Flow Pumping Remark/
S. No. Description of Pump Qty. Motor KW Motor
Rate Head Location
KW
A. FIRE FIGHTING PUMPS LOCATED IN FIRE PUMP ROOM AT BASEMENT-2
Electrical Driven Hydrant 2850 pump Room
1. 110M 1 No. 106 KW 106 KW
Pump LPM (Basement-2)
Where
Q = Flow in lpm flowing through nozzle
K = Nozzle Factor = 45 (As per manufacturer HD Fire)
Total Flow rate required =34 Nos. Nozzle x 56.92 lpm Flow on each
nozzle.
=1935 LPM
= 116.11 m3/Hour
Maximum water curtain Pump capacity required= 1935 LPM = 116.11 m3/hour
As Per water curtain requirement, there shall be minimum pressure of 1.6 kg/sq.cm at the last water
curtain
Note: Considering that basement shall be provided the water curtain system:
Total Vertical Length of Pipe from Plant Room to remotest water curtain = 9M
Total Horizontal Length of Pipe from Plant Room to remotest water curtain= 50 M
2
Head Loss Calculations -Annexure -II
C = 120
= 0.23 bar
Say = 2
Total Vertical Length of Pipe from Plant Room to remotest Fire Hydrant = 64 M
Total Horizontal Length of Pipe from Plant Room to remotest Fire Hydrant = 80 M
Total Length of Pipe from Plant Room to remotest Fire Hydrant = 144 M
Equivalent Length of Pipe Due to Fittings @ 10 % =14.4 M
Total Length of Pipe = 158.4 M
3
Say = 159 M
Design calculation for total pump head requirement as per using following pipe diameter.
C = 120
= 0.85 bar
Say = 9 M
A) Suction Header size for Sprinkler , Hydrant ,Diesel & water curtain pump:
Flow rate Q for Sprinkler & Hydrant pump = 2850 LPM
4
= 171 M3/Hr
No. of Pumps = 2No.
Flow rate Q for Water = 2280 LPM
Curtain pump = 136.8 M3/Hr
No. of Pumps = 1No.
Total Flow Rate = 0.133M3/s
Considered water velocity (v) = 1.5m/s
Suction pipe = 2 Nos.
Flow rate Q = Area x velocity
= Axv
D ( considering 2 nos. suction pipe) = √4Q/π v
= 0.250m
= 250mm
* Say = 250mm- 2 Nos
B) Delivery Header size for Sprinkler, Hydrant , Diesel & Water curtain Pump:
5
= Axv
d = √4Q/π v
= 0.200m
= 200mm
Say = 200mm
D) Individual Delivery Header size for Sprinkler , Hydrant ,Diesel pump:
Flow rate Q = 2850LPM
= 171M3/Hr
Considered water velocity (v) = 3m/sec
Flow rate Q = Area x velocity
= Axv
d =
= 0.142m
= 142mm
Say = 150mm
E) Suction size of jockey pumps :
Flow rate Q = 180LPM
= 10.8M3/Hr
= 0.003M3/s
Considered water velocity (v) = 1.5m/s
Flow rate Q = Area x velocity
= Axv
d = √4Q/π v
= 0.080m
= 80.02mm
Say = 80mm
F) Delivery size jockey pumps:
Flow rate Q = 180LPM
= 10.8M3/Hr
= 0.003M3/s
Considered water velocity (v) = 3m/s
Flow rate Q = Area x velocity
= Axv
d = √4Q/π v
= 0.065m
= 65.01mm
Say = 65mm
6
Flow rate Q = Area x velocity
= Axv
d = √4Q/π v
= 0.200 m
= 200 mm
Say = 200 mm