Job Number Sheet

1353
Job Title
220 kv OHL INTER CONNECTION FOR MIRFA IWPP (LOT 1B & 2B)
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com TRANSCO
E-Mail : mail@prokon.com Calcs by Checked by Date
MAHMOUD ALI 19.12.2015
Circular column design C12

Circular column design by PROKON. (CirCol Ver W2.6.08 - 26 Jun 2015)

Design code : BS8110 - 1997

Input tables
General design parameters and loads:
Load Ultimate Limit State Design Loads
Case Description
P (kN) Mx top (kNm) My top (kNm) Mx bot (kNm) My bot (kNm)
1 CASE-30U(UPLIFT) -1083 270 0 0 0
2 CASE-30C(COMP.) 1128 280 0 0 0
3 CASE-31U(UPLIFT) -1080 276 0 0 0
4 CASE-31C(COMP.) 1125 283 0 0 0

Ø (mm) 800
d' (mm) 75
Lo (m) 5.5
fcu (MPa) 35
fy (MPa) 450

General design parameters: Y

Given:
d = 800 mm 750

d' = 75 mm
Lo = 5.500 m 500

fcu = 35 MPa X X

fy = 450 MPa
250

Therefore:
0

Y
250

500

750
0

π. d2
Ac =
4
π×8002
=
4
= 502.7×103 mm²

diax' = dia - d'


= 800 - 75
= 725.000 mm

diay' = dia - d'


= 800 - 75
= 725.000 mm
Job Number Sheet
1353
Job Title
220 kv OHL INTER CONNECTION FOR MIRFA IWPP (LOT 1B & 2B)
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com TRANSCO
Calcs by Checked by Date
E-Mail : mail@prokon.com MAHMOUD ALI 19.12.2015

Assumptions:
(1) The general conditions of clause 3.8.1 are applicable.
(2) The section is symmetrically reinforced.
(3) The specified design axial loads include the self-weight of the column.
(4) The design axial loads are taken constant over the height of the column.

Design approach:
The column is designed using an iterative procedure:
(1) The column design charts are constructed.
(2) An area steel is chosen.
(3) The corresponding slenderness moments are calculated.
(4) The design axis and design ultimate moment is determined .
(5) The steel required for the design axial force and moment is read from
the relevant design chart.
(6) The procedure is repeated until the convergence of the area steel
about the design axis.
(7) The area steel perpendicular to the design axis is read from the relevant
design chart.
(8) The procedure is repeated for each load case.
(9) The critical load case is identified as the case yielding the largest
steel area about the design axis.

Through inspection:
Load case 3 (CASE-31U(UPLIFT)) is critical.

Check column slenderness:


End fixity and bracing for bending about the X-X axis:
At the top end: Condition 2 (partially fixed).
At the bottom end: Condition 2 (partially fixed).
The column is unbraced.
∴ ßx = 1.50 Table 3.22

End fixity and bracing for bending about the Y-Y axis:
At the top end: Condition 2 (partially fixed).
At the bottom end: Condition 2 (partially fixed).
The column is unbraced.
∴ ßy = 1.50 Table 3.22

Effective column height:

lex = ßx. Lo
= 1.5×5.5
= 8.250 m

ley = ßy. Lo
= 1.5×5.5
= 8.250 m
Job Number Sheet
1353
Job Title
220 kv OHL INTER CONNECTION FOR MIRFA IWPP (LOT 1B & 2B)
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com TRANSCO
E-Mail : mail@prokon.com Calcs by Checked by Date
MAHMOUD ALI 19.12.2015
Column slenderness about both axes:

lex
λx =
dia
8.25
=
.8
= 10.312

ley
λy =
dia
8.25
=
.8
= 10.312

Minimum Moments for Design:


Check for mininum eccentricity: 3.8.2.4
Check that the eccentricity exceeds the minimum in the plane of bending:
Use emin = 20mm

Mmin = emin. N
= .02×-1080
= -21.6000 kNm

Check if the column is slender: 3.8.1.3

λx = 10.3 > 10

λy = 10.3 > 10

∴ The column is slender.

Check slenderness limit: 3.8.1.7

Lo = 5.500 m < 60⋅ dia' = 48.000 m

∴ Slenderness limit not exceeded.

Initial moments:
The initial end moments about the X-X axis:
M1 = Smaller initial end moment = 0.0 kNm
M2 = Larger initial end moment = 276.0 kNm
Job Number Sheet
1353
Job Title
220 kv OHL INTER CONNECTION FOR MIRFA IWPP (LOT 1B & 2B)
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com TRANSCO
Calcs by Checked by Date
E-Mail : mail@prokon.com MAHMOUD ALI 19.12.2015
The initial moment near mid-height of the column : 3.8.3.7

Mi = - 0.4. M1 + 0.6. M2
= - 0.4×0 + 0.6×276
= 165.600 kNm

Mi2 = 0.4. M2
= 0.4×276
= 110.400 kNm

∴ Mi ≥ 0.4M2 = 165.6 kNm

The initial end moments about the Y-Y axis:


M1 = Smaller initial end moment = 0.0 kNm
M2 = Larger initial end moment = 0.0 kNm

The initial moment near mid-height of the column : 3.8.3.7

Mi = - 0.4. M1 + 0.6. M2
= - 0.4×0 + 0.6×0
= 0.0000×100 kNm

Mi2 = 0.4. M2
= 0.4×0
= 0.0000×100 kNm

∴ Mi ≥ 0.4M2 = 0.0 kNm

Deflection induced moments: 3.8.3.1


Design ultimate capacity of section under axial load only:

1 . .
Nuz = 0.4444. fcu. Ac + fy Asc
1.15
1
= 0.4444×35000×.50265 + ×450000×.00582
1.15
= 10.10×103 kN

Maximum allowable stress and strain:


Job Number Sheet
1353
Job Title
220 kv OHL INTER CONNECTION FOR MIRFA IWPP (LOT 1B & 2B)
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com TRANSCO
E-Mail : mail@prokon.com Calcs by Checked by Date
MAHMOUD ALI 19.12.2015

Allowable compression stress in steel

1 .
fsc = fy
1.15
1
= ×450
1.15
= 391.304 MPa

Allowable tensile stress in steel

1 .
fst = fy
1.15
1
= ×450
1.15
= 391.304 MPa

Allowable tensile strain in steel

fst
ey =
Es
391.3
=
200000
= 0.0020

Allowable compressive strain in concrete

ec = 0.0035

Design ultimate load and moment:


Design axial load:
Pu = -1080.0 kN

For bending about the X-X axis, the maximum design moment is the greatest of: 3.8.3.7
(a) 3.8.3.2

M = M2 + Madd
= 276 + 0
= 276.000 kNm

(d) 3.8.3.2

M = emin. N
= .02×-1080
= -21.6000 kNm
Job Number Sheet
1353
Job Title
220 kv OHL INTER CONNECTION FOR MIRFA IWPP (LOT 1B & 2B)
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com TRANSCO
Calcs by Checked by Date
E-Mail : mail@prokon.com MAHMOUD ALI 19.12.2015

Thus 3.8.3.2

M = 276.0 kNm

Moment distribution along the height of the column for bending about the X-X:
At the top, Mx = 276.0 kNm
Near mid-height, Mx = 165.6 kNm
At the bottom, Mx = 0.0 kNm

Moments about X-X axis( kNm)


Mx=276.0 kNm
Mxtop=276.0 kNm Mxmin=-21.6 kNm

+ =

Mxbot=0.0 kNm

Initial Additional Design

For bending about the Y-Y axis, the maximum design moment is the greatest of: 3.8.3.7
(a) 3.8.3.2

M = M2 + Madd
=0 +0
= 0.0000×100 kNm

(d) 3.8.3.2

M = emin. N
= .02×-1080
= -21.6000 kNm

Thus 3.8.3.2

M = 0.0 kNm

Moment distribution along the height of the column for bending about the Y-Y:
At the top, My = 0.0 kNm
Near mid-height, My = 0.0 kNm
At the bottom, My = 0.0 kNm
Job Number Sheet
1353
Job Title
220 kv OHL INTER CONNECTION FOR MIRFA IWPP (LOT 1B & 2B)
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com TRANSCO
E-Mail : mail@prokon.com Calcs by Checked by Date
MAHMOUD ALI 19.12.2015

Moments about Y-Y axis( kNm)


My=0.0 kNm
Mytop=0.0 kNm Mymin=-21.6 kNm

+ =

Mybot=0.0 kNm

Initial Additional Design

Design of column section for ULS:


Through inspection:
The critical section lies at the top end of the column.

The column is designed to withstand the uni-axially applied moment about


the major axis.

For bending about the design axis:

Column design chart


Moment max = 2878 kNm @ 4079kN

20E3
18E3
16E3
14E3
12E3
10E3
8000
Axial Load (kN)

6000
2% 3% 4% 5% 6%
4000 0% 1%
1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

3200

3400
200

400

600

800

2000

-2000
-4000
-6000
-8000
-10E3

Bending Moment (kNm)

Reinforcement required about the X-X axis:


From the design chart, Asc = 5820 = 1.16%
Job Number Sheet
1353
Job Title
220 kv OHL INTER CONNECTION FOR MIRFA IWPP (LOT 1B & 2B)
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com TRANSCO
Calcs by Checked by Date
E-Mail : mail@prokon.com MAHMOUD ALI 19.12.2015
For bending perpendicular to the design axis:

Column design chart

Moment max = 2878 kNm @ 4079kN


20E3
18E3
16E3
14E3
12E3
10E3
8000
Axial Load (kN)

6000
2% 3% 4% 5% 6%
4000 0% 1%
1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

3200

3400
200

400

600

800

2000

-2000
-4000
-6000
-8000
-10E3

Bending Moment (kNm)

Reinforcement required about the Y-Y axis:


From the design chart, Asc = 2760

Design chart for bending about any axis:

Column design chart


Moment max = 2878 kNm @ 4079kN

20E3
18E3
16E3
14E3
12E3
10E3
8000
Axial Load (kN)

6000
2% 3% 4% 5% 6%
4000 0% 1%
1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

3200

3400
200

400

600

800

2000

-2000
-4000
-6000
-8000
-10E3

Bending Moment (kNm)


Job Number Sheet
1353
Job Title
220 kv OHL INTER CONNECTION FOR MIRFA IWPP (LOT 1B & 2B)
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com TRANSCO
E-Mail : mail@prokon.com Calcs by Checked by Date
MAHMOUD ALI 19.12.2015
Summary of design calculations:
Design results for all load cases:

Load case Axis N (kN) M1 (kNm) M2 (kNm) Mi (kNm) Madd (kNm) Design M (kNm) M' (kNm) Asc (mm²)
X-X 0.0 270.0 162.0 0.0 X-X 270.0
1 Y-Y -1083.0 0.0 0.0 0.0 0.0 Top 0.0 270.0 5741 (1.14%)

X-X 0.0 280.0 168.0 48.0 X-X 328.0


2 Y-Y 1128.0 0.0 0.0 0.0 48.0 Top 48.0 331.5 2011 (0.40%)

X-X 0.0 276.0 165.6 0.0 X-X 276.0


3 Y-Y -1080.0 0.0 0.0 0.0 0.0 Top 0.0 276.0 5820 (1.16%)

X-X 0.0 283.0 169.8 47.9 X-X 330.9


4 Y-Y 1125.0 0.0 0.0 0.0 47.9 Top 47.9 334.3 2011 (0.40%)

Load case 3 (CASE-31U(UPLIFT)) is critical.