Sie sind auf Seite 1von 35

Motor Starting Basics

Understand these concepts before starting squirrel cage induction motors.


by Blake Bailey
06/19/2019

Questions about starting electric motors are common. Motor starting problems resulting from these questions can be costly and
confusing, leading to production delays and sometimes catastrophic motor failure. This article will briefly explore some of the most
common questions about the direct online (DOL) starting of squirrel cage induction motors. Through proper application, end users
can have confidence that their motors and related equipment will not incur damage during the starting cycle.

Reading Speed-Torque-Current Curves


Speed-torque-current curves are plots of a motor’s torque and speed characteristics from zero speed up to no load speed
(practically synchronous speed for an induction motor). All terms are commonly plotted as either percentage of full load or in their
actual units (e.g. revolutions per minute [rpm], foot-pounds of torque and amperes). It is conventional for torque and current to both
be plotted on the same graph, as well as being presented separately as shown in Image 1. Typically, plots of reduced voltage
torque and current, as well as the load’s speed-torque characteristics, are also given. For the latter, it is key to obtain the load’s
speed-torque curve and not simply the “running curves” for pumps and fans. Finally, these graphs can be plotted either horizontally
(speed on the x-axis, torque and current on the y-axis) or vertically (speed on the y-axis, torque and current on the x-axis).
torque curve at zero speed will show locked rotor torque (Images courtesy of designmotors)

Key performance information related to motor starting is shown on speed-torque-current plots. In Image 1, the intersection of the
torque curve at zero speed will show locked rotor torque (LRT), while the maximum torque value shown represents breakdown
torque (BDT). Both full load torque (FLT) and current levels (FLC/FLA) are found by drawing a vertical line from the rated speed
point until it intersects both plots. The point on the current plot corresponding to zero speed will show locked rotor current
(LRC/LRA), while the motor’s no load current (NLC/NLA) is shown by the point corresponding to the highest speed shown.

Reading Thermal Damage Curves


Thermal damage curves are plots that provide information about acceleration times, operational time limits at finite current levels
and time limits on operation above full load. These curves are also known as “thermal limit curves,” “safe operating time curves” or
“acceleration curves.” They are typically plotted with motor current as the x-axis and time in seconds as the y-axis on a logarithmic
scale. As seen in Image 2, the plots found closest to the current scale show motor current during acceleration. These plots, typically
at various voltage levels, intersect the speed scale at a point that represents LRC and intersect the time scale at the full-load current
point to show anticipated acceleration time.
There are usually one or two plots shown above the accelerating current curves, which show safe locked rotor times as well as a
“running” or “overload” curve. The safe locked rotor time (“safe stall time”) plot(s) are intended to show the number of seconds a
motor can safely withstand a given current level at various voltage levels.

If shown separately, the “cold” curve provides the safe locked rotor times for the motor when it is first started (the “cold” condition),
while the “hot” curve provides the safe stall times after a motor has either been recently started or run under load. It should be noted
that Image 2 only shows a single plot connecting the safe stall time plots in cold condition with the “overload” curve. The safe stall
time plots should never overlap or come substantially close to the motor accelerating current plots, as this represents dangerous
heating in the rotor bars and end rings.

The overload curve shows the time that a motor can safely operate while running at, or above, full-load current. Typically, the upper
bounds of this curve correspond to a continuous time associated with the motor’s highest safely rated load level (often the service
factor). If this plot is followed to higher levels of current (and therefore lower values of time), it will often be plotted to intersect the
safe stall time curve(s), but most often is shown to just nearly intersect them.

Locked Rotor Performance


Locked rotor performance encompasses the motor characteristics related to when a motor is in a locked (stalled) condition, such as
at initial energization. Locked rotor performance is affected by combinations of the motor design, driven-load characteristics and
onsite conditions. Typically, end users will specify locked rotor performance requirements and provide information on the driven
load in addition to installation details such as typical voltage dip levels or if the motor will be started via a method besides DOL.
Typically, the motor design for locked rotor is centered around providing the required torque while minimizing LRC and potential ill
effects on full-load operation.
Most standard commercial induction motors are rated as National Electrical Manufacturers Association (NEMA) Design B, which
provides a reasonable balance between LRT and LRC for most loads. For larger motors or specialty applications, however, finer
performance requirements might be in place, which require a motor design with features like a custom rotor bar shape or
specialized rotor alloy. Aside from starting the motor via a device such as an auto-transformer, special contactor arrangement, or
variable frequency drive (VFD), the greatest effect that on-site conditions have on locked rotor performance is the customer’s
voltage dip level.

LRC decreases in basically direct proportion with voltage, while LRT decreases as approximately voltage squared and can quickly
cause starting issues for processes that start under load. Careful coordination between the end user and motor supplier is required
to ensure that a proper motor design is selected for both onsite conditions and the load’s profile to provide reliable, safe locked rotor
performance.

Determining Acceleration Time


Closely related to locked rotor performance is the acceleration time a motor takes to start its load. Many of the same cause and
effect relationships between motor design, onsite conditions, and load characteristics hold true for effects on both locked rotor
performance and acceleration time. In the case of acceleration time, however, the entire speed-torque characteristics of the motor
and load must be considered with net accelerating torque and total inertia being the most vital characteristics.
Image 3. Acceleration time
figure

There are several methods available for estimating acceleration time, but all methods must begin with the motor and load’s speed-
torque curves and total inertia. The most basic method divides the speed torque characteristics up into equal intervals (typically
somewhere around 10 as shown in Image 3) and finds the net accelerating torque available during that period to calculate its
individual contribution to acceleration time. Net accelerating torque is defined as the load torque subtracted from the motor torque at
a given point (generally the motor torque should be at least 10 percent greater than load torque). Once net accelerating torque and
time have been found for all intervals from zero speed to full-load speed, the times in seconds are added to provide total estimated
acceleration time. For every interval, the total inertia (motor and load reflected to motor shaft) must be accounted for, as high inertia
loads (e.g. large centrifugal fans) can lengthen acceleration times.

Finally, similar to locked rotor performance, voltage dip and recovery must be considered, as they will reduce motor torque available
and thus increase total acceleration time.

Other Related Areas


There are numerous questions surrounding motor starting that can be explored outside of this analysis, but some other points for
consideration are:

 a motor’s rated KVA Code Letter (assigns a “code letter” defined by NEMA MG-1 that gives an idea of the motor’s locked
rotor current level when compared to its rated hp)
 how to interpret a large motor’s acceleration nameplate information (for example, understanding what the number of hot and
cold starts means and how to interpret the time required between them)
 the theory behind safe locked rotor times and how these values are derived (principally these are based on the amount of
time anticipated for critical motor components like rotor bars, end rings and stator windings to reach damaging temperatures)

With this information, end users and those involved in specifying induction motors can confidently operate and select motors for
various starting scenarios. Note: this article has been written with squirrel cage induction motors in mind, most of these concepts
are applicable to other motor types, including wound field synchronous (with squirrel cage rotor windings) and wound rotor induction
motors.

Das könnte Ihnen auch gefallen