Chapter 1 Overview
Thanks for using AC70 series sensorless vector control frequency inverter produced by Veichi Electric co.,ltd. This
manual introduces you how to use it perfectly. Please read this manual carefully and fully understand the safety
requirement and cautions before use (installation, wiring, operation, maintain, checking, and etc...).
1.1 Safety Requirement and Cautions
Pls do totally understand this part before using the inverter.
Warning signs and meanings
This manual has used below signs that mean there is an important part of security. While observing against the rules,
there is danger of injury even death or machine system damage.
Important: Wrong operation may cause the inverter and other machine system damage
Warning position 2
1
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW
Operation requirement
Only Professional trained person are allowed to operate the equipment such as installation, wiring, running, maintain
and etc. “Professional trained person”in this manual means the workers on this product must experience professional
skill train, must be familiar with installation, wiring, running and maintain and can rightly deal with emergency cases in
use.
Safety guidance
Safety regulations and warning signs come for your security. They are measures to prevent the operator and machine
system from damage. Please carefully read this manual before using and strictly observe the warning signs while
operating. Safety regulations and warning signs are classified into: routine regulation, transport and store regulation,
installation and wiring regulation, running regulation, maintenance regulation, dismantlement and disposal regulation.
● Routine regulation
● This product carries dangerous voltage and controls driver machine with potential danger. If
you don’t abide by the regulations or requirements in this manual, there is danger of body
injury even death and machine system damage.
● Only qualified personnel are allowed to operate the equipment.this product. Before using, the
operator must be familiar with all safety specifications and operation regulations in this
manual. Safe and stable work of the product is based on right operation and maintenance.
● Do not wire while the power is connected. Otherwise, there is danger of death for electric
shock. Before wiring, inspection, maintenance, please cut power supply of all related
equipments and ensure mains DC voltage in safe range. And please operate it after 5 mins.
● Away from children and public.
● Only used in application fields as maker stated. No use in equipments related to special fields
such as emergency, succor, ship, medical treatment, aviation, nuclear and etc.
● Unauthorized alteration or use of accessories which are not sold or recommended by the
maker may cause faults.
● Please make sure this manual is in the final user’ hand before using.
● Before installation and debugging please carefully read and totally understand these safety
regulation and warning signs.
● Transport and store regulation
●Correct transport, store, installation and careful operation an maintenance are important for
inverter safe operation.
● In transport and store process, make sure the inverter is free from impact and vibration. It
must be stored where is dry without corrosive air and conductive dust, and the temperature
must be lower than 60℃.
● Installation and wiring regulation
● Only professional trained person can operate it.
● Power wire, motor wire and control wire should be all connected firmly. Earth must be reliable
and earth resistance must be lower than 10Ω.
● Before opening the inverter, please disconnect all related equipment power supply and make
sure the mains DC voltage is in safe range and operate after 5mins.
● Human body electrostatic will damage inner sensitive components seriously. Before
operation, please follow ESD measures. Otherwise, there is danger of inverter damage.
● Inverter output voltage is pulse wave. If components such as capacitor which improves power
factor and pressure-sensitive resistance for anti-thunder and so on are installed at the output
side, please dismantle them or change to input side.
2
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW
● No switch components such as breaker and contactor at the output side. (If there must be
one, please make sure the output current is 0 while the switch acting).
● The power supply cable and motor cable specifications must satisfy all conditions in table 3-7
3-8 .
● Run regulation
● Inverter runs at high voltage. So dangerous voltage is in some components inevitably.
● No matter where the fault is, there is danger of serious accident, even human body injury
what means dangerous malfunction possibility. So there must be additional external prevent
measures or other safety devices, such as independent current limiting switch, machinery
and so on.
● Maintenance regulation
● Only Shenzhen Veichi Electric co., ltd service department or its authorized service center or
professional person trained and authorized by Veichi can maintain the products. They should
be very familiar with the safety warning and operation gist in this manual.
● Any defective components must be changed in time.
● Before opening the inverter to repair please cut power supply of all related equipments and
ensure mains DC voltage in safe range. And please do operation after 5 mins.
● Dismantlement and disposal regulation
● Packing case can be reused. Please keep them and reuse or send back to maker.
● Dismantled metal components are retractable and can be reused.
● Some components such as electrolytic capacitor are harmful to environment. Please dispose
according to environmental protection departments.
3
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW
Voltage, frequency single phase 220V, 3 phase, 220V,380V, 660V and 1140V
Voltage:<±15%; frequency±5%
Allowable fluctuations
Distortion of voltage to confirm to IEC61800-2
Power Input
Closing striking current less than rated current
Power Factor ≥0.94( integrated DC reactor)
Efficiency ≥96%
3 Phase, 0~Input voltage, tolerance less than 5% in standard
Output Voltage
rating condition
G type: 0 to 400Hz, P type: 0-400Hz, Z type: 0-400Hz, L type:
Frequency Control Range 0-400Hz,
H type: 0-3000Hz.
Power Output frequency accuracy ±5% of maximum frequency
Output Z type: 150% rated current for 60 sec, 180% rated current for 30
sec, 250% rated current for instantaneous
G, H, L type model: 150% of rated output current for 60 sec,180% of
Overload Tolerance
rated current for 10s, 2 00% of rated current for instantaneous
P type: 120% rated current 60 sec, 150% rated current for
instantaneous
Motor Control Mode Open loop sensorless vector control without PG, V/F control
Control system Optimized Space Vector PWM Modulation
4
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW
5
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW
Environment Vibration Less than 0.5g when frequency less than 20Hz
Storage Temperature -25—+65°C
Installation mode Wall-mounted mode, floor stand cabinet install
Protection Degree IP20
Cooling Method Forced air-cooling
6
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BEFORE USE
Model
MODEL: AC70-T3-011G/015P
Input power
SOURCE: 3 380V 50/60Hz
OUTPUT1: 11KW 25A 0.00-400.0Hz G models output
Model explanation
inverter series
code inverter type
AC70 General use
G general format
P blower and water pump
Z plastic machine
code voltage class
L draw bench
T three phase
H mid inverter governor
S single phase
GD Cabinet with base
PD Cabinet with base
code voltage class
7
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BEFORE USE
8
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
9
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
10
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
100
75
50
25
-10 0 10 20 30 40 50 TEMPERATURE(℃)
Chart 3-2:AC70 series inverter derating surve while over permit temperature
● Derate according to the chart while over altitude limit.
PERMIT OUTPUT CURRENT(%)
100
80
Chart 3-3:AC70 series inverter derating surve while over permit altitude
3.4 EMI Protection
The inverter is designed to be used in industrial environment with strong electromagnetic interference. Generally
speaking, if the installation quality is good, it is ensured that the inverter can work safely without fault. Please install the
inverter according to the following rules to ensure stable running and avoid electromagnetic interference impact.
● Ensure that all equipments in the cabinet have been connected reliably to the common Y-type earth point or earth
bus with thick and short cable. The motor earth should be as close as possible. Please do not connect the motor
case to the inverter earth terminal or the protective area of control system.
● Ensure that all equipments connected to the inverter have been reliably connected to the same earth net or Y-type
earth point with thick and short cable.
● The conductor has better to be flat and with multi core, what has lower resistance at high frequency.
●The cutting terminal should be as soigne as possible. Unshielded wire section must be as short as possible.
● In control cable wiring, it should be as far from the power supply cable and motor cable as possible. And
independent cable trough should be used. While the control cable must cross to the power supply cable or motor
cable, it should be 90º vertical cross.
● Ensure that the contactor in the cabinet has wave surge suppresser. Or‘R-C’damping circuit is connected to the
winding of AC contactor. Voltage dependent resistor corresponding to the winding voltage is used. And freewheel
diode or components such as voltage dependent resistor corresponding to the winding voltage are connected to DC
contactor. It is very important while contactor, controlled by output relay of inverter, acts frequently.
● Cable connected to motor should be shielded cable or armoured cable. The two barriers are earthed reliably by
cable grounding card.
● Build noise filters at the input side to reduce electromagnetic interference from other equipments at the power grid
side. The noise filter should be as close to the inverter power input terminal as possible. Meantime, the filter must
earth reliably as the inverter.
● Build noise filters at the output side to reduce radio interference and inductive disturbance. The noise filter must be
as close to the inverter output terminal as possible. Meantime, the filter must earth reliably as the inverter.
11
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
12
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Table 3-2: Corresponding relationship between inverter/motor cable length and carrier frequency
13
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
● Installation direction
To prevent inverter cooling effect reducing, please do install the inverter vertically.
Chart 3-10: Multi AC70 series inverters paratactic installation space requirement
14
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
H1
H
Inverter size Install size Install
Inverter model
W H D D1 W1 H1 aperture
AC70-S2-R40G
AC70-S2-1R5G
AC70-S2-2R2G
159 246 157.5 148 147.2 236 ф5.5
AC70-S2-004G
AC70-T3-R75G/1R5P
AC70-T3-2R2G/004P
AC70-T3-004G/5R5P
159 246 157.5 148 147.2 236 ф5.5
AC70-T3-5R5G/7R5P
AC70-T3-7R5G/011P
195 291 167.5 158 179 275 ф7
AC70-T3-011G/015P
AC70-T3-015G/018P
(plastic cover machine)
AC70-T3-018G/022P
230 330 200 190 208 315 Ф7
(plastic cover machine)
AC70-T3-022G/030P
(plastic cover machine)
15
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
W
W1 D
H1
H2
H
Install aperture
16
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
W
W1
D
H1
H2
H
17
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
W D
H1
H
D1
W1
18
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
W D
H1
H
W1
D1
19
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Keyboard dimension
Chart 3-12:AC70 series inverter mouth for 1 line LED keyboard dimension
16.5 63.5
35.6
114.5
110.5
17.1
53.75
65.5 19.5
20
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
111
Mouth for keyboard with box
119
Mouth for keyboard with box Mouth for keyboard with box
AC70-T3-160G/630P AC70-T3-015G/132P
142
64
70
75
Chart 3-14:AC70 series inverter mouth for 2 line LED keyboard dimension
Note: LCD keyboard total same size as LED keyboard.
21
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
22
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Standard diagram
● Standard diagram
Frequency Inverter
Note1
+24V
PLC
AC220V Maximum output:
10
J1
switch _
mA
twisted-pair shielding line J2
20
0
(grounding nearby) J3
A02
Analog current Input +10V twisted-pair shielding
GND
(0~20mA)/(4~20mA) line (grounding nearby by inverter)
AS
J4 Pin 5
10
0
VR
Note2
Analog voltage Input VS2 -
+
(0~5V)/(0~10V)
A01
GND
GND
Note:
1 Maximum output 50mA +10V input terminal
Note: Maximum output is 2mA when
2. VS1/VS2 terminal resistor valuve 89ohm A01/A02 as for frequency voltage signal
3 AS terminal resistor valuve 250ohm output
Mark:
1. stand for main loop terminal
2. stand for control loop terminal
23
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
(AO2)
J2 0~20mA current output or
4~20mA current output
(K2)
(AO2)
J3
0~10V voltage output
(AO1)
J4 J4 connect
0~10V voltage output
(AO1)
(K1) J5 0~20mA current output or
J5 conne
4~20mA current output
24
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Note: 1, Fuse, dc reactor, braking unit, braking resistor, input actor, input filter,output reactor, output filter are optional
parts, please refer to “peripheral equipment”.
2, P1 terminal and (+) short connect. If need add dc reactor, please take away the short connect part between P1 and
(+).
Main circuit terminals
● Main circuit terminals array and definition
Arrangement sequence of main circuit terminal with 18.5kW or less power(15 ~ 18.5KW for steel cover machine)
(-)(+) PB R S T U V W E
Arrangement sequence of main circuit terminal with 15-22KW(15~22KW for plastic cover machine)
25
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Arrangement sequence of main circuit terminal with 22~30KW (standard machine without PB terminal)
(22KW for steel
cover machine)
Arrangement sequence of main circuit terminal with 132kW: Arrangement sequence of main circuit terminal with 160~560kW
Terminal Name
(-) DC power output, (-) means DC bus cathode, (+) means DC
DC power terminal
(+) bus anode, used for external braking unit.
(+)
Braking resistance terminal Used for external braking resistance to realize quick stop.
PB
P1
DC reactor terminal Used for external DC reactor.
(+)
R
S Inverter input terminal Used to connect 3-phase AC power supply.
T
U
V Inverter output terminal Used to connect the motor.
W
26
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
27
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Contactor Breaker
Model DC reactor Input filter Output filter
specification specification
28
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
29
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Table 3-10:AC70 series inverter control loop terminals array and definition
Bolt Cable
Fixed moment
Terminal specification specification Cable type
(N·m)
(mm) (mm2)
Twisted-pair
A+ B- M2.5 0.4~0.6 0.75
shielded cable
Twisted-pair
+10V GND A01 A02 VS1 VS2 AS M2.5 0.4~0.6 0.75
shielded cable
+24V COM Y1 Y2 TA TB TC PLC PUL
M2.5 0.4~0.6 0.75 Shielded cable
X1 X2 X3 X4 X5 X6
Table 3-11:Control loop terminal wiring specification
Braking unit (braking resistance) connection
● Brake resistance wiring of machine with 18.5KW or less power(15KW-18.5KW for steel cover machine)
Brakeing
resistor
(-) (+) PB R S T U V W E
Fig 3-20: AC70 Series Frequency Inverter Brake resistance wiring of machine with 18.5KW or less power
30
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Brakeing
resistor
Fig 3-21: AC70 Series Frequency Inverter Brake resistance wiring of machine with 15-22KW(for plastic cover machine)
● Brake resistance wiring of machine with 22KW and 30KW(built-in brake is optional)(22KW for steel cover machine)
R S T (+) PB (-) U V W
POWER INPUT MOTOR OUTPUT
Brakeing
resistor
Fig 3-22: AC70 Series Frequency Inverter Brake resistance wiring of machine with 22KW and 30KW(built-in
brake is optional)(22KW for steel cover machine)
● Brake resistance wiring of machine with 37KW or above
POWER ACTIVE
R S T (+) PB (-) U V W
POWER INPUT MOTOR OUTPUT Brakeing
resistor
- + + PB
Fig 3-23: AC70 Series Frequency Inverter Brake resistance wiring of machine with 37KW or above
● Suggested braking resistance specification parameters
Braking resistance value and power in the chart are decided according to common inertia load and intermittent braking
mode. While used in large inertia occasion or long time frequent brake occasion, please adjust resistance value and
power according to the inverter specification and the rated parameter of braking unit. If any problem, please consult
customer service department of Veichi Electric Com., Ltd.
31
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Three-phase 380V
Motor power(kW) Resistance value(Ω) Resistance power(W) Braking torque (%)
0.75 kW 750Ω 150W 100%
1.5 kW 400Ω 300W 100%
2.2 kW 250Ω 400W 100%
4.0 kW 150Ω 500W 100%
5.5 Kw 100Ω 600W 100%
7.5 kW 75Ω 780W 100%
11 kW 50Ω 1,200W 100%
15 kW 40Ω 1,500W 100%
18.5 kW 32Ω 2,000W 100%
22 kW 28Ω 2,200W 100%
30 kW 24Ω 3,000W 100%
37 kW 20Ω 3,700W 100%
45 kW 16Ω 4,500W 100%
55 kW 13Ω 5,500W 100%
75 kW 9Ω 7,500W 100%
90 kW 6.8Ω 9,300W 100%
110 kW 6.2Ω 11,000W 100%
132 kW 4.7Ω 13,000W 100%
160 kW 3.9Ω 15,000W 100%
185 kW 3.3Ω 17,000W 100%
200 kW 3Ω 18,500W 100%
220 kW 2.7Ω 20,000W 100%
250 kW 2.4Ω 22,500W 100%
280 kW 2Ω 25,500W 100%
315 kW 1.8Ω 30,000W 100%
355 kW 1.5Ω 33,000W 100%
400 kW 1.2Ω 42,000W 100%
450 kW 1.2Ω 42,000W 100%
500 kW 1Ω 42,000W 100%
560 kW 1Ω 50,000W 100%
Single-phase 220V
Motor power(kW) Resistance value(Ω) Resistance power(W) Braking moment (%)
0.4 kW 400Ω 100W 100%
0.75 kW 200Ω 120W 100%
1.5 kW 100Ω 300W 100%
2.2 kW 75Ω 300W 100%
Table 3-12: Suggested braking resistance specification parameters of AC70 series inverter
● Build-in braking unit max braking performance
Braking unit of AC70 series product with low power can be selected according to the suggested braking resistance
specification parameters in table 3-11. In large inertia or long time frequent brake occasion, the moment maybe should
be increased. The max braking power is showed in the following table, the range of which can not be over in use.
Otherwise the equipment maybe destroyed. If any problem, please consult Veichi Electric Com., Ltd customer service
department.
32
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Three-phase380V
Inverter model Motor power Max braking current Min resistance
AC70-T3-R75G/1R5P 0.75 kW 3.5A 200Ω
AC70-T3-1R5G/2R2P 1.5 kW 3.5A 200Ω
AC70-T3-2R2G/004P 2.2 kW 7A 100Ω
AC70-T3-004G/5R5P 4 kW 10A 75Ω
AC70-T3-5R5G/7R5P 5.5 KW 10A 75Ω
AC70-T3-7R5G/011P 7.5 kW 14A 50Ω
AC70-T3-011G/015P 11 kW 17A 40Ω
AC70-T3-015G/018P 15 kW 23A 30Ω
AC70-T3-018G/022P 18.5 kW 28A 25Ω
AC70-T3-022G/030P 22 kW 30A (optional) 24Ω(optional)
AC70-T3-030G/037P 30 kW 35A (optional) 22Ω(optional)
Single-phase 220V
Inverter model Motor power Max braking current Min resistance
AC70-S2-R40G 0.4 kW 3.8A 100Ω
AC70-S2-R75G 0.75 kW 3.8A 100Ω
AC70-S2-1R5G 1.5 kW 6.5A 60Ω
AC70-S2-2R2G 2.2 kW 10.5A 40Ω
Table 3-13:AC70 series inverter build-in braking unit max braking power
33
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
X1 X1
X2 X2
X3 X3
exterior
X4 X4
control exterior
signal control
X5 signal X5
X6 X6
COM COM
shielded cale E shielded cale E
dismantle 24v and PLC connector
use inner 24v power AC70 use exterior 24v power AC70
+24V
PLC + - PLC
COM COM
X1 X1
X2 X2
exterior
exterior
control
control
signal X3 signal X3
X4 X4
X5 X5
X6 X6
+24V +24V
wind wind
+
Y1 Y1
-
COM COM
control exterior relay by inner 24V power of inverter control exterior relay by inner 24V power of inverter
34
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
AC70 AC70
_
V _
V
10
10
0
0
+ - + -
A01 A02
GND GND
double shielded cable double shielded cable
E E
AC70 AC70
_
mA kHz
50
20
0
0
+ - + -
A02 A02
GND GND
double shielded cable double shielded cable
E E
Explaination:
1.Bias resistor value calculation:
pulse voltage
R= 2
max pulse output current
1.Bias resistor power calculation:
2
pulse voltage
P=
bias resistor value
Chart 3-28: Pulse input signal connection mode of AC70 series inverter
35
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING
Chart 3-29: Standby control system of power supply directly driving mode
36
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
● While operation, please follow the ESD regulations. Otherwise, the inverter maybe
damaged.
● Please don’t cut the power directly while the inverter drives the motor running. The power
can’t be cut until the motor totally stop. Otherwise, the inverter maybe damaged.
● Please don’t cut or connect motor while the inverter drives the motor running. The motor
can’t be cut or connect until the inverter output is 0. Otherwise, the inverter maybe
damaged.
Important ● Control cable should be twisted-pair shielded cable. The barrier should be
connected to the inverter earth terminal reliably to prevent the inverter from abnormal
working.
● Unprofessional person can not operate, install, wiring, debug and maintain.
● Change, dismantle or maintain without permission may cause inverter damage. This case
is not within our quality assurance range.
37
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
● Key function
Keyboard Can be used as input channel for given frequency, upper frequency limit,
potentiometer given torque, given PID or PID feedback setting.
38
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
39
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
FWD
REV
JOG
Arrowhead direction
Terminal connect
Standy or running Basic parameter External terminal parameter Special function parameters
PRG
40
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
41
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
2. Dual line keypad cycle switching display monitor parameters operation flow chart.
Hz A V RPM % Hz A V RPM %
Hz A V RPM % Hz A V RPM %
Output
Motor speed
frequency
SET SET
Hz A V RPM % Hz A V RPM %
Output
frequency Motor speed
Hz A V RPM % Hz A V RPM %
SET SET
Hz A V RPM % Hz A V RPM %
Hz A V RPM % Hz A V RPM %
SET
Input voltage
Hz A V RPM %
Hz A V RPM %
Giving frequency
On Spark Off
42
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
Change digit
Back menu
43
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
Parameter no
Stanby or running state PRG
Pameter value
Change digit
Function paramer no
Find parameter no
Parameter no
PRG Back
Parameter value
Change digit
SET Confirm
Find paramerter no
Paramerter no Paramerter no
44
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
Start
no yes
Whether motor and
load if can dismount
45
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
yes no
load break off test
yes
self-tuning failture, fault alarm
no parameter renew
self-tuning finished,parameter
H-57-H-61 renewed
over
46
keyboard digital =0
giving
keyboard =1
potentionmeter
=2
terminal VS1
=3
analog AS given
E-02
=4
terminal VS2
● Frequency giving flow
channel selection
=5
terminal PUL
=7
up/down control F0.11
E-05
main frequency reference giving f1
=8
f1 =0
PID control
f2 =1
program control =9 f≤f3 output
frequency f
=10
f1 priority f2=2
reserve
f1+f2*k =3
AC70 VC CONTROL FREQUENCY INVERTER MANUAL
=11
optional card f
E-03 f1-K*f2 =4
47
=12
terminal switch max{f1.k*f2} =5
frequency giving
auxilliary channel
keyboard digital =0 min{f1.k*f2} =6
giving f>f3 output f3
=1 f2+K*f1 =7 frequency
keyboard
potentionmeter
=2
f2-K*f1 =8
terminal VS1 auxiliary frequency reference giving f2
=3
max{k*f1.f2} =9
analog AS given
min{k*f1.f2} =10
=4
terminal VS2
=5
terminal PUL
=6
RS485 communication
=7
up/down control
=8
PID running
=9
PID control
F direct start
constant speed
set frequency
E-01
E-28
=0
T
=1 E-29
=2
constant speed
set frequency
E-28
start
E-38 T
DC baaking E-29
start frequency hold time
run command
stop
speed track restart
E-53
E-34
=0
=1
F
constant speed
set
frequency constant speed
stop output
DC baaking
start frequency
E-37
terminal function 6 T
E-36
Xi open braking time
(Xi=X0~X6)
connect
free stop
48
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
start
trial run
over
49
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
50
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
52
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
53
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
system fault
yes
Clear short circuit Whether there is short circuit between outout terminal U/V/W and the motor
no
yes
Short the cable or Cable between output terminal U/V/W and motor
add outout reactor is too long that leakage current cause inverter protection
no
yes
Clear disturbance Is there serious electromagnetic disturbance?
no
yes
While disconnect output wire and run,whether there is system fault alarm
no
no
yes
Connect load and
Three phase outout voltage balance is ok or not?
operate as follows
yes
yes
Reduce load or
Whether overload or not?
enhance power
no no no
no yes
Display E.SC Display E.SC Display E.SC while Display E.SC while
while start while stop constant speed machine stop
yes
yes
yes no
yes
no
Torque enhance value Whether acceleration Whether deceleration Whether load
is suitable or not time is too short time is too short change suddently
no yes yes
yes
no
Torque enhance ACC time can be Dec time can be Reduce load change
valuecan be prolonged or not
reduced or not prolonged or not or enhance power
54
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
yes
Whether short circuit between output terminal
Clear short circuit
U/V/W and motor or earth circuit
no no no
yes
Reduce load or
Whether load is too large
enhance power
no
no
Whether torque
Can be reduced? enhance value is too no no
yes yes
yes
yes
Set longer acceleration Whether set longer Reduce load change
time or not? decelerationtime or improve power
yes
Prolong setting time
no
no
55
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
no
Reduce power voltage
Fower votage in fixed range or not
into fixed range
no no no
yes
Stop motor and restart. Whether it stops while restart the motor
Or DC braking,then start
(E-30:1). Or speed track
no no no
start(E-30:2)
Whether act while load suddently changes to"0"
no no no
no
Whether DC circuit voltage of main loop is above protection value while act
yes no
no
yes
ACC time can be
prolong or not prolong
no
yes
Reduce Load intertia can be reduced or not
no no no
56
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
yes
Restart after reset Whether power off,including instant power off
no no
no no
Modify power supply
no
system as required Whether power voltage is in fixed range as required
yes yes
yes
Is there any big load start or stop under the same power supply
no no
no
Adjust E-55 setting votage between DC circuit P+ and N- in
main loop is over E-55 setting or not
yes yes
Inner inverter
overheat OH
no
Change fan Whether cooling fan works normally
yes
Maybe temperature ditection no
circuit fault.please seek for Whether temperature display(C-09)is
technic support the same as the actual temperature
yes
yes
Reduce load and Whether load and carried frequency
carried frequency E-20 setting are too high
no
yes
Clear the air-logged channel Whether air cooling channels are air-logged
no
Adjust the temperature to no
the fixed range as required Whether the temperature is within the fixed range as required
yes
57
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
Over load
yes
no
Whether electric thermal relay overload
Correct setting value
relay setting E-50 is suiable
yes
Reduce load or yes
improve capacity Whether load too high
no no
Restart after motor stop or yes
change start mode E-30 Whether the motor stops while restart
to 1/2
no no
yes
Prolong ACC/DCC time Whether ACC/DCC time is too short
no no no
Change torque improving
Whether torque improving or V/F curve setting is suitable
or V/F curve setting
yes yes
No display
Inverter keyboard
LED no display
yes
58
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING
Motor heat
motor heat
no yes
Adjust torque imporoving Whether torque improving and V/ Whether motor continuously
value and V/F characteristic F characteristic are suitable or not run at low speed
no
yes
yes
Reduce load or
Whether load is too large Use special motor for inverter
improve capacity
no
yes
Whether output terminals U/V/W output
voltage /current three phase balance well Maybe motor fault
no
Motor does
not work
yes no
Work after solving Whether keyboard Have input command
fault and reset displays fault information signal or not
yes
no
no
It works after checking
Have input frequency It works after checking the
the cause and solving
signal or not cause and slving the problem
the problem
yes
yes It works after correct the
Whether upper frequency limit E-10 or given frequency
upper frequency or given
is lower than the start frequency E-28 setting frequency
yes
no
Is there voltage output on output terminal U/V/W Maybe inverter fault .Please
and three phase balance ok or not? find technic support
yes
yes
no
Whether load Whether wiring is
is too large Correct connect
correct or not
yes
no
no
Motor fault Whether torque improving Improve torque
value is suitable improving value
yes
59
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIODIC OVERHAUL AND MAINTENANCE
60
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIODIC OVERHAUL AND MAINTENANCE
:No operation under power connected state. Otherwise there is danger of electric shock death. Before
operation, please cut all related equipments power, ensure that the main circuit DC current has dropped to safe range.
And please operate after 5 mins.
● Periodic overhaul
Under normal state, one overhaul every 3 or 4 months is ok. Please confirm the actual overhaul period according to the
machine use condition and work circumstance while using the machine.
Main circuit
Items Checking content Treatment
Check insulated resistance; Tighten and change bad component;
Whole body
Check circumstance. Clear and improve circumstance
● Check whether the wire and
connector color changes, whether there ● Change bad wire.
is disrepair , crack color change or ● Fasten terminals and change bad
Electric connection aging in insulated layer. terminals.
●Check whether the connect terminals ● Measure earth resistance and fasten
are damaged or loose. earth terminals.
● Earth checking.
● Check if there is abnormal vibration ● Tighten, lubricate and change the bad
Mechanical connection
or noise or something is loose. machine components.
● Check whether there is dust or
semi-conductive ● Clear
rubbish.
component ● Change damaged component
● If there is obvious out change?
● Whether there is liquid leak, color
Electrolytic capacitor change,or creak? Whether there is ● Change damaged component
safety valve outcrop, inflation, creak or
liquid leak.
●Peripheral equipment outlook and
Peripheral equipment ●Clear and change damaged component
insulation checking.
●Fasten connector
●Bad smell,color change, bad rust and
PCB ●Clear PCB
connector checking.
●Change bad PCB
● Check whether the fan is damaged
or blocked up.
●Whether rubbish and dust is sticked ● Clear
Cooling system
to the heat sink . ● Change damaged component
●Is air inlet/outlet blocked? Or is there
something sticking to the inlet/outlet.
● Whether is it damaged? Check
Keyboard ● Change damaged component
whether display is complete.
●Check if there is abnormal vibration ●Tighten machine and electric connection
Motor
or noise. and lubricate the machine components.
:No operation under power connected state. Otherwise there is danger of electric shock death. Before
operation, please cut all related equipments power, ensure that the main circuit DC current has dropped to safe range.
And please operate after 5 mins.
6.3 Maintenance
All equipments and components have useful lifetime. Right maintenance can prolong the lifetime. But it can not avoid
damage. Please change the components before their lifetime over.
● Fan
While changing fan, please use original fan. You can contact Veichi company or the dealer. There are inverter models
with many fans in one machine. To prolong these machines lifetime, you had better change all fans while changing the
cooling fan.
● Fan change method:
1, Install the fan vertically into the cover as shown in the picture (the label should face the outside).
2, Press the elastic clip of the fan by finger toward the inner side and insert the leading terminal of the fan vertically by a
little strength.
3, Insert the two elastic clips of the fan cover vertically into the fan installation slots.
62
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIODIC OVERHAUL AND MAINTENANCE
● Fan dismantlement:
1, Pinch the two elastic clips of the fan and pull out. Then dismantle the fan cover.
2, Press the elastic clip of the fan by finger toward the inner side and pull out the leading terminal of the fan vertically by
a little strength.
3, Poke the clips toward the outside and detach the fan from the cover by a little strength.
:1, No operation under power connected state. Otherwise there is danger of electric shock death. Before
operation, please cut all related equipments power, ensure that the main circuit DC current has dropped to safe range.
And please operate after 5 mins.
2, While the inverter is working, the heat sink temperature will be higher as the consumption. To prevent from scald,
please do not touch the heat sink and do not change the fan until the temperature being safe.
3, To ensure the best performance of the inverter, please use the original fan.
●Other components
The replacement of the other components has strict requirements on maintenance technique and product familiarity.
And they can not be used without strict detection after replacement. So we do not suggest the user to replace the other
inner components. If they need to change indeed, please contact to the dealer or the sales department of Veichi electric
company.
63
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIPHERAL EQUIPMENTS AND OPTIONS
64
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIPHERAL EQUIPMENTS AND OPTIONS
Output side noise filter Reduce the output side wire electromagnetic disturbance.
Winding surge absorbable unit Restrain surge voltage when the AC contactor acts.
65
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIPHERAL EQUIPMENTS AND OPTIONS
MI/RFI filter
To protect human body and inverter, please choose leakage current breaker which can use AC/DC power and can face
high frequency leakage current. There should be one leakage current breaker with more than 200mA sensitive current
for every frequency inverter. If the frequency inverter outputs different wave, the high frequency leakage current can be
higher, which will lead to breaker fault. In this case, please take below treatments:
Improve the sensitive current of the leakage current breaker
Reduce the carrier frequency of the inverter
Electromagnetic contactor
Electromagnetic contactor is a peripheral equipment what is set to actually separate power and inverter connection.
While inverter protective function is acting or carrying out emergency stop operation, the main loop power can be cut by
peripheral equipment. Please do not connect the electromagnetic switch or electromagnetic contactor to output circuit.
Otherwise the inverter may be damaged. While the power recovers after instant stop, if it needs to prevent the inverter
to auto-restart, please install electromagnetic contactor for control at the input side.
AC input reactor and DC reactor
To restrain current sharp change and high hypo harmonic current, it needs to use AC input reactor and DC reactor. It
can also improve power factor at the input side. In the following cases, AC input reactor or DC reactor must be used
(use both will bring better effect).
Need to restrain high hypo harmonic current and improve power side factor;
Need to switch input phase capacitance;
Frequency inverter is connected to large capacitance power transformer (600kVA above);
Silicon-controlled converters such as DC motor driver are connected to the same power system.
If user has higher requirement on other harmonic restraint, please connect the external DC reactor. Before connect the
external DC reactor, make sure to dismantle the short connector between the terminals P1 and (+).
Surge restrainer
Surge restrainer is divided into winding surge restrainer and main loop surge restrainer according to the use position.
Pls choose the right one which is suitable for the occasion. The aim of surge restrainer installation is to restrain the
surge voltage brought by switch components such as inductive load which is surrounding the frequency inverter
(electromagnetic contactor, electromagnetic relay, electromagnetic valve, electromagnetic winding). Do not connect the
surge restrainer to the output side of the frequency inverter. Otherwise the frequency inverter will be damaged.。
Input side noise filter
Rectifier bridge of the inverter is uncontrolled rectifier bridge. And input current is discontinuous impulse current. So the
harmonic current noise signal, which flows to power wire from the inverter inner, may bring bad impact on the
surrounding machines (radio, phone, non contact switch, sensor). This time, we suggest to install input side noise filter
to lighten the noise into the power wire. Besides, it can also reduce noise from the power wire into the frequency
inverter.
: Please use the noise filter special for the frequency inverter and the connection wire between the filter and
the inverter should be as short as possible.
Output side noise filter
The frequency inverter outputs square wave with high-speed peak value voltage switch. So there is high-speed dv/dt
converter on the output cables that will produce a large number of radio disturbance and inductive signal. By installation
noise filter at the output side, the impact can be relieved. Please do not install the input-phase capacitance and the
noise filter to the output circuit. Otherwise there is danger of damage to the frequency inverter.
0-phase reactor
0-phase reactor is used to reduce the electromagnetic inductive disturbance of the frequency inverter, which is suitable
for the input side and output side. It equals to a three-phase common mode inductance. In actual use, according to the
actual magnetic core size and cable specification, it is better to make sure 3-5 circles winding ratio to bring the best
performance.
Braking reactor or braking unit
Renewed power consumption unit, please see the sixth part of the chapter three “electric installation”.
Heat relay
Please install the heat relay at the output side of the frequency inverter. When the motor enters into overload state, it
will cut the power source to protect the motor. While using one frequency inverter to run one motor, there is no need to
install heat relay. The motor overload protection current [E-49] of the frequency will work. While using one frequency
inverter to run multi-motors or the motor is run directly by the power grid, please install heat relay between the
frequency and the motor. While installing the heat relay, please design to cut the sequence control circuit of the MC at
the main loop input side by the connection spot of the relay or design to input the heat relay action into the frequency
inverter as the exterior malfunction.And please pay attention to the following tips to avoid heat relay fault and motor
overheating at low speed.
67
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIPHERAL EQUIPMENTS AND OPTIONS
68
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
0: Open loop vector control without PG Also call sensorless vector control mode, are suitable for application
one inverter drive one motor which need high performance control requirement. It can achieve fast torque response,
wide speed control range and high torque output even under low speed without motor feedback.
Note: It needs to perform motor auto tuning with configure motor parameters correctly before first time
running with this control mode.
1: V/F control mode Adjusting the speed with V/F ratio, Use this mode for simple speed control and for multiple
motor applications with low demands to dynamic response or speed accuracy. This control mode is also used when
the motor parameters are unknown and Auto-Tuning cannot be performed. The speed control range is 1:40.
Uses for selecting inverter running, stop and running direction command input channel.
0: Operator keypad Running and stop of inverter control by forward running key FWD, reverse running or Job
key REV/JOG and stop key STOP/RESET of operator keypad. When [E-08] parameters set to 0, REV/JOG is
defined for reverse running, when [E-08] parameter set to 1, REV/JOG is defined for JOG running.
1: External terminal control Running, stop and rotation direction of inverter control by ON and OFF of FWD
terminal or reverse terminal. Please refer to [F-08].
2: RS485 Communications port control Running, stop and rotation direction of inverter control by given signal
of RS485 control port.
Note: STOP/RESET of keypad, reset command from control terminal or RS485 communication are all
enabled when fault reset.
Tips: 1. The running direction of inverter control is disabled by this command when programming control
and (VS2) terminal input bipolar adjustment, direction control is valid.
2. STOP/RESET key function is programmable, it can be defined emergency stop button function
when selecting external terminal control or RS495 control, refer to [F-07]; If use STOP/RESET
button on keypad to stop inverter when selecting external terminal control, inverter will be stop and
locked the external terminal command, it need to input external terminal stop command to unlock it,
and then external terminal running command will be activated again. It is the same for RS485
communication control.
3. When selecting operator keypad control, direction control by external terminal takes is priority to
control by keypad; it means that when reverse terminal and COM is on, if the direction command is
changed by keypad, it will be keep the same original running direction after the terminal and COM is
off.
It is used for selecting main frequency reference given of inverter, the frequency given will control or affect the
output frequency of inverter; terminal (VS2) analog voltage signal and program control channel also will control the
running direction of inverter directly.
0: Operator keypad digital Main frequency reference given by parameters [E-16] configuring: it is available to
modify the [E-16] preset value via up/down arrow button on keypad when inverter in running status or stop state.
1: Potentiometer of keypad Main frequency given is determined by potentiometer of keypad.
2: Terminal VS1 analog voltage 0-10V Main frequency given determined by control terminal VS1 analog input,
Regarding the relationship between input analog and frequency, filter time of input analog, Please refer to
parameters in detail [F-41, F-42, F-43, F-56, F-57, F-58] parameters
69
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
3: Terminal AS analog current signal 4-20mA Main frequency given is determined and modified by ( AS)
analog current input; Regarding the relationship between input analog and frequency, filter time of input analog,
Please refer to parameters in detail [F-50, F-51, F-52, F-56, F-57, F-58].
4: Terminal VS2 analog voltage -10-10V Main frequency given is determined and modified by control terminal
VS2 analog input, Regarding the relationship between input analog and frequency, filter time of input analog,
Please refer to parameters in detail [F-44, F-45, F-46, F-47, F-48, F-49, F-56F, -57, F-58]
5: Pulse train signal Main frequency given is determined and modified by control terminal (PUL) analog input,
Regarding the relationship between input analog and frequency, please refer to parameters in detail [F-53, F-54,
F-55, F-56, F-57, F-58]
6: RS485 communication port Main frequency given is determined by receiving signal of (A+) and (B-) of
RS485 communication port.
7: Up and Down control Main frequency given is determined by increasing UP and decreasing (DOWN) terminal
connecting or disconnecting( ON/OFF) with COM terminal; each of multi- terminal ( X1-X6) can be programmed by
frequency UP terminal and DOWN terminal, refer to [F-01-F-06] in detail; Initial frequency of up and down terminal
control can be configured, please refer to parameter [F-07] LED ten digit option and [F-70].
The acceleration and deceleration time of UP and Down control running is determined by acceleration/ deceleration
time 1 [E13-E-14] setting; The rate of speed change of Up and Down terminal is determined by acceleration/
deceleration time 2 [F-24-F-25] setting.
8: General PID operation Select it use to set up general PID close loop control system. When it has been applied,
the [H-16] present setting value can be modified by up and down arrow button of keypad.
9: Constant pressure PID control It can be used to set up constant pressure PID control ( constant pressure
water supply system etc) close loop system, the [H-16] present setting value can be modified by up and down
arrow button of keypad.
10: Program running Main frequency given and rotation direction are configured by inverter’s inner simple PLC
process control. Up to 8 steps speed control is available, more detail refer to [E-13, E-14, F-09-F-16, F-24-F-29,
H-32-H-51].
Run and stop command of program running determined by present setting value of running control command
selection.
When a step running time is set to 0, it means it will skip over this step when perform the program running. It is
easy to set up the steps required of program running.
When [E-46] parameter is set to 2 for forbidding reverse running, inverter will be run at 0 speed when arriving to a
step which have been set to reverse running.
Program running and multi-step speed operation are designed to achieve inverter variable-speed operation under a
certain laws. Among the multi step operation, multi step speed switch over and rotation direction changing are
achieved through the different combinations of external multi-step speed terminal with COM terminal ON and OFF.
Multi step frequency, operation time, rotation direction can be defined by function parameters. Multi step speed
control can be defined by each multi-function terminal, Please refer to [F-01-F-06] parameters.
11: Swing frequency run Output frequency periodically changes by pre-set decel & accel time. This function
70
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
is especially applicable to system which speed change vary with before and after the bobbin diameter in textile
field.
12: Terminal selection The main frequency given channel programmed by terminal selection, refer to the
parameter [F-01-F-06]
The relationship between terminal mode and frequency given channel as following table:
Frequency Frequency Frequency Frequency
given selection given selection given selection given selection Frequency given channel
terminal 4 terminal 3 terminal 2 terminal 1
OFF OFF OFF OFF Operator keypad digital
OFF OFF OFF ON Potentiometer of keypad
OFF OFF ON OFF Terminal(VS1) voltage signal
OFF OFF ON ON Terminal (AS) current signal
OFF ON OFF OFF Terminal (VS2) voltage single
OFF ON OFF ON Terminal pulse train signal
OFF ON ON OFF RS485 communication port
OFF ON ON ON UP/Down control
ON OFF OFF OFF General PID operation
ON OFF OFF ON Constant pressure PID control
ON OFF ON OFF Program running
ON OFF ON ON Swing frequency run
Tips: Frequency reference terminal valid combinations are 0-11(decimal), if not among this range, output
frequency will be 0. The OFF of table stands for corresponding terminal with COM is disconnect, ON
stands for corresponding terminal with COM is connect.
Used for selecting frequency reference given auxiliary channel. The combination mode of auxiliary and main
channel programmed by [E-05] parameters
0: Operator keypad digital given Auxiliary frequency given is set by up and down arrow key of keypad or
parameters [E-16] configuring.
1: Potentiometer of keypad Auxiliary frequency given determined by potentiometer of keypad.
2: Terminal VS1 analog voltage 0-10V Auxiliary frequency given is determined and modified by control terminal
VS1 analog input.
3: Terminal AS analog current signal 4-20mA Auxiliary frequency given is determined and modified by (AS)
analog current input.
4: Terminal VS2 analog voltage -10-10V Auxiliary frequency given is determined and modified by control
terminal VS2 analog input.
5: Pulse train signal Auxiliary frequency given is determined and modified by control terminal (PUL) analog input.
6: RS485 communication port Auxiliary frequency given is determined by receiving signal of (A+) and (B-) of
RS485 communication port.
7: Up and Down control Auxiliary frequency given is determined by increasing UP and decreasing DOWN
terminal connecting or disconnecting( ON/OFF) with COM terminal; each of multi- terminal (X1-X6) can be
programmed by frequency UP terminal and DOWN terminal, refer to [F-01-F-06 ]in detail; Initial frequency of up
and down terminal control can be configured, please refer to parameter [F-07] LED ten digit option and [F-70].
8: General PID operation Selects it use to set up general PID close loop control system. When it has been applied,
the [H-16] present setting value can be modified by up and down arrow button of keypad.
9: Constant pressure PID control It can be used to set up constant pressure PID control (constant pressure water
supply system etc) close loop system, the [H-16] present setting value can be modified by up and down arrow
71
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
button of keypad.
10: Program running Main frequency given and rotation direction of inverter are configured by inverter’s inner
simple PLC process control. Up to 8 steps speed control is available, refer to [E-13, E-14, F-09-F-16, F-24-F-29,
H-32-H-52]
Tips: Frequency main channel and frequency auxiliary channel can be set the same channel. In this case,
the corresponding relationships between the frequency setting values and input signal are rather special, it
need to consider the frequency main channel and auxiliary channel both characteristic at the same time.
The combination of main and auxiliary frequency given still limited by upper frequency limit and lower
frequency limit.
Frequency reference given channel gain: Uses to amplify or lessen the frequency input channel signal.
Proportional regulating of frequency given both main and auxiliary channel is available.
Frequency given channel combination mode: Uses for selecting frequency given main channel and auxiliary
channel combination. K stands for [E-04] setting value, MAX means takes the bigger among the both channel, MIN
means takes the smaller among the both.
0:Main channel is valid, auxiliary channel is invalid.
1:Auxiliary channel valid, main channel invalid
2:Both channel non “0” value valid, main channel priority
3:Main channel + ( K × auxiliary channel)
4:Main channel -(K × auxiliary channel)
5:MAX [main channel , (K × auxiliary channel)]
6:MIN [main channel , (K × auxiliary channel)]
7:Auxiliary channel + (K × main channel)
8:Auxiliary channel - (K × main channel)
9:MAX [(K × main channel), auxiliary channel]
10: MIN [(K × main channel), auxiliary channel]
Tips: 1. Terminal (VS2) will be quite special in the multi-channel combination case.
A. When (VS2) terminal don not activate the bipolarity adjustment and direct control function both ([F-48] set to 0),
the combination mode determined [E-05] combination mode setting.
B. When (VS2) terminal activate the bipolarity adjustment and direction control function both ([F-48] set to 1 ),
( VS2 ) terminal frequency given with bipolarity and frequency given in another channel implement signed arithmetic
based on the combination mode selected, the absolute value is for frequency given, the signed determine the
direction rotation of motor after calculation.
C. When (VS2) activate the bipolarity adjustment but no direction control. ([F-48] set to 2 ). ( VS2 ) terminal
frequency given with bipolarity and frequency given in another channel implement signed arithmetic based on the
combination mode selected, the absolute value is for frequency given, the rotation direction depend on the[E-01]
Running control command selection.
2. Swing frequency running, jog function and multi-step is disabled combine with auxiliary channel.
Uses to select the monitoring items displayed in two LED on the keyboard respectively. In the monitoring status, the
upper LED monitoring item and the lower monitoring item can be modify directly via SET key and SHIFT key.
0: Frequency reference Given 1: Output frequency 2: Output current 3: Input voltage
4: Output voltage 5: Machine speed 6: PID given 7: PID feedback value
When there is only one LED on the keyboard, it is disable to modify the lower LED monitoring via the [E-07] and
SHIFT key.
72
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Maximum frequency: Maximum frequency of [E-09] is the maximum allowable output frequency of inverter
frequency, also is the reference point of acceleration and deceleration time setting.
Upper limit frequency: Output frequency upper limit value which is set base on the highest allowable speed of
machine. When the frequency given is higher than upper limit value, the actual running frequency is upper limit
frequency.
Lower limit frequency: Output frequency lower limit value of inverter. When the frequency given is lower than
lower limit value, the actual speed depend on the [E-12] setting.
Maximum frequency, upper limit frequency and lower limit frequency should be cautiously set base on the
nameplate parameter of actual control motor and the need of the running conditions.
Except of upper limit frequency and lower limit frequency, the output frequency while inverter running is limited by
parameters setting of start-up frequency, free stop frequency, DC braking stop initial frequency, jump frequency and
so on. The relationships between the maximum frequency, upper limit frequency and lower limit frequency is shown
as the follow Fig.
Maximum frequency, upper limit frequency and lower limit frequency relationship. Fig.
Note: Lower limit frequency range is disabled for Jog function, only the upper limit frequency range is
enable for Jog function.
If the lower limit frequency operation mode [E-12] set to 0, the frequency given lower than the lower limit frequency,
the inverter would be run at 0.
If the lower limit frequency operation mode [E-12] set to 1, the frequency given lower than the lower limit frequency,
the inverter would be run at lower limit frequency.
73
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Acceleration time 1: when[E-15]LED tens digit place to 1, it defined required time of out frequency accelerates
from 0.00Hz to maximum frequency[E-09], when[E-15]tens bit place to 0, it defined required time of output
frequency accelerates from 0.00Hz to motor rated frequency, refer to[E-15].
Deceleration time 1: when [E-15] tens digit place to 1, it defined required time of out frequency decelerates from
maximum frequency [E-09] to 0.00Hz , when [E-15] tens bit place to 0, it defined required time of output frequency
decelerates from motor rated frequency to 0.00Hz, refer to [E-15].
Note: 1. In the general circumstance ( no special specify ), the acceleration/ deceleration time 1 is default
setting. The acceleration time is only valid for normal acceleration running, not including the DC
braking starting time and DC braking starting frequency holding time. The deceleration time only
for normal deceleration running, not includes DC braking stop time.
2. If activate the equidistant function, inverter would be accelerate base on the accel. time 1, but
decelerates based on equidistant stop decel. time setting. Refer to [E-15].
3. If need apply other accel. & decel. time group, should be configure by control terminals setting,
in the program running case, the accel./decel. time 1 is defined for first accel./decel. time, other 3
groups of accel./decel time setting is available, refer to [F-24-F-29]
4. Jog acceleration and deceleration time are programmed by [E-26, E27]separately.
74
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Frequency Frequency
Motor Motor
Rated freq. Rated freq.
Time Time
Note: 1. This function is disabled when the frequency given less than10% of maximum frequency, the
inverter decelerate based on the deceleration time, it will not performed the equidistant function when the
frequency given less than 10% of maximum frequency.
2. The overvoltage and over current suppression occurs when the deceleration time is too short, the actual
of deceleration time will be longer, and the equidistant function can’t be performed.
LED Thousands digit:
0: Disable
1: Enable
75
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
It uses to set or modify frequency reference when the frequency given channel is set to operator keypad digital
given.
Shortcut setting is available as well, changing the frequency reference via up/down arrow key of operator keypad
when inverter running or in standby mode.
V/F curve mode: Uses to select V/F curve mode to meet various of load characteristic requirement. AC70 vector
control inverter provides 4 kinds of fixed V/F curve and one kind of user defined V/F curve. Constant torque curve is
optional for general load and descend torque curve is optional for square torque load such as water pumps and
fans load.etc.
0: Constant torque curve
1: Descend torque curve(1.5 power curve)
2: Descend torque curve(1.7 Power curve)
3: Descend torque curve(2.0 Square curve)
4: User define curve :Inverter runs base on user defined V/F curve,[E-18] function is disable, User can program
appropriate V/F curves according to the load characteristic, for details please refer to[H-01-H-10].
Torque boost: When [E-00] is set to 1(V/F control mode), it is used to enhanced torque output under low
frequency running through output voltage boost compensation, when [E-00] is set to 0 ( OLV control without PG ),
the torque boost improvement follows vector control mode,[E-18]setting parameters is disable.
Torque boost value selecting should be according to load inertia. If the boost value is too big, will result in motor
overexcited running, and motor over heat easily, even worst, inverter will occurs over current fault protection, or
can’t start inverter properly.
76
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
This function mainly used to torque boost in OLV control mode. The value setting is smaller, the response of torque
boost is faster, the fluctuation of current is bigger, suitable for sudden changing load application; vice versa, the
filter time setting is bigger, the response of torque boost is slower, the fluctuation of current is smaller, suitable for
constant load application.
This function mainly used to improve the noise emitting and vibration possibility occurs during inverter operation.
The waveform of current will be good when the carrier frequency is bigger, the noise of motor is smaller. It is very
suitable for application that silent required, but in this case, but the switching loss of main component is bigger, the
temperature rise, efficiency reduces, and output power is smaller. Meanwhile, the radio interference will be bigger,
the leakage of capacitor also increases when run in high carrier frequency, that will result in malfunction of residual
leakage protector which if have installed, over current will be possibility occurs as well. When frequency carrier is
low, it is contrary to the phenomenon mentioned above.
The response of difference motors to carrier frequency is different. The best carrier frequency should be adjust to
gain according actual application site. But the carrier frequency should be set smaller for bigger capacity motor.
Veichi reserve the right to restrict biggest carrier frequency.
Carrier frequency Motor noise Electrical interference Switching loss
0.7KHz big small small
8.0KHz ↑ ↓ ↓
15.0KHz small big big
Below 4KW: When the carrier frequency is 6 KHz, rated current is the maximum output current.
5.5KW-22KW: When the carrier frequency is 3 KHz, rated current is the maximum output current.
30KW-75KW: When the carrier frequency is 2 KHz, rated current is the maximum output current.
Above 93KW: When the carrier frequency is 1.5 KHz, rated current is the maximum output current.
Note: In order to obtain better control characteristics, the ratio of the carrier frequency to maximum
frequency of the inverter should not less than 36. If inverter works long-term in low frequency, suggest to
reduce the carrier frequency to reduce the impact of the dead zone time.
LED unit Digit: Associate of carrier frequency and output frequency configure.
0: Output frequency associate is disabled.
1: Output frequency associate is enabled.
77
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
When the associate of carrier frequency of output frequency is enable, the inverter will adjust the carrier frequency
automatically according the output frequency, this function can improve the torque performance in low speed, if
combine with torque boost function will make performance better in low speed.
LED tens digit: Associate of carrier frequency and module temperature configure.
0: Module temperature associate is valid.
1: Module temperature associate is invalid.
Inverter will reduce the carrier frequency when the temperature of inverter rise, this function can reduce the
switching loss to prevent over heat fault occurs.
LED hundreds digit: PWM mode selection
0: Fixed PWM mode The noise frequency of motor is fixed.
1: Random PWM mode 1 This mode enables the harmonic spectrum of inverter output voltage evenly distributing in
a wide frequency range to inhibit the electrical noise and vibration effectively, carrier frequency is 2.0KHz.
2: Random PWM mode 2 As the same as above mention, but carrier frequency is 2.5KHz.
LED thousands digit: Inhibition of shock.
0: Inhibition of shock is disabled.
1: Inhibition of shock is enabled.
This function enables output frequency of inverter automatically regulate with the load of motor changing. This can
compensate slip frequency of motor dynamically, it enables the motor maintaining a constant rotation speed to
reduce the load changing impacts on the motor speed effectively.
If cooperate with auto torque boost function, the torque performance in low frequency characteristic of inverter will
be significantly improved. The value of slip frequency compensation should be set base on motor rated slip, should
not set the value of compensation too large.
1: Enable
If only activate the slip compensation function in V/F control mode, this parameters used for selecting slip
compensation function.
LED Hundreds digit: Reserve
LED Thousands digit: Over modulation
0: Over modulation allowed
1: Over modulation not allowed
0: Disable
1: Enable in full process
2: Disable only in deceleration
Output voltage auto regulation function that is AVR function. When AVR function disable, the output voltage change
vary with input voltage. When the AVR enable, the output voltage will keep in setting value as long as the minimum
of fluctuation input voltage bigger than output voltage setting (Motor rated voltage). When the power supply voltage
less than rated output voltage, the output voltage will decrease follow with input voltage.
The jog frequency function has the highest control priority (terminal jog function). It means in any condition, when
jog command is valid, the inverter immediately run from the current running frequency to the jog frequency based
on jog accelerates/decelerates time. The jog accelerates/decelerates time is defined as same as
accelerates/decelerates time, which can be configured by the keyboard, control terminal or job function control
command of RS485.
Note: The setting value of the jog running frequency is only limited by the upper limit frequency. Only the
priority of job terminal control free from limitation of running control command channel. Other jog
command have priority only under the same running control command channel, such as the keypad job
command is enabled only in the operator keypad control running.
Start frequency: The initial output frequency when inverter starting. The large starting torque is available if the
starting frequency is properly set. It can gain high impact when starting instantaneous for some load that has a
bigger static friction force in static status. But it will result in a trip if the value is set to big.
Start frequency holding time: It means the inverter keeps running time under starting frequency.
79
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Note: The frequency output is 0 when the frequency given less than starting frequency during the
acceleration process.
80
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Power off restart waiting time: when the [E-31] setting is valid, inverter starts operation after waiting time [E-32]
when power on again.
The principles of this time setting is base on the factors such as the work resume preparation time of equipments
which correlate with the frequency inverter after power on again.
When inverter receives the stop command under deceleration stop mode, it will decelerate to free stop frequency
base on the deceleration time, and then lock output, motor stop freely.
Note: This function is valid in stop mode only, disable in Forward/Reverse process.
0: Deceleration stop Inverter stop output after decelerate to free stop frequency according to deceleration time
and deceleration mode given.
During the decelerate process, when the frequency given less than starting frequency of DC braking stop, the
output frequency will jump to zero, and perform DC injection braking, after then stop working if the DC injection
braking function is activated.
During the deceleration process, when the DC bus voltage over the [E-53] dynamic braking threshold voltage value,
the inverter will output pulse voltage base on dynamic braking ratio [E-54] setting for built in braking unit model
( through 15G/18.5P), able to connecting external braking resistor. For no built braking unit machine, can connect
external braking unit.
This stop mode mainly used to application which need quick braking required.
1: Free stop After receiving the stop command, frequency inverter will block the output and motor will run to
81
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
stop freely. Generally coordinate external mechanical braking to achieve quick stop when this stop mode has been
selecting.
DC braking voltage: The value of voltage which is injected to motor when executing DC braking function. The
value of voltage benchmark against the input rated current of inverter.
This function can output torque under zero speed. Generally, it uses to improve the stop accuracy and realize quick
stop, but it can’t be apply for normal deceleration. The inverter will stop output once DC braking has been
performed. If the DC raking current set to big, over current fault occurs easily during stop.
DC braking time when stop: DC braking current lasting time when inverter stops, if the braking time is set to 0, it
means the DC braking function is disabled.
DC braking starting frequency when stop It means when inverter decelerated to this frequency, the inverter
will stop output, and perform the DC braking function. If the output frequency less than DC braking starting
frequency when stop during running process, the inverter will stop output, start DC braking function when receiving
the stop command.
The inverter will start DC braking, and the output frequency jump to zero if the frequency given less than DC
braking staring frequency when stop during the deceleration process. The DC braking staring frequency when stop
should be set smaller when there are no strictly requirement for stop. When the DC braking staring frequency when
stop[E-37]parameters setting smaller than free stop frequency [E-33] setting, the inverter will decelerate to free
stop frequency, and then stop output execute DC braking.
DC braking time when start: It refer to DC braking voltage lasting time when stop, Only if [E-30] parameters unit
digit set to 1, the DC braking function will be enabled. When the braking time set to 0.0s, not perform DC braking
function
The Jump frequencies are frequency ranges at which the drive will not operate. The drive can be programmed with
three separate Jump frequencies to avoid operating at speeds that cause resonance in driven machinery. If the
frequency reference falls within a Jump frequency dead band, the drive will clamp the frequency reference just
below the dead band and only accelerate past it when the frequency reference rises above the upper end of the
dead band.
Jump frequency range: The frequency up and own jumping bias base on jump frequency
82
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Setting value
Note: 1. The output frequency still will pass the jumping range during acceleration or deceleration. Make
sure the parameters don't overlap or inset setting.
2. Jumping frequency is disabled for jog, multi-step speed and swing frequency.
Number of automatic fault reset: 0: Disable, The auto reset function is disabled, reset only by manual.
1—3: Enable, 1-3 parameters used for defining the numbers of auto reset. (The maximum time of auto reset is
enabled)
The inverter may be trip to stop cause by fluctuation of grid and other accidents reason during operation. Auto reset
for overload, over current, system abnormal, overvoltage, under voltage. etc fault occurs is allowable to restart
inverter operation ensure system working continuously. Inverter will restart with speed search restart mode during
auto reset.
If the auto reset fails to restart during the setting give numbers, the fault protection will be activate, inverter stop
output. The maximum of auto reset number setting is 3, the reset numbers will be recount after inverter running
normally for 10 minutes, the record times clears automatically. Suggest configure number of auto reset to 1 times
will be better.
The fault output terminal can be set disable or enable during fault auto reset process. Refer to [F-30,F-31,F-32]
Fault auto reset waiting time: Uses for defining the waiting time from fault occurs to reset attempts.
Note: 1. This function only enable for overload, over current, system abnormal, over voltage, under voltage
during running, disable for other fault happen.
2. Reset can’t make if fault fail to solve, no reset for the temperature of inverter over 70℃
Tips: Users must be cautious to consider the start characteristic of the mechanical devices in crane, lifting
application. It should be cautious in using this function for application which can’t start with load or the
alarm will come out immediately when inverter stop output.
Inverter enables command operation after machine warm up time, once power supply switch to inverter. It displays
count down in seconds after switch on.
0: Consistent with the default direction Actual rotation direction is the same with the requirement. The
actual direction don’t change.
83
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
1: Opposite to the default direction Actual rotation direction is opposite to the requirement. The actual
direction will be change.
2: Reverse running forbidden When this parameter is set as prohibition, all the reverse command from
Running control command selection (operator keypad, external terminal, RS485 communication, bipolar VS2 and
program running) are invalid.
The setting will not be modified after the factory default setting.
Note: 1. When the reverse running forbidden is selected, when the bipolar control receiving the reverse
frequency command, the inverter will be operation with 0 speed, the case is the same, inverter will be
operate with 0 speed during program running control if there are some certain step speed reverse direction
are set.
2. All reverse command will be auto turn to running command, running with forward direction.
The function defined the transient waiting time from forward to reverse or from reverse to forward during 0Hz.
FOR/REV dead zone time special designed for big inertia load application which has mechanical dead zone
required.
During the inverter deceleration, the energy generated by motor feedback to inverter inside due to load inertia effect,
which will cause the voltage of inverter over the maximum voltage threshold. The over voltage protecting occurs if
without any measure. When overvoltage protection is activated, the inverter deceleration stops (output frequency
stop descend) when detecting the DC bus voltage over[E-53]setting, deceleration only allow to continue until the
DC bus voltage is lower than the protective value.
Note: It will cause the stop time from deceleration given to stop to be longer if the stall protection is active.
Coefficient value of
E-50 Range:30%-120% Default:0%
electronic thermal
Motor will generate heat seriously in a long time overload running. This parameter is used to set coefficient of
thermal relay of motor in inverter. When the rated current of motor is equal to rated current of inverter, the value can
be set 100%, when the rated current of motor can’t match the rated current of inverter, this parameter value can be
set for motor overheat protection properly.
The factory default setting of overload capacity of inverter as follows:
G type: 150%× rated current for 1 minute.
F type: 120%× rated current for 1 minute.
The parameters setting value can follow below formula:
Coefficient value of electronic thermal=rated current/ rated output current of inverter
Note: This function would fail when one inverter drives multiple motors in parallel. Please install the
thermal relay before motor input to protect motor effectively
85
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
It is used to define the ratio of stall protection current limit to rated current motor.
G type default setting: 160%
P type default setting: 120%
Stalling protecting current limit function means that inverter will limit load current automatically with in time
monitoring during the acceleration, make it lower than the limit setting, (Stops acceleration or lower the output
frequency to achieve the value of output current controlling), to protect big current occurs result in fault alarm trip.
This function is suitable for application where has big inertia or load fluctuates severe particularly.
This parameters datum line is rated current of inverter. It will extend acceleration time longer. It means the current
limit function is activated if the frequency can’t accelerate to set value or frequency given, but fluctuates in the fixed
frequency range. Please reduce the load or adjust the some relevant parameters.
This parameter is defined as the ratio of the stall protection DC bus voltage threshold to rated DC bus voltage of
frequency inverter.
Rated inverter DC bus voltage value=Rated input voltage of inverter×1.414
It defines the over overvoltage stall protecting threshold during the deceleration time. While the DC side pumping
voltage cause by decelerating exceeds this parameter settings, the inverter will auto-prolong the deceleration time.
Decelerating overvoltage suppression threshold voltage: This value is enabled while [E-49] set to 1
Dynamic braking over voltage threshold voltage: The dynamic braking will be activate when the DC bus voltage
rise over than rated voltage of inverter [E-53] setting. The voltage of dynamic braking stop is lower 20V than
[E-53] setting, please make this setting cautiously.
This function is valid for inverter which built in braking accessory only, AC70 series 22G/30 and 30G/37 both
inverters have braking accessory option, standard built in braking accessory through 15G/18P inverter. Please
86
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Ratio of dynamic braking: This parameter defines the average of voltage which applied on the braking resistor
when braking unit effecting. The voltage applied on the braking resistor is PWM wave, the duty cycle is equal to
ratio of dynamic braking. The ratio bigger, energy release faster, the braking effects better, and the same time the
more energy consumes on the braking resistor.
Selecting the braking resistor value, power and braking effects should take comprehensive consideration to set this
parameter.
This parameter defines the DC bus side lower limiter voltage while inverter in normal working condition. It allow to
set under voltage protecting levels lower to ensure inverter normal working for power grid lower situation.
Note: The output torque will be reduced when the power grid voltage is low. For the constant power load
and constant torque load application, the too low power grid voltage will increase input and output current,
which will reduce the inverter ruing reliability.
E-56-E-58 Reserve
It uses to set the display factor of keypad monitor, 100.0% correspond with motor rated speed. The upper limit
machine speed is 65000 RPM.
Ratio of output voltage to rated voltage of inverter. This function uses to coordinate the output voltage to meet
various types of V/F characteristic requirement.
Output voltage of inverter = rated voltage of inverter ×Ratio of inverter output voltage
When reset the factory setting, this parameter setting values will not be changed.
0:G model, it is suitable for constant torque load.
1:P model, it is suitable for variable torque(such as fan, water pump load).
The AC70 series frequency inverter adopts G/P in one mode. The power of the motor adaptability used in the
constant torque load (G model) is lower one grade than that used in fan, water pump load (P model)
This parameter defines the time of inverter try to run stably when inverter detected the frequency point during speed
search process. Inverter accelerates to frequency set point with acceleration time given.
For the big inertia load, extend the speed search stability keeping time can reduce the instantaneous impact current
of speed search start.
87
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Parameters change
E-63 Range:0-2 default: 0
protection
0:All the parameters changing allowed Except for the parameters only for inquiry, any other parameters can be
changed (Note: Some parameters only can be changed in the stop state, some parameters can not be changed in
any condition).
1: Only keyboard digital given parameter changing allowed Except for the keyboard digital given frequency and
keyboard number PID given quantitative parameter, any other parameter don’t allow changing.
2: All the parameters prohibit changing All the parameters of frequency inverter unchangeable; When users
need to change the parameter, They have to change this parameter as 0 or 1.
0: Null
1: Restores to factory default setting value Function parameters will restore to factory default setting after
performed parameters initialization.
2. Clear fault record All historical fault record will be cleared.
3. Transfer parameters of inverter to keypad and save. Copy parameters saved of inverter to keypad and preserve.
4. Transfer parameters saved of keypad to inverter Download parameters of keypad to inverter.
Note:
1. During the inverter running state, Parameters saved of keypad can’t transfer to inverter when in fault
state or no parameters save in keypad.
2. If keypad is pulled out during transferring parameters of inverter to keypad and saving process, this
function will be fail. It need redo parameters copy.
3. If the first part of parameters has been modified, the latter part hasn’t been changed when keypad is
pulled out during transferring parameters copy of keypad to inverter. This function need redo again.
4. The current running state of inverter will not be stored in parameters of inverter transfer to keypad
operation. All keypad are null and invalid when transferring the parameters saved of keypad to
inverter.
5. When E.CPE (parameters copy abnormal) appears on the keypad in parameters copy operation, the
copy is stopped at this moment. It need redo copy again with pressing PRG button return to monitor
state.
6. The parameter saved of keypad can’t be transfer to inverter if the version is incompatible with E.EDI
display.
Note: The current setting value of [E-46, E-61]will not be affected when performing the factory default
restoring. The setting value 3 or 4 of [E-64] parameters will be set to 0 automatically after parameters copy.
88
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
0: Null operation
1: State monitoring inquiry Selects this function to enter monitoring menu(group C parameters),and inquire
each state parameters of the frequency inverter. In the monitoring state, with long pressing (1 second) PRG key
and enter directly the state of the group C parameters that is status of state monitoring inquiry.
Monitoring Communication
Content Unit
code cod
C-01 Frequency reference given 0.01Hz C01H
C-02 Output frequency 0.01Hz C02H
C-03 Output current 0.1A C03H
C-04 Input voltage V C04H
C-05 Output voltage V C05H
C-06 Machine speed RPM C06H
C-07 PID given value % C07H
C-08 PID feedback value % C08H
C-09 Module temperature ℃ C09H
Accumulative running time ( the total timing of
C-10 output frequency which large than 0Hz, 0Hz Hour C0AH
running and stop status timing is disabled )
C-11 Accumulative running timing after last power on Minute C0BH
C-12 Output current percentage % C0CH
C-13 Multi-Step operation remainder time percentage % C0DH
C-14 Input terminals OFF/ON status Refer to below table C0EH
C-15 Output terminals OFF/ON status Refer to below table C0FH
C-16 Terminal VS1 input value 0.1V C10H
C-17 Terminal AS input value 0.1mA C11H
C-18 Terminal VS2 input value 0.1V C12H
C-19 Terminal pulse input value ※ C13H
C-20 Counter record ※ C14H
C-21 DC bus voltage V C15H
C-22 Analog output A01 ※ C16H
C-23 Frequency/voltage/current outputA02 ※ C17H
C-24 Reserve -- C18H
C-25 Inverter rated power kW C19H
C-26 Inverter rated voltage V C1AH
C-27 Inverter rated current 0.1A C1BH
C-28 Software version ※ C1CH
89
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
90
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Er.08 Running direction while the latest fault 0.Forward 1.reverse E08H
0. Stop 1. Constant running
Er.09 Running status while the latest fault E09H
2. Acceleration 3. Deceleration
0. Normal 1. Only voltage amplitude limit
Er.10 Protection status while the latest fault 2. Only current amplitude limit 3. Both E0AH
voltage and current amplitude limit
Er.11 Input terminal status while the latest fault See above table E0BH
Output terminal status while the latest
Er.12 See above table E0CH
fault
Er.13 The latest first fault information E0DH
91
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Interference suppression
E-67 Range:0000-1221 Default:0001
selection
92
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Defines the control digital terminal function, it is enabled when short connecting ON with COM terminal.
Setting
Definition Function description
value
0 Invalid(check optional is available) This port is free
1 Forward jog operation Jog command input port. Terminal jog commands
2 Reverse jog operation have the highest priority.
5 Multi steps speed control 1 The multi steps speed commands input port, up to
6 Multi steps speed control 2 8 steps speed control is available; The multi steps
7 Multi steps speed control 3 speed commands has priority only next to the jog
93
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
1: Two wire running control mode Running and direction are separated. Uses the forward running terminal X1
(forward running) to determine running control, reverse running terminal X2 (reverse running) to determine direction
control. Refer to below fig.
2. Three wire control mode 1 Three wire control terminal (Xi) is used for stop running terminal. Running
command determined by forward running terminal X1 (forward running), direction determined by reverse running
terminal X2 ( reverse running). 3 wire running control terminal Xi is used for enable input.
95
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Tip: In 3 wire control mode 1 Fig, SB1 is a normal close stop button, SB2 is a normal open button. K1 is a
direction selection switch; Xi is multi-function terminal (X1-X6) which have been programmed for 3 wire
running control terminal.
3: 3 wire control mode 2 In this mode, 3 wire running control terminal (Xi) is used for stop running terminal, the
running command is generated by forward running terminal X1(forward running) or reverse running terminal
X2( reverse running ), also control the direction at the same time.
Tip: In 3 wire control mode 2 Fig, SB1 is a normal close button, SB2 and SB3 both are normal open button
and pulse edge is valid, uses for inverter direction control.
4: 3 wire control mode 3 3wire running control terminal (X1) is used for running command given terminal,
running in connecting ON, stop in disconnecting OFF. Rotation direction is determined by forward running terminal
X1 ( forward running) or reverse running terminal X2( reverse running). Every staring running with last time direction
memorized
Tip: 1. SB2 and SB3 both are normal open button, and enable by pulse edge.
2. If need start motor in forward direction, press the K1 first, and press SB2 immediately.
96
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
3. If need start motor in reverse direction, press the K1 first, and press SB3 immediately.
5: 3 wire control mode 4 3 wire running control terminal (X1) uses for stop command terminal, running
command is determined by forward running terminal X1 (forward running), direction is controlled by reverse running
terminal X2( reverse running), and direction will be change after every Xi is activated. Every starts running based on
last direction memorized. 3 wire running control terminal X1 for effective input.
Tip: SB1 is a normal stop button, SB2 is a normal open button. K1 used for running direction selection
button. Xi is multi-function terminal (X1-X6) which have been programmed for 3 wire running control
terminal.
LED ten digit: Reserve
LED hundred digit: Reserve
LED thousand: Reserve
Uses for setting program running and multi-step speed running frequency separately.
Multi-step speed control has the priority only next to the jog function. If users choose the multi-step speed running
mode, they need to set four multi-function input terminals as multi-step control terminal. ON/OFF between the four
terminals and (COM) determine the running speed steps. Its running and direction is controlled by the running
signal and direction given by the running control command channel [E-01]. And its acceleration, deceleration time is
controlled by the acceleration, deceleration time 1 in default. Or specifies the particular acceleration, deceleration
time by [F-01]-[F-06] parameters setting.
Swing frequency control need to configure the [F-09] and [F-10], refer to [H-51]parameters for the requirement
setting of [F-09] and [F-10]. Inverter will appear fault alarm “Err5” if wrong setting.
Tip 1. Multiple step speed running don’t limited by lower limit frequency, but subject to upper limit frequency.
2. Output of program running is subject to limit by upper and lower limit frequency. Inverter will run with lower limit
frequency when the frequency given less than lower limit frequency.
97
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Short connecting with COM stands for ON, disconnecting for OFF
Terminal
Multi-step control Multi-step control Multi-step control Multi-step control
Step
terminal 4 terminal 3 terminal 2 terminal 1
Speed
OFF OFF OFF ON 1X
OFF OFF ON OFF 2X
OFF OFF ON ON 3X
OFF ON OFF OFF 4X
OFF ON OFF ON 5X
OFF ON ON OFF 6X
OFF ON ON ON 7X
ON OFF OFF OFF 8X
F-17-F-18 Reverse
This group parameters will be use in software speed search mode. Software speed search will detect out the motor
speed from current, and stores voltage based on [F-20] voltage stores time under upper limit frequency or given
frequency. When the output current bigger than [F-21], inverter will lower the output frequency with [F-19] speed
search speed tracking. When the current lower than [F-21] and maintain [E-62] time setting, it judges the output
frequency and motor speed is synchronous, will accelerate or decelerate to frequency reference given. Software
speed search processing schematic as following tale:
Note: The motor may decelerate suddenly when drive a light load.
Frequency reducing accel/decel. time: When parameters[E-67] is set to “2****”, inverter will reduce frequency
98
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
to protect over current occurs when load fluctuates suddenly. This parameter is used to define the acceleration
/deceleration time of frequency reducing.
Acceleration time 2/3/4: When the [E-15] LED ten digit is set to 0, this refers to requirement time of accelerate
from 0.00Hz to maximum frequency [E-09]. When the [E-15] LED ten digit is set to1, this refers to requirement time
of accelerate from 0.00Hz to motor rated frequency [H-53]. Refers to [E-15] parameters in detail.
Deceleration time 2/3/4: When the [E-15] LED ten digit is set to 0, this refers to requirement time of decelerates
from maximum frequency [E-09] to 0.00Hz. When the [E-15] LED ten digit is set to 1, this refers to the requirement
time of decelerates from motor rated frequency [H-53] to 0.00Hz. Refers to [E-15] parameters in detail.
Note: 1. It need to program the acceleration, deceleration time 2 during in UP/DW control ruing, refers to
[E-02] in detail.
2. It need to program the acceleration, deceleration time 2 during swing frequency control, refers to
[H-65] parameters in detail.
3. In program running mode, defines acceleration/deceleration time from 2 to 4 separately. Definition
of the acceleration /deceleration time is the same as Accel./Decel. time 1. The Accel./Decel time are
configured by [H-35]-[H-49] parameters.
4. Acceleration/deceleration time of multi-step speed are programmed by [F-01]-[F-06]. The default
setting is acceleration/ deceleration time 1.
Setting
Definition Function description
Value
Zero frequency (
0 Output signal when inverter is running and output frequency is 0 Hz,
standby state)
Output signal when fault alarms happening (including OU, OL, SC,
1 Fault alarm 1
OC, OH, LUS, etc), enable output including fault reset auto period
Output signal when fault alarms happening (including OU,OL,SC,OC,
2 Fault alarm 2
OH,LUS, etc), disable during fault auto reset period.
When the output frequency is approaching or arriving to the frequency
Frequency arriving
3 given bias range, outputs valid signal, otherwise output invalid signal.
detection
The bias range is determined by the parameter [F-33].
When the output frequency over than frequency detecting level [F-34]
Frequency level setting, output valid signal after [F-35] relay time setting. When the
4
detection output frequency lower than frequency detecting level, output a invalid
signal after the same [F-35] relay time setting.
99
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
100
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
When output frequency approaches or close to frequency reference given value, output terminal outputs signal.
[F-33] function uses to adjust the bias of the detection amplitude.
Output frequency level detection: Uses it to program the frequency detection level, when the output frequency
high [F-34] setting value, output terminal will output signal after [F-35] setting relay time. When the output
78frequency low to than [F-34] setting value, output terminal will stop output signal after [F-35] setting relay time.
If the output current continues to be over the setting level of the parameter [F-36], after the delay time [F-37], the
output terminal outputs valid signal. In the same way, when the output current is lower than the setting level of
[F-36] ,after the delay time [F-37] , the output terminal outputs invalid signal.
output current
detection level
delay time
delay time
OL pre-alarm
output signal time
OL pre-alarm
This parameter is used to timing for the frequency inverter. The timer start-up is activated by the external trigger
terminal of the timer(trigger terminal is selected by [F-01-F06]). Timing from receiving the external trigger signal,
while reaching the timed time, it outputs a width is 1 second pulse signal by the corresponding output terminal.
If the external trigger signal always locate trigger condition, the corresponding terminal outputs a pulse signal every
[F-38] setting time.
101
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
This parameter stipulate the counting action of the interior counter, clock terminal of the counter is selected by the
parameter [F-01-F-06].
When the count value to the exterior clock reaches [F-39] setting value, in the corresponding output terminal, it
outputs a valid signal with a width equal to exterior clock cycle. The output signal stops while the next count signal
is input.
When the count value to the exterior clock reaches [F-40] setting value, in the corresponding output terminal, it
outputs a valid signal. While it reached [F-39] and the counter clear to zero, this output valid signal abolishes.
The clock cycle is required to be greater than 10 ms; And the minimum pulse width is 5ms.
VS1 terminal input voltage lower limit This function defines the minimum signal of the analog input terminal
(VS1)receiving. Frequency inverter will automatically filter the voltage signal whose value is lower than this value.
VS1 terminal input voltage upper limit This function defines the maximum signal of the analog input terminal
(VS1)receiving. Frequency inverter will automatically filter the voltage signal whose value is higher than this
value.
VS1 terminal input voltage gain This function is used to amplify or reduce the (VS1) terminal input analog
value.
102
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
VS2 terminal input voltage lower limit This function defines the minimum signal which received by the analog
input terminal (VS2). Frequency inverter will automatically filters the voltage signal whose value is lower than this
value.
VS2 terminal input voltage upper limit This function defines the maximum signal which received by the
analog input terminal (VS2). Frequency inverter will automatically filter the voltage signal whose value is higher than
this value.
VS2 terminal input voltage gain S2 This function is used to amplify or reduce the (VS2) terminal analog value.
VS2 terminal input zero offset This function is used to adjust the (VS2) terminal zero point in the bipolar
control mode; Its adjustment direction is opposite to the actual zero point. If the actual input voltage is +0.5V, at this
moment, users should set the zero offset as-0.5V to let the voltage corresponding to the zero voltage (only valid
when [F-48] is set as 1 or 2)
103
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
F-57 corresponding
frequency
frequency
lower limit
input voltage
F-56 corresponding
frequency
F-57 corresponding
Frequency
frequency
Lower limit
input voltage
Upper limit
input voltage
F-57 corresponding
frequency
VS2 bipolar control diagram
Tip: When (VS2) is used as PID given or feedback channel, the function of bipolar is invalid. At this moment,
the usage of (VS2) terminal is the same with the (VS1) terminal. Namely, when (VS2) <0, frequency inverter
think the input of this port is 0.
AS terminal input
F-50 Range: 0.00mA-[F-51] Default: 4.20mA
current lower limit
AS terminal input
F-51 Range:[F-50]-20.00mA Default: 19.50mA
current upper limit
AS terminal input current
F-52 gain Range: 0.01-5.00 Default: 1.00
AS terminal input current lower limit This function defines the minimum signal which received by the analog
input terminal(AS),frequency inverter will automatically filters the current signal whose value is lower than this value;
For example, if the factory setting of this value ‘4.00’,4.00-20.00mA input current is available.
AS terminal input current upper limit This function defines the maximum signal which received by the analog
input terminal (AS), frequency inverter will automatically filters the current signal whose value is higher than this
value.
AS terminal input current gain This function is used to amplify or reduce the (AS) terminal.
104
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
F-53 Pulse input frequency lower limit Range: 0.0KHz-[F-54] Default: 0.0KHz
F-54 Pulse input frequency upper limit Range:[F-53]-50.0KHz Default:10.0 KHz
F-55 Pulse input frequency gain Range: 0.01-5.00 Default: 1.00
Terminal input frequency lower limit This function defines the minimum frequency received by the analog
input terminal (PUL). Frequency inverter will automatically filter the frequency whose value is lower than this value;
Terminal input frequency upper limit This function defines the maximum frequency received by the analog
input terminal (PUL). Frequency inverter will automatically filter the frequency whose value is higher than this value.
Terminal input frequency gain This function is used to amplify or reduce the (PUL) terminal input signal.
These two parameters stipulate the corresponding relation between the external input analog value, upper/lower
limit of the pulse signal and frequency.
105
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
frequency frequency
This is defined as the size of the input analog quantity signal filtering, for the purpose of eliminating the interference
signal. The longer filtering time is, the stronger anti-interfere ability is, but the respond speed slow down; The
shorter filter time is, the weaker anti-interfere ability is, but the respond speed become faster;
Tips: when (AO2)port is frequency pulse output or 4-20mA output, ‘0%’ corresponding output quantity is
not zero.
106
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Used to adjust AO1 terminal output analog value and AO2 output signal value.
F-65 AO1 output signal zero adjust Range : -10%-10% Default: 0.0
F-66 AO2 output signal zero adjust Range : -10%-10% Default: 0.0
Used to adjust the output signal zero point of (AO1) terminal and (AO2) terminal. It is invalid to adjust this value
when (AO2) is frequency pulse output.
Keypad potentiometer input voltage lower limit This function defines the minimum signal received by the
keyboard potentiometer. Frequency inverter will automatically filters the signal whose value is lower than this value;
Keypad potentiometer input voltage upper limit This function defines the maximum signal received by the
keyboard potentiometer. Frequency inverter will automatically filters the signal whose value is upper than this value.
Keypad potentiometer gain This function is used to amplify or reduce keyboard potentiometer input analog
quantity.
Tips: Keypad potentiometer input voltage upper limit is corresponding to frequency upper limit [E-10] ,
Keyboard potentiometer input voltage upper limit is corresponding to 0.00 Hz.
107
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
The starting frequency output when inverter runs in UP/DW control mode. It is enabled only [F-07] LED ten digit
has been set for 1 or 2 .
When the [F-07] LED ten digit sets for 1, [F-71] parameters will memorize the last UP and DOWN control
momentary frequency. User can review and modify the last stop momentary frequency via [F-71] in stop status.
When the [F-07] LED ten digit sets for 2, the starting frequency can be preset via [F-70] parameters in UP/DW
control.
8.3. Special Function Parameters
V1: 3%
Output voltage F1: 1.00Hz
V2: 28%
V5
F2: 10.00Hz
V4 V3: 55%
F3: 25.00Hz
V3 V4: 80%
F4: 37.50Hz
V2 V5: 100%
F5: 50.00Hz
V1
F F F F F Output frequency
108
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
V1, V2, V3, V4, V5 is base on the frequency rated output voltage
PID control is a common method used in the process control. The output frequency is adjusted via a series of
proportion, integral, differential calculation of difference value between feedback value of controlled object and PID
given value, make up a negative feedback PID adjustment to achieve a goal which controlled objected stabilizes on
the PID given value.
0: Positive characteristic Suitable for occasions where maintains the PID balance by reducing the
frequency inverter output frequency while the PID feedback quantity is greater than PID given value. Such as apply
in constant pressure water supply, gas supply and tension control of winding application.
1: Negative characteristic Suitable for occasions where maintains the PID balance by increasing the
frequency inverter output frequency while the PID feedback value is greater than PID given value. Such as apply
in central air-conditioning constant temperature control and tension control of unwinding.
While frequency inverter receiving the operation command, frequency inverter will automatically control output
frequency after calculating for the given signal and feedback signal of the terminal according to the PID setting
control mode.
While the PID controls to cancel the terminal connection, frequency inverter will convert the given signal to output
frequency directly without PID control.
0. External terminal VS1 Set by the external terminal (VS1) (0V-10V) analog signal.
1. External terminal AS Set by the external terminal (AS) (4-20mA) analog signal.
2. External terminal VS2 (bipolar invalid) Set by the external terminal (VS2) analog signal.([F-48] can’t be set
for 1 or 2) .
3. External pulse signal Set by the external terminal (PUL) pulse frequency signal.
Note: PID controller given signal source and PID controller feedback source can’t be set in the same
channel, otherwise PID is disabled.
109
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
This function make frequency inverter accelerate to PID preset frequency [H-14] with acceleration time 1 after PI
operation starts, and will keep running for PID preset frequency running time [H-15] given, and then executes the
PID close loop operation.
Frequency
preset
frequency
Time
preset frequency
running time
PID preset frequency running time diagram
Only when [H-12] parameters is set for 1,this parameter is valid. Take the sensor maximum measuring range [H-18]
as a benchmark. When this parameter is changed, PID given value of monitoring target will automatically
synchronize change.
This function is used to amplify or reduce the input analog value of feedback channel
This function is used to adjust the display data of PID given value and PID feedback value.
Actual LED display value= given (feedback) signal - lower input limit × sensor largest range
Upper input limit-lower input limit
For example in pressure control, if it is set for sensor maximum pressure, the display value is actual pressure value.
Assumes that take external terminal (VS1) for feedback single input channel, when VS1 upper limit voltage is 9V,
the lower limit is 0.5V, the present feedback voltage is 4.5V, the maximum sensor measure range is 20mpa.
LED display value =(4.5-0.5)×20/(9-0.5)=9.4mpa
110
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Adjusting parameters in PID control function, these parameters should be set according to actual system
characteristic in respectively.
Proportion gain P: This parameter determines the impact degree of Proportion gain P respond to deviations.
When gain is large, it responds quickly, but would bring out oscillation. When gain is small, respond will delay.
Integral time constant I: It decides the size of respond effect for Integral time I. When the integral time is big, the
respond is slow, In addition, anti-external interference is become weaker. If the integral time is small, the respond
speed is quick. But oscillation would occur if it is set too small.
Differential gain D: When the deviation of PID feedback value and PID given value changes, The output and the
change rate of deviation are proportionally adjusted. This adjustment is only related to the direction and size of the
deviation change and has nothing to do with the direction and size of the deviation itself. While the feedback signal
changes, differential adjustment is used to adjust according the change trend to restrain the change of feedback
signal. Please be careful to use the differential adjustment. Because it will amply the system interference, especially
for a higher changing frequency interference.
This parameter is only valid for the sampling period of feedback value. The regulator will calculates a time in every
sampling period. The small sampling period, the quicker respond time.
The maximum deviation allows for PID feedback value to PID given value. PID will be stop, keep output constant
when the feedback value within this deviation range. It will coordinate the contradiction between the accuracy of
system output and stability with using this function properly.
Starting threshold value: When inverter goes into sleep mode, inverter restarts should require PID feedback value
less than starting threshold value setting. If the the starting threshold value is set too high, inverter will start and
stop frequently. If it set too low, it will cause pressure not enough. This parameter is defined as percentage of PID
feedback value to sensor maximum measuring range account for.
111
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Sleep threshold value: This parameter use as a standard value for adjusting system if go to sleep mode when no
need working. It is that inverter always standby for sleep detecting, if PID feedback value higher than or equal to
PID given setting value is detected, and try to keep holding for a while in setting value around, inverter will start
sleep detecting. If the feedback value higher than sleep threshold value during the sleep detecting mode, inverter
will reduce the output frequency to lower limit frequency, and keep outputting lower limit frequency for a while, and
then reduce to 0Hz, go into sleep mode. If feedback value lower to sleep threshold during above process, sleep
detecting will be disable, go back to PID adjusting working. Smaller setting of this parameter, system will go to sleep
mode easier. When it is set for 100.0%, the system will not go to sleep mode.
This parameter is defined as percentage of PID feedback value to sensor maximum measuring range account for.
This function only is enabled in constant pressure PID control.
H-26 Alarm upper limit value Range: Alarm lower limit value-100.0% Default: 100.0%
H-27 Alarm lower limit value Range: 0.0%-Alarm upper limit value Default: 0.0%
While PID feedback reaches or exceeds the setting value, if any output terminals [F-30-F-32] is set as 15, (PID
feedback value upper limit alarming), it outputs alarm signal; This parameter is defined as percentage of the
maximum measuring range of the sensor that the PID feedback value accounts for.
While PID feedback reaches or under the setting value, if any output terminals [F-30-F-32] is set as 16, (PID
feedback quantity upper limit alarming), it outputs reaching signal; This parameter is defined as percentage of the
largest range of the sensor that the PID feedback quantity accounts for.
This function only is enabled in constant pressure PID control.
When the frequency inverter is in the PID control mode, this function is valid; If the detection feedback signal is less
than [H-28], the sensor is deemed to be open circuit. At this moment ,if any one of output terminal [F-30-F-32] is set
as‘17’ (sensor disconnect), the output signal is valid; This parameter is defined as the percentage of the sensor
maximum range that the feedback signal accounts for.
Sensor disconnection alarm running selection
0:Continuous operation
1:Close down
In the process of PID adjustment, while system detects sensor open circuit, this parameter is used to choose
whether frequency inverter stop working. If choose working on ,frequency inverter will cancel closed-loop control,
with PID given values as frequency output; If choose close down, when the system detects the alarm which is
mentioned above, the inverter will stop output and display the malfunction information immediately.
The feedback sensor malfunction is displayed as "SEn". When it detects the PID feedback quantity is greater than
the setting of [H-28], the feedback sensor fault is deemed to be vanish, and system restores PID closed-loop
control.
H-30 Upper limit threshold Range: lower limit threshold-100.0% Default: 100.0%
H-31 Lower limit threshold Range:0.0%-upper limit threshold Default: 0.0%
This parameter will limit PID given during upper limit threshold and lower limit threshold range. This parameters is
defined the ratio of upper limit threshold, lower limit threshold to maximum measuring range. This function only is
enabled in constant pressure PID control.
112
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
The acceleration/deceleration time are selected by parameter [H-35-H-42]; Run time is up to parameter [H-43-
H-50]; The time unit is second. While the first step time up, it shifts to the next step speed. The time, direction,
acceleration/deceleration time of each step speed can be programmed; While finishing the 8th section speed
running, frequency inverter will output "0" frequency. If one step running time is set to zero, it will skip over this step.
1. Continuous cycle running (time by second)
After the frequency inverter finishing 8th section speed running, return to the 1st step speed to begin to work for
uninterrupted cycles. Running direction and acceleration/deceleration time are selected by the parameter
[H-35-H-42]; Run time is set up by parameter [H-43-H-50], the time unit is second.
2: single cycle, continuous running (time by second)
After finishing a single cycle running, the frequency inverter running don’t stop. It works on at the final step speed
whose running time is not zero. Running direction and acceleration/deceleration time are selected by the parameter
[H-35-H-42]; Run time is set up by parameter [H-43-H-50], the time unit is second.
3. Single cycle running (time by minute)
Direction and acceleration/deceleration time are selected by parameter [H-35-H-42]; Running time is set up by
parameter [H-43-H-50]; The time unit is minute. The others are identical with mode ‘0’.
4: continuous cycle (time by minute)
Running direction and acceleration\deceleration time are selected by the parameter [H-35-H-42]; Running time is
set up by parameter [H-43-H-50]; The time unit is minute; The others are identical with mode ‘1’.
5: Single cycle, continuous running (time by minute)
Running direction and acceleration/deceleration time are selected by the parameter [H-35-H-42]; Running time is
set up by parameter [H-50-H-50]; The time unit is minute; The others are identical with mode "1"
Output frequency
14X
4X
........ 15X
3X
2X
1X
Time
........
T1 T2 T3 T4 T14 T15
Single cycle
Output frequency
14X
4X
........ 15X
3X 3X ...
2X 2X
1X 1X
Time
........ ...
T1 T2 T3 T4 T14 T15 T1 T2 T3
Continuous cycle
2X
1X
Time
........
T1 T2 T3 T4 T14 T15
113
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
In the program running, use to set 8 steps rotation direction and acceleration /deceleration time respectively.
Setting code Description
0 Forward; Acceleration time 1/Deceleration time 1
1 Forward; Acceleration time 2/Deceleration time 2
2 Forward; Acceleration time 3/Deceleration time 3
3 Forward; Acceleration time 4/Deceleration time 4
4 Reverse; Acceleration time 1/Deceleration time 1
5 Reverse; Acceleration time 1/Deceleration time 2
114
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Use to set 8 steps speed running time, unit of time is set by [H-32] parameters.
During the swing frequency operation, the FOR/REV switching function will be forbidden, running direction is
programmed after stop only. f1 is the setting value of [F-09]; f2 is the setting value of [F-10]; Acceleration time T1 of
the amplitude is the setting value of [F-24]; And the acceleration time T2 of the amplitude is the setting value of
[F-25].
The acceleration/deceleration time in swing frequency running is defined by acceleration/deceleration time 1. When
using the swing frequency running function, frequency inverter will run with the acceleration/deceleration time 1 to
the f1 setting frequency, then begin swing frequency running. While stop, frequency inverter will run for
acceleration/deceleration time 1 from the running frequency to stop. Acceleration/deceleration time of the amplitude
is defined by acceleration/deceleration time 2. It is defined as the same as acceleration/deceleration time 1.
The parameter settings in the swing frequency running should satisfy the following formula request, otherwise
display "Err5".
f1>f2+ᇞf
f2≥0.50Hz
0≤ᇞf≤20.00Hz
Output frequency
swing frequency f1
f f f
swing frequency f2 f f f
Time
115
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
[H-52] uses to set motor rated power, unit is 0.1kw. Refer to motor nameplate to configure this parameter. Inverter
will automatically select corresponding default value as [H-53-H-61] default value after every changing of this
parameter. [H-57-H-61] parameters will be modified after motor auto tuning when highly accuracy motor control is
required. The motor parameters [H-52-H-56] must be set properly before perform motor auto tuning.
[H-63-H-65] parameters use to adjusting the motor magnetic saturation in vector control mode, improve the motor
overload capacity and rung stability.
116
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION
Uses to define communication address of local machine when it has been set for slave one. It makes no sense if it
is set for main inverter.
0:1200bps
1:2400bps
2:4800bps
3:9600bps
4:19200bps
5:38400bps
Communication setting
H-70 Range:0.01-5.00 Default:1.00
frequency ratio
Take frequency reference from upper controller multiply this parameter for this machine frequency reference.
Modification with proportional scale for given frequency from upper controller is available.
If the interval time between a communication and the next communication exceeds communication overtime time, it
is considered there is communication disconnection fault, malfunction disconnection action mode is decided by the
[H-72].
RS485 communication
H-72 Range:0-2 Default: 1
broken responding mode
command .
2. No alarm but stop When the inverter setting given communication command doesn’t receive next frame
command or any other communication command respond over [H-17] given time, inverter stop running.
LED “00” digit: Communication write operation mode.
0: Reply for write operation
1: No reply for write operation
LED “000” digit:: Reserve
LED “0000” digit: Reserve
Note: When inverter has been set for main machine, don’t perform RS485 communication broken checking.
This parameter defines the intermediate interval time between the frequency inverter receiving the data and
responding data back to the upper control. If the response delay time is shorter than the system handling time, the
response time should according to the system; If the response delay time is longer than the system handling time,
after system processing the data, it waits until the response delay time is up, then sends data to the upper
controller.
This function enable frequency inverter reducing the output frequency when power fails instantaneous or voltage
lower suddenly, compensate voltage lowed with energy feedback from load, to maintain inverter continue running in
shortly.
When the input voltage lower to [H-74], inverter will start to reduce speed and DC bus voltage rise. When the input
voltage recovers to [H-75], speed reducing will stop. When the current speed keep stable running after [H-77]
setting time, inverter will accelerate to frequency reference given.
[H-76] is defines as deceleration gain, the bigger setting, the quicker voltage rising, which suitable for small inertia
load. If this parameters is set for small, the voltage recovery rising slowly, which suitable for big inertia.
This parameters is valid only in vector control mode, uses for controlling the torque compensation upper limit. Take
the rated inverter voltage as reference benchmark for compensation voltage.
H-80 Reserve
118
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
Appendix 1: Appendix
9.1 Appendix 1: Function Code Simple List
●
“ ”: Stand for this parameter can be modified in running mode.
“〇”: Stand for this parameter can not be modified in running mode.
“×”: Stand for this parameter is read only, can’t be modified.
“–”: Stand for factory authority parameters. Veichi setting is available only.
“※”: Stand for this parameter is related to frequency inverter model.
Basic function code group
pr Comm
Refe
Code Factory op unicati
Function name Setting range and definition r to
function default ert on
y page
code
0: Open loop vector control without
E-00 Control method selection PG 1 〇 69 100H
1: V/F control mode
0: Operator keypad
Running control command 1: External terminal control
E-01 2: RS485 Communications port 0 〇 69 101H
channel selection
control
0: Operator keypad digital given
1: Potentiometer of keypad
2: Terminal VS1 analog voltage
0-10V
3: Terminal AS analog current
signal 4-20mA
4: Terminal VS2 analog voltage
Frequency reference
-10-10V
E-02 given main channel 1 〇 69 102H
selection 5: Pulse train signal
6: RS485 communication port
7: Up and Down control
8: General PID operation
9: Constant pressure PID control
10: Program running
11: Swing frequency run
12: Terminal selection:
0: Operator keypad digital
1: Potentiometer of keypad
2: Terminal VS1 analog voltage
0-10V
3: Terminal AS analog current
Frequency reference signal 4-20mA
4: Terminal VS2 analog voltage
E-03 given auxiliary channel -10-10V 0 〇 71 103H
selection 5: Pulse train signal
6: RS485 communication port
7: Up and Down control
8: General PID operation
9: Constant pressure PID control
10: Program running
119
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
Frequency reference
E-04 given channel gain 0.01-5.00 1.00 〇 72 104H
0: Main channel is valid, auxiliary
channel is invalid.
1: Auxiliary channel valid,main
channel invalid
2: Both channel is valid if non zero
value, main channel priority
3: Main channel + K×auxiliary
channel)
4: main channel -(K×auxiliary
Frequency reference channel)
E-05 given channel 5: MAX [main channel , 0 〇 72 105H
(K×auxiliary channel)]
combination mode 6: MIN [main channel , (K×auxiliary
channel)]
7: Auxiliary channel + (K×main
channel)
8: Auxiliary channel - (K×main
channel)
9: MAX [(K×main channel),
auxiliary channel]
10: MIN [(K×main channel),
auxiliary channel]
0: Frequency Given
Upper LED monitor
E-06
selection
1: Output frequency 0 ● 72 106H
2: Output current
3: Input voltage
4: Output voltage
Lower LED monitor 5: Machine speed
E-07
selection
1 ● 72 107H
6: PID given given
7: PID feedback value
REV/JOG key of keypad 0: Reverse
E-08
function selection 1: Jog
0 ● 73 108H
120
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
121
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
122
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
125
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
126
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
Frequency reducing
F-23
acceleration time
0.1-6500.0s 0.3s ● 98 217H
127
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
128
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
AS terminal input
F-51
current upper limit
[F-50] - 20.0mA 19.50mA ● 104 233H
129
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
130
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
Keyboard potentiometer
F-67 Input voltage lower limit
0.00V - [F-68] 0.20V ● 107 243H
Keyboard potentiometer
F-68 Input voltage upper limit
[F-67] - 5.50V 4.80V ● 107 244H
Keyboard potentiometer
F-69 gain
0.00-5.00 1.00 ● 107 245H
131
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
Sensor maximum
H-18
measuring range
1.0-100.0 100.0 ● 110 312H
H-30 Upper limit threshold lower limit threshold-100.0% 100.0% ● 112 31EH
H-31 Lower limit threshold 0.0%-Upper limit threshold 0.0% ● 112 31FH
0: Single cycle running (time by
second)
1: Continuous cycle running
2: single cycle, continuous running
(time by second)
H-32 Program running mode 3: Single cycle running (time by 0 〇 112 320H
minute)
4: Continuous cycle (time by
minute)
5: Single cycle, continuous running
(time by minute)
0: Running at the first step speed
1: Continue to run with breakpoint
Program run breakpoint running frequency and retiming.
H-33 0 〇 114 321H
restore mode selection 2: Continue to run with the
breakpoint running frequency and
residual time.
Program running state
H-34 power down memory 0: NO power down memory 0 114 322H
〇
selection 1: power down memory
1 step speed direction and 0: Forward; Acceleration time
H-35
accel/decel time 1/Deceleration time 1
0 ● 114 323H
2 step speed direction and 1: Forward; Acceleration time
H-36
accel/decel time 1/Deceleration time 2
1 ● 114 324H
3 step speed direction and 2: Forward; Acceleration time
H-37
accel/decel time 1/Deceleration time 3
2 ● 114 325H
4 step speed direction and 3: Forward; Acceleration time
H-38
accel/decel time 1/Deceleration time 4
3 ● 114 326H
5 step speed direction and 4: Reverse; Acceleration time
H-39
accel/decel time 1/Deceleration time 1 4 ● 114 327H
132
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
Differential frequency
H-51
∆f in swing frequency
0.00-20.00Hz 2.00Hz ● 115 333H
0: Null operation.
H-62 Motor auto tuning selection 1: Rotational motor auto tuning. 0 〇 116 33EH
2: Stationary auto tuning
Motor magnetic saturation
H-63
coefficient 1
0-9999 ※ ● 116 33FH
133
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
134
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
One frame message must be transmitted as a continued data flow. If there is a pause over 1.5 byte before the end, the
receiving equipment will clear the half-baked information. And the next byte will be considered as the address domain of
135
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
a new frame. Similarly, if the interval between a new frame start-up and the former frame is smaller than 3.5 byte time,
the receiving equipment will think that it is the former one frame continuation. Because of the jumbled frame, finally
CRC checking value is incorrect, what leads to the communication mistake.
RTU frame’s standard structure:
Frame START Transmission time of 3.5 bytes
Communication address:
Slave machine address
0~247(decimal)(0 is broadcast address)
03H:read slave machine parameter
Function code CMD 06H: write slave machine parameter
08H:circuit auto-detection
Data domain
DATA(N-1)
parameter address, parameter number, parameter values ,
…
DATA(0)
CRC CHK low-order
Detecting value:16 bit CRC check value
CRC CHK high-order
Frame ending transmission time of 3.5 bytes
5.2 Order code and communication data description
5.2.1 Order code:03H, read N word (can continue reading 5 words at most)
For example:A frequency inverter who is slave machine with address 01 H and memory initial address 0101H([E-01])
reads 3 words continuously. Then the structure of that frame is described as follows:
RTU host machine order information
START Transmission time of 3.5 bytes
Slave machine address 01H
Order code 03H
Start address high-order 01H
Start address low-order 01H
Data number high-order 00H
Data number low-order 03H
CRC CHK low-order 55H
CRC CHK high-order F7H
END Transmission time of 3.5 bytes
RTU Slave machine responding information (normal)
START Transmission time of 3.5 bytes
Slave machine address 01H
Order code 03H
Byte number low-order 06H
Data address 0101H high-order 00H
Data address 0101H low-order 02H
Data address 0102H high-order 00H
Data address 0102H low-order 00H
Data address 0103H high-order 00H
Data address 0103H low-order 06H
CRC CHK low-order D8H
CRC CHK high-order B7H
END Transmission time of 3.5 bytes
136
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
137
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
138
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
139
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
140
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
2 Monitor Menu
Input F 50.00Hz
Output F 50.00Hz
Chart 1 (a) at stop state Chart1 (b) at FWD running state Chart1 (c) at REV running state
Chart1 (d) at JOG FWD state Chart1 (e) at JOG REV state
It can display two monitoring parameters and running or stop status every state of inverter, details refer to chart 1.User
can select first -line monitoring parameters by ,and select second-line monitoring parameters by .
3 Monitoring Parameter Menu
141
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
4 Parameters Menu
(1) First level menu(Reserve)
(2) Second level menu
Chart 3(a) Basic parameter Chart 3(b) External terminal Chart 3(c) Function parameter
The second level menu include 3 part: Basic parameter, External terminal, Function parameter, as show in chart 3.
Press key and enter into 3(a).User can select anyone of them by press or key. Press key
means selecting the item, And Press key to move monitoring interface, Basic parameter, External terminal,
Function parameter these 4 inverter face circular by turn.
(3) Third level menu
Chart 4 (a) changing line Chart 4 (b) data Chart 4 (c) group
After going into second level menu, press key to go into third level menu. Third level menu includes three kinds,
changing line, data and group.
Changing line: First line displays second level items, second and third line display third level items, and position of
cursor is factory default setting, details refer to char t 4(a).
Press key to replace items,
Press or to move cursor,
Press to return back,
Press to select item, and then return back.
Data: First line displays second level menu items, and second line displays data ,details refer to chart 4(b)
Press to replace items,
Press or to increase or decrease data while pressing , Press or to increase or decrease
data from lowest bit without pressing ,
Press to return back.
Press to confirm modifying data, and then return back.
Group: First line displays second level menu items, second line displays group number, and third line displays third level
menu items, details refer to chart 4(c)
Press to change another group, Press or to change items,
Press key to return back.
Press to confirm modifying items, and then return back.
If pressing or cannot modify items in third level menu, and display ”Read only” all that reminder user of
parameter is no t allowed to modify or when inverter is running ,modifying is forbidden
142
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
5 Fault
X5 X6 X7 X8 Y2
Chart7 (a) copying Chart7 (b) copy complete Chart7 (c) copy fault
Chart7 (d) download Chart7 (e) download complete Chart7 (f) download fault
Parameter copy: details please refer to chart 7 (a), 7(b), 7(c)
Check E-64 and select item “sending to keyboard from inverter”,and then press .When it displays “completely
copy ”, it means finishing copy operation details refer to chart 7(b).When it displays ”copy fault” ,it means operation is
failed, details please refer to chart 8(c).Press key to return .
Download: same way as copy
Note:Inverters must be the same series , when downloading parameters
143
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX
8 Self-tuning
Chart 8 (c) rotary type self-tuning Chart 8(d) exciting magnetic detecting
Resting type self-tuning: steps as chart 8 (a), (b) and (d).Please set H-62=2, and press key to go into motor
detecting waiting menu, details refer to chart 8(a).Then press key, and it will display resting self-tuning, details
refer to 8(b), It displays “exciting detecting” when self-tuning is over, details refer to chart 9(d), then it will return back
automatically.
Rotary self-tuning: steps as chart 8 (a),(b)and (d). Please set F-62=1, and press key to go into motor detecting
waiting menu, details refer to chart 8(a).Then press key, and it will display resting self-tuning, details refer to 8(b),
while resting self-tuning is over, it displays rotary self-tuning, details refer to chart8(c), After rotary self-tuning over, it
displays exciting detecting, details refer to chart 8(d), then it will return back automatically.
9 Other Menus
Locked code
Voltage is low
0
Chart 9 (a) keyboard locked Chart 9 (b) low voltage Chart 9 (c) model of inverter
Keyboard locked, as chart 9(a).Keyboard will display locked menu when going into next menu, after user setting
password and selecting parameter locked function. Please type correct password and then go into next menu.
Low voltage, as chart 9(b).When input voltage is low, it will display this warning.
Model of inverter, as chart 9(c).When power on, if communication is ok, it will display this menu, and if not, it will display
keyboard connection fault.