2.4 (0.1)ーL 2 to 16 (0.1)ーL 0.4 to 2.4 (0.1)
5A 1 to 6 (0.1)ーL 5 to 40 (0.1)ーL 1 to 6 (0.1)
2 to 12 (0.1)ーL 10 to 80 (1)ーL 2 to 12 (0.1)
Time setting n=0.5 to 50 (n=0.1) 0 to 3s (0.1s)*48 0 to 3s (0.1s)*49
Output duration *46 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Rated burden [VA] 0.4
Continuous withstand current 100% of rated value
Auxiliary ★Voltage [V] DC 100, 110, 125, 200, 220, 250
energizing AC 100, 110, 127, 200, 220, 250 50, 60Hz
source *47
Rated burden DC 100, 110, 125V rated : 6.5W 200, 220, 250V rated : 8.5W
AC 100, 110, 127V rated : 15VA 200, 220, 250V rated : 20VA
Operation Display hold function *53 With With – With With –
indicators DC auxiliary energizing source LED: Time lag x 1, Instantaneous x 1 LED: Operation x 1
AC auxiliary LED: Time lag x 1, Instantaneous x 1 LED: Operation x 1 LED: Operation x 1
energizing source Magnetic inversion: Time lag x 1, Instantaneous x 1 – Magnetic inversion: Operation x 1
Contacts Arrangement Trip: Time lag 1NO ("a" make contact), Instantaneous: 1NO Trip: 1NO, Alarm: 1NC
Alarm: 1NC ("b" break contact), External output: 1NO External output: 1NO
Limiting making capacity [A] 15 (R-load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10 (L-load, L/R=0.04, 110V DC)
Characteristics Operate time *42,*45 *42,*50 *42,*51
Operate value accuracy [%] *52 ±5 *52
Holding factor [%] 10 5 10
Characteristics influenced 1) ±5% variability characteristics of the rated input frequency.
by frequency (1)Operate value:The inverse time-lag element is within ±10%, and the instantaneous element and
independent time-lag element are within ±5% of the rating.
(2)Operate time:At inverse time-lag element operate time setting n=10, and instantaneous element and
independent time-lag element operate time setting 3s:
Inverse time-lag element:within ±12% of the rated value at input current 300%, within ±7% at input current
500% or 1000%
Instantaneous element:within ±5% of the rated value at input current 200%
Independent time-lag element:within ±5% of the rated value at input current 300%
2)ー20 to +50% variability characteristics of the rated input frequency.
(1)Operate value:At the inverse time-lag element, instantaneous element and independent time-lag element
are within ±20% of the rated value.
(2)Operate time:At inverse time-lag element operate time setting n=10, and instantaneous element and
independent time-lag element operate time setting 3s:
Inverse time-lag element:within ±40% of the rated value at input current 300%, within ±30% at input current
500% or 1000%
Instantaneous element:within ±10% of the rated value at input current 200%
Independent time-lag element:within ±10% of the rated value at input current 300%
Mass [kg] 2
Outline drawing Fig. DUT1
Previous relay type DQAJB1,C1,D1HJ DQAJB1,C1,D1HC DQAJB1HA DQARA1HH DQARA1HB DQARA1HA
(DQAJB1,C1,D1HH) (DQAJB1,C1,D1HB) DQAJD1HA
Notes
*41: The value in parentheses indicates the pitch, and "L" indicates that the setting is locked..
*42: Refer to "Operate time characteristics".
*43: This product, the frequency characteristic of which is enhanced from the specifications of the JEC standard, can handle broadband. Its noise immunity
complies with the standard of B-402.
*44: Refer to the identifications on page 9 for the tenth digit or later of the code symbol.
*45: The operational characteristics of the inverse time-lag element of wide-frequency products are C1 to C5, a total of five characteristics.
*46: The output duration of 1±0.1s is used in the case of the circuit breaker trippong, and that of 0.2±0.1s is used on other occasions
*47: Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*48: Zero represents instantaneous operate time (40ms max.).
*49: Zero represents instantaneous operate time (50ms max.).
*50: ±5% of max. time setting, or for min. time setting, 40ms max. when 200% input current of operate setting value.
*51: ±5% of max. time setting, or for min. time setting, 50ms max. when 300% input current of operate setting value.
*52: ±5% in accuracy guaranteed setting range (1.5 times min. of min. operate setting value to max. operate setting value), ±10% for outside the accuracy guaranteed setting range.
*53: If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold function.
If "A" is selected, the LED indicator has no display hold function.

1ー 3
Operate time characteristics

■Inverse time-lag element DUT□□H□□ー2, DUT□□N□□ー2, DUT□□F□□ー2


Note : The operate time properties of the inverse time-lag element of wide-frequency products (Type : DUT□□F□□-2) are C1 to C5, a total of five characteristics.
¡Normal inverse time-lag (characteristic code : C1) ¡Short inverse time-lag (characteristic code : C2)
Inverse time-lag element operating time properties (reference) Inverse time-lag element operating time properties (reference)
I : Input multiple of operating current setting I : Input multiple of operating current setting
    0.14 n   0.034    n
t =     × n : Operational time setting t =     × n : Operational time setting
0.02 0.02
  I − 1  10 t : Operational time(s)   I − 1  10 t : Operational time(s)
[s] [s]
1000 100

100 10

n
50
40
1.53
Operate time
Operate time

30
n
50 1.04 20
10 1
40 0.72
6.3 30
10
4.3 9
20 8
7
3 6
10 5
9 4
8 3
7
6
5 2
1 4 0.1

3
1
2 0.5

0.5
0.1 0.01
100 200 300 500 700 1000 2000[%] 100 200 300 500 700 1000 2000[%]
Input current (100% = Setting current) Input current (100% = Setting current)
Operate time accuracy:Refer to *1 Operate time accuracy:Refer to *1 and *2
Input current 300% 500% 1000% Input current 300% 500% 1000%
Setting value Time Accuracy Time Accuracy Time Accuracy Setting value Time Accuracy Time Accuracy Time Accuracy
Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%] Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%]
50 31.5 ±12 ー ー 15 ±7 50 7.65 ±12 ー ー 3.6 ±7
10 6.3 ±12 4.3 ±7 3 ±7 10 1.53 ±12 1.04 ±7* 0.72 ±7*
Accuracy guaranteed

Accuracy guaranteed

7 4.41 ±10 ー ー 2.1 ±6 7 1.071 ±10 ー ー 0.504 ±6*


Within

Within

4 2.52 ±8 ー ー 1.2 ±5 4 0.612 ±8 ー ー 0.288 ±5*


1 0.63 ±6 ー ー 0.3 ±4 1 0.153 ±6* ー ー 0.072 ±4*
±18 ±10 ±18 ±10
setting range

setting range

50 31.5 ー ー 15 50 7.65 ー ー 3.6


10 6.3 ±18 4.3 ±10 3 ±10 10 1.53 ±18 1.04 ±10 0.72 ±10*
±15 ±9 ±15 ±9*
Outside

Outside

7 4.41 ー ー 2.1 7 1.071 ー ー 0.504


4 2.52 ±12 ー ー 1.2 ±7 4 0.612 ±12 ー ー 0.288 ±7*
1 0.63 ±9 ー ー 0.3 ±6 1 0.153 ±9 ー ー 0.072 ±6*

Notes *1:Operate time accuracyε〔%〕 T10: Nominal operate time at reference operate time *2:Accuracy of items marked "*" is ±100ms
setting "n" = 10 when the value "ε・T10 " given in the
When "n" ≦ 10          When "n">10
n n Tn : Actual operate time at operate time setting "n" above equation " ε " is smaller than
Tn −    ×T10 Tn −    ×T10 100ms.
10 10
ε=        ×100 〔%〕 ε=        ×100
n
〔%〕 Where
T10   ×T10
10 Operate time setting
n =                            ×10
Reference operate time setting

1ー 4
¡Long inverse time-lag (characteristic code : C3) ¡Very inverse time-lag (characteristic code : C4)
Inverse time-lag element operating time properties (reference) Inverse time-lag element operating time properties (reference)
I : Input multiple of operating current setting I : Input multiple of operating current setting
    1.12   n   13.5   n
t =     × n : Operational time setting t =   × n : Operational time setting
[s]   I − 1  10 t : Operational time(s) [s]   I − 1  10
0.02
t : Operational time(s)
10000 1000

1000 100

n
100 50 10
40 6.75
50
Operate time
Operate time

30
n
34 3.38
20 50
24 40
10 30
9 1.5
8 20
7
10 6 1
5 10
4 9
8
3 7
6
2 5
4
3
1
2

1 0.5 0.1
1
0.5

0.1 0.01
100 200 300 500 700 1000 2000[%] 100 200 300 500 700 1000 2000[%]
Input current (100% = Setting current) Input current (100% = Setting current)
Operate time accuracy:Refer to *1 on page 1-4. Operate time accuracy:Refer to *1 and *2 on page 1-4.
Input current 300% 500% 1000% Input current 300% 500% 1000%
Setting value Time Accuracy Time Accuracy Time Accuracy Setting value Time Accuracy Time Accuracy Time Accuracy
Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%] Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%]
50 250 ±12 ー ー 120 ±7 50 33.75 ±12 ー ー 7.5 ±7
10 50 ±12 34 ±7 24 ±7 10 6.75 ±12 3.38 ±7* 1.5 ±7
Accuracy guaranteed

Accuracy guaranteed

7 35 ±10 ー ー 16.8 ±6 7 4.725 ±10 ー ー 1.05 ±6*


Within

Within

4 20 ±8 ー ー 9.6 ±5 4 2.7 ±8 ー ー 0.6 ±5*


1 5 ±6 ー ー 2.4 ±4 1 0.675 ±6 ー ー 0.15 ±4*
±18 ±10 ±18 ±10
setting range

setting range

50 250 ー ー 120 50 33.75 ー ー 7.5


10 50 ±18 34 ±10 24 ±10 10 6.75 ±18 3.38 ±10 1.5 ±10
±15 ±9 ±15 ±9
Outside

Outside

7 35 ー ー 16.8 7 4.725 ー ー 1.05


4 20 ±12 ー ー 9.6 ±7 4 2.7 ±12 ー ー 0.6 ±7
1 5 ±9 ー ー 2.4 ±6 1 0.675 ±9 ー ー 0.15 ±6*

1ー 5
¡Strong very inverse time-lag (characteristic code : C5) ¡Extremely inverse time-lag (characteristic code : C6)
Inverse time-lag element operating time properties (reference) Inverse time-lag element operating time properties (reference)
I : Input multiple of operating current setting I : Input multiple of operating current setting
  120   n    80   n
t =   × n : Operational time setting t =   × n : Operational time setting
2
[s]   I − 1  10 t : Operational time(s) [s]   I − 1  10 t : Operational time(s)
10000 10000

1000
1000

100

100
60
Operate time
Operate time

n
30 10
50 10
40
30
13.3 3.3
20
10
10
9 n
8 1 50
7 0.8 40
6
5 30
4 20
3
2 10
9
1 8
7
1 0.1 6
5
4
3
0.5 1 2
0.5

0.1 0.01
100 200 300 500 700 1000 2000[%] 100 200 300 500 700 1000 2000[%]
Input current (100% = Setting current) Input current (100% = Setting current)
Operate time accuracy:Refer to *1 on page 1-4. Operate time accuracy:Refer to *1 and *2 on page 1-4.
Input current 300% 500% 1000% Input current 300% 500% 1000%
Setting value Time Accuracy Time Accuracy Time Accuracy Setting value Time Accuracy Time Accuracy Time Accuracy
Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%] Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%]
50 300 ±12 ー ー 66.5 ±7 50 50 ±12 ー ー 4 ±7
10 60 ±12 30 ±7 13.3 ±7 10 10 ±12 3.3 ±7 0.8 ±7*
Accuracy guaranteed

Accuracy guaranteed

7 42 ±10 ー ー 9.31 ±6 7 7 ±10 ー ー 0.56 ±6*


Within

Within

4 24 ±8 ー ー 5.32 ±5 4 4 ±8 ー ー 0.32 ±5*


1 6 ±6 ー ー 1.33 ±4 1 1 ±6 ー ー 0.08 ±4*
±18 ±10 ±18 ±10
setting range

setting range

50 300 ー ー 66.5 50 50 ー ー 4
10 60 ±18 30 ±10 13.3 ±10 10 10 ±18 3.3 ±10 0.8 ±10*
±15 ±9 ±15 ±9*
Outside

Outside

7 42 ー ー 9.31 7 7 ー ー 0.56
4 24 ±12 ー ー 5.32 ±7 4 4 ±12 ー ー 0.32 ±7*
1 6 ±9 ー ー 1.33 ±6 1 1 ±9 ー ー 0.08 ±6*

1ー 6
■Instantaneous element ■Independent time-lag element
DUT□□H□□ー2, DUT□□N□□ー2, DUT□□F□□ー2 DUT□□T□□ー2, DUT□□M□□ー2, DUT□□G□□ー2

[s] [s]
5 5

4 4

Operate time setting

Operate time setting


3 3s 3 3s
Operate time

Operate time
2.1s 2.1s
2 2

1.2s 1.2s
1 1

0.3s 0.3s
0 0
100 200 300 400   500[%] 100 200 400 600 800   1000[%]
Input current (100% = Setting current) Input current (100% = Setting current)

Operate time accuracy:Refer to *1 on page 1-4. Operate time accuracy:Refer to *1 and *2 on page 1-4.
Input current 200% Input current 300%
Setting value Accuracyε[%] (operate time range) Setting value Accuracyε[%] (operate time range)
operate time setting [s] operate time setting [s]
All current 3 ±5 (2.850 to 3.150s) All current 3 ±5 (2.850 to 3.150s)
setting setting
2.1 ±4.3 (1.971 to 2.229s) 2.1 ±4.3 (1.971 to 2.229s)
1.2 ±3.5 (1.095 to 1.305s) 1.2 ±3.5 (1.095 to 1.305s)
0.3 ±2.8 (0.216 to 0.384s) 0.3 ±2.8 (0.216 to 0.384s)
Remark:Operate time in the state where operate time setting is 0s. Remark:Operate time in the state where operate time setting is 0s.
DUT□E type relay:80ms max. DUT□E type relay:80ms max.
DUT□A type relay:40ms max. DUT□A type relay:50ms max.

1ー 7
Internal connection diagrams

DUTUEHA□ー2, DUTAEHA□ー2 DUTUETA□ー2, DUTAETA□ー2


DUTUENA□ー2, DUTAENA□ー2 DUTUEMA□ー2, DUTAEMA□ー2
DUTUAHA□ー2, DUTAAHA□ー2 DUTUATA□ー2, DUTAATA□ー2
DUTUANA□ー2, DUTAANA□ー2 DUTUAMA□ー2, DUTAAMA□ー2
DUTUAFA□ー2, DUTAAFA□ー2 DUTUAGA□ー2, DUTAAGA□ー2

L H AL L H L AL L

3 4 11 12 13 14 15 16 17 9 10 18 3 4 11 12 14 15 16 17 9 10 18
+ − + −
I Trip Alarm External SO. I Trip Alarm External SO.
output output

 DUTUAHB□ー2, DUTAAHB□ー2 DUTUATB□ー2, DUTAATB□ー2

L H AL L H L AL L

1 2 5 6 11 12 13 14 15 16 17 9 10 18 1 2 5 6 11 12 14 15 16 17 9 10 18
+ − + −
IR IT Trip Alarm External SO. IR IT Trip Alarm External SO.
output output

 DUTUAHC□ー2, DUTAAHC□ー2 DUTUATC□ー2, DUTAATC□ー2

L H AL L H L AL L

1 2 3 4 5 6 11 12 13 14 15 16 17 9 10 18 1 2 3 4 5 6 11 12 14 15 16 17 9 10 18
+ − + −
IR IS IT Trip Alarm External SO. IR IS IT Trip Alarm External SO.
output output

 DUTREHA□ー2, DUTBEHA□ー2 DUTRETA□ー2, DUTBETA□ー2


 DUTRAHA□ー2, DUTBAHA□ー2 DUTRATA□ー2, DUTBATA□ー2

L H AL L H L AL L

A3 A4 A5 A6 A7 B14 B15 A9 A10 B9 B10 B18 A3 A4 A5 A6 B14 B15 A9 A10 B9 B10 B18
+ − + −
I Trip Alarm External SO. I Trip Alarm External SO.
output output

1ー 8
Digital Type Ground Overcurrent Relay for Non-ground Line
DUT □ C

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Ground fault detection of non-ground line
Principle and name Digital type ground overcurrent relay for non-ground line
Classification Auxiliary energizing source ★Type *5,*6
Unit standard DC DUTUCTASー1 DUTUCTAKー1 DUTUCTAAー1
structure type AC DUTACTASー1 DUTACTAKー1 DUTACTAAー1
DQ series DC DUTRCTASー1 DUTRCTAKー1 DUTRCTAAー1
replacement
type *2 AC DUTBCTASー1 DUTBCTAKー1 DUTBCTAAー1
Ratings ★Frequency [Hz] 50, 60
★Current (input 1) [A] AC*1 2
Element Independent time-lag
Setting ★Setting value [mA] AC 1.5 to 15(0.1), 10 to 100(1), 40 to 400(1)
range *8 [ZCT secondary current]
Time setting [s] 0 to 3(0.1) Note that, 0 denotes 0.2±0.05 immediately
Output duration *3 [s] 1±0.1 0.2±0.1 0.2±0.1
Rated burden Operating current value setting 1.5 to 15mA: 2.7Ω 10 to 100mA: 0.82Ω 40 to 400mA: 0.27Ω
Continuous withstand current 100% of rated value
Auxiliary ★Voltage [V] DC 100, 110, 125, 200, 220, 250
energizing AC 100, 110, 127, 200, 220, 250 50, 60Hz
source *4
Rated burden DC 100, 110, 125V rated : 6.5W 200, 220, 250V rated : 8.5W
AC 100, 110, 127V rated : 15VA 200, 220, 250V rated : 20VA
Operation Display hold function *7 With With ー
indicators Auxiliary energizing source DC LED: Operation x 1
AC LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1
Contacts Arrangement Trip: 1NO ("a" make contact), Alarm: 1NC ("b" break contact), External output: 1NO
Limiting making capacity [A] 15 (R-load, 0.5s, 110V DC)
Continuous current carrying [A] 5
capacity
Limiting breaking capacity [VA] DC 10 (L-load, L/R=0.04, 110V DC)
Characteristics Operate time Refer to "Operate time characteristics".
Operate value accuracy [%] ±10
Holding factor [%] 20
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2
Previous relay type DQAWD□HH(G) DQAWD□HB(D) DQAWD□HA(N)
Notes
*1:The rated current indicates that of the relay, not that of a zero-sequence rated current of the ZCT.
Be sure to select L-class (200/1.5mA, Z=10Ω, pf=0.5) of JEC-1201 as ZCT.
*2:DQ series replacement relays having the same terminal arrangement with DQ series relays. The replacement relays provided with panel mounting adapter,
to make the depth same as DQ series relays, are also available. For details, please contact Fuji.
*3:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of 0.2±0.1s is used on other occasions
*4:Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*5:Its noise immunity complies with the standard of B-402.
*6:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*7:If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold function.
If "A" is selected, the LED indicator has no display hold function.
*8:The value in parentheses indicates the pitch.

■Internal connection diagrams


DUTUCTA□ー1, DUTACTA□ー1 DUTRCTA□ー1, DUTBCTA□ー1

X AL X X AL X

3 4 11 12 14 15 16 17 9 10 18 A3 A4 A5 A6 B14 B15 A7 A8 A9 A10 B18


+ − + −
3Io Trip Alarm External SO. 3Io Trip Alarm External SO.
output output

1ー 9
■Operate time characteristics

[s] Operate time accuracy


5
Input cuurent 300% of operating current setting
Operating Operate time setting Operate time *1 Accuracyε[s]
current setting [s] [s] (operate time range)
4 All current 3.0 3.2 ±0.35(2.85 to 3.55)
setting 2.1 2.3 ±0.35(1.95 to 2.65)
1.2 1.4 ±0.35(1.05 to 1.75)

Operate time setting


3.0s 0.3 0.5 ±0.35(0.15 to 0.85)
3
Operate time

0 0.2 ±0.05(0.15 to 0.25)


Note*1:The operate time of this equipment is fixed timer(0.2s)
2.1s +operating time setting(0 to 3s)
2

1.2s

0.3s
0s
0
100 200 300 400 500 600 700 800 900 1000 [%]

Input current (100%=Operating current setting)

1ー 10
Digital Type DC Current Relay
DUT □ AD, DUT □ BD

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Detection of overcurrent and short-circuit in DC circuit Detection of undercurrent and disconnection in DC circuit
Principle and name Digital type DC overcurrent relay Digital type DC undercurrent relay
Classification Auxiliary energizing source ★Type *4
Unit standard DC DUTUADAS−1 DUTUADAK−1 DUTUADAA−1 DUTUBDAS−1 DUTUBDAK−1 DUTUBDAA−1
structure type AC DUTAADAS−1 DUTAADAK−1 DUTAADAA−1 DUTABDAS−1 DUTABDAK−1 DUTABDAA−1
DQ series DC DUTRADAS−1 DUTRADAK−1 DUTRADAA−1 UTRBDAS−1 DUTRBDAK−1 DUTRBDAA−1
replacement
type *1 AC DUTBADAS−1 DUTBADAK−1 DUTBADAA−1 DUTBBDAS−1 DUTBBDAK−1 DUTBBDAA−1
Ratings ★Current(input 1) DC 50mA, 100mA, 2A, 10A
Element Independent time−lag
Setting ★Setting value 50mA rated : 5 to 12mA (1), 100mA rated : 10 to 80mA (1)
range *7 DC 2A rated : 0.08 to 1A (0.01), 10A rated : 1 to 6A (0.1)

Time setting 0 to 30 (0.1) Note that, 0 denotes 0.1±50ms immediately


Output duration *2 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Rated burden 50mA rated : 50mW, 100mA rated : 0.2W, 2A rated : 0.3W, 10A rated : 2W
Continuous withstand current DC 50mA rated : 0.1A, 100mA rated : 0.2A, 2A rated : 4A, 10A rated : 10A
Auxiliary ★Voltage [V] DC 100, 110, 125, 200, 220, 250
energizing
source *3 AC 100, 110, 127, 200, 220, 250 50, 60Hz
Rated burden DC 100, 110, 125V rated : 6.5W 200, 220, 250V rated : 8.5W
AC 100, 110, 127V rated : 15VA 200, 220, 250V rated : 20VA
Operation Display hold function *5 With With – With With –
indicators Auxiliary energizing source DC LED: Operation x 1 LED: Operation x 1
AC LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1 LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1
Contacts Arrangement Trip: 1NO ("a" make contact),
Alarm: 1NC ("b" break contact), External output: 1NO
Limiting making capacity [A] 15 (R-load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10 (L-load, L/R=0.04, 110V DC)
Characteristics Operate time Refer to "Operate time characteristics"
Operate value accuracy [%] ±5 (assured setting accuracy range), *50mA rating specification: ±10, others (outside the assured setting accuracy range) ±20 *6
Holding factor [%] 10 (assured setting accuracy range), others (outside the assured setting accuracy range) 20 *6
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2
Previous relay type DQACA1, 2HH DQACA1, 2HB DQACA1, 2HA DQACB1, 2HH DQACB1, 2HB DQACB1, 2HA
Notes
*1:DQ series replacement relays having the same terminal arrangement with DQ series relays. The replacement relays provided with panel mounting adapter, to
make the depth same as DQ series relays, are also available. For details, please contact Fuji. 
*2:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of 0.2±0.1s is used on other occasions.
*3:Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*4:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*5:If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold function.If
"A" is selected, the LED indicator has no display hold function.
*6:The following table shows the assured accuracy ranges for the setting values.
*When operating the relay in minute electric current or outside the assured setting accuracy range, secure enough operate time for setting to avoid any
incorrect output of an electric relay caused by external influence, such as noise.
*7:The value in parentheses indicates the pitch.
Rated current Setting value Assured setting accuracy range
50mA 5 to 12mA 5 to 12mA
100mA 10 to 80mA 20 to 80mA
2A 0.08 to 1A 0.16 to 1A
10A 1 to 6A 2 to 6A

■Internal connection diagrams


 DUTUADA□ー1, DUTAADA□ー1  DUTRADA□ー1, DUTBADA□ー1
DUTUBDA□ー1, DUTABDA□ー1 DUTRBDA□ー1, DUTBBDA□ー1
Undercurrent relay closes Undercurrent relay closes
without input current without input current

AL AL

3 4 11 12 14 15 16 17 9 10 18 A3 A4 A5 A6 B14 B15 A9 A10 B9 B10 B18


+ + − + + −
I Trip Alarm External SO. I Trip Alarm External SO.
output output

1ー 11
Operate time characteristics

■DC overcurrent relay ■DC undercurrent relay

 Operate time characteristics  Operate time characteristics

[s] [s]
5 5

4 4

Operate time setting

Operate time setting


3.0s 3.0s
Operate time

3 3

Operate time
2.1s 2.1s
2 2

1.2s 1.2s
1 1

0.3s 0.3s

0 0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 [%] 100 80 60 40 20 0 [%]
Input current (100% =Operating current setting)
Input current (100% =Operating current setting)

Operate time accuracy (refer to*1) Operate time accuracy (refer to*1)
Name Overcurrent relay Name Undercurrent relay
Input current 0→300% of operating current setting Input current 200% of operating current setting →0
Operate current Operate time Operate time Accuracyε[%] Operate current Operate time Operate time Accuracyε[%]
setting setting [s] [s] (operate time range) setting setting [s] [s] (operate time range)
All current setting 3.0 3.1 ±5 (2.945 to 3.255s) All current setting 3.0 3.1 ±5 (2.945 to 3.255s)
2.1 2.2 ±4.3 (2.067 to 2.333s) 2.1 2.2 ±4.3 (2.067 to 2.333s)
1.2 1.3 ±3.5 (1.192 to1.409s) 1.2 1.3 ±3.5 (1.192 to1.409s)
0.3 0.4 ±2.8 (0.313 to 0.487s) 0.3 0.4 ±2.8 (0.313 to 0.487s)
0 0.1 ±50ms (50 to 150ms) 0 0.1 ±50ms (50 to 150ms)

 Operate time characteristic in 0s setting  Operate time characteristic in 0s setting


[ms] [ms]
350 300

300 250

250 200
Operate time
Operate time

200 150

150
100
100
50
50
0
0 100 80 60 40 20 0 [%]
0 200 400 600 800 1000 1200 1400 1600 1800 2000 [%] Input current (100% =Operating current setting)
Input current (100% =Operating current setting)

Notes *1:Operate time accuracyε[%] T10: Reference value for operate time setting (3s)
T0 : Nominal operate time (0.1s for both overcurrent and undercurrent relays) in operate time setting“0s”
Tn : Actual operate time at operate time setting "n"
n
Tnー ×T 10 +T 0 Where
10
ε= ×100 [%] Operate time setting
(T 10 +T 0 ) n =                            ×10
Reference operate time setting

1ー 12
Digital Type Field Ground Overcurrent Relay
DUT □ F

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Ground fault detection of DC circuit (mainly rotor field winding)
Principle and name DUT series field ground overcurrent relay
Unit standard structure type ★Type *3, 4 DUTUFDAS−1 DUTUFDAK−1 DUTUFDAA−1 DUTAFDAS−1 DUTAFDAK−1 DUTAFDAA−1
Ratings ★Voltage [V] DC Field voltage : 500V or less (Rated current on the side of DC overcurrent relay : 50mA DC)
Setting range ★Operation setting 5 to 8 (1)
*9 [mA] DC
★Time setting [s] 0 to 30 (0.1)
0 : Instantaneous (within 0.15s ± 50ms)
Output duration [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Input circuit load DC current input circuit : 1W
(Short-circuiting between the [1] terminal of the external auxiliary power source box and the [4] terminal of the
DC current relay)
Auxiliary ★Voltage [V] 100, 110, 125, 200, 220, 250 DC 100, 110, 127, 200, 220, 250 (50. 60Hz) AC
energizing Rated burden 100, 110, 125V DC rated : 6.5W 100, 110, 127V AC rated : 15VA
source *6 200, 220, 250V DC rated : 8.5W 200, 220, 250V AC rated : 20VA
★External auxiliary power source box • Auxiliary energizing source voltage rating (50/60Hz) 100V, 110V, 120V, 200V, and 220V AC
(Type : YZ14-2) *1, 2 • Output voltage : 50V DC
• Auxiliary energizing source input circuit load : 6VA at the application of rated voltage
Operation With/without indication holding function With With − With With −
indicator Auxiliary energizing source LED : Operation x 1 LED : Operation x 1, Magneticinversely indicator: Operation x 1 LED : Operation x 1
Contact Composition Trip : 1a, Alarm : 1b, External output : 1a
Limiting marking capacity [A] 15 (Resistive load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10 (Inductive load, L/R=0.04, 110V DC)
Characteristics Operate time Refer to "Operate time characteristics"
Accuracy of operating value [%] ±10
Holding factor [%] 10
Resetting time [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
External auxiliary power source box 100% of the rating of auxiliary energizing source : 50V DC±10%
Output voltage characteristics 80 to 115% of the rating of auxiliary energizing source : 50V DC±20%
Mass [kg] DC overcurrent relay : 2, External auxiliary power source box : 4
Outline drawing DC overcurrent relay : Fig. DUT1, External auxiliary power source box : Refer to fig. below
Previous relay type DQACD□NH DQACD□NB DQACD□NA DQACD□NH DQACD□NB DQACD□NA
Notes
*1:The field circuit is equipped with an external auxiliary power source box (type : ■External auxiliary power source box : YZ14-2
YZ14-2) for supplying DC voltage, which is connected externally to the DC
current input circuit of the relay. 185
*2:An external auxiliary power source box (type : YZ14-2) is supplied with this 120 4-ø7 100
relay. Specify the rating of the control power supply voltage (AC) from those
listed in the specification. Install the external auxiliary power source box within
the distribution board and keep the length of the connecting wiring with the DC
overcurrent relay as short as possible, taking the effect of disturbance noise
into consideration.
*3:Its noise immunity complies with the standard B-402.
*4:Refer to the identification on page 8 for the tenth digit or later of the code
symbol.
*5:The output duration of 1±0.1s is used in the case of the circuit breaker tripping,
and that of 0.2±0.1s is used on other occasions.
*6:Since power outage guarantee time of AC rating auxiliary energizing source is
271
310
286

2 seconds, if the sum of operate time from the relay to the CB and resetting
time of the relay exceeds 2 seconds, it is required to provide a auxiliary
energizing source whose voltage does not drop even in case of an accident.
Note, however, that there may be such cases where the time exceeds 2
seconds depending on input condition or operation status of the relay.
*7:When the 8th digit of the type designation is "S" or "K", both LED and magnetic
inverse indicator have indication holding function. However, when the 8th digit
of the type designation is "A", LED dose not have indication holding function. Name plate
*8:Since the outside dimension of the relay case does not fit the conventional
model (type : DQACD*N*), and thus external connection of the external
25

auxiliary power source box is required, modification of the distribution board is


required when a conventional item is to be updated. 2
Fastening screw for terminal cover:2-M3×6
*9:The value in parentheses indicates the pitch. 187
4-M4×8 screw

12 3 4
84
41.5

16

13 13
13

1ー 13
■Operate time characteristics

 Operate time characteristics  Operate time characteristics in 0s setting

[s] [ms]
5 350

300

250

Operate time
200
4
150
Operate time
100
setting
50
3.0s
3
Operate time

0
100 120 140 160 180 200[%]
Input current (100% = Operating current setting)
2.1s
2

1.2s
1

0.3s

0
0 120 140 160 180 200 [%]

Input current (100% = Operating current setting)

Operate time accuracy (refer to*1) *1 Operate time accuracyε[%]

Input current 150% of operating current setting→0 n


T 10 +T 0
10
Operating current Operate time Operate time Accuracyε[%] ε= ×100[%]
setting setting [s] [s] (operate time range) (T 10 +T 0 )

Minimum 3.0 3.15 ±5 (2.993 to 3.308s) Where, T10:Reference operate time setting (3s)
2.1 2.25 ±4.3 (2.115 to 2.385s) T0 :Nominal operate time (0.15s) at operate time setting of 0s
Tn :Actual operate time measurement at operate time setting of n
1.2 1.35 ±3.5 (1.240 to 1.460s)
Operate time setting
0.3 0.45 ±2.8 (0.362 to 0.538s) Where, n= ×10
Reference operate time setting
0 0.15 ±50ms (100 to 200ms)

■Internal connection diagrams and example of application circuit

 Internal connection diagram  Example of application circuit

DC overcurrent F1(Positive side)


relay Rgp
Ve : Field circuit
Field circuit G
voltage
AL F2(Negative side)
Rgn

+
External auxiliary power
3 4 11 12 14 15 16 17 9 10 18
source box (YZ14-2) ①
+ –
2
Trip Alarm External SO. Series resistance
External, auxiliary SR SR=5kΩ
power source output
box YZ14-2 1 – D1-D4
C1 VT ③ Auxiliary energizing
Vr
source voltage (AC)
R1
+ for external auxiliary
Direct input power source box
Vr : DC50V ④



Control DC overcurrent relay
power * Input circuit resistance=15Ω
supply ⑩
④ 64E

DUT field overcurent ground relay

1ー 14
Digital Type Ground Overvoltage Relay
DUT□GH, DUT□GT
DUT□GN, DUT□GM (Noise immunity conforming to standard of B-402)

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Detection of ground overvoltage
Principle and name Digital type ground overvoltage relay
Classification Auxiliary ★Type *8
energizing source
Unit standard DC DUTUGHAS−2 DUTUGHAK−2 DUTUGHAA−2 DUTUGTAS−2 DUTUGTAK−2 DUTUGTAA−2
structure type AC DUTAGHAS−2 DUTAGHAK−2 DUTAGHAA−2 DUTAGTAS−2 DUTAGTAK−2 DUTAGTAA−2
DQ series DC DUTRGHAS−2 DUTRGHAK−2 DUTRGHAA−2 DUTRGTAS−2 DUTRGTAK−2 DUTRGTAA−2
replacement type *1 AC DUTBGHAS−2 DUTBGHAK−2 DUTBGHAA−2 DUTBGTAS−2 DUTBGTAK−2 DUTBGTAA−2
Unit standard DC DUTUGNAS−2 DUTUGNAK−2 DUTUGNAA−2 DUTUGMAS−2 DUTUGMAK−2 DUTUGMAA−2
structure type *7 AC DUTAGNAS−2 DUTAGNAK−2 DUTAGNAA−2 DUTAGMAS−2 DUTAGMAK−2 DUTAGMAA−2
Rat- ★Frequency [Hz] 50, 60
ings ★Voltage (one input) [V] AC 110, 190

Element Inverse time-lag Independent time-lag


Setting ★Setting value 5 to 50(1)
range *2 [V] AC 5 to 70(1)
Time setting n=0.5 to 50(n=0.1) 0 to 30s(0.1s)*3
Output duration *4 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Rated burden [VA] 0.8
Continuous withstand voltage 130% of rated value
Auxiliary ★Voltage DC 100, 110, 125, 200, 220, 250
energizing [V]
AC 100, 110, 127, 200, 220, 250 50, 60Hz
source *5
Rated DC 100, 110, 125V rated : 6.5W 200, 220, 250V rated : 8.5W
burden AC 100, 110, 127V rated : 15VA 200, 220, 250V rated : 20VA
Operation Display hold With With – With With –
indicators function *10
Auxiliary DC LED: Operation x 1
energizing
source AC LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1 LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1
Con- Arrangement Trip: 1NO ("a" make contact), Alarm: 1NC ("b" break contact), External output: 1NO
tacts Limiting making capacity [A] 15 (R-load, 0.5s, 110V DC)
Continuous current [A] 5
carrying capacity
Limiting breaking capacity [VA] DC 10 (L-load, L/R=0.04, 110V DC)
Chara- Operate time Refer to "Operate time characteristics"
cteris- Operate value accuracy [%] *6
tics
Holding factor [%] 5
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2
Previous relay type DQVJA1HH DQVJA1HB DQVJA1HA DQVRA1HH, DQVRA1HB, DQVRA1HA,
DQVWA2(F1)HH,G DQVWA2(F1)HB,D DQVWA2(F1)HA,N

Notes
*1:DQ series replacement relay having the same external terminal arrangement with DQ series relay. DQ series replacement relay with panel mounting
adapter that has the same depth with DQ series relay, is also available. For details, contact Fuji.
*2:The value in parentheses indicates the pitch.
*3:Zero represents instantaneous operate time (70ms max.).
*4:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of 0.2±0.1s is used on other occasions.
*5:Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*6:±5% in accuracy guaranteed setting range. ±15% for outside the accuracy guaranteed setting range. 10 to 50V (or 10 to 70V) for accuracy
guaranteed setting range. 5 to 10V below for outside the accuracy guaranteed setting range.
*7:Noise immunity per B-402 (Digital Protective Relays and Protective Equipment).
*8:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*9:Relays of rated voltage of 220 V (operation setting: 120 to 300 V) can also be manufactured.
*10:If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold
function. If "A" is selected, the LED indicator has no display hold function.

2ー 1
Digital Type Overvoltage Relay
DUT□VH, DUT□VT
DUT□VN, DUT□VM (Noise immunity conforming to standard of B-402)

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Detection of overvoltage
Principle and name Digital type overvoltage relay
Classification Auxiliary ★Type *8
energizing source
Unit standard DC DUTUVHAS−2 DUTUVHAK−2 DUTUVHAA−2 DUTUVTAS−2 DUTUVTAK−2 DUTUVTAA−2
structure type AC DUTAVHAS−2 DUTAVHAK−2 DUTAVHAA−2 DUTAVTAS−2 DUTAVTAK−2 DUTAVTAA−2
DQ series DC DUTRVHAS−2 DUTRVHAK−2 DUTRVHAA−2 DUTRVTAS−2 DUTRVTAK−2 DUTRVTAA−2
replacement type *1 AC DUTBVHAS−2 DUTBVHAK−2 DUTBVHAA−2 DUTBVTAS−2 DUTBVTAK−2 DUTBVTAA−2
Unit standard DC DUTUVNAS−2 DUTUVNAK−2 DUTUVNAA−2 DUTUVMAS−2 DUTUVMAK−2 DUTUVMAA−2
structure type *7 AC DUTAVNAS−2 DUTAVNAK−2 DUTAVNAA−2 DUTAVMAS−2 DUTAVMAK−2 DUTAVMAA−2
Rat- ★Frequency [Hz] 50, 60
ings ★Voltage (one input) [V] AC 110 *9

Element Inverse time-lag Independent time-lag


Setting ★Setting value 60 to 150(1)
range *2 [V] AC
Time setting n=0.5 to 50(n=0.1) 0 to 5s(0.1s)*3
Output duration *4 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Rated burden [VA] 0.8
Continuous withstand voltage 300% of rated value
Auxiliary ★Voltage DC 100, 110, 125, 200, 220, 250
energizing [V]
AC 100, 110, 127, 200, 220, 250 50, 60Hz
source *5
Rated DC 100, 110, 125V rated : 6.5W 200, 220, 250V rated:8.5W
burden AC 100, 110, 127V rated : 15VA 200, 220, 250V rated:20VA
Operation Display hold With With – With With –
indicators function *10
Auxiliary DC LED: Operation x 1
energizing
source AC LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1 LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1
Con- Arrangement Trip: 1NO ("a" make contact), Alarm: 1NC, External output: 1NO
tacts Limiting making capacity [A] 15 (R-load, 0.5s, 110V DC)
Continuous current [A] 5
carrying capacity
Limiting breaking capacity [VA] DC 10 (L-load, L/R=0.04, 110V DC)
Chara- Operate time Refer to "Operate time characteristics"
cteris- Operate value accuracy [%] ±5
tics
Holding factor [%] 5
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2
Previous relay type DQVJC1HH DQVJC1HB DQVJC1HA DQVRA1HH, DQVRA1HB, DQVRA1HA,
DQVWA2(F1)HH,G DQVWA2(F1)HB,D DQVWA2(F1)HA,N

Notes
*1:DQ series replacement relay having the same external terminal arrangement with DQ series relay. DQ series replacement relay with panel mounting
adapter that has the same depth with DQ series relay, is also available. For details, contact Fuji.
*2:The value in parentheses indicates the pitch.
*3:Zero represents instantaneous operate time (70ms max.).
*4:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of 0.2±0.1s is used on other occasions.
*5:Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*6:±5% in accuracy guaranteed setting range. ±15% for outside the accuracy guaranteed setting range. 10 to 50V (or 10 to 70V) for accuracy
guaranteed setting range. 5 to 10V below for outside the accuracy guaranteed setting range.
*7:Noise immunity per B-402 (Digital Protective Relays and Protective Equipment).
*8:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*9:Relays of rated voltage of 220 V (operation setting: 120 to 300 V) can also be manufactured.
*10:If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold
function. If "A" is selected, the LED indicator has no display hold function.

2ー 2
Digital Type Undervoltage Relay
DUT□UH, DUT□UT
DUT□UN, DUT□UM (Noise immunity conforming to standard of B-402)

★Information required with your inquiry or order. The pitch in parentheses need not be specified
Application Detection of undervoltage
Principle and name Digital type undervoltage relay
Classification Auxiliary ★Type *17
energizing source
Unit standard DC DUTUUHAS−2 DUTUUHAK−2 DUTUUHAA−2 DUTUUTAS−2 DUTUUTAK−2 DUTUUTAA−2
structure type AC DUTAUHAS−2 DUTAUHAK−2 DUTAUHAA−2 DUTAUTAS−2 DUTAUTAK−2 DUTAUTAA−2
DQ series DC DUTRUHAS−2 DUTRUHAK−2 DUTRUHAA−2 DUTRUTAS−2 DUTRUTAK−2 DUTRUTAA−2
replacement type *11 AC DUTBUHAS−2 DUTBUHAK−2 DUTBUHAA−2 DUTBUTAS−2 DUTBUTAK−2 DUTBUTAA−2
Unit standard DC DUTUUNAS−2 DUTUUNAK−2 DUTUUNAA−2 DUTUUMAS−2 DUTUUMAK−2 DUTUUMAA−2
structure type *16 AC DUTAUNAS−2 DUTAUNAK−2 DUTAUNAA−2 DUTAUMAS−2 DUTAUMAK−2 DUTAUMAA−2
Rat- ★Frequency [Hz] 50, 60
ings ★Voltage (one input) [V] AC 63.5, 110 *18
Element Inverse time-lag Independent time-lag
Setting ★Setting value 63.5V rated:10 to 60(1)
range *12 [V] AC 110V rated:15 to 100(1)
Time setting n=0.5 to 50(n=0.1) 0 to 30s(0.1s)*13
Output duration *14 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Rated burden [VA] 0.8
Continuous withstand voltage 130% of rated value
Auxiliary ★Voltage DC 100, 110, 125, 200, 220, 250
energizing [V]
AC 100, 110, 127, 200, 220, 250 50, 60Hz
source *15
Rated DC 100, 110, 125V rated:6.5W 200, 220, 250V rated:8.5W
burden AC 100, 110, 127V rated:15VA 200, 220, 250V rated:20VA
Operation Display hold With With – With With –
indicators function *19
Auxiliary DC LED: Operation x 1
energizing
source AC LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1 LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1
Con- Arrangement Trip: 1NO ("a" make contact), Alarm: 1NC ("b" break contact), External output: 1NO
tacts Limiting making capacity [A] 15 (R-load, 0.5s, 110V DC)

Continuous current [A] 5


carrying capacity
Limiting breaking capacity [VA] DC 10 (L-load, L/R=0.04, 110V DC)
Chara- Operate time Refer to "Operate time characteristics"
cteris- Operate value accuracy [%] ±5
tics
Holding factor [%] 5
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2

Previous relay type DQVJD1HH DQVJD1HB DQVJD1HA DQVRB1HH, DQVRB1HB, DQVRB1HA,


DQVWB2HH,G DQVWB2HB,D DQVWB2HA,N

Notes
*11:DQ series replacement relay having the same external terminal arrangement with DQ series relay. DQ series replacement relay with panel mounting
adapter that has the same depth with DQ series relay, is also available. For details, contact Fuji.
*12:The value in parentheses indicates the pitch.
*13:Zero represents instantaneous operate time (70ms max.).
*14:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of 0.2±0.1s is used on other occasions.
*15:Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*16:Noise immunity per B-402 (Digital Protective Relays and Protective Equipment).
*17:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*18:Relays of rated voltage of 220 V (operation setting: 50 to 200 V) can also be manufactured.
*19:If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold

2ー 3
Digital Type Voltage Relay (A Wide Frequency Band )
DUT□VG, DUT□UG

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Detection of overvoltage Detection of undervoltage
Principle and name Digital type overvoltage relay (A wide frequency band) Digital type undervoltage relay (A wide frequency band)
Classification Auxiliary energizing source ★Type *22, *23 ★Type *22, *23
Unit standard DC DUTUVGASー2 DUTUVGAKー2 DUTUVGAAー2 DUTUUGASー2 DUTUUGAKー2 DUTUUGAAー2
structure type AC DUTAVGASー2 DUTAVGAKー2 DUTAVGAAー2 DUTAUGASー2 DUTAUGAKー2 DUTAUGAAー2
Ratings ★Frequency [Hz] 50, 60
★Voltage (one input) [V] AC 110 *26 63.5, 110 *27
Element Independent time-lag
Setting ★Setting value [V] AC 60 to 150(1) 63.5V rated:10 to 60(1) 110V rated:15 to 100(1)
range *21
Time setting 0 to 5s(0.1s)*29 0 to 30s(0.1s)*29
Output duration *24 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Rated burden [VA] 0.8 0.8
Continuous withstand voltage 300% of rated value 130% of rated value
Auxiliary ★Voltage [V] DC 100, 110, 125, 200, 220, 250
energizing
AC 100, 110, 127, 200, 220, 250 50, 60Hz
source
*25 Rated burden DC 100, 110, 125V rated : 6.5W 200, 220, 250V rated : 8.5W
AC 100, 110, 127V rated : 15VA 200, 220, 250V rated : 20VA
Operation Display hold function *28 With With – With With –
indicators Auxiliary energizing source DC LED: Operation x 1 LED: Operation x 1
AC LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1 LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1
Contacts Arrangement Trip: 1NO ("a" make contact), Alarm: 1NC ("b" break contact), External output: 1NO
Limiting making capacity [A] 15 (R-load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10 (L-load, L/R=0.04, 110V DC)
Characteristics Operate time Refer to "Operate time characteristics" Refer to "Operate time characteristics"
Operate value accuracy [%] ±5 ±5
Holding factor [%] 5 5
Characteristics influenced 1) ±5% variability characteristics of the rated input 1) ±5% variability characteristics of the rated input
by frequency frequency. (1)Operate value: within ±5% of the rated frequency. (1)Operate value: within ±5% of the rated
value. (2)Operate time: within ±5% of the rated value value. (2)Operate time: within ±5% of the rated value
at operate time setting 3s and input voltage 120%. at operate time setting 3s and input voltage 70%.
2) ー20 to +50% variability characteristics of the rated 2) ー20 to +50% variability characteristics of the rated
input frequency. (1) Operate value: within ±20% of the input frequency. (1)Operate value: within ±20% of the
rated value. (2)Operate time: within ±10% of the rated rated value. (2)Operate time: within ±10% of the rated
value at operate time setting 3s and input voltage value at operate time setting 3s and input voltage
120%. 70%.
Mass [kg] 2
Outline drawing Fig. DUT1
Previous relay type DQVRA1HH DQVRA1HB DQVRA1HA DQVRB1HH DQVRB1HB DQVRB1HA
Notes
*21 : The value in parentheses indicates the pitch.
*22 : This product, the frequency characteristic of which is enhanced from the specifications of the JEC standard, can handle broadband. Its noise immunity
complies with the standard of B-402.
*23 : Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*24 : The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of 0.2±0.1s is used on other occasions.
*25 : Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*26 : Relays of rated voltage of 220 V (operation setting : 120 to 300 V) can also be manufactured.
*27 : Relays of rated voltage of 220 V (operation setting : 50 to 200 V) can also be manufactured.
*28 : If "S" or "K" is selected for the 8th digit of the code symbol. both LED and magnetic inversion operation indicators are provided with a display hold function.
If "A" is selected. the LED indicator has no display hold function.
*29 : Zero represents instantaneous operate time (70ms max.).

2ー 4
Operate time characteristics

■Inverse time-lag element

 Ground overvoltage relay DUT□GHA□ー 2, DUT□GNA□ー2  Overvoltage relay DUT □ VHA □ー 2, DUT □ VNA □ー 2
Inverse time-lag element operating time properties (reference) Inverse time-lag element operating time properties (reference)
V : Input multiple of operating voltage setting V : Input multiple of operating voltage setting
    10   n     8.8   n
t =     × n : Operational time setting t =     × n : Operational time setting
2
  V − 1  10 t : Operational time(s)
2
  V − 1  10 t : Operational time(s)
[s] 〔s〕
1000 1000

100

100

22.73(120% input)

8(150% input)
3.33(200% input)
10
20
n
Operate time

Operate time

50
12.75
40
10
30
7.04
20

1
10
9
8
7
6
5
4
n 1 3
50
0.1 40 2
30
20
0.5 1   2 3 4 5 6 7 8 9 10
1

0.5

0.01 0.1
100 200 300 500 700 1000 2000[%] 100 120 140 160 180   200[%]
Input voltage (100% = Setting voltage) Input voltage (100% = Setting voltage)

Operate time accuracy:Refer to *1 Operate time accuracy:Refer to *1


Input voltage 120% 150% 200% Input voltage 120% 130% 150%
Setting value Time Accuracy Time Accuracy Time Accuracy Setting value Time Accuracy Time Accuracy Time Accuracy
Operate Time "n"    [s] ε [%]    [s] ε [%]    [s] ε [%] Operate Time"n"    [s] ε [%]    [s] ε [%]    [s] ε [%]
10 22.73 ±20 8 ±15 3.33 ±10 All 10 20 ±20 12.75 ±18 7.04 ±15
Accuracy guaranteed

7 ー ー 5.6 ±12 2.331 ±9 voltage 7 14 ±16 ー ー 4.928 ±12


Within

4 ー ー 3.2 ±9 1.332 ±8 setting 4 8 ±11 ー ー 2.816 ±9


1 ー ー 0.8 ±6 0.333 ±6 1 2 ±6 ー ー 0.704 ±6
setting range

10 22.73 ±30 8 ±23 3.33 ±15


Outside

7 ー ー 5.6 ±18 2.331 ±14


4 ー ー 3.2 ±14 1.332 ±12
1 ー ー 0.8 ±9 0.333 ±9

Note *1:Operate time accuracy ε


〔%〕 T10: Nominal operate time at reference operate time setting "n" = 10
Tn : Actual operate time at operate time setting "n"
When "n" ≦ 10          When "n">10
n n
Tn −    xT10 Tn −    ×T10 Where
10 10
ε=        ×100 〔%〕 ε=        ×100
n
〔%〕 Operate time setting
T10   × T10 n =                            ×10
10 Reference operate time setting

2ー 5
■ Independent time-lag element

 Undervoltage relay DUT □ UHA □ー 2, DUT □ UNA □ー 2  Ground overvoltage relay DUT □ GTA □ー 2, DUT □ GMA □ー 2
Inverse time-lag element operating time properties (reference)
V : Input multiple of operating voltage setting
  − 6.35   n
t =     × n : Operational time setting
2
  V − 1  10 t : Operational time(s)
[s]
[s]
5
1000

Operate time setting


3 3.0s

Operate time
100

2.1s
2

n
50
1.2s
40 1
30
Operate time

12.45 20 0.3s
10 0
6.35 100 200 400 600 800  1000[%]
10
9 Input voltage (100% = Setting voltage)
8
7
6
5 Operate time accuracy:Refer to *1 on page 2-5.
4
Input voltage 150%
3 Setting value Accuracyε[%] (operate time range)
Operate Time setting [s]
2
All voltage 3 ±5 (2.850 to 3.150s)
1 setting 2.1 ±4.3(1.971 to 2.229s)
1 1.2 ±3.5(1.095 to 1.305s)
0.3 ±2.8(0.216 to 0.384s)
Remark:Operate time is 70ms maximum in the state where operate time
0.5 setting is 0s.

0.1
100 80 60 40 20   0[%]
Input voltage (100% = Setting voltage)

Operate time accuracy:Refer to *1 on page 2-5.


Input voltage 70% 0%
Setting value Time Accuracy Time Accuracy
Operate Time "n"    [s] ε [%]    [s] ε [%]
All voltage 10 12.45 ±20 6.35 ±10
setting 7 8.715 ±16 4.445 ±9
4 4.98 ±11 2.54 ±8
1 1.245 ±6 0.635 ±6

2ー 6
 Overvoltage relay DUT □ VTA □ー 2, DUT □ VMA □ー 2  Undervoltage relay DUT □ UTA □ー 2, DUT □ UMA □ー 2
DUT □ VGA □ー 2 DUT □ UGA □ー 2

[s] [s]
5 5

4 4

Operate time setting


Operate time setting

3 3s 3 3s
Operate time

Operate time

2.1s 2.1s
2 2

1.2s 1.2s
1 1

0.3s 0.3s
0 0
100 120 140 160 180   200[%] 100 80 60 40 20 0[%]
Input voltage (100% = Setting voltage) Input voltage (100% = Setting voltage)

Operate time accuracy:Refer to *1 on page 2-5. Operate time accuracy:Refer to *1 on page 2-5.
Input voltage 120% Input voltage 70%
Setting value Accuracyε[%] (operate time range) Setting value Accuracyε[%] (operate time range)
Operate Time setting [s] Operate Time setting [s]
All voltage 3 ±5 (2.850 to 3.150s) All voltage 3 ±5 (2.850 to 3.150s)
setting ±4.3(1.971 to 2.229s) setting
2.1 2.1 ±4.3(1.971 to 2.229s)
1.2 ±3.5(1.095 to 1.305s) 1.2 ±3.5(1.095 to 1.305s)
0.3 ±2.8(0.216 to 0.384s) 0.3 ±2.8(0.216 to 0.384s)
Remark:Operate time is 70ms maximum in the state where operate time Remark:Operate time is 70ms maximum in the state where operate time
setting is 0s. setting is 0s.

2ー 7
Internal connection diagrams

DUTUGHA□ー2, DUTAGHA□ー2  DUTUUHA□ー2, DUTAUHA□ー2


DUTUGNA□ー2, DUTAGNA□ー2   DUTUUNA□ー2, DUTAUNA□ー2
DUTUVHA□ー2, DUTAVHA□ー2
DUTUVNA□ー2, DUTAVNA□ー2
Closed when
input voltage
OFF

L AL L L AL L

1 2 11 12 14 15 16 17 9 10 18 1 2 11 12 14 15 16 17 9 10 18
+ − + −
V Trip Alarm External SO. V Trip Alarm External SO.
output output

DUTUGTA□ー2, DUTAGTA□ー2  DUTUUTA□ー2, DUTAUTA□ー2


DUTUGMA□ー2, DUTAGMA□ー2  DUTUUMA□ー2, DUTAUMA□ー2
DUTUVTA□ー2, DUTAVTA□ー2  DUTUUGA□ー2, DUTAUGA□ー2
DUTUVMA□ー2, DUTAVMA□ー2
DUTUVGA□ー2, DUTAVGA□ー2
Closed when
input voltage
OFF

L AL L L AL L

1 2 11 12 14 15 16 17 9 10 18 1 2 11 12 14 15 16 17 9 10 18
+ − + −
V Trip Alarm External SO. V Trip Alarm External SO.
output output

 DUTRGHA□ー2, DUTBGHA□ー2  DUTRUHA□ー2, DUTBUHA□ー2


 DUTRVHA□ー2, DUTBVHA□ー2
Closed when
input voltage
OFF

L AL L L AL L

A1 A2 A5 A6 B14 B15 A9 A10 B9 B10 B18 A1 A2 A5 A6 B14 B15 A9 A10 B9 B10 B18
+ − + −
V Trip Alarm External SO. V Trip Alarm External SO.
output output

 DUTRGTA□ー2, DUTBGTA□ー2  DUTRUTA□ー2, DUTBUTA□ー2


 DUTRVTA□ー2, DUTBVTA□ー2
Closed when
input voltage
OFF

L AL L L AL L

A1 A2 A5 A6 B14 B15 A9 A10 B9 B10 B18 A1 A2 A5 A6 B14 B15 A9 A10 B9 B10 B18
+ − + −
V Trip Alarm External SO. V Trip Alarm External SO.
output output

2ー 8
Digital Type DC Voltage Relay
DUT□VD, DUT□UD

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application ①Detection of overvoltage in DC circuits, ②Detection of overcurrent in DC circuits ③Detection of undrvoltage in DC circuits, ④Detection of undercurrent and disconnection in DC circuits
Principle and name Digital type DC overvoltage relay Digital type DC undervoltage relay
Classification Auxiliary ★Type *4 ★Type *4
energizing source
Unit standard structure type DC DUTUVDAS−1 DUTUVDAK−1 DUTUVDAA−1 DUTUUDAS−1 DUTUUDAK−1 DUTUUDAA−1
AC DUTAVDAS−1 DUTAVDAK−1 DUTAVDAA−1 DUTAUDAS−1 DUTAUDAK−1 DUTAUDAA−1
DQ series replacement type *1 DC DUTRVDAS−1 DUTRVDAK−1 DUTRVDAA−1 DUTRUDAS−1 DUTRUDAK−1 DUTRUDAA−1
AC DUTBVDAS−1 DUTBVDAK−1 DUTBVDAA−1 DUTBUDAS−1 DUTBUDAK−1 DUTBUDAA−1
Rat- ★Voltage Direct connection (In the case of application ①③) 110V, 220V, 500V
ings (input 1) DC Shunt connection (In the case of application ②④) 100%=300mV, 100%=150mV, 100%=100mV, 100%=60mV
Element Independent time-lag
★ Setting Direct connection (In the case of application ①③) 110V rated : 10 to 100V (1), 220V rated : 10 to 120V (1), 500V rated : 40 to 250V (1)
value DC Shunt connection (In the case of application ②④) 100%=300mV rated : 20 to 150% (1), 100%=150mV rated : 40 to 200% (1),
*8 100%=100mV rated : 60 to 300% (1), 100%=60mV rated : 100 to 500% (1)
Time setting *8 0 to 30s (0.1s) Note taht, 0 denotes 0.15s±50ms immediately 0 to 30s (0.1s) Note taht, 0 denotes 0.2s±50ms immediately
Output duration *2 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Rated Direct connection (In the case of application ①③) 110V rated : 8W, 220V rated : 30W, 500V rated : 35W
burden Shunt connection (In the case of application ②④) 100%=300mV rated : 4mW, 100%=150mV rated : 1mW,
100%=100mV rated : 0.5mW, 100%=60mV rated : 0.3mW
Continuous Direct connection (In the case of application ①③) 110V rated : 220V, 220V rated : 400V, 500V rated : 600V
withstand Shunt connection (In the case of application ②④) 100%=300mV rated : 1100% of rated, 100%=150mV rated : 2200% of rated,
input DC 100%=100mV rated : 3300% of rated, 100%=60mV rated : 6600% of rated
Auxiliary ★Voltage [V] DC 100, 110, 125, 200, 220, 250
energizing AC 100, 110, 127, 200, 220, 250 50, 60Hz
source *3
Rated burden DC 100, 110, 125V rated : 6.5W 200, 220, 250V rated : 8.5W
AC 100, 110, 127V rated : 15VA 200, 220, 250V rated : 20VA
External resistor Direct connection (In the case of application ①③) 110V rated : 2kΩ, 220V rated : 2kΩ, 500V rated : 10kΩ
(Type YZ3) *6
Internal Shunt connection (In the case of application ②④) 100%=300mV rated : 20Ω, 100%=150mV rated : 20Ω,
resistance value 100%=100mV rated : 20Ω, 100%=60mV rated : 20Ω
Operation Display hold function *5 With With – With With –
indicators Auxiliary energizing source DC LED: Operation x 1 LED: Operation x 1
AC LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1 LED: Operation x 1, Magnetic inversion: Operation x 1 LED: Operation x 1
Con- Arrangement Trip: 1NO ("a" make contact), Alarm: 1NC ("b" break contact), External output: 1NO
tacts Limiting making capacity [A] 15 (R-load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity DC [VA] 10 (L-load, L/R=0.04, 110V DC)
Chara- Operate time Refer to "Operate time characteristics"
cteris- Operate value accuracy [%] ±5 (assured setting accuracy range), others (outside the assured setting accuracy range) ±15 *7
tics
Holding factor [%] 10 (assured setting accuracy range), others (outside the assured setting accuracy range) 20 *7
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1 (YZ3 : refer page 2-9)
drawing DQ series replacement type
Fig. DUT2 (YZ3 : refer page 2-9)
Previous relay type DQVCA1, 2HH DQVCA1, 2HB DQVCA1, 2HA, DQVCB1, 2HH DQVCB1, 2HB DQVCB1, 2HA,
Notes
*1:DQ series replacement relays having the same terminal arrangement with DQ series relays. The replacement relays provided with panel mounting
adapter, to make the depth same as DQ series relays, are also available. For details, please contact Fuji.
*2:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of 0.2±0.1s used on other occasions.
*3:Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*4:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*5:If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic
inversion operation indicators are provided with a display hold function.If "A" ■External resistor Type YZ3
is selected, the LED indicator has no display hold function.
*6:One external resistor (type: YZ3) suiting each specification is attached to this relay. 30 2 −φ7 2.3
Be sure to connect the relay to this resistor when using it.
22

*7:The following table shows the assured accuracy ranges for the setting values.
*When operating the relay in minute electric voltage or outside the assured setting Name plate
accuracy range, secure enough operate time for setting to avoid
any incorrect output of an electric relay caused by external influence, such as noise.
*8:The value in parentheses indicates the pitch.
Rated current Setting value Assured setting accuracy range
304
280

252

266

110V 10 to 100V 20 to 100V


220V 10 to 120V 20 to 120V
500V 40 to 250V 100 to 250V
13

100%=300mV 20 to 150% 60 to 150%


100%=150mV 40 to 200% 120 to 200%
3.5

30

10

100%=100mV 60 to 300% 180 to 300% 9.5 17 9.5 Terminal 55.4 7


screws
100%=60mV 100 to 500% 300 to 350% 90 M3.5
105

2ー 9
Operate time characteristics Connection diagrams

■ DC overvoltage relay ■ DC undervoltage relay


Operate time characteristics Operate time characteristics
[s] [s]
4 4

3.0s 3.0s

Operate time setting

Operate time setting


3 3
Operate time

Operate time
2.1s 2.1s
2 2

1.2s 1.2s
1 1

0.3s 0.3s
0 0
100 120 140 160 180   200[%] 100 80 60 40 20    0[%]
Input voltage (100% =Operating voltage setting) Input voltage (100% =Operating voltage setting)

Operate time accuracy (refer to*1) Operate time accuracy (refer to*1)
Name Overvoltage relay Name Undervoltage relay
Input voltage 0→150% of operating voltage setting Input voltage 200% of operating voltage setting → 70%
Operate voltage Operate time Operate time Accuracyε[%] Operate voltage Operate time Operate time Accuracyε[%]
setting setting [s] [s] (operate time range) setting setting [s] [s] (operate time range)
All voltage setting 3.0 3.15 ±5 (2.993 to 3.308s) All voltage setting 3.0 3.2 ±5 (3.040 to 3.360s)
2.1 2.25 ±4.3 (2.115 to 2.385s) 2.1 2.3 ±4.3 (2.162 to 2.438s)
1.2 1.35 ±3.5 (1.240 to1.460s) 1.2 1.4 ±3.5 (1.288 to1.512s)
0.3 0.45 ±2.8 (0.362 to 0.538s) 0.3 0.5 ±2.8 (0.410 to 0.590s)
0 0.15 ±50ms (100 to 200ms) 0 0.2 ±50ms (150 to 250ms)

Operate time characteristic in 0s setting Operate time characteristic in 0s setting


[ms] [ms]
350 350

300 300
250 250
Operate time

Operate time

200 200
150
150
100
100
50
50
0
100 120 140 160 180 200 [%] 0
100 80 60 40 20 0 [%]
Input voltage (100% = Operating voltage setting)
Input voltage (100% = Operating voltage setting)

Notes *1:Operate time accuracyε[%] T10: Reference value for operate time setting (3s)
T0 : Nominal operate time (overvoltage : 0.15s, undervoltage : 0.2s) in operate time setting“0s”
n
Tn ー ×T 10 +T 0 Tn : Actual operate time at operate time setting "n"
10
ε= ×100 [%] Where
(T 10 +T 0 ) Operate time setting
n =                            ×10
Reference operate time setting

■ Internal connection diagrams

 DUTUVDA □ー 1, DUTAVDA □ー 1  DUTRVDA □ー 1, DUTBVDA □ー 1


DUTUUDA □ー 1, DUTAUDA □ー 1 DUTRUDA □ー 1, DUTBUDA □ー 1
Undervoltage relay closes Undervoltage relay closes
without input voltage. without input voltage.

AL AL

1 2 11 12 14 15 16 17 9 10 18 A1 A2 A5 A6 B14 B15 A9 A10 B9 B10 B18


YZ3 + − YZ3 + −
+ Trip Alam External SO. + Trip Alam External SO.
output output
P N P N
V V

2ー 10
Digital Type Ground Directional Relay
DUT□D

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Selective ground fault detection of non-grounded or resistance grounded distribution line
Principle and name Digital type ground directional relay
Unit standard structure type ★Type DUTUDTBS−3 DUTUDTBK−3 DUTUDTBA−3 DUTADTBS−3 DUTADTBK−3 DUTADTBA−3
DQ series replacement type *1 *7, *8 DUTRDTBS−3 DUTRDTBK−3 DUTRDTBA−3 DUTBDTBS−3 DUTBDTBK−3 DUTBDTBA−3
Rat- ★Frequency [Hz] 50, 60
ings ★Zero-sequence voltage [V] AC 3Vo=110, 190
★Zero-sequence current *6 [A] AC 3Io=2
Setting ★Operate voltage [V] 5 to 30(1)
range *2 ★Operate current [mA] 1 to 10(0.5), 10 to 100(1)*9
★Max. sensitivity [°] 45 to 75(1)
phase angleθ
★Operate time [s] 0 to 3(0.1),{Zero is instantaneous (0.2±0.05)}
Output duration *3 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Burden Voltage circuit:1VA, rated
Current circuit Operate current value at 1 of power-factor : 1 to 10mA is 2.7Ω burden, 10 to 100mA is 0.27Ω burden
Continuous withstand input [% of rating] Voltage circuit:115,Current circuit:100
Auxiliary ★Voltage [V] DC100, 110, 125, 200, 220, 250 AC100, 110, 127, 200, 220, 250 50, 60Hz
energizing
source *4 Rated burden DC100, 110, 125V rated:6.5W AC100, 110, 127V rated:15VA
DC200, 220, 250V rated:8.5W AC200, 220, 250V rated:20VA
Operation Display hold function *10 With With – With With –
indicating Operation indicators LED: Operation x 1 LED: Operation x 1,Magnetic inversion: Operation x 1 LED: Operation x 1
Con- Arrangement Trip: 1NO ("a" make contact), Alarm: 1NC ("b" break contact), External output: 1NO
tacts Limiting making capacity [A] 15(R-load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10(L-load, L/R=0.04, 110V DC)
Char- Influenced by phase angle *5 Operate phase angle is (θ+80˚)±5˚ leading max., (θ+280˚)±5˚ lagging max., under 1000% of operate current setting.
acter- (under 30% of rated voltage) Max. sensitivity phase angle (θ) is ±5˚ max. of setting value.
istics Influenced by voltage-current *5 Operate current accuracy is ±10% max. of setting value under max. sensitivity phase angle (The input phase of
(under 30% of rated voltage) voltage and current).
Accuracy Operate voltage [%] ±10
Operate current [%] ±10
Max. sensitivity phase angle θ [˚] ±5 (under 30% of rated voltage, 1000% of operate currrent setting)
Operate time [s] (operate time setting value +0.2)±0.35 (under operate time setting value = 0.3 to 3)
Resetting time [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Holding factor [%] 20
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2
Previous relay type DQWJA1HH DQWJA1HB DQWJA1HA DQWPA□HH DQWPA□HB DQWPA□HA
DQWPA□HH DQWPA□HB DQWPA□HA DQWPF□HH DQWPF□HB DQWPF□HA
DQWPF□HH DQWPF□HB DQWPF□ HA
DQWPA□HG DQWPA□HD DQWPA□HN
DQWPF□HG DQWPF□HD DQWPF□HN
Notes
*1:DQ series replacement relay having the same external terminal arrangement with DQ series *6:Zero-sequence current (3Io) flowing into secondary side of zero-sequence current transfomer (ZCT).
relay. DQ series replacement relay with panel mounting adapter that has the same depth Use ZCT complying with L-class (200/1.5mA, Z=10Ω, pf=0.5) defined by JEC-1201.
with DQ series relay, is also available. For details, contact Fuji. *7:Noise immunity per B-402 (Digital Protective Relays and Protective Equipment).
*2:The value in parentheses indicates the pitch. *8:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*3:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of *9:The current 10 to 100 mA applies when zero-sequence active component current of the resistance
0.2±0.1s is used on other occasions. grounded distribution line adopting a grounding transformer (GTR) is about 3IN = 5-40 A or larger.
*4:Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may *10:If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic
exceed 2s depending on input or operating conditions. inversion operation indicators are provided with a display hold function. If "A" is selected,
*5:Refer to characteristic diagrams. the LED indicator has no display hold function.

■Internal connection diagrams

 DUTUDTB□ー3, DUTADTB□ー3 DUTRDTB□ー3, DUTBDTB□ー3

X AL X X AL X

1 2 3 4 11 12 14 15 16 17 9 10 18 A1 A2 A3 A4 A5 A6 B14 B15 A7 A8 A9 A10 B18


+ − + −
3Vo 3Io Trip Alarm External SO. 3Vo 3Io Trip Alarm External SO.
output output

3ー 1
Characteristic diagrams

■Characteristics influenced by phase angle ■Characteristics influenced by voltage-current

[%]
90°
1200

Zero-sequence current (3lo)


120° 60° 1000

(100%=Setting current)
Leading
Operating range 800
current

150° 30° 600

400

200
[%]
180° 200 400 600 800 1000 1200
0° 0
Zero-sequence current (3lo) 0 20 40 60 80 100 [%]
(100%=Setting current)
Zero-sequence voltage (3Vo)
(100%=Zero-sequence rated voltage)

 Zero-sequence rated voltage 3Vo : 100%=110V


210° 330°  Max. sensitivity phase angle between zero-sequence input
voltage and currentθis constant.
 Operate voltage setting : 5V (equivalent to 4.5%)
 Operate current setting : 100%=1.5mA
240° 300°

270°

Zero-sequence voltage 3Vo=30% of rated voltage


Max. sensitivity phase angle θ=60°(leading current)

■Operete time characteristics

[s] Operate time accuracy


5
Zero-sequence voltage 3Vo 100% of rated voltage
Zero-sequence current 3Io 1000% of setting current
Setting value Operate time Accuracyε[s]
Operate
4 Operate Time setting [s] (Operate time range)
time
setting [s]
All voltage, 3.0 3.2 ±0.35(2.85 to 3.55)
3.0s current 2.1 2.3 ±0.35(1.95 to 2.65)
3 setting
Operate time

1.2 1.4 ±0.35(1.05 to 1.75)


0.3 0.5 ±0.35(0.15 to 0.85)
2.1s 0.2 ±0.05(0.15 to 0.25)
0
2

1.2s

0.3s
0s
0
100 200 300 400 500 600 700 800 900 1000 [%]

Zero-sequence current 3Io (100%=Setting current)

3ー 2
Digital Type Ground Directional Relay
for Resistance Grounded Neutral System
DUT□J

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Ground fault detection in resistance grounded neutral transmission line
Principle and name Digital type ground directional relay for resistance grounded neutral system
Unit standard structure type ★Type DUTUJTBS−1 DUTUJTBK−1 DUTUJTBA−1 DUTAJTBS−1 DUTAJTBK−1 DUTAJTBA−1
DQ series replacement type *1 *7, *8 DUTRJTBS−1 DUTRJTBK−1 DUTRJTBA−1 DUTBJTBS−1 DUTBJTBK−1 DUTBJTBA−1
Rat- ★Frequency [Hz] 50, 60
ings ★Zero-sequence voltage [V] AC 3Vo=110, 190
★Zero-sequence current *6 [A] AC 3Io or Io =1, 5
Setting ★Operate voltage [V] 5 to 20(0.5)
range *2 ★Operate current [A] 5A Raing: 0.1 to 0.8(0.01), 0.5 to 3.0(0.1) 1A Rating: 0.02 to 0.16(0.01), 0.1 to 0.6(0.01) *10
★Max. sensitivity [°] 0 to 30(1)
phase angleθ
★Operate time [s] 0 to 30(0.1),{Zero is instantaneous (50ms or less)}
Output duration *3 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Burden Voltage circuit: 1VA, rated Current circuit: 0.4VA, rated
Continuous withstand input [% of rating] Voltage circuit:115,Current circuit:100
Auxiliary ★Voltage [V] 100, 110, 125, 200, 220, 250 DC 100, 110, 127, 200, 220, 250 AC 50, 60Hz
energizing
source *4 Rated burden 100, 110, 125V DC rated:6.5W 100, 110, 127V AC rated:15VA
200, 220, 250V DC rated:8.5W 200, 220, 250V AC rated:20VA
Operation Display hold function *9 With With – With With –
indicating Operation indicators LED: Operation x 1 LED: Operation x 1,Magnetic inversion: Operation x 1 LED: Operation x 1
Con- Arrangement Trip: 1NO ("a" make contact), Alarm: 1NC ("b" break contact), External output: 1NO
tacts Limiting making capacity [A] 15(R-load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10(L-load, L/R=0.04, 110V DC)
Char- Influenced by phase angle *5 Operate phase angle is (θ+80˚)±5˚ leading max., (θ+280˚)±5˚ lagging max., under 1000% of operate current setting.
acter- (input voltage: 30V) Max. sensitivity phase angle (θ) is ±5˚ max. of setting value.
istics Influenced by voltage-current *5 Operate current accuracy is ±5% max. of setting value under max. sensitivity phase angle (θ). Others are within 15%
(input voltage: 30V) (The input phase of voltage and current).
Accuracy Operate voltage [%] ±5
Operate current [%] ±5 (Accuracy guaranteed setting range). Others are within ±15.
Max. sensitivity phase angle θ [˚] ±5 (input voltage: 30V, 1000% of operate currrent setting)
Operate time See the operate time characteristics
Resetting time [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Holding factor [%] Voltage circuit: 5, Cuurent circuit: 5 (Accuracy guaranteed setting range), others: 10
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2
Previous relay type DQWPB□HH DQWPB□HB DQWPB□HA – – –
DQWPB□HG DQWPB□HD DQWPB□HN
Notes
*1:DQ series replacement relay having the same external terminal arrangement with DQ series relay. DQ series replacement relay with panel mounting adapter that has the same
depth with DQ series relay, is also available. For details, contact Fuji.
*2:The value in parentheses indicates the pitch.
*3:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, and that of 0.2±0.1s is used on other occasions.
*4:Power interruption guarantee time of AC auxiliary energizing source is 2s. However, it may exceed 2s depending on input or operating conditions.
*5:Refer to characteristic diagrams.
*6:Io: The zero-sequence current in tertiary circuit of CT with tertiary winding.
3Io: The zero-sequence current in the residual circuit of 3XCT (star connection).
*7:Noise immunity per B-402 (Digital Protective Relays and Protective Equipment).
*8:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*9:If "S" or "K" is selected for the 8th digit of the code symbol, both LED and magnetic inversion operation indicators are provided with a display hold function. If "A" is selected, the
LED indicator has no display hold function.
*10:The following gives the accuracy guaranteed setting range.

Rated Operating current Assured setting


current setting range accuracy range
■Internal connection diagrams
5A 0.1 to 0.8A 0.2 to 0.8A DUTUJTB□ー1, DUTAJTB□ー1 DUTRJTB□ー1, DUTBJTB□ー1
5A 0.5 to 3.0A 1.0 to 3.0A
1A 0.02 to 0.16A 0.04 to 0.16A
1A 0.1 to 0.6A 0.2 to 0.6A
X AL X X AL X

1 2 3 4 11 12 14 15 16 17 9 10 18 A1 A2 A3 A4 A5 A6 B14 B15 A7 A8 A9 A10 B18


+ − + −
3Vo 3Io Trip Alarm External SO. 3Vo 3Io Trip Alarm External SO.
(Io) output (Io) output

3ー 3
Characteristic diagrams

■Characteristics influenced by phase angle ■Characteristics influenced by voltage-current

[%]
1200

Zero-sequence current (3lo or Io)


90°
120° 60° 1000

(100%=Setting current)
Leading
current 800
Operating range
30° 600
150°
400

200
〔%〕
200 400 600 800 1000
180° 0° 0
Zero-sequence current (3lo or Io) 0 20 40 60 80 100 [%]
(100%=Setting current) Zero-sequence voltage (3Vo)
(100%=Zero-sequence rated voltage)

The input phase angle of zero-sequence voltage


210° 330° and zero-sequence current is kept constant at the
maximum sensitivity phase angle of
Operating voltage setting: minimum
Operating current setting: minimum
240° 300°
270°

Zero-sequence voltage 3Vo=30V


Max. sensitivity phase angle setting θ=0°

■Operete time characteristics

[s] Operate time accuracy : Refer to *1


5
Zero-sequence voltage 3Vo 100% of rated voltage
Zero-sequence current 3Io or Io 300% of setting current
Setting value Accuracyε[%]
4 Operate Operate Time setting [s] (Operate time range)
time All voltage, 3.0 ±5(2.850 to 3.150s)
setting current 2.1 ±4.3(1.971 to 2.229s)
setting
3 3.0s 1.2 ±3.5(1.095 to 1.305s)
Operate time

0.3 ±2.8(0.216 to 0.384s)


0 Less 50ms

2.1s
2 Note *1:Operate time accuracy ε
〔%〕

When "n" ≦ 10          When "n">10


n n
Tn −    xT10 Tn −    ×T10
1.2s 10 10
1 ε=        ×100 〔%〕 ε=        ×100
n
〔%〕
T10   × T10
10
T10: Nominal operate time at reference operate time setting "n" = 10
0.3s
Tn : Actual operate time at operate time setting "n"
0
100 200 400 600 800 1000 [%] Where
Operate time setting
n =                            ×10
Zero-sequence current 3Io or Io (100%=Setting current) Reference operate time setting

3ー 4
Digital Type Phase Directional Relay
DUT□K

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Phase fault in transmission line
Principle and name Digital type phase directional relay
Unit standard structure type ★Type DUTUKTBS−1 DUTUKTBK−1 DUTUKTBA−1 DUTAKTBS−1 DUTAKTBK−1 DUTAKTBA−1
DQ series replacement type *1 *5, *7 DUTRKTBS−1 DUTRKTBK−1 DUTRKTBA−1 DUTBKTBS−1 DUTBKTBK−1 DUTBKTBA−1
Rat- ★Frequency [Hz] 50, 60
ings ★Voltage [V] AC 110, 115
★Current [A] AC 1, 5
★Operate voltage [V] 2.2 (fixed) *With voltage memory function *6, *8
Setting ★Operating current [A] 5A Rating: 0.1 to 1.0 (0.01), 1.0 to 8.0 (0.1), 2.0 to 12.0 (0.1)
range *2 1A Rating: 0.2 to 1.6 (0.1), 0.4 to 2.4 (0.1) *6, *10
★Max. sensitivity [°] 45 (fixed)
phase angleθ
★Operate time [s] 0 to 3(0.1),{Zero is instantaneous (50ms or less)}
Output duration *3 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Burden Voltage circuit:1VA, rated
Current circuit:0.4VA, rated
Continuous withstand input [% of rating] Voltage circuit:115,Current circuit:100
Auxiliary ★Voltage [V] 100, 110, 125, 200, 220, 250 DC 100, 110, 127, 200, 220, 250 AC 50, 60Hz
energizing
source *4 Rated burden 100, 110, 125V DC rating: 6.5W 100, 110, 127V AC rating: 15VA
200, 220, 250V DC rating: 8.5W 200, 220, 250V AC rating: 20VA
Operation Display hold function *10 With With – With With –
indicating Operation indicators LED: Operation x 1 LED: Operation x 1,Magnetic inversion: Operation x 1 LED: Operation x 1
Con- Arrangement Trip: 1NO ("a" make contact), Alarm: 1NC ("b" break contact), External output: 1NO
tacts Limiting making capacity [A] 15(R-load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10(L-load, L/R=0.04, 110V DC)
Char- Influenced by phase angle *5 Operate phase angle is (θ+80˚)±5˚ leading max., (θ+280˚)±5˚ lagging max., under 1000% of operate current setting.
acter- Max. sensitivity phase angle (θ) is ±5˚ max. of setting value. *9
istics Influenced by voltage-current *5 Operate current accuracy is ±5% max. of setting value under max. sensitivity phase angle (θ). Others are within 15%
(The input phase of voltage and current). *10
Accuracy Operate voltage [%] ±10
Operate current [%] ±5 (Accuracy guaranteed setting range). Others are within ±15% *10
Max. sensitivity phase angle θ [˚] ±5 (Input rated voltage and 1000% of operating current setting) *9
Operate time [s] See the operate time charactaristics.
Resetting time [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Holding factor [%] Voltage circuit: 10, Current circuit: 5 (Accuracy guaranteed setting range), others:10 *10
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2
Previous relay type DQWPC□HH DQWPC□HB DQWPC□HA DQWPC□HH DQWPC□HB DQWPC□HA
DQWPC□HG DQWPC□HD DQWPC□HN DQWPC□HG DQWPC□HD DQWPC□HN
Notes
*1:DQ series replacement relay having the same external terminal arrangement with "output duration specification: Slow reset type (8th digits of the type: S). "It is
DQ series relay. DQ series replacement relay with panel mounting adapter that recommended to select "Operating time setting: 0s" for operation.
has the same depth with DQ series relay, is also available. For details, contact *9:If overcurrent of 15A or more is caused by an operating current setting on input
Fuji. current conditions, you can apply "200% of an operating current setting" as an
*2:The value in parentheses indicates the pitch. input current condition for decision.
*3:The output duration of 1±0.1s is used in the case of the circuit breaker tripping, *10:The following gives the accuracy guaranteed setting range.
and that of 0.2±0.1s is used on other occasions.
*4:Power interruption guarantee time of AC auxiliary energizing source is 2s.
Rating Operating current setting range Accuracy guaranteed setting range
However, it may exceed 2s depending on input or operating conditions. 5A 0.1 to 1.0A 0.2 to 1.0A
*5:Noise immunity per B-402 (Digital Protective Relays and Protective Equipment).
5A 1.0 to 8.0A 2.0 to 8.0A
*6:To connect input terminals of voltage and curent, use a line voltage as input
voltage and adopt 90º connection with phase current for input current. 5A 2.0 to 12.0A 4.0 to 12.0A
*7:Refer to the identifications on page 8 for the tenth digit or later of the code symbol. 1A 0.2 to 1.6A 0.4 to 1.6A
*8:An operating voltage is fixed to 2.2V (corresponding to 2% of a rated voltage).
Internal processing of a voltage memory function is adopted for a voltage input 1A 0.4 to 2.4A 0.8 to 2.4A
section. If considering short curcuit of three phase of a nearest end, select

3ー 5
Characteristic diagrams

■Characteristics influenced by phase angle ■Characteristics influenced by voltage-current


90°
120° 60°
Leading
current
Operating range [%]
150° 30° 800

(100%= operating current setting)


600
〔%〕

Input current
200 400 600 800 1000
180° 0°
Operation region
100% = operating current setting
400
(minimum of accuracy guaranteed
setting range)

200
210° 330°

0 20 40 60 80 100 [%]
240° 300°
Input voltage (100%= rated voltage)
270°

Input voltage = rated voltage


Max. sensitivity phase angle setting θ=45°

■Operete time characteristics

[s] Operate time accuracy : Refer to *1


5
Input voltage Rated voltage to 50% of rated voltage
Input current 200% of operating current setting
Operate Operate time Errorε[%]
4 setting setting [s] (Operate time range)
Operate
time All setting 3.0 +5(2.850 to 3.150s)
setting
2.1 +4.3(1.971 to 2.229s)
3 3.0s 1.2 +3.5(1.095 to 1.305s)
Operate time

0.3 +2.8(0.216 to 0.384s)


0 Less 50ms

2.1s
2 Note *1:Operate time accuracy ε
〔%〕

When "n" ≦ 10
n
1.2s Tn −    xT10
10
1 ε=        ×100 〔%〕
T10

T10: Nominal operate time at reference operate time setting "n" = 10


0.3s
Tn : Actual operate time at operate time setting "n"
0
100 200 400 600 800 1000 [%] Where
Operate time setting
n =                            ×10
Input current (100%= operating current setting) Reference operate time setting

■Internal connection diagrams

 DUTUKTB□ー1, DUTAKTB□ー1 DUTRKTB□ー1, DUTBKTB□ー1

X AL X X AL X

1 2 3 4 11 12 14 15 16 17 9 10 18 A1 A2 A3 A4 A5 A6 B14 B15 A7 A8 A9 A10 B18


+ − + −

VVW IR Trip Alarm External SO. VVW IR Trip Alarm External SO.
output output
Adopt 90゚connection Adopt 90゚connection

3ー 6
Digital Type Reverse Power Relay
DUT□L

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Reverse power protection
Principle and name Digital type reverse power relay
Unit standard structure type ★Type DUTULTBS−1 DUTULTBK−1 DUTULTBA−1 DUTALTBS−1 DUTALTBK−1 DUTALTBA−1
DQ series replacement type *1 *5, *6 DUTRLTBS−1 DUTRLTBK−1 DUTRLTBA−1 DUTBLTBS−1 DUTBLTBK−1 DUTBLTBA−1
Rat- ★Frequency [Hz] 50, 60
ings ★Voltage [V] AC 110, 115
★Current [A] AC 1, 5
★Operate voltage [V] 110V Rating: 5.5 (fixed), 115V Rating: 5.8 (fixed) *8
Setting ★Operating current [A] 5A Rating: 15 to 100 (5), 100 to 500 (10)
range *2 1A Rating: 15 to 100 (5) *9
★Max. sensitivity [°] 0 (fixed)
phase angleθ
★Operate time [s] 0 to 30(0.1),{Zero is instantaneous (50ms or less)} *7
Output duration *3 [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Burden Voltage circuit:Rated burden 1VA
Current circuit:Rated burden 0.4VA
Continuous withstand input [% of rating] Voltage circuit:115,Current circuit:100
Auxiliary ★Voltage [V] 100, 110, 125, 200, 220, 250 DC 100, 110, 127, 200, 220, 250 AC 50, 60Hz
energizing
source *4 Rated burden 100, 110, 125V DC rating: 6.5W 100, 110, 127V AC rating: 15VA
200, 220, 250V DC rating: 8.5W 200, 220, 250V AC rating: 20VA
Operation Display hold function *10 With With – With With –
indicating Note3) Operation indicators LED: Operation x 1 LED: Operation x 1,Magnetic inversion: Operation x 1 LED: Operation x 1
Con- Arrangement Trip: 1NO ("a" make contact), Alarm: 1NC ("b" break contact), External output: 1NO
tacts Limiting making capacity [A] 15(R-load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10(L-load, L/R=0.04, 110V DC)
Char- Influenced by phase angle *5 Operate phase angle is (θ+80˚)±5˚ leading max., (θ+280˚)±5˚ lagging max., under 1000% of operate current setting.
acter- Max. sensitivity phase angle (θ) is ±5˚ max. of setting value.
istics Influenced by voltage-current *5 Operate current accuracy is ±5% max. of setting value under max. sensitivity phase angle (θ). Others are within 15%
(The input phase of voltage and current). *9
Accuracy Operate voltage [%] ±10
Operate current [%] ±5 (Accuracy guaranteed setting range). Others are within ±15% *9
Max. sensitivity phase angle θ [˚] ±5 (Input rated voltage and 1000% of operating current setting)
Operate time [s] See the operate time charactaristics.
Resetting time [s] 1±0.1 0.2±0.1 0.2±0.1 1±0.1 0.2±0.1 0.2±0.1
Holding factor [%] Voltage circuit: 10, Current circuit: 5 (Accuracy guaranteed setting range), others:10 *9
Mass [kg] 2
Outline Unit standard structure type Fig. DUT1
drawing DQ series replacement type Fig. DUT2
Previous relay type DQWPD□HH DQWPD□HB DQWPD□HA DQWPD□HH DQWPD□HB DQWPD□HA
DQWPD□HG DQWPD□HD DQWPD□HN DQWPD□HG DQWPD□HD DQWPD□HN
Notes
*1:DQ series replacement relay having the same external terminal arrangement with *8:Using the auto transformer (AT) with center top, adjust phase on the voltage
DQ series relay. DQ series replacement relay with panel mounting adapter that circuit side so that the maximum sensitivity phase angle θ as seen from the
has the same depth with DQ series relay, is also available. For details, contact primary side of AT lags 10゚behind voltage.
Fuji. *9:The following gives the accuracy guaranteed setting range.
*2:The value in parentheses indicates the pitch.
*3:The output duration of 1±0.1s is used in the case of the circuit breaker tripping,
Rating Operating current setting range Accuracy guaranteed setting range
and that of 0.2±0.1s is used on other occasions. 5A 15 to 100mA 45 to 100mA
*4:Power interruption guarantee time of AC auxiliary energizing source is 2s.
5A 100 to 500mA 300 to 500mA
However, it may exceed 2s depending on input or operating conditions.
*5:Noise immunity per B-402 (Digital Protective Relays and Protective Equipment). 1A 15 to 100mA 45 to 100mA
*6:Refer to the identifications on page 8 for the tenth digit or later of the code symbol.
*7:To prevent malfunction of the relay because of a disturbance in a system, set
enough operating time before oparation.

3ー 7
Characteristic diagrams

■Characteristics influenced by phase angle ■Characteristics influenced by voltage-current


90°
120° 60°
Leading
current
Operating range
150° 30°
[%]

(100%= operating current setting)


〔%〕
200 400 600 800 1000 500
180° 0° Operation region
Input current
(100% = operating current setting)

Input current
100
210° 330°

0 20 40 60 80 100[%]
Input voltage (100%= rated voltage)
240° 300°
270°
Input voltage = rated voltage
Max. sensitivity phase angle setting θ=0°

■Operete time characteristics

[s] Operate time accuracy:Refer to *1


5
Input voltage 100% of rated voltage (fixed)
Input current 300% of operating current setting
Operate Operate time Errorε[%]
4 setting setting [s] (Operate time range)
Operate
time All setting 3.0 +5(2.850 to 3.150s)
setting
2.1 +4.3(1.971 to 2.229s)
3 3.0s 1.2 +3.5(1.095 to 1.305s)
Operate time

0.3 +2.8(0.216 to 0.384s)


0 Less 50ms

2.1s Note *1:Operate time accuracy ε


〔%〕
2
When "n" ≦ 10          When "n">10
n n
Tn −    xT10 Tn −    ×T10
10 10
1.2s ε=        ×100 〔%〕 ε=        ×100
n
〔%〕
1 T10   ×T10
10
T10: Nominal operate time at reference operate time setting "n" = 10
0.3s
Tn : Actual operate time at operate time setting "n"
0
100 200 400 600 800 1000 [%] Where
Operate time setting
Input current (100%= operating current setting) n =                            ×10
Reference operate time setting

■Internal connection diagrams

 DUTULTB□ー1, DUTALTB□ー1 DUTRLTB□ー1, DUTBLTB□ー1

X AL X X AL X

1 2 3 4 11 12 14 15 16 17 9 10 18 A1 A2 A3 A4 A5 A6 B14 B15 A7 A8 A9 A10 B18


+ − + −
IR Trip Alarm External SO. IR Trip Alarm External SO.
output output
AT AT
U U
V V
W W

3ー 8
DUT Series Protective Relays Testing Tool
DUTT

★Information required with your inquiry or order


Application Test of DUT series protective relay
Principle and name Testing tool
★Type DUTT1
Rat- Voltage and current 250V AC 5A, 250V DC 0.25A
ings Continuous withstand input 100% of relay rated input
Input terminal 1) AC input terminal:1−2, 3−4, 5−6, 7−8
2) Auxiliary energizing source input terminal:9−10
3) Frame ground terminal:18
*The terminal numbers above are as same as those of input terminals of DUT series protective relays.
Output terminal 1) Trip output terminal:11−12−13
2) External output terminal:16−17
3) Continuous monitoring (alarm) output terminal:14−15
*The terminal numhers above are as same as those of output terminals of DUT series protective relays.
Mass [kg] 7.1
Note) Comprex-element relay cannot be applied.

Connection diagram Outline drawing


DUTT1 DUTT1

Relay input
section DUT protective relay case

1 1
INPUT
2 2
3 3
INPUT
AC input 4 4
terminal 5 5
INPUT
6 6
7 7

270
INPUT
8 8
9 9
Auxiliary energizing source P(R)
input terminal
10 10
N(T)

Frame ground (FG) terminal 18 18

Relay output
section 11 11

TRIP 12 12

13 13

14 14
ALARM
15 15

16 16
OUTPUT
17 17 11
1
TRIP
INPUT 12

2 13

14
3
ALARM
INPUT 15

4 16
300

DUT protective relay case OUTPUT


17
5
INPUT

6 9 P(R)
CONTROL
SOURCE

7 10 N(T)
INPUT

8 18 FG
Name plate

305
8

4ー 1
Digital Type Complex-element Relay
DUTS □

★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Overload and phase fault detection (Mainly for facilities of special high-voltage and
high-voltage users)
Principle and name Digital overcurrent relay
Type *1, 2 DUTSASSS−1 DUTSASSK−1
Abbreviation of protective function element Overcurrent element : 3OCR (With instantaneous element)
Ratings ★Frequency [Hz] 50, 60
★Current [A] AC 1, 5
Pitch in ( ). 3OCR Inverse ★Operating current setting [A] AC 5A rating : 1 to 6 (0.1)−L 2 to 12 (0.1)−L
L denotes time lag 1A rating : 0.2 to 1.2 (0.1)−L 0.4 to 2.4 (0.1)−L
setting lock element *See page 9 for combination with instantaneous element
provided. Time setting n=0.5 to 50 (n=0.1)
Instant- ★Operating current setting [A] AC 5A rating : 5 to 40 (0.1)−L 10 to 80 (1)−L
aneous 1A rating : 1 to 8 (0.1)−L 2 to 16 (0.1)−L
element *See page 9 for combination with inverse time element
Time setting 0 to 3 (0.1)
0 denotes instantaneous (40ms or less)
  ★Output duration *3 [s] 1±0.1 0.2±0.1
Reted burden [VA] 0.4/circuit
Continuous allowable input [% of rating] 100
Auxiliary energizing ★Voltage [V] 100, 110, 125
source Rated burden 100, 110, 125V rating : 8.5W
Operation indicator (LED) *4 3OCR : Time limit x 1, Instantaneous x 1
Con- Composition Trip : 3OCR inverse time lag element : 2a, 3OCR instantaneous element : 2a
tact Alarm : 1b
Limiting making capacity [A] 15 (R−load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10 (L−load, L/R=0.04, 110V DC)
Charac- Operate time See the operate time characteristics
teristics Operating current accuracy Inverse time lag element : ±5 (accuracy guaranteed setting range) or, beyond that
range, within±10%
Holding factor [%] 5 (All element commonness)
Mass [kg] 3.6
Outline drawing Fig. DUT3
Previous relay type See the previous and new type list
Notes
*1:Its noise immunity complies with the standard B-402
*2:Refer to the identification on page 9 for the tenth digit or later of the code symbol.
*3:The output duration is the duration from tripping, or closing of the external output contact, to opening of the contact (reset time), in the case when input
conditions have turned from operation conditions to reset conditions.
If either "Slow reset type = 1s±0.1s" or "Instantaneous reset type = 0.2±0.1s" is specified, the specified output duration is selected for all the combined
protective elements.
*4:The phase display in Table 3-1 3OCR is as follows depending on R, S, and T phases, with trip output remained the OR output of each phase.
Set value display (7 segments) by phase : "1 : R phase," "2 : S phase," and "3 : T phase"

5ー 1
★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Overload, phase fault and earth fault detection (Mainly for facilities of special high-
voltage and high-voltage users)
Principle and name Digital overcurrent relay
Type *5, 6 DUTSESSS−1 DUTSESSK−1
Abbreviation of protective function element Overcurrent element : 3OCR (With instantaneous element) + Earth-fault overcurrent
element : EFR
Ratings ★Frequency [Hz] 50, 60
★Current [A] 1, 5
Pitch in ( ). 3OCR Inverse ★Operating current setting [A] AC 5A rating : 1 to 6 (0.1)−L 2 to 12 (0.1)−L
L denotes time lag 1A rating : 0.2 to 1.2 (0.1)−L 0.4 to 2.4 (0.1)−L
setting lock element *See page 9 for combination with instantaneous element
provided. Time setting n=0.5 to 50 (n=0.1)
Instant- ★Operating current setting [A] AC 5A rating : 5 to 40 (0.1)−L 10 to 80 (1)−L
aneous 1A rating : 1 to 8 (0.1)−L 2 to 16 (0.1)−L
element *See page 9 for combination with instantaneous element
Time setting 0 to 3 (0.1)
0 denotes instantaneous (40ms or less)
EFR ★Operating current setting [A] AC 5A rating : 0.1 to 0.8 (0.01)−L 0.5 to 4 (0.1)−L
1A rating : 0.02 to 0.16 (0.1)−L 0.1 to 0.8 (0.1)−L
*See page 9 for combination with instantaneous element
Time setting [s] n=0.5 to 50 (n=0.1)
*EFR : Inverse time characteristics
★Output duration *7 [s] 1±0.1 0.2±0.1
Reted burden [VA] 0.4/circuit
Continuous allowable input [% of rating] 100
Auxiliary energizing ★Voltage [V] 100, 110, 125
source Rated burden 100, 110, 125V rating : 8.5W
Operation indicator (LED) *8 3OCR Time limit x 1, Instantaneous x 1, EFR x 1
Con- Composition Trip : 3OCR inverse time lag element : 2a, 3OCR instantaneous element : 2a, EFR : 2a
tact Alarm : 1b
Limiting making capacity [A] 15 (resistive load, 0.5s, 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10 (inductive load, L/R=0.04, 110V DC)
Charac- Operate time See the operate time characteristics
teristics Operating 3OCR Inverse time lag element : ±5 (accuracy guaranteed setting range) or, beyond that
current range, within±10%
accuracy Instantaneous elemet : ±5
EFR Inverse time lag element : ±5 (accuracy guaranteed setting range) or, beyond that
range, within±15%
Holding factor [%] 5 (All element commonness)
Mass [kg] 3.7
Outline drawing Fig. DUT3
Previous relay type See the previous and new type list.
Notes
*5:Its noise immunity complies with the standard B-402
*6:Refer to the identification on page 9 for the tenth digit or later of the code symbol.
*7:The output duration is the duration from tripping, or closing of the external output contact, to opening of the contact (reset time), in the case when input
conditions have turned from operation conditions to reset conditions.
If either "Slow reset type = 1s±0.1s" or "Instantaneous reset type = 0.2±0.1s" is specified, the specified output duration is selected for all the combined
protective elements.
*8:The phase display in Table 3-1 3OCR is as follows depending on R, S, and T phases, with trip output remained the OR output of each phase.
(See Table 3-1 for details)
Set value display (7 segments) by phase : "1 : R phase, " "2 : S phase, " and "3 : T phase"

5ー 2
★Information required with your inquiry or order. The pitch in parentheses need not be specified.
Application Short-circuit / earth-fault detection of non-grounded distribution line
Principle and name Digital feeder protective relay
Type *9, 10 DUTSDSSS−1 DUTSDSSK−1
Abbreviation of protective function element Overcurrent element : 2OCR (With instantaneous element) + Earth-fault directional element : EFR
Ratings ★Frequency [Hz] 50, 60
★2OCR current [A] AC 1, 5
DGR zero-phase current 3lo *13 [A] AC 2
★DGR zero-phase voltage 3Vo [V] AC 110, 190
Pitch in ( ). 2OCR Inverse ★Operating current setting [A] AC 5A rating : 1 to 6 (0.1)−L 2 to 12 (0.1)−L
L denotes time lag 1A rating : 0.2 to 1.2 (0.1)−L 0.4 to 2.4 (0.1)−L
setting lock element *See page 9 for combination with instantaneous element
provided. Time setting n=0.5 to 50 (n=0.1)
Instant- ★Operating current setting [A] AC 5A rating : 5 to 40 (0.1)−L 10 to 80 (1)−L
aneous 1A rating : 1 to 8 (0.1)−L 2 to 16 (0.1)−L
element *See page 9 for combination with instantaneous element
Time setting 0 to 3 (0.1) 0 denotes instantaneous (40ms or less)
DGR Voltage operation value [V] AC 5 to 30 (1) *See page 9 for combination of specifications
★Current operation value [mA] AC 1 to 10 (0.5)−L 10 to 100 (1)−L
*See page 9 for combination with instantaneous element
Maximum sensitivity phase angle θ[˚] 45 to 75 (1)
Time setting [s] 0 to 3 (0.1) 0 Instantaneous (0.2±0.05s)
Output duration *11 [s] 1±0.1 0.2±0.1
2OCR rated burden [VA] 0.4/circuit
DGR burden Voltage circuit : Rated burden : 1VA
Current circuit : Current operation value 1 to 10mA : Burden of 2.7Ω (pf=1)
Current operation value 10 to 100mA : Burden of 0.27Ω (pf=1)
Continuous allowable input [% of rating] Current circuit : 100, Voltage circuit (DGR) : 115
Auxiliary energizing ★Voltage [V] 100, 110, 125
source Rated burden 100, 110, 125V rating : 8.5W
Operation indicator (LED) 2OCR : Time limit x 1, Instantaneous x 1, DGR x 1 *12
Con- Composition Trip : 2OCR inverse time lag element : 2a, 2OCR instantaneous element : DGR : 2a
tact Alarm : 1b
Limiting making capacity [A] 15 (resistive load, 0.5s 110V DC)
Continuous current carrying capacity [A] 5
Limiting breaking capacity [VA] DC 10 (inductive load, L/R=0.04, 110V DC)
Charac- Operate time See the operate time characteristics
teristics Operating 2OCR Inverse time lag element : ±5 (accuracy guaranteed setting range) or, beyond that
current range, within±15%
accuracy Instantaneous elemet : ±5
DGR Phase characteristics See characteristics diagram. Operation phase angle is within (θ+80˚) ±5˚ on the
leading phase side and within (θ+280˚) ± 5˚ on the lagging phase side, and the
maximum sensitivity phase angle (θ) is within ± 5˚ of the set value, at 30% of the rated
voltage and 1000% of the current operation setting.
Current-voltage characteristics See characteristics diagram. The current operation value accuracy is within ±10% of
the set value at the voltage of 30% of the rated voltage and the input phase of current
voltage of the maximum sensitivity phase angle (θ)
Voltage operation value accuracy ±10%
Current operation value accuracy ±10%
Operate time accuracy (Operation time setting 0.2) ±0.35 (At operation time setting 0.3 to 3.)
Holding factor 2OCR : All element 5, DGR : 20
Mass [kg] 3.7
Outline drawing Fig. DUT3
Previous relay type See the previous and new type list
Notes
*9:Its noise immunity complies with the standard B-402
*10:Refer to the identification on page 9 for the tenth digit or later of the code symbol.
*11:The output duration is the duration from tripping, or closing of the external output contact, to opening of the contact (reset time), in the case when input
conditions have turned from operation conditions to reset conditions.
If either "Slow reset type = 1s±0.1s" or "Instantaneous reset type = 0.2±0.1s" is specified, the specified output duration is selected for all the combined
protective elements.
*12:The phase display in 2OCR is as follows depending on R, and T phases, with trip output remained the OR output of each phase. (See Table 3-2 for details.)
Set value display (7 segments) by phase : "1 : R phase, " and "3 : T phase"
*13:3lo represents the zero-phase current fed on the secondary side of the zero-phase rectifier (ZCT).
Use JEC-1201 class L ZCT (200/1.5 mA, Z-10Ω, pf=0.5).
5ー 3
Operate time characteristics

■OCR inverse time-lag element, EFR operate time characteristics

 Normal inverse time-lag (characteristic code : C1)  Short inverse time-lag (characteristic code : C2)
Inverse time-lag element operating time properties (reference) Inverse time-lag element operating time properties (reference)
I : Input multiple of operating current setting I : Input multiple of operating current setting
    0.14 n   0.034    n
t =     × n : Operational time setting t =     × n : Operational time setting
0.02 0.02
  I − 1  10 t : Operational time(s)   I − 1  10 t : Operational time(s)
[s] [s]
1000 100

100 10

n
50
40
1.53
Operate time
Operate time

30
n
50 1.04 20
10 1
40 0.72
6.3 30
10
4.3 9
20 8
7
3 6
10 5
9 4
8 3
7
6
5 2
1 4 0.1

3
1
2 0.5

0.5
0.1 0.01
100 200 300 500 700 1000 2000[%] 100 200 300 500 700 1000 2000[%]
Input current (100% = Setting current) Input current (100% = Setting current)
Operate time accuracy:Refer to *1 Operate time accuracy:Refer to *1 and *2
Input current 300% 500% 1000% Input current 300% 500% 1000%
Setting value Time Accuracy Time Accuracy Time Accuracy Setting value Time Accuracy Time Accuracy Time Accuracy
Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%] Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%]
50 31.5 ±12 ー ー 15 ±7 50 7.65 ±12 ー ー 3.6 ±7
10 6.3 ±12 4.3 ±7 3 ±7 10 1.53 ±12 1.04 ±7* 0.72 ±7*
Accuracy guaranteed

Accuracy guaranteed

7 4.41 ±10 ー ー 2.1 ±6 7 1.071 ±10 ー ー 0.504 ±6*


Within

Within

4 2.52 ±8 ー ー 1.2 ±5 4 0.612 ±8 ー ー 0.288 ±5*


1 0.63 ±6 ー ー 0.3 ±4 1 0.153 ±6* ー ー 0.072 ±4*
±18 ±10 ±18 ±10
setting range

setting range

50 31.5 ー ー 15 50 7.65 ー ー 3.6


10 6.3 ±18 4.3 ±10 3 ±10 10 1.53 ±18 1.04 ±10 0.72 ±10*
±15 ±9 ±15 ±9*
Outside

Outside

7 4.41 ー ー 2.1 7 1.071 ー ー 0.504


4 2.52 ±12 ー ー 1.2 ±7 4 0.612 ±12 ー ー 0.288 ±7*
1 0.63 ±9 ー ー 0.3 ±6 1 0.153 ±9 ー ー 0.072 ±6*

Notes *1:Operate time accuracyε〔%〕 T10: Nominal operate time at reference operate time *2:Accuracy of items marked "*" is ±100ms
setting "n" = 10 when the value "ε・T10 " given in the
When "n" ≦ 10          When "n">10
n n Tn : Actual operate time at operate time setting "n" above equation " ε" is smaller than
Tn −    ×T10 Tn −    ×T10 100ms.
10 10
ε=        ×100 〔%〕 ε=        ×100
n
〔%〕 Where
T10   ×T10
10 Operate time setting
n =                            ×10
Reference operate time setting

5ー 4
¡Long inverse time-lag (characteristic code : C3) ¡Very inverse time-lag (characteristic code : C4)
Inverse time-lag element operating time properties (reference) Inverse time-lag element operating time properties (reference)
I : Input multiple of operating current setting I : Input multiple of operating current setting
    1.12   n   13.5   n
t =     × n : Operational time setting t =   × n : Operational time setting
[s]   I − 1  10 t : Operational time(s) [s]   I − 1  10
0.02
t : Operational time(s)
10000 1000

1000 100

n
100 50 10
40 6.75
50
Operate time
Operate time

30
n
34 3.38
20 50
24 40
10 30
9 1.5
8 20
7
10 6 1
5 10
4 9
8
3 7
6
2 5
4
3
1
2

1 0.5 0.1
1
0.5

0.1 0.01
100 200 300 500 700 1000 2000[%] 100 200 300 500 700 1000 2000[%]
Input current (100% = Setting current) Input current (100% = Setting current)
Operate time accuracy:Refer to *1 on page 5-4. Operate time accuracy:Refer to *1 and *2 on page 5-4.
Input current 300% 500% 1000% Input current 300% 500% 1000%
Setting value Time Accuracy Time Accuracy Time Accuracy Setting value Time Accuracy Time Accuracy Time Accuracy
Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%] Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%]
50 250 ±12 ー ー 120 ±7 50 33.75 ±12 ー ー 7.5 ±7
10 50 ±12 34 ±7 24 ±7 10 6.75 ±12 3.38 ±7* 1.5 ±7
Accuracy guaranteed

Accuracy guaranteed

7 35 ±10 ー ー 16.8 ±6 7 4.725 ±10 ー ー 1.05 ±6*


Within

Within

4 20 ±8 ー ー 9.6 ±5 4 2.7 ±8 ー ー 0.6 ±5*


1 5 ±6 ー ー 2.4 ±4 1 0.675 ±6 ー ー 0.15 ±4*
±18 ±10 ±18 ±10
setting range

setting range

50 250 ー ー 120 50 33.75 ー ー 7.5


10 50 ±18 34 ±10 24 ±10 10 6.75 ±18 3.38 ±10 1.5 ±10
±15 ±9 ±15 ±9
Outside

Outside

7 35 ー ー 16.8 7 4.725 ー ー 1.05


4 20 ±12 ー ー 9.6 ±7 4 2.7 ±12 ー ー 0.6 ±7
1 5 ±9 ー ー 2.4 ±6 1 0.675 ±9 ー ー 0.15 ±6*

5ー 5
¡Strong very inverse time-lag (characteristic code : C5) ¡Extremely inverse time-lag (characteristic code : C6)
Inverse time-lag element operating time properties (reference) Inverse time-lag element operating time properties (reference)
I : Input multiple of operating current setting I : Input multiple of operating current setting
  120   n    80   n
t =   × n : Operational time setting t =   × n : Operational time setting
2
[s]   I − 1  10 t : Operational time(s) [s]   I − 1  10 t : Operational time(s)
10000 10000

1000
1000

100

100
60
Operate time
Operate time

n
30 10
50 10
40
30
13.3 3.3
20
10
10
9 n
8 1 50
7 0.8 40
6
5 30
4 20
3
2 10
9
1 8
7
1 0.1 6
5
4
3
0.5 1 2
0.5

0.1 0.01
100 200 300 500 700 1000 2000[%] 100 200 300 500 700 1000 2000[%]
Input current (100% = Setting current) Input current (100% = Setting current)
Operate time accuracy:Refer to *1 on page 5-4. Operate time accuracy:Refer to *1 and *2 on page 5-4.
Input current 300% 500% 1000% Input current 300% 500% 1000%
Setting value Time Accuracy Time Accuracy Time Accuracy Setting value Time Accuracy Time Accuracy Time Accuracy
Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%] Operate Time "n" [s] ε [%] [s] ε [%] [s] ε [%]
50 300 ±12 ー ー 66.5 ±7 50 50 ±12 ー ー 4 ±7
10 60 ±12 30 ±7 13.3 ±7 10 10 ±12 3.3 ±7 0.8 ±7*
Accuracy guaranteed

Accuracy guaranteed

7 42 ±10 ー ー 9.31 ±6 7 7 ±10 ー ー 0.56 ±6*


Within

Within

4 24 ±8 ー ー 5.32 ±5 4 4 ±8 ー ー 0.32 ±5*


1 6 ±6 ー ー 1.33 ±4 1 1 ±6 ー ー 0.08 ±4*
±18 ±10 ±18 ±10
setting range

setting range

50 300 ー ー 66.5 50 50 ー ー 4
10 60 ±18 30 ±10 13.3 ±10 10 10 ±18 3.3 ±10 0.8 ±10*
±15 ±9 ±15 ±9*
Outside

Outside

7 42 ー ー 9.31 7 7 ー ー 0.56
4 24 ±12 ー ー 5.32 ±7 4 4 ±12 ー ー 0.32 ±7*
1 6 ±9 ー ー 1.33 ±6 1 1 ±9 ー ー 0.08 ±6*

5ー 6
■OCR instantaneous element oprating time characteristics

[s]
5

Operate time setting


3 3s
Operate time

2.1s
2

1.2s
1

0.3s
0
100 200 300 400   500[%]
Input current (100% = Setting current)

Operate time accuracy:Refer to *1 and *2 on page 5-4.


Input current 200%
Setting value Accuracyε[%] (operate time range)
operate time setting [s]
All current 3 ±5 (2.850 to 3.150s)
setting
2.1 ±4.3 (1.971 to 2.229s)
1.2 ±3.5 (1.095 to 1.305s)
0.3 ±2.8 (0.216 to 0.384s)
Remark:Operate time in the state where operate time setting is 0s.
DUT□E type relay:80ms max.
DUT□A type relay:40ms max.

5ー 7
Characteristic diagrams

■Characteristics influenced by phase angle ■Characteristics influenced by voltage-current

[%]
90°
1200

Zero-sequence current (3lo)


120° 60° 1000

(100%=Setting current)
Leading
Operating range 800
current

150° 30° 600

400

200
[%]
180° 200 400 600 800 1000 1200
0° 0
Zero-sequence current (3lo) 0 20 40 60 80 100 [%]
(100%=Setting current)
Zero-sequence voltage (3Vo)
(100%=Zero-sequence rated voltage)

 Zero-sequence rated voltage 3Vo : 100%=110V


210° 330°  Max. sensitivity phase angle between zero-sequence input
voltage and currentθis constant.
 Operate voltage setting : 5V (equivalent to 4.5%)
 Operate current setting : 100%=1.5mA
240° 300°

270°

Zero-sequence voltage 3Vo=30% of rated voltage


Max. sensitivity phase angle θ=60°(leading current)

■Operete time characteristics

[s] Operate time accuracy


5
Zero-sequence voltage 3Vo 100% of rated voltage
Zero-sequence current 3Io 1000% of setting current
Setting value Operate time Accuracyε[s]
Operate
4 Operate Time setting [s] (Operate time range)
time
setting [s]
All voltage, 3.0 3.2 ±0.35(2.85 to 3.55)
3.0s current 2.1 2.3 ±0.35(1.95 to 2.65)
3 setting
Operate time

1.2 1.4 ±0.35(1.05 to 1.75)


0.3 0.5 ±0.35(0.15 to 0.85)
2.1s 0.2 ±0.05(0.15 to 0.25)
0
2

1.2s

0.3s
0s
0
100 200 300 400 500 600 700 800 900 1000 [%]

Zero-sequence current 3Io (100%=Setting current)

5ー 8
Internal connection diagrams

3OCR : DUTSASS□ー1

L H L H

1 2 3 4 5 6 9 10 11 12 13 15 16 17 19 20 FG
+ –
IR Is IT SO. Trip Alarm

L : 3OCR inverse time lag element


3OCR H : 3OCR instantaneous element

3OCR+EFR : DUTSESS□ー1

L H L L H L

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 FG
+ –
IR Is IT 3I O SO. Trip Alarm

L : 3OCR inverse time lag element


3OCR EFR H : 3OCR instantaneous element

 2OCR+DGR : DUTSDSS□ー1

L H DGR L H DGR

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 FG

+ –
IR IT 3I O 3V O SO. Trip Alarm

L : 2OCR inverse time lag element


2OCR DGR H : 2OCR instantaneous element

5ー 9
Static Type Undercurrent Relay, Current-limit Relay
DRAW type

★Information required with your inquiry or order.


Application Undercurrent or disconnection Current-limit starting of AC wound-rotor motor
detection in AC circuit (for control) (for control)
Principle and name Static type undercurrent relay Static type current-limit relay
Type DRAWN5SA DRAWN6SA
Ratings Frequency [Hz] 50/60 (common)
Current AC[A] 5
Setting range AC[A] 1 to 5 (continuously adjustable stabilizing method: Note 1)
Rated burden [VA] 1
Continuous withstand current AC[A] 8
Auxiliary energizing Voltage AC[V] 100/110, 200/220, 50/60Hz common Note 2),5)
source (Rated voltage is selectable with external terminal connection.)
Rated burden [VA] 5
Contacts Composition 1c Note3)
Limiting marking capacity [A] 15
Resistive load. 0.5s, 110V DC
Continuous current carrying capacity [A] 5
Limiting breaking capacity DC[VA] 30 (max. 250V DC or 1A)
Inductive load, L/R=0.04, 110V DC
Characteristics Operate time [ms] 60 or less 60 or less
(at the input from 120% to 0% of setting value) (at the input from 150% to 0% of setting value)
Accuracy of operating value [%] ± 5
Holding factor [%] 5 ± 5 25 ± 5
Resetting time [ms] 50 or less 50 or less
(at the input from 0% to 120% of setting value) (at the input from 0% to 150% of setting value)
Mass [kg] 1
Outline drawing Fig. DRAW1
Previous relay type UAS4-1 UAS4-1
DRAWN1, DRAWN3 DRAWN2, DRAWN4
Note 1) Since stabilizing operation is a continuous adjustable stabilizing method using a setting knob, be sure to check the operation value measurement while
stabilizing.
Note 2) Since the auxiliary energizing power is selected by external terminal connection, check the auxiliary energizing power rated voltage and external connection
to be used in advance.
Note 3) "Operation" and "Resetting" contact outputs of this electrical relay are as follows.
• "Operation" when the current input is the setting value or lower: External terminal ( 5 - 6 ) B contact closed
• "Resetting" when the current input is the setting value or higher: External terminal ( 5 - 6 ) B contact open

■Internal connection diagrams ■Figure of characteristic


• Auxiliary energizing power • Auxiliary energizing power Operate time characteristics:
rated voltage rated voltage DRAWN5SA, DRAWN6SA
In case of 100/110V, 50/60Hz In case of 200/220V, 50/60Hz
[ms]
Auxiliary energizing power input Auxiliary energizing power input
60
Operate time

7 8 9 10 11 12 7 8 9 10 11 12 40

20

Ry Ry
0
1 2 3 4 5 6 1 2 3 4 5 6 100 80 60 40 20 0 [%]
Input current (100%=Operate current setting)

Current input Contact output Current input Contact output


(From CT second coil) (From CT second coil)

Note 4) The contact status of these diagrams shows the status of no AC input.
Note 5) For the auxiliary energizing power, provide an external connection
according to the rated voltage as shown in the left figure. (External
terminals: 9 - 10 )
Note 6) Since the external terminals 3 , 7 , and 8 are unused, do not connect
wiring to them.

6ー 1
Auxiliary Relay
TELR series

★Information required with your inquiry or order.


Coil specifications Single coil (DC)
Applications Generar control circuit High speed operation
(With SA) (With SA)
★Type Grouped plug-in type units *1 TELR–HHB5CA–DC110V TELR–HHB5VA–DC110V
Coil ratings ★Voltage DC [V] 100/110V DC 100/110V DC
Coil resistance [Ω] First (operation) coil : 5000 First (operation) coil resistance : 1300
Sum total of internal series resistance values : 1000
Guaranteed operate value 80% or less of ratings
Guaranteed resetting value 10% or more of ratings 5% or more of ratings
Continuous withstand value 130% is continuous of ratings
Contact *2 Arrangement 5c 4c (1c in 5c is used for an internal contact)
ratings Limiting making capacity L/R=0.04 0.5s 110V DC, 5A 110V DC, 5A
Continuous current carrying capacity [A] 5A 5A
Limiting braleing capacity L/R=0.04 110V DC, 0.3A 110V DC, 0.3A
Time Operate time (at rated input) [ms] 25 (+5, –8) 10 (+5, –3)
characteristics Resetting time (at rated input) [ms] 25 (±10) 25 (±10)
Outline drawings [ms] Fig. TELR1
Previous relay type DRHHB1CA, DRHHB5CA DRHHB5VA
Notes
*1:Note 1: Since the relay can be stored in a grouped plug-in type relay case for the conventional DRHH series (vertical case: DQBA2, DQBD1; horizontal case:
DSBA1, DSBB1), the relay can be replaced keeping the conventional wiring as is.
*2:Applicable voltage of contacts : 24 to 220V

■Internal connection diagrams

TELR–HHB5CA–DC110V TELR–HHB5VA–DC110V

Socket No. (+) Socket No. (+)


1 53 4 43 41 33 31 23 21 13 11 1 43 41 33 31 23 21 13 11
Coil No. Connection Coil No.

A 3 1 6 4 9 7 3 1 6 4 No.

Connection
First
No.
D1 Z1 B 3 1 6 4 9 7 3 1 6 4

B 5 8 2 5
First
Element D1 Z1
2 52 42 32 22 12
A 2 5 8 2 5
(-) Socket Element
2 42 32 22 12
(-) Socket

7ー 1
★Information required with your inquiry or order.
Coil specifications Double coil (DC)
Applications Current trip circuit
★Type Grouped plug-in type units *1 TELR–HHB1UA–DC 0.3A TELR–HHB1UA–DC 0.8A TELR–HHB1UA–DC 0.1A
Coil ratings ★Voltage DC [V] 0.3 0.8 1.0
Coil resistance [Ω] First (operation) coil : 8.9 First (operation) coil : 0.8 First (operation) coil : 0.8
Second (SHC) coil : 350 Second (SHC) coil : 330 Second (SHC) coil : 330
Guaranteed operate value 100% or less of ratings
Guaranteed resetting value 10% or more of ratings 150mA or more
Continuous withstand value 130% is continuous, 600% of ratings 30s
Contact *2 Arrangement 4c (1c in 5c is used for an internal contact)
ratings Limiting making capacity L/R=0.04 0.5s 110V DC, 5A
Continuous current carrying capacity [A] 5A
Limiting braleing capacity L/R=0.04 110V DC, 0.3A
Time Operate time (300% input of ratings) [ms] 4 to 6 at the connection of circuit configuration 1.
characteristics 10 to 20 at the connection of circuit configuration 2.
Resetting time (300% input of ratings) [ms] 50 to 75

Outline drawings Fig. TELR1


Previous relay type DRHHB1UA
Notes
*1:Note 1: Since the relay can be stored in a grouped plug-in type relay case for the conventional DRHH series (vertical case: DQBA2, DQBD1; horizontal case:
DSBA1, DSBB1), the relay can be replaced keeping the conventional wiring as is.
*2:Applicable voltage of contacts : 24 to 220V
*3:By installing external wiring to the secondary coil (to maintain a short circuit), as shown in the following circuit configurations 1 and 2, the operating time can
be changed.

■Internal connection diagrams

TELR–HHB1UA–DC□□A
(Circuit configuration 1) (Circuit configuration 2)

Socket No. Socket No.


(+) (+) (+) (+)
1 3 53 43 41 33 31 23 21 13 11 1 3 53 43 41 33 31 23 21 13 11
Coil No. Coil No.
Connection Connection
A C 3 1 6 4 9 7 3 1 6 4 No. A C 3 1 6 4 9 7 3 1 6 4 No.

First Second First Second

B D 2 5 8 2 5 B D 2 5 8 2 5
Element Element
2 4 52 42 32 22 12 2 4 52 42 32 22 12
(-) (-) (-) (-)
Socket Socket
External wiring External wiring

7ー 2
Keep relay
TELR series

★Information required with your inquiry or order.


Coil specifications Coil (DC)
Applications General control circuit
(With SA)
★Type Grouped plug-in type units *1 TELR–KHB5AB–DC 110V
Coil ratings ★Voltage DC [V] 100/110V DC
Coil registance [Ω] First (operation) coil : 1000
Second (reset) coil : 1000
Guaranteed operate value 80% or less of ratings
Guaranteed resetting value 80% or less of ratings
Continuous withstand value Independent of input because input is shut off by built-in contact of the time of operation or reset.
Contact *2 Arrangement 5c (1c in 6c is used for an internal contact)
ratings Limiting making capacity L/R=0.04 0.5s 110V DC, 5A
Continuous current carrying capacity [A] 5A
Limiting braleing capacity L/R=0.04 110V DC, 0.3A
Time Operate time (at rated input) [ms] 20 or less
characteristics Resetting time (at rated input) [ms] 25 or less
Outline drawings Fig. TELR2
Previous relay type DRKHB1AB, DRKHB5AB
Notes
*1:Note 1: Since the relay can be stored in a grouped plug-in type relay case for the conventional DRHH series (vertical case: DQBA2, DQBD1; horizontal case:
DSBA1, DSBB1), the relay can be replaced keeping the conventional wiring as is.
Since the internal circuit structure is different from the conventional DRKH series models, refer to the updating notes described below.
*2:Applicable voltage of contacts : 24 to 220V

■Internal connection diagrams

TELR–KHB5AB–DC110V

L side Socket R side Socket L side Socket


Socket No.
(+) (+)
Coil No.
1 3 23 21 13 11 33 31 23 21 13 11
Connection
C D 3 1 6 4 9 7 3 1 6 4 9 7 No.

First Second
D1 Z1 D2 Z2

A B 2 5 8 2 5 8
Element
2 4 22 12 32 22 12
(-)
Socket

■Notes for updating to the TELR series keep relay


The input terminals of the operating (first) coil and resetting (second) coil of the TELR series keep relay are polarized and feature a
terminal structure that is common with the Nos. 2 to 4 input terminals (negative polarity). For this reason, these TELR series characteris-
tics are different from those of the conventional DRKH series models.
When updating the conventional DRKHB series models, pay particular attention to the polarity of the input terminals of these coils. If the
No. 2 and No. 4 input terminals are used as + polarity in the conventional model wiring, be sure to change the wiring.

7ー 3
Time-lag relay
TELR series

★Information required with your inquiry or order.


Applications Protective relay device, or controll circuit
★Type Grouped plug-in type units *1 TELR–TK1PA–100/220–A TELR–TK1PA–100/220–B TELR–TK1PA–100/220–C
Ratings Frequency DC/50, 60Hz *2
Voltage 100 to 220V (Free) *2
★Setting range [s] 0.5 to 3 1 to 30 30 to 180
Rated burden 3W/VA
Range of voltage change 80 to 255V AC/DC
Continuous withstand voltage 255V AC/DC
Contact *3 Arrengement Time-lag : 2c, Instantaneous 1c
ratings Continuous current carrying capatity [A] 5A
Characteristics Guaranteed operate value [V] 80 to 255 AC/DC
Guaranteed resetting value [V] 10 AC/DC
Error margin of setting [%] ±2.5
Change of error margin [%] 2.5
Operate time for instantaneous contact [ms] 25 or less
Resetting time [ms] 120 or less
Disengaging time [ms] 100 or less
Allowable momentary interruption time of input [ms] 10 or less
Outline drawings Fig. TELR3
Previous relay type DRTKA1PA
Notes
*1:Note 1: Since the relay can be stored in a grouped plug-in type relay case for the conventional DRHH series (vertical case: DQBA2, DQBD1; horizontal case:
DSBA1, DSBB1), the relay can be replaced keeping the conventional wiring as is.
*2:Applicable to the AC/DC free voltage input
*3:The maximum contact voltage value is 125V DC.

■Internal connection diagrams

TELR–TK1PA–100/220–□

Time-lag Time-lag Instantaneous

(Input)

1 2 11 12 13 21 22 23 31 32 33

Socket No.

Operating precautions
(1) Do not touch the patterns and circuit parts of the printed board as far as possible. Do not allow easily chargeable clothes and gloves to come into contact with the
printed board.
(2) Ensure the relay is not exposed to any strong impact or external force during handling or transportation.
(3) Pay special attention to the heating of the storage case whenever the relay is activated.
(4) When the relay is to be operated repetitively, ensure a pause longer than the resetting time (120 ms).
(5) Do not operate the setting knob while the operate time is being measured to prevent any measurement error from occurring.

7ー 4
Outline drawings

Fig. DUT1: DUT (Unit standard structure type)

Panel
2 of M6 bolts and nuts

152
190

174

Name plate

Insulated terminal cover

179
120 30 201

Mounting hole dimensions on panel Terminal arrangement (seen from the rear)

44 4.9
Terminal number,
12 to 18 of M4×8mm screws
18
11 11 11 11 11 11 11 11 11

17
16
15
174
154

14
8 7
13 13 13

13
6 5
12
11 4 3
10 2 1
9
Connection sheet

16
2 of 7mm diameter holes
+2
112 0 110

Remark:When mounting two or more relays adjacent to


each other, the minimum mounting pitch of the
relays (from center to center) should be 130mm
horizontally and 210mm vertically.

[Unit : mm]

Fig−1
Fig. DUT2: DUT (DQ series replacement type)

Panel
2 of M6 bolts and nuts

152

156
190

174

Terminal block adapter

Insulated terminal cover


Name plate

179
120 30 233

Mounting hole dimensions on panel Terminal arrangement (seen from the rear)

44 4.9
Terminal number,
20 of M4×8mm screws
B18
11 11 11 11 11 11 11 11 11

B17
B16
B15
174
154

B14
B13
Connection sheet B12
11 11 11 11 B11
6.6 B10
B9
A10 A8 A6 A4 A2
A9 A7 A5 A3 A1
1.1
2 of 7mm diameter holes 11 11 11 11
+2
112 0 110

Remark:When mounting two or more relays adjacent to


each other, the minimum mounting pitch of the
relays (from center to center) should be 130mm
horizontally and 210mm vertically.

[Unit : mm]

Fig−2
Fig. DUT3 : DUT (Complex-element relay)

Panel
M6 bolts and nuts
279

296

257
110 25 179

120 30 202

Mounting hole dimensions on panel Terminal arrangement (seen from the rear)
44

External terminal of the


control circuit
121(Terminal pitch : 11x11)

20

19

18

17

16

15 ⑮
14 ⑭

44.5

13
259

279

12 ⑫
11 ⑪
10 ⑩
9
Connection ⑨
sheet
77.5

13

117.5

8 7
⑧ ⑦
6 5
⑥ ⑤
13

4 3
④ ③
2 1
② ①
FG
2–ø7
13

FG

External terminal of FG terminal Terminal number


+2
112 0 the AC input terminal (M4×8mm screws)
16 44 External terminal layout

25.7

[Unit : mm]

Fig−3
Fig. DRAW1: DRAW (Static type undercurrent relay, current-limit relay)

87
Mounting hole
2-φ4.5

4
Cover (clear)
7 8 9 10 11 12

Setting knob

140
116
148

112
Name plate

1 2 3 4 5 6
16

Connection name plate

4
13
69 Terminal screw
73 2x6-M3.5x8 17

Fig−4
Fig. TELR1 (Auxiliary relay)
47.5

Installation screw Socket

180

1
Cover
13 12 11

1 23 22 21
59

57
2 33 32 31

3 43 42 41

4 53 52

1
47.5
Pulling out steering wheel

Fig. TELR2 (Keep relay)


47.5

Installation screw Socket


180
Cover
1

R L
13 12 11 13 12 11

1 23 22 21 1 23 22 21
57
59

2 33 32 31 2 33 32 31

注 意
! CAUTION
永久磁石使用につき異物付着に注意
REMOVE FOREIGN OBJECTS ATTRACTED BY MAGNET
3 43 42 41 3 43 42 41

4 53 52 4 53 52
1

Pulling out steering wheel 100

Fig. TELR3 (Time-lag relay)


Installation screw Socket
11 13 12 11
31

21
11
33

32

23

22
13

12

Setting switch TIME-LAG RELAY


1.5 2
2.5
1
21 1 1 23 22 21
3
0.5
57

31 2 2 33 32 31
SEC

TIME UP
41 3 3 43 42 41
MFG 0902

4 4 53 52

Pulling out stay 178 47.5


[Unit : mm]

Fig−5
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan
Phone : (03)5435-7111

Internet address : http://www.fujielectric.co.jp