DACT available only on the FNP-XXXXD Refer to section A.

3 in the FireNET Plus


To Telephone Installation Manual for Compatible Devices Class A Style 6 or 7 - For SLC Devices (Smoke / Heat Sensors and Modules) NOTE: SLC LOOPS 1 -& 2 ARE SUPERVISED SLC INITIATING DEVICES
Maximum Wire Length for SLC Loop out
Wire Guage
Line NOTE: Style 7 - Refer to Section 5.16.1 in Manual & return (Class A and B)
18 AWG 1,950 Feet
(Supervised) Class B Style Y - For Indicating Devices NOTE: SLC Max Impedance is 50 Ohm, 1uF, 1mH 16 AWG 3,100 Feet
- - -
Hochiki America 14 AWG 5,000 Feet
EOL Device
(Supervised) (EOLD)
NOTE: See FireNET PLUS Installation Manual as
P/N 0400-01023
+ + + Class B Style 4 - For SLC Devices (Smoke / Heat Sensors and Modules) noted below for SLC branch circuit cable requirments
or 0400-01046
Total wire must not exceed 5,000 feet from the
NOTE: FireNET Plus employs an option for Sounder Time- control panel when using #14 AWG
Out (for NAC/SOM/ASB), which can be programmed in 5
min. increments between 5-60 min. Option is disabled by RS485 OUT TO
setting the value to 0 (default condition). NEXT NODE
(Supervised)
Refer to A.4 for RS485 IN FROM
Compatible Devices PREVIOUS NODE ZERO OHM SHORTING
(Regulated) JUMPERS MUST BE USED
(Supervised)
Conventional Relay Contacts rated FOR CLASS B OPERATION
for 1A @ 30VDC. P/N S2026
AUX 24VDC POWER Must be connected to power
RJ31X Jack # 1 TO ACCESSORIES,
360 mA max. each
limited source.
(Not supervised) (Resistive)
RS485 TO
ACCESSORIES
Use only UL Listed RJ31X (Supervised) (Supervised)
Jacks and Cords
Expander board required for SLC Loop 2,
AGENCY LISTINGS AND HA part # FNP-1127-SLC

REQUIREMENTS
UL and NFPA Information
Install in accordance with NFPA 70, 72 and 13. + - + - + - + - + - + - NC C NO NC C NO NC C NO + - + - + - + - + - TERMINAL STRIP ELECTRICAL RATINGS FOR MAIN CONTROL UNIT

P2T
L1T

P1R

L2T

P2R
L1R

P1T

L2R
E E
24V OUT AUX 24V NAC1 NAC2 SLC1 IN SLC1 OUT TROUBLE FIRE SUPERVISORY NET OUT NET IN COMMS SLC2 OUT SLC2 IN
The FireNET Plus is suitable as follows: Terminal Rating
- Commercial Protected- Premises Control Unit for Description
Label Voltage Current
Local signaling. Install Indoors only in a dry
environment. E 0VDC -
Ground Ground Terminals
- Types of signaling services are automatic, manual, E 0VDC -
waterflow, & sprinkler supervisory.
L1T Incoming telephone line from RJ31X 48VDC 30mA
- Style 4, 6, or 7 for Signaling Line Circuits
- Style Y for Notification Appliance Circuits
Fire More Events
L1R
Telco Line 1 jack (FNP-1127D only) 48VDC 30mA
- Non-coded signaling General P1T Premise telephone connection (FNP- 48VDC 30mA
- Central Station Service (DACT) AC Power on Phone 1
Disablement P1R 1127D only) 48VDC 30mA
- Remote Station Service (DACT)
- Auxiliary Service (Local Energy) L2T Incoming telephone line from RJ31X 48VDC 30mA
Pre-Alarm General Trouble Telco Line 2
-UL Releasing Function for Pre-Action with use or L2R jack (FNP-1127D only) 48VDC 30mA
SOM-R Module
P2T Premise telephone connection (FNP- 48VDC 30mA
Phone 2
F.C.C. Information On Test Power Trouble P2R 1127D only) 48VDC 30mA
The FireNET Plus has been verified to comply with 24V OUT + 24VDC 360mA
FCC Rules Part 15, Class A Operation is subject to Panel Sounder Aux Power 24 VDC auxiliary power
the following conditions: Supervisory 24V OUT - 24VDC 360mA
Silenced
1. This device may not cause radio interference.
Exit Enter AUX 24V +
Aux Power 24 VDC auxiliary power
24VDC 360mA
2. This device must accept any interference AUX 24V - 24VDC 360mA
Delay Active NAC Trouble
received, including any that may cause
undesired operation. NAC1 + Notification Appliance Circuits #1 & 2. 24VDC 2.3 A
F.C.C. registration number: US:KNTAL00BASA-FACP NAC1 - NAC Circuits (EOLD PN# 0400-1023 required) 24VDC 2.3 A
NAC2 + 1&2 24VDC Regulated @ 1.6A Continuous 24VDC 2.3 A
More More 24VDC @ 2.3A Special Application
Re-Sound Alarm Panel Sounder Lamp Reset Fire Drill Programmable Enable Access NAC2 - 24VDC 2.3 A
Alarm Silence Silence Test Function Fire Events Events SLC1 IN + Signaling Line Circuit “In” terminals 32VDC 250mA
SLC1 IN - used for return loop for Class A wiring. 32VDC 250mA
SLC Loop 1
SLC1 OUT + Signaling Line Circuit “Out” terminals 32VDC 250mA
SLC1 OUT - used for Class A or Class B wiring. 32VDC 250mA
RS232 Data port / PC Port
NC 30VDC 1A
Trouble
C Form “C” relay contacts 30VDC 1A
May be connected to a Remote Relay
NO 30VDC 1A
Annunciator with EMS Graphix and used NC 30VDC 1A
as a Supplementary remote annunciator. C Fire Relay Form “C” relay contacts
PC/Dialer Reset Watchdog Watchdog Contrast 30VDC 1A
The connection between PC port and NO 30VDC 1A
Computer must be within 20 ft. in the same Operated Reset
NC 30VDC 1A
room and in conduit. PC / Dialer switch Supervisory
C Form “C” relay contacts 30VDC 1A
must always be in PC Position. Relay
NO 30VDC 1A
NET OUT + 12VDC 100mA
WARNING NET OUT -
Network Out RS485 network to other panels
12VDC 100mA
NET IN + 12VDC 100mA
THIS UNIT INCLUDES AN Network In RS485 network from other panels
NET IN - 12VDC 100mA
OPTIONAL ALARM COMMS + 12VDC 100mA
Battery COMMS Bus RS485 to expansion boards
VERIFICATION FEATURE COMMS - 12VDC 100mA
Connection AC POWER
that will result in a delay of + - L N E SLC2 OUT + Signaling Line Circuit “Out” terminals 32VDC 250mA
the system alarm signal from SLC2 OUT - SLC Loop 2 used for Class A or Class B wiring. 32VDC 250mA
F7 – 3A, 250VAC, slow SLC2 IN + (optional) 32VDC 250mA
the indicated circuits. The blow, 5 x 20mm fuse
Signaling Line Circuit “In” terminals
SLC2 IN - used for return loop for Class A wiring. 32VDC 250mA
total delay time (control plus 10 Amp in-line Fuse (supervised) (on rear of control board)
Bussman AGC-10 or equiv.
smoke detectors) shall not Battery cables and
EARTH
jumpers are supplied
exceed 60 seconds. No other
with the panel
GROUND All circuits are inherently Power
smoke detector shall be AC 120VAC INPUT
EARTH GROUND STUD
NEUTRAL 20 AMP Breaker
Limited except AC/Battery inputs and
connected to these circuits (Supervised)
telephone lines.
Max
unless approved by the local HOT
(supervised)
POSITIVE NEGATIVE
Authority Having Jurisdiction. (+) (-)
All Supervised Circuits are identified.
*Zone(s)________________ 12 VOLT Sealed Rechargeable 12 VOLT Sealed Rechargeable
*where alarm verification is used Battery Battery TERMINAL STRIP ELECTRICAL RATINGS FOR THE POWER SUPPLY
60 AH Maximum 60 AH Maximum
Rating
Programmed Delay is 60 Connector Terminal Description Voltage Current
HOCHIKI AMERICA CORPORATION
seconds by default. The TB6 G Earth Ground N/A N/A

delay is programmable from BATTERIES SHOULD BE INSPECTED ANNUALLY & REPLACED EVERY 3-5 YEARS N AC Neutral 120VAC, 50/60Hz 2.1A This Product shall be installed in
5 – 60 seconds.
(DO NOT PARALLEL BATTERIES) 240VAC, 50/60Hz 1.1A accordance with the FireNET PLUS
USE ONLY UL RECOGNIZED SEALED LEAD ACID BATTERIES
L AC Line 120VAC, 50/60Hz 2.1A Installation Manual, PN # 1700-10840
240VAC, 50/60Hz 1.1A

FireNET PLUS WIRING DIAGRAM TB3 + Battery


- Battery
+24VDC

DC Common
5A Max

5A Max
Version # 1.05 Issued: 10/31/2013