Sie sind auf Seite 1von 147

Contents

Chapter1 Overview .............................................................................................................................................. 1


1.1 Safety Requirement and Cautions ............................................................................................................ 1
1.2 Technical Criterion..................................................................................................................................... 4
Chapter 2 Before Use .......................................................................................................................................... 7
2.1 Purchase Inspection .................................................................................................................................. 7
2.2 Nameplate ................................................................................................................................................. 7
2.3 Rated Output Current ................................................................................................................................ 8
Chapter 3 Installation and Wiring ...................................................................................................................... 9
3.1 Safety Precautions .................................................................................................................................... 9
3.2 Treatment for Inverter after Longtime Store.............................................................................................. 9
3.3 Inverter Stable Running Environment ..................................................................................................... 10
3.4 EMI Protection ......................................................................................................................................... 11
3.5 Machinery Installation .............................................................................................................................. 13
3.6 Electric Installation................................................................................................................................... 22
Chapter 4 Basic Operation and Trial Run ....................................................................................................... 37
4.1 Safety Precautions .................................................................................................................................. 37
4.2 Keyboard Layout and Function Specification.......................................................................................... 38
4.3 Basic Operation ....................................................................................................................................... 40
4.4 Trial Run .................................................................................................................................................. 45
Chapter 5 Fault Diagnoses and Processing ................................................................................................... 50
5.1 Fault Types .............................................................................................................................................. 50
5.2 Fault Information and Details .................................................................................................................. 50
5.3 Fault Diagnoses Process ........................................................................................................................ 54
Chapter 6 Periodic Overhaul and Maintenance ............................................................................................. 60
6.1 Safety Precautions .................................................................................................................................. 60
6.2 Overhaul .................................................................................................................................................. 60
6.3 Maintenance ............................................................................................................................................ 61
Chapter 7 Peripheral Equipments and Options ............................................................................................. 64
7.1 Safety Precautions .................................................................................................................................. 64
7.2 Peripheral Equipments ............................................................................................................................ 64
7.3 The Use of Peripheral Equipments ......................................................................................................... 66
Chapter 8 Function Parameter Specification ................................................................................................. 69
8.1 Basic Parameters Specification .............................................................................................................. 69
8.2 External Terminal Parameters................................................................................................................. 93
8.3 .Special Function Parameters ............................................................................................................... 108
Chapter 9 Appendix......................................................................................................................................... 119
9.1 Appendix 1: Function Code Simple List ................................................................................................ 119
9.2 Appendix 2: RS485 Communication Protocol ....................................................................................... 135
9.3 Appendix 3: LCD Keyboard Manual ...................................................................................................... 141
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW

Chapter 1 Overview
Thanks for using AC70 series sensorless vector control frequency inverter produced by Veichi Electric co.,ltd. This
manual introduces you how to use it perfectly. Please read this manual carefully and fully understand the safety
requirement and cautions before use (installation, wiring, operation, maintain, checking, and etc...).
1.1 Safety Requirement and Cautions
Pls do totally understand this part before using the inverter.
Warning signs and meanings
This manual has used below signs that mean there is an important part of security. While observing against the rules,
there is danger of injury even death or machine system damage.

Danger: Wrong operation may cause death or large accident.

Warning: Wrong operation may cause death or large accident.

Caution: Wrong operation may cause minor wound.

Important: Wrong operation may cause the inverter and other machine system damage

Warning signs position


Warning position 1

Warning position 2

Drawing 1:Warning positions on crust of AC70 series inverter

1
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW

Operation requirement
Only Professional trained person are allowed to operate the equipment such as installation, wiring, running, maintain
and etc. “Professional trained person”in this manual means the workers on this product must experience professional
skill train, must be familiar with installation, wiring, running and maintain and can rightly deal with emergency cases in
use.
Safety guidance
Safety regulations and warning signs come for your security. They are measures to prevent the operator and machine
system from damage. Please carefully read this manual before using and strictly observe the warning signs while
operating. Safety regulations and warning signs are classified into: routine regulation, transport and store regulation,
installation and wiring regulation, running regulation, maintenance regulation, dismantlement and disposal regulation.
● Routine regulation
● This product carries dangerous voltage and controls driver machine with potential danger. If
you don’t abide by the regulations or requirements in this manual, there is danger of body
injury even death and machine system damage.
● Only qualified personnel are allowed to operate the equipment.this product. Before using, the
operator must be familiar with all safety specifications and operation regulations in this
manual. Safe and stable work of the product is based on right operation and maintenance.
● Do not wire while the power is connected. Otherwise, there is danger of death for electric
shock. Before wiring, inspection, maintenance, please cut power supply of all related
equipments and ensure mains DC voltage in safe range. And please operate it after 5 mins.
● Away from children and public.
● Only used in application fields as maker stated. No use in equipments related to special fields
such as emergency, succor, ship, medical treatment, aviation, nuclear and etc.
● Unauthorized alteration or use of accessories which are not sold or recommended by the
maker may cause faults.
● Please make sure this manual is in the final user’ hand before using.
● Before installation and debugging please carefully read and totally understand these safety
regulation and warning signs.
● Transport and store regulation

●Correct transport, store, installation and careful operation an maintenance are important for
inverter safe operation.
● In transport and store process, make sure the inverter is free from impact and vibration. It
must be stored where is dry without corrosive air and conductive dust, and the temperature
must be lower than 60℃.
● Installation and wiring regulation
● Only professional trained person can operate it.
● Power wire, motor wire and control wire should be all connected firmly. Earth must be reliable
and earth resistance must be lower than 10Ω.
● Before opening the inverter, please disconnect all related equipment power supply and make
sure the mains DC voltage is in safe range and operate after 5mins.
● Human body electrostatic will damage inner sensitive components seriously. Before
operation, please follow ESD measures. Otherwise, there is danger of inverter damage.
● Inverter output voltage is pulse wave. If components such as capacitor which improves power
factor and pressure-sensitive resistance for anti-thunder and so on are installed at the output
side, please dismantle them or change to input side.
2
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW

● No switch components such as breaker and contactor at the output side. (If there must be
one, please make sure the output current is 0 while the switch acting).

● The power supply cable and motor cable specifications must satisfy all conditions in table 3-7
3-8 .

● Run regulation
● Inverter runs at high voltage. So dangerous voltage is in some components inevitably.
● No matter where the fault is, there is danger of serious accident, even human body injury
what means dangerous malfunction possibility. So there must be additional external prevent
measures or other safety devices, such as independent current limiting switch, machinery
and so on.
● Maintenance regulation
● Only Shenzhen Veichi Electric co., ltd service department or its authorized service center or
professional person trained and authorized by Veichi can maintain the products. They should
be very familiar with the safety warning and operation gist in this manual.
● Any defective components must be changed in time.
● Before opening the inverter to repair please cut power supply of all related equipments and
ensure mains DC voltage in safe range. And please do operation after 5 mins.
● Dismantlement and disposal regulation
● Packing case can be reused. Please keep them and reuse or send back to maker.
● Dismantled metal components are retractable and can be reused.
● Some components such as electrolytic capacitor are harmful to environment. Please dispose
according to environmental protection departments.

3
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW

1.2 Technical Specification


Tech.
Items Description
Specification

Voltage, frequency single phase 220V, 3 phase, 220V,380V, 660V and 1140V
Voltage:<±15%; frequency±5%
Allowable fluctuations
Distortion of voltage to confirm to IEC61800-2
Power Input
Closing striking current less than rated current
Power Factor ≥0.94( integrated DC reactor)
Efficiency ≥96%
3 Phase, 0~Input voltage, tolerance less than 5% in standard
Output Voltage
rating condition
G type: 0 to 400Hz, P type: 0-400Hz, Z type: 0-400Hz, L type:
Frequency Control Range 0-400Hz,
H type: 0-3000Hz.
Power Output frequency accuracy ±5% of maximum frequency
Output Z type: 150% rated current for 60 sec, 180% rated current for 30
sec, 250% rated current for instantaneous
G, H, L type model: 150% of rated output current for 60 sec,180% of
Overload Tolerance
rated current for 10s, 2 00% of rated current for instantaneous
P type: 120% rated current 60 sec, 150% rated current for
instantaneous
Motor Control Mode Open loop sensorless vector control without PG, V/F control
Control system Optimized Space Vector PWM Modulation

Carrier frequency 0.6~15kHz, Randomly-modulated carrier

Speed control range OLV without PG with rated load: 1:100,


Key Control Stable speed control accuracy OLV without PG: less than 1% rated synchronous speed
performance OLV without PG control mode: ≤20ms
Torque response
Frequency Accuracy Digital inputs: maximum × ±0.01%
(Temperature Fluctuation) Analog inputs: maximum × ± 0.2%
Digital inputs: 0.01 Hz
Frequency Setting Resolution
Analog inputs: 0.5% of maximum output frequency
Starting Frequency: 0.00 to 50.00Hz,
DC Braking Braking Time: 0.0 to 60.0s
Standard
Braking current: 0.0 to 150% rated current
Function
Auto torque boost:0.0% to 100%
Torque boost
Manual torque boost: 0.0% to 25%

4
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW

5 kinds curve programmable setting:1 user setting, 1 of linear


V/F curve characteristic torque curve setting. 3 kinds derating torque
setting( 1.5 power, 1.7 power, 2.0 Power curve )
Two kinds curve: line Accel/Decel, S curve Accel/Decel.
Accel / Decel. curve
4 Aceel/Decel time unit is 0.1s, maximum time 6500.0s
Power voltage compensation is available, setting range from 50 to
Rated output voltage
100%( rated voltage), the output voltage can't over than input
automatic voltage regulation for keeping output voltage stable when
AVR( Auto Voltage Regulation
fluctuation of grid
Optimized the output voltage according the load to achieve energy
Auto energy saving running
saving
Auto current limit during running mode to avoid trip occurs
Auto current limit
frequently
Momentary Power Loss with To achieve continuous running with regenerative enery and DC bus
no stop running function voltage regulation when momentary power loss

PID control, Carrier frequency adjustable, current limiter, Speed


Search, Momentary Power Loss restart,8 Step Speed (max), 3-wire
Sequence, Slip Compensation, Frequency Jump, Upper/lower
Limits for Frequency Reference, DC Injection Braking at Start and
Standard Function
Stop, Energy Saving Control, Modbus Comm RS485, Fault Restart,
job function, Cooling Fan on/off Switch, timing stop, high pulse
output, programmable auto running, swing frequency, counter,
frequency arriving detect and frequency lever detect.
Keypad digital setting, potentiometer of keypad, analog voltage
terminal VS1, analog voltage terminal VS2, analog current terminal
Frequency Setting Methods
AS, RS485 communication and multiple terminal, main and auxiliary
composition setting.
voltage terminal VS1, VS2, current terminal AS, communication ,
Feedback Input Channel
and pulse input PUL
Running command channel keypad given, external terminal given, communication given
Start, Stop, FEW/Reverse, Job, Multiple speed, free stop, Reset,
Input command signal
Accel/Decel time, Frequency set point channel, External fault
2 Photo coupler relays: 2 (24 V, up to 50 mA)
1 Contact relays: 1 (250 Vac/up to 1 A, 30 Vdc/up to 1 A)
Output signal
0-10V output, 4 to 20mA output
Frequency pulse output
Overvoltage, under voltage, current limit, over current, overload,
Protection function
electric thermal relay, overheat, Stall prevention, parameter lock

5
AC70 VC CONTROL FREQUENCY INVERTER MANUAL OVERVIEW

One line digit-segments LED display to monitor 1 running status


LED Display
Double line digit-segment display to monitor 1 running status
Parameters copy upload and download parameter code to achieve easy copy
Output frequency, Frequency set point, Out current, Output voltage,
keypad
Monitor Function motor speed, PID feedback value, PID given setting, IGBT module
Display
temperature, I/O terminal status.
Overvoltage, under voltage, over current, short circuit, phase loss,
Alarms over load, over heat, stall prevention, current limit, parameter lock
damage, running status at present alarm, past trip alarm
Indoor, Altitude should less than 1000m, Free corrosive gases and
Installation Site
direct sunlight
Running Temperature, -10~+40°C ( wall mounting),
humidity 20% to 95% RH (No condensation)

Environment Vibration Less than 0.5g when frequency less than 20Hz
Storage Temperature -25—+65°C
Installation mode Wall-mounted mode, floor stand cabinet install
Protection Degree IP20
Cooling Method Forced air-cooling

Table 1: Technical Specification

6
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BEFORE USE

Chapter 2 Before Use


2.1 Purchase Inspection
Pls check whether any package is damaged while receiving the product you ordered. If the package is ok, pls open it
and check the inverter. If damage caused in transport, it is not duty of Veichi company. But please contact Veichi or the
transport company immediately.
After checking the product, please also check if the model is the one you ordered.The model of the product is on the
nameplate “MODEL”column. If the model is not in accordance with your need, please contact the agent or the sales
departments in our company.
2.2 Nameplate
Nameplate position and content

Model
MODEL: AC70-T3-011G/015P
Input power
SOURCE: 3 380V 50/60Hz
OUTPUT1: 11KW 25A 0.00-400.0Hz G models output

OUTPUT2: 15KW 32A 0.00-400.0Hz P models output

SER NO: Production series no


******************

Chart 2-1: AC70 series inverter nameplate

Model explanation

AC70 - T 3 - 011 G /015 P

inverter series
code inverter type
AC70 General use
G general format
P blower and water pump
Z plastic machine
code voltage class
L draw bench
T three phase
H mid inverter governor
S single phase
GD Cabinet with base
PD Cabinet with base
code voltage class

2 220V code fit power of motor(kW)


3 380V 7R5 7.5
6 660V 011 11
11 1140V 015 15
018 18.5
022 22
030 30

Chart 2-2: AC70series inverter nameplate meaning and naming rules

7
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BEFORE USE

2.3 Rated Output Current


Input voltage 220V 380V 660V 1140V
Rated power (kw) Rated output current (A)
0.4 2.5
0.75 4 2.3
1.5 7 3.7
2.2 10 5.0
4 16 10
5.5 20 13
7.5 30 17 10
11 42 25 15
15 55 32 18
18.5 70 38 22
22 80 45 28
30 110 60 35
37 130 75 45 25
45 160 90 52 31
55 200 110 63 38
75 260 150 86 52
90 320 180 98 58
110 380 210 121 75
132 420 250 150 86
160 550 310 175 105
185 600 340 198 115
200 660 380 218 132
220 720 415 235 144
250 470 270 162
280 510 330 175
315 600 345 208
355 670 380 220
400 750 430 260
450 810 466 270
500 860 540 325
560 990 600 365
630 1100 680 400

8
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Chapter 3: Installation and Wiring


3.1 Safety Precautions
This chapter explains the warnings for safe use and stable running of the product.
Cautions in use
●While install the inverter in the closed cabinet, please build in cooling fan, air-conditioner or
other cooling equipment to ensure the temperature at the air-in port below 40℃. So that the
inverter can work safely and reliably.
●While installing, please use cloth or paper cover the inverter to prevent metal dust, oil, water
and others.And remove it carefully after working.
● While operation, please follow the ESD regulations. Otherwise, the inverter may be
damaged.
● While multi inverters are installed in the same cabinet, enough space must be left for cooling
fan.
●Inverter can not work over rated range.Otherwise, the inverter may be damaged.
●While transporting the inverter, please hold the firm case. If only hold the pre-cover, there is
danger of inverter main body falling, injury or inverter damage.
Cautions in use motor
●Different motor has different max allowable running speed. Motor can not run over the max
allowable running speed.
●While inverter is running at low speed, the motor auto-cool effect is seriously worse. If motor
runs at low speed for long time, it will be damaged for overheat. If needed, please use special
motor for inverter.
●While constant speed machinery runs at inconstant speed, there maybe sympathetic vibration.
Please install vibration-proof rubber under motor rack or use jumping frequency control
function.
●While using frequency inverter or working frequency power supply to drive, the torque
characteristic are different. Please do confirm the torque characteristic of the equipment
connected.
●The rated current of shift gear motor is different from that of standard motor. Please confirm it
and choose the right frequency inverter. Moreover, please do switch the pole while the inverter
input current is 0. Otherwise it may bring inverter protection or damage.
●The rated current of diving motor is higher than that of standard motor, please confirm it and
choose the right inverter.
●While the wire between motor and inverter is long, the max torque of the motor will reduce for
voltage drop. So please use thick cable while the distance between the motor and the inverter
is long.
3.2 Treatment for Inverter after Longtime Store
If the inverter store time is over one year, you must pre-charge the aluminum capacitor in the inverter again and install
the inverter after the aluminum capacitor characteristic recovering. For the specific method, please follow the grads in
the chart below and give corresponding proportional voltage for every grad more than 30 mins while the inverter is
no-load.
If the input voltage of one grad is at the action critical point of contactor, fan or other equipment, please increase or
reduce the corresponding input voltage for the grad to avoid any component working under critical state.

9
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Chart 3-1: treatment for inverter after longtime store


3.3 Inverter Stable Running Environment
Installation environment is very important to the best use of this product for long time. Pls install this product in the
environment as the following table requirement.
Environment Requirement
Install place Indoor without direct sunshine
Install temperature -10 ~ +40℃
Store temperature -20 ~ +60℃
Humidity <95%RH, no condensation
Please install the inverter in place as follows:
● Place without oil mist, corrosive gases, flammable gas, dust or etc.
● Place without metal dust, oil, water or etc into inverter (please do not install inverter on
flammable material such as food and etc).
Surrounding
● Place without radioactive material or flammable material.
● Place without poisonous gases or liquid.
● Place with very little salification erosion.
● Place whihout direct sunshine.
Altitude <1000m
<10~20Hz:9.8m/s2
Vibration
<20~55Hz:5.9m/s2
● Inverter can not be installed horizontally must be installed vertically.
Installation and ● Please independently install high heating equipments such as braking resistor and etc which
cooling can not be installed in the same cabinet with inverter, installed at the air-in port of the inverter
is strictly prohibited.
Table 3-1:AC70 series inverter running environment condition
● In order to improve the product stability, pls do not use the inverter where temperature changes sharply. While
using in closed space such as control cabinet, please use cooling fan or air-condition to cool inverter to avoid
temperature over limit range. Please also prevent inverter from freeze, too low temperature may cause components
freeze fault.

10
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

● Derate according to the chart while over temperature limit.

PERMIT OUTPUT CURRENT(%)

100

75

50

25

-10 0 10 20 30 40 50 TEMPERATURE(℃)

Chart 3-2:AC70 series inverter derating surve while over permit temperature
● Derate according to the chart while over altitude limit.
PERMIT OUTPUT CURRENT(%)

100

80

0 1000 2000 3000 4000 ALTITUDE(M)

Chart 3-3:AC70 series inverter derating surve while over permit altitude
3.4 EMI Protection
The inverter is designed to be used in industrial environment with strong electromagnetic interference. Generally
speaking, if the installation quality is good, it is ensured that the inverter can work safely without fault. Please install the
inverter according to the following rules to ensure stable running and avoid electromagnetic interference impact.
● Ensure that all equipments in the cabinet have been connected reliably to the common Y-type earth point or earth
bus with thick and short cable. The motor earth should be as close as possible. Please do not connect the motor
case to the inverter earth terminal or the protective area of control system.
● Ensure that all equipments connected to the inverter have been reliably connected to the same earth net or Y-type
earth point with thick and short cable.
● The conductor has better to be flat and with multi core, what has lower resistance at high frequency.
●The cutting terminal should be as soigne as possible. Unshielded wire section must be as short as possible.
● In control cable wiring, it should be as far from the power supply cable and motor cable as possible. And
independent cable trough should be used. While the control cable must cross to the power supply cable or motor
cable, it should be 90º vertical cross.
● Ensure that the contactor in the cabinet has wave surge suppresser. Or‘R-C’damping circuit is connected to the
winding of AC contactor. Voltage dependent resistor corresponding to the winding voltage is used. And freewheel
diode or components such as voltage dependent resistor corresponding to the winding voltage are connected to DC
contactor. It is very important while contactor, controlled by output relay of inverter, acts frequently.
● Cable connected to motor should be shielded cable or armoured cable. The two barriers are earthed reliably by
cable grounding card.
● Build noise filters at the input side to reduce electromagnetic interference from other equipments at the power grid
side. The noise filter should be as close to the inverter power input terminal as possible. Meantime, the filter must
earth reliably as the inverter.
● Build noise filters at the output side to reduce radio interference and inductive disturbance. The noise filter must be
as close to the inverter output terminal as possible. Meantime, the filter must earth reliably as the inverter.

11
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

● Anytime, control circuit wire should be shielded cable.


● Add zero phase reactor in power supply wire near inverter input terminal and add zero phase reactor in the motor
wire near inverter output terminal to reduce electromagnetic interference to the inverter efficiently.
● Earthing Right and reliable earthing is the basic condition of safe and reliable running of the product. For right
earthing, please read the following notice carefully.
●In order to avoid electric shock, earthing cable should be the size as electric
equipment technique standard required and cable length should be as short as
possible. Otherwise, inverter leakage current will cause unstable potential of the
earthing terminal which is far from the earthing point, and electric shock accident will
happen frequently.
●Earth terminal must be earthing. Earth resistance must be below 10Ω. Otherwise,
there is danger of death.
● Please do not share earth cable with welder or other big current/pulse power
equipment. Otherwise, inverter will act abnormally.
●While multi inverters are used at the same time, please do not wind the earth wire to
loop-type. Otherwise, inverter will act abnormally.

Chart 3-4: multi AC70 series inverters united earthing

Chart 3-5:AC70 series inverter system earthing


Remark: motor must earth as close as possible. Motor case can not be connected to the inner earth terminal of the
inverter. It also can not share the earth net with the control system.
● Shield of inverter power cable, motor cable, control cable Cable
Shielding layer (reticulate/armoured) should be winded reliably by cable earth card and fix to inverter earth piece by bolt.
Please refer to the following chart.

12
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Chart 3-6:Cable earth card for cables earthing


●Corresponding relationship between inverter/motor cable length and carrier frequency.
While cable distance between inverter and motor is long (especially low frequency output), cable voltage drop will make
motor torque reduce. Further more, cable HF leakage current will increase. Then inverter output current will increase,
that will cause inverter over-current trip. The current detection accuracy and running stability will be impacted. Please
follow as below table to adjust carrier frequency according to the cable length. While the cable distance is over 100m,
please adopt distributed capacity reduce measure (Such as “no metal conductor covers cable”, “wire each phase cable
apart” and so on).
Cable length <20m 20~50m 50~100m >100m

Carrier frequency 0.7~15kHz 0.7~8kHz 0.7~4kHz 0.7~2kHz

Table 3-2: Corresponding relationship between inverter/motor cable length and carrier frequency

3.5 Machinery Installation


Installation notice and related requirement
● AC70 inverter components

Chart 3-7:AC70 series inverter components

13
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

● Installation direction
To prevent inverter cooling effect reducing, please do install the inverter vertically.

Chart 3-8:AC70 series inverter installation direction


● Installation space
Single machine installation: to ensure enough ventilation and wiring space for inverter cooling, please follow installation
conditions as follows. The back of the inverter should stick to the wall. So that the surrounding air of radiator can flow
freely to ensure the cooling effect.

Chart 3-9:Single AC70 series inverter installation space


Multi inverters paratactic installation: while installing multi inverters in cabinet, please ensure installation space as
follows.

Chart 3-10: Multi AC70 series inverters paratactic installation space requirement

14
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Dimension of Inverter and Keyboard


W D
W1 D1

H1
H
Inverter size Install size Install
Inverter model
W H D D1 W1 H1 aperture
AC70-S2-R40G

AC70-S2-R75G 122 182 154.5 145 112 171 ф5

AC70-S2-1R5G

AC70-S2-2R2G
159 246 157.5 148 147.2 236 ф5.5
AC70-S2-004G

AC70-S2-5R5G 195 291 167.5 158 179 275 ф7

AC70-T3-R75G/1R5P

AC70-T3-1R5G/2R2P 122 182 154.5 145 112 171 ф5

AC70-T3-2R2G/004P

AC70-T3-004G/5R5P
159 246 157.5 148 147.2 236 ф5.5
AC70-T3-5R5G/7R5P

AC70-T3-7R5G/011P
195 291 167.5 158 179 275 ф7
AC70-T3-011G/015P
AC70-T3-015G/018P
(plastic cover machine)
AC70-T3-018G/022P
230 330 200 190 208 315 Ф7
(plastic cover machine)
AC70-T3-022G/030P
(plastic cover machine)

15
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

W
W1 D

H1

H2
H

Install aperture

Inverter size Install size Install


Inverter model
W H D H2 W1 H1 aperture
AC70-T3-015G/018P
(steel cover machine)
235 345 200 311 160 331.5 ф7
AC70-T3-018G/022P
(steel cover machine)
AC70-T3-022G/030P
(steel cover machine) 255 410 225 370 180 395 Ф7
AC70-T3-030G/037P
AC70-T3-037G/045P
AC70-T3-045G/055P 305 570 260 522 180 550 Ф9
AC70-T3-055G/075P
AC70-T3-075G/093P
AC70-T3-093G/110P 380 620 290 564 240 595 ф11
AC70-T3-110G/132P

16
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

W
W1
D

H1

H2
H

Inverter size Install size Install


Inverter model
W H D H2 W1 H1 aperture
AC70-T3-132G/160P 500 780 340 708 350 755 ф11
AC70-T3-160G/185P
AC70-T3-185G/200P 650 1060 400 950 400 1023 ф16
AC70-T3-200G/220P
AC70-T3-220G/250P
AC70-T3-250G/280P 750 1170 400 1050 460 1128 ф18
AC70-T3-280G/315P
AC70-T3-315G/355P
AC70-T3-355G/400P 850 1280 450 1150 550 1236 ф20
AC70-T3-400G/450P

NOTE: Without build-in dc reactor

17
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

W D

H1
H

D1

W1

Inverter size Install size Install


Inverter model
W H D H1 W1 D1 aperture
AC70-T3-160GD/185PD
AC70-T3-185GD/200PD 650 1600 400 1500 492 332 ф14
AC70-T3-200GD/220PD
AC70-T3-220GD/250PD
AC70-T3-250GD/280PD 750 1700 400 1600 582 332 ф14
AC70-T3-280GD/315PD
AC70-T3-315GD/355PD
AC70-T3-355GD/400PD 850 1800 450 1700 622 382 ф14
AC70-T3-400GD/450PD

NOTE: With build-in dc reactor

18
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

W D

H1
H

W1
D1

Inverter size Install size Install


Inverter model
W H D H1 W1 D1 aperture
AC70-T3-450G/500P
AC70-T3-500G/560P 1200 1850 550 1750 960 466 ф14
AC70-T3-560G/630P

Table 3-3:AC70 series inverter dimension

19
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Keyboard dimension

Chart 3-11:AC70 series inverter 1 line LED keyboard dimension

Chart 3-12:AC70 series inverter mouth for 1 line LED keyboard dimension

16.5 63.5

35.6
114.5

110.5
17.1
53.75

65.5 19.5

Chart 3-13:AC70 series inverter 2 line LED keyboard dimension

20
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

111
Mouth for keyboard with box

119
Mouth for keyboard with box Mouth for keyboard with box
AC70-T3-160G/630P AC70-T3-015G/132P

142

64
70

75

Chart 3-14:AC70 series inverter mouth for 2 line LED keyboard dimension
Note: LCD keyboard total same size as LED keyboard.

Dismantle and install tail-hood

Installation: First the tail-hood upwardly inclines around 15


degrees and inserts the top fixed flat into the fixed hole in the
front cover. Then slightly press the tail-hood downward. While
your hear "Ka", it means that the tail-hood is into the place.
Chart 3-15:AC70 series inverter tail-hood installation

Dismantlement: At the tail of the frequency inverter, there is a


special dismantlement hole design. Put your finger into the
hole, upwardly pull the cover with a little force until the buckle
between the tail-hood and the crust tear off, and then remove
the tail-hood down.
Chart 3-16:AC70 series inverter tail-hood dismantlement

21
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Dismantlement and installation of keyboard

Chart 3-17:AC70 series inverter keyboard installation and dismantlement


3.6 Electric Installation
This chapter explains the regulations that users have to obey to ensure safe use, best performance and reliable
running.
Safety precaution
● Must earth reliably while inverter is running. Otherwise there is danger of casualty and
unstable inverter performance.
● To ensure safe running, only trained professional person can do installation and wiring
job.
● No operation under power connected state. Otherwise there is danger of electric shock
even death.
● Before operation, please cut all related equipments power, ensure that the main circuit
DC current has dropped to safe range. And please operate after 5 mins.
● Control cable, power cable and motor cable must be separated. They can not be in the
same cable trough or cable rack.
● This equipment can only be used as the maker states. Please consult Veichi while using
in special case.
● No insulation test for the inverter or the related cable by HV insulation test equipment.
● If the inverter or the peripheral equipment (filer, reactor and etc) needs insulation test,
firstly 500V megohmmeter should be used to test the insulation resistance which should
not be lower than 4MΩ.

22
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Standard diagram
● Standard diagram

Frequency Inverter
Note1
+24V

PLC
AC220V Maximum output:

passive source output


3A/240VAC
(Forward Run/Stop) X1 5A/30VDC
coil
TA
(Reverse Run/Stop) X2
TB twisted-pair shielding line
Multi-function digital input

(Jog run forward) X3 (grounding nearby by inverter)


TC
(Jog run Reverse) X4
AC0V
(Free stop) X5

(Fault reset) X6 +24V

collector type status output


coil
Y1
COM twisted-pair shielding
Note:multiple function digtal input default line (grounding nearby by inverter)
setting
coil
Y2 Note:
COM Note: 1 Maximum output of +24V
terminal-DC 24v/100mA
Note3 2 Maximum output of Y1/Y2 DC24V/50mA
pulse input
PUL
Frequency reference setting input

10
J1
switch _
mA
twisted-pair shielding line J2

20
0
(grounding nearby) J3

analog monitor signal output


+ -

A02
Analog current Input +10V twisted-pair shielding
GND
(0~20mA)/(4~20mA) line (grounding nearby by inverter)
AS
J4 Pin 5

VR mini 2Kohm VS1 _


V
J5 switch

10
0
VR
Note2
Analog voltage Input VS2 -
+
(0~5V)/(0~10V)
A01
GND
GND
Note:
1 Maximum output 50mA +10V input terminal
Note: Maximum output is 2mA when
2. VS1/VS2 terminal resistor valuve 89ohm A01/A02 as for frequency voltage signal
3 AS terminal resistor valuve 250ohm output

Mark:
1. stand for main loop terminal
2. stand for control loop terminal

Chart 3-18:AC70 series inverter standard diagram


Note: 1.NPN or PNP transistor signal can be selected as input of multi-function input terminal(X1~X6). Inverter
built-in power supply (+24V terminal) or external power supply (PLC terminal) can be chosen as bias
voltage. Factory setting ‘+24V’ short connect with ‘PLC’.
2. Analog monitor output is special output of meters such as frequency meter, current meter, voltage meter
and etc. It can not be used for control operations such as feedback control.
3. As there are multi pulse styles, please refer to the line connect mode description details.
● Auxiliary terminal output capacity

Terminal Function definition Max output


10V auxiliary power supply output, constitutes loop
+10V 50mA
with GND.
As frequency,voltage signal, max
A01/A02 Analog monitor output, constitutes loop with GND.
output 2mA
24V auxiliary power supply output, constitutes loop
+24V 100mA
with COM.

23
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Collector open circuit output, can set the


Y1/Y2 DC24V/50mA
action-object by program.
Passive connector output,can set the action-object 3A/240VAC
TA/TB/TC
by program. 5A/30VDC
Table 3-4:AC70 series inverter auxiliary terminals output capacity
● Switch terminals connection function specification
Switch Optional
Picture example Function specification
terminal position
(AO2)
J1 0.0~50kHz open collect pole pulse
frequency output

(AO2)
J2 0~20mA current output or
4~20mA current output
(K2)
(AO2)
J3
0~10V voltage output

(AO1)
J4 J4 connect
0~10V voltage output

(AO1)
(K1) J5 0~20mA current output or
J5 conne
4~20mA current output

J6 conne RS485 communication initial port


J6
connect matching resistor 120Ω

(K3) J7 J7 conne Matching resistor disconnect

Table 3-5:AC70 series inverter switch terminal connection function specification

24
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Main circuit wiring


● Main circuit wiring

Chart 3-19:AC70 frequency inverter main circuit wiring

Note: 1, Fuse, dc reactor, braking unit, braking resistor, input actor, input filter,output reactor, output filter are optional
parts, please refer to “peripheral equipment”.
2, P1 terminal and (+) short connect. If need add dc reactor, please take away the short connect part between P1 and
(+).
Main circuit terminals
● Main circuit terminals array and definition

Arrangement sequence of main circuit terminal with 18.5kW or less power(15 ~ 18.5KW for steel cover machine)

(-)(+) PB R S T U V W E

Arrangement sequence of main circuit terminal with 15-22KW(15~22KW for plastic cover machine)

25
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Arrangement sequence of main circuit terminal with 22~30KW (standard machine without PB terminal)
(22KW for steel
cover machine)

Arrangement sequence of main circuit terminal with 37~110kW

Arrangement sequence of main circuit terminal with 132kW: Arrangement sequence of main circuit terminal with 160~560kW

Terminal Name
(-) DC power output, (-) means DC bus cathode, (+) means DC
DC power terminal
(+) bus anode, used for external braking unit.

(+)
Braking resistance terminal Used for external braking resistance to realize quick stop.
PB
P1
DC reactor terminal Used for external DC reactor.
(+)
R
S Inverter input terminal Used to connect 3-phase AC power supply.
T
U
V Inverter output terminal Used to connect the motor.
W

Earth Earth terminal, earth resistance<10 OHM


E
Table 3-6:AC70 series inverter main circuit terminals array and definition

26
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

● 3-phase 380V machine main circuit wiring


Main circuit terminals Suggested fixed Suggested Copper-core cable
Model
screw specifications moment (N·m) specification mm2 (AWG)
AC70-T3-R75G/1R5P M4 1.2~1.5 1.5mm2(14)
AC70-T3-1R5G/2R2P M4 1.2~1.5 2.5mm2(12)
AC70-T3-2R2G/004P M4 1.2~1.5 2.5mm2(12)
AC70-T3-004G/5R5P M4 1.2~1.5 4mm2(10)
AC70-T3-5R5G/7R5P M4 1.2~1.5 6mm2(9)
AC70-T3-7R5G/011P M5 2~2.5 6mm2(9)
AC70-T3-011G/015P M5 2~2.5 10mm2(7)
AC70-T3-015G/018P M6 4~6 10mm2(7)
AC70-T3-018G/022P M6 4~6 16mm2(5)
AC70-T3-022G/030P M8 8~10 16mm2(5)
AC70-T3-030G/037P M8 8~10 25mm2(3)
AC70-T3-037G/045P M8 8~10 25mm2(3)
AC70-T3-045G/055P M8 8~10 35mm2(2)
AC70-T3-055G/075P M10 11~13 35mm2(2)
AC70-T3-075G/093P M10 11~13 50mm2(1)
AC70-T3-093G/110P M10 11~13 50mm2(1/0)
AC70-T3-110G/132P M10 11~13 70mm2(2/0)
AC70-T3-132G/160P M10 11~13 95mm2(3/0)
AC70-T3-160G/185P M12 14~16 95mm2(4/0)
AC70-T3-185G/200P M12 14~16 120mm2
AC70-T3-200G/220P M12 14~16 150mm2
AC70-T3-220G/250P M12 14~16 150mm2
AC70-T3-250G/280P M12 14~16 185mm2
AC70-T3-280G/315P M12 14~16 185mm2
AC70-T3-315G/355P M16 20~23 240mm2
AC70-T3-355G/400P M16 20~23 240mm2
AC70-T3-400G/450P M16 20~23 300mm2
AC70-T3-450G/500P M16 20~23 400mm2
AC70-T3-500G/560P M16 20~23 400mm2
AC70-T3-560G/630P M16 20~23 500mm2
Note: Here we suggest to use copper joins as mains electric connectors of machine over 185KW. Pls refer the cut
section area above.
Table 3-7: Suggested cable diameter and fixed moment 3-phase 380V machine main circuit

27
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

● Single-phase 220V machine main circuit wiring


Main circuit terminals Suggested fixed Suggested Copper-core cable
Model
screw specifications moment (N·m) specification mm2 (AWG)
AC70-S2-R40G M4 1.2~1.5 1.5mm2(14)
AC70-S2-R75G M4 1.2~1.5 2.5mm2(12)
AC70-S2-1R5G M4 1.2~1.5 2.5mm2(12)
AC70-S2-2R2G M4 1.2~1.5 4mm2(10)
Table 3-8: Suggested cable diameter and fixed moment single-phase 220V machine main circuit
● Suggested main circuit components specification

Contactor Breaker
Model DC reactor Input filter Output filter
specification specification

AC70-T3-R75G/1R5P 10A 10A ------ NFI-005 NFO-010


AC70-T3-1R5G/2R2P 10A 10A ------ NFI-005 NFO-010
AC70-T3-2R2G/004P 16A 15A ------ NFI-010 NFO-010
AC70-T3-004G/5R5P 16A 20A ------ NFI-010 NFO-010
AC70-T3-5R5G/7R5P 25A 20A ------ NFI-020 NFO-020
AC70-T3-7R5G/011P 25A 30A ------ NFI-020 NFO-020
AC70-T3-011G/015P 32A 40A ------ NFI-036 NFO-036
AC70-T3-015G/018P 40A 50A ------ NFI-036 NFO-036
AC70-T3-018G/022P 50A 60A ------ NFI-050 NFO-050
AC70-T3-022G/030P 50A 75A DCL-50 NFI-050 NFO-050
AC70-T3-030G/037P 63A 100A DCL-80 NFI-080 NFO-080
AC70-T3-037G/045P 80A 125A DCL-100 NFI-100 NFO-100
AC70-T3-045G/055P 100A 150A DCL-110 NFI-100 NFO-100
AC70-T3-055G/075P 125A 175A DCL-125 NFI-150 NFO-150
AC70-T3-075G/093P 160A 200A DCL-150 NFI-150 NFO-150
AC70-T3-093G/110P 220A 250A DCL-200 NFI-200 NFO-300
AC70-T3-110G/132P 220A 300A DCL-200 NFI-200 NFO-300
AC70-T3-132G/160P 250A 400A DCL-300 NFI-300 NFO-300
AC70-T3-160G/185P 300A 500A DCL-300 NFI-300 NFO-300
AC70-T3-185G/200P 400A 600A DCL-400 NFI-400 NFO-400
AC70-T3-200G/220P 400A 700A DCL-400 NFI-400 NFO-400
AC70-T3-220G/250P 630A 800A DCL-500 NFI-600 NFO-600
AC70-T3-250G/280P 630A 1000A DCL-600 NFI-600 NFO-600
AC70-T3-280G/315P 630A 1200A DCL-600 NFI-600 NFO-600
AC70-T3-315G/355P 630A 1200A DCL-800 ------ ------
AC70-T3-355G/400P 800A 1400A DCL-800 ------ ------
AC70-T3-400G/450P 1000A 1600A DCL-1000 ------ ------
AC70-T3-450G/500P 1000A 2000A DCL-1000 ------ ------

28
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

AC70-T3-500G/560P 1000A 2000A DCL-1200 ------ ------


AC70-T3-560G/630P ------ 2000A DCL-1200 ------ ------
Note: For DC reactor, input filter, output filter and other components specification details and circuit mode, please refer
chapter 7 “peripheral equipments and options”
Table 3-9: Suggested mains fittings for 3-phase 380V machine
Control loop terminals
● Control loop terminals array

TA TB TC X1 X2 X3 X4 X5 X6 +10V A02 A01 GND


Y1 Y2 COM +24V PLC COM PUL AS VS1 VS2 GND A+ B-

Sort Terminal Name Function definition

Passive TA Normally-open contact


Can set the action-object by programme.
connection TB Normally-closed contact
Max contact capacity:3A/240VAC 5A/30VDC
output TC Common contact

Y1 Collector open output 1 Can set the action-object by programme.


State output
Y2 Collector open output 2 Max contact capacity:DC30V/50mA

Auxiliary +24V Auxiliary power output +


Max output: 24VDC/100mA.
power supply COM Auxiliary power output -
X1 Multi-function contact input 1
Build-in photoelectric converter can set the
X2 Multi-function contact input 2
action-object by program.
X3 Multi-function contact input 3 Input condition: Max DC30V/8mA.
Multi-function X4 Multi-function contact input 4 Note:Factory setting is common-collector
contact input characteristic input. If need common-emitter
X5 Multi-function contact input 5
characteristic input, please remove the short
X6 Multi-function contact input 6
connector between“+24V” and “PLC”, then use
Multi-function the short connector to connect “PLC” and “COM”.
PLC
contact input common terminal
Pulse range:0.0~50.00kHz. Factory setting is
Pulse input PUL Pulse input collector open output (R80,R82 transfer to
R81,R83 can be active input)

29
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Can set the action and object by program.


Physical type of output signal: 0~10VDC.
A01 Analog output 1
0~20mA , 4~20mA. It can be selected by
parameter [F-62] and J4,J5 (see table 3-5)
Analog output
Can set the action-object by program. Physical
type of output signal: 0~10VDC. 0~20mA ,
A02 Analog output 2
4~20mA, It can be selected by parameter [F-62]
and J1 J2 J3 (see table 3-5)
AS Current analog input As inverter control signal or feedback signal, can
set the act range and response speed by
Analog input VS1 Voltage analog input 1
program. VS1/VS2 resistance:100KΩ; AS
VS2 Voltage analog input 2 resistance: 250Ω.
Signal auxiliary power supply
+10V Max output 10VDC/50mA
Signal auxiliary terminal
power supply Signal auxiliary power supply Common auxiliary power of analog output,
GND
terminal analog input signal.
Communication A+ Communication terminal A+
RS485 communication port
terminal B- Communication terminal B-

Table 3-10:AC70 series inverter control loop terminals array and definition

● Control loop terminal wiring specification

Bolt Cable
Fixed moment
Terminal specification specification Cable type
(N·m)
(mm) (mm2)
Twisted-pair
A+ B- M2.5 0.4~0.6 0.75
shielded cable
Twisted-pair
+10V GND A01 A02 VS1 VS2 AS M2.5 0.4~0.6 0.75
shielded cable
+24V COM Y1 Y2 TA TB TC PLC PUL
M2.5 0.4~0.6 0.75 Shielded cable
X1 X2 X3 X4 X5 X6
Table 3-11:Control loop terminal wiring specification
Braking unit (braking resistance) connection
● Brake resistance wiring of machine with 18.5KW or less power(15KW-18.5KW for steel cover machine)

Brakeing
resistor

(-) (+) PB R S T U V W E

Fig 3-20: AC70 Series Frequency Inverter Brake resistance wiring of machine with 18.5KW or less power

30
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

● Brake resistance wiring of machine with 15-22KW(for plastic cover machine)

Brakeing
resistor

Fig 3-21: AC70 Series Frequency Inverter Brake resistance wiring of machine with 15-22KW(for plastic cover machine)

● Brake resistance wiring of machine with 22KW and 30KW(built-in brake is optional)(22KW for steel cover machine)

R S T (+) PB (-) U V W
POWER INPUT MOTOR OUTPUT
Brakeing
resistor

Fig 3-22: AC70 Series Frequency Inverter Brake resistance wiring of machine with 22KW and 30KW(built-in
brake is optional)(22KW for steel cover machine)
● Brake resistance wiring of machine with 37KW or above

Dynamic Brake Unit

POWER ACTIVE

R S T (+) PB (-) U V W
POWER INPUT MOTOR OUTPUT Brakeing
resistor

- + + PB

Fig 3-23: AC70 Series Frequency Inverter Brake resistance wiring of machine with 37KW or above
● Suggested braking resistance specification parameters
Braking resistance value and power in the chart are decided according to common inertia load and intermittent braking
mode. While used in large inertia occasion or long time frequent brake occasion, please adjust resistance value and
power according to the inverter specification and the rated parameter of braking unit. If any problem, please consult
customer service department of Veichi Electric Com., Ltd.

31
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Three-phase 380V
Motor power(kW) Resistance value(Ω) Resistance power(W) Braking torque (%)
0.75 kW 750Ω 150W 100%
1.5 kW 400Ω 300W 100%
2.2 kW 250Ω 400W 100%
4.0 kW 150Ω 500W 100%
5.5 Kw 100Ω 600W 100%
7.5 kW 75Ω 780W 100%
11 kW 50Ω 1,200W 100%
15 kW 40Ω 1,500W 100%
18.5 kW 32Ω 2,000W 100%
22 kW 28Ω 2,200W 100%
30 kW 24Ω 3,000W 100%
37 kW 20Ω 3,700W 100%
45 kW 16Ω 4,500W 100%
55 kW 13Ω 5,500W 100%
75 kW 9Ω 7,500W 100%
90 kW 6.8Ω 9,300W 100%
110 kW 6.2Ω 11,000W 100%
132 kW 4.7Ω 13,000W 100%
160 kW 3.9Ω 15,000W 100%
185 kW 3.3Ω 17,000W 100%
200 kW 3Ω 18,500W 100%
220 kW 2.7Ω 20,000W 100%
250 kW 2.4Ω 22,500W 100%
280 kW 2Ω 25,500W 100%
315 kW 1.8Ω 30,000W 100%
355 kW 1.5Ω 33,000W 100%
400 kW 1.2Ω 42,000W 100%
450 kW 1.2Ω 42,000W 100%
500 kW 1Ω 42,000W 100%
560 kW 1Ω 50,000W 100%
Single-phase 220V
Motor power(kW) Resistance value(Ω) Resistance power(W) Braking moment (%)
0.4 kW 400Ω 100W 100%
0.75 kW 200Ω 120W 100%
1.5 kW 100Ω 300W 100%
2.2 kW 75Ω 300W 100%
Table 3-12: Suggested braking resistance specification parameters of AC70 series inverter
● Build-in braking unit max braking performance
Braking unit of AC70 series product with low power can be selected according to the suggested braking resistance
specification parameters in table 3-11. In large inertia or long time frequent brake occasion, the moment maybe should
be increased. The max braking power is showed in the following table, the range of which can not be over in use.
Otherwise the equipment maybe destroyed. If any problem, please consult Veichi Electric Com., Ltd customer service
department.
32
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Three-phase380V
Inverter model Motor power Max braking current Min resistance
AC70-T3-R75G/1R5P 0.75 kW 3.5A 200Ω
AC70-T3-1R5G/2R2P 1.5 kW 3.5A 200Ω
AC70-T3-2R2G/004P 2.2 kW 7A 100Ω
AC70-T3-004G/5R5P 4 kW 10A 75Ω
AC70-T3-5R5G/7R5P 5.5 KW 10A 75Ω
AC70-T3-7R5G/011P 7.5 kW 14A 50Ω
AC70-T3-011G/015P 11 kW 17A 40Ω
AC70-T3-015G/018P 15 kW 23A 30Ω
AC70-T3-018G/022P 18.5 kW 28A 25Ω
AC70-T3-022G/030P 22 kW 30A (optional) 24Ω(optional)
AC70-T3-030G/037P 30 kW 35A (optional) 22Ω(optional)
Single-phase 220V
Inverter model Motor power Max braking current Min resistance
AC70-S2-R40G 0.4 kW 3.8A 100Ω
AC70-S2-R75G 0.75 kW 3.8A 100Ω
AC70-S2-1R5G 1.5 kW 6.5A 60Ω
AC70-S2-2R2G 2.2 kW 10.5A 40Ω

Table 3-13:AC70 series inverter build-in braking unit max braking power

33
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Multi-function contact input connection


● NPN transistor connection mode

use inner 24v power +24V


AC70 use exterior 24v power exterior 24v power +24V AC70

factory short connect PLC PLC


- +

X1 X1

X2 X2

X3 X3

exterior
X4 X4
control exterior
signal control
X5 signal X5

X6 X6

COM COM
shielded cale E shielded cale E
dismantle 24v and PLC connector

Chart 3-24: NPN transistor digital input signal connection mode


● PNP transistor connection mode

use inner 24v power AC70 use exterior 24v power AC70
+24V

+24V exterior 24v power

PLC + - PLC

COM COM

X1 X1

X2 X2
exterior
exterior
control
control
signal X3 signal X3

X4 X4

X5 X5

X6 X6

shielded cale E shielded cale E

Chart 3-25 PNP transistor digital input signal connection mode


Digital output signal connection
AC70 AC70

+24V +24V

wind wind
+

Y1 Y1
-

double shielded cable


exterior 24v power

COM COM

COM COM double shielded cable


E E

control exterior relay by inner 24V power of inverter control exterior relay by inner 24V power of inverter

Chart 3-26:AC70 series inverter digital output signal connection mode

34
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Analog output signal connection


A01 as 0~10V output indicator A02 as 0~10V output indicator
5 5

AC70 AC70
_
V _
V

10

10
0

0
+ - + -

A01 A02

GND GND
double shielded cable double shielded cable
E E

A02 as 0~20mA output indicator A02 as 0.2~50KHZ output indicator


10 25

AC70 AC70
_
mA kHz

50
20
0

0
+ - + -
A02 A02

GND GND
double shielded cable double shielded cable
E E

Chart 3-27:AC70 series inverter analog output signal connection mode


Connection of pulse input signal
Connection of passive pulse signal input Connection of active pulse signal input
AC70 Passive pulse AC70
input bias resistor
+24V

pulse signal source pulse signal source


PUL PUL PUL PUL

COM COM COM COM

E STP cable E STP cable

Explaination:
1.Bias resistor value calculation:
pulse voltage
R= 2
max pulse output current
1.Bias resistor power calculation:
2
pulse voltage
P=
bias resistor value

Chart 3-28: Pulse input signal connection mode of AC70 series inverter

35
AC70 VC CONTROL FREQUENCY INVERTER MANUAL INSTALLATION AND WIRING

Standby control system


Frequency inverter is composed of semiconductor, passive electronic component and driving part. All of them have
useful time, which means these parts may happen characteristic change or out of use in normal working environment.
And it will cause product fault. To avoid production stop led by the fault, we suggest preparing standby control system
when using the inverter.
Chart 3-29 is a standby control system for manual switch to power supply driving motor at inverter fault. Standby control
systems such as power supply Y/Δ step-down start way driving motor, power supply self-coupling reduction voltage
start mode driving motor, power supply soft start mode driving motor or standby inverter system can be chose to use
according the actual requirement and environment.

Chart 3-29: Standby control system of power supply directly driving mode

36
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

Chapter 4: Basic Operation and Trial Run


4.1 Safety Precautions
● No wiring while power supply is connected.Otherwise there is danger of electric shock.

● No operation while the cover is open.Otherwise, there is danger of electric shock.


● Please ensure reliable earth. Otherwise,there is danger of electric shock and fire.
● Before wiring please cut power supply of all related equipments and ensure main DC
voltage in safe range. And please do operation after 5 mins.
● Only professional trained person is allowed to operate this product.
● Please do not dismantle the inverter cover while it is electrified. Otherwise, there is danger
of electric shock.
● Please do not touch the printed circuit board of the inverter while it is electrified.
Otherwise, there is danger of electric shock.
● Please ensure reliable mains cable connection. If the mains cable is loose, there is danger
of fire caused by joint overheat.
● Before electrifying, please check the power voltage again. Wrong power voltage can
cause fault or damage the inverter, even cause fire.
● Please do not install inverter on flammable material or attach flammable material to the
inverter. Before electrifying, please clear the surroundings.

● While operation, please follow the ESD regulations. Otherwise, the inverter maybe
damaged.
● Please don’t cut the power directly while the inverter drives the motor running. The power
can’t be cut until the motor totally stop. Otherwise, the inverter maybe damaged.
● Please don’t cut or connect motor while the inverter drives the motor running. The motor
can’t be cut or connect until the inverter output is 0. Otherwise, the inverter maybe
damaged.
Important ● Control cable should be twisted-pair shielded cable. The barrier should be
connected to the inverter earth terminal reliably to prevent the inverter from abnormal
working.
● Unprofessional person can not operate, install, wiring, debug and maintain.
● Change, dismantle or maintain without permission may cause inverter damage. This case
is not within our quality assurance range.

37
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

4.2 Keyboard Layout and Functions Specification


● Keyboard appearance

● Key function

Key Name Function


Enter menu while standby or running. Press this key to return while
Menu key modify parameter. While standby or running, press for 1 sec to enter
condition monitoring interface.
Press to modify parameter while in menu interface.Press again to confirm
Confirm/modify
after modifying. While standby or running, press to change LED
key
monitoring items at stop.

Select parameter group in menu interface. Modify parameter while in


Up/down key modify interface. Modify given frequency, PID, given torque or magnetic
powder clutch given torque while at standby or condition monitoring state.

Select digit of function no modified by up/down key;Select parameter


Shift key digits modified by up/down key. Change LED monitoring items while
standby or running.
While run/stop is controlled by keyboard, press this key, the inverter
Forward run key forward rotate and the indicator is always on. While reverse, the indicator
sparks.
This key function can be defined by parameter [E-08]. Press it, machine
Jog/reverse key reverses and indicator is off if this key is defined as REVERSE. Machine
will jog and indicator is on if this key is defined as JOG.
Machine stops if press it while run/stop is controlled by keyboard. Its
Stop/reset key efficiency range is defined via function no [F-07]. Inverter resets if press it
in fault state (no reset if fault is not solved).

Keyboard Can be used as input channel for given frequency, upper frequency limit,
potentiometer given torque, given PID or PID feedback setting.

38
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

● Indicator light meanings

Name State Meaning


Hz Spark Digital display given frequency.
Hz On Digital display output frequency.
A On Digital display actual output current.
V On Digital display input voltage.

Unit indicator V Spark Digital display output voltage.


light S On Time unit is second.
S Spark Time unit is ms, min, or h.
RPM On Digital display motor speed.
% Spark Digital display given PID.
% On Digital display PID feedback.
FWD On Inverter is forward rotating.
State
FWD Spark Inverter is reverse rotating.
indicator light
FWD Off Inverter stops.

Function REV/JOG On Jog.


indicator light REV/JOG Off Reverse.
Chart 4-1: Indicator light meanings
● Number and character table

Chart 4-2:Number and character table

39
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

●LED keyboard stamp explain:


Stamp Explain

Frequency inverter stop

FWD

REV

JOG

REV second stamp

Remind press key

Remind press key

Cursor can up or remind up

Cursor can down or remind down

It flashing means fault

Arrowhead direction

Terminal not connect

Terminal connect

Two relay output: one on, another off

4.3 Basic Operation


4.3.1 Menu Structure and Operation
AC70 series frequency inverter parameter setting adopts 3 groups of menus which can be checked and modified easily.
Three menus are basic parameter, external terminal parameter and special function parameters. Operation method:
PRG PRG PRG

Standy or running Basic parameter External terminal parameter Special function parameters

PRG

Chart 4-1: FWD/REV and 3 groups of menus switch operation


Note: One line display and dual line display keypad has the same operation process and operation method.

40
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

4.3.2 State Display Switching


The LED display kinds of monitor parameters of AC70 series inverter in running or stop mode. User can uses [E-06,
E-07] to select specific monitor parameters in one line display keypad, also can uses [E-06, E-07] to select upper line
display and lower line display contents in two line display keypad.
User can uses SET and shift key to see specific monitor parameter in one-way circulation in one line display keypad or
in two line display keypad. Please refer to following operation flow chart.

1, One line display keyboard cycle switching display.

Chart 4-2: One line display keyboard cycle dislay

41
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

2. Dual line keypad cycle switching display monitor parameters operation flow chart.

Hz A V RPM % Hz A V RPM %

Giving Input voltage


frequency

Hz A V RPM % Hz A V RPM %

Output
Motor speed
frequency

SET SET

Hz A V RPM % Hz A V RPM %
Output
frequency Motor speed

Hz A V RPM % Hz A V RPM %

Output current PID giving value

SET SET

Hz A V RPM % Hz A V RPM %

Output current PID giving value

Hz A V RPM % Hz A V RPM %
SET

Input voltage

PID feedback value


SET

Hz A V RPM %

PID feedback value


SET

Hz A V RPM %

Giving frequency

On Spark Off

SET Change first line parameter by cycle

Change second line parameter by cycle

Chart 4-3: Dual line display keypad cycle display

42
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

4.3.3 Parameter Setting Mode


AC70 series frequency inverter best performance is based on parameter right setting. Here take[F-08]as a sample to
show how to set parameter for both small keyboard and big keyboard.
1, Small keyboard set mode

Stanby or running state


PRG
Enter menu PRG SET Enter parameter modify state

Function paramer no Change digit

Change digit

Find parameter no Display parameter and spark

Enter next menu PRG


Change paramer value

Change digit PRG Back

Find paramerter no SET Confirm

Back menu

Chart 4-4: Small keyboard parameter set

43
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

2, Big keyboard set mode

Parameter no
Stanby or running state PRG
Pameter value

Enter menu PRG SET Enter parameter modify state

Change digit
Function paramer no

Parameter value Parameter no

Change digit Parameter value spark

Find parameter no

Enter next menu PRG Change paramer value

Parameter no
PRG Back
Parameter value

Change digit
SET Confirm
Find paramerter no

Paramerter no Paramerter no

Parameter value Parameter value

Chart 4-5: Big keyboard parameter set

44
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

4.4. Trial Run


● Trial run commissioning guide

Start

Check power connect if corret, motor wiring if correct

Set H-52 to H-56 according


to motor nameplate and wiring

Press JOG/REV to perform jog run

check the direction,if wrong,change wire after cut


power or set E-46 to change the direction

no yes
Whether motor and
load if can dismount

stationary auto tuning,H-62 change to 2. Rotational auto tuning, H-62 is change to 1.


Press FWD,wait for auto tuning stop Press FWD,wait for auto tuning stop

VF control mode Vector control mode


whether motor and
load if can dismout
No. Yes

Set E-00=1,choose VF Set E-00=0,choose vector


control mode control mode

Set run frequency giving


channel E-02

Set start frequency E-28

Set run command giving channel E-01=0

Press FWD to run

Press stop/reset to stop

Trial runn stop

Chart 4-6: Trial run

45
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

● Parameter auto-tuning selection


Motor parameter auto-tuning
start

check inverter power wire connection,check wire connection


between inverter and motor,electrify

set motor rated power H-52 according to nameplate

set motor rated power H-53 according to nameplate

set motor rated speed H-54 according to


nameplate

set motor rated votage H-55 according to


nameplate

set motor rated current H-56 according to


nameplate

yes no
load break off test

set H-62=1, rated self-study,press set H-62=2,static self-study,


SET to enter self-tuning waitting state press SET to g waitting state

press FWD to start self-tuning

yes
self-tuning failture, fault alarm
no parameter renew

detect fault cause,clear


fault ang try again no

self-tuning finished,parameter
H-57-H-61 renewed

over

Chart 4-7: Parameter self-tuning selections

46
keyboard digital =0
giving

keyboard =1
potentionmeter

=2
terminal VS1

=3
analog AS given

E-02
=4
terminal VS2
● Frequency giving flow

channel selection
=5
terminal PUL

frequency giving main


auxilliary channels calculation synthesize
=6
RS485communication

=7
up/down control F0.11
E-05
main frequency reference giving f1
=8
f1 =0
PID control
f2 =1
program control =9 f≤f3 output
frequency f
=10
f1 priority f2=2
reserve
f1+f2*k =3
AC70 VC CONTROL FREQUENCY INVERTER MANUAL

=11
optional card f
E-03 f1-K*f2 =4

47
=12
terminal switch max{f1.k*f2} =5

frequency giving
auxilliary channel
keyboard digital =0 min{f1.k*f2} =6
giving f>f3 output f3
=1 f2+K*f1 =7 frequency
keyboard
potentionmeter

=2
f2-K*f1 =8
terminal VS1 auxiliary frequency reference giving f2

=3
max{k*f1.f2} =9
analog AS given
min{k*f1.f2} =10
=4
terminal VS2

=5
terminal PUL

=6
RS485 communication

=7
up/down control

=8
PID running

=9
PID control

=10 Chart4-8:frequency giving flow


program run
BASIC OPERATION AND TRIAL RUN
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

● Start/stop control flow

F direct start

constant speed
set frequency

start frequency accelerate

E-01
E-28
=0
T
=1 E-29

=2

F braking and start frequency start

constant speed
set frequency

start frequency accelerate


Output frequency
constant speed run

E-28

start
E-38 T
DC baaking E-29
start frequency hold time
run command
stop
speed track restart

E-53

decel eatel energy


stop baaking

E-34
=0
=1
F
constant speed
set
frequency constant speed
stop output
DC baaking
start frequency

E-37

terminal function 6 T
E-36
Xi open braking time
(Xi=X0~X6)
connect

free stop

Chart 4-9: Start/stop control flow

48
AC70 VC CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN

● Open-loop VC control(speed mode)

start

If change motor or electrify for the first time,


please self-tuning according to chart 4-7

set E-00=0,choose VC control mode

according to chart 4-8,set giving frequency

set E-01 to choose run command giving channel

according to chart 4-9,set start/stop control

trial run

whether control performance no


reaches requirment

adjust H-52 H-61 parameters to optimize


yes VC control performance,to improve output
torque/speed accuracy

over

Chart 4-10: Open-loop VC control

49
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING

Chapter 5: Fault Diagnoses and Processing


This chapter explains the display content and processing of the inverter fault, alarm and operation fault. It also simply
explains the bad situation caused by inverter or motor fault and how to solve it. For the adjustment guide in trial run,
please refer this chapter too.
5.1 Fault Types
Type Inverter action while fault happens
While inverter detection fault, the state likes this:
● Keyboard display character showing fault content.
● Inverter stops output. Motor stops free slide.
● While function F-31/F-32 is set as 1(fault output),Y1/Y2 terminals output valid open
Equipment fault collector digital output.
● While function F-30 is 1(fault output), TA-TC terminals output open passive digital
output.
● While there is fault as OL, OC, SC, OV, UL2, if [E-43] is not 0, the inverter will
automatically restart after E-44 setting time.
In certain application occasions, external related equipments fault signals are
considered in the inverter control system as usage of monitoring, protection or switch
External fault
control. At this time, if one multi function terminal is defied as “external fault”, the inverter
stops output alarm signal.
5.2 Fault Information and Details
Keyboard Fault
Fault type Possible causes Treatment
display code
Too low ● Power supply is too low ● Check input power,clear
L.U.1 voltage while ● Voltage detection circuit is fault.
stop abnormal ● Seek support from factory.
● Power supply is too low
● Power capacitance is too ● Check input power,clear
Too low small, or there is big impact fault.
E.LU2
voltage in run current in the power grid. ● Improve power supply.
● Inner DC main contactor is ● Seek support from factory.
not connect well
● Detect power voltage and
● Power voltage fluctuation
clear fault.
Accel. over limit.
E.oU1 ● Restart motor until it
over-voltage ● Start when motor is
completely stop.Set E-30 as
running .
1or2.
● Deceleration time is too ● Prolong Deceleration time.
short. ● Reduce load inertia or
Decel. ● Load potential energy or improve inverter capacitance or
E.oU2
over-voltage inertia is too large. add braking unit.
● Power voltage fluctuation ● Detect power voltage and
over limit. clear fault.
Constant ● Detect power voltage and
● Power voltage fluctuation
E.oU3 speed clear fault.
over limit.
over-voltage ● Install input reactor.

50
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING

● Check input power,clear


Over-voltage ●Power voltage fluctuation
E.oU4 fault.
while stop over limit.
● Seek support from factory.
● Acceleration time is too
● Prolong acc time.
short.
● Restart motor until it totally
● Start running motor.
stop.Set E-30 as 1or2.
Accel. ● V/F curve setting is not
E.oC1 ● Reset V/F curve or torque
over-current suitable.Or torque boost too
boost value.
high.
● Select inverter with right
● Inverter capacitance is too
capacitance.
small.
● Deceleration time is too
● Prolong Deceleration time.
short.
● Connect external braking
Decel. ● Load potential energy or
E.oC2 resistance or braking unit.
over-current inertia is too large.
● Select inverter with right
● Power voltage fluctuation
capacitance.
over limit.
● Check load change and
Constant ● Sudden load change.
clear it.
E.oC3 speed ● Power grid voltage is too
● Check input power,clear
over-current low.
fault.
● V/F curve setting is not
● Reset V/F curve or torque
suitable. Or torque boost too
boost value.
high.
● Check input power,clear
● Power grid voltage is too
fault.
low.
Motor ● Unreasonable H-56 setting.
E.oL1 ● incorrect overload
over-load ● Adjust load or select
protection setting.
inverter with right capacitance.
● Locked-rotor run or too
● If need long time low speed
heavy load.
run,please choose special
● Universal motor long time
motor for inverter.
low speed run.
● Load is too heavy. ● Select inverter with right
● Acceleration time is too capacitance.
short. ● Prolong acceleration time
Inverter
E.oL2 ● Start running motor. ● Restart motor until it totally
over-load
● V/F curve setting is not stop.Set E-30 as 1or2.
suitable.Or torque boost too ● Reset V/F curve or torque
high. boost value.
● Acceleration time is too ● Prolong acceleration time.
short. ● Check periphery
System ● Short circuit between equipments and restart after
E. SC
abnormality inverter output phases or earth. fault cleared.
● Module is damaged. ● Seek support from factory.
● Electromagnetic disturb. ● Check system wiring,
51
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING

earth, shield and deal as


required.
● Temperature is too high. ● Make the environment
● Air channel is blocked. meeting the requirement.
● Fan connection parts is ● Clear the air channel.
Inverter
E.oH loose. ● Check and re-connect the
over-heat
● Fan is damaged. wire
● Temperature detection ● Change the same new fan.
circuit fault ● Seek support from factory.
● Detection overtime
● Check motor connection
● Perform static detection
wire.
while motor is running.
● Detect after motor stop
Motor static ● Capacitance difference is
E.TE1 totally.
detection fault too big between motor and
● Change inverter model.
inverter.
● Reset parameter according
● Motor parameter setting
to nameplate.
mistake.
● Detect while motor is
● Detect after motor stop
running.
totally.
● Detect with load.
● Re-detect without load.
● Detection overtime
Motor rotation ● Check motor connection
E.TE2 ● Capacitance difference is
detection fault wire.
too big between motor and
● Change inverter model.
inverter.
● Reset parameter according
● Motor parameter setting
to nameplate.
mistake.
● Electromagnetic disturb in
● re-input and save.
93SE Memory fault memory period.
● Seek support from factory.
● EEPROM damage.

LIFE Reserved ●Seek support from factory.

● Check 3phase input power


Input phase and phase.
ERR1 ● 3 input phase missing
missing ● Check 3phase input power
wiring.
● Check wire between
Output phase ● 3 phase output of inverter
ERR2 inverter and motor, earth and
missing missing connection with motor
motor insulation.
Current ● Detect circuit fault. ● Seek for technique support.
ERR3
detection fault ● Phase imbalance ● Check motor and wiring.
Inverter ● Peripheral equipment fault
ERR4 ●Check peripheral equipment.
external fault protection.
Swing
● User not set right swing
ERR5 frequency ● Set parameter again.
frequency running parameter.
fault

52
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING

● Keyboard wire fault.


Keyboard ● Check keyboard wire
ERR6 ● Keyboard component
connect fault ● Seek support from factory.
damage.
● Parameter copy
● Check wire.
Parameter communication is fault.
E.CPE ● Select the specified
copy fault ● Copy keyboard is not match
external keyboard model.
the inverter.
● Baud rate not right. ● Set right Baud rate
RS485 ● Communication connection ● Check communication
E.CE communicatio not right. wiring
n fault ● Communication format not ● Check Communication
right. format
● Alarm while PID analog
value feedback signal is small ● Confirm sensor
than [H-28]. state,change it if problem
Feedback
SEn ● PID feedback wire problem. ● Check wiring.
sensor fault
● Feedback sensor problem. ● Adjust feedback channel
● Feedback input circuit signal
problem.
● Keyboard wire fault.
Keyboard ● Check keyboard wire
E.PAn ● Keyboard component
connect fault ● Seek support from factory.
damage.
Inverter ● Peripheral equipment fault
E. EF ●Check peripheral equipment.
external fault protection.
● Keyboard wire fault.
Keyboard ● Check keyboard wire
E.PAn ● Keyboard component
connect fault ● Seek support from factory.
damage.
Chart 5-1: Fault information and details

53
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING

5.3 Fault Diagnoses Process


System fault diagnoses process

system fault

yes
Clear short circuit Whether there is short circuit between outout terminal U/V/W and the motor

no
yes
Short the cable or Cable between output terminal U/V/W and motor
add outout reactor is too long that leakage current cause inverter protection

no
yes
Clear disturbance Is there serious electromagnetic disturbance?

no
yes
While disconnect output wire and run,whether there is system fault alarm

no
no
yes
Connect load and
Three phase outout voltage balance is ok or not?
operate as follows

yes
yes
Reduce load or
Whether overload or not?
enhance power
no no no
no yes
Display E.SC Display E.SC Display E.SC while Display E.SC while
while start while stop constant speed machine stop
yes
yes
yes no
yes
no
Torque enhance value Whether acceleration Whether deceleration Whether load
is suitable or not time is too short time is too short change suddently

no yes yes
yes
no
Torque enhance ACC time can be Dec time can be Reduce load change
valuecan be prolonged or not
reduced or not prolonged or not or enhance power

yes yes yes no

Check braking mode,


Reduce Prolong setting time
seek tec support

Reduce load or Inverter fault or misaction caused by


enhance power noises.Pls find technic support

54
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING

Over current diagnoses process

Accelerate over Decelerate over Constant speed


curent E.0C1 curent E.0C2 over curent E.0C3

yes
Whether short circuit between output terminal
Clear short circuit
U/V/W and motor or earth circuit

no no no

yes
Reduce load or
Whether load is too large
enhance power

no
no
Whether torque
Can be reduced? enhance value is too no no

yes yes

Is acceleration time Is deceleration


Reduce the value
set too short? time set too short?
no
yes no yes

May fault or misaction


caused by noise.Please no
Whether load
find technic support
changes suddently

yes
yes
Set longer acceleration Whether set longer Reduce load change
time or not? decelerationtime or improve power
yes
Prolong setting time
no
no

Reduce load change Check braking mode


or improve power and seek for technic support

55
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING

Over voltage diagnoses process

ACC over DCC over Constant speed Stop state over


voltage(OU1) voltage(OU2) over voltage(OU3) voltage(OU4)

no
Reduce power voltage
Fower votage in fixed range or not
into fixed range

yes yes yes


yes
Clear short circuit Phase or earth short cirsuit bwteen U/V/W and motor

no no no
yes
Stop motor and restart. Whether it stops while restart the motor
Or DC braking,then start
(E-30:1). Or speed track
no no no
start(E-30:2)
Whether act while load suddently changes to"0"

no no no
no

Whether DC circuit voltage of main loop is above protection value while act

Maybe inverter fault or


misact.Plese seek for yes yes yes yes
no
technic support
Whether act while yes
suddently stop ACC Can prolong DCC time or not

yes no
no
yes
ACC time can be
prolong or not prolong

no
yes
Reduce Load intertia can be reduced or not

no no no

Whether used braking unit or DC braking function Use braking unit or DC


braking function
yes yes yes

Please check braking unit and seek for technic support

56
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING

Supply voltage is too low


Voltage is too low Voltage is too low
while stop Lu1 while running Lu2

yes
Restart after reset Whether power off,including instant power off

no no

Change fault component


yes
Is there any fault component or bad contact in power circuit
and correct bad contact

no no
Modify power supply
no
system as required Whether power voltage is in fixed range as required

yes yes
yes
Is there any big load start or stop under the same power supply

no no

no
Adjust E-55 setting votage between DC circuit P+ and N- in
main loop is over E-55 setting or not

yes yes

Maybe inverter fault.please seek for technic support

Inner inverter over heat

Inner inverter
overheat OH

no
Change fan Whether cooling fan works normally

yes
Maybe temperature ditection no
circuit fault.please seek for Whether temperature display(C-09)is
technic support the same as the actual temperature

yes
yes
Reduce load and Whether load and carried frequency
carried frequency E-20 setting are too high

no
yes
Clear the air-logged channel Whether air cooling channels are air-logged

no
Adjust the temperature to no
the fixed range as required Whether the temperature is within the fixed range as required

yes

Maybe machine fault or misact.seek for technic support

57
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING

Over load

Motor overload OL1 Inverter overload OL2

no Whether electric thermal relay overload


Change externa
characteristic matches the motor overload
lthermal relay
characteristic

yes
no
Whether electric thermal relay overload
Correct setting value
relay setting E-50 is suiable

yes
Reduce load or yes
improve capacity Whether load too high

no no
Restart after motor stop or yes
change start mode E-30 Whether the motor stops while restart
to 1/2

no no
yes
Prolong ACC/DCC time Whether ACC/DCC time is too short

no no no
Change torque improving
Whether torque improving or V/F curve setting is suitable
or V/F curve setting

yes yes

Maybe inverter fault or misact.Please seek for technic support

No display

Inverter keyboard
LED no display

Whether keyboard yes Whether power indicater no Whether circuit breaker


connect line is reliable linght on power board is at power side is connect to
on or not contacter
yes
yes no no

connect Whether power input connect


terminals R/S/T is normal
no
yes

Whether there is short connect Find our the fault cause


or DC reactor between terminals and clear the fault
P1 and P+l
no

yes

Maybe inverter fault or motor heat Short connect or


caused by noise.Please find technic support connect DC reactor

58
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FAULT DIAGNOSES AND PROCESSING

Motor heat

motor heat

no yes
Adjust torque imporoving Whether torque improving and V/ Whether motor continuously
value and V/F characteristic F characteristic are suitable or not run at low speed
no

yes
yes
Reduce load or
Whether load is too large Use special motor for inverter
improve capacity

no

yes
Whether output terminals U/V/W output
voltage /current three phase balance well Maybe motor fault

no

Maybe inverter fault or motor heat caused by


noise.Please find technic support

Motor does not rotate

Motor does
not work

yes no
Work after solving Whether keyboard Have input command
fault and reset displays fault information signal or not
yes
no
no
It works after checking
Have input frequency It works after checking the
the cause and solving
signal or not cause and slving the problem
the problem

yes
yes It works after correct the
Whether upper frequency limit E-10 or given frequency
upper frequency or given
is lower than the start frequency E-28 setting frequency
yes

no
Is there voltage output on output terminal U/V/W Maybe inverter fault .Please
and three phase balance ok or not? find technic support

yes
yes
no
Whether load Whether wiring is
is too large Correct connect
correct or not
yes
no
no
Motor fault Whether torque improving Improve torque
value is suitable improving value

yes

Maybe motor is locked because of too large load.Load


should be reduced.If there is braking or brake uni,
please check whether it is loose

59
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIODIC OVERHAUL AND MAINTENANCE

Chapter 6: Periodic Overhaul and Maintenance


6.1 Safety Precautions
This chapter explains the safety rules in overhaul and maintenance.
● No operation under power connected state. Otherwise there is danger of electric shock
death.
● Before operation, please cut all related equipments power, ensure that the main circuit
DC current has dropped to safe range. And please operate after 5 mins.
● No operation while cover/panel is dismantled. Otherwise there is danger of electric shock
death.
● Do not dismantle the cover or PCB under power connected state. Otherwise there is
danger of electric shock death.
● Only professional person can maintain or change fittings. Otherwise there is danger.
● Do not ware loose clothes while install, debug, maintain. Rated protective tools and
safeguard should be adopted.
● Tighten screw according to named moment. If main circuit wire connection is loose, there
is danger of overheat fire.
● Machine and motor earth must be reliable. Otherwise there is danger of electric shock if
touches the cover.
● While operation, please follow the ESD regulations. Otherwise the inverter maybe
damaged.
● Do not change the circuit or structure of the inverter. Otherwise the inverter maybe
damaged.
●Please confirm the rotate direction while no-load.Wrong direction can bring body injury or
huge wealth loss.
● Do not use damaged machine. Otherwise there is danger of accident.
6.2 Overhaul
Frequency inverter is composed by semi-conductive component, passive electronic component and motive component.
All of these components have useful life. Even under normal working environment, some of the components can not
work after the life time. To avoid malfunction, daily checking, periodic overhaul, component changing and other
maintenance should be carried out to prevent. We suggest one overhaul every 3-4 monthes after installation. The
overhaul period should be shorter while under cases as below.
High temperature, high altitude;
Start and stop frequently;
AC power supply or load fluctuates badly;
With bad wave or impact;
With dust, metal dust, salt, vitriol, chlorine;
Bad store condition;
● Daily checking
To avoid machine damage and to prolong life time, please check the following items every day.
Items Checking content Treatment
Check if power supply meets the
Power supply requirement and whether there is Treat it as nameplate explains.
lack-phase.
Check whether it meets the table3-1
Surroundings Make sure the problem and solve it.
requirement.
Check whether the inverter or the motor Check whether it overload. Tighten screw.
Cooling system heat or change color abnormally and cooling Check whether cooling fan is dirty or rotate
fan working state. block.
Tighten machine and electric connection
Motor Check if there is abnormal vibration or noise.
and lubricate the machine components.
Check whether output current is over the
Make sure whether it overload and whether
Load rated value of the motor or the inverter and
the machine model is right.
have lasted for a period.

60
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIODIC OVERHAUL AND MAINTENANCE

:No operation under power connected state. Otherwise there is danger of electric shock death. Before
operation, please cut all related equipments power, ensure that the main circuit DC current has dropped to safe range.
And please operate after 5 mins.
● Periodic overhaul
Under normal state, one overhaul every 3 or 4 months is ok. Please confirm the actual overhaul period according to the
machine use condition and work circumstance while using the machine.
Main circuit
Items Checking content Treatment
Check insulated resistance; Tighten and change bad component;
Whole body
Check circumstance. Clear and improve circumstance
● Check whether the wire and
connector color changes, whether there ● Change bad wire.
is disrepair , crack color change or ● Fasten terminals and change bad
Electric connection aging in insulated layer. terminals.
●Check whether the connect terminals ● Measure earth resistance and fasten
are damaged or loose. earth terminals.
● Earth checking.
● Check if there is abnormal vibration ● Tighten, lubricate and change the bad
Mechanical connection
or noise or something is loose. machine components.
● Check whether there is dust or
semi-conductive ● Clear
rubbish.
component ● Change damaged component
● If there is obvious out change?
● Whether there is liquid leak, color
Electrolytic capacitor change,or creak? Whether there is ● Change damaged component
safety valve outcrop, inflation, creak or
liquid leak.
●Peripheral equipment outlook and
Peripheral equipment ●Clear and change damaged component
insulation checking.
●Fasten connector
●Bad smell,color change, bad rust and
PCB ●Clear PCB
connector checking.
●Change bad PCB
● Check whether the fan is damaged
or blocked up.
●Whether rubbish and dust is sticked ● Clear
Cooling system
to the heat sink . ● Change damaged component
●Is air inlet/outlet blocked? Or is there
something sticking to the inlet/outlet.
● Whether is it damaged? Check
Keyboard ● Change damaged component
whether display is complete.
●Check if there is abnormal vibration ●Tighten machine and electric connection
Motor
or noise. and lubricate the machine components.

:No operation under power connected state. Otherwise there is danger of electric shock death. Before
operation, please cut all related equipments power, ensure that the main circuit DC current has dropped to safe range.
And please operate after 5 mins.
6.3 Maintenance
All equipments and components have useful lifetime. Right maintenance can prolong the lifetime. But it can not avoid
damage. Please change the components before their lifetime over.

Component Useful lifetime


Fan 2~3year
Electrolytic capacitor 4~5 year
PCB 8~10 year
61
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIODIC OVERHAUL AND MAINTENANCE

● Fan
While changing fan, please use original fan. You can contact Veichi company or the dealer. There are inverter models
with many fans in one machine. To prolong these machines lifetime, you had better change all fans while changing the
cooling fan.
● Fan change method:

1, Install the fan vertically into the cover as shown in the picture (the label should face the outside).

2, Press the elastic clip of the fan by finger toward the inner side and insert the leading terminal of the fan vertically by a
little strength.

3, Insert the two elastic clips of the fan cover vertically into the fan installation slots.

62
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIODIC OVERHAUL AND MAINTENANCE

● Fan dismantlement:

1, Pinch the two elastic clips of the fan and pull out. Then dismantle the fan cover.

2, Press the elastic clip of the fan by finger toward the inner side and pull out the leading terminal of the fan vertically by
a little strength.

3, Poke the clips toward the outside and detach the fan from the cover by a little strength.

:1, No operation under power connected state. Otherwise there is danger of electric shock death. Before
operation, please cut all related equipments power, ensure that the main circuit DC current has dropped to safe range.
And please operate after 5 mins.
2, While the inverter is working, the heat sink temperature will be higher as the consumption. To prevent from scald,
please do not touch the heat sink and do not change the fan until the temperature being safe.
3, To ensure the best performance of the inverter, please use the original fan.
●Other components
The replacement of the other components has strict requirements on maintenance technique and product familiarity.
And they can not be used without strict detection after replacement. So we do not suggest the user to replace the other
inner components. If they need to change indeed, please contact to the dealer or the sales department of Veichi electric
company.

63
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIPHERAL EQUIPMENTS AND OPTIONS

Chapter 7: Peripheral Equipments and Options


7.1 Safety rules
User must obey to the following safety rules and related requirements while using the peripheral equipments and
options.
● No operation under power connected state. Otherwise there is danger of electric shock
death.
● Before operation, please cut all related equipments power, ensure that the main circuit
DC current has dropped to safe range. And please operate after 5 mins.
● No operation while cover/panel is dismantled. Otherwise there is danger of electric
shock death.
● Do not dismantle the cover or PCB under power connected state. Otherwise there is
danger of electric shock death.
● Only professional person can install, debug or maintain the peripheral equipments and
options. Otherwise there is danger.
● Do not ware loose clothes while install, debug, maintain. Rated protective tools and
safeguard should be adopted.
● Do not change wire, dismantle jumping wire, optional card, or change cooling fan while
the inverter is running. Otherwise there is danger of electric shock death.
● Tighten screw according to named moment. If main circuit wire connection is loose,
there is danger of overheat fire.
● Earth of the peripheral equipments and options must be reliable to prevent human body
injury.
● While operation, please follow the ESD regulations. Otherwise the inverter may be
damaged.
● Do not cut the power supply while the inverter is outputting voltage. Otherwise the
inverter may be damaged.
7.2 Peripheral Equipments
Normal peripheral equipments are showed as below. To order the peripheral equipments, please consult our dealer or
sales department.

Peripheral equipment Functions

Protect power system and prevent malfunction impact other


Breaker equipments working when short-circuit happens. And
over-load protection.

Earth protection prevent electric shock(suggest to use the


Leakage current breaker
type which can prevent high-frequency leakage current)

Separate power and inverter indeed and realize basic relay


Electromagnetic contactor
control.

Improve power side factor and isolate the noise disturbance


AC input reactor
to the frequency inverter from the power side.

DC reactor Restrain ultra harmonics and improve power factor.

64
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIPHERAL EQUIPMENTS AND OPTIONS

Reduce frequency inverter disturbance to the power and


Input side noise filter
reduce the power grid disturbance.

Braking resistor Passive energy consume unit of electric braking.

Electric braking control unit, controlling the braking


Consumption braking unit resistance consume the regenerated electric power of the
motor efficiently.

Output side noise filter Reduce the output side wire electromagnetic disturbance.

Standby system Standby system for inverter malfunction.

Heat relay Protect the motor while over load.

Reduce electromagnetic disturbance of the frequency


0-phase reactor
inverter (suitable for input/output side).

Restrain surge voltage while main loop switch components


Main loop surge absorbable unit
act.

Winding surge absorbable unit Restrain surge voltage when the AC contactor acts.

65
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIPHERAL EQUIPMENTS AND OPTIONS

7.3 Use of Peripheral Equipments

Chart 7-1:Peripheral equipments connection fig


Note:
Wiring breaker
To ensure wiring safe, protect power system and prevent malfunction expand to impact other equipment working while
short-circuit happens, and protect while over-load, please do use wiring breaker between power supply and main loop
power input terminals R,S,T.
: While choosing the breaker, the capacitance should be 1.5-2 times of the rated output current of the
frequency inverter. Please compare the time characteristic and protective time to the inverter (150% of the rated output
current, one minute). Make sure there will be no skip.
: Before main loop wiring, make sure to cut the breaker and electromagnetic contactor. Otherwise there is
danger of electric shock.
Leakage current breaker
The frequency inverter outputs peak voltage high-speed switch square wave. So there is high-frequency leakage
current. For earth protection to prevent electric shock and leakage current fire, please install leakage current breaker.
Usually, one set frequency inverter will bring 100mA leakage current (while the power cable length is 1m). If the length
prolongs 1m, there will be 5mA more leakage current. So please use leakage current breaker special for high frequency
leakage at the power input side of the frequency inverter. The factors which impact leakage current are as below:
Capacitance of inverter
Carrier frequency
Motor cable type and wire length
66
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIPHERAL EQUIPMENTS AND OPTIONS

MI/RFI filter
To protect human body and inverter, please choose leakage current breaker which can use AC/DC power and can face
high frequency leakage current. There should be one leakage current breaker with more than 200mA sensitive current
for every frequency inverter. If the frequency inverter outputs different wave, the high frequency leakage current can be
higher, which will lead to breaker fault. In this case, please take below treatments:
Improve the sensitive current of the leakage current breaker
Reduce the carrier frequency of the inverter
Electromagnetic contactor
Electromagnetic contactor is a peripheral equipment what is set to actually separate power and inverter connection.
While inverter protective function is acting or carrying out emergency stop operation, the main loop power can be cut by
peripheral equipment. Please do not connect the electromagnetic switch or electromagnetic contactor to output circuit.
Otherwise the inverter may be damaged. While the power recovers after instant stop, if it needs to prevent the inverter
to auto-restart, please install electromagnetic contactor for control at the input side.
AC input reactor and DC reactor
To restrain current sharp change and high hypo harmonic current, it needs to use AC input reactor and DC reactor. It
can also improve power factor at the input side. In the following cases, AC input reactor or DC reactor must be used
(use both will bring better effect).
Need to restrain high hypo harmonic current and improve power side factor;
Need to switch input phase capacitance;
Frequency inverter is connected to large capacitance power transformer (600kVA above);
Silicon-controlled converters such as DC motor driver are connected to the same power system.
If user has higher requirement on other harmonic restraint, please connect the external DC reactor. Before connect the
external DC reactor, make sure to dismantle the short connector between the terminals P1 and (+).
Surge restrainer
Surge restrainer is divided into winding surge restrainer and main loop surge restrainer according to the use position.
Pls choose the right one which is suitable for the occasion. The aim of surge restrainer installation is to restrain the
surge voltage brought by switch components such as inductive load which is surrounding the frequency inverter
(electromagnetic contactor, electromagnetic relay, electromagnetic valve, electromagnetic winding). Do not connect the
surge restrainer to the output side of the frequency inverter. Otherwise the frequency inverter will be damaged.。
Input side noise filter
Rectifier bridge of the inverter is uncontrolled rectifier bridge. And input current is discontinuous impulse current. So the
harmonic current noise signal, which flows to power wire from the inverter inner, may bring bad impact on the
surrounding machines (radio, phone, non contact switch, sensor). This time, we suggest to install input side noise filter
to lighten the noise into the power wire. Besides, it can also reduce noise from the power wire into the frequency
inverter.

: Please use the noise filter special for the frequency inverter and the connection wire between the filter and
the inverter should be as short as possible.
Output side noise filter
The frequency inverter outputs square wave with high-speed peak value voltage switch. So there is high-speed dv/dt
converter on the output cables that will produce a large number of radio disturbance and inductive signal. By installation
noise filter at the output side, the impact can be relieved. Please do not install the input-phase capacitance and the
noise filter to the output circuit. Otherwise there is danger of damage to the frequency inverter.
0-phase reactor
0-phase reactor is used to reduce the electromagnetic inductive disturbance of the frequency inverter, which is suitable
for the input side and output side. It equals to a three-phase common mode inductance. In actual use, according to the
actual magnetic core size and cable specification, it is better to make sure 3-5 circles winding ratio to bring the best
performance.
Braking reactor or braking unit
Renewed power consumption unit, please see the sixth part of the chapter three “electric installation”.
Heat relay
Please install the heat relay at the output side of the frequency inverter. When the motor enters into overload state, it
will cut the power source to protect the motor. While using one frequency inverter to run one motor, there is no need to
install heat relay. The motor overload protection current [E-49] of the frequency will work. While using one frequency
inverter to run multi-motors or the motor is run directly by the power grid, please install heat relay between the
frequency and the motor. While installing the heat relay, please design to cut the sequence control circuit of the MC at
the main loop input side by the connection spot of the relay or design to input the heat relay action into the frequency
inverter as the exterior malfunction.And please pay attention to the following tips to avoid heat relay fault and motor
overheating at low speed.
67
AC70 VC CONTROL FREQUENCY INVERTER MANUAL PERIPHERAL EQUIPMENTS AND OPTIONS

Run at low speed


One frequency inverter run multi motors
Motor cable is very long
Detect malfunction mistakenly for carrier frequency is too high
Low speed and heat relay
In normal case, the heat relay is suitable for the universal motor. While using the frequency inverter to run the universal
motor (standard motor), the motor current is 5-10% bigger, comparing with the commercial power supply. Besides, at
low speed, even in the motor rated current range, the cooling capability of the fan driven by the motor axis will reduce,
which will bring motor overheat. So please set the motor overheat protection current [E-49] in the frequency inverter to
be valid.
Motor cable is very long
While the motor cable is very long and the carrier frequency is very high, impacted by the leakage current, the heat
relay may fail. To avoid it, please reduce the carrier frequency or set higher detection value of the heat relay. Before
enhancing the detection value, do confirm whether there is other cause for the motor overheat. Otherwise there is
danger.

68
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Chapter 8: Function Parameters Specification


8.1 Basic Parameters Specification
E-00 control method selection range:0-1 Default: 1

0: Open loop vector control without PG Also call sensorless vector control mode, are suitable for application
one inverter drive one motor which need high performance control requirement. It can achieve fast torque response,
wide speed control range and high torque output even under low speed without motor feedback.

Note: It needs to perform motor auto tuning with configure motor parameters correctly before first time
running with this control mode.

1: V/F control mode Adjusting the speed with V/F ratio, Use this mode for simple speed control and for multiple
motor applications with low demands to dynamic response or speed accuracy. This control mode is also used when
the motor parameters are unknown and Auto-Tuning cannot be performed. The speed control range is 1:40.

Running control command


E-01 Setting range:0-2 Default: 0
channel selection

Uses for selecting inverter running, stop and running direction command input channel.
0: Operator keypad Running and stop of inverter control by forward running key FWD, reverse running or Job
key REV/JOG and stop key STOP/RESET of operator keypad. When [E-08] parameters set to 0, REV/JOG is
defined for reverse running, when [E-08] parameter set to 1, REV/JOG is defined for JOG running.
1: External terminal control Running, stop and rotation direction of inverter control by ON and OFF of FWD
terminal or reverse terminal. Please refer to [F-08].
2: RS485 Communications port control Running, stop and rotation direction of inverter control by given signal
of RS485 control port.

Note: STOP/RESET of keypad, reset command from control terminal or RS485 communication are all
enabled when fault reset.
Tips: 1. The running direction of inverter control is disabled by this command when programming control
and (VS2) terminal input bipolar adjustment, direction control is valid.
2. STOP/RESET key function is programmable, it can be defined emergency stop button function
when selecting external terminal control or RS495 control, refer to [F-07]; If use STOP/RESET
button on keypad to stop inverter when selecting external terminal control, inverter will be stop and
locked the external terminal command, it need to input external terminal stop command to unlock it,
and then external terminal running command will be activated again. It is the same for RS485
communication control.
3. When selecting operator keypad control, direction control by external terminal takes is priority to
control by keypad; it means that when reverse terminal and COM is on, if the direction command is
changed by keypad, it will be keep the same original running direction after the terminal and COM is
off.

Frequency reference given


E-02 Setting range:0-12 Default: 1
main channel selection

It is used for selecting main frequency reference given of inverter, the frequency given will control or affect the
output frequency of inverter; terminal (VS2) analog voltage signal and program control channel also will control the
running direction of inverter directly.
0: Operator keypad digital Main frequency reference given by parameters [E-16] configuring: it is available to
modify the [E-16] preset value via up/down arrow button on keypad when inverter in running status or stop state.
1: Potentiometer of keypad Main frequency given is determined by potentiometer of keypad.
2: Terminal VS1 analog voltage 0-10V Main frequency given determined by control terminal VS1 analog input,
Regarding the relationship between input analog and frequency, filter time of input analog, Please refer to
parameters in detail [F-41, F-42, F-43, F-56, F-57, F-58] parameters

69
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

3: Terminal AS analog current signal 4-20mA Main frequency given is determined and modified by ( AS)
analog current input; Regarding the relationship between input analog and frequency, filter time of input analog,
Please refer to parameters in detail [F-50, F-51, F-52, F-56, F-57, F-58].
4: Terminal VS2 analog voltage -10-10V Main frequency given is determined and modified by control terminal
VS2 analog input, Regarding the relationship between input analog and frequency, filter time of input analog,
Please refer to parameters in detail [F-44, F-45, F-46, F-47, F-48, F-49, F-56F, -57, F-58]
5: Pulse train signal Main frequency given is determined and modified by control terminal (PUL) analog input,
Regarding the relationship between input analog and frequency, please refer to parameters in detail [F-53, F-54,
F-55, F-56, F-57, F-58]
6: RS485 communication port Main frequency given is determined by receiving signal of (A+) and (B-) of
RS485 communication port.
7: Up and Down control Main frequency given is determined by increasing UP and decreasing (DOWN) terminal
connecting or disconnecting( ON/OFF) with COM terminal; each of multi- terminal ( X1-X6) can be programmed by
frequency UP terminal and DOWN terminal, refer to [F-01-F-06] in detail; Initial frequency of up and down terminal
control can be configured, please refer to parameter [F-07] LED ten digit option and [F-70].
The acceleration and deceleration time of UP and Down control running is determined by acceleration/ deceleration
time 1 [E13-E-14] setting; The rate of speed change of Up and Down terminal is determined by acceleration/
deceleration time 2 [F-24-F-25] setting.

8: General PID operation Select it use to set up general PID close loop control system. When it has been applied,
the [H-16] present setting value can be modified by up and down arrow button of keypad.
9: Constant pressure PID control It can be used to set up constant pressure PID control ( constant pressure
water supply system etc) close loop system, the [H-16] present setting value can be modified by up and down
arrow button of keypad.
10: Program running Main frequency given and rotation direction are configured by inverter’s inner simple PLC
process control. Up to 8 steps speed control is available, more detail refer to [E-13, E-14, F-09-F-16, F-24-F-29,
H-32-H-51].
Run and stop command of program running determined by present setting value of running control command
selection.
When a step running time is set to 0, it means it will skip over this step when perform the program running. It is
easy to set up the steps required of program running.
When [E-46] parameter is set to 2 for forbidding reverse running, inverter will be run at 0 speed when arriving to a
step which have been set to reverse running.
Program running and multi-step speed operation are designed to achieve inverter variable-speed operation under a
certain laws. Among the multi step operation, multi step speed switch over and rotation direction changing are
achieved through the different combinations of external multi-step speed terminal with COM terminal ON and OFF.
Multi step frequency, operation time, rotation direction can be defined by function parameters. Multi step speed
control can be defined by each multi-function terminal, Please refer to [F-01-F-06] parameters.
11: Swing frequency run Output frequency periodically changes by pre-set decel & accel time. This function
70
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

is especially applicable to system which speed change vary with before and after the bobbin diameter in textile
field.
12: Terminal selection The main frequency given channel programmed by terminal selection, refer to the
parameter [F-01-F-06]
The relationship between terminal mode and frequency given channel as following table:
Frequency Frequency Frequency Frequency
given selection given selection given selection given selection Frequency given channel
terminal 4 terminal 3 terminal 2 terminal 1
OFF OFF OFF OFF Operator keypad digital
OFF OFF OFF ON Potentiometer of keypad
OFF OFF ON OFF Terminal(VS1) voltage signal
OFF OFF ON ON Terminal (AS) current signal
OFF ON OFF OFF Terminal (VS2) voltage single
OFF ON OFF ON Terminal pulse train signal
OFF ON ON OFF RS485 communication port
OFF ON ON ON UP/Down control
ON OFF OFF OFF General PID operation
ON OFF OFF ON Constant pressure PID control
ON OFF ON OFF Program running
ON OFF ON ON Swing frequency run
Tips: Frequency reference terminal valid combinations are 0-11(decimal), if not among this range, output
frequency will be 0. The OFF of table stands for corresponding terminal with COM is disconnect, ON
stands for corresponding terminal with COM is connect.

Frequency reference given


E-03 Range:0-10 Default: 0
auxiliary channel selection

Used for selecting frequency reference given auxiliary channel. The combination mode of auxiliary and main
channel programmed by [E-05] parameters
0: Operator keypad digital given Auxiliary frequency given is set by up and down arrow key of keypad or
parameters [E-16] configuring.
1: Potentiometer of keypad Auxiliary frequency given determined by potentiometer of keypad.
2: Terminal VS1 analog voltage 0-10V Auxiliary frequency given is determined and modified by control terminal
VS1 analog input.
3: Terminal AS analog current signal 4-20mA Auxiliary frequency given is determined and modified by (AS)
analog current input.
4: Terminal VS2 analog voltage -10-10V Auxiliary frequency given is determined and modified by control
terminal VS2 analog input.
5: Pulse train signal Auxiliary frequency given is determined and modified by control terminal (PUL) analog input.
6: RS485 communication port Auxiliary frequency given is determined by receiving signal of (A+) and (B-) of
RS485 communication port.
7: Up and Down control Auxiliary frequency given is determined by increasing UP and decreasing DOWN
terminal connecting or disconnecting( ON/OFF) with COM terminal; each of multi- terminal (X1-X6) can be
programmed by frequency UP terminal and DOWN terminal, refer to [F-01-F-06 ]in detail; Initial frequency of up
and down terminal control can be configured, please refer to parameter [F-07] LED ten digit option and [F-70].
8: General PID operation Selects it use to set up general PID close loop control system. When it has been applied,
the [H-16] present setting value can be modified by up and down arrow button of keypad.
9: Constant pressure PID control It can be used to set up constant pressure PID control (constant pressure water
supply system etc) close loop system, the [H-16] present setting value can be modified by up and down arrow
71
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

button of keypad.
10: Program running Main frequency given and rotation direction of inverter are configured by inverter’s inner
simple PLC process control. Up to 8 steps speed control is available, refer to [E-13, E-14, F-09-F-16, F-24-F-29,
H-32-H-52]
Tips: Frequency main channel and frequency auxiliary channel can be set the same channel. In this case,
the corresponding relationships between the frequency setting values and input signal are rather special, it
need to consider the frequency main channel and auxiliary channel both characteristic at the same time.
The combination of main and auxiliary frequency given still limited by upper frequency limit and lower
frequency limit.

Frequency reference given


E-04 Range:0.01-5.00 Default:1.00
channel gain
Frequency reference given
E-05 Range:0-10 Default: 0
channel combination mode

Frequency reference given channel gain: Uses to amplify or lessen the frequency input channel signal.
Proportional regulating of frequency given both main and auxiliary channel is available.
Frequency given channel combination mode: Uses for selecting frequency given main channel and auxiliary
channel combination. K stands for [E-04] setting value, MAX means takes the bigger among the both channel, MIN
means takes the smaller among the both.
0:Main channel is valid, auxiliary channel is invalid.
1:Auxiliary channel valid, main channel invalid
2:Both channel non “0” value valid, main channel priority
3:Main channel + ( K × auxiliary channel)
4:Main channel -(K × auxiliary channel)
5:MAX [main channel , (K × auxiliary channel)]
6:MIN [main channel , (K × auxiliary channel)]
7:Auxiliary channel + (K × main channel)
8:Auxiliary channel - (K × main channel)
9:MAX [(K × main channel), auxiliary channel]
10: MIN [(K × main channel), auxiliary channel]
Tips: 1. Terminal (VS2) will be quite special in the multi-channel combination case.
A. When (VS2) terminal don not activate the bipolarity adjustment and direct control function both ([F-48] set to 0),
the combination mode determined [E-05] combination mode setting.
B. When (VS2) terminal activate the bipolarity adjustment and direction control function both ([F-48] set to 1 ),
( VS2 ) terminal frequency given with bipolarity and frequency given in another channel implement signed arithmetic
based on the combination mode selected, the absolute value is for frequency given, the signed determine the
direction rotation of motor after calculation.
C. When (VS2) activate the bipolarity adjustment but no direction control. ([F-48] set to 2 ). ( VS2 ) terminal
frequency given with bipolarity and frequency given in another channel implement signed arithmetic based on the
combination mode selected, the absolute value is for frequency given, the rotation direction depend on the[E-01]
Running control command selection.
2. Swing frequency running, jog function and multi-step is disabled combine with auxiliary channel.

E-06 Upper LED monitor selection Range:0-7 Default:0


E-07 Lower LED monitor selection Rang:0-7 Default:1

Uses to select the monitoring items displayed in two LED on the keyboard respectively. In the monitoring status, the
upper LED monitoring item and the lower monitoring item can be modify directly via SET key and SHIFT key.
0: Frequency reference Given 1: Output frequency 2: Output current 3: Input voltage
4: Output voltage 5: Machine speed 6: PID given 7: PID feedback value
When there is only one LED on the keyboard, it is disable to modify the lower LED monitoring via the [E-07] and
SHIFT key.

72
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

E-08 REV/JOG key of keypad function selection Range:0,1 Default: 0

Uses to select REV/JOG key of keypad function


0:Reverse This key is defined as reverse key(at this moment , keyboard functional indicator REV / JOG is not
light). When the running control command selection is programmed as Operator keypad control , press this key ,
frequency inverter will perform reverse running.
1: Jog This key is defined as jog running key(at this moment , keyboard functional indicator REV / JOG is light).
When the running control command selection is programmed as operator keypad control, press this key, frequency
inverter will perform job running.

E-09 Maximum frequency Range:0.01-600.0Hz Default:50.00Hz


Range: lower limit frequency-
E-10 Upper limit frequency Default:50.00Hz
maximum frequency
E-11 Lower limit frequency Range: 0.00-Upper limit frequency Default:0.00Hz
E-12 Lower limit frequency running mode Range:0,1 Default:1

Maximum frequency: Maximum frequency of [E-09] is the maximum allowable output frequency of inverter
frequency, also is the reference point of acceleration and deceleration time setting.

Upper limit frequency: Output frequency upper limit value which is set base on the highest allowable speed of
machine. When the frequency given is higher than upper limit value, the actual running frequency is upper limit
frequency.

Lower limit frequency: Output frequency lower limit value of inverter. When the frequency given is lower than
lower limit value, the actual speed depend on the [E-12] setting.
Maximum frequency, upper limit frequency and lower limit frequency should be cautiously set base on the
nameplate parameter of actual control motor and the need of the running conditions.
Except of upper limit frequency and lower limit frequency, the output frequency while inverter running is limited by
parameters setting of start-up frequency, free stop frequency, DC braking stop initial frequency, jump frequency and
so on. The relationships between the maximum frequency, upper limit frequency and lower limit frequency is shown
as the follow Fig.

Maximum frequency, upper limit frequency and lower limit frequency relationship. Fig.
Note: Lower limit frequency range is disabled for Jog function, only the upper limit frequency range is
enable for Jog function.
If the lower limit frequency operation mode [E-12] set to 0, the frequency given lower than the lower limit frequency,
the inverter would be run at 0.

If the lower limit frequency operation mode [E-12] set to 1, the frequency given lower than the lower limit frequency,
the inverter would be run at lower limit frequency.

73
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

E-13 Acceleration time 1 Range:0.1-6500.0s Default:※


E-14 Deceleration time 1 Range:0.1-6500.0s Default:※

Acceleration time 1: when[E-15]LED tens digit place to 1, it defined required time of out frequency accelerates
from 0.00Hz to maximum frequency[E-09], when[E-15]tens bit place to 0, it defined required time of output
frequency accelerates from 0.00Hz to motor rated frequency, refer to[E-15].

Deceleration time 1: when [E-15] tens digit place to 1, it defined required time of out frequency decelerates from
maximum frequency [E-09] to 0.00Hz , when [E-15] tens bit place to 0, it defined required time of output frequency
decelerates from motor rated frequency to 0.00Hz, refer to [E-15].

Note: 1. In the general circumstance ( no special specify ), the acceleration/ deceleration time 1 is default
setting. The acceleration time is only valid for normal acceleration running, not including the DC
braking starting time and DC braking starting frequency holding time. The deceleration time only
for normal deceleration running, not includes DC braking stop time.
2. If activate the equidistant function, inverter would be accelerate base on the accel. time 1, but
decelerates based on equidistant stop decel. time setting. Refer to [E-15].
3. If need apply other accel. & decel. time group, should be configure by control terminals setting,
in the program running case, the accel./decel. time 1 is defined for first accel./decel. time, other 3
groups of accel./decel time setting is available, refer to [F-24-F-29]
4. Jog acceleration and deceleration time are programmed by [E-26, E27]separately.

E-15 Accel/decel mode selection Range:0000-0111 Default:0000

LED unit digit: accelerate /decelerate mode.


AC70 series sensorless vector provide 2 kinds accelerate /decelerate mode, both kinds is enable during normal
start, stop, forward and reverse running, accelerate, decelerate process.
0: linear accelerate Suitable for general load.
1: S curve S curve type accelerate/decelerate curve are designed for reducing noise and vibration, reduce
starting and stopping shock or decreasing torque required during low speed, accelerate in short time required
during high speed.ect during accelerate and decelerate process if need.

74
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Frequency Frequency
Motor Motor
Rated freq. Rated freq.

Time Time

Accl.time1 Decel time.1 Accel.time1 Decel.time1

Linear accel./decel. fig. S curve accel./decel. fig.

LED tens digit: Accelerate/decelerate time datum point.


0: Motor rated frequency Accelerate and decelerated time base on [H-53] motor rated frequency parameters
setting.
1: Maximum frequency Accelerate and decelerated time base on [H-09] maximum frequency setting.
LED hundreds digit: Equidistant stop function
0: Disable
1: Enable
Equidistant stop function: Takes the maximum frequency deceleration time as datum line, the inverter stop rotation
running turns as same as the maximum frequency stop rotation turns after inverter performed stop command with
any frequency. For example, the maximum frequency is 60Hz, deceleration time is 1s. If the maximum frequency
decelerate stop rotation turns is 5, so the stop rotation turns also is 5 with 40Hz frequency given. The deceleration
time of equidistant stop during difference frequency given change as following curve diagram show.

Note: 1. This function is disabled when the frequency given less than10% of maximum frequency, the
inverter decelerate based on the deceleration time, it will not performed the equidistant function when the
frequency given less than 10% of maximum frequency.
2. The overvoltage and over current suppression occurs when the deceleration time is too short, the actual
of deceleration time will be longer, and the equidistant function can’t be performed.
LED Thousands digit:
0: Disable
1: Enable

75
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Frequency reference given Rang: lower limit frequency-upper limit


E-16 Default:50.00Hz
by digital keypad frequency

It uses to set or modify frequency reference when the frequency given channel is set to operator keypad digital
given.
Shortcut setting is available as well, changing the frequency reference via up/down arrow key of operator keypad
when inverter running or in standby mode.

E-17 V/F curve mode Range:0-4 Default: 0


E-18 Torque boost Range:0.0%-25.0% Default: ※

V/F curve mode: Uses to select V/F curve mode to meet various of load characteristic requirement. AC70 vector
control inverter provides 4 kinds of fixed V/F curve and one kind of user defined V/F curve. Constant torque curve is
optional for general load and descend torque curve is optional for square torque load such as water pumps and
fans load.etc.
0: Constant torque curve
1: Descend torque curve(1.5 power curve)
2: Descend torque curve(1.7 Power curve)
3: Descend torque curve(2.0 Square curve)
4: User define curve :Inverter runs base on user defined V/F curve,[E-18] function is disable, User can program
appropriate V/F curves according to the load characteristic, for details please refer to[H-01-H-10].

Torque boost: When [E-00] is set to 1(V/F control mode), it is used to enhanced torque output under low
frequency running through output voltage boost compensation, when [E-00] is set to 0 ( OLV control without PG ),
the torque boost improvement follows vector control mode,[E-18]setting parameters is disable.
Torque boost value selecting should be according to load inertia. If the boost value is too big, will result in motor
overexcited running, and motor over heat easily, even worst, inverter will occurs over current fault protection, or
can’t start inverter properly.

76
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

E-19 Filter time 0.01-99.99 Default:※

This function mainly used to torque boost in OLV control mode. The value setting is smaller, the response of torque
boost is faster, the fluctuation of current is bigger, suitable for sudden changing load application; vice versa, the
filter time setting is bigger, the response of torque boost is slower, the fluctuation of current is smaller, suitable for
constant load application.

E-20 Carrier frequency Range:0.7KHz-15.0KHz default:※

This function mainly used to improve the noise emitting and vibration possibility occurs during inverter operation.
The waveform of current will be good when the carrier frequency is bigger, the noise of motor is smaller. It is very
suitable for application that silent required, but in this case, but the switching loss of main component is bigger, the
temperature rise, efficiency reduces, and output power is smaller. Meanwhile, the radio interference will be bigger,
the leakage of capacitor also increases when run in high carrier frequency, that will result in malfunction of residual
leakage protector which if have installed, over current will be possibility occurs as well. When frequency carrier is
low, it is contrary to the phenomenon mentioned above.
The response of difference motors to carrier frequency is different. The best carrier frequency should be adjust to
gain according actual application site. But the carrier frequency should be set smaller for bigger capacity motor.
Veichi reserve the right to restrict biggest carrier frequency.
Carrier frequency Motor noise Electrical interference Switching loss
0.7KHz big small small
8.0KHz ↑ ↓ ↓
15.0KHz small big big
Below 4KW: When the carrier frequency is 6 KHz, rated current is the maximum output current.
5.5KW-22KW: When the carrier frequency is 3 KHz, rated current is the maximum output current.
30KW-75KW: When the carrier frequency is 2 KHz, rated current is the maximum output current.
Above 93KW: When the carrier frequency is 1.5 KHz, rated current is the maximum output current.
Note: In order to obtain better control characteristics, the ratio of the carrier frequency to maximum
frequency of the inverter should not less than 36. If inverter works long-term in low frequency, suggest to
reduce the carrier frequency to reduce the impact of the dead zone time.

E-21 Carrier characteristic Range:0000-1211 Default: 1010

LED unit Digit: Associate of carrier frequency and output frequency configure.
0: Output frequency associate is disabled.
1: Output frequency associate is enabled.

77
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

When the associate of carrier frequency of output frequency is enable, the inverter will adjust the carrier frequency
automatically according the output frequency, this function can improve the torque performance in low speed, if
combine with torque boost function will make performance better in low speed.
LED tens digit: Associate of carrier frequency and module temperature configure.
0: Module temperature associate is valid.
1: Module temperature associate is invalid.
Inverter will reduce the carrier frequency when the temperature of inverter rise, this function can reduce the
switching loss to prevent over heat fault occurs.
LED hundreds digit: PWM mode selection
0: Fixed PWM mode The noise frequency of motor is fixed.
1: Random PWM mode 1 This mode enables the harmonic spectrum of inverter output voltage evenly distributing in
a wide frequency range to inhibit the electrical noise and vibration effectively, carrier frequency is 2.0KHz.
2: Random PWM mode 2 As the same as above mention, but carrier frequency is 2.5KHz.
LED thousands digit: Inhibition of shock.
0: Inhibition of shock is disabled.
1: Inhibition of shock is enabled.

E-22 V/F slip compensation Range:0%-200% Default: 100%

This function enables output frequency of inverter automatically regulate with the load of motor changing. This can
compensate slip frequency of motor dynamically, it enables the motor maintaining a constant rotation speed to
reduce the load changing impacts on the motor speed effectively.

If cooperate with auto torque boost function, the torque performance in low frequency characteristic of inverter will
be significantly improved. The value of slip frequency compensation should be set base on motor rated slip, should
not set the value of compensation too large.

E-23 Energy saving mode selection Range: 0000-0011 Default: 1000

LED unit digit: Auto energy saving selection


0: disable
1: enable
During running process, inverter can automatic calculate the best output voltage to load according to the load
condition for energy saving. Energy saving function works by reducing output voltage, enhancing the power factor
and improve motor efficiency.
LED tens digit: V/F slip compensation
0: Disable
78
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

1: Enable
If only activate the slip compensation function in V/F control mode, this parameters used for selecting slip
compensation function.
LED Hundreds digit: Reserve
LED Thousands digit: Over modulation
0: Over modulation allowed
1: Over modulation not allowed

E-24 Voltage auto regulation function Range:0,1,2,3 Default:2

0: Disable
1: Enable in full process
2: Disable only in deceleration
Output voltage auto regulation function that is AVR function. When AVR function disable, the output voltage change
vary with input voltage. When the AVR enable, the output voltage will keep in setting value as long as the minimum
of fluctuation input voltage bigger than output voltage setting (Motor rated voltage). When the power supply voltage
less than rated output voltage, the output voltage will decrease follow with input voltage.

E-25 Jog frequency Range:0.50Hz-maximum frequency Default:5.00Hz


E-26 Jog acceleration time Range:0.1-6500.0s Default:2.0s
E-27 Jog deceleration time Range:0.1-6500.0s Default:2.0s

The jog frequency function has the highest control priority (terminal jog function). It means in any condition, when
jog command is valid, the inverter immediately run from the current running frequency to the jog frequency based
on jog accelerates/decelerates time. The jog accelerates/decelerates time is defined as same as
accelerates/decelerates time, which can be configured by the keyboard, control terminal or job function control
command of RS485.
Note: The setting value of the jog running frequency is only limited by the upper limit frequency. Only the
priority of job terminal control free from limitation of running control command channel. Other jog
command have priority only under the same running control command channel, such as the keypad job
command is enabled only in the operator keypad control running.

E-28 Start frequency Range:0.00-60.00Hz Default:0.50Hz


E-29 Start frequency holding time Range time:0.0-20.0s Default:0.0s

Start frequency: The initial output frequency when inverter starting. The large starting torque is available if the
starting frequency is properly set. It can gain high impact when starting instantaneous for some load that has a
bigger static friction force in static status. But it will result in a trip if the value is set to big.
Start frequency holding time: It means the inverter keeps running time under starting frequency.

79
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Note: The frequency output is 0 when the frequency given less than starting frequency during the
acceleration process.

E-30 Starting mode selection Range:0000-1102 Default:※000

LED unit digit: Starting mode selection.


0: Starts from starting frequency Inverter starts with [E-28] starting frequency given and [E-29]starting
frequency holding time given. Applicable for application which has big static friction torque, light load inertia, Or suit
to work together with machinery that equipped external mechanical braking. That is occasion where the shaft of
motor can maintain still before start, but after motor stop.
1: DC braking first, and then start from starting frequency Perform DC braking function first with DC braking
voltage [E-35] and DC braking time [E-38] to feed motor a center DC braking energy (Electromagnetic braking),
and then starts with starting frequency. Applicable for occasion there are forward or reverse running of small inertia
load in stop status.
2: Restart after speed searching Inverter try to detect the speed of a rotating motor shaft that is driven by
external forces first and start the motor operation directly from the detected speed to frequency given according
acceleration /deceleration time.
Note: During forward/reverse switching process in normal operation, and perform accel/decel process
after frequency given modifying, both start from 0.0Hz or stop to 0.0Hz.
LED tens digit: Reserve
LED hundreds digit: Speed search direction
0: Speed search performs only in running direction
1: Bi-speed search performs
LED thousands digit: Speed search mode
0: Software speed search
1: Hardware speed search

80
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

E-31 Power off restart selection Range:0,1 Default:0


E-32 Power off restart waiting time Range:0.0-10.0s Default:0.5s

Power off restart selection:


0: Disable Inverter runs must receive running command given after power off when Power on.
In operator keypad or RS485 communication control mode, the running command will be clear automatically when
inverter off.
In the external terminal control mode, the control command of FWD/REV terminal is valid, ignore any parameters
setting of [E-31] when power on again after inverter power off.
1: Enable If inverter is running before power off, the inverter starts automatically after waiting time [E-32] setting
when power on again.
Note: The restart power off function enable inverter operates automatically after power on again. There fore,
there is huge contingency, please be cautious to apply this function ensure safety of person and
equipment.

Power off restart waiting time: when the [E-31] setting is valid, inverter starts operation after waiting time [E-32]
when power on again.
The principles of this time setting is base on the factors such as the work resume preparation time of equipments
which correlate with the frequency inverter after power on again.

E-33 Free stop frequency Range:0.00-60.00Hz Default:0.00Hz

When inverter receives the stop command under deceleration stop mode, it will decelerate to free stop frequency
base on the deceleration time, and then lock output, motor stop freely.
Note: This function is valid in stop mode only, disable in Forward/Reverse process.

E-34 Stop mode Range :0,1 Default:0

0: Deceleration stop Inverter stop output after decelerate to free stop frequency according to deceleration time
and deceleration mode given.
During the decelerate process, when the frequency given less than starting frequency of DC braking stop, the
output frequency will jump to zero, and perform DC injection braking, after then stop working if the DC injection
braking function is activated.
During the deceleration process, when the DC bus voltage over the [E-53] dynamic braking threshold voltage value,
the inverter will output pulse voltage base on dynamic braking ratio [E-54] setting for built in braking unit model
( through 15G/18.5P), able to connecting external braking resistor. For no built braking unit machine, can connect
external braking unit.
This stop mode mainly used to application which need quick braking required.
1: Free stop After receiving the stop command, frequency inverter will block the output and motor will run to
81
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

stop freely. Generally coordinate external mechanical braking to achieve quick stop when this stop mode has been
selecting.

E-35 DC braking voltage Range:0%-150% Default:50%


E-36 DC braking time when stop Range:0.0-30.0s Range:0.0s
E-37 DC braking starting frequency when stop Range:0.00-60.00Hz Range:0.00Hz
E-38 DC braking time when start Range:0.0-10.0s Range:0.0s

DC braking voltage: The value of voltage which is injected to motor when executing DC braking function. The
value of voltage benchmark against the input rated current of inverter.
This function can output torque under zero speed. Generally, it uses to improve the stop accuracy and realize quick
stop, but it can’t be apply for normal deceleration. The inverter will stop output once DC braking has been
performed. If the DC raking current set to big, over current fault occurs easily during stop.

DC braking time when stop: DC braking current lasting time when inverter stops, if the braking time is set to 0, it
means the DC braking function is disabled.

DC braking starting frequency when stop It means when inverter decelerated to this frequency, the inverter
will stop output, and perform the DC braking function. If the output frequency less than DC braking starting
frequency when stop during running process, the inverter will stop output, start DC braking function when receiving
the stop command.
The inverter will start DC braking, and the output frequency jump to zero if the frequency given less than DC
braking staring frequency when stop during the deceleration process. The DC braking staring frequency when stop
should be set smaller when there are no strictly requirement for stop. When the DC braking staring frequency when
stop[E-37]parameters setting smaller than free stop frequency [E-33] setting, the inverter will decelerate to free
stop frequency, and then stop output execute DC braking.

DC braking time when start: It refer to DC braking voltage lasting time when stop, Only if [E-30] parameters unit
digit set to 1, the DC braking function will be enabled. When the braking time set to 0.0s, not perform DC braking
function

E-39 Jump frequency 1 Range:0.00-600.0Hz Default:0.00Hz


E-40 Jump frequency 2 Range:0.00-600.0Hz Default:0.00Hz
E-41 Jump frequency 3 Range:0.00-600.0Hz Default:0.00Hz
E-42 Jump frequency range Range:0.00-5.00Hz Default:0.00Hz

The Jump frequencies are frequency ranges at which the drive will not operate. The drive can be programmed with
three separate Jump frequencies to avoid operating at speeds that cause resonance in driven machinery. If the
frequency reference falls within a Jump frequency dead band, the drive will clamp the frequency reference just
below the dead band and only accelerate past it when the frequency reference rises above the upper end of the
dead band.
Jump frequency range: The frequency up and own jumping bias base on jump frequency

82
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

The setting value after jumping

Jumping frequency 3 Jumping range

Jumping frequency 2 Jumping range

Jumping frequency 1 Jumping range

Setting value

Jumping frequency and jumping range relationship

Note: 1. The output frequency still will pass the jumping range during acceleration or deceleration. Make
sure the parameters don't overlap or inset setting.
2. Jumping frequency is disabled for jog, multi-step speed and swing frequency.

Number of auto restart


E-43 Range:0-3 Default:0
attempts
E-44 Fault auto reset waiting time Range:0.1-20.0s Default:1.0s

Number of automatic fault reset: 0: Disable, The auto reset function is disabled, reset only by manual.
1—3: Enable, 1-3 parameters used for defining the numbers of auto reset. (The maximum time of auto reset is
enabled)
The inverter may be trip to stop cause by fluctuation of grid and other accidents reason during operation. Auto reset
for overload, over current, system abnormal, overvoltage, under voltage. etc fault occurs is allowable to restart
inverter operation ensure system working continuously. Inverter will restart with speed search restart mode during
auto reset.
If the auto reset fails to restart during the setting give numbers, the fault protection will be activate, inverter stop
output. The maximum of auto reset number setting is 3, the reset numbers will be recount after inverter running
normally for 10 minutes, the record times clears automatically. Suggest configure number of auto reset to 1 times
will be better.
The fault output terminal can be set disable or enable during fault auto reset process. Refer to [F-30,F-31,F-32]
Fault auto reset waiting time: Uses for defining the waiting time from fault occurs to reset attempts.
Note: 1. This function only enable for overload, over current, system abnormal, over voltage, under voltage
during running, disable for other fault happen.
2. Reset can’t make if fault fail to solve, no reset for the temperature of inverter over 70℃
Tips: Users must be cautious to consider the start characteristic of the mechanical devices in crane, lifting
application. It should be cautious in using this function for application which can’t start with load or the
alarm will come out immediately when inverter stop output.

E-45 Machine warm up time Range:0.0-6500s Default:0.0s

Inverter enables command operation after machine warm up time, once power supply switch to inverter. It displays
count down in seconds after switch on.

E-46 Running direction selection Range:0-2 Default:0

0: Consistent with the default direction Actual rotation direction is the same with the requirement. The
actual direction don’t change.
83
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

1: Opposite to the default direction Actual rotation direction is opposite to the requirement. The actual
direction will be change.
2: Reverse running forbidden When this parameter is set as prohibition, all the reverse command from
Running control command selection (operator keypad, external terminal, RS485 communication, bipolar VS2 and
program running) are invalid.
The setting will not be modified after the factory default setting.

Note: 1. When the reverse running forbidden is selected, when the bipolar control receiving the reverse
frequency command, the inverter will be operation with 0 speed, the case is the same, inverter will be
operate with 0 speed during program running control if there are some certain step speed reverse direction
are set.
2. All reverse command will be auto turn to running command, running with forward direction.

E-47 FOR/REV dead zone time Range:0.0-10.0s Default:0.0s

The function defined the transient waiting time from forward to reverse or from reverse to forward during 0Hz.
FOR/REV dead zone time special designed for big inertia load application which has mechanical dead zone
required.

E-48 Cooling fans running selection Range:0,1,2 Default:※

Uses select cooling fan running mode.


0: Fan runs when inverter switch on. Cooling fan stop when under voltage condition, it runs when power supply is
stable.
1: Relates with temperature during inverter stop mode, fan runs when inverter running
Fan stop or not is relate to temperature of module during stop mode, fan would operate when the temperature is
above 45℃, stop when module temperature lower 40℃. Fan runs immediately when inverter receives a run
command.
2. Fan stop during inverter stop mode, relates with temperature during inverter running. Fan stop or not is related to
temperature of module during inverter running mode, fan runs when the temperature of module is above 45℃,
stops when temperature of module is lower than 40℃. Fan stops always during inverter stop mode.
Note: Use this function correctly enable extend fans working life.

Inverter protecting mode


E-49 selection Range:0000-1111 Default:0※11

LED unit digit: Overvoltage protecting selection during deceleration


0: Disable 1 Enable
84
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

During the inverter deceleration, the energy generated by motor feedback to inverter inside due to load inertia effect,
which will cause the voltage of inverter over the maximum voltage threshold. The over voltage protecting occurs if
without any measure. When overvoltage protection is activated, the inverter deceleration stops (output frequency
stop descend) when detecting the DC bus voltage over[E-53]setting, deceleration only allow to continue until the
DC bus voltage is lower than the protective value.
Note: It will cause the stop time from deceleration given to stop to be longer if the stall protection is active.

LED ten digit: Output phase missing protection


0: Disable 1: Enable
Used for detecting if output wiring missing when inverter power on, if there are any output phase missing, the Err2
occurs, fault output terminal will be activated.
LED hundred digit: Input phase missing protection
0: Disable 1: Enable
Inverter performs phase missing detecting for 3 phase AC input, if any phase missing, Err1 will occurs, and stop
output. Motor will carry out free stop, the fault output terminals will be activate.
LED thousand digit: Inverter overload, over heat protect mode selection.
0: Free stop 1: running with current limit
This parameter will determine the protection mode when overload, over heat occurs.
Free stop means that output of inverter stop immediately, and active ‘OL2’and ‘OH’ fault alarm.
The running with current limit is that inverter running is based on output current limit. If the current over the current
limit value, the output frequency will be decreased to reduce the load current. The output terminal [F-30-F-32]can
be used to output pre-alarm signal when overload happens.
Current limit value during overvoltage and overheat=rated current ×100%

Coefficient value of
E-50 Range:30%-120% Default:0%
electronic thermal

Motor will generate heat seriously in a long time overload running. This parameter is used to set coefficient of
thermal relay of motor in inverter. When the rated current of motor is equal to rated current of inverter, the value can
be set 100%, when the rated current of motor can’t match the rated current of inverter, this parameter value can be
set for motor overheat protection properly.
The factory default setting of overload capacity of inverter as follows:
G type: 150%× rated current for 1 minute.
F type: 120%× rated current for 1 minute.
The parameters setting value can follow below formula:
Coefficient value of electronic thermal=rated current/ rated output current of inverter
Note: This function would fail when one inverter drives multiple motors in parallel. Please install the
thermal relay before motor input to protect motor effectively

85
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Stall protecting current limit


E-51 Range:100%-250% Default:160G/120P
value

It is used to define the ratio of stall protection current limit to rated current motor.
G type default setting: 160%
P type default setting: 120%
Stalling protecting current limit function means that inverter will limit load current automatically with in time
monitoring during the acceleration, make it lower than the limit setting, (Stops acceleration or lower the output
frequency to achieve the value of output current controlling), to protect big current occurs result in fault alarm trip.
This function is suitable for application where has big inertia or load fluctuates severe particularly.

This parameters datum line is rated current of inverter. It will extend acceleration time longer. It means the current
limit function is activated if the frequency can’t accelerate to set value or frequency given, but fluctuates in the fixed
frequency range. Please reduce the load or adjust the some relevant parameters.

Stall protecting DC bus


E-52 Range:105%-160% Default:138%
voltage threshold

This parameter is defined as the ratio of the stall protection DC bus voltage threshold to rated DC bus voltage of
frequency inverter.
Rated inverter DC bus voltage value=Rated input voltage of inverter×1.414
It defines the over overvoltage stall protecting threshold during the deceleration time. While the DC side pumping
voltage cause by decelerating exceeds this parameter settings, the inverter will auto-prolong the deceleration time.

Dynamic braking and


E-53 decelerating over voltage Range: 105%-160% Default: 130%
suppression threshold voltage
E-54 Ratio of dynamic braking Range: 0%-100% Default: 100%

Decelerating overvoltage suppression threshold voltage: This value is enabled while [E-49] set to 1

Dynamic braking over voltage threshold voltage: The dynamic braking will be activate when the DC bus voltage
rise over than rated voltage of inverter [E-53] setting. The voltage of dynamic braking stop is lower 20V than
[E-53] setting, please make this setting cautiously.
This function is valid for inverter which built in braking accessory only, AC70 series 22G/30 and 30G/37 both
inverters have braking accessory option, standard built in braking accessory through 15G/18P inverter. Please

86
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

select braking unit or braking accessory if need for other model.

Ratio of dynamic braking: This parameter defines the average of voltage which applied on the braking resistor
when braking unit effecting. The voltage applied on the braking resistor is PWM wave, the duty cycle is equal to
ratio of dynamic braking. The ratio bigger, energy release faster, the braking effects better, and the same time the
more energy consumes on the braking resistor.
Selecting the braking resistor value, power and braking effects should take comprehensive consideration to set this
parameter.

DC bus under voltage


E-55 Range:60%-90% Default: 65%
protecting value

This parameter defines the DC bus side lower limiter voltage while inverter in normal working condition. It allow to
set under voltage protecting levels lower to ensure inverter normal working for power grid lower situation.
Note: The output torque will be reduced when the power grid voltage is low. For the constant power load
and constant torque load application, the too low power grid voltage will increase input and output current,
which will reduce the inverter ruing reliability.

E-56-E-58 Reserve

Rotation speed display scale


E-59 Range:0.1-2000.0 % Default:100.0%
factor

It uses to set the display factor of keypad monitor, 100.0% correspond with motor rated speed. The upper limit
machine speed is 65000 RPM.

Ratio of inverter output


E-60 voltage Range:50%-110% Default:100%

Ratio of output voltage to rated voltage of inverter. This function uses to coordinate the output voltage to meet
various types of V/F characteristic requirement.
Output voltage of inverter = rated voltage of inverter ×Ratio of inverter output voltage

E-61 G/P type setting Range:0 ,1 Default:0

When reset the factory setting, this parameter setting values will not be changed.
0:G model, it is suitable for constant torque load.
1:P model, it is suitable for variable torque(such as fan, water pump load).
The AC70 series frequency inverter adopts G/P in one mode. The power of the motor adaptability used in the
constant torque load (G model) is lower one grade than that used in fan, water pump load (P model)

Speed search stability


E-62 Range:0.20-10.00s Default:0.600s
keeping time

This parameter defines the time of inverter try to run stably when inverter detected the frequency point during speed
search process. Inverter accelerates to frequency set point with acceleration time given.
For the big inertia load, extend the speed search stability keeping time can reduce the instantaneous impact current
of speed search start.

87
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Parameters change
E-63 Range:0-2 default: 0
protection

0:All the parameters changing allowed Except for the parameters only for inquiry, any other parameters can be
changed (Note: Some parameters only can be changed in the stop state, some parameters can not be changed in
any condition).
1: Only keyboard digital given parameter changing allowed Except for the keyboard digital given frequency and
keyboard number PID given quantitative parameter, any other parameter don’t allow changing.
2: All the parameters prohibit changing All the parameters of frequency inverter unchangeable; When users
need to change the parameter, They have to change this parameter as 0 or 1.

E-64 Parameter initialization Range:0-4 Default: 0

0: Null
1: Restores to factory default setting value Function parameters will restore to factory default setting after
performed parameters initialization.
2. Clear fault record All historical fault record will be cleared.
3. Transfer parameters of inverter to keypad and save. Copy parameters saved of inverter to keypad and preserve.
4. Transfer parameters saved of keypad to inverter Download parameters of keypad to inverter.
Note:
1. During the inverter running state, Parameters saved of keypad can’t transfer to inverter when in fault
state or no parameters save in keypad.
2. If keypad is pulled out during transferring parameters of inverter to keypad and saving process, this
function will be fail. It need redo parameters copy.
3. If the first part of parameters has been modified, the latter part hasn’t been changed when keypad is
pulled out during transferring parameters copy of keypad to inverter. This function need redo again.
4. The current running state of inverter will not be stored in parameters of inverter transfer to keypad
operation. All keypad are null and invalid when transferring the parameters saved of keypad to
inverter.
5. When E.CPE (parameters copy abnormal) appears on the keypad in parameters copy operation, the
copy is stopped at this moment. It need redo copy again with pressing PRG button return to monitor
state.
6. The parameter saved of keypad can’t be transfer to inverter if the version is incompatible with E.EDI
display.
Note: The current setting value of [E-46, E-61]will not be affected when performing the factory default
restoring. The setting value 3 or 4 of [E-64] parameters will be set to 0 automatically after parameters copy.

E-65 Factory password Range:0-9999 Default: 0

Manufacturer inquiry parameters.

LED unit digit:


0: Null operation
1: State monitoring inquiry
E-66 Information check 2: Fault information inquiry Default: 0
LED ten digit: LCD display language
0:Chinese
1:English

88
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

LED unit digit:


0: Null operation
1: State monitoring inquiry
2: Fault information inquiry

0: Null operation
1: State monitoring inquiry Selects this function to enter monitoring menu(group C parameters),and inquire
each state parameters of the frequency inverter. In the monitoring state, with long pressing (1 second) PRG key
and enter directly the state of the group C parameters that is status of state monitoring inquiry.

Monitoring Communication
Content Unit
code cod
C-01 Frequency reference given 0.01Hz C01H
C-02 Output frequency 0.01Hz C02H
C-03 Output current 0.1A C03H
C-04 Input voltage V C04H
C-05 Output voltage V C05H
C-06 Machine speed RPM C06H
C-07 PID given value % C07H
C-08 PID feedback value % C08H
C-09 Module temperature ℃ C09H
Accumulative running time ( the total timing of
C-10 output frequency which large than 0Hz, 0Hz Hour C0AH
running and stop status timing is disabled )
C-11 Accumulative running timing after last power on Minute C0BH
C-12 Output current percentage % C0CH
C-13 Multi-Step operation remainder time percentage % C0DH
C-14 Input terminals OFF/ON status Refer to below table C0EH
C-15 Output terminals OFF/ON status Refer to below table C0FH
C-16 Terminal VS1 input value 0.1V C10H
C-17 Terminal AS input value 0.1mA C11H
C-18 Terminal VS2 input value 0.1V C12H
C-19 Terminal pulse input value ※ C13H
C-20 Counter record ※ C14H
C-21 DC bus voltage V C15H
C-22 Analog output A01 ※ C16H
C-23 Frequency/voltage/current outputA02 ※ C17H
C-24 Reserve -- C18H
C-25 Inverter rated power kW C19H
C-26 Inverter rated voltage V C1AH
C-27 Inverter rated current 0.1A C1BH
C-28 Software version ※ C1CH

89
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Input terminal OFF/ON state schematic diagram

Output terminal OFF/ON status schematic diagram

2: Fault information inquiry


After inquiry setting, digital LED display below table information. Recycling shows is available via press up and
down keys.
Commu
Serial
Definition Remark nication
number
code
Refer to fault information code to get
Er.01 The latest fault information E01H
more in detail
The cumulative running time before the
Er.02 Units: hour E02H
latest fault
Er.03 Output frequency while the latest fault Units: Hz E03H
Er.04 DC bus voltage while the latest fault Units: V E04H

Er.05 Output current while the latest fault Units: A E05H


Er.06 Output voltage while the latest fault Units: V E06H
Er.07 Module temperature while the latest fault Units:℃ E07H

90
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Er.08 Running direction while the latest fault 0.Forward 1.reverse E08H
0. Stop 1. Constant running
Er.09 Running status while the latest fault E09H
2. Acceleration 3. Deceleration
0. Normal 1. Only voltage amplitude limit
Er.10 Protection status while the latest fault 2. Only current amplitude limit 3. Both E0AH
voltage and current amplitude limit

Er.11 Input terminal status while the latest fault See above table E0BH
Output terminal status while the latest
Er.12 See above table E0CH
fault
Er.13 The latest first fault information E0DH

Er.14 The latest second fault information E0EH

Er.15 The latest third fault Information E0FH


Fault information code table:
Serial
Keyboard display content Fault information
number
0 ---- No fault
The power supply is too low in stop (Don’t record this fault in fault
1 L.U.1
logging)
The power supply is too low in running (Don’t record this fault in
2 L.U.2
fault logging)
3 o.U.1 Overvoltage in acceleration
4 o.U.2 Overvoltage in deceleration
5 o.U.3 Overvoltage in constant speed
6 o.U.4 Over voltage in stop
7 o.C.1 Over current in acceleration
8 o.C.2 Over current in deceleration
9 o.C.3 Over current Constant speed
10 o.L.1 Motor overload
11 o.L.2 Inverter overload
12 Sc System fault
13 o.H. Inverter interior overheat
14 Sen Feedback sensor fault (Don’t record this fault in fault logging)
15 Err1 Phase missing in input side
16 Err2 Phase missing in output side
17 Err3 Current detected fault (Don’t record this fault in fault logging)
18 Err4 Inverter external fault
19 Err5 Swing frequency running parameter setting error
Keypad communication fault (Don’t record this fault in fault
20 Err6
logging)
Reserved (Seek to the technical support, don’t record this fault in
21 LIFE
fault logging)

91
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

22 93SE Storage fault (Don’t record this fault in fault logging)


23 E.TE1 Stationary auto tuning fault (Don’t record this fault in fault logging)
24 E.TE2 Rational auto turning fault (Don’t record this fault in fault logging)
25 Reserve
26 E.CE RS485 communication fault
Communication fault of keypad during power on (Don’t record this
27 E.PAn
fault in fault logging)
28 E.CPE Parameters copy fault (Don’t record this fault in fault logging)
LED ten digit: LCD display language
0:Chinese
1:English

Interference suppression
E-67 Range:0000-1221 Default:0001
selection

LED unit digit: Overvoltage interference suppression


0: Disable
1: Enable When this function is activated, the inverter will take intellectualized judge for over voltage fault, only
respond for true fault signal, suppresses the interference. It may causes alarm delay, should be used with caution
LED ten digit: SC interference suppression
0: Disable
1: SC interference suppression 1 When this function is activated, the inverter will take intellectualized judge for SC
fault, only respond for true fault signal, suppresses the interference. It may causes alarm delay, should be used with
caution.
2: SC interference suppression 2 It has strong SC interference suppression ability compare to SC interference
suppression 1. It may causes alarm delay, should be used with caution.
LED hundred digit: over current interference suppression
0: Disable
1: Over current interference suppression 1 When this function is activated, the inverter will take intellectualized
judge for over current fault, only respond for true fault signal, suppresses the interference. It may causes alarm
delay, should be used with caution.
2: Over current interference suppression 2 It has strong over current interference suppression ability compare to
over current interference suppression 1 It may causes alarm delay, should be used with caution.
LED thousand digit: over current in deceleration suppression
0: Disable
1: Enable When this function is activated, the current limit function will be executed if over current occurs during the
deceleration.
2: Enable frequency reduce for protecting over current. Selects this value for 2, if the output current achieve to
[E-52] current threshold given setting, the inverter will decelerate according to the [F-23] deceleration time given
setting, when after the output current lower to [E-52] current threshold, inverter will accelerate to frequency
reference given according to [F-22] acceleration time given setting.

92
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

8.2 External Terminal Parameters


F-01 Input signal selection 1(X1) Range:0-28 Default:27
F-02 Input signal selection2(X2) Range:0-28 Default:28

F-03 Input signal selection 3(X3) Range:0-28 Default:1

F-04 Input signal selection 4(X4) Range:0-28 Default:2

F-05 Input signal selection 5 (X5) Range:0-28 Default:3

F-06 Input signal selection 6(X6) Range:0-28 Default:4

Defines the control digital terminal function, it is enabled when short connecting ON with COM terminal.
Setting
Definition Function description
value
0 Invalid(check optional is available) This port is free
1 Forward jog operation Jog command input port. Terminal jog commands
2 Reverse jog operation have the highest priority.

3 Free stop Free stop command input port


4 Fault reset External reset command input port when fault

5 Multi steps speed control 1 The multi steps speed commands input port, up to
6 Multi steps speed control 2 8 steps speed control is available; The multi steps
7 Multi steps speed control 3 speed commands has priority only next to the jog

8 Multi steps speed control 4 command;

9 UP/Down running frequency increasing UP


Realize the ascend, descend control function,
UP /Down running frequency decreasing
10 enable when [E-02]or[E-03]is set as“7”;
DW
Defines as D(X) in three line operation control,
11 Three wire operation control D (X)
refer to parameters [F-08].
PID control is canceled when PID control
12 PID control cancel operating, take PID given signal as frequency
reference given, inverter runs at this speed
13 External fault alarm Input port of external fault signal
Acceleration/deceleration time selection
14
terminal 1
Refer to the below fig.
Acceleration/deceleration time selection
15
terminal 2
Frequency main channel When [E-02]is selected for“12”,Frequency given
16
selection terminal 1 main channel control by terminal ; Four digital
Frequency main channel terminals will be combined to 0-11 controlling
17
selection terminal 2 channels, separately corresponding to the[E-02]

93
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Frequency main channel 0-11 frequency input channels


18
selection terminal 3
Frequency main channel
19
selection terminal 4
During the program running, this signal enable
program running to pause. Output frequency will be
20 Program running pause 0 if this command is activated, continue to run base
on running status before pause if pause signal
disappears.
During the program running, if this signal is valid, it
21 Program restart enables the program running to restart, starts to
run from first stage;
22 Timer trigger terminal Start timer to start timing, refer to in detail [F-38].
23 Timer reset terminal Clear the records of the timer
24 Counter reset terminal Clear the records of the counter
25 Counter clock input terminal Refer to [F-39, F-40]
Only terminal control channel is enabled Only terminal control channel is enabled, keypad
26
selection and Rs485 command channel is invalid.
27 Forward running Refer to forward running description in detail.
28 Reverse running Refer to forward running description in detail.

Acceleration/deceleration time selection reference list.


Terminal 2 Terminal 1 Acceleration/deceleration time selection
OFF OFF Acceleration time 1 and deceleration time 1
OFF ON Acceleration time 1 and deceleration time 2
ON OFF Acceleration time 1 and deceleration time 3
ON ON Acceleration time 1 and deceleration time 4

Short connect with(COM)is “ON”, disconnection is “OFF”


Forward running description: As the running command given by terminal, and if [F-08] set as standard operation
control, when this terminal is valid, inverter runs in forward direction, refer to [F-08] parameters for other control
mode function.
Reverse running description: As the running command given by terminal, and if [F-08] set as standard operation
control, when this terminal is valid, inverter runs in reverse direction, refer to [F-08] parameters for other control
mode function.

Input signal respond mode


F-07 Range:0000-1121 Default:0001
selection

LED unit digit: Free stop terminal recover mode


0: Recover to original command with speed search function
1: Don’t recover to original command
2: Recover to original command without speed search function, No speed search of this function need to set unit
digit of [E-30] for 2 together.
94
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

LED ten digit: UP and DW terminal control starting frequency setting


0: Runs with UP/DW terminal adjusting without save the frequency record after power loss.
1: UP/DW terminal adjusting, save the frequency record after power off stop. Inverter will run to last stop moment
frequency and then perform UP/DW adjusting. (Refer to [F-70] to Check or modify last stop moment frequency).
2. Runs to preset frequency [F-70] first, and then execute UP/DW adjusting.
LED hundred digit: STOP/RESE of keypad effective range selection.
0: STOP/RESE key valid only when under keypad control
1: STOP/RESE key valid under any run command source. This function is suitable for using emergency stop in
NOT keypad control mode.
Note: If selects to STOP/RESE key valid under any run command source, pressing the stop key of keypad,
inverter will be located in stop lock status when in terminal control or RS485 control mode. If want to using
terminal or Rs485 running control channel command to restart inverter running, you must sent stop
command by given channel to unlock stop status first. Frequency inverter enable to restart after stop
status unlocking.
LED thousand digit: Terminal running mode selection after fault reset
0: Start inverter running directly after power on in terminal control mode
1: Stop first and then start in terminal control mode
Note: When fault occurs of inverter, reset valid signal can be sent by the all 3 running control command. If
the frequency inverter adopts the terminal control mode, after frequency inverter reset by receiving
terminal or the other two channels’ reset signal, this parameter can be used to select whether to carry on
the terminal running command.

F-08 Terminal running control mode Range:0000-0005 Default: 0000

LED unit digit: Terminal control mode selection


0: Standard running control mode Running and direction are bonded together. This 2 wire control mode is
most commonly using. Uses X1 (forward running) and X2 (reverse running) terminals command to determine the
Forward /Reverse running of motor. Refer to below fig.

1: Two wire running control mode Running and direction are separated. Uses the forward running terminal X1
(forward running) to determine running control, reverse running terminal X2 (reverse running) to determine direction
control. Refer to below fig.

2. Three wire control mode 1 Three wire control terminal (Xi) is used for stop running terminal. Running
command determined by forward running terminal X1 (forward running), direction determined by reverse running
terminal X2 ( reverse running). 3 wire running control terminal Xi is used for enable input.

95
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Tip: In 3 wire control mode 1 Fig, SB1 is a normal close stop button, SB2 is a normal open button. K1 is a
direction selection switch; Xi is multi-function terminal (X1-X6) which have been programmed for 3 wire
running control terminal.
3: 3 wire control mode 2 In this mode, 3 wire running control terminal (Xi) is used for stop running terminal, the
running command is generated by forward running terminal X1(forward running) or reverse running terminal
X2( reverse running ), also control the direction at the same time.

Tip: In 3 wire control mode 2 Fig, SB1 is a normal close button, SB2 and SB3 both are normal open button
and pulse edge is valid, uses for inverter direction control.
4: 3 wire control mode 3 3wire running control terminal (X1) is used for running command given terminal,
running in connecting ON, stop in disconnecting OFF. Rotation direction is determined by forward running terminal
X1 ( forward running) or reverse running terminal X2( reverse running). Every staring running with last time direction
memorized

Tip: 1. SB2 and SB3 both are normal open button, and enable by pulse edge.
2. If need start motor in forward direction, press the K1 first, and press SB2 immediately.

96
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

3. If need start motor in reverse direction, press the K1 first, and press SB3 immediately.
5: 3 wire control mode 4 3 wire running control terminal (X1) uses for stop command terminal, running
command is determined by forward running terminal X1 (forward running), direction is controlled by reverse running
terminal X2( reverse running), and direction will be change after every Xi is activated. Every starts running based on
last direction memorized. 3 wire running control terminal X1 for effective input.

Tip: SB1 is a normal stop button, SB2 is a normal open button. K1 used for running direction selection
button. Xi is multi-function terminal (X1-X6) which have been programmed for 3 wire running control
terminal.
LED ten digit: Reserve
LED hundred digit: Reserve
LED thousand: Reserve

F-09 1 step speed setting 1X Rang:0.00Hz-upper limit frequency Default: 30.00Hz


F-10 2 step speed setting 2X Rang:0.00Hz-upper limit frequency Default:25.00Hz
F-11 3 step speed setting 3X Rang:0.00Hz-upper limit frequency Default: 40.00Hz
F-12 4 step speed setting 4X Rang:0.00Hz-upper limit frequency Default: 50.00Hz
F-13 5 step speed setting 5X Rang:0.00Hz-upper limit frequency Default: 50.00Hz
F-14 6 step speed setting 6X Rang:0.00Hz-upper limit frequency Default: 40.00Hz
F-15 7 step speed setting 7X Rang:0.00Hz-upper limit frequency Default: 25.00Hz
F-16 8 step speed setting 8X Rang:0.00Hz-upper limit frequency Default: 10.00Hz

Uses for setting program running and multi-step speed running frequency separately.
Multi-step speed control has the priority only next to the jog function. If users choose the multi-step speed running
mode, they need to set four multi-function input terminals as multi-step control terminal. ON/OFF between the four
terminals and (COM) determine the running speed steps. Its running and direction is controlled by the running
signal and direction given by the running control command channel [E-01]. And its acceleration, deceleration time is
controlled by the acceleration, deceleration time 1 in default. Or specifies the particular acceleration, deceleration
time by [F-01]-[F-06] parameters setting.
Swing frequency control need to configure the [F-09] and [F-10], refer to [H-51]parameters for the requirement
setting of [F-09] and [F-10]. Inverter will appear fault alarm “Err5” if wrong setting.
Tip 1. Multiple step speed running don’t limited by lower limit frequency, but subject to upper limit frequency.
2. Output of program running is subject to limit by upper and lower limit frequency. Inverter will run with lower limit
frequency when the frequency given less than lower limit frequency.

97
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Short connecting with COM stands for ON, disconnecting for OFF
Terminal
Multi-step control Multi-step control Multi-step control Multi-step control
Step
terminal 4 terminal 3 terminal 2 terminal 1
Speed
OFF OFF OFF ON 1X
OFF OFF ON OFF 2X
OFF OFF ON ON 3X
OFF ON OFF OFF 4X
OFF ON OFF ON 5X
OFF ON ON OFF 6X
OFF ON ON ON 7X
ON OFF OFF OFF 8X

F-17-F-18 Reverse

F-19 Speed search tracking speed Range:0.1-10.0% Default: 0.2%


F-20 Voltage stores time Range:0.10-10.00s Default: 0.60s
Speed search respond current
F-21 Range:10-200% Default: 120%
threshold value

This group parameters will be use in software speed search mode. Software speed search will detect out the motor
speed from current, and stores voltage based on [F-20] voltage stores time under upper limit frequency or given
frequency. When the output current bigger than [F-21], inverter will lower the output frequency with [F-19] speed
search speed tracking. When the current lower than [F-21] and maintain [E-62] time setting, it judges the output
frequency and motor speed is synchronous, will accelerate or decelerate to frequency reference given. Software
speed search processing schematic as following tale:

Note: The motor may decelerate suddenly when drive a light load.

F-22 Frequency reducing acceleration time Range:0.1-6500.0s Default: 2.0s


F-23 Frequency reducing deceleration time Range:0.1-6500.0s Default: 0.3s

Frequency reducing accel/decel. time: When parameters[E-67] is set to “2****”, inverter will reduce frequency
98
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

to protect over current occurs when load fluctuates suddenly. This parameter is used to define the acceleration
/deceleration time of frequency reducing.

F-24 Acceleration time 2 Range: 0.1-6500.0s Default: ※


F-25 Deceleration time 2 Range: 0.1-6500.0s Default: ※
F-26 Acceleration time 3 Range: 0.1-6500.0s Default: ※
F-27 Deceleration time 3 Range: 0.1-6500.0s Default: ※
F-28 Acceleration time 4 Range: 0.1-6500.0s Default: ※
F-29 Deceleration time 4 Range: 0.1-6500.0s Default: ※

Acceleration time 2/3/4: When the [E-15] LED ten digit is set to 0, this refers to requirement time of accelerate
from 0.00Hz to maximum frequency [E-09]. When the [E-15] LED ten digit is set to1, this refers to requirement time
of accelerate from 0.00Hz to motor rated frequency [H-53]. Refers to [E-15] parameters in detail.

Deceleration time 2/3/4: When the [E-15] LED ten digit is set to 0, this refers to requirement time of decelerates
from maximum frequency [E-09] to 0.00Hz. When the [E-15] LED ten digit is set to 1, this refers to the requirement
time of decelerates from motor rated frequency [H-53] to 0.00Hz. Refers to [E-15] parameters in detail.
Note: 1. It need to program the acceleration, deceleration time 2 during in UP/DW control ruing, refers to
[E-02] in detail.
2. It need to program the acceleration, deceleration time 2 during swing frequency control, refers to
[H-65] parameters in detail.
3. In program running mode, defines acceleration/deceleration time from 2 to 4 separately. Definition
of the acceleration /deceleration time is the same as Accel./Decel. time 1. The Accel./Decel time are
configured by [H-35]-[H-49] parameters.
4. Acceleration/deceleration time of multi-step speed are programmed by [F-01]-[F-06]. The default
setting is acceleration/ deceleration time 1.

Relay output terminal


F-30 (TA,TB,TC) Range: 0-22 Default: 1

F-31 Output terminal Y1 Range: 0-22 Default: 4


F-32 Output terminal Y2 Range: 0-22 Default: 7

Setting
Definition Function description
Value
Zero frequency (
0 Output signal when inverter is running and output frequency is 0 Hz,
standby state)
Output signal when fault alarms happening (including OU, OL, SC,
1 Fault alarm 1
OC, OH, LUS, etc), enable output including fault reset auto period
Output signal when fault alarms happening (including OU,OL,SC,OC,
2 Fault alarm 2
OH,LUS, etc), disable during fault auto reset period.
When the output frequency is approaching or arriving to the frequency
Frequency arriving
3 given bias range, outputs valid signal, otherwise output invalid signal.
detection
The bias range is determined by the parameter [F-33].
When the output frequency over than frequency detecting level [F-34]
Frequency level setting, output valid signal after [F-35] relay time setting. When the
4
detection output frequency lower than frequency detecting level, output a invalid
signal after the same [F-35] relay time setting.

99
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

5 running statues Output signal when inverter in running status.


6 Reverse running Output signal when inverter runs in reverse direction
Under voltage of
7 Output signalwhen inverter shows “LU1/2” alarms due to under voltage
inverter
Outputs signal, when the output current of frequency inverter reach to
8 Overload pre-alarm
[F-36] and [F-37] setting values, it outputs signal.
Output frequency reach Outputs signal, when the output frequency reach to upper limit
9
upper limit frequency frequency.
Output frequency reach Outputs signal, when the output frequency reach to lower limit
10
lower limit frequency frequency.
Outputs valid signal when inverter stop resulted in by external fault
11 External fault stop
alarm signal input.
When it is time up to the given setting time of timer of inverter’s inside.
12 Timer times up
Outputs a 1 second width valid pulse signal.
Counter reach When counter reach to maximum value, output terminal outputs a valid
13
maximum values signal with width equal to external clock period.
When the counter reach the setting values, output terminal outputs
Counter reach setting valid signal, and continue to count until achieve to maximum value.
14
values This valid signal will cancel when counter reset which cause by
counted up to maximum value.
PID feedback upper Outputs signal when detecting PID feedback value reach to upper limit
15
limit alarm alarm value [H-26].
PID feedback lower limit Outputs signal when detecting PID feedback value reach to lower limit
16
alarm alarm value [H-27].
When the feedback less then [H-28] setting value, the sensor is
17 Sensor broken considered to broken during the detecting signal in PID control. It will
output signal.
Program running When program finishes the cycle running, it output 500ms low level
18
cycle completed signal.
Program running When program finishes the step running, it outputs 500ms low level
19
step completed signal.
Dynamic braking
20 Outputs signal when perform dynamic braking.
processing
When selects this function, output terminal status can be changed by
Output terminal control [H-79] setting. [H-79] value configured by RS485 communication, the
21
by external binary 0,1, 2 are corresponding to relay output terminal, Y1, and Y2
terminal.
22. Fault alarm 1.
(Including fault auto Output signal when fault alarms happening (including OU, OL, SC,
22
reset period, including OC, OH, LUS, etc), enable output including fault reset auto period
fault-LU1 )
Tip: The output terminal of relay TA-TC close, TB-TC open are considered to valid signal, low level output
terminal Y1, Y2 combine with (+24) terminal output 24V power supply considered valid signal.

100
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

F-33 Frequency arriving detect bias Range: 0.00-50.00Hz Default: 1.00 Hz


F-34 Output frequency level detection Range: 0.00-600.0Hz Default:30.00 Hz
Output frequency level detecting
F-35 Range: 0.0-20.0s Default: 0.0s
relay time

When output frequency approaches or close to frequency reference given value, output terminal outputs signal.
[F-33] function uses to adjust the bias of the detection amplitude.
Output frequency level detection: Uses it to program the frequency detection level, when the output frequency
high [F-34] setting value, output terminal will output signal after [F-35] setting relay time. When the output
78frequency low to than [F-34] setting value, output terminal will stop output signal after [F-35] setting relay time.

F-36 Overload pre-alarm level Range: 50%-200% Default: 150%


F-37 Overload pre-alarm delay time Range: 0.0-20.0s Range: 1.0s

If the output current continues to be over the setting level of the parameter [F-36], after the delay time [F-37], the
output terminal outputs valid signal. In the same way, when the output current is lower than the setting level of
[F-36] ,after the delay time [F-37] , the output terminal outputs invalid signal.

output current
detection level

delay time
delay time
OL pre-alarm
output signal time

OL pre-alarm

F-38 Timer setting value Range: 1-65000s Default: 1s

This parameter is used to timing for the frequency inverter. The timer start-up is activated by the external trigger
terminal of the timer(trigger terminal is selected by [F-01-F06]). Timing from receiving the external trigger signal,
while reaching the timed time, it outputs a width is 1 second pulse signal by the corresponding output terminal.
If the external trigger signal always locate trigger condition, the corresponding terminal outputs a pulse signal every
[F-38] setting time.

101
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

F-39 Counter maximum value Range: 1-65000 Default: 1000


F-40 Counter setting value Range: 1-counter maximum value Default: 100

This parameter stipulate the counting action of the interior counter, clock terminal of the counter is selected by the
parameter [F-01-F-06].
When the count value to the exterior clock reaches [F-39] setting value, in the corresponding output terminal, it
outputs a valid signal with a width equal to exterior clock cycle. The output signal stops while the next count signal
is input.
When the count value to the exterior clock reaches [F-40] setting value, in the corresponding output terminal, it
outputs a valid signal. While it reached [F-39] and the counter clear to zero, this output valid signal abolishes.
The clock cycle is required to be greater than 10 ms; And the minimum pulse width is 5ms.

counter arrive setting counter arrive maximum

output terminal counter arrive max output

output terminal counter arrive max output

VS1 terminal input


F-41 Range: 0.00V-[F-42] Default: 0.50V
voltage lower limit
VS1 terminal input
F-42 Range:[F-41]-10.00V Default: 9.50V
voltage upper limit
VS1 terminal input
F-43 Range: 0.01-5.00 Default: 1.00
voltage gain

VS1 terminal input voltage lower limit This function defines the minimum signal of the analog input terminal
(VS1)receiving. Frequency inverter will automatically filter the voltage signal whose value is lower than this value.

VS1 terminal input voltage upper limit This function defines the maximum signal of the analog input terminal
(VS1)receiving. Frequency inverter will automatically filter the voltage signal whose value is higher than this
value.

VS1 terminal input voltage gain This function is used to amplify or reduce the (VS1) terminal input analog
value.

VS2 terminal input


F-44 Range: -10.00V-[F-45] Default: 0.50V
voltage lower limit
VS2 terminal input
F-45 Range: [F-44]-10.00V Default:9.50V
voltage upper limit
VS2 terminal input
F-46 Range: 0.01-5.00 Default:1.00
voltage gain
VS2 terminal input
F-47 Range: -1.00V-1.00V Default:0.00V
zero offset
VS2 terminal input
F-48 bipolar adjust and direction Range: 0,1,2 Default: 0
control

102
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

VS2 terminal input


F-49 bipolar control zero Range: 0.00V-3.00V Default: 0.20V
hysteresis band

VS2 terminal input voltage lower limit This function defines the minimum signal which received by the analog
input terminal (VS2). Frequency inverter will automatically filters the voltage signal whose value is lower than this
value.

VS2 terminal input voltage upper limit This function defines the maximum signal which received by the
analog input terminal (VS2). Frequency inverter will automatically filter the voltage signal whose value is higher than
this value.

VS2 terminal input voltage gain S2 This function is used to amplify or reduce the (VS2) terminal analog value.

VS2 terminal input zero offset This function is used to adjust the (VS2) terminal zero point in the bipolar
control mode; Its adjustment direction is opposite to the actual zero point. If the actual input voltage is +0.5V, at this
moment, users should set the zero offset as-0.5V to let the voltage corresponding to the zero voltage (only valid
when [F-48] is set as 1 or 2)

VS2 terminal input bipolar adjust and direction control


0: Bipolar adjust and direction control both invalid: the output frequency is determined by the input voltage of
terminal (VS2).
1: Bipolar adjust and direction control both valid: the output frequency of frequency inverter is determined by the
absolute value of amplitude of the input voltage of terminal (VS2). While output phase sequence (machine
direction)is determined by the polar of the input voltage terminal(VS2), frequency inverter neglects its direction
turning setting orders only except this order. When the voltage (VS2)> 0,frequency inverter outputs positive phase
sequence, machine forward rotates. When voltage (VS2) < 0,frequency inverter outputs negative phase sequence,
machine reverses.
When the parameter [E-46] is set as 2 prohibit reverse, if (VS2) <0, machine reverse, frequency inverter will
operates as 0 frequency.
The Bipolar analog input signal(-10V~0V~+10V)is stipulated as following: 0V~+10V step is corresponding to
from [F-56] input frequency lower limit setting to [F-57] input frequency upper limit setting, forward running; 0V~
-10V step is corresponding to from [F-56] input frequency lower limit setting to [F-57] input frequency upper limit
setting, reverse running.
Tips: In two channels combination, bipolar signal will carry out signed calculation based on the combination mode
selection. Negative voltage and frequency DW signal are negative signal. All other input signals of VS2 are positive
signal. If calculation result is positive, the machine forward rotates. If the calculation result is negative, machine
runs in reverse direction.
2. Bipolar adjust valid, direction control invalid: In two channels combination, it used to add or reduce frequency of
another channel. It carries out signed calculation while combination. If the result is positive, machine runs according
to [E-01] given direction. If the result is negative, the output frequency is ‘0’. Bipolar signal takes part in frequency
calculation, do not change or decide the direction of the machine.
VS2 terminal input bipolar control zero hysteresis band This function is used in the bipolar control mode to
adjust the (VS2) terminal zero point corresponding voltage range. If the zero point range is set as -1V~+1V, the
hysteresis band should be set as 1V. (only valid when it is set as ‘1 ’ of [F-48] parameter )

103
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

F-57 corresponding
frequency
frequency

lower limit
input voltage
F-56 corresponding
frequency

lower limit VS2 input analog


input voltage

VS2 unipolar control diagram

F-57 corresponding
Frequency
frequency

Lower limit
input voltage

zero point F-56 corresponding


frequency
F-56 corresponding VS2 input analog
frequency

Upper limit
input voltage

F-57 corresponding
frequency
VS2 bipolar control diagram

Tip: When (VS2) is used as PID given or feedback channel, the function of bipolar is invalid. At this moment,
the usage of (VS2) terminal is the same with the (VS1) terminal. Namely, when (VS2) <0, frequency inverter
think the input of this port is 0.

AS terminal input
F-50 Range: 0.00mA-[F-51] Default: 4.20mA
current lower limit
AS terminal input
F-51 Range:[F-50]-20.00mA Default: 19.50mA
current upper limit
AS terminal input current
F-52 gain Range: 0.01-5.00 Default: 1.00

AS terminal input current lower limit This function defines the minimum signal which received by the analog
input terminal(AS),frequency inverter will automatically filters the current signal whose value is lower than this value;
For example, if the factory setting of this value ‘4.00’,4.00-20.00mA input current is available.

AS terminal input current upper limit This function defines the maximum signal which received by the analog
input terminal (AS), frequency inverter will automatically filters the current signal whose value is higher than this
value.

AS terminal input current gain This function is used to amplify or reduce the (AS) terminal.
104
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

F-53 Pulse input frequency lower limit Range: 0.0KHz-[F-54] Default: 0.0KHz
F-54 Pulse input frequency upper limit Range:[F-53]-50.0KHz Default:10.0 KHz
F-55 Pulse input frequency gain Range: 0.01-5.00 Default: 1.00

Terminal input frequency lower limit This function defines the minimum frequency received by the analog
input terminal (PUL). Frequency inverter will automatically filter the frequency whose value is lower than this value;

Terminal input frequency upper limit This function defines the maximum frequency received by the analog
input terminal (PUL). Frequency inverter will automatically filter the frequency whose value is higher than this value.

Terminal input frequency gain This function is used to amplify or reduce the (PUL) terminal input signal.

Input lower limit correspond


F-56 Rang: 0.00Hz-[F-57] Default: 0.00Hz
setting frequency
Input upper limit correspond
F-57 Range: [F-56]-maximum frequency Default: 50.00Hz
setting frequency

These two parameters stipulate the corresponding relation between the external input analog value, upper/lower
limit of the pulse signal and frequency.

Input signal characteristic


F-58 Range:0000-1111 Default:0000
selection

LED unit digit: VS1 input characteristic selection


0: Positive characteristic 1: Negative characteristic
LED ten digit: AS input characteristic selection
0: Positive characteristic 1: Negative characteristic
LED hundred digit: VS2 input characteristic selection
0: Positive characteristic 1: Negative characteristic
Tips: When(VS2)opens bipolar function ([F-48]is set as 1 or 2 ), this parameter is invalid.
LED thousand digit: Pulse input characteristic selection
0: Positive characteristic 1: Negative characteristic
When in positive characteristic stage, lower limit of external analog input value and the pulse signal corresponds to
[F-56], upper limit of exterior analog input value and the pulse signal corresponds to [F-57].
When in negative characteristic stage, lower limit of exterior analog input value and the pulse signal corresponds to
[F-57], upper limit of exterior analog input value and the pulse signal corresponds to[F-56].
As shown in the Fig. [F-56] (fmin), the biggest analog input and the pulse signal corresponding frequency setting
means their upper limit value corresponding frequency setting, As shown in the Fig. [F-57] (fmax).

105
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

frequency frequency

fmax fmax input quantity

fmin input quantity fmin

input lower input upper input lower input upper


limit limil limit limil
Relationship between frequency setting and input quantity

Terminal analog input filtering


F-59 Range: 0.01-5.00s Default: 0.50s
time constant

This is defined as the size of the input analog quantity signal filtering, for the purpose of eliminating the interference
signal. The longer filtering time is, the stronger anti-interfere ability is, but the respond speed slow down; The
shorter filter time is, the weaker anti-interfere ability is, but the respond speed become faster;

F-60 Output terminal(AO1)selection Range: 0-7 Default: 1


F-61 Output terminal(AO2)selection Range:0-7 Default: 3

Output signal (A01) and (A02) mode is programmed by [F-62]


0: Output signal disable
1: Output frequency/speed
2: Output current
3: Given frequency/speed reference
4: PID given value
5: PID feedback value
6: DC bus voltage
7: Output voltage

Tips: when (AO2)port is frequency pulse output or 4-20mA output, ‘0%’ corresponding output quantity is
not zero.

106
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Analog output signal


F-62 Range: 0000-0023 Default: 0003
selection

LED unit digit: A02 output signal mode selection


0: Frequency pulse train output default setting for 0.2KHz to 10.0KHz;
1:0-20mA
2:4-20mA
3:0-10V
LED ten digit: A01 output signal mode selection
0:0-10V
1:0-20mA
2:4-20mA
LED hundred digit: Reserve
LED thousand digit: Reserve
Tip: After output mode selected by software configured, it also need to select by J1, I2, J3, J4, J5 ,
terminals pin short connection. Refer to following for selecting in detail.
A02 selects for frequency pulse train output, need select J1 among J1, J2, J3 dial switching.
A02 selects for 0-20ma or 4-20mA output signal, need select J2 among J1, J2, J3 dial switching.
A02 selects for 0-10V output signal, need select J2 among J1, J2, J3 dial switching.
A01 selects for 0-20mA or 4-20mA output signal, need make J5 short connection, J4 disconnect.
A01 selects for 0-10V output signal, need make J4 short connection, J5 disconnect.
In the factory default setting of A01 and A02 output signal is 0-10V analog output. If need other output
mode, please configure the software and hardware according requirement.

F-63 AO1 output signal gain Range: 25%-200% Default: 100%


F-64 AO2 output signal gain Range: 25%-200% Default: 100%

Used to adjust AO1 terminal output analog value and AO2 output signal value.

F-65 AO1 output signal zero adjust Range : -10%-10% Default: 0.0
F-66 AO2 output signal zero adjust Range : -10%-10% Default: 0.0

Used to adjust the output signal zero point of (AO1) terminal and (AO2) terminal. It is invalid to adjust this value
when (AO2) is frequency pulse output.

Keypad potentiometer input


F-67 Range: 0.00V-[F-68] Default: 0.20V
lower limit voltage
Keypad potentiometer input
F-68 Range:[F-67]-5.50V Default: 4.80V
upper limit voltage
F-69 Keypad potentiometer gain Range: 0.00-5.00 Default: 1.00

Keypad potentiometer input voltage lower limit This function defines the minimum signal received by the
keyboard potentiometer. Frequency inverter will automatically filters the signal whose value is lower than this value;
Keypad potentiometer input voltage upper limit This function defines the maximum signal received by the
keyboard potentiometer. Frequency inverter will automatically filters the signal whose value is upper than this value.
Keypad potentiometer gain This function is used to amplify or reduce keyboard potentiometer input analog
quantity.
Tips: Keypad potentiometer input voltage upper limit is corresponding to frequency upper limit [E-10] ,
Keyboard potentiometer input voltage upper limit is corresponding to 0.00 Hz.

107
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

UP/DW terminal preset


F-70 Range: 0.00Hz-Maximum frequency Default:0.00Hz
frequency
UP/DW Power-off
F-71 Range: 0.00Hz-Maximum frequency Default:0.00Hz
memorized frequency

The starting frequency output when inverter runs in UP/DW control mode. It is enabled only [F-07] LED ten digit
has been set for 1 or 2 .
When the [F-07] LED ten digit sets for 1, [F-71] parameters will memorize the last UP and DOWN control
momentary frequency. User can review and modify the last stop momentary frequency via [F-71] in stop status.
When the [F-07] LED ten digit sets for 2, the starting frequency can be preset via [F-70] parameters in UP/DW
control.
8.3. Special Function Parameters

H-01 User setting voltage V1 Range: 0.0%-[H-03] Default: 3.0%


H-02 User setting frequency F1 Range : 0.00Hz-[H-04] Default:1.00Hz
H-03 User setting voltage V2 Range:[H-01-H-05] Default: 28.0%
H-04 User setting frequency F2 Range:[H-02-H-06] Default: 10.00Hz
H-05 User setting voltage V3 Range:[H-03-H-07] Default: 55.0%
H-06 User setting frequency F3 Range:[H-04-H-08] Default: 25.00Hz
H-07 User setting voltage V4 Range:[H-05-H-09] Default: 80.0%
H-08 User setting frequency F4 Range:[H-06-H-10] Default: 37.50Hz
H-09 User setting voltage V5 Range:[H-07]-100.0% Default: 100.0%
H-10 User setting frequency F5 Range:[H-08]-maximum frequency Default: 50.00Hz

User define V/F curve:


User can define 1st, 2nd , 3rd , 4th , 5th point of V/f curve percentage for output voltage reference, corresponding to
F1/F2/F3/F4/f frequency point separately. User also can define1st, 2nd , 3rd , 4th , 5th of frequency point to
correspond V1,V2, V3, V4, V5.

V1: 3%
Output voltage F1: 1.00Hz
V2: 28%
V5
F2: 10.00Hz
V4 V3: 55%
F3: 25.00Hz
V3 V4: 80%
F4: 37.50Hz
V2 V5: 100%
F5: 50.00Hz
V1
F F F F F Output frequency

User defines V/f curve schematic


This parameter setting must satisfy the following conditions:
0≤F1≤F2≤F3≤F4≤F5≤ maximum frequency upper limit; 0≤V1≤V2≤V3≤V4≤V5≤100%

108
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

V1, V2, V3, V4, V5 is base on the frequency rated output voltage

H-11 PID output characteristic Range: 0, 1 Default: 0

PID control is a common method used in the process control. The output frequency is adjusted via a series of
proportion, integral, differential calculation of difference value between feedback value of controlled object and PID
given value, make up a negative feedback PID adjustment to achieve a goal which controlled objected stabilizes on
the PID given value.

0: Positive characteristic Suitable for occasions where maintains the PID balance by reducing the
frequency inverter output frequency while the PID feedback quantity is greater than PID given value. Such as apply
in constant pressure water supply, gas supply and tension control of winding application.
1: Negative characteristic Suitable for occasions where maintains the PID balance by increasing the
frequency inverter output frequency while the PID feedback value is greater than PID given value. Such as apply
in central air-conditioning constant temperature control and tension control of unwinding.
While frequency inverter receiving the operation command, frequency inverter will automatically control output
frequency after calculating for the given signal and feedback signal of the terminal according to the PID setting
control mode.
While the PID controls to cancel the terminal connection, frequency inverter will convert the given signal to output
frequency directly without PID control.

PID controller given signal


H-12 sources Range: 0-6 Default: 1

0: Keypad potentiometer Given by the potentiometer of keypad analog signal.


1: PID keypad digital given Given value configured by [H-16] in general PID control
2: External terminal VS1 Given by the external terminal(VS1)(0V-10V)analog signal.
3: External terminal AS Given by the external terminal(AS)(4-20mA)analog signal.
4: External terminal VS2 Given by the external terminal(VS2)analog signal.([F-48] can’t be set for 1 or 2).
5: External pulse signal Given by the external terminal(PUL)pulse frequency signal.
6: RS485 interface Given by RS485 communication interface receiving signal.

PID controller feedback


H-13 signal source Range: 0-3 Default: 1

0. External terminal VS1 Set by the external terminal (VS1) (0V-10V) analog signal.
1. External terminal AS Set by the external terminal (AS) (4-20mA) analog signal.
2. External terminal VS2 (bipolar invalid) Set by the external terminal (VS2) analog signal.([F-48] can’t be set
for 1 or 2) .
3. External pulse signal Set by the external terminal (PUL) pulse frequency signal.
Note: PID controller given signal source and PID controller feedback source can’t be set in the same
channel, otherwise PID is disabled.

109
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

H-14 PID preset frequency Range: 0.00Hz-maximum frequency Default: 0.00Hz


PID preset frequency
H-15 running time Range: 0.1-6500.0s Default: 0.0s

This function make frequency inverter accelerate to PID preset frequency [H-14] with acceleration time 1 after PI
operation starts, and will keep running for PID preset frequency running time [H-15] given, and then executes the
PID close loop operation.
Frequency

preset
frequency

PID adjustment running

Time

preset frequency
running time
PID preset frequency running time diagram

H-16 PID keypad digital given Range: 0.0%-100.0% Default:50.0%

Only when [H-12] parameters is set for 1,this parameter is valid. Take the sensor maximum measuring range [H-18]
as a benchmark. When this parameter is changed, PID given value of monitoring target will automatically
synchronize change.

H-17 PID channel gain Range: 0.01-5.00 Default: 1.00

This function is used to amplify or reduce the input analog value of feedback channel

Sensor maximum measuring


H-18 Range:1.0-100.0 Default:100.0
range

This function is used to adjust the display data of PID given value and PID feedback value.
Actual LED display value= given (feedback) signal - lower input limit × sensor largest range
Upper input limit-lower input limit
For example in pressure control, if it is set for sensor maximum pressure, the display value is actual pressure value.
Assumes that take external terminal (VS1) for feedback single input channel, when VS1 upper limit voltage is 9V,
the lower limit is 0.5V, the present feedback voltage is 4.5V, the maximum sensor measure range is 20mpa.
LED display value =(4.5-0.5)×20/(9-0.5)=9.4mpa

110
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

H-19 Proportion gain P Range: 0.1-100.0 Default: 20.0


H-20 Integral time constant I Range: 0.1-100.0s Default: 2.0s
H-21 Differential gain D Range: 0.0-10.0 Default: 0.0

Adjusting parameters in PID control function, these parameters should be set according to actual system
characteristic in respectively.
Proportion gain P: This parameter determines the impact degree of Proportion gain P respond to deviations.
When gain is large, it responds quickly, but would bring out oscillation. When gain is small, respond will delay.

Integral time constant I: It decides the size of respond effect for Integral time I. When the integral time is big, the
respond is slow, In addition, anti-external interference is become weaker. If the integral time is small, the respond
speed is quick. But oscillation would occur if it is set too small.

Differential gain D: When the deviation of PID feedback value and PID given value changes, The output and the
change rate of deviation are proportionally adjusted. This adjustment is only related to the direction and size of the
deviation change and has nothing to do with the direction and size of the deviation itself. While the feedback signal
changes, differential adjustment is used to adjust according the change trend to restrain the change of feedback
signal. Please be careful to use the differential adjustment. Because it will amply the system interference, especially
for a higher changing frequency interference.

H-22 Sampling period Range: 0.01-60.00s Default: 0.10s

This parameter is only valid for the sampling period of feedback value. The regulator will calculates a time in every
sampling period. The small sampling period, the quicker respond time.

H-23 PID control deviation limit Range: 0.0%-20.0% Default: 0.0%

The maximum deviation allows for PID feedback value to PID given value. PID will be stop, keep output constant
when the feedback value within this deviation range. It will coordinate the contradiction between the accuracy of
system output and stability with using this function properly.

H-24 Starting threshold value Range:0.0%-Sleep threshold value Default:0.0%


H-25 Sleep threshold value Range: Starting threshold value-100.0% Default:100.0%

Starting threshold value: When inverter goes into sleep mode, inverter restarts should require PID feedback value
less than starting threshold value setting. If the the starting threshold value is set too high, inverter will start and
stop frequently. If it set too low, it will cause pressure not enough. This parameter is defined as percentage of PID
feedback value to sensor maximum measuring range account for.

111
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Sleep threshold value: This parameter use as a standard value for adjusting system if go to sleep mode when no
need working. It is that inverter always standby for sleep detecting, if PID feedback value higher than or equal to
PID given setting value is detected, and try to keep holding for a while in setting value around, inverter will start
sleep detecting. If the feedback value higher than sleep threshold value during the sleep detecting mode, inverter
will reduce the output frequency to lower limit frequency, and keep outputting lower limit frequency for a while, and
then reduce to 0Hz, go into sleep mode. If feedback value lower to sleep threshold during above process, sleep
detecting will be disable, go back to PID adjusting working. Smaller setting of this parameter, system will go to sleep
mode easier. When it is set for 100.0%, the system will not go to sleep mode.
This parameter is defined as percentage of PID feedback value to sensor maximum measuring range account for.
This function only is enabled in constant pressure PID control.

H-26 Alarm upper limit value Range: Alarm lower limit value-100.0% Default: 100.0%
H-27 Alarm lower limit value Range: 0.0%-Alarm upper limit value Default: 0.0%

While PID feedback reaches or exceeds the setting value, if any output terminals [F-30-F-32] is set as 15, (PID
feedback value upper limit alarming), it outputs alarm signal; This parameter is defined as percentage of the
maximum measuring range of the sensor that the PID feedback value accounts for.
While PID feedback reaches or under the setting value, if any output terminals [F-30-F-32] is set as 16, (PID
feedback quantity upper limit alarming), it outputs reaching signal; This parameter is defined as percentage of the
largest range of the sensor that the PID feedback quantity accounts for.
This function only is enabled in constant pressure PID control.

H-28 Sensor disconnection detection Range: 0.0%-20.0% Default: 0.0%


Sensor disconnection alarm
H-29 Range: 0,1 Default: 0
operation selection

When the frequency inverter is in the PID control mode, this function is valid; If the detection feedback signal is less
than [H-28], the sensor is deemed to be open circuit. At this moment ,if any one of output terminal [F-30-F-32] is set
as‘17’ (sensor disconnect), the output signal is valid; This parameter is defined as the percentage of the sensor
maximum range that the feedback signal accounts for.
Sensor disconnection alarm running selection
0:Continuous operation
1:Close down
In the process of PID adjustment, while system detects sensor open circuit, this parameter is used to choose
whether frequency inverter stop working. If choose working on ,frequency inverter will cancel closed-loop control,
with PID given values as frequency output; If choose close down, when the system detects the alarm which is
mentioned above, the inverter will stop output and display the malfunction information immediately.
The feedback sensor malfunction is displayed as "SEn". When it detects the PID feedback quantity is greater than
the setting of [H-28], the feedback sensor fault is deemed to be vanish, and system restores PID closed-loop
control.

H-30 Upper limit threshold Range: lower limit threshold-100.0% Default: 100.0%
H-31 Lower limit threshold Range:0.0%-upper limit threshold Default: 0.0%

This parameter will limit PID given during upper limit threshold and lower limit threshold range. This parameters is
defined the ratio of upper limit threshold, lower limit threshold to maximum measuring range. This function only is
enabled in constant pressure PID control.

H-32 Program running mode Range:0-5 Default: 0

0. Single cycle running (time by second)


While receiving running instructions, the frequency inverter starts operation from the 1st step speed and direction.

112
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

The acceleration/deceleration time are selected by parameter [H-35-H-42]; Run time is up to parameter [H-43-
H-50]; The time unit is second. While the first step time up, it shifts to the next step speed. The time, direction,
acceleration/deceleration time of each step speed can be programmed; While finishing the 8th section speed
running, frequency inverter will output "0" frequency. If one step running time is set to zero, it will skip over this step.
1. Continuous cycle running (time by second)
After the frequency inverter finishing 8th section speed running, return to the 1st step speed to begin to work for
uninterrupted cycles. Running direction and acceleration/deceleration time are selected by the parameter
[H-35-H-42]; Run time is set up by parameter [H-43-H-50], the time unit is second.
2: single cycle, continuous running (time by second)
After finishing a single cycle running, the frequency inverter running don’t stop. It works on at the final step speed
whose running time is not zero. Running direction and acceleration/deceleration time are selected by the parameter
[H-35-H-42]; Run time is set up by parameter [H-43-H-50], the time unit is second.
3. Single cycle running (time by minute)
Direction and acceleration/deceleration time are selected by parameter [H-35-H-42]; Running time is set up by
parameter [H-43-H-50]; The time unit is minute. The others are identical with mode ‘0’.
4: continuous cycle (time by minute)
Running direction and acceleration\deceleration time are selected by the parameter [H-35-H-42]; Running time is
set up by parameter [H-43-H-50]; The time unit is minute; The others are identical with mode ‘1’.
5: Single cycle, continuous running (time by minute)
Running direction and acceleration/deceleration time are selected by the parameter [H-35-H-42]; Running time is
set up by parameter [H-50-H-50]; The time unit is minute; The others are identical with mode "1"

Output frequency
14X
4X
........ 15X
3X

2X
1X
Time

........
T1 T2 T3 T4 T14 T15

Single cycle

Output frequency
14X
4X
........ 15X
3X 3X ...

2X 2X
1X 1X
Time

........ ...
T1 T2 T3 T4 T14 T15 T1 T2 T3

Continuous cycle

Output frequency 14X


4X
........ 15X ...
3X

2X
1X
Time

........
T1 T2 T3 T4 T14 T15

Single cycle,continuous running

113
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

Program run breakpoint restore


H-33 mode selection Range: 0,1,2 Default: 0

0: Running at the first step speed


1: Continue to run with breakpoint running frequency and retiming.
2: Continue to run with the breakpoint running frequency and residual time.
This parameter defines the restart running mode after break off due to various reasons (stop, fault, power fail).
If select 0 mode, inverter restarts running with first step speed.
If select 1 mode, inverter restarts running from break of running step, and start timing.
If select 2 mode, inverter restarts running from break of running step, and run with residual time after break off.

Program running state power down


H-34 memory selection Range: 0,1 Default:0

0: NO power down memory


1: power down memory
This parameter defines if inverter will memorize current program running status after power down in program
running mode (running step, residual time of current step, acceleration/deceleration and running direction, etc). If
select power down memory, and combine with [H-33] parameters can defines next restore program running mode
when power on. It need to protect inverter will continue running with before power off running status, this
parameters should set to1.

1 step speed direction and


H-35 accel/decel time Range: 0-7 Default: 0

2 step speed direction and


H-36 Range: 0-7 Default: 1
accel/decel time
3 step speed direction and
H-37 Range: 0-7 Default: 2
accel/decel time
4 step speed direction and
H-38 Range: 0-7 Default: 3
accel/decel time
5 step speed direction and
H-39 Range: 0-7 Default: 4
accel/decel time
6 step speed direction and
H-40 Range: 0-7 Default: 5
accel/decel time
7 step speed direction and
H-41 Range: 0-7 Default: 6
accel/decel time
8 step speed direction and
H-42 Range: 0-7 Default: 7
accel/decel time

In the program running, use to set 8 steps rotation direction and acceleration /deceleration time respectively.
Setting code Description
0 Forward; Acceleration time 1/Deceleration time 1
1 Forward; Acceleration time 2/Deceleration time 2
2 Forward; Acceleration time 3/Deceleration time 3
3 Forward; Acceleration time 4/Deceleration time 4
4 Reverse; Acceleration time 1/Deceleration time 1
5 Reverse; Acceleration time 1/Deceleration time 2
114
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

6 Reverse; Acceleration time 1/Deceleration time 3


7 Reverse; Acceleration time 1/Deceleration time 4

H-43 1 step speed running time T1 Range: 0.0-6000.0 Default: 10.0


H-44 2 step speed running time T2 Range: 0.0-6000.0 Default: 10.0
H-45 3 step speed running time T3 Range: 0.0-6000.0 Default: 10.0
H-46 4 step speed running time T4 Range: 0.0-6000.0 Default: 10.0
H-47 5 step speed running time T5 Range: 0.0-6000.0 Default: 10.0
H-48 6 step speed running time T6 Range: 0.0-6000.0 Default: 10.0
H-49 7 step speed running time T7 Range: 0.0-6000.0 Default: 10.0
H-50 8 step speed running time T8 Range: 0.0-6000.0 Default: 10.0

Use to set 8 steps speed running time, unit of time is set by [H-32] parameters.

Differential frequency △f in swing


H-51 frequency Range:0.00Hz-20.00Hz Default:2.00Hz

During the swing frequency operation, the FOR/REV switching function will be forbidden, running direction is
programmed after stop only. f1 is the setting value of [F-09]; f2 is the setting value of [F-10]; Acceleration time T1 of
the amplitude is the setting value of [F-24]; And the acceleration time T2 of the amplitude is the setting value of
[F-25].
The acceleration/deceleration time in swing frequency running is defined by acceleration/deceleration time 1. When
using the swing frequency running function, frequency inverter will run with the acceleration/deceleration time 1 to
the f1 setting frequency, then begin swing frequency running. While stop, frequency inverter will run for
acceleration/deceleration time 1 from the running frequency to stop. Acceleration/deceleration time of the amplitude
is defined by acceleration/deceleration time 2. It is defined as the same as acceleration/deceleration time 1.
The parameter settings in the swing frequency running should satisfy the following formula request, otherwise
display "Err5".
f1>f2+ᇞf
f2≥0.50Hz
0≤ᇞf≤20.00Hz

Output frequency
swing frequency f1
f f f

swing frequency f2 f f f
Time

acc time 1 T2 T1 T2 T1 T2 dec time 1


runing order

swing frequency running diagram

H-52 Motor rated power Range: 0.4-1100.0KW Default: ※


H-53 Motor rated frequency Range: 0-600.00Hz Default: 50.00Hz

115
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

H-54 Motor rated speed Range: 0-18000RPM Default: ※


H-55 Motor rated voltage Range: 0-1500V Default: ※
H-56 Motor rated current Range: 0.1-1000.0A Default: ※
H-57 Motor no load current Range: 0.01-650.00A Default: ※
H-58 Motor stator resistor Range: 0.001-65.000Ω Default: ※
H-59 Motor rotator resistor Range: 0.001-65.000Ω Default: ※
H-60 Motor stator inductance Range: 0.1-6500.0mH Default: ※
Motor rotator mutual
H-61 Range: 0.1-6500.0mH Default: ※
inductance

[H-52] uses to set motor rated power, unit is 0.1kw. Refer to motor nameplate to configure this parameter. Inverter
will automatically select corresponding default value as [H-53-H-61] default value after every changing of this
parameter. [H-57-H-61] parameters will be modified after motor auto tuning when highly accuracy motor control is
required. The motor parameters [H-52-H-56] must be set properly before perform motor auto tuning.

H-62 Motor auto tuning selection Range:0-2 Default: 0

0. Null operation. No need perform motor parameters auto tuning.


1. Rotational motor auto tuning. Please make sure configure [H-52-H-56] parameters follow motor name plate
correctly before perform motor auto tuning. After executing rotary motor auto tuning, motor will locate stationary
state, it will measuring the stator resistor, rotor resistor and stator& rotator inductance of AC asynchronous motor
first, and then motor will run, and perform no load current and mutual inductance of stator& rotator measure
automatically, write the measured value to [H-57-H-61]. Motor parameters will be reset after auto tuning
automatically.
Press the running key to start rotational auto tuning after parameters setting, ‘T-02’ will be show in the digital
keypad during then running, motor will be stop after auto tuning finish, inverter will restore ready status.
2. Stationary auto tuning Please make sure configure [H-52-H-56] parameters follow motor name plate correctly
before perform motor auto tuning. After executing stationary motor auto tuning, motor will locate stationary state, it
will measuring the stator resistor, rotor resistor and stator& rotator inductance of AC asynchronous motor first, and
put the measured parameters to correspond parameters.
Press the running key to start rotational auto tuning after parameters setting, ‘T-01’ will be show in the digital
keypad, motor will stop after auto tuning , and inverter will restore to ready status.
Note: 1. Must disconnect load from motor before set [H-62] for 1 to execute rotational motor auto tuning. It is
forbidden perform auto tuning with load.
2. For some application which not easy to execute rotational auto tuning (the motor can’t dispatch from load) or no
need high performance control for motor, please select stationary auto tuning or no need perform auto tuning.
Please make sure configure [H-52-H-56] parameters with motor nameplate correctly.
4. Make sure motor should stand in stop state before execute the auto tuning, otherwise auto tuning can’t carry out
normally.
5. It will alarm E.TE1 fault if stationary auto tuning fails, it will alarm E.TE2 if rotational auto tuning fails.

Motor magnetic saturation


H-63 Range: 0-9999 Default: ※
coefficient 1
Motor magnetic saturation
H-64 Range: 0-9999 Default:※
coefficient 2
Motor magnetic saturation
H-65 Range: 0-9999 Default:※
coefficient

[H-63-H-65] parameters use to adjusting the motor magnetic saturation in vector control mode, improve the motor
overload capacity and rung stability.
116
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

H-66 Linkage main station setting Range: 0,1,2 Default: 0

0: Local machine configure as linkage slave station


1: Main station control mode 1. Sent frequency reference and running command of main inverter to slave inverter.
2: Main station control mode 2. Sent output frequency and running command of main inverter to slave inverter.
When this frequency configure for main station, it has linking control function, enable to control other AC70 inverter
of network synchronous running.

H-67 Local inverter address Range: 1-247 Default: 1

Uses to define communication address of local machine when it has been set for slave one. It makes no sense if it
is set for main inverter.

H-68 Data format Range: 0,1,2,3 Default: 3

0: (N,8,1), no check, data bit: 8, stop bit: 1


1: (E,8,1), even parity check, data bit: 8, stop bit: 1
2: (0,8,1), odd parity check, data bit: 8, stop bit: 1
3: (0,8,2), no check, data bit: 8, stop bit: 2

H-69 Baud rate Range:0- 5 Default:3

0:1200bps
1:2400bps
2:4800bps
3:9600bps
4:19200bps
5:38400bps

Communication setting
H-70 Range:0.01-5.00 Default:1.00
frequency ratio

Take frequency reference from upper controller multiply this parameter for this machine frequency reference.
Modification with proportional scale for given frequency from upper controller is available.

Time of communication time


H-71 out Range:0.0-6500.0s Default:10.0s

If the interval time between a communication and the next communication exceeds communication overtime time, it
is considered there is communication disconnection fault, malfunction disconnection action mode is decided by the
[H-72].

RS485 communication
H-72 Range:0-2 Default: 1
broken responding mode

LED“0” digit: RS485 communication broken responding mode


0: giving alarm and free stop When the inverter setting given communication command don’t receive next
frame command or any other communication command respond over [H-17] given time, inverter will giving alarm
and free stop .
1: No alarm and continue running Inverter don’t make any fault detect, continue running with last communication
117
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION

command .
2. No alarm but stop When the inverter setting given communication command doesn’t receive next frame
command or any other communication command respond over [H-17] given time, inverter stop running.
LED “00” digit: Communication write operation mode.
0: Reply for write operation
1: No reply for write operation
LED “000” digit:: Reserve
LED “0000” digit: Reserve
Note: When inverter has been set for main machine, don’t perform RS485 communication broken checking.

H-73 Respond relay Range: 0.000-1.000s Default: 0.005s

This parameter defines the intermediate interval time between the frequency inverter receiving the data and
responding data back to the upper control. If the response delay time is shorter than the system handling time, the
response time should according to the system; If the response delay time is longer than the system handling time,
after system processing the data, it waits until the response delay time is up, then sends data to the upper
controller.

Instantaneous stop decel.


H-74 Range: 0%-200% Default: 20%
respond voltage lower limit
Instantaneous stop decel.
H-75 Range: 0%-200% Default: 90%
respond voltage upper limit
Instantaneous stop decel.
H-76 Range: 0.01-10.00 Default:2.00
gain
H-77 Voltage recover stability time Range: 0.0-100.0s Default:2.0s

This function enable frequency inverter reducing the output frequency when power fails instantaneous or voltage
lower suddenly, compensate voltage lowed with energy feedback from load, to maintain inverter continue running in
shortly.
When the input voltage lower to [H-74], inverter will start to reduce speed and DC bus voltage rise. When the input
voltage recovers to [H-75], speed reducing will stop. When the current speed keep stable running after [H-77]
setting time, inverter will accelerate to frequency reference given.
[H-76] is defines as deceleration gain, the bigger setting, the quicker voltage rising, which suitable for small inertia
load. If this parameters is set for small, the voltage recovery rising slowly, which suitable for big inertia.

Torque compensation upper


H-78 Range: 0.00-60.00% Default:50.00%
limit

This parameters is valid only in vector control mode, uses for controlling the torque compensation upper limit. Take
the rated inverter voltage as reference benchmark for compensation voltage.

Output terminal external


H-79 Range: 0-9999 Default: 0
control status

H-80 Reserve

118
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

Appendix 1: Appendix
9.1 Appendix 1: Function Code Simple List

“ ”: Stand for this parameter can be modified in running mode.
“〇”: Stand for this parameter can not be modified in running mode.
“×”: Stand for this parameter is read only, can’t be modified.
“–”: Stand for factory authority parameters. Veichi setting is available only.
“※”: Stand for this parameter is related to frequency inverter model.
Basic function code group

pr Comm
Refe
Code Factory op unicati
Function name Setting range and definition r to
function default ert on
y page
code
0: Open loop vector control without
E-00 Control method selection PG 1 〇 69 100H
1: V/F control mode
0: Operator keypad
Running control command 1: External terminal control
E-01 2: RS485 Communications port 0 〇 69 101H
channel selection
control
0: Operator keypad digital given
1: Potentiometer of keypad
2: Terminal VS1 analog voltage
0-10V
3: Terminal AS analog current
signal 4-20mA
4: Terminal VS2 analog voltage
Frequency reference
-10-10V
E-02 given main channel 1 〇 69 102H
selection 5: Pulse train signal
6: RS485 communication port
7: Up and Down control
8: General PID operation
9: Constant pressure PID control
10: Program running
11: Swing frequency run
12: Terminal selection:
0: Operator keypad digital
1: Potentiometer of keypad
2: Terminal VS1 analog voltage
0-10V
3: Terminal AS analog current
Frequency reference signal 4-20mA
4: Terminal VS2 analog voltage
E-03 given auxiliary channel -10-10V 0 〇 71 103H
selection 5: Pulse train signal
6: RS485 communication port
7: Up and Down control
8: General PID operation
9: Constant pressure PID control
10: Program running

119
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

Frequency reference
E-04 given channel gain 0.01-5.00 1.00 〇 72 104H
0: Main channel is valid, auxiliary
channel is invalid.
1: Auxiliary channel valid,main
channel invalid
2: Both channel is valid if non zero
value, main channel priority
3: Main channel + K×auxiliary
channel)
4: main channel -(K×auxiliary
Frequency reference channel)
E-05 given channel 5: MAX [main channel , 0 〇 72 105H
(K×auxiliary channel)]
combination mode 6: MIN [main channel , (K×auxiliary
channel)]
7: Auxiliary channel + (K×main
channel)
8: Auxiliary channel - (K×main
channel)
9: MAX [(K×main channel),
auxiliary channel]
10: MIN [(K×main channel),
auxiliary channel]
0: Frequency Given
Upper LED monitor
E-06
selection
1: Output frequency 0 ● 72 106H
2: Output current
3: Input voltage
4: Output voltage
Lower LED monitor 5: Machine speed
E-07
selection
1 ● 72 107H
6: PID given given
7: PID feedback value
REV/JOG key of keypad 0: Reverse
E-08
function selection 1: Jog
0 ● 73 108H

E-09 Maximum frequency 0.01-600.00Hz 50.00Hz 〇 73 109H


lower limit frequency - maximum
E-10 Upper limit frequency
frequency
50.00Hz ● 73 10AH

E-11 Lower limit frequency 0.00-Upper limit frequency 0.00Hz ● 73 10BH


0: Stop
Lower limit frequency
E-12
running mode
1: running with lower limit 1 ● 73 10CH
frequency
E-13 Acceleration time 1 0.1-6500.0s ※ ● 74 10DH
E-14 Deceleration time 1 0.1-6500.0s ※ ● 74 10EH

120
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

LED unit digit: decelerate


/decelerate mode.
0: linear accelerate
1: S curve
LED tens digit:
Accelerate/decelerate time
datum point.
Acceleration /deceleration 0: Motor rated frequency
E-15
mode selection 1: Maximum frequency
0000 ● 74 10FH
LED hundreds digit:
Equidistance stop function
0: Disable
1: Enable
LED Thousands digit:
0: Disable
1: Enable
Frequency given by digital lower limit frequency - Upper limit
E-16
keypad frequency
50.00Hz ● 76 110H

0: Constant torque curve


1: Descend torque curve(1.5 power
curve)
2: Descend torque curve(1.7
E-17 V/F curve mode 0 〇 76 111H
Power curve)
3: Descend torque curve(2.0
Square curve)
4: User define curve
E-18 Torque boost 0.0%-25.0% ※ ● 76 112H
E-19 Filter time constant 0.01-99.99 ※ ● 77 113H
E-20 Carrier frequency 0.7KHz-15.0KHz ※ ● 77 114H
LED unit Digit: Associate of
carrier frequency and output
frequency configure.
0: Output frequency associate is
disabled.
1: Output frequency associate is
enabled.
LED tens digit: Associate of
carrier frequency and module
temperature configure.
0: Module temperature associate is
E-21 Carrier characteristic
disabled.
1010 ● 77 115H
1: Module temperature associate is
enabled.
LED Hundreds digit: PWM mode
selection
0: Fixed PWM mode
2: Random PWM mode 1
LED Thousands digit:
Inhibition of shock
0: Inhibition of shock is disabled
1: Inhibition of shock is enabled
E-22 V/F slip compensation 0%-200% 100% 〇 78 116H

121
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

LED unit digit: Auto energy


saving selection
0: disable
1: enable
LED tens digit: V/F slip
Energy saving mode compensation
E-23 0: Disable 1000 〇 78 117H
selection
1: Enable
LED hundreds digit: reserved
LED thousands digit:
Overmodulation
0: Overmodulation allow
1: Overmodulation not allow
0: Disable
Voltage auto regulation
E-24
function
1: Enable in full process 2 ● 79 118H
2:Disable only in deceleration
E-25 Jog frequency 0.50Hz - upper limit frequency 5.00Hz ● 79 119H
E-26 Jog acceleration time 0.1-6500.0s 2.0s ● 79 11AH
E-27 Jog deceleration time 0.1-6500.0s 2.0s ● 79 11BH
E-28 Starting frequency 0.00-60.00Hz 0.50Hz 〇 79 11CH
Starting frequency holding
E-29 0.0-20.0s 0.0s 〇 79 11DH
time
LED unit digit: Starting mode
selection.
0:Starts from starting frequency
1: DC braking first, and then start
from starting frequency
2: Restart after speed search
LED tens digit: reserved
LED Hundreds digit: Speed
E-30 Starting mode selection ※000 〇 80 11EH
search direction
0: Speed search performs only in
running direction
1: bi-direction speed search
LED Thousands digit: Speed
search mode
0: Software speed search
1: Hardware speed search
E-31 Power off restart selection 0: Disable 1: Enable 0 ● 81 11FH
Power off restart waiting
E-32
time
0.0-10.0s 0.5s ● 81 120H

E-33 Free stop frequency 0.00-60.00Hz 0.00Hz ● 81 121H


E-34 Stop mode 0: Deceleration stop 1: Free stop 0 ● 81 122H
E-35 DC braking current 0-150% 50% ● 82 123H
DC braking time when
E-36
stop
0.0-30.0s 0.0s ● 82 124H
DC braking starting
E-37
frequency when stop
0.00-60.00Hz 0.00Hz ● 82 125H
E-38 DC braking time when 0.0-10.0s 0.0s ● 82 126H

122
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

E-39 Jump frequency 1 0.00-600.0Hz(Fmax) 0.00Hz ● 82 127H


E-40 Jump frequency 2 0.00-600.0Hz(Fmax) 0.00Hz ● 82 128H
E-41 Jump frequency 3 0.00-600.0Hz(Fmax) 0.00Hz ● 82 129H
E-42 Jump frequency range 0.00-5.00Hz 0.00Hz ● 82 12AH
Number of auto restart 0: Disable
E-43
attempts 1-3: Enable
0 ● 83 12BH
Fault auto reset waiting
E-44
time
0.1-20.0s 1.0s ● 83 12CH

E-45 Machine warm up time 0.0-6500s 0.0s ● 83 12DH


0: Consistent with the default
Running direction direction
E-46 0 〇 83 12EH
selection 1: Opposite to the default direction
2: Reverse running forbidden.
E-47 FOR/REV dead zone time 0.0-10.0s 0.0s ● 84 12FH
0: Fan runs when switch on.
1: Fan runs or not relates with
temperature during inverter stop
Cooling fans running mode, fan runs when inverter
E-48
selection running.
※ ● 84 130H
2.Fan stop during inverter stop
mode, running if not relates with
temperature during inverter ruing
LED unit digit: Overvoltage
protecting selection during
deceleration
0: Disable 1 Enable
LED ten digit: Output phase
missing protection
0: Disable 1 Enable
Inverter protecting mode
E-49
selection
LED hundred digit: Input phase 0※11 ● 84 131H
missing protection
0: Disable 1 Enable
LED thousand digit: Inverter
overload, over heat protect
mode selection.
0: Free stop
1: Running with current limit
Coefficient value of 30%-120% (disable for value less
E-50
electronic thermal than 30 )
0% ● 85 132H
Stall protecting current 160 G
E-51
limit value
100%-250%
120 P ● 86 133H
Stall protecting DC bus
E-52
voltage threshold value
105-160% 138% ● 86 134H
Dynamic braking and
E-53 decelerating over voltage 105-160% 130% ● 86 135H
suppression threshold
E-54 Ratio of dynamic braking 0-100% 100% ● 86 136H
DC bus under voltage
E-55
protecting value
60-90% 65% ● 87 137H

E-56 reserved 87 138H


123
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

E-57 reserved 87 139H


E-58 reserved 87 13AH
Rotation speed display
E-59
scale factor
0.1-2000.0% 100.0% ● 87 13BH
Ratio of inverter output
E-60 50-110% 100% 〇 87 13CH
voltage
E-61 G/P type setting 0: G type 1: P type 0 〇 87 13DH
Speed search stabilizing
E-62
keeping time
0.200-10.000s 0.600s ● 87 13EH
0: All the parameters changing is
allowed
Parameters change 1: Only keyboard digital given
E-63
protection parameter changing allowed
0 ● 88 13FH
2: All the parameters prohibit
changing
0: Null
1: Restores to factory default
setting value
2: Clear fault record
E-64 Parameter initialization 0 〇 88 140H
3: Transfer parameters of inverter
to keypad and save.
4: Transfer parameters saved of
keypad to inverter
E-65 Factory password 0-9999 0 ● 88 141H
LED unit digit:
0: Null operation
1: State monitoring inquiry
E-66 Information check 2: Fault information inquiry 0 ● 88 142H
LED ten digit: LCD display
language
0:Chinese 1:English
LED unit digit: Overvoltage
interference suppression
0: Disable 1: Enable
LED ten digital: SC interference
suppression
0: Disable
1: SC interference suppression 1
2: SC interference suppression 2
LED hundred digital: over
current interference
Interference suppression suppression
E-67
selection 0: Disable
0001 ● 92 143H
1: Over current interference
suppression 1
2: Over current interference
suppression 2
LED thousand digital: over
current in deceleration
suppression
0: Disable 1: Enable
2: Enable frequency reducing for
protecting over current.
124
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

External terminal parameters


pr Comm
Refe
Code Factory op unicati
Function name Setting range and define r to
function default ert on
y page
code
0: Invalid
1: Forward jog operation
Input signal selection 1
F-01 2: Reverse jog operation 27 〇 93 201H
(X1)
3: Free stop
4: Fault reset
5: Multi steps speed control 1
6: Multi steps speed control 2
Input signal selection2 7: Multi steps speed control 3
F-02 28 〇 93 202H
(X2) 8: Multi steps speed control 4
9: UP/Down running frequency
increasing UP
10:UP/Down running frequency
decreasing DW
Input signal selection 3 11: Three wire operation control D
F-03 1 〇 93 203H
(X3) (X)
12: PID control cancel
13: External fault alarm
14: Acceleration/deceleration time
selection terminal 1.
Input signal selection 4 15:Acceleration/deceleration time
F-04 2 〇 93 204H
(X4) selection terminal 2
16: Frequency main channel
selection terminal 1
17: Frequency main channel
selection terminal 2
Input signal selection 5 18: Frequency main channel
F-05 3 〇 93 205H
(X5) selection terminal 3
19: Frequency main channel
selection terminal 4
20: Program running pause
21: Program restart
22: Timer trigger terminal
23: Timer reset terminal
Input signal selection 6 24: Counter reset terminal
F-06 4 〇 93 206H
(X6) 25:Counter clock input terminal
26:Only terminal control channel is
enabled selection
27: Forward running
28: Reverse running

125
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

LED unit digit: Free stop


terminal recover mode
0: Recover to original command
with speed search function.
1:Don’t recover to original
command after free stop terminal
disconnecting.
2: Recover to original command
without speed search function.
LED ten digit: UP and DW
terminal control starting
frequency setting
0: Runs with UP/DW terminal
adjusting without save the
frequency record after power loss.
1: Run to last stop moment
frequency and then perform
Input signal respond mode UP/DW adjusting.
F-07 0001 〇 94 207H
selection 2: Runs to preset frequency[F-70]
first, and then execute UP/DW
adjusting.
LED hundred digit: STOP/RESE
of keypad effective range
selection.
0: STOP/RESE key valid only
when under keypad control
1: STOP/RESE key valid under
any run command source
LED thousand digit: Terminal
running mode selection after
fault reset
0: Start inverter running directly
after power on in terminal control
mode
1: Stop first and then start in
terminal control mode.

126
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

LED unit digit: Terminal control


mode selection
0: Standard running control mode
1: 2wire running control mode
2: 2 wire control mode 1
Terminal running control
F-08 3: 3 wire control mode 2 0000 〇 95 208H
mode
4: 3 wire control mode 3
5: 3 wire control mode 4
LED ten digit:reserved
LED hundred digit:reserved
LED thousand: reserved
F-09 1 step speed setting 1X 30.00Hz ● 97 209H
F-10 2 step speed setting 2X 25.00Hz ● 97 20AH
F-11 3 step speed setting 3X 40.00Hz ● 97 20BH
F-12 4 step speed setting 4X 50.00Hz ● 97 20CH
0.00Hz-upper limit frequency
F-13 5 step speed setting 5X 50.00Hz ● 97 20DH
F-14 6 step speed setting 6X 40.00Hz ● 97 20EH
F-15 7 step speed setting 7X 25.00Hz ● 97 20FH
F-16 8 step speed setting 8X 10.00Hz ● 97 210H
F-17 reserved 98 211H
F-18 reserved 98 212H
Speed search tracking
F-19 0.1-10.0% 0.2% 〇 98 213H
speed
F-20 Voltage stores time 0.10S-10.00S 0.60s 〇 98 214H
Speed search respond
F-21 10%-200% 120% 〇 98 215H
current threshold value
Frequency reducing
F-22
acceleration time
0.1-6500.0s 2.0s ● 98 216H

Frequency reducing
F-23
acceleration time
0.1-6500.0s 0.3s ● 98 217H

F-24 Acceleration time 2 ※ ● 99 218H


F-25 Deceleration time 2 ※ ● 99 219H
F-26 Acceleration time 3 ※ ● 99 21AH
0.1-6500.0s
F-27 Deceleration time 3 ※ ● 99 21BH
F-28 Acceleration time 4 ※ ● 99 21CH
F-29 Deceleration time 4 ※ ● 99 21DH

127
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

0: Zero frequency (standby state)


1: Fault alarm 1. (Including fault
auto reset period. )
2: Fault alarm 2. (Not includes fault
auto reset period.)
3: Frequency arriving detection
4: Frequency level detection
5: Running statues
Relay output terminal
F-30 6: Reverse running 1 ● 99 21EH
(TA,TB,TC)
7: Under voltage of inverter
8: Overload pre-alarm
9: Output frequency reach upper
limit frequency
10. Output frequency reach lower
limit frequency
11. External fault stop
12. Timer times up
13. Counter reach maximum
values
14. Counter reach setting values
15. PID feedback upper limit alarm
16. PID feedback lower limit alarm
F-31 Output terminal Y1 17. Sensor broken 4 ● 99 21FH
18.Program running cycle
completed
19.Program running step
completed
20:Dynamic braking processing
21: Output terminal control by
external
F-32 Output terminal Y2 22. Fault alarm 1. (Including fault 7 ● 99 220H
auto reset period,including
fault-LU1 )
Frequency arriving detect
F-33 bias 0.00-50.00Hz 1.00Hz ● 101 221H

Output frequency level


F-34
detection
0.00-600.0Hz 30.00Hz ● 101 222H

Output frequency level


F-35
detecting relay time
0.0-20.0s 0.0s ● 101 223H

F-36 Overload pre-alarm level 50-200% 150% ● 101 224H


Overload pre-alarm delay
F-37
time
0.0-20.0s 1.0s ● 101 225H

F-38 Timer setting value 1-65000s 1s ● 101 226H


F-39 Counter maximum value 1-65000 1000 ● 102 227H
F-40 Counter setting value 1- Counter maximum value 100 ● 102 228H

128
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

VS1 terminal input


F-41
voltage lower limit
0.00V- [F-42] 0.50V ● 102 229H

VS1 terminal input


F-42
voltage upper limit
[F-41]-10.00V 9.50V ● 102 22AH

VS1 terminal input


F-43
voltage gain
0.01-5.00 1.00 ● 102 22BH

VS2 terminal input


F-44
voltage lower limit
-10.0V –[F-45] 0.5V ● 102 22CH

VS2 terminal input


F-45
voltage upper limit
[F-44]-10.0V 9.5V ● 102 22DH

VS2 terminal input


F-46
voltage gain
0.01-5.00 1.00 ● 102 22EH

VS2 terminal input


F-47
voltage lower limit
-1.00V-1.00V 0.00V ● 102 22FH
0: Bipolar adjust and direction
control both invalid
VS2 terminal input
1: Bipolar adjust and direction
F-48 bipolar adjust and
control both valid 0 ● 102 230H
direction control
2:Bipolar adjust valid, direction
control invalid
VS2 terminal input
F-49 bipolar control zero 0.00V-3.00V 0.20V ● 103 231H
hysteresis band
AS terminal input
F-50
current lower limit
0.00mA - [F-51] 4.20mA ● 104 232H

AS terminal input
F-51
current upper limit
[F-50] - 20.0mA 19.50mA ● 104 233H

AS terminal input current


F-52
gain
0.01-5.00 1.00 ● 104 234H

Pulse input frequency


F-53 lower 0.00KHz- [F-54] 0.00KHz ● 105 235H

Pulse input frequency


F-54
upper limit
[F-53] - 50.00KHz 10.00KHz ● 105 236H

F-55 Pulse input frequency gain 0.01-5.00 1.00 ● 105 237H


Input lower limit
F-56 correspond setting 0.00Hz - [F-57] 0.00Hz ● 105 238H

Input upper limit


F-57 correspond setting [F-56] - maximum frequency 50.00Hz ● 105 239H
frequency

129
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

LED unit digit: VS1 input


characteristic selection
0: Positive characteristic
1: Negative characteristic
LED ten digit: AS input
characteristic selection
0: Positive characteristic
Input signal 1: Negative characteristic
F-58
LED hundred digit: VS2 input
0000 ● 105 23AH
characteristic selection
characteristic selection
0: Positive characteristic
1: Negative characteristic
LED thousand digit: Pulse input
characteristic selection
0: Positive characteristic
1: Negative characteristic
Terminal analog input
F-59 filtering time constant 0.01-5.00 0.50 ● 106 23BH
0: Output signal disable
Output terminal(AO1) 1: Output frequency/speed
F-60
selection 2: Output current
1 ● 106 23CH
3: Given frequency/speed
reference
4: PID given value
Output terminal(AO2)
F-61
selection
5: PID feedback value 3 ● 106 23DH
6: DC bus voltage
7: Output voltage
LED unit digit: A02 output signal
mode selection
0: Frequency pulse train output 1:
0-20mA
2: 4-20mA
3: 0-10V
Analog output signal
F-62 selection
LED ten digit: A01 output signal 0003 ● 107 23EH
mode selection
0: 0-10V
1: 0-20mA
2: 4-20mA
LED hundred digit: reserved
LED thousand digit: reserved
AO1 output signal
F-63 gain
25%-200% 100% ● 107 23FH

AO2 output signal


F-64 gain
25%-200% 100% ● 107 240H

AO1 output signal zero


F-65 adjust
-10.0%-10.0% 0.0% ● 107 241H
AO2 output signal zero
F-66 adjust
-10.0%-10.0% 0.0% ● 107 242H

130
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

Keyboard potentiometer
F-67 Input voltage lower limit
0.00V - [F-68] 0.20V ● 107 243H
Keyboard potentiometer
F-68 Input voltage upper limit
[F-67] - 5.50V 4.80V ● 107 244H

Keyboard potentiometer
F-69 gain
0.00-5.00 1.00 ● 107 245H

UP/DW terminal preset


F-70 frequency
0.00Hz - upper limit frequency 0.00Hz ● 108 246H
UP/DW Power-off
F-71 0.00Hz - upper limit frequency 0.00Hz 〇 108 247H
memorized frequency
Special function parameters
pr Comm
Refe
Code Factory op unicati
Function name Setting range and define r to
function default er on
page
ty code
H-01 User setting voltage V1 0.0% -[H-03] 3.0% 〇 108 301H
H-02 User setting frequency F1 0.0Hz-[H-04] 1.00Hz 〇 108 302H
H-03 User setting voltage V2 [H-01-H-05] 28.0% 〇 108 303H
H-04 User setting frequency F2 [H-02-H-06] 10.00Hz 〇 108 304H
H-05 User setting voltage V3 [H-03-H-07] 55.0% 〇 108 305H
H-06 User setting frequency F3 [H-04-H-08] 25.00Hz 〇 108 306H
H-07 User setting voltage V4 [H-05-H-09] 80.0% 〇 108 307H
H-08 User setting frequency F4 [H-06-H-10] 37.50Hz 〇 108 308H
H-09 User setting voltage V5 [H-07]-100.0% 100.0% 〇 108 309H
H-10 User setting frequency F5 [H-08]-maximum frequency 50.00Hz 〇 108 30AH
0: Positive characteristic
H-11 PID output characteristic 0 〇 109 30BH
1: Negative characteristic
0: Keypad potentiometer
1: PID keypad digital given
2: External terminal VS1:0-10V
PID controller given signal
H-12 3: External terminal AS: 4-20mA 1 〇 109 30CH
sources
4: External terminal VS2
5: External pulse signal
6: RS485 interface
0: External terminal VS1:0-10V
1: External terminal AS: 4-20mA
PID controller feedback
H-13 2: External terminal VS2 ( bipolar 1 〇 109 30DH
signal source
invalid)
3: External pulse signal
H-14 PID preset frequency 0.00Hz-upper limit frequency 0.00Hz 〇 110 30EH
PID preset frequency
H-15
running time
0.0-6500.0s 0.0s ● 110 30FH

H-16 PID keypad digital given 0.0-100.0% 50.0% ● 110 310H


H-17 PID channel gain 0.01-5.00 1.00 ● 110 311H

131
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

Sensor maximum
H-18
measuring range
1.0-100.0 100.0 ● 110 312H

H-19 Proportion gain P 0.1-100.0 20.0 ● 111 313H


H-20 Integral time constant I 0.1-100.0s 2.0s ● 111 314H
H-21 Differential gain D 0.0-10.0 0.0 ● 111 315H
H-22 Sampling period 0.01-60.00s 0.10s ● 111 316H
H-23 PID control deviation limit 0.0-20.0% 0.0% ● 111 317H
H-24 Starting threshold value 0.0%-Sleep threshold value 0.0% ● 111 318H
H-25 Sleep threshold value Starting threshold value-100.0% 100.0% ● 111 319H
H-26 Alarm upper limit value Alarm lower limit value-100.0% 100.0% ● 112 31AH
H-27 Alarm lower limit value 0.0%-Alarm upper limit value 0.0% ● 112 31BH
Sensor disconnection
H-28
detection
0.0-20.0% 0.0% ● 112 31CH

Sensor disconnection 0: continue running


H-29
alarm operation selection 1: Stop
0 ● 112 31DH

H-30 Upper limit threshold lower limit threshold-100.0% 100.0% ● 112 31EH
H-31 Lower limit threshold 0.0%-Upper limit threshold 0.0% ● 112 31FH
0: Single cycle running (time by
second)
1: Continuous cycle running
2: single cycle, continuous running
(time by second)
H-32 Program running mode 3: Single cycle running (time by 0 〇 112 320H
minute)
4: Continuous cycle (time by
minute)
5: Single cycle, continuous running
(time by minute)
0: Running at the first step speed
1: Continue to run with breakpoint
Program run breakpoint running frequency and retiming.
H-33 0 〇 114 321H
restore mode selection 2: Continue to run with the
breakpoint running frequency and
residual time.
Program running state
H-34 power down memory 0: NO power down memory 0 114 322H

selection 1: power down memory
1 step speed direction and 0: Forward; Acceleration time
H-35
accel/decel time 1/Deceleration time 1
0 ● 114 323H
2 step speed direction and 1: Forward; Acceleration time
H-36
accel/decel time 1/Deceleration time 2
1 ● 114 324H
3 step speed direction and 2: Forward; Acceleration time
H-37
accel/decel time 1/Deceleration time 3
2 ● 114 325H
4 step speed direction and 3: Forward; Acceleration time
H-38
accel/decel time 1/Deceleration time 4
3 ● 114 326H
5 step speed direction and 4: Reverse; Acceleration time
H-39
accel/decel time 1/Deceleration time 1 4 ● 114 327H

132
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

6 step speed direction and 5: Reverse; Acceleration time


H-40
accel/decel time 1/Deceleration time 2
5 ● 114 328H
7 step speed direction and 6: Reverse; Acceleration time
H-41
accel/decel time 1/Deceleration time 3
6 ● 114 329H
8 step speed direction and 7: Reverse; Acceleration time
H-42
accel/decel time 1/Deceleration time 4 7 ● 114 32AH

1 step speed running time


H-43
T1
10.0 ● 115 32BH

2 step speed running time


H-44
T2
10.0 ● 115 32CH

3 step speed running time


H-45
T3
10.0 ● 115 32DH

4 step speed running time


H-46
T4
10.0 ● 115 32EH
0.0-6000s(min)
5 step speed running time
H-47
T5
10.0 ● 115 32FH

6 step speed running time


H-48
T6
10.0 ● 115 330H

7 step speed running time


H-49
T7
10.0 ● 115 331H

8 step speed running time


H-50
T8
10.0 ● 115 332H

Differential frequency
H-51
∆f in swing frequency
0.00-20.00Hz 2.00Hz ● 115 333H

H-52 Motor rated power 0.4-1100.0KW ※ 〇 115 334H


H-53 Motor rated frequency 0.00-600.00Hz 50.00Hz 〇 115 335H
H-54 Motor rated speed 0-18000RPM ※ 〇 116 336H
H-55 Motor rated voltage 0-1500V ※ 〇 116 337H
H-56 Motor rated current 0.1-1000.0A ※ 〇 116 338H
H-57 Motor no load current 0.01-650.00A ※ 〇 116 339H
H-58 Motor stator resistor 0.001-65.000Ω ※ 〇 116 33AH
H-59 Motor rotator resistor 0.001-65.000Ω ※ ● 116 33BH
H-60 Motor stator inductance 0.1-6500.0mH ※ ● 116 33CH
Motor rotator mutual
H-61
inductance
0.1-6500.0mH ※ ● 116 33DH

0: Null operation.
H-62 Motor auto tuning selection 1: Rotational motor auto tuning. 0 〇 116 33EH
2: Stationary auto tuning
Motor magnetic saturation
H-63
coefficient 1
0-9999 ※ ● 116 33FH

Motor magnetic saturation


H-64
coefficient 2
0-9999 ※ ● 116 340H

133
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

Motor magnetic saturation


H-65
coefficient 3
0-9999 ※ ● 116 341H

0: Local machine configure as


linkage slave station
H-66 Linkage main station setting
1: Main station control mode 1.
0 ● 117 342H
2: Main station control mode 2.
H-67 Local inverter address 1-247 1 ● 117 343H
0: No check (N,8,1)
1: Even parity check(E,8,1)
H-68 Data format 3 〇 117 344H
2: Odd parity check (O,8,1)
3: No check (N,8,2)
0: 1200bps
1: 2400bps
2: 4800bps
H-69 Baud rate 3 〇 117 345H
3: 9600bps
4: 19200bps
5: 38400bps
Communication setting
H-70
frequency ratio
0.00-20.00 1.00 ● 117 346H

Time of communication time


H-71
out 0.0-6500.0s 10.0s ● 117 347H

LED“0” digit: RS485


communication
broken responding mode
0.Give alarm and free stop
1.No alarm and continue running
RS485 communication 2.No alarm but stop
H-72
broken responding mode LED “00” digit: Communication 0001 ● 117 348H
write operation mode.
0: Reply for write operation
1: No reply for write operation
LED “000” digit:: reserved
LED “0000” digit: reserved
H-73 Respond relay 0.000-1.000s 0.005s ● 118 349H
Instantaneous stop decel.
H-74
respond voltage lower limit
0%-200% 20% ● 118 34AH

Instantaneous stop decel.


H-75
respond voltage upper limit
0%-200% 90% ● 118 34BH

Instantaneous stop decel.


H-76
gain
0.01-10.00 2.00 ● 118 34CH

Voltage recover stability


H-77
time
0.0-100.0s 2.0s ● 118 34DH

Torque compensation upper


H-78 0.00-60.00% 50.00% 118 34EH
limit
Output terminal external
H-79
control status
0-9999 0 ● 118 34FH

H-80 Reserved 118 350H

134
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

Appendix 2: RS485 Communication Protocol


1 Communication Protocol
AC70 series frequency inverter can select the RS485 communication interface. The international standard ModBus
communication protocol is adopted for master-slave communication. The consumer can carry out centralized control by
PC/PLC, upper machine, main station frequency inverter etc (Setting of the frequency inverter control command,
running frequency, relative function parameters modification, frequency inverter working state and malfunction
information monitoring etc.. to adapt to the special application requirements.
2 Protocol Content
This ModBus protocol defines the information content and format of asynchronous transmission in series
communication. It includes: host machine polling, broadcast and the format of slave machine response. Host machine
data frame includes: slave machine address (or broadcast address), ask action code, data and fault check. Slave
machine response is same structure: action check, back data and fault check. If slave machine meet fault while accept
frame, or can’t compete the action asked, fault information will be feed back to host machine.
3 Application Mode
AC70 series frequency inverter controls network for “single host machine and many slave machines” with
RS232/RS485.
Remote RS485 communication needs shield cable and shield grounding.
For long distance communication, we suggest to open J6 and add 120Ωresistance to prevent signal reflection.
4 Main Line Structure
1, Port mode: RS485 port
2, Transmission mode: Asynchronous series, half duplex transmission mode. At same time, one of the host machine
and slave machine sends data, anther receives data. Data is sent one by one frame as report form in asynchronous
series communication.
3, Topological structure: One host machine with several slave machines. Range of slave machine address is 1 to 247.
O is broadcast address. Every slave machine address is only one. It is the base of ModBus series communication.
5 Protocol Explain
AC70 series frequency inverter communication protocol is main-slave ModBus communication protocol of
asynchronous series. In the net, only the host machine can set up protocol “inquire/ order”. Slave machines can only
respond to host machine. Host machine means PC, main frequency inverter, industrial control equipment or PLC…
Slave machines are AC70 frequency inverters and other control equipments with same communication protocol. Host
machine can communicate with only one slave machine or broadcast to all slave machines. Slave machine need
feedback every “inquire/order” of host machine, but no need feedback broadcast.
5.1 Communication frame structure
The ModBus protocol communication data format of AC70 series frequency inverter is RTU (remote terminal unit) mode.
Communication data format is as follows:
The byte composition: Include initiation bit, 8 data bit, check bit and stop bit.
No check bit
Initiation
Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7 Bit8 Even check bit stop bit
bit
Odd check
In RTU mode, it always starts after at least 3.5 byte transmission time which is easy realized under Baud rate. And next
data is: slave machine address, operation order code, data and CRC check. Every domain transmission is hexadecimal
0...9,A...F. Network equipment detects the network bus unceasingly, including the interval time. While receiving the first
domain (address information, each network equipments carry out decoding to judge whether the byte is for itself. While
the final byte transmission is completed, there will be at least 3.5 bytes transmission time interval to indicate that this
frame is over. Then a new information’ transmission can begin

One frame message must be transmitted as a continued data flow. If there is a pause over 1.5 byte before the end, the
receiving equipment will clear the half-baked information. And the next byte will be considered as the address domain of
135
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

a new frame. Similarly, if the interval between a new frame start-up and the former frame is smaller than 3.5 byte time,
the receiving equipment will think that it is the former one frame continuation. Because of the jumbled frame, finally
CRC checking value is incorrect, what leads to the communication mistake.
RTU frame’s standard structure:
Frame START Transmission time of 3.5 bytes
Communication address:
Slave machine address
0~247(decimal)(0 is broadcast address)
03H:read slave machine parameter
Function code CMD 06H: write slave machine parameter
08H:circuit auto-detection
Data domain
DATA(N-1)
parameter address, parameter number, parameter values ,

DATA(0)
CRC CHK low-order
Detecting value:16 bit CRC check value
CRC CHK high-order
Frame ending transmission time of 3.5 bytes
5.2 Order code and communication data description
5.2.1 Order code:03H, read N word (can continue reading 5 words at most)
For example:A frequency inverter who is slave machine with address 01 H and memory initial address 0101H([E-01])
reads 3 words continuously. Then the structure of that frame is described as follows:
RTU host machine order information
START Transmission time of 3.5 bytes
Slave machine address 01H
Order code 03H
Start address high-order 01H
Start address low-order 01H
Data number high-order 00H
Data number low-order 03H
CRC CHK low-order 55H
CRC CHK high-order F7H
END Transmission time of 3.5 bytes
RTU Slave machine responding information (normal)
START Transmission time of 3.5 bytes
Slave machine address 01H
Order code 03H
Byte number low-order 06H
Data address 0101H high-order 00H
Data address 0101H low-order 02H
Data address 0102H high-order 00H
Data address 0102H low-order 00H
Data address 0103H high-order 00H
Data address 0103H low-order 06H
CRC CHK low-order D8H
CRC CHK high-order B7H
END Transmission time of 3.5 bytes

136
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

RTU Slave machine responding information (abnormal)


START Transmission time of 3.5 bytes
Slave machine address 01H
Order code 83H
Error code 04H
CRC CHK low-order 40H
CRC CHK high-order F3H
END Transmission time of 3.5 bytes
5.2.2 Order code:06H, write a Word.
Function: write a word data in the designated data address. It can be used to revise the frequency inverter parameters.
For example: 5000 (1388 H. is written into 0110H [ ( E-16]) address of slave frequency inverter with address 02H. Then
the structure of this frame is described as follows:
RTU host machine order information
START Transmission time of 3.5 bytes
Slave machine address 02H
Order code 06H
Write data address high-order 01H
Write data address low-order 10H
Data content high-order 13H
Data content low-order 88H
CRC CHK low-order 84H
CRC CHK high-order 96H
END Transmission time of 3.5 bytes
RTU Slave machine responding information (normal)
START Transmission time of 3.5 bytes
Slave machine address 02H
Order code 06H
Write data address high-order 01H
Write data address low-order 10H
Data content high-order 13H
Data content low-order 88H
CRC CHK low-order 84H
CRC CHK high-order 96H
END Transmission time of 3.5 bytes
RTU Slave machine responding information (abnormal)
START Transmission time of 3.5 bytes
Slave machine address 02H
Order code 86H
Error code 01H
CRC CHK low-order 73H
CRC CHK high-order A0H
END Transmission time of 3.5 bytes
5.2.3 Order code:08H, circuit auto-detection
Function: Send back the slave machine responding information which is identical with the host machine command
information. It is used to check whether the signal transmission between the host machine and slave machine is regular
or not. The checking code and the data can be set freely.
RTU Host machine command information
START Transmission time of 3.5 bytes
Slave machine address 01H
Order code 08H
Detecting code high-order 00H
Detecting code low-order 00H

137
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

Data high-order 13H


Data low-order 88H
CRC CHK low-order EDH
CRC CHK high-order 5DH
END Transmission time of 3.5 bytes
RTU Slave machine responding information (normal)
START Transmission time of 3.5 bytes
Slave machine address 01H
Order code 08H
Detecting code high-order 00H
Detecting code low-order 00H
Data high-order 13H
Data low-order 88H
CRC CHK low-order EDH
CRC CHK high-order 5DH
END Transmission time of 3.5 bytes
RTU Slave machine responding information (abnormal)
START Transmission time of 3.5 bytes
slave machine address 01H
Order code 88H
Error code 03H
CRC CHK low-order 06H
CRC CHK high-order 01H
END Transmission time of 3.5 bytes
5.2.4 Communication frame error check mode
The standard ModBus serial network adopts two kinds of error check mode: odd/even checking which is used to check
every character and CRC detecting which is used to check one frame of data.
1, Odd-even checking
The users can configure the controller with odd or even checking, or no checking, what will determine how to set
odd/even checking in every character.
If odd /even checking have been allocated, "1" bit will be accounted to the bit number of each character (7 bits in ASCII
mode, 8 bits in RTU.. For example, the RTU character frame contains the following 8 bits: 1 1 0 0 0 1 0 1
There are 4 bits with number"1". If using the even checking, odd/even checking bit of the frame will be 0, then there are
still 4 bits with number"1". If using odd checking, odd/even checking bit of the frame will be 1. Then there are 5 bits with
number"1".
If odd/even checking has not been allocated, there will be no checking bit during the transmission, and no checking
detection. One additional stop bit will be filled into the character frame in transmission.
2, CRC-16(cycle redundant check)
While the RTU frame form in use; the frame has included the frame error detecting domain which calculates base on
the CRC method. The CRC domain checks the content of the entire frame. The CRC domain is two bytes, containing
binary values of 16 bits. It is added to the frame after calculated by the transmission equipment. The receiving
equipment calculates CRC who receives frame again, and compares it with the value of the receiving CRC domain. If
both CRC value are not equal, it means the transmission has mistake. CRC is firstly stored in 0xFFFF. Then a program
is used to process the continuous 6 or above bytes in the frame and the value of current registers. Only 8Bit in every
character is valid to CRC. Start bit、stop bit and parity check bit are invalid.
In the process of CRC coming out, each 8 characters independently XOR with register content. The result moves to
minimum effective digit. LSB is extracted to be detected. If LSB is 1, the register is independently XOR with the pre-set
value. If LSB is 0, it is no XOR. This process needs to repeat 8 times. After the last bit (the eighth bit. is accomplished.
Next 8 bits bytes will independently XOR with register content. All the final bytes in the frame are CRC value after
processed.
This CRC operation method adopts the international standard CRC checking rule. Users can consult the relevant
standard CRC operation while editing the CRC algorithm to compile out the real CRC calculation program as required.
Now here provide the user a simple CRC operation function (with C language programming:
unsigned int crc_chk_value(unsigned char *data_value,unsigned char length)
{

138
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

unsigned int crc_value=0xFFFF;


int i;
while(length--)
{
crc_value^=*data_value++;
for(i=0;i<8;i++)
{
if(crc_value&0x0001)
{
crc_value=(crc_value>>1)^0xa001;
}
else
{
crc_value=crc_value>>1;
}
}
}
return(crc_value);
}
5.2.5 Communication data address definition
It is used to control frequency inverter operation, get state information and parameter setting of frequency inverter.
(1.AC70 serial function parameter address express rules
Take frequency inverter function parameter serial numbers as register address which are divided into the high byte and
the low byte two parts. The high byte expresses the function parameter group serial numbers. The byte expresses the
inner serial numbers of each function parameter group. All need to be changed to hexadecimal.
Address domain high byte definition:
x1xxH:basic parameter group (E group)
x2xxH:external terminal parameter group(F group)
x3xxH:dedicated function parameter group (H group).
xCxxH: monitoring parameter group (C group).
xExxH: fault information group (ER group).
Attention: due to possibility that the parameters are frequently rewritten exists in the communication, EEPROM are
frequently stored. So its lifetime is cut down. As for the consumer, some function is unnecessarily to store in the
communication mode, only require to changing the value of RAM inner, can satisfy the usage requirement. As AC70
communication protocol stipulates, when it use writing order (06 H), if the parameter function code address domain
highest digit is 0, merely write in the frequency inverter RAM, power down without storing, if the parameter function
code address high half digit is 1, write in EEPROM, namely power off with storing.
For example, rewriting the function parameter [E-16], not depositing to EEPROM, address expresses for 0110H,
depositing to EEPROM, address expresses for 1110H.
Only write in the frequency inverter RAM, power down without storing.
START Transmission time of 3.5 bytes
Slave machine address 02H
Order code 06H
Write data address high-order 01H
Write data address low-order 10H
Data content high-order 13H
Data content low-order 88H

139
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

CRC CHK low-order 84H


CRC CHK high-order 96H
END Transmission time of 3.5 bytes
Write in EEPRAM, power off with storing.
START Transmission time of 3.5 bytes
Slave machine address 02H
Order code 06H
Write data address high-order 11H
Write data address low-order 10H
Data content high-order 13H
Data content low-order 88H
CRC CHK low-order 84H
CRC CHK high-order 96H
END Transmission time of 3.5 bytes
(2) Other communication parameter address specification:
Function Address Explain R/W trait
Communication Communication give frequency, power down
3000H W/R
give frequency without storing
0000H:No command
0001H:FWD
0002H:REV

Communication 0003H:Forwarder JOG


3001H W
order setting 0004H:Reverse JOG
0005H:Decelerate to stop
0006H:Free stop
0007H:Fault recover
Bit0 0: Stop 1:WORKING
Bit1 0: Not ACC 1:ACC
Frequency inverter
3002H Bit2 0: Not DEC 1:DEC R
state
Bit3 0: FWD 1:REV
Bit4 0: Normal 1:Fault
Fault code 3003H Fault code(See fault code table) R

140
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

Appendix 3: LCD Keyboard Manual


1 Function Characteristic
LCD keyboard is designed for user checking function parameters more directly. Language of LCD keyboard includes
English and Chinese, and is compatible with other LED keyboard designed by our company.
It can display two monitoring parameters at the same time when inverter stops or runs.
States of running, stop and fault all have vivid image that makes user to understand and remember states of inverter
more conveniently.
It also has parameter copy and download functions, and can download parameters of same series inverter .It is
convenient for user to change batch parameters
Potentiometer is also on the keyboard and used for changing given frequency
Note:
1. If special type inverter needs LCD keyboard, please contact with our company.
2. User must confirm that type of LCD keyboard and type of inverter are suited.

Software version of LCD Type of inverters


KB10B AC70
KB30B AC80B
KB50B AC80C
KB70B AC100

2 Monitor Menu
Input F 50.00Hz

Output F 50.00Hz

Chart 1 (a) at stop state Chart1 (b) at FWD running state Chart1 (c) at REV running state

Input F 5.00Hz Input F 5.00Hz

Output F 5.00Hz Output F 5.00Hz

Chart1 (d) at JOG FWD state Chart1 (e) at JOG REV state

It can display two monitoring parameters and running or stop status every state of inverter, details refer to chart 1.User
can select first -line monitoring parameters by ,and select second-line monitoring parameters by .
3 Monitoring Parameter Menu

Chart 2 Monitoring menu


Please press key long time for 1s, then it will go into monitoring menu as chart 2.And user can check parameters
by or key, pressing or key to return back.

141
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

4 Parameters Menu
(1) First level menu(Reserve)
(2) Second level menu

Chart 3(a) Basic parameter Chart 3(b) External terminal Chart 3(c) Function parameter
The second level menu include 3 part: Basic parameter, External terminal, Function parameter, as show in chart 3.
Press key and enter into 3(a).User can select anyone of them by press or key. Press key
means selecting the item, And Press key to move monitoring interface, Basic parameter, External terminal,
Function parameter these 4 inverter face circular by turn.
(3) Third level menu

Chart 4 (a) changing line Chart 4 (b) data Chart 4 (c) group
After going into second level menu, press key to go into third level menu. Third level menu includes three kinds,
changing line, data and group.
Changing line: First line displays second level items, second and third line display third level items, and position of
cursor is factory default setting, details refer to char t 4(a).
Press key to replace items,
Press or to move cursor,
Press to return back,
Press to select item, and then return back.
Data: First line displays second level menu items, and second line displays data ,details refer to chart 4(b)
Press to replace items,
Press or to increase or decrease data while pressing , Press or to increase or decrease
data from lowest bit without pressing ,
Press to return back.
Press to confirm modifying data, and then return back.
Group: First line displays second level menu items, second line displays group number, and third line displays third level
menu items, details refer to chart 4(c)
Press to change another group, Press or to change items,
Press key to return back.
Press to confirm modifying items, and then return back.
If pressing or cannot modify items in third level menu, and display ”Read only” all that reminder user of
parameter is no t allowed to modify or when inverter is running ,modifying is forbidden

142
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

5 Fault

Chart 5 (a) fault Chart 5 (b) fault reason


Fault: First line displays fault icon shining, second line displays fault code and name, and third line reminder user of
pressing to check fault reasons, details refer to chart 5(a). Press to go into fault reason.
Press to reset fault when fault has been cleared
Fault reason: First line displays fault icon、code and name, other lines display reasons, details please refer to chart
5(b).If there up or down arrows, please press or to change another page to check reasons,
Press or to return back
6 Terminal State
C- 14 Input terminal C- 15 Output terminal
X1 X2 X3 X4 Y1

X5 X6 X7 X8 Y2

Chart 6 (a) input terminal Chart 6 (b) output terminal


Input terminal: details please refer to chart 6(a)
Output terminal: details please refer to char 6(b)
Note: If monitoring items are both terminal state in both lines, it will displays input terminal firstly.
7 Parameters Copy

Parameter copying . . . Copy is over Copy fault

Chart7 (a) copying Chart7 (b) copy complete Chart7 (c) copy fault

Downloading . . . Download is over Download fault

Chart7 (d) download Chart7 (e) download complete Chart7 (f) download fault
Parameter copy: details please refer to chart 7 (a), 7(b), 7(c)
Check E-64 and select item “sending to keyboard from inverter”,and then press .When it displays “completely
copy ”, it means finishing copy operation details refer to chart 7(b).When it displays ”copy fault” ,it means operation is
failed, details please refer to chart 8(c).Press key to return .
Download: same way as copy
Note:Inverters must be the same series , when downloading parameters

143
AC70 VC CONTROL FREQUENCY INVERTER MANUAL APPENDIX

8 Self-tuning

Detect waiting Resting self-tuning

Chart 8 (a) waiting Chart 8 (b) resting type self-tuning

Rotary self-tuning Exciting detect

Chart 8 (c) rotary type self-tuning Chart 8(d) exciting magnetic detecting
Resting type self-tuning: steps as chart 8 (a), (b) and (d).Please set H-62=2, and press key to go into motor
detecting waiting menu, details refer to chart 8(a).Then press key, and it will display resting self-tuning, details
refer to 8(b), It displays “exciting detecting” when self-tuning is over, details refer to chart 9(d), then it will return back
automatically.
Rotary self-tuning: steps as chart 8 (a),(b)and (d). Please set F-62=1, and press key to go into motor detecting
waiting menu, details refer to chart 8(a).Then press key, and it will display resting self-tuning, details refer to 8(b),
while resting self-tuning is over, it displays rotary self-tuning, details refer to chart8(c), After rotary self-tuning over, it
displays exciting detecting, details refer to chart 8(d), then it will return back automatically.
9 Other Menus
Locked code
Voltage is low
0

Chart 9 (a) keyboard locked Chart 9 (b) low voltage Chart 9 (c) model of inverter
Keyboard locked, as chart 9(a).Keyboard will display locked menu when going into next menu, after user setting
password and selecting parameter locked function. Please type correct password and then go into next menu.
Low voltage, as chart 9(b).When input voltage is low, it will display this warning.
Model of inverter, as chart 9(c).When power on, if communication is ok, it will display this menu, and if not, it will display
keyboard connection fault.

144

Das könnte Ihnen auch gefallen