GENERAL NOTES: LEGEND:

LIGHTING
1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, EXISTING APPLICABLE RULES AND REGULATIONS OF THE MUNICIPALITY INVOLVED AND THE
2x36W T8 FLUORESCENT LUMINAIRE WITH OPAL DIFFUSER FOR SURFACE MOUNTING
REQUIREMENTS OF THE LOCAL UTILITY COMPANY. A
1x28W T5 BATTEN FLUORESCENT FIXTURE SURFACE MOUNTED
2. POWER SUPPLY FOR THE GENERAL POWER AND LIGHTINGS SHALL BE 230 VOLTS, SINGLE PHASE, 2-WIRE + GROUND (LINE TO NEUTRAL) 60 Hz. B

1x28W T5 BATTEN FLUORESCENT FIXTURE SURFACE MOUNTED


B1 WEATHERPROOF
3. ALL MATERIALS AND EQUIPMENT SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR THE INTENDED LOCATION
AND PURPOSE. 1x28W T5 FLUORESCENT FIXTURE SURFACE MOUNTED
Bx EXPLOSION PROOF (CLASS 1 DIVISION 1)
4. WIRING METHOD SHALL BE IN CABLE TRAY, IMC, OR METAL MOULDING UNLESS OTHERWISE SPECIFIED BY THE
OWNER. 2x18W CFL DOWNLIGHT WITH FORMED ALUMINUM
HOUSING WITH SPECULAR REFLECTOR SURFACE MOUNTED
5. ALL DIMENSIONS ARE IN MILLIMETER UNLESS OTHERWISE SPECIFIED. - CIRCUIT HOMERUN
DB-XX
6. ALL ELECTRICAL PANELS SHALL BE PAINTED WITH RUST INHIBITING PRIMER BEFORE APPLICATION OF FINISHING
DISTRIBUTION BOARD
PAINT. PANELS FOR INDOOR USE SHALL BE NEMA 1 TYPE OF CONSTRUCTION AND NEMA 4X TYPE FOR OUTDOOR USE.

7. ALL CIRCUIT BREAKERS TO BE USED SHALL BE BOLT-ON TYPE AND OF INDUSTRIAL QUALITY UNLESS OTHERWISE PE PHOTOCELL
SPECIFIED.
LIGHTING CIRCUIT

INSULATION SHALL BE THHN UNLESS OTHERWISE INDICATED. S SINGLE POLE SWITCH

9. MINIMUM TRADE SIZE OF CONDUITS ALLOWED SHALL BE 15mm DIA. UNLESS OTHERWISE INDICATED. Sx SINGLE POLE SWITCH
EXPLOSION PROOF (CLASS 1 DIVISION 1)
10. WIRE COLOR CODING SHALL BE AS FOLLOWS: POWER

PHASE CONDUCTORS, (R, Y, B): RED, YELLOW AND BLUE RESPECTIVELY DUPLEX POWER OUTLET
NEUTRAL, (N) : WHITE
SINGLE POWER OUTLET
GROUND, (G) : GREEN
DUPLEX RJ45 DATA OUTLET
11. UNLESS OTHERWISE SPECIFIED MOUNTING HEIGHTS SHALL BE MEASURED FROM LINE OF REFERENCE TO CENTER
OF DEVICE AS FOLLOWS: DUPLEX TELEPHONE OUTLET

11.1 DUPLEX RECEPTACLES : 300mm AFFL THREE PHASE ISOLATOR (RATING AS INDICATED)
11.2 COUNTER RECEPTACLE : 200mm ACT
11.3 LIGHTING SWITCHES : 1400mm AFFL SINGLE PHASE ISOLATOR (RATING AS INDICATED)
11.4 DISCONNECT SWITCHES : 1400mm AFFL OR AFG
J JUNCTION BOX
11.5 FIRE ALARM BELL WITH PULL STATION : 1400mm FFL
11.6 WALL MOUNTED OUTLET : 300mm AFFL POWER CIRCUIT
11.7 WALL MOUNTED TELEPHONE OUTLET : 300mm AFFL
11.8 EMERGENCY LIGHT :2200mm AFFL
FAN COIL UNIT
12. MOUNTING HEIGHTS FOR ALL WALL MTD PANELS SHALL BE AS FOLLOWS: FCU XXX

12.1 LIGHTING AND POWER PANELS : 1800mm AFFL TO TOP OF PANEL


12.2 CONTROL PANELS : 1800mm AFFL TO TOP OF PANEL AUXILIARY
13. NON-CURRENT CARRYING METALLIC PARTS OF THE ELECTRICAL SYSTEM SHALL BE PROVIDED WITH GROUNDING EXIT SIGN
WIRES SUITABLY SIZED AS REQUIRED BY THE PEC. ALL WIRETRAYS AND CONDUITS SHALL BE BONDED TOGETHER
AND PROPERLY CONNECTED TO THE GROUNDING TERMINAL.
EMERGENCY LIGHT COMPLETE WITH
EL SINGLE POWER OUTLET
14. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL CONDUITS, WIRES AND PULL LINES AS SPECIFIED AND AS
NECESSARY TO COMPLETE THE WORK.
M MANUAL PULL STATION
15. ALL LIGHTING FIXTURES SHALL BE INSTALLED COMPLETE WITH ALL FITTINGS, DIFFUSER AND LAMPS.
FIRE ALARM BELL
16. ALL MOTORS SHALL BE PROVIDED WITH MAGNETIC CONTACTOR AND OVERLOAD RELAY.
S SMOKE DETECTOR

HD HEAT DETECTOR
CONNECTION.

18. MINIMUM SHORT CIRCUIT CURRENT SHALL BE 10KAIC FOR LIGHTING LOAD AND 22KAIC FOR MAIN AND MOTOR LOAD. FACP FIRE ALARM CONTROL PANEL

19. THE COMPLETE ELECTRICAL INSTALLATIONS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED SITE
ELECTRICAL ENGINEER.

140W LED FLOODLIGHT, PURE WHITE, IP65 WITH ANGLE OF ILLUMINATION OF 120 DEGREES
TO BE INSTALLED WITH MOTION SENSOR AND PHOTOCELL MOUNTED ON 12 METER HOT-DIP
GALVANIZED TAPERED POLE

AREA LIGHTING RETICULATION. SEE LOAD SCHEDULE FOR WIRES AND CONDUIT TO USE.

ELECTRICAL HANDHOLE
NON-VEHICULAR TYPE 600X600mm

LIGHTING CONTROL PANEL

CIRCUIT HOMERUN