Sie sind auf Seite 1von 119

SK1230+1157_GB 21.05.

2007 14:22 Uhr Seite 1

Product Range Catalogue | 2007

LZM1-4 circuit-breaker series up to 1600 A


Switching and protection –
Moeller adresses worldwide: the new LZM1-4 circuit-breaker series
www.moeller.net/address
up to 1600 A
E-Mail: info@moeller.net
Internet: www.moeller.net

Issued by Moeller GmbH


Hein-Moeller-Str. 7-11 Reliable and safely controlling,
D-53115 Bonn switching and managing
power. In industry, in buildings
© 2007 by Moeller GmbH and in machine construction.
Subject to alterations Innovative protection concepts.
SK1230-1176GB MDS/Insight 05/07 With built-in diagnostics and
communication functions.
Housed in modern switch-
board systems.

LZM circuit-breaker
IZM circuit-breaker
Switchboard
systems

Xtra Combinations

Xtra Combinations from Moeller offers a range of products


and services, enabling the best possible combination options
for switching, protection and control in power distribution
and automation.

Using Xtra Combinations enables you to find more efficient


solutions for your tasks while optimising the economic
viability of your machines and systems.

It provides:
■ Flexibility and simplicity
■ Great system availability
■ The highest level of safety

All the products can be easily combined with one another


mechanically, electrically and digitally, enabling you to arrive
at flexible and stylish solutions tailored to your application –
quickly, efficiently and cost-effectively.
The products are proven and of such excellent quality that
they ensure a high level of operational continuity, allowing
you to achieve optimum safety for your personnel, machinery,
installations and buildings.

Thanks to our state-of-the-art logistics operation, our com-


prehensive dealer network and our highly motivated service
personnel in 80 countries around the world, you can count
on Moeller and our products every time. Challenge us!
We are looking forward to it!
http://catalog.moeller.net Contents 1
Moeller SK1230-1176GB

Circuit-breakers LZM1, 2, 3, 4
Circuit-breakers, switch-disconnectors
up to 1600 A

Circuit-breakers LZM1, 2, 3, 4
from 15 to 1600 A

up to 1600 A
Page Page Page

System overview Rotary handles with door interlock 57 Technical data


Reliably and safely controlling, switching Main switch assembly kit 58
Circuit-breakers 88
Circuit-breakers 2
and managing power, in industry, in buildings Accessories 60
Temperature influence 92
and in machine construction. Enabled by Technical overview 4 Mechanical interlock 62
Effective power loss 94
innovative protection concepts. Ordering Multi-function device adapter 63
Terminal capacities 96
Accessories 64
Circuit-breaker thermo-magnetic 6 Auxiliary contact 98
release, 3-pole Insulated enclosures 66
Equipping with auxiliary contacts, time 99
Circuit-breaker, magnetic short-circuit 8 Residual-current release frequency 68 differences
releases, 3 pole response
Undervoltage release, shunt release, 100
Circuit-breaker, electronic releases, 10 Engineering
Remote operator, capacitor unit 101
3 pole
Selectivity: incoming circuit-breaker, 70 Residual current relay 102
Circuit-breaker thermo-magnetic 12 outgoing circuit-breaker
release, 4-pole Residual current release 104
MCB, backup protection 74
Circuit-breakers, electronic releases, 16 Dimensions
4 pole Direction of blow-out, minimum 75
clearances, tube cable lugs Size 1: basic units 106
Circuit-breaker series LZM1 to LZM4 Connection types 20
Auxiliary switches, 76 Size 1: accessories 107
- just 4 compact frame sizes Plug-in units 40 trip-indicating auxiliary contacts
- available as 3 and 4-pole device Size 2: basic units 115
Withdrawable units 41 Mechanical interlock 77
- now also up to 1600 A
- flexible mounting using modular function groups Auxiliary contact with screw terminals 42 for (door-coupling) rotary handle Size 2: accessories 116
- full rated current at 50 °C ambient temperature Undervoltage release with screw 44 Mechanical interlock for remote 78 Size 3: basic units 127
Standard/trip-indicating auxiliary contact from - switch suitable for world-wide use terminals operator, residual-current relay
Size 3: accessories 128
the Titan range Page 6 Undervoltage release, off-delayed 49 Sizes 1, 2: tripping characteristics 79
Size 4: basic units 137
- reduced number of variants and stockholding requirement Sizes 2, 3: tripping characteristics 80
Shunt release with screw terminals 50 Size 4: accessories 138
- simple front installation at the same position
- simple clip-on feature saves mounting costs Door coupling rotary handles Door coupling rotary handles 54 Sizes 3, 4: tripping characteristics 81
- attractively priced identical parts from the control circuit - identical drilling template for all Rotary handles 56 Frame size 1: let-through characteristics 82
device range variants Frame size 2: let-through characteristics 83
Page 42 - innovative automatic centring
- axis support for long-term reliable Sizes 1, 3: let-through characteristics 84
operation Sizes 2, 3: let-through characteristics 85
- side-wall operation ensuring space-
saving main switch installation Frame size 2: residual-current release 86
frequency response
Page 54

Remote operators
- common functional concept of all
variants
- low closing delays 60 ms
to 100 ms
- locking and sealing features provide
security
Page 64
2 System overview
Circuit-breakers
LZM Moeller SK1230-1176GB http://catalog.moeller.net

5
7

4 6
8
Circuit-breakers

25 9
10

3
2

24

11

13 12

14

23

19
20 16
15
21
17

18
System overview 3
Circuit-breakers
http://catalog.moeller.net Moeller SK1230-1176GB LZM
Basic units Add-on functions Mounting accessories

Circuit-breaker 1 Standard auxiliary contact (HIN) 13 Control circuit terminal 8


Rated uninterrupted current up to 1600 A Switching with the main contacts. Used for For two terminals at top or bottom
Switching capacity 25, 36, 50, 70 kA at 415 V indication and interlock functions. LZM1 a page 23
Adjustable releases for overload and short- a page 42 LZM2 a page 27
circuit LZM3 a page 31
Trip-indicating auxiliary contact (HIA) 13
Adjustable time selectivity

Circuit-breakers
General trip indication '+', when tripped by LZM4 a page 39
Earth-fault protection voltage release, overload release or short-
Protection of systems, cables, motors, Tunnel terminals for Al and Cu cable 6
circuit release
generators Standard with control circuit terminal
a page 42
3 and 4 pole versions,IEC/EN 60947, CCC LZM1 a page 21
a page 6 Early-make auxiliary contacts 24 LZM2 a page 25
For interlocking and load shedding circuits, as LZM3 a page 31
well as for early make of the undervoltage LZM4 a page 37
release in main switch/Emergency-stop
applications Box terminals 7
a page 42 Standard version of frame size 1 assembled
within the circuit-breaker enclosure
Voltage release 24
LZM1 a page 21
Undervoltage release
Non-delayed LZM2 a page 25
OFF-delayed LZM3 a page 29
Shunt release
Terminal cover 4
a page 44
Protection against direct contact where cable
lugs, busbars or tunnel terminals are used
Delay unit for undervoltage release 25
LZM1 a page 23
a page 49
LZM2 a page 27
Rear drive 14 LZM3 a page 32
a page 60 LZM4 a page 39

Door coupling rotary handle 16, Terminal cover, knockout 3


Lockable 18 LZM1 a page 23
With door interlock LZM2 a page 27
a page 54 LZM3 a page 32
LZM4 a page 39
Main switch rotary handle for side panel 15
mounting Clip plate 10
a page 58 NZM1-XC35 for 35 mm top-hat rail
Extension shaft 17 NZM2-XC75 for 75 mm top-hat rail
Can be cut to required length. a page 61
a page 54 Rear connection 11
LZM1 a page 21
Rotary handle 19
LZM2 a page 25
Lockable
LZM3 a page 31
a page 56
LZM4 a page 37
Remote operator 22
Plug-in and withdrawable unit 9
For remote switching of circuit-breakers and
switch-disconnectors a page 40
a page 64 Insulating surround 21
For use with toggle lever, rotary drive and
Toggle lever interlock device 23
remote operator protruding from the enclosure
a page 61
a page 61
External warning plate/designation label 20
a page 60
Spacer 12
a page 61
IP2X protection 2
against contact with a finger
For box terminals
LZM1 a page 23
LZM2 a page 27
LZM3 a page 32
IP2X protection 5
against contact with a finger
For barrier
LZM1 a page 23
LZM2 a page 27
LZM3 a page 32
4 Technical overview Technical overview 5
Circuit-breaker, 3/4-pole Circuit-breaker, 3/4-pole
LZM1, LZM2, LZM3, LZM4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM1, LZM2, LZM3, LZM4
Circuit-breaker
With main switch characteristics to IEC/EN 60204 and isolating
characteristics to IEC/EN 60947, CCC
Circuit-breakers

Circuit-breakers
Rated uninterrupted current Iu = Rated current In Thermomagnetic releases Magnetic short-circuit release Electronic releases
Adjustable overload release Ir System and cable protection Motor protection Systems, cable, selectivity and generator
Adjustable short-circuit release Ii protection
Delayed short-circuit release Isd
Iu Iu Ir Ii Iu Iu Iu Ii Iu Iu Ir Isd Ii
A A A A A A A A A A A A A

Ambient temperature at 100% Iu 20 20 0.8 – 1 x In 350 0.4 – 1 x In 2 – 10 x Ir 2 – 12 x In


min./max. -25 / +50 °C 25 25 400 800
32 32 630 1000
40 40 8 – 10 x In 40 8 – 14 x In 1250
50 50 6 – 10 x In 50 1600
63 63 63 2 – 6 x Ir 2 – 8 x Ir
80 80 80
100 100 100

125 125 250 125 250


160 160 320 LZM1: 8xIn 160 320
6 – 10 x In
200 400 200 400
250 500 500
300
Basic switching capacity LZMB1-A... LZMB2-A... LZMB1-S... LZMB2-S...
400/415 V kA/cos v 25 0.25 25 0.25 25 0.25 25 0.25
440 V kA/cos v 25 0.25 25 0.25 25 0.25 25 0.25
Comfort switching capacity LZMC1-A... LZMC2-A... LZMC3-A... LZMC1-S... LZMC2-S... LZMC3-S...
400/415 V kA/cos v 36 0.25 36 0.25 36 0.25 36 0.25 36 0.25 36 0.25
440 V kA/cos v 30 0.25 30 0.25 30 0.25 30 0.25 30 0.25 30 0.25
525 V kA/cos v 12 0.5 12 0.5 12 0.5 12 0.50 12 0.25 12 0.25
690 V kA/cos v 8 0.5 8 0.5 8 0.5 8 0.50 8 0.50 8 0.50
Normal switching capacity LZMN1-A... LZMN2-A... LZMN3-A... LZMN1-S... LZMN2-S... LZMN3-S... LZMN3-...E... LZMN4-...E...
400/415 V kA/cos v 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25
440 V kA/cos v 35 0.25 35 0.25 35 0.25 35 0.25 35 0.25 35 0.25 35 0.25 35 0.25
525 V kA/cos v 20 0.30 25 0.25 25 0.25 20 0.30 25 0.25 25 0.25 25 0.25 25 0.25
690 V kA/cos v 10 0.50 20 0.30 20 0.30 10 0.50 20 0.30 20 0.30 20 0.30 20 0.30
Strong switching capacity LZMS1-A-... LZMS2-A-... LZMS3-A-... LZMS1-S-... LZMS2-S... LZMS3-S... LZMS3-...E... LZMS4-...E...
400/415 V kA/cos v 70 0.20 70 0.20 70 0.20 70 0.20 70 0.20 70 0.20 70 0.20 70 0.20
440 V kA/cos v 35 0.25 65 0.20 65 0.20 35 0.25 65 0.20 65 0.20 65 0.20 65 0.20
525 V kA/cos v 20 0.30 36 0.25 36 0.25 20 0.30 36 0.25 36 0.25 36 0.25 36 0.25
690 V kA/cos v 10 0.50 20 0.30 25 0.30 10 0.50 20 0.30 25 0.30 25 0.30 35 0.25

Notes The stated switching capacity values are rated ultimate short-circuit breaking capacities (Icu)
6 Ordering Ordering 7
Circuit-breaker, thermo-magnetic release, 3 pole Circuit-breaker, thermo-magnetic release, 3 pole
LZM...1, LZM...2, LZM...3 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM....1, LZM...2,LZM...3
Basic switching capacity 25 kA Comfort switching capacity 36 kA Normal switching capacity 50 kA Strong switching capacity 70 kA
at 415 V 50/60 Hz at 415 V 50/60 Hz at 415 V 50/60 Hz at 415 V 50/60 Hz
Rated current = Setting range Part no. Price Part no. Price Part no. Price Part no. Price Std. pack Notes
rated uninterrupted Article no. see price Article no. see price Article no. see price list Article no. see price list
current list list
In = Iu Overload releases Short-circuit releases

A Ir Ii
Circuit-breakers

Circuit-breakers
A A
I

Protection of systems and cables


3 pole
Terminals standard, terminal screws as accessories
20 15…20 350 LZMB1-A20 LZMC1-A20 LZMN1-A20 LZMS1-A20 1 off IEC/EN 60947-2
109232 109432 109442 109452 Adjustable overload releases Ir
25 20…25 350 LZMB1-A25 LZMC1-A25 LZMN1-A25 LZMS1-A25 • 0.8 – 1 x In (ex-works 0.8 x In)
109233 109433 109443 109453 Adjustable short-circuit releases Ii
• 6 – 10 x In (ex-works 6 x In)
32 25…32 350 LZMB1-A32 LZMC1-A32 LZMN1-A32 LZMS1-A32 – LZM...-A40: 8 – 10 x In (ex-works 8 x In)
109234 109434 109444 109454 Fixed short-circuit release Ii
40 32…40 320…400 LZMB1-A40 LZMC1-A40 LZMN1-A40 LZMS1-A40 • 350 A at In = 20 – 32 A
109235 109435 109445 109455 • 1280 A at In = 160 A (LZM1)
50 40…50 300…500 LZMB1-A50 LZMC1-A50 LZMN1-A50 LZMS1-A50
109236 109436 109446 109456
63 50…63 380…630 LZMB1-A63 LZMC1-A63 LZMN1-A63 LZMS1-A63
109237 109437 109447 109457
80 63…80 480…800 LZMB1-A80 LZMC1-A80 LZMN1-A80 LZMS1-A80
109238 109438 109448 109458
100 80…100 600…1000 LZMB1-A100 LZMC1-A100 LZMN1-A100 LZMS1-A100
109239 109439 109449 109459
125 100…125 750…1250 LZMB1-A125 LZMC1-A125 LZMN1-A125 LZMS1-A125
109430 109440 109450 109460
160 125…160 1280 LZMB1-A160 LZMC1-A160 LZMN1-A160 LZMS1-A160
109431 109441 109451 109461
Terminal screws standard, terminals as accessories
20 15…20 350 LZMS2-A20 1 off
109534
25 20…25 350 LZMS2-A25
109535
32 25…32 350 LZMS2-A32
109536
40 32…40 320…400 LZMS2-A40
109537
50 40…50 300…500 LZMS2-A50
109538
63 50…63 380…630 LZMS2-A63
109539
80 63…80 480…800 LZMS2-A80
109540
100 80…100 600…1000 LZMS2-A100
109541
125 100…125 750…1250 LZMS2-A125
109542
160 125…160 960…1600 LZMB2-A160 LZMC2-A160 LZMN2-A160 LZMS2-A160
109522 109526 109530 109543
200 160…200 1200…2000 LZMB2-A200 LZMC2-A200 LZMN2-A200 LZMS2-A200
109523 109527 109531 109544
250 200…250 1500…2500 LZMB2-A250 LZMC2-A250 LZMN2-A250 LZMS2-A250
109524 109528 109532 109545
300 240…300 1500…2500 LZMB2-A300 LZMC2-A300 LZMN2-A300 LZMS2-A300
109525 109529 109533 109546
250 200…250 1500…2500 LZMC3-A250 LZMN3-A250 LZMS3-A250
109597 109601 109605
320 250…320 1920…3200 LZMC3-A320 LZMN3-A320 LZMS3-A320
109598 109602 109606
400 320…400 2400…4000 LZMC3-A400 LZMN3-A400 LZMS3-A400
109599 109603 109607
500 400…500 3000…5000 LZMC3-A500 LZMN3-A500 LZMS3-A500
109600 109604 109608

Notes Notes for terminals a 21


8 Ordering Ordering 9
Circuit-breaker, magnetic short-circuit releases, 3 pole Circuit-breaker, magnetic short-circuit releases, 3 pole
LZM...1, LZM...2, LZM...3 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM...1, LZM...2, LZM...3
Basic switching capacity Comfort switching capacity Normal switching capacity Strong switching capacity
25 kA at 415 V 50/60 Hz 36 kA at 415 V 50/60 Hz 50 kA at 415 V 50/60 Hz 70 kA at 415 V 50/60 Hz
Rated current = rated Setting range Motor rating Rated Part no. Price Part no. Price Part no. Price Part no. Price Std. pack Notes
uninterrupted current Short-circuit AC-3 at 400 V operational Article no. Article no. Article no. Article no.
releases 50/60 Hz current AC-3 see price see price see price see price
at 400 V list list list list
50/60 Hz
In = Iu Ii P Ie
Circuit-breakers

Circuit-breakers
A A kW A
I

Short-circuit protection
Motor protection in conjunction with overload relay
• With short-circuit release
• Without overload release
3 pole
Terminals standard, terminal screws as accessories
40 320…560 18.5 36 LZMB1-S40 LZMC1-S40 LZMN1-S40 LZMS1-S40 1 off IEC/EN 60947-4-1 and IEC/EN 60947-2
109462 109467 109472 109477 The circuit-breaker fulfills all requirements for AC-3 switching category.
50 400…700 22 41 LZMB1-S50 LZMC1-S50 LZMN1-S50 LZMS1-S50 Adjustable short-circuit releases Ii
109463 109468 109473 109478 • 8 – 14 x In (ex-works 12 x In)
– LZM...1-S100, LZM...2-S200: 8 – 12.5 x In (ex-works 12 x In)
63 504…882 30 55 LZMB1-S63 LZMC1-S63 LZMN1-S63 LZMS1-S63 Without overload release Ir
109464 109469 109474 109479 – LZM...3-S400: 7 – 12.5 x In
80 640…1120 37 68 LZMB1-S80 LZMC1-S80 LZMN1-S80 LZMS1-S80 – LZM...3-S500: 6 – 10 x In
109465 109470 109475 109480
Selection
100 800…1250 55 99 LZMB1-S100 LZMC1-S100 LZMN1-S100 LZMS1-S100
109466 109471 109476 109481 of circuit-breakers without overload release when combining with ZEV electronic mo-
tor-protective relay:
Terminal screws standard, terminals as accessories
The tripping response of the ZEV motor-protective relay is matched by setting of the
40 320…560 18.5 36 LZMS2-S40 1 off tripping class (CLASS), to the starting behaviour of the motor to be protected.
109556
50 400…700 22 41 LZMS2-S50
In in A Maximum permissible tripping class CLASS
109557
LZM...1-S... 40 30
63 504…882 30 55 LZMS2-S63
109558 50 30
80 640…1120 37 68 LZMS2-S80 63 30
109559 80 20
100 800…1400 55 99 LZMS2-S100 100 15
109560
LZM...2-S... 40 30
125 1000…1750 55 99 LZMB2-S125 LZMC2-S125 LZMN2-S125 LZMS2-S125
109547 109550 109553 109561 50 30
160 1280…2240 75 134 LZMB2-S160 LZMC2-S160 LZMN2-S160 LZMS2-S160 63 30
109548 109551 109554 109562 80 30
200 1600…2500 110 196 LZMB2-S200 LZMC2-S200 LZMN2-S200 LZMS2-S200 100 30
109549 109552 109555 109563 125 30
250 2000…3500 250 LZMC3-S250 LZMN3-S250 LZMS3-S250 160 20
109609 109613 109617
200 10
320 2560…4480 320 LZMC3-S320 LZMN3-S320 LZMS3-S320
109610 109614 109618 LZM...3-S... 250 30
400 2800…5000 400 LZMC3-S400 LZMN3-S400 LZMS3-S400 320 30
109611 109615 109619 400 30
500 3000…5000 450 LZMC3-S500 LZMN3-S500 LZMS3-S500 500 20
109612 109616 109620

Tripping class Tripping time Tp with load on all poles of 7.2 times
current setting value
10 A 2 s < Tp F 10 s
10 4 s < Tp F 10 s
20 6 s < Tp F 20 s
30 9 s < Tp F 30 s

Motor-starter combination of classification types 1 and 2 can be found in the “Fuseless


motor-starter combinations” section of the Main Catalogue.

Notes Notes for terminals a 21


10 Ordering Ordering 11
Electronic releases, 3 pole Electronic releases, 3 pole
LZM...3, LZM...4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM...3, LZM...4
Normal switching capacity 50 kA Strong switching capacity 70 kA
at 415 V 50/60 Hz at 415 V 50/60 Hz
Rated current = rated Setting range Part no. Price Part no. Price Std. pack Notes
uninterrupted current Article no. see price list Article no. see price list
Overload Short-circuit releases
releases
Non-delayed Delayed short-
circuit release
Circuit-breakers

Circuit-breakers
In = Iu Ir Ii Isd
A A A A
I I

Protection of systems and cables


3 pole
Terminal screws standard, terminals as accessories
400 200…400 800…4400 LZMN3-AE400 LZMS3-AE400 1 off IEC/EN 60947-2
109639 109641
630 315…630 1260…5040 LZMN3-AE630 LZMS3-AE630 Adjustable overload releases Ir
109640 109642 • 0.5 – 1 x In (ex-works 0.8 x In)

R.m.s. value measurement and “thermal memory”

800 400…800 1600…9600 LZMN4-AE800 LZMS4-AE800 Adjustable short-circuit releases Ii


110942 110946 • LZM...3-AE400: 2 – 11 x In (ex-works 6 x In)
• LZM...3-AE630: 2 – 8 x In (ex-works 6 x In)
1000 500…1000 2000…12000 LZMN4-AE1000 LZMS4-AE1000 • LZM...4-AE...: 2 – 12 x In (ex-works 6 x In)
110943 110947
1250 630…1250 2500…15000 LZMN4-AE1250 LZMS4-AE1250
110944 110948
1600 800…1600 3200…19200 LZMN4-AE1600 LZMS4-AE1600
110945 110949

Systems and cable protection, selectivity and generator protection


3 pole
Terminal screws standard, terminals as accessories
400 200…400 800…4400 400…4000 LZMN3-VE400 LZMS3-VE400 1 off IEC/EN 60947-2
109651 109653
630 315…630 1260…5040 472…4410 LZMN3-VE630 LZMS3-VE630 Adjustable overload releases Ir
109652 109654 • 0.5 – 1 x In (ex-works 0.8 x In)

R.m.s. value measurement and “thermal memory”

Adjustable time delay setting to overcome current peaks tr


800 400…800 1600…9600 800…8000 LZMN4-VE800 LZMS4-VE800 • 2 … 20 s with 6 x Ir as well as infinity (without overload release) (ex-factory 10 s)
110960 110964
1000 500…1000 2000…12000 1000…10000 LZMN4-VE1000 LZMS4-VE1000 Adjustable delayed short-circuit releases Isd
110961 110965 • 2 – 10 x Ir (ex-works 6 x Ir)
1250 630…1250 2500…15000 1250…12500 LZMN4-VE1250 LZMS4-VE1250 – LZM…3-VE630: 1.5 – 7 x Ir (ex-works 6 x Ir)
110962 110966
Adjustable delay time tsd
1600 800…1600 3200…19200 1600…16000 LZMN4-VE1600 LZMS4-VE1600 • Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-works 0 ms)
110963 110967
Adjustable non-delayed short-circuit releases Ii
• LZM…3-VE400: 2 – 11 x In (ex-works 6 x In)
• LZM…3-VE630: 2 – 8 x In (ex-works 6 x In)
• LZM…4-VE…: 2 – 12 x In (ex-works 12 x In)
i2t constant function
• LZM3, LZM4 switched (ex-works OFF)

Notes Notes for terminals a 29


12 Ordering Ordering 13
Thermomagnetic release, 4 pole Thermomagnetic release, 4 pole
LZM...1 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM...1
Basic switching capacity 25 kA at Comfort switching capacity Normal switching capacity 50 kA Strong switching capacity 70 kA
415 V 50/60 Hz 36 kA at 415 V 50/60 Hz at 415 V 50/60 Hz at 415 V 50/60 Hz
Rated current = rated Setting range Part no. Price Part no. Price Part no. Price Part no. Price Std. pack Notes
uninterrupted current Article no. see price list Article no. see price list Article no. see price list Article no. see price list
In = Iu Overload releases Short-circuit
releases

A Main pole Neutral


Circuit-breakers

Circuit-breakers
conductor
Ir Ir Ii

A A A
I

Protection of systems and cables


4 pole
Terminals standard, terminal screws as accessories
20 15…20 15…20 350 LZMB1-4-A20 LZMC1-4-A20 LZMN1-4-A20 LZMS1-4-A20 1 off IEC/EN 60947-2
109482 109492 109502 109512
25 20…25 20…25 350 LZMB1-4-A25 LZMC1-4-A25 LZMN1-4-A25 LZMS1-4-A25 Adjustable overload releases Ir
109483 109493 109503 109513 • 0.8 – 1 x In (ex-works 0.8 x In)
32 25…32 25…32 350 LZMB1-4-A32 LZMC1-4-A32 LZMN1-4-A32 LZMS1-4-A32 Setting on neutral pole implemented via the main pole setting Ir of the main pole.
109484 109494 109504 109514
40 32…40 32…40 320…400 LZMB1-4-A40 LZMC1-4-A40 LZMN1-4-A40 LZMS1-4-A40 Adjustable short-circuit releases Ii
109485 109495 109505 109515 • 6 – 10 x In (ex-works 6 x In)
– LZM…1-4-A40: 8 – 10 x In (ex-works 8 x In)
50 40…50 40…50 300…500 LZMB1-4-A50 LZMC1-4-A50 LZMN1-4-A50 LZMS1-4-A50
109486 109496 109506 109516
Fixed short-circuit release Ii
63 50…63 50…63 380…630 LZMB1-4-A63 LZMC1-4-A63 LZMN1-4-A63 LZMS1-4-A63 • 350 A at In = 20 – 32 A
109487 109497 109507 109517 • 1280 A at In = 160 A (8 x In)
80 63…80 63…80 480…800 LZMB1-4-A80 LZMC1-4-A80 LZMN1-4-A80 LZMS1-4-A80
109488 109498 109508 109518 LZM..1-4-A…
• With 100 % overload and short-circuit protection in 4th pole
100 80…100 80…100 600…1000 LZMB1-4-A100 LZMC1-4-A100 LZMN1-4-A100 LZMS1-4-A100
109489 109499 109509 109519
125 100…125 100…125 750…1250 LZMB1-4-A125 LZMC1-4-A125 LZMN1-4-A125 LZMS1-4-A125
109490 109500 109510 109520
160 125…160 125…160 1280 LZMB1-4-A160 LZMC1-4-A160 LZMN1-4-A160 LZMS1-4-A160
109491 109501 109511 109521

Notes Notes for terminals a 21


14 Ordering Ordering 15
Thermomagnetic release, 4 pole Thermomagnetic release, 4 pole
LZM…2, LZM…3 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM…2, LZM…3
Basic switching capacity 25 kA at Comfort switching capacity 36 kA Normal switching capacity 50 kA at Strong switching capacity 70 kA at
415 V 50/60 Hz at 415 V 50/60 Hz 415 V 50/60 Hz 415 V 50/60 Hz
Rated current = rated Setting range Part no. Price Part no. Price Part no. Price Part no. Price Std. Notes
uninterrupted current Overload releases Short-circuit Article no. see price Article no. see price Article no. see price Article no. see price pack
releases list list list list
Main pole Neutral
conductor
I n = Iu Ir Ir Ii
Circuit-breakers

Circuit-breakers
A A A A
I

Protection of systems and cables


4 pole
Terminal screws standard, terminals as accessories
20 15…20 15…20 350 LZMS2-4-A20 1 off IEC/EN 60947-2
109582
25 20…25 20…25 350 LZMS2-4-A25 Adjustable overload releases Ir
109583 • 0.8 – 1 x In (ex-works 0.8 x In)
32 25…32 25…32 350 LZMS2-4-A32 Setting on neutral pole implemented via the main pole setting Ir of the main pole.
109584
40 32…40 32…40 320…400 LZMS2-4-A40 Adjustable short-circuit releases Ii
109585 • 6 – 10 x In (ex-works 6 x In)
50 40…50 40…50 300…500 LZMS2-4-A50
Fixed short-circuit release Ii
109586
• 350 A at In = 20 – 32 A
63 50…63 50…63 380…630 LZMS2-4-A63
109587 LZM..2/3-4-A…
80 63…80 63…80 480…800 LZMS2-4-A80 • With 100 % overload and short-circuit protection in 4th pole
109588 LZM..2/3-4-A…/60
• With 60 % overload and short-circuit protection in 4th pole
100 80…100 80…100 600…1000 LZMS2-4-A100
109589
125 100…125 100…125 750…1250 LZMS2-4-A125
109590
160 125…160 125…160 960…1600 LZMB2-4-A160 LZMC2-4-A160 LZMN2-4-A160 LZMS2-4-A160
109564 109570 109576 109591
160 125…160 80…100 960…1600 LZMB2-4-A160/100 LZMC2-4-A160/100 LZMN2-4-A160/100 LZMS2-4-A160/100
109565 109571 109577 109592
200 160…200 160…200 1200…2000 LZMB2-4-A200 LZMC2-4-A200 LZMN2-4-A200 LZMS2-4-A200
109566 109572 109578 109593
200 160…200 100…125 1200…2000 LZMB2-4-A200/125 LZMC2-4-A200/125 LZMN2-4-A200/125 LZMS2-4-A200/125
109567 109573 109579 109594
250 200…250 200…250 1500…2500 LZMB2-4-A250 LZMC2-4-A250 LZMN2-4-A250 LZMS2-4-A250
109568 109574 109580 109595
250 200…250 125…160 1500…2500 LZMB2-4-A250/160 LZMC2-4-A250/160 LZMN2-4-A250/160 LZMS2-4-A250/160
109569 109575 109581 109596
320 250…320 250…320 1920…3200 LZMC3-4-A320 LZMN3-4-A320 LZMS3-4-A320
109621 109627 109633
320 250…320 160…200 1920…3200 LZMC3-4-A320/200 LZMN3-4-A320/200 LZMS3-4-A320/200
109622 109628 109634
400 320…400 320…400 2400…4000 LZMC3-4-A400 LZMN3-4-A400 LZMS3-4-A400
109623 109629 109635
400 320…400 200…250 2400…4000 LZMC3-4-A400/250 LZMN3-4-A400/250 LZMS3-4-A400/250
109624 109630 109636
500 400…500 400…500 3000…5000 LZMC3-4-A500 LZMN3-4-A500 LZMS3-4-A500
109625 109631 109637
500 400…500 250…320 3000…5000 LZMC3-4-A500/320 LZMN3-4-A500/320 LZMS3-4-A500/320
109626 109632 109638

Notes Notes for terminals a 25


16 Ordering Ordering 17
Circuit-breakers, electronic releases, 4 pole Circuit-breakers, electronic releases, 4 pole
LZM…3, LZM…4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM…3, LZM…4
Normal switching capacity 50 kA Strong switching capacity 70 kA
at 415 V 50/60 Hz at 415 V 50/60 Hz
Rated current = rated Setting range Part no. Price Part no. Price Std. pack Notes
uninterrupted current Overload releases Short-circuit releases Article no. see price list Article no. see price list
Main pole Neutral
conductor
In = Iu Ir Ir Ii
Circuit-breakers

Circuit-breakers
A A A A
I

Protection of systems and cables


4 pole
Terminal screws standard, terminals as accessories
400 200…400 200…400 800…4400 LZMN3-4-AE400 LZMS3-4-AE400 1 off IEC/EN 60947-2
109643 109647 Adjustable overload releases Ir
400 200…400 125…250 800…4400 LZMN3-4-AE400/250 LZMS3-4-AE400/250 • 0.5 – 1 x In (ex-works 0.8 x In)
109644 109648 Setting on neutral pole implemented via the main pole setting Ir of the
main pole.
630 315…630 315…630 1260…5040 LZMN3-4-AE630 LZMS3-4-AE630 R.m.s. value measurement and “thermal memory”
109645 109649 Adjustable short-circuit releases Ii
630 315…630 200…400 1260…5040 LZMN3-4-AE630/400 LZMS3-4-AE630/400 • LZM...3-4-AE400: 2 – 11 x In (ex-works 6 x In)
109646 109650 • LZM...3-4-AE630: 2 – 8 x In (ex-works 6 x In)
• LZM...4-4-AE...: 2 – 12 x In (ex-works 6 x In)
800 400…800 400…800 1600…9600 LZMN4-4-AE800 LZMS4-4-AE800
110968 110976
LZM...-4-AE...
800 400…800 250…500 1600…9600 LZMN4-4-AE800/500 LZMS4-4-AE800/500 • With 100 % overload and short-circuit protection in 4th pole
110969 110977 LZM...-4-AE.../...
1000 500…1000 500…1000 2000…12000 LZMN4-4-AE1000 LZMS4-4-AE1000 • With 60 % overload and short-circuit protection in 4th pole
110970 110978
1000 500…1000 315…630 2000…12000 LZMN4-4-AE1000/630 LZMS4-4-AE1000/630
110971 110979
1250 630…1250 630…1250 2500…15000 LZMN4-4-AE1250 LZMS4-4-AE1250
110972 110980
1250 630…1250 400…800 2500…15000 LZMN4-4-AE1250/800 LZMS4-4-AE1250/800
110973 110981
1600 800…1600 800…1600 3200…19200 LZMN4-4-AE1600 LZMS4-4-AE1600
110974 110982
1600 800…1600 500…1000 3200…19200 LZMN4-4-AE1600/1000 LZMS4-4-AE1600/1000
110975 110983

Notes Notes for terminals a 29


18 Ordering Ordering 19
Circuit-breakers, electronic releases, 4 pole Circuit-breakers, electronic releases, 4 pole
LZM...3, LZM...4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM...3, LZM...4
Normal switching capacity 50 kA Strong switching capacity 70 kA
at 415 V 50/60 Hz at 415 V 50/60 Hz
Rated current = Setting range Part no. Price Part no. Price Std. pack Notes
rated uninterrupted Overload releases Short-circuit releases Article no. see price list Article no. see price list
current
Main pole Neutral Non-delayed Delayed short-
conductor circuit release
In = Iu Ir Ir Ii Isd
Circuit-breakers

Circuit-breakers
A A A A A
I I

Systems and cable protection, selectivity and generator protection


4 pole
Terminal screws standard, terminals as accessories
400 200…400 200…400 800…4400 400…4000 LZMN3-4-VE400 LZMS3-4-VE400 1 off IEC/EN 60947-2
109655 109659
400 200…400 125…250 800…4400 400…4000 LZMN3-4-VE400/250 LZMS3-4-VE400/250 Adjustable overload releases Ir
109656 109660 • 0.5 – 1 x In (ex-works 0.8 x In)
630 315…630 315…630 1260…5040 472…4410 LZMN3-4-VE630 LZMS3-4-VE630 Setting on neutral pole implemented via the main pole setting Ir of the main pole.
109657 109661
630 315…630 200…400 1260…5040 472…4410 LZMN3-4-VE630/400 LZMS3-4-VE630/400 R.m.s. value measurement and “thermal memory”
109658 109662
Adjustable time delay setting to overcome current peaks tr
800 400…800 400…800 1600…9600 800…8000 LZMN4-4-VE800 LZMS4-4-VE800
• 2 … 20 s with 6 x Ir as well as infinity (without overload release) (ex-factory 10 s)
110984 110992
– LZM...3-4-VE630: 2 – 14 s at 6 x Ir also infinity (without overload release)
800 400…800 250…500 1600…9600 800…8000 LZMN4-4-VE800/500 LZMS4-4-VE800/500
110985 110993 Adjustable delayed short-circuit releases Isd
1000 500…1000 500…1000 2000…12000 1000…10000 LZMN4-4-VE1000 LZMS4-4-VE1000 • 2 – 10 x Ir (ex-works 6 x Ir)
110986 110994 – LZM...3-4-VE630: 1.5 – 7 x Ir (ex-works 6 x Ir)
1000 500…1000 315…630 2000…12000 1000…10000 LZMN4-4-VE1000/630 LZMS4-4-VE1000/630 Adjustable delay time tsd
110987 110995 • Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-works 0 ms)
1250 630…1250 630…1250 2500…15000 1250…12500 LZMN4-4-VE1250 LZMS4-4-VE1250
110988 110996 Adjustable non-delayed short-circuit releases Ii
1250 630…1250 400…800 2500…15000 1250…12500 LZMN4-4-VE1250/800 LZMS4-4-VE1250/800 • LZM...3-4-VE400: 2 – 11 x In (ex-works 6 x In)
110989 110997 • LZM...3-4-VE630: 2 – 8 x In (ex-works 6 x In)
• LZM...4-4-VE...: 2 – 12 x In (ex-works 12 x In)
1600 800…1600 800…1600 3200…19200 1600…16000 LZMN4-4-VE1600 LZMS4-4-VE1600
110990 110998 i2t constant function (ex-works OFF)
1600 800…1600 500…1000 3200…19200 1600…16000 LZMN4-4-VE1600/1000 LZMS4-4-VE1600/1000 • LZM3, LZM4 switched (ex-works OFF)
110991 110999
LZM...-4-VE...
• With 100 % overload and short-circuit protection in 4th pole
LZM...-4-VE.../...
• With 60 % overload and short-circuit protection in 4th pole

Notes Notes for terminals a 29


20 Ordering Ordering 21
Connection types Connection types
LZM1 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM1
Part no.
Max. cable connection For use with Terminal capacities Terminal capacities Article no. when Std. pack Notes
area ordered separately
Type of conductor AWG/kcmil Cu strip (number of segments Copper busbar width x
x width x segment thickness
thickness)

mm2 mm mm
Circuit-breakers

Circuit-breakers
Box terminal
Standard equipment
LZM1(-4) Three- and four-pole Cu cable 1 x 10 – 701) 1 x 8 – 2/0 2 x 9 x 0.8 NZM1-XKC 1 off Standard connection with all switches LZM1.
2 x 6 – 25 2x9–4 9 x 9 x 0.8 260015 Conversion kit for circuit-breaker with screw connection.
10

Type contains parts for a 3 or 4-pole switch side.


NZM1-4-XKC 1 off Fitted within the switch housing
12 267075

Screw connection
LZM1(-4) Three- and four-pole Copper cable lugs 1 x 10 – 70 1 x 8 – 2/0 min. 12 x 5 NZM1-XKS 1 off Type contains parts for a terminal located at top or
2 x 6 – 25 2x9–4 max. 16 x 5 260019 bottom for 3 or 4-pole circuit-breakers.
Aluminium cable lug 1 x 10 – 35 1x8–2 min. 12 x 5 NZM1-4-XKS 1 off Fitted outside the switch housing
2 x 10 – 35 2x8–2 max. 16 x 5 266725 Mounting of the cover NZM1(-4)-XKSA obligatory
o 6.5 (supplied).
7

16

Tunnel terminal
LZM1(-4) Three- and four-pole Copper cable 1 x 16 – 95 1 x 6 – 3/0 NZM1-XKA 1 off Type contains parts for a terminal located at top or
Al cable – 266730 bottom for 3 or 4-pole circuit-breakers.
NZM1-4-XKA 1 off A standard with control circuit terminal for 1 x 0.75 – 2.5
14.5 266731 mm2 (18 – 14 AWG) or 2 x 0.75 – 1.5 mm2 (18 – 14
AWG) copper conductors.
Fitted outside the switch housing
Use with flexible and highly flexible conductors ferrules.
Maximum specified cross-section can only be connected
when stranded and without ferrules.
Mounting of the cover NZM1(-4)-XKSA obligatory
(supplied).

Connection on rear
– LZM1(-4) Three- and four-pole Copper cable lugs 1 x 2.5 – 25 F 12 x 5 NZM1-XKR 1 off Type contains parts for a terminal located at top or
2 x 2.5 – 25 F 16 x 5 266734 bottom for 3 or 4-pole circuit-breakers.
Aluminium cable lug 1 x 10 – 35 NZM1-4-XKR 1 off
2 x 10 – 35 266737

Notes 1) Up to 240 mmB can be connected depending on the cable manufacturer.


22 Ordering Ordering 23
Connection types Connection types
LZM1 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM1
Part no.
Max. cable connection For use with Terminal capacities Article no. when Std. pack Notes
area ordered separately
Type of conductor AWG/kcmil

mm2

Control circuit terminal


Circuit-breakers

Circuit-breakers
– LZM1(-4) Three- and four-pole Screw connection 1 x 0.75 – 2.5 1 x 18 – 14 NZM1-XSTS 1 off Type contains parts for two terminal locations located at top or bottom for 3 or 4-pole circuit-breakers.
2 x 0.75 – 1.5 2 x 18 – 16 260150 Included as standard with tunnel terminal
Degree of protection IP1X
– Box terminal NZM-XSTK 1 off NZM-XSTK cannot be combined with NZM1(-4)-XIPK IP2X protection against contact with a finger.
266739 Height or thickness of the control terminals:
NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

Cover
– LZM1(-4) 3 pole NZM1-XKSA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
260021 Protection against direct contact where cable lugs, busbars or tunnel terminals are used
– 4 pole NZM1-4-XKSA 1 off Contained in kit with tunnel terminals or screw connection terminals.
266741 Degree of protection IP1X on the connection side when using insulated conductor material.

Terminal cover, knockout


For box terminals
– LZM1 3-pole NZM1-XKSFA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.
100780 Enhancement of the protection against direct contact (simple finger protection).
– LZM1(-4) 4 pole NZM1-4-XKSFA 1 off
100781

IP2X protection against contact with a finger


For box terminals
– LZM1 3 pole NZM1-XIPK 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
266744 Enhancement of the protection against direct contact to IP2X.
– LZM1(-4) 4 pole NZM1-4-XIPK 1 off Protection when reaching into the cable connection area with the connection of cables in the box terminal.
266745 Cannot be combined with NZM-XSTK control circuit terminal.

For cover NZM1(-4)-XKSA


– LZM1 3 pole NZM1-XIPA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
266748 Enhancement of the protection against direct contact to IP2X.
– LZM1(-4) 4 pole NZM1-4-XIPA 1 off
266749
24 Ordering Ordering 25
Connection types Connection types
LZM2 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM2

Max. cable For use with Terminal capacities Terminal capacities Part no. Part no. Std. Notes
connection area Type of Terminal AWG/kcmil Cu strip (number of Copper busbar Article no. when ordered Article no. when ordered pack
conductor capacities segments x width x width x with basic unit separately
segment thickness) thickness

mm2 mm mm
Circuit-breakers

Circuit-breakers
Box terminal
LZM2(-4) Three- Copper 1 x 4 – 185 1 x 11 – 350 f 2 x 9 x 0.8 +NZM2-160-XKCO NZM2-160-XKC 1 off Type suffix and type contain parts for a circuit-breaker
and four- conductors 2 x 4 – 70 2 x 12 – 2/0 262218 262240 side at top or bottom for 3 or 4 pole circuit-breakers.
pole Cu cable +NZM2-160-XKCU Conversion kit for circuit-breaker with screw connection.
15

262223 Fitted within the switch housing


O = for fitting at the top
18 +NZM2-250-XKCO NZM2-250-XKC U = for fitting at the bottom
262242 262244 Ue f 525 V AC:
+NZM2-250-XKCU • Use cover NZM2(4)-XKSA.
262243 Use ferrules with flexible and highly flexible conductors.
+NZM2-4-160-XKCO NZM2-4-160-XKC Max. cross section shown can only be connected when
266751 266755 flexible and without ferrules.
+NZM2-4-160-XKCU
266753
+NZM2-4-250-XKCO NZM2-4-250-XKC
266752 266756
+NZM2-4-250-XKCU
266754
Screw connection
Standard equipment
LZM2(-4) Three- Copper cable 1 x 4 – 185 1 x 11 – 3/0 f 2 x 16 x 0.8 f 16 x 5 NZM2-XKS 1 off Type contains parts for a terminal located at top or
and four- lugs 2 x 4 – 70 2 x 12 260030 bottom for 3 or 4 pole circuit-breakers.
pole 1 x 10 – 50 1 x 8 – 1/0 Standard connection with all LZM2 circuit-breakers.
Aluminium cable 2 x 10 – 50 2 x 8 – 1/0 Conversion kit for circuit-breaker with box terminal.
o 8.5
8

lug Use special cable lug narrow version, a 27


24 NZM2-4-XKS 1 off Fitted within the switch housing
266750 If a busbar is used, insulation (400 mm) e.g sleeving and
a NZM2(-4)-XKSA cover are required.
Ue f 525 V AC:
• For all other connection material a NZM2(-4)-XKSA
shroud must be used.

Tunnel terminal
LZM2(-4) Three- Copper cable 1 x 16 … 185 1 x 6 – 350 NZM2-XKA 1 off Type contains parts for a terminal located at top or
and four- Al cable 1 x 16 … 185 – 271457 bottom for 3 or 4-pole circuit-breakers.
pole A standard with control circuit terminal for 1 x 0.75 – 2.5
mm2 (18 – 14 AWG) or 2 x 0.75 – 1.5 mm2 (18 – 16
20.5 AWG) copper conductors.
NZM2-4-XKA 1 off Fitted outside the switch housing
271458 Use with flexible and highly flexible conductors ferrules.
Maximum specified cross-section can only be connected
when stranded and without ferrules.
Mounting of the cover NZM2(-4)-XKSA obligatory
(supplied).

Connection on rear
When using cable lugs without NZM3(-4)-XKSA cover, they must be insulated.
LZM2(-4) Three- Copper cable 1 x 4 – 185 f 2 x 16 x 0.8 f 16 x 5 +NZM2-XKRO NZM2-XKR 1 off Type suffix and type contain parts for a circuit-breaker
and four- lugs 2 x 4 – 70 F 6 x 24 x 0.5 F 20 x 5 266763 266765 side at top or bottom for 3 or 4-pole circuit-breakers.
pole 1 x 10 – 50 +NZM2-XKRU NZM2-4-XKR O = for fitting at the top
Aluminium cable 2 x 10 – 50 266764 266768 U = for fitting at the bottom
lug
+NZM2-4-XKRO
266766
+NZM2-4-XKRU
266767
Notes 1) Up to 240 mmB can be connected depending on the cable manufacturer.
26 Ordering Ordering 27
Connection types Connection types
LZM2 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM2

Max. cable connection For use with Terminal capacities Part no. Std. Notes
area Type of conductor Terminal capacities AWG/kcmil Copper busbar Article no. when ordered pack
width x separately
thickness
mm
mm2
Circuit-breakers

Circuit-breakers
Control circuit terminal
LZM2(-4) Three- and four- Screw connection 1 x 0.75 – 2.5 1 x 18 – 14 NZM2-XSTS 1 off Type contains parts for two terminal locations located at top or bottom for 3 or 4-pole circuit-
pole 2 x 0.75 – 1.5 2 x 18 – 16 260156 breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
NZM-XSTK cannot be combined with NZM2(-4)-XIPK IP2X protection against contact with a finger.
LZM3(-4) Three- and four- Box terminal 1 x 0.75 – 2.5 1 x 18 – 14 NZM-XSTK 1 off Height or thickness of the control circuit terminals:
pole 2 x 0.75 – 1.5 2 x 18 – 16 266739 NZM-XSTK = 2 mm
NZM-XSTS = 2 mm

Cover
LZM2 3 pole NZM2-XKSA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
260038 Protection against direct contact where cable lugs, busbars or tunnel terminals are used
LZM2(-4) 4 pole NZM2-4-XKSA 1 off Degree of protection IP1X on the connection side when using insulated conductor material.
266770

Connection cover, knockout


LZM2 3 pole NZM2-XKSFA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
104640 Enhancement of the protection against direct contact (simplified protection against contact with a
finger).
LZM2(-4) 4 pole NZM2-4-XKSFA 1 off
104641
IP2X protection against contact with a finger
For box terminals
LZM2 3 pole NZM2-XIPK 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
266773 Enhancement of the protection against direct contact to IP2X.
Protection when reaching into the cable connection area with the connection of cables in the box
LZM2(-4) 4 pole NZM2-4-XIPK 1 off terminal.
266774 With 2 conductors minimum cross-section 25 mm2.
Cannot be combined with NZM-XSTK control circuit terminal.
For covers NZM2(-4)-XKSA or NZM2(-4)
LZM2 3 pole NZM2-XIPA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
266777 Enhancement of the protection against direct contact to IP2X.
LZM2(-4) 4 pole NZM2-4-XIPA 1 off
266778

Copper cable lug


When using cable lugs without NZM3(-4)-XKSA cover, they must be insulated.
95 mm2 LZM2(-4) Three- and four- KS95-NZM7 3 off Type contains a cable lug for 3-pole or 4-pole switches.
pole 059775 Special cable lug, narrow style
120 mm2 KS120-NZM7
059776
150 mm2 KS150-NZM7
059777
185 mm2 NZM2-XKS185
260032
28 Ordering Ordering 29
Connection types Connection types
LZM3 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM3

Max. cable connection Rated For use with Terminal capacities Terminal capacities Part no. Part no. Std. pack Notes
area current1) Article no. when Article no. when
In Type of Terminal AWG/kcmil Cu strip (number of Copper busbar ordered with ordered
conductor capacities segments x width x width x basic unit separately
segment thickness) thickness
A mm2 mm mm

Box terminal
Circuit-breakers

Circuit-breakers
max. 500 LZM3(-4) Three- and Copper 1 x 35 – 240 1 x 2 – 500 min. 6 x 16 x 0.8 +NZM3-XKCO NZM3-XKC 1 off Type suffix and type contain parts for a circuit-
400 UL/CSA four-pole conductors 2 x 16 – 120 max. 20 x 24 x 0.5 262246 260042 breaker side at top or bottom for 3 or 4-pole
Cu cable or +NZM3-XKCU circuit-breakers.
16

max. 11 x 21 x 1 262245 Conversion kit for circuit-breaker with screw


connection.
630 1 x 35 – 240 1 x 2 – 500 min. 6 x 16 x 0.8 +NZM3-4-XKCO NZM3-4-XKC Fitted within the switch housing
25
2 x 16 – 120 max. 20 x 24 x 0.5 266781 266783 O = for fitting at the top
or +NZM3-4-XKCU U = for fitting at the bottom
max. 11 x 21 x 1 266782 Ue f 525 V AC:
• Use NZM3(-4)-XKSA cover.
Use with flexible and highly flexible conductors
ferrules, note the max. terminal capacity when
using ferrules.

Screw connection
630 LZM3(-4) Three- and Copper cable 1 x 16 – 240 1 x 4 – 350 10 x 32 x 1.0 30 x 10 NZM3-XKS 1 off Type contains parts for a terminal located at top or
four-pole lugs 2 x 16 – 240 2 x 350 + 5 x 32 x 1.0 + 30 x 5 260039 bottom for 3 or 4-pole circuit-breakers.
15

max. 400 1 x 10 – 120 NZM3-4-XKS 1 off Standard connection with all LZM3 circuit-
Aluminium 2 x 10 – 120 266780 breakers.
o 10.5 cable lug Conversion kit for circuit-breaker with box
32 terminal.
Use special cable lugs narrow version, a 32
Fitted within the switch housing
When a busbar is used insulation is required
(400 mm) e.g. using heat shrink and a shroud
NZM3(-4)-XKSA.
Ue f 525 V AC:
A shroud NZM3(-4)-XKSA must be used with all
other connection types.

Connection width extension


630 LZM3(-4) Three- and Copper cable 2 x 300 2 x 500 (2 x) 10 x 50 x 1.0 (2 x) 10 x 50 NZM3-XKV70 1 off Type contains parts for a terminal located at top or
four-pole lugs 100514 bottom for 3 or 4 pole circuit-breakers.
NZM3-4-XKV70 1 off Central drill holes, e.g. for up to 2 cable lugs per
Aluminium 100515 phase.
cable lug Can be fitted to circuit-breaker with screw
termination
Phase isolator supplied.
Distance between pole centres with NZM3(-4)-
XKV70: 70 mm
Drill hole available for control cable.
Connection terminals NZM3(-4)-XK300 and
NZM3(-4)-XK22X21 can be installed.

Notes 1) The following applies for the rated current: The values have been determined conform
to IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-
sections and are intended for the purpose of orientation.
30 Ordering Ordering 31
Connection types Connection types
LZM3 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM3

Max. cable Rated For use with Terminal capacities Terminal capacities Part no. Part no. Std. Notes
connection area current1) Article no. when Article no. when pack
Type of Terminal AWG/kcmil Cu strip (number of Copper ordered with ordered
conductor capacities segments x width x busbar width basic unit separately
In segment thickness) x thickness
A mm2 mm mm
Circuit-breakers

Circuit-breakers
Terminals for connection width extension
max. 500 LZM3 3 pole Cu cable 1 x 120 – 300 NZM3-XK300 1 off Type contains parts for a terminal located at top or
100782 bottom for 3 or 4-pole circuit-breakers.
LZM3(-4) 4 pole NZM3-4-XK300 1 off Only in conjunction with connection width
100783 extension NZM3(-4)-XKV70.
Use with flexible and highly flexible conductors
630 LZM3 3 pole (2 x) 11 x 21 x 1.0 NZM3-XK22X21 1 off ferrules.
100784 Standard with control circuit terminal for 1 x 0.75
LZM3(-4) 4 pole (2 x) 11 x 21 x 1.0 NZM3-4- 1 off – 2.5 mm2 or 2 x 0.75 – 1.5 mm2 copper
XK22X21 conductors.
100785
Tunnel terminal
– max. 350 LZM3(-4) Three- and four- Copper 1 x 16 – 1852) 1 x 6 – 350 NZM3-XKA1 1 off Type contains parts for a terminal located at top or
pole conductors – 271459 bottom for 3 or 4-pole circuit-breakers.
Cu cable NZM3-4-XKA1 1 off A standard with control circuit terminal for 1 x
Al 271460 0.75 – 2.5 mm2 (18 – 14 AWG) or 2 x 0.75 – 1.5
conductors mm2 (18 – 16 AWG) copper conductors.
Al cable Fitted outside the switch housing
20.5 Use with flexible and highly flexible conductors
ferrules. Maximum specified cross-section can only
be connected when stranded and without ferrules.
– max. 630 1 x 50 – 240 1 x 0 – 500 NZM3-XKA2 1 off Mounting of the cover NZM3(-4)-XKSA obligatory
2 x 50 – 240 2 x 0 – 500 271461 (supplied).
NZM3-4-XKA2 1 off
271462

22.5

Connection on rear
not UL/CSA approved
max. 630 LZM3(-4) Three- and four- Copper 1 x 16 – 240 +NZM3-XKRO NZM3-XKR 1 off Type suffix and type contain parts for a circuit-
pole cables 2 x 16 – 240 266790 266792 breaker side at top or bottom for 3 or 4-pole circuit-
Cu cable +NZM3-XKRU NZM3-4-XKR 1 off breakers.
266791 266795 O = for fitting at the top
U = for fitting at the bottom
+NZM3-4-XKRO
266793
+NZM3-4-XKRU
266794
max. 500 – – 1 x 10 – 120 min.6 x 16 x 0.8 Min. 20 x 5
2 x 10 – 120 Max. 10 x 32 x 1.0 Max. 30 x 10
Control circuit terminal
– LZM3(-4) Three- and four- Screw 1 x 0.75 – 2.5 1 x 18 – 14 NZM3/4-XSTS 1 off Type contains parts for two terminal locations
pole connection 2 x 0.75 – 1.5 2 x 18 – 16 266797 located at top or bottom for 3 or 4 pole circuit-
breakers.
Included as standard with tunnel terminal
Degree of protection IP1X
– LZM3(-4) Box NZM-XSTK 1 off Height or thickness of the control circuit terminals
terminal 266739 NZM-XSTS = 2 mm

Notes 1) The following applies for the rated current: The values have been determined conform to
IEC/EN 60947 (switchgear standard) and generally relate to the max. defined cross-sections
and are intended for the purpose of orientation.
The engineering standards which apply in each case must be observed.
32 Ordering Ordering 33
Connection types Connection types
LZM3 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM3

Max. cable connection For use with Part no. Std. pack Notes
area Article no. when
ordered separately

Cover
– – LZM3(-4) 3 pole NZM3-XKSA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
260045 Insulation/protection against direct contact where cable lugs, busbars or tunnel terminals are used.
Included in set with tunnel terminals
Circuit-breakers

Circuit-breakers
– – 4 pole NZM3-4-XKSA 1 off
266801 Degree of protection IP1X on the connection side when using insulated conductor material.

Phase isolator
– – LZM3(-4) 3 pole NZM3-XKP 1 off Type contains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.
100512 Included with the connection width extension.
– – 4 pole NZM3-4-XKP 1 off Cannot be combined with the NZM3(-4)-XKA tunnel terminal, NZM3(-4)-XKR connection on rear.
100513 Insulation protection with connection of cable lugs, busbars or braid.

Connection cover, knockout


– – LZM3(-4) 3 pole NZM3-XKSFA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
104642 Enhancement of the protection against direct contact to (simplified protection against contact with a finger).
– – 4 pole NZM3-4-XKSFA 1 off
104643
IP2X protection against contact with a finger
– LZM3(-4) 3 pole NZM3-XIPK 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
266804 Enhancement of the protection against direct contact to IP2X.
4 pole NZM3-4-XIPK 1 off Protection when reaching into the cable connection area with the connection of cables in the box terminal.
266805 With 2 conductors minimum cross-section 70 mm2.
Cannot be combined with NZM-XSTK control circuit terminal.

For cover NZM3(-4)-XKSA


– LZM3(-4) 3 pole NZM3-XIPA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
266808 Enhancement of the protection against direct contact to IP2X.
– 4 pole NZM3-4-XIPA 1 off
266809

Copper cable lug


When using cable lugs without NZM3(-4)-XKSA cover, they must be insulated.
185 mm2 – LZM3(-4) 3 and 4 pole NZM3-XKS185 3 off Type contains a cable lug for 3-pole or 4-pole switches.
LZM4(-4) 260040 Special cable lug, narrow style

900 mm2 – 3 and 4 pole NZM3-XKS240 3 off


260041
34 Ordering Ordering 35
Connection types Connection types
LZM4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM4

Max. cable connection area Rated For use with Terminal capacities Terminal capacities Part no. Std. pack Notes
current1) Article no. when
Type of Terminal AWG/kcmil Cu strip (number of Copper busbar width ordered separately
conductor capacities segments x width x x thickness
In segment thickness)

A mm2 mm mm
Circuit-breakers

Circuit-breakers
Screw connection
Standard equipment
2-hole max. 1250 LZM4(-4) Three- and Cu cable lugs 1 x 120 – 185 1 x 250 – 350 (2 x) 10 x 50 x 1.0 (2 x) 50 x 10 off Double hole fitting for M10 screws with 25 mm clearance.
four-pole 4 x 50 – 185 4 x 0 – 350 Use special cable lug narrow version.

20
Ue f 525 V or cross-section > 185 mm2: Use of shroud NZM4(-4)-
XKSA required.
o10.5 o10.5 1600 off
25
50

3-hole 2000 LZM4 3 pole Cu cable lugs (2 x) 80 x 10 off Triple hole fitting for M10 screws with 25 mm pitch.
Phase divider for insultion above is supplied.
20

o10.5 o10.5 o10.5


25 25
80

Module plate
Single max. 1250 LZM4 3 pole Copper cable 1 x 120 – 300 1 x 250 – 600 (2 x) 10 x 40 x 1.0 (2 x) 40 x 10 NZM4-XKM1 1 off Type contains parts for a terminal located at top or bottom for 3 or
hole lugs 2 x 95 – 300 2 x 000 – 600 (2 x) 10 x 50 x 1.0 (2 x) 50 x 10 266814 4-pole circuit-breakers.
LZM4-4 4 pole NZM4-4-XKM1 1 off For M10 screws. Can be enlarged for M12 screws.
266815 Use special cable lug narrow version.
Can be fitted to circuit-breaker with screw termination
Double max. 1400 LZM4 3 pole Copper cable 2 x 95 – 185 2 x 000 – 350 NZM4-XKM2 1 off Insulation through NZM4(-4)-XKSA cover or NZM4(-4)-XKP phase
hole lugs 4 x 35 – 185 4 x 2 – 350 266820 separator necessary
LZM4-4 4 pole 4 x 50 NZM4-4-XKM2 1 off
266821
Double max. 1250 LZM4 3 pole Copper cable 2 x 95 – 300 2 x 000 – 600 NZM4-XKM2S- 1 off Type contains parts for a terminal located at top or bottom for 3 or
hole lugs 1250 4-pole circuit-breakers.
284471 Insulation through cover NZM4(-4)-XKSA or phase isolator
LZM4-4 4 pole NZM4-4-XKM2S- 1 off NZM4(4)-XKP necessary.
1250
284472
max. 1600 LZM4 3 pole Copper cable 2 x 95 – 300 2 x 000 – 500 NZM4-XKM2S- 1 off
lugs 1600
284473
LZM4-4 4 pole 2 x 95 – 300 2 x 000 – 500 NZM4-4-XKM2S- 1 off
1600
284474
Connection width extension
max. 1600 LZM4 3 pole Cu cable lugs 4 x 300 4 x 600 min. 10 x 50 x 1.0 max. (2 x) 80 x 10 NZM4-XKV95 1 off Type contains parts for a terminal located at top or bottom for 3 or
6 x 95 – 240 6 x 000 … 281591 4-pole circuit-breakers.
500 NZM4-XKV110 1 off Five way holes, e.g. for up to 9 cable lugs per phase.
281593 Can be fitted to circuit-breaker with screw termination
Phase isolator supplied.
LZM4-4 4 pole NZM4-4-XKV95 1 off Distance between pole centres with NZM4(-4)-XKV95: 95 mm
281592 Installation conditions for current transformer up to 130 mm width
NZM4-4-XKV120 1 off with 80 mm busbar width.
281594 Distance between pole centres with NZM4-XKV110: 107.5 mm
Installation conditions for current transformer up to 135 mm width
with 80 mm busbar width.
Distance between pole centres with NZM4-4-XKV120: 122 mm
Installation conditions for current transformer up to 164 mm width
with 80 mm busbar width.
4 mm drilled holes for control circuit terminal available.

Notes 1) Thefollowing applies for the rated current: The values have been determined conform to IEC/EN 60947
(switchgear standard) and generally relate to the max. defined cross-sections and are intended for the
purpose of orientation.
36 Ordering Ordering 37
Connection types Connection types
LZM4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM4

Max. cable connection area Rated For use with Terminal Terminal capacities Part no. Std. pack Notes
current1) capacities Article no. when
In Type of Terminal AWG/kcmil Cu strip (number of Copper busbar ordered separately
conductor capacities segments x width x width x
segment thickness) thickness
A mm
mm2 mm
Circuit-breakers

Circuit-breakers
Flat cable terminal
– max. 1100 LZM4 3 pole min.6 x 16 x 0.8 NZM4-XKB 1 off Type contains parts for a terminal located at top or bottom for 3 or
max. (2 x) 10 x 32 x 1.0 266829 4-pole circuit-breakers.
– LZM4-4 4 pole min.6 x 16 x 0.8 NZM4-4-XKB 1 off Conversion kit for circuit-breaker with screw connection.
max. (2 x) 10 x 32 x 1.0 266831 Insulation through cover NZM4(-4)-XKSA or phase isolator
NZM4(4)-XKP necessary.
With switch mpunting on conductive mounting plates use of the
shroud NZM4(-4)-XKSA necessary (supplied item).

Tunnel terminal
– max. 1400 LZM4 3 pole Copper 1 x 50 – 240 1 x 0 – 500 NZM4-XKA 1 off Type contains parts for a terminal located at top or bottom for 3 or
conductors 4 x 50 – 240 4 x 0 – 500 266836 4 pole circuit-breakers.
– LZM4-4 4 pole Cu cable 1 x 50 – 240 1 x 0 – 500 NZM4-4-XKA 1 off A standard with control circuit terminal for 1 x 0.75 … 2.5 mm2
Al 4 x 50 – 240 4 x 0 – 500 266837 (18 … 14 AWG) or 2 x 0.75 … 1.5 mm2 (18 … 16 AWG) copper
conductors conductors.
Al cable Can be fitted to circuit-breaker with screw termination
22.5 Use ferrules with flexible and highly flexible conductors. Max.
cross section shown can only be connected when flexible and
without ferrules.
Use of the NZM4(-4)-XKSA cover obligatory(supplied).

Connection on rear
– max. 1250 LZM4(-4) Three- and Copper cable 1 x 120 – 185 (2 x) 10 x 50 x 1.0 (2 x) 50 x 10 NZM4-XKR 1 off Type contains parts for a terminal located at top or bottom for 3 or
four-pole lugs 2 x 95 – 185 266842 4-pole circuit-breakers.
4 x 35 – 185 NZM4-4-XKR 1 off Can also be retrofitted:
1 x 185 266843 NZM4...-XKM... module plate or NZM4-...-XKV... connection width
Aluminium 2 x 70 – 185 extension
cable lug 4 x 50 – 185
– 1600 – off

Notes 1) The following applies for the rated current: The values have been determined conform to IEC/EN 60947
(switchgear standard) and generally relate to the max. defined cross-sections and are intended for the purpose
of orientation.
38 Ordering Ordering 39
Connection types Connection types
LZM4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM4

Max. cable connection area For use with Terminal capacities Part no. Std. pack Notes
Article no. when ordered
Type of conductor Terminal AWG/kcmil separately
capacities

mm2
Circuit-breakers

Circuit-breakers
Control circuit terminal
– LZM3(-4) Three- and Screw connection 1 x 0.75 – 2.5 1 x 18 – 14 NZM3/4-XSTS 1 off Type contains parts for two terminal locations located at top or bottom for 3 or 4 pole circuit-breakers.
four-pole 2 x 0.75 – 1.5 2 x 18 – 16 266797 Included as standard with tunnel terminal
Degree of protection IP1X
Height or thickness of the control circuit terminals
NZM-XSTS = 2 mm

Cover
– LZM4 3 pole NZM4-XKSA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4 pole circuit-breakers.
266846 Protection against direct contact where cable lugs, busbars, flat cable terminals or tunnel terminals are used.
– LZM4-4 4 pole NZM4-4-XKSA With module plates, flat braid terminals and tunnel terminals included in the kit.
266847 When using insulated conductor material to degree of protection: IP1X.

Connection cover, knockout


– LZM4 3 pole NZM4-XKSFA 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
292193 Enhancement of the protection against direct contact to (simplified protection against contact with a finger).
– LZM4-4 4 pole NZM4-4-XKSFA
292194

Phase isolators
– LZM4 3 pole NZM4-XKP 1 off Type contains parts for a terminal located at top or bottom for 3 or 4-pole circuit-breakers.
281595 Included with the connection width extension.
Cannot be combined with the tunnel terminal NZM4(-4)-XKA, connection NZM4-XKR on rear.
Insulation protection where cable lugs, busbars, module plates or flat cable terminals are used.
– LZM4-4 4 pole NZM4-4-XKP
281596

Cable lug
185 mm2 LZM3(-4) 3 and 4 pole NZM3-XKS185 3 off Type contains a cable lug for 3-pole or 4-pole switches.
LZM4(-4) 260040 Special cable lug, narrow style
900 mm2 NZM3-XKS240
260041
40 Ordering
Plug-in units
NZM2-XSV… Moeller SK1230-1176GB http://catalog.moeller.net

For use with Number of poles Part no. Price Part no. Price Std. Notes
Article no. when see price Article no. when see price pack
ordered with list ordered list
basic unit separately

Plug-in and withdrawable units


For circuit-breakers LZM
Plug-in adapter elements
Circuit-breakers

Complete
Only in combination with circuit-breaker
Terminal screws standard, terminals as accessories
LZM2-4 4 pole +NZM2-4-XSV 1 off Inmax. at:
266698 20 °C: 250 A
LZM2 3 pole +NZM2-XSV 40 °C: 230 A (LZM...2-...)
266697 Mounting position: vertical,
90° right, 90° left
Order control circuit plug unit
separately!

Sockets
e.g. for reserved slots
Retrofit of circuit-breaker with plug-in module.
Terminal screws standard, terminals as accessories

LZM2 3 pole NZM2-XSVS 1 off


266699
LZM2-4 4 pole NZM2-4-XSVS
266700

Removable module
Fits socket base
Only in combination with circuit-breaker
LZM2 3 pole +NZM2-XSVE 1 off
266701
LZM2-4 4 pole +NZM2-4-XSVE
266702

Control circuit plug unit


LZM2(-4) for auxiliary contact, NZM2-XSVHI 1 off –
shunt/undervoltage 266705
release
LZM2(-4) for remote operator NZM2-XSVR –
266706
Ordering 41
Withdrawable units
http://catalog.moeller.net Moeller SK1230-1176GB NZM3-XAV…
For use with Number Part no. Price Part no. Price Std. pack Notes
of poles Article no. when see price Article no. when see price
ordered with list ordered list
basic unit separately

Withdrawable unit
with control circuit plug unit
For circuit-breakers LZM

Circuit-breakers
Withdrawable unit with auxiliary plug-in adapter
Complete
Only in combination with circuit-breaker
Terminal screws standard, terminals as accessories
LZM3 3 pole +NZM3-XAV 1 off Inmax. at:
266707 20 °C: 605 A (LZM3), 1600 A
LZM3-4 4 pole +NZM3-4-XAV (LZM4)
266708 40 °C: 550 A (LZM3), 1500 A
(LZM4)
LZM4 3 pole +NZM4-XAV
266709 Mounting position
LZM4-4 4 pole +NZM4-4-XAV LZM3: vertical, 90 ° left
266710 LZM4: vertical

3 positions
Connected, test, disconnected
The 3 positions are indicated
mechanically.

Socket base Additionally, auxiliary contacts


e.g. for reserved slots are use for remote signalling. An
Retrofit of circuit-breaker with withdrawable optional M22-(C)K01normally
carrier. closed contact or M22-(C)K10
normally open contact per
Terminal screws standard, terminals as accessories position
LZM3 3 pole NZM3-XAVS 1 off Also see the RMQ-Titan
266711 control circuit device range in the
LZM3-4 4 pole NZM3-4-XAVS Main Catalogue
266712
All connections of auxiliary
LZM4 3 pole NZM4-XAVS switches (HIA, HIN, HIV) and
266713 voltage releases to the control
LZM4-4 4 pole NZM4-4-XAVS circuit plug units are already
266714 present.

Withdrawable carrier
LZM3 3 pole +NZM3-XAVE 1 off
266715
LZM3-4 4 pole +NZM3-4-XAVE
266716
LZM4 3 pole +NZM4-XAVE
266717
LZM4-4 4 pole +NZM4-4-XAVE
266718
42 Ordering Ordering 43
Auxiliary contact with screw terminals Auxiliary contact with screw terminals
LZM, M22-… Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM, M22-…
For use with Auxiliary contacts: f = safety Contact Part no. Price Part no. Price Std. pack Notes Notes
function, by positive opening to sequence Article no. when see price list Article no. see price list
IEC/EN 60947-5-1 ordered when
separately ordered
N/O = Normally N/C = Normally separately
open closed

Auxiliary contacts
Standard auxiliary contact (HIN)
Circuit-breakers

Circuit-breakers
Switching with the main contacts
Used for indicating and interlocking tasks
LZM1(-4), 2(-4), 3(-4), 4(-4) 1 N/O 1.X3 M22-K10 M22-CK10 20 off For Std. pack: The following can be clipped into the switches:
216376 216384 M22-(C)K... : • LZM1- one standard auxiliary contact
1.X4 Std. pack = 20 off • LZM2 - up to 2 standard auxiliary contacts M22-(C)K…
1 N/C f 1.X1 M22-K01 M22-CK01 20 off • LZM3 and LZM4 - up to 3 standard auxiliary contacts M22-(C)K…
216378 216385 Any combinations of the auxiliary contact types ispossible.
1.X2
Marking on switch: HIN
With 3 m connection LZM1(-4), 2(-4), 3(-4), 4(-4) 1 N/O 1 N/C f 1.X3 1.X1 M22-CK11 20 off
cable instead of 107940
screw termination. 1.X4 1.X2

2 N/O 1.X3 1.X3 M22-CK20


107898
1.X4 1.X4

2 N/C f 1.X1 1.X1 M22-CK02


107899
1.X2 1.X2

Early-make auxiliary contact


For interlocking and load shedding circuits, as well as for early make of the undervoltage release in main switch/Emergency-Stop
applications
With clamp terminal LZM1(-4) 2 N/O 3.13 3.23 NZM1-XHIV 1 off Not in conjunction with NZM…-XU… undervoltage release or NZM…-
on the left-hand 259426 XA… shunt release
switch side. 3.14 3.24 Early make with switch on and switch off (manual actuation): approx. 20 ms

With clamp terminal 2 N/O 3.13 3.23 NZM1-XHIVR


on the right-hand 292195
switch side. 3.14 3.24

With 3 m connection 2 N/O 3.13 3.23 NZM1-XHIVL


cable instead of 259432
screw termination. 3.14 3.24

LZM2(-4), 3(-4) 2 N/O 3.13 3.23 NZM2/3-XHIV


259430
3.14 3.24

LZM4(-4) 2 N/O 3.13 3.23 NZM4-XHIV Not in conjunction with undervoltage release NZM…-XU, shunt release
266172 NZM…-XA… or remote operator NZM…-XR…
3.14 3.24 Early make with switch on (manual actuation): approx. 90 ms

Trip indicating auxiliary contact (HIA), (HIAFI)


General trip indication '+', when tripped by voltage release, overload release, short-circuit release or by the residual-current release
due to residual-current.
LZM1(-4), 2(-4), 3(-4), 4(-4) 1 N/O 4.X3 M22-K10 M22-CK10 20 off For Std. pack: The following can be clipped into the switches:
216376 216384 M22-(C)K... : • LZM1 - one trip-indicating auxiliary switch
4.X4 Std. pack = 20 off • LZM2 - one M22-(C)K… trip-indicating auxiliary switch
1 N/C f 4.X1 M22-K01 M22-CK01 • LZM3 - one M22-(C)K… trip-indicating auxiliary switch
216378 216385 • LZM4 - up to two M22-(C)K… trip-indicating auxiliary switches
4.X2
Any combinations of the auxiliary contact types is possible.
With 3 m connection LZM1(-4), 2(-4), 3(-4), 4(-4) 1 N/O 1 N/C f 4.X3 4.X1 M22-CK11 Marking on switch: HIA
cable instead of 107940 Labeling in FI-Block: HIAFI.
screw termination. 4.X4 4.X2
If the trip-indicating auxiliary contact in the fault-current block is used, the
2 N/O 4.X3 4.X3 M22-CK20 N/C contacts operates as a N/O contact and the N/C contact operates as an
107898 N/O contact (circuit symbol)
4.X4 4.X4

2 N/C f 4.X1 4.X1 M22-CK02


107899
4.X2 4.X2
44 Ordering
Undervoltage release with screw terminal
LZM1 Moeller SK1230-1176GB http://catalog.moeller.net

For use with Rated control voltage Part no. Price Std. pack Notes
Article no. when see price
Us ordered separately list

Undervoltage releases
Circuit-breakers

Without auxiliary contact


Non-delayed disconnection of LZM circuit-breakers when the control voltage sinks
below 35 – 70% US.
For use with Emergency-Stop devices in conjunction with Emergency-Stop button.

With clamp LZM1(-4) 24 V 50/60 Hz NZM1-XU24AC 1 off When the undervoltage


terminal on the 259434 release is de-energized,
left-hand switch 110 V – 130 V 50/60 Hz NZM1-XU110-130AC accidental contact with the
side. 259440 main contacts of the switch
during attempts to switch on,
208 V 240 V 50/60 Hz NZM1-XU208-240AC is safely prevented .
259442
380 V – 440 V 50/60 Hz NZM1-XU380-440AC Undervoltage release cannot
259444 be installed simultaneously
with NZM...-XHIV... early-
D1 480 V – 525 V 50/60 Hz NZM1-XU480-525AC
make auxiliary contact or
259446
U< NZM...-XA... shunt release.
D2 600 V 50/60 Hz NZM1-XU600AC
259448
12 V DC NZM1-XU12DC
259450
24 V DC NZM1-XU24DC
259452
110 V – 130 V DC NZM1-XU110-130DC
259458
220 V – 250 V DC NZM1-XU220-250DC
259460
With 3 m LZM1(-4) 24 V 50/60 Hz NZM1-XUL24AC 1 off
connection 259462
cable instead of 110 V – 130 V 50/60 Hz NZM1-XUL110-130AC
screw 259468
termination.
208 V 240 V 50/60 Hz NZM1-XUL208-240AC
259471
380 V – 440 V 50/60 Hz NZM1-XUL380-440AC
259473
D1 480 V – 525 V 50/60 Hz NZM1-XUL480-525AC
259475
U<
D2 600 V 50/60 Hz NZM1-XUL600AC
259477
12 V DC NZM1-XUL12DC
259479
24 V DC NZM1-XUL24DC
259481
110 V 130 V DC NZM1-XUL110-130DC
259487
220 V – 250 V DC NZM1-XUL220-250DC
259489
Ordering 45
Undervoltage release with screw terminal
http://catalog.moeller.net Moeller SK1230-1176GB LZM2/3…, LZM4
For use with Rated control voltage Part no. Price Std. pack Notes
Article no. when ordered see price
Us separately list

Undervoltage releases

Circuit-breakers
Without auxiliary contact
Non-delayed disconnection of LZM circuit-breakers when the control voltage sinks
below 35 – 70% US.
For use with Emergency-Stop devices in conjunction with Emergency-Stop button.

LZM2(-4) 24 V 50/60 Hz NZM2/3-XU24AC 1 off When the undervoltage


LZM3(-4) 259491 release is de-energized,
110 V – 130 V 50/60 Hz NZM2/3-XU110-130AC accidental contact with the
259497 main contacts of the switch
during attempts to switch
208 V 240 V 50/60 Hz NZM2/3-XU208-240AC on, is safely prevented .
259499
380 V – 440 V 50/60 Hz NZM2/3-XU380-440AC Undervoltage release cannot
259501 be installed simultaneously
with NZM...-XHIV... early-
480 V – 525 V 50/60 Hz NZM2/3-XU480-525AC
make auxiliary contact or
259503
NZM...-XA... shunt release.
D1 600 V 50/60 Hz NZM2/3-XU600AC
259505
U<
D2 12 V DC NZM2/3-XU12DC
259507
24 V DC NZM2/3-XU24DC
259509
110 V 130 V DC NZM2/3-XU110-130DC
259515
220 V – 250 V DC NZM2/3-XU220-250DC
259517
LZM4(-4) 24 V 50/60 Hz NZM4-XU24AC 1 off
266189
110 V – 130 V 50/60 Hz NZM4-XU110-130AC
266192
208 V – 240 V 50/60 Hz NZM4-XU208-240AC
266193
380 V – 440 V 50/60 Hz NZM4-XU380-440AC
266194
480 V – 525 V 50/60 Hz NZM4-XU480-525AC
266195
600 V 50/60 Hz NZM4-XU600AC
266196
D1 12 V DC NZM4-XU12DC
266203
U<
D2 24 V DC NZM4-XU24DC
266204
110 V – 130 V DC NZM4-XU110-130DC
266207
220 V – 250 V DC NZM4-XU220-250DC
266208
46 Ordering
Undervoltage release with screw terminal
LZM1, LZM2/3 Moeller SK1230-1176GB http://catalog.moeller.net

For use Rated control voltage Part no. Price Std. pack Notes
with Article no. when ordered see price
Us separately list
V

Undervoltage releases
With two early-make auxiliary contacts
For interlocking and load-shedding circuits, as well as for early-make of the
Circuit-breakers

undervoltage release in main-switch applications.

With clamp LZM1(-4) 24 V 50/60 Hz NZM1-XUHIV24AC 1 off When the undervoltage


terminal on 259531 release is de-energized,
the left-hand 110 V – 130 V 50/60 Hz NZM1-XUHIV110-130AC accidental contact with the
switch side. 259537 main contacts of the switch
during attempts to switch on
208 V – 240 V 50/60 Hz NZM1-XUHIV208-240AC is safely prevented.
259539 Early-make of the auxiliary
380 V – 440 V 50/60 Hz NZM1-XUHIV380-440AC contacts with on and off
259541 switching (manual
operation): approx. 20 ms.
480 V – 525 V 50/60 Hz NZM1-XUHIV480-525AC
Undervoltage releases cannot
D1 3.13 259543
be installed simultaneously
12 V DC NZM1-XUHIV12DC with NZM...-XHIV... early-
259545 make auxiliary contact or
24 V DC NZM1-XUHIV24DC NZM...-XA... shunt release.
D2 3.14
259547
110 V – 130 V DC NZM1-XUHIV110-130DC
259553
220 V – 250 V DC NZM1-XUHIV220-250DC
259555
With 3 m LZM1(-4) 24 V 50/60 Hz NZM1-XUHIVL24AC 1 off
connection 259557
cable instead 110 V – 130 V 50/60 Hz NZM1-XUHIVL110-130AC
of screw 259563
termination.
208 V – 240 V 50/60 Hz NZM1-XUHIVL208-240AC
259565
380 V – 440 V 50/60 Hz NZM1-XUHIVL380-440AC
259567
D1 3.13 480 V – 525 V 50/60 Hz NZM1-XUHIVL480-525AC
259569
12 V DC NZM1-XUHIVL12DC
259571
3.14
24 V DC NZM1-XUHIVL24DC
D2
259573
110 V – 130 V DC NZM1-XUHIVL110-130DC
259579
220 V – 250 V DC NZM1-XUHIVL220-250DC
259581
LZM2(-4) 24 V 50/60 Hz NZM2/3-XUHIV24AC 1 off When the undervoltage
LZM3(-4) 259583 release is de-energized,
110 V – 130 V 50/60 Hz NZM2/3-XUHIV110-130AC accidental contact with the
259589 main contacts of the switch
during attempts to switch on
208 V – 240 V 50/60 Hz NZM2/3-XUHIV208-240AC is safely prevented.
259591 Early-make of the auxiliary
380 V – 440 V 50/60 Hz NZM2/3-XUHIV380-440AC contacts with on and off
259594 switching (manual
operation): approx. 20 ms.
D1 3.13 480 V – 525 V 50/60 Hz NZM2/3-XUHIV480-525AC Cannot be used in
259598 conjunction with NZM...-XR...
12 V DC NZM2/3-XUHIV12DC remote operator.
259600 Undervoltage releases cannot
be installed simultaneously
3.14
24 V DC NZM2/3-XUHIV24DC with NZM...-XHIV... early-
D2
259602 make auxiliary contact or
110 V – 130 V DC NZM2/3-XUHIV110-130DC NZM...-XA... shunt release.
259608
220 V – 250 V DC NZM2/3-XUHIV220-250DC
259610
Ordering 47
Undervoltage release with screw terminal
http://catalog.moeller.net Moeller SK1230-1176GB LZM1, LZM2/3…, LZM4
For use with Rated control voltage Part no. Price Std. pack Notes
Article no. when ordered see price
Us separately list
V

Undervoltage releases
With two early-make auxiliary contacts

Circuit-breakers
For interlocking and load-shedding circuits, as well as for early-make
of the undervoltage release in main-switch applications.

LZM4(-4) 24 V 50/60 Hz NZM4-XUHIV24AC 1 off When the undervoltage release is de-


266217 energized, accidental contact with the
110 V – 130 V 50/60 Hz NZM4-XUHIV110-130AC main switches of the switch during
266220 attempts to switch on is safely prevented.
Early-make of the auxiliary contacts with
208 V – 240 V 50/60 Hz NZM4-XUHIV208-240AC switch on (manual operation):
266221 approx. 90 ms.
380 V – 440 V 50/60 Hz NZM4-XUHIV380-440AC Cannot be used in conjunction with
266222 NZM...-XR... remote operator.
Undervoltage releases cannot be
480 V – 525 V 50/60 Hz NZM4-XUHIV480-525AC
installed simultaneously with NZM...-
266223
XHIV... early-make auxiliary contact or
D1 3.13 12 V DC NZM4-XUHIV12DC NZM...-XA... shunt release.
266231
24 V DC NZM4-XUHIV24DC
266232
3.14
110 V – 130 V DC NZM4-XUHIV110-130DC
D2
266235
220 V – 250 V DC NZM4-XUHIV220-250DC
266236
48 Ordering
Undervoltage release with screw terminal
LZM1, LZM2/3…, LZM4 Moeller SK1230-1176GB http://catalog.moeller.net

For use with Rated control voltage Part no. Price Std. pack
Article no. when ordered separately see price list
Us
V

Undervoltage releases
With two separate early-make auxiliary contacts
Circuit-breakers

Coil connection wired to clamp terminal, auxiliary switch connections wired with 3 m loose
connection cables
LZM1(-4) 24 V 50/60 Hz NZM1-XUHIV20KL24AC 1 off
D1 3.13 3.23
284388
110 V – 130 V 50/60 Hz NZM1-XUHIV20KL110-130AC
D2 3.14 3.24 284389
208 V – 240 V 50/60 Hz NZM1-XUHIV20KL208-240AC
284400
24 V DC NZM1-XUHIV20KL24DC
284387
Coil connection with 3 m loose connection cables, auxiliary switch connections wired to clamp
terminal
LZM1(-4) 24 V 50/60 Hz NZM1-XUHIV20LK24AC 1 off
D1 3.13 3.23
284402
110 V – 130 V 50/60 Hz NZM1-XUHIV20LK110-130AC
D2 3.14 3.24 284403
208 V … 240 V 50/60 Hz NZM1-XUHIV20LK208-240AC
284404
24 V DC NZM1-XUHIV20LK24DC
284401
Coil connection with 3 m loose connection cables, auxiliary switch connections wired to clamp
terminal
LZM2(-4) 24 V 50/60 Hz NZM2/3-XUHIV20LK24AC 1 off
D1 3.13 3.23
LZM3(-4) 285291
110 V – 130 V 50/60 Hz NZM2/3-XUHIV20LK110-130AC
D2 3.14 3.24 284407
208 V – 240 V 50/60 Hz NZM2/3-XUHIV20LK208-240AC
284408
24 V DC NZM2/3-XUHIV20LK24DC
284405

Contacts 3.23 and 3.24 with separate 3 m connection cables.


LZM4(-4) 24 V 50/60 Hz NZM4-XUHIV2024AC 1 off
D1 3.13 3.23
266244
110 V – 130 V 50/60 Hz NZM4-XUHIV20110-130AC
D2 3.14 3.24 266247
208 V 240 V 50/60 Hz NZM4-XUHIV20208-240AC
266248
380 V – 440 V 50/60 Hz NZM4-XUHIV20380-440AC
266249
24 V DC NZM4-XUHIV2024DC
266258

Notes When the undervoltage release is de-energized, accidental contact with the main switches of the switch during attempts to switch on is safely
prevented.
Early-make of the auxiliary contacts with on and off switching (manual operation): approx. 20 ms.
Cannot be used in conjunction with NZM...-XR... remote operator.
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
Ordering 49
Undervoltage releases, off-delayed
http://catalog.moeller.net Moeller SK1230-1176GB LZM1, LZM2/3..., LZM4
For use with Part no. Price Std. pack Notes
Article no. when see price
ordered separately list

Undervoltage releases, off-delayed


Combination of separate delay unit and special tripping device.

Circuit-breakers
Delay unit
Voltage dips of less than the setting between 0.06 – 16 s do not
cause disconnection of the NZM circuit-breaker or N switch-
disconnector.
LZM1(-4), 2(-4), 3(-4), 4(-4) UVU-NZM 1 off Adjustable delay time 70 ms – 4 s.
260154 With additional capacitor up to 16 s.
50/60 Hz A special tripping device is required.
220 V – 240 V Cannot be installed simultaneously with
380 V – 440 V NZM...-XHIV... or NZM...-XA... shunt release.
480 V – 550 V Delay unit for separate installation (Fixing: top-
hat rail or screws).
DC/AC For other operating voltages use control
24 V transformer.

Special tripping device


For combination with separate delay unit
Without auxiliary contacts
NZM1-X… with 3 m separate connection cables instead of screw
terminal, NZM2, 3 , 4 with screw terminal
D1 LZM1(-4) NZM1-XUVL 1 off UVU-NZM delay unit is additionally required.
271607 Cannot be installed simultaneously with
U
LZM2(-4) NZM2/3-XUV separate NZM...-XHIV early-make auxiliary
D2 contact or NZM...-XA... shunt release.
LZM3(-4) 259527
LZM4(-4) NZM4-XUV
266588
With 2 early-make auxiliary contacts
NZM1-X… with 3 m separate connection cables instead of
screw terminal, NZM2, 3 , 4 with screw terminal
D1 3.13 LZM1(-4) NZM1-XUVHIVL 1 off Cannot be used in conjunction with NZM...-
271608 XR... remote operator.
LZM2(-4) NZM2/3-XUVHIV UVU-NZM delay unit is additionally required.
LZM3(-4) 259684 Cannot be installed simultaneously with
U
separate NZM...-XHIV early-make auxiliary
D2 3.14 LZM4(-4) NZM4-XUVHIV contact or NZM...-XA... shunt release.
266596 LZM1, 2, 3: Early-make of the auxiliary contacts
with on and off switching (manual operation):
approx. 20 ms.
LZM4: Early-make of the auxiliary contacts with
switch on (manual operation): approx. 90 ms.

With 2 separately operating early-make auxiliary contacts


NZM1-X… with 3 m separate connection cables instead of
screw terminal, NZM2(3)(4)-X… with screw terminal, contact
3.23 and 3.24 with 3 m separate connection cables.
LZM1(-4) NZM1-XUVHIV20L 1 off Cannot be used in conjunction with NZM...-
D1 3.13 3.23 271609 XR... remote operator.
LZM2(-4) NZM2/3-XUVHIV20 UVU-NZM delay unit is additionally required.
D2 3.14 3.24 LZM3(-4) 259688 Cannot be installed simultaneously with
separate NZM...-XHIV early-make auxiliary
LZM4(-4) NZM4-XUVHIV20 contact or NZM...-XA... shunt release.
266604 LZM1, 2, 3: Early-make of the auxiliary contacts
with on and off switching (manual operation):
approx. 20 ms.
LZM4: Early-make of the auxiliary contacts with
switch on (manual operation): approx. 90 ms.
50 Ordering
Shunt releases with screw terminal
LZM1, LZM2/3, LZM4 Moeller SK1230-1176GB http://catalog.moeller.net

For use Rated control voltage Part no. Price Std. Notes
with Article no. when ordered see price pack
separately list
Us
V

Shunt releases
Without auxiliary contact
Circuit-breakers

Switches are tripped by a voltage pulse or by the application of uninterrupted


voltage.
With clamp LZM1(-4) 12 V AC/DC NZM1-XA12AC/DC 1 off When the undervoltage
terminal on the 259706 release is de-energized,
left-hand switch 24 V AC/DC NZM1-XA24AC/DC accidental contact with the
side. 259708 main contacts of the switch
during attempts to switch
110 V – 130 V AC/DC NZM1-XA110-130AC/DC on, is safely prevented.
259724
Shunt release cannot be
installed simultaneously
C1 208 V – 250 V AC/DC NZM1-XA208-250AC/DC with NZM...-XHIV... early-
259726 make auxiliary contact or
C2 380 V – 440 V AC/DC NZM1-XA380-440AC/DC NZM...-XU... undervoltage
259728 release.
With 3 m LZM1(-4) 12 V AC/DC NZM1-XAL12AC/DC 1 off
connection cable 259734
instead of screw 24 V AC/DC NZM1-XAL24AC/DC
termination. 259736
110 V – 130 V AC/DC NZM1-XAL110-130AC/DC
259742

C1 208 V – 250 V AC/DC NZM1-XAL208-250AC/DC


259744
C2 380 V – 440 V AC/DC NZM1-XAL380-440AC/DC
259746
Without auxiliary contact
Switches are tripped by a voltage pulse or by the application of uninterrupted
voltage.
LZM2(-4) 12 V AC/DC NZM2/3-XA12AC/DC 1 off When the undervoltage
LZM3(-4) 259752 release is de-energized,
24 V AC/DC NZM2/3-XA24AC/DC accidental contact with the
259754 main contacts of the switch
during attempts to switch
110 V – 130 V AC/DC NZM2/3-XA110-130AC/DC on, is safely prevented.
259760
208 V – 250 V AC/DC NZM2/3-XA208-250AC/DC Shunt release cannot be
259763 installed simultaneously
with NZM...-XHIV... early-
C1 380 V – 440 V AC/DC NZM2/3-XA380-440AC/DC make auxiliary contact or
259766 NZM...-XU... undervoltage
C2
release.

LZM4(-4) 12 V AC/DC NZM4-XA12AC/DC 1 off


266446
24 V AC/DC NZM4-XA24AC/DC
266447
110 V – 130 V AC/DC NZM4-XA110-130AC/DC
266450
208 V – 250 V AC/DC NZM4-XA208-250AC/DC
266451

C1 380 V – 440 V AC/DC NZM4-XA380-440AC/DC


266452
C2
Ordering 51
Shunt releases with screw terminal
http://catalog.moeller.net Moeller SK1230-1176GB LZM...-X...
For use with Part no. Price Std. pack Notes
Article no. when see price
ordered list
separately

Shunt releases

Circuit-breakers
Capacitor unit 230 V 50/60 Hz
in conjunction with NZM...-XA2082-50AC/DC
shunt release
Enclosure: degree of protection IP20
LZM1(-4) NZM-XCM 1 off Enables the safe use of circuit-breakers as mesh network circuit-breakers
LZM2(-4) 229413 in the range from 0 … 110 % Un with constant switch-off time of 40 ms.
LZM3(-4) If the mains voltage is absent, the installed capacitor supplies power for
LZM4(-4) actuating the shunt release for at least 12 hours.
The configuration of the capacitor unit is undertaken independently of the
circuit-breaker.
Connect NZM-XCM to the power feed side.

Design note:
Connect a standard auxiliary contact as N/O in series with the shunt
release!
Standard auxiliary contact not included as standard.

For use Rated control Part no. Price Std. Notes


with voltage Article no. when ordered see price pack
separately list

Us
V

Shunt releases
Without auxiliary contacts
For mesh-network circuit-breakers
For intermittent operation
Maximum on time = 1 s
Operating range 10 – 110 % Us
C1 LZM3(-4) 230 V AC NZM3-XA-230AC-MNS 1 off Cannot be installed simultaneously with NZM...-
274097 XHIV... early-make auxiliary contact or NZM...-XU...
undervoltage release.
C2

Intermittent operation guaranteed by series


connection of an M22-(C)K10 make contact.
The maximum operating time of the shunt release for
mesh network circuit-breaker is 1 s.

C1 LZM4(-4) 230 V AC NZM4-XA-230AC-MNS 1 off L1 (L+)


274138
C2

a
-S11
0

1.13
Q M22-...K10
HIN 1.14

C1
-Q1 NZM...-XA...-MNS
C2

N (L-, L2)

a Reverse-power relay contact


-S11 Remote off
Q Standard auxiliary contact
-Q1 Shunt release
52 Ordering
Shunt releases with screw terminal
LZM1, LZM2/3, LZM4 Moeller SK1230-1176GB http://catalog.moeller.net

For use Rated control voltage Part no. Price Std. Notes
with Article no. when ordered see price pack
Us separately list
V

Shunt releases
With early-make auxiliary contact
Not in combination with remote operator.
Circuit-breakers

With clamp LZM1(-4) 12 V AC/DC NZM1-XAHIV12AC/DC 1 off When the shunt release is
terminal on 259772 energized, accidental
the left-hand 24 V AC/DC NZM1-XAHIV24AC/DC contact with the main
switch side. 259774 contacts of the switch
during attempts to switch on
110 V – 130 V AC/DC NZM1-XAHIV110-130AC/DC is safely prevented.
259780 Early-make of the auxiliary
contact with on and off
switching (manual
C1 3.13 208 V – 250 V AC/DC NZM1-XAHIV208-250AC/DC operation): approx. 20 ms.
259782 Shunt release cannot be
C2 3.14 380 V – 440 V AC/DC NZM1-XAHIV380-440AC/DC installed simultaneously
259784 with NZM...-XHIV.. early-
make auxiliary contact or
With 3 m LZM1(-4) 12 V AC/DC NZM1-XAHIVL12AC/DC 1 off NZM...-XU... undervoltage
connection 259790 release.
cable instead 24 V AC/DC NZM1-XAHIVL24AC/DC
of screw 259792
termination.
110 V – 130 V AC/DC NZM1-XAHIVL110-130AC/DC
259798

C1 3.13 208 V – 250 V AC/DC NZM1-XAHIVL208-250AC/DC


259800
C2 3.14 380 V – 440 V AC/DC NZM1-XAHIVL380-440AC/DC
259802
With early-make auxiliary contact
LZM2(-4) 12 V AC/DC NZM2/3-XAHIV12AC/DC 1 off When the shunt release is
LZM3(-4) 259808 energized, accidental
24 V AC/DC NZM2/3-XAHIV24AC/DC contact with the main
259810 contacts of the switch
during attempts to switch on
110 V – 130 V AC/DC NZM2/3-XAHIV110-130AC/DC is safely prevented.
259816 Early-make of the auxiliary
208 V – 250 V AC/DC NZM2/3-XAHIV208-250AC/DC contact with on and off
259818 switching (manual
operation): approx. 20 ms.
C1 3.13 380 V – 440 V AC/DC NZM2/3-XAHIV380-440AC/DC Cannot be used in
259820 conjunction with NZM...-
C2 3.14
XR... remote operator.
Shunt release cannot be
LZM4(-4) 12 V AC/DC NZM4-XAHIV12AC/DC 1 off installed simultaneously
266470 with NZM...-XHIV.. early-
24 V AC/DC NZM4-XAHIV24AC/DC make auxiliary contact or
266471 NZM...-XU... undervoltage
release.
110 V – 130 V AC/DC NZM4-XAHIV110-130AC/DC
266474
208 V – 250 V AC/DC NZM4-XAHIV208-250AC/DC
266475

C1 3.13 380 V – 440 V AC/DC NZM4-XAHIV380-440AC/DC


266476
C2 3.14
Ordering 53
Shunt releases with screw terminal
http://catalog.moeller.net Moeller SK1230-1176GB NZM...-XAHIV-...
For use Rated control Part no. Price Std. pack
with voltage Article no. when ordered see price
Us separately list

Shunt releases

Circuit-breakers
For mesh-network circuit-breakers
For intermittent operation
Maximum on time = 1 s
Operating range 10 – 110 % Us
C1 3.13 With early-make auxiliary LZM3(-4) 230 V AC NZM3-XAHIV-230AC-MNS 1 off
contact 274141
C2 3.14

C1 3.13 230 V AC NZM4-XAHIV-230AC-MNS 1 off


274143
C2 3.14

Notes Cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
Cannot be used in conjunction with NZM...-XR... remote operator.

Intermittent operation guaranteed by series connection of a N/O contact M22-(C)K10 (standard auxiliary contact).
The maximum operating time of the shunt release for mesh network circuit-breaker is 1 s.
LZM3: Early-make of the auxiliary contact with on and off switching (manual operation): approx. 20 ms.
LZM4: Early-make of the auxiliary contact with switch on (manual operation): approx. 90 ms.
54 Ordering Ordering 55
Door coupling rotary handles Door coupling rotary handles
LZM1, LZM2, LZM3, LZM4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM1, LZM2, LZM3, LZM4
For a max. shaft length of 60 mm Extremely narrow fittings
For use with Part no. Price Std. pack Notes Part no. Price Std. pack Notes Part no. Price Std. pack Notes
Article no. see price Article no. see price Article no. see price
list list list

Door coupling rotary handle


Circuit-breakers

Circuit-breakers
Complete including rotary drive and coupling parts
An additional extension shaft is necessary with the NZM...-XT(V)D(V)(R)(-60) types.
Degree of protection IP66
Standard, black/grey
Lockable on the 0 position LZM1(-4) NZM1-XTVD 1 off Door interlock NZM1-XTVD-60 1 off Door interlock NZM1-XTVD-0 1 off Door interlock
on the handle using up to 3 260166 • Not defeated in the locked 271504 • Not defeated in the locked OFF 279392 • Not defeated in the locked OFF
padlocks. With door LZM2(-4) NZM2-XTVD OFF and ON positions NZM2-XTVD-60 and ON positions NZM2-XTVD-0 and ON positions
interlock 260168 • Can be modified such that it 271505 • Can be modified such that it 279393 • Can be modified such that it can
can be defeated from the can be defeated from the be defeated from the outside
LZM3(-4) NZM3-XTVD outside using a screwdriver, NZM3-XTVD-60 outside using a screwdriver, NZM3-XTVD-0 using a screwdriver, when it is in
260170 when it is in the unlocked 271506 when it is in the unlocked ON 279394 the unlocked ON position.
LZM4(-4) NZM4-XTVD ON position. NZM4-XTVD-60 position. NZM4-XTVD-0 • Door can be opened in OFF
266614 • Door can be opened in OFF 271507 • Door can be opened in OFF 279395 NZM...-XTVD(V)-0
NZM...-XTVD(V) NZM...-XTVD(V)-60 • For extremely narrow fittings
Lockable on the handle on LZM1(-4) NZM1-XTVDV • External warning plate/ NZM1-XTVDV-60 • For maximum shaft length 60 NZM1-XTVDV-0 • With special short extension
the switch using up to 3 260172 designation label can be 271508 mm 279396 shaft
padlocks. Can be locked in clipped on • Without shaft support • Cannot be combined with
LZM2(-4) NZM2-XTVDV NZM2-XTVDV-60 • Cannot be combined with NZM2-XTVDV-0 NZM...-XDZ additional handle
0 position on the handle, 260174 271509 279397
with adequate NZM...-XDZ additional handle • External warning plate/
modification also in I LZM3(-4) NZM3-XTVDV NZM3-XTVDV-60 • External warning plate/ NZM3-XTVDV-0 designation label can be clipped
position. With door 260176 271510 designation label can be 279398 on
interlock. Lockable in the 0 LZM4(-4) NZM4-XTVDV NZM4-XTVDV-60 clipped on NZM4-XTVDV-0
position 266616 271511 279399

Red-yellow for Emergency-Stop


Lockable on the handle on LZM1(-4) NZM1-XTVDVR 1 off Door interlock NZM1-XTVDVR-60 1 off Door interlock NZM1-XTVDVR-0 1 off Door interlock
the switch using up to 3 260178 • Not defeatable in the 271512 • Not defeatable in the locked 279400 • Not defeatable in the locked OFF
padlocks. Lockable in 0 locked OFF position. OFF position. position.
position on handle. With • Can be modified such that it • Can be modified such that it • Can be modified such that it can
door interlock. Lockable in can be defeated from the can be defeated from the be defeated from the outside
the 0 position LZM2(-4) NZM2-XTVDVR outside using a screwdriver, NZM2-XTVDVR-60 outside using a screwdriver, NZM2-XTVDVR-0 using a screwdriver, when it is in
260180 when it is in the unlocked 271513 when it is in the unlocked ON 279401 the unlocked ON position.
LZM3(-4) NZM3-XTVDVR ON position. NZM3-XTVDVR-60 position. NZM3-XTVDVR-0 • Door can be opened in OFF
260182 • Door can be opened in OFF 271514 • Door can be opened in OFF 279402 NZM...-XTVDVR-0
NZM...-XTVDVR NZM...-XTVDVR-60 • For extremely narrow fittings
LZM4(-4) NZM4-XTVDVR • External warning plate/ NZM4-XTVDVR-60 • For maximum shaft length 60 NZM4-XTVDVR-0 • With special short extension
266618 designation label can be 271515 mm 279403 shaft
clipped on • Without shaft support • Cannot be combined with
• Cannot be combined with NZM...-XDZ additional handle
NZM...-XDZ additional handle • External warning plate/
• External warning plate/ designation label can be clipped
designation label can be on
clipped on

Extension shaft
Max. mounting depth: 400 LZM1(-4) NZM1/2-XV4 1 off Can be cut to required length
mm LZM2(-4) 261232
LZM3(-4) NZM3/4-XV4
LZM4(-4) 261234
Max. mounting depth: 600 LZM1(-4) NZM1/2-XV6
mm LZM2(-4) 260191
LZM3(-4) NZM3/4-XV6
LZM4(-4) 260193

Notes Circuit-breaker can also be installed in a lying position 90 ° left/right, with the handle still in the same position.
56 Ordering
Rotary handles
NZM…-XDV… Moeller SK1230-1176GB http://catalog.moeller.net

For use with Part no. Price Std. Notes


Article no. when see price pack
ordered separately list

Rotary handle on circuit-breaker


Complete with rotary drive
Circuit-breakers

Standard, black/grey
Lockable on the 0 position LZM1(-4) NZM1-XDV 1 off NZM1(2)(3)-X…: Can also be
on the switch using up to 3 260125 combined with insulating surround.
padlocks. MODAN handle position detection by
LZM2(-4) NZM2-XDV wire release can be retrofitted.
260127

LZM3(-4) NZM3-XDV
260129
LZM4(-4) NZM4-XDV
266608

Lockable on the 0 position LZM1(-4) NZM1-XDVG 1 off Can also be combined with insulating
on the handle using up to 3 285247 surround.
padlocks.
LZM2(-4) NZM2-XDVG
285248

Red-yellow for Emergency-Stop


Lockable on the 0 position LZM1(-4) NZM1-XDVR 1 off NZM1(2)(3)-X…: Can also be
on the switch using up to 3 260135 combined with insulating surround.
padlocks. MODAN handle position detection by
LZM2(-4) NZM2-XDVR wire release can be retrofitted.
260137

LZM3(-4) NZM3-XDVR
260140
LZM4(-4) NZM4-XDVR
266610

Lockable on the 0 position LZM1(-4) NZM1-XDVGR Can also be combined with insulating
on the handle using up to 3 285249 surround.
padlocks.
LZM2(-4) NZM2-XDVGR
285280

Notes Circuit-breaker can also be installed in a lying position 90 ° left/right, with the handle still in the same position.
Ordering 57
Rotary handles with door interlock
http://catalog.moeller.net Moeller SK1230-1176GB NZM...-XDTV...
For use with Part no. Price Std. Notes
Article no. when see price pack
ordered separately list

Rotary handle on switch with door interlock


Complete with rotary drive and insulating surround

Circuit-breakers
Standard, black/grey
Lockable on the 0 LZM1(-4) NZM1-XDTV 1 off Door interlock
position on the handle 260131 • In the ON position, can be defeated from
using up to 3 padlocks, the outside using a 1 mm pin
can also be modified for • Not defeated in the locked OFF and ON
the I position. Also positions
available with door LZM2(-4) NZM2-XDTV • Door can be opened in OFF
interlock e.g. for MCC 260133 • Can only be switched ON when the door
service distribution. is closed

Red-yellow for Emergency-Stop

Lockable on the 0 LZM1(-4) NZM1-XDTVR 1 off


position on the handle 260142
using up to 3 padlocks.
Also available with door LZM2(-4) NZM2-XDTVR
interlock e.g. for MCC 260144
service distribution

Notes Circuit-breaker can also be installed in a lying position 90 ° left/right, with the handle still in the same position.
58 Ordering
Main switch assembly kit
NZM...-XHB..., NZM...-XS... Moeller SK1230-1176GB http://catalog.moeller.net

Type For use with Part no. Price Std. pack


Article no. when see price list
ordered separately

Main switch assembly kit


Equipment supplied:
• Rotary door-coupling handle
Circuit-breakers

• NZM...-XV4 extension shaft


• External warning plate/designation label in German/English
• Black and yellow flash
For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger
can be ordered a 23
Other external warning plates/designation labels can be clipped on.
With black door coupling rotary handle
Lockable on the 0 position on the LZM1(-4) NZM1-XHB 1 off
handle using up to 3 padlocks, can 266626
also be modified for the I position. LZM2(-4) NZM2-XHB
With door interlock. 266627
LZM3(-4) NZM3-XHB
266628
LZM4(-4) NZM4-XHB
271779
With red door coupling rotary handle for using switch as Emergency-Stop device according to IEC/EN 602041

Lockable on the 0 position on the LZM1(-4) NZM1-XHBR


handle using up to 3 padlocks. 266632
Lockable door as additional feature, LZM2(-4) NZM2-XHBR
locking facility on circuit-breaker in 0 266633
position. LZM3(-4) NZM3-XHBR
266634
LZM4(-4) NZM4-XHBR
271842
Main switch assembly kit for side panel mounting
Actuation of the switch on the control panel side wall
Switch mounting on mounting plate
Equipment supplied:
• Door coupling rotary handle
• NZM...-XV4 extension shaft
• External warning plate/designation label in German/English
• Black and yellow flash
For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger
can be ordered a 23
Other external warning plates/designation labels can be clipped on.
Standard, black/grey
Lockable on the 0 position on the For operation on LZM1(-4) NZM1-XS-L 1 off
handle using up to 3 padlocks, can the left 266641
also be modified for the I position. LZM2(-4) NZM2-XS-L
266642
LZM3(-4) NZM3-XS-L
266643
LZM4(-4) NZM4-XS-L
289806
For operation on LZM1(-4) NZM1-XS-R
the right 266644
LZM2(-4) NZM2-XS-R
266645
LZM3(-4) NZM3-XS-R
266646
LZM4(-4) NZM4-XS-R
289807
Red-yellow for Emergency-Stop
Lockable on the 0 position on the For operation on LZM1(-4) NZM1-XSR-L
handle using up to 3 padlocks. the left 266653
LZM2(-4) NZM2-XSR-L
266654
LZM3(-4) NZM3-XSR-L
266655
LZM4(-4) NZM4-XSR-L
289808
For operation on LZM1(-4) NZM1-XSR-R
the right 266656
LZM2(-4) NZM2-XSR-R
266657
LZM3(-4) NZM3-XSR-R
266658
LZM4(-4) NZM4-XSR-R
289809
Ordering 59
Main switch assembly kit
http://catalog.moeller.net Moeller SK1230-1176GB NZM...XS(R)M...
Type For use with Part no. Price Std.
Article no. when see price pack
ordered list
separately

Main switch assembly kit for side panel mounting with mounting bracket
For direct mounting of circuit-breaker and handle in the side wall of the control cabinet

Circuit-breakers
Equipment supplied:
• Door coupling rotary handle
• Mounting bracket
• Special short extension shaft
• External warning plate/designation label in German/English
• Black and yellow flash
For enhanced protection against direct contact on the incomer side, IP2X protection against contact with a finger can be
ordered a 23
Other external warning plates/designation labels can also be clipped on.
Standard, black/grey
Can be locked in 0 position, with adequate For operation on the LZM1(-4) NZM1-XSM-L 1 off
modification also in I position. Narrowest minimum left 266663
clearance between enclosure side plates of control For operation on the LZM2(-4) NZM2-XSM-L
panel and circuit-breaker is defined by mounting left 266664
bracket. Extensions cannot be used.
For operation on the LZM1(-4) NZM1-XSM-R
right 266665
For operation on the LZM2(-4) NZM2-XSM-R
right 266666
Red-yellow for Emergency-Stop
Lockable in 0 position on handle. Narrowest For operation on the LZM1(-4) NZM1-XSRM-L 1 off
minimum clearance between enclosure side plates left 266671
of control panel and circuit-breaker is defined by For operation on the LZM2(-4) NZM2-XSRM-L
mounting bracket. Extensions cannot be used. left 266672
For operation on the LZM1(-4) NZM1-XSRM-R
right 266673
For operation on the LZM2(-4) NZM2-XSRM-R
right 266674
Add-on plate
For fitting to the mounting bracket when using N conductor or PE conductor terminals K25, K50, K95 or K150.
LZM1(-4) NZM1/2-XZB 1 off
LZM2(-4) 266676

Additional terminal arrangement for side wall operator with mounting bracket
NZM1-XS(R)M-…, NZM2-XS(R)M-…
Additional terminals K25, K50, K95, K150 a 66

Actuation:
3 pole 4 pole
For operation on the right For operation on the left For operation on the right For operation on the left
MII MI MI MII
MI MII

Mounting areas MI MII


Variation options V1 V2 V3 V4 V1 V2
Maximum number of additional K25 2x – – – – –
terminals K50 – 2x – – – –
K95 – – 1x – 1x –
K150 – – – 1x – 1x

Example: In mounting area MI, variation option 1 allows the K25 additional terminal to be mounted twice.
60 Ordering
Accessories
NZM...-XRAV..., ZFS..., BPF-... Moeller SK1230-1176GB http://catalog.moeller.net

For use with Part no. Price Std. pack Notes


Article no. when see price list
ordered separately

Rear drive
For direct rear connection of the switch to the side of the control panel or
control panel door. Switch actuation on rear through side plate or control
panel door.
For switch with toggle lever.
Circuit-breakers

For enhanced protection against direct contact on the incomer side, IP2X
protection against contact with a finger can be ordered a 21
Degree of protection IP66, UL/CSA Type 4X
Standard, black/grey
Lockable on the 0 LZM1 NZM1-XRAV 1 off External warning plate can be clipped on
position on the 107245
handle using up to LZM2 NZM2-XRAV
3 padlocks. 107247

Red-yellow for Emergency-Stop


Lockable on the 0 LZM1 NZM1-XRAVR 1 off
position on the 107249
handle using up to LZM2 NZM2-XRAVR
3 padlocks. 107261

External warning plate/designtion label

German/English LZM1(-4) ZFS61/62-NZM7 1 off A bilingual external warning plate/


LZM2(-4) 272525 designation label in German/English is
German LZM3(-4) ZFS61-NZM7 already included in the main switch
LZM4(-4) 051089 assembly kit.
English ZFS62-NZM7
065957
French ZFS63-NZM7
065958
Blank (for engraving or printing) ZFS60-NZM7
065896
Further languages ZFS*-NZM7 External warning plates are available in the
999978 following languages:
64 Bulgarian 73 Romanian
65 Danish 74 Russian
66 Finnish 75 Swedish
67 Dutch 76 Serbo-Croatian
68 Italian 77 Spanish
69 Greek 78 Czech
70 Norwegian 79 Turkish
71 Polish 80 Hungarian
72 Portuguese 81 Afrikaans
To obtain the order number, insert the lan-
guage code number into the type reference
required.
Ordering example
External warning plate in Finnish:
ZFS66-NZM7
Lightning symbol
Including terminal marking for main switch
Small U X L1 T1 N PEN
V Y L2 T2
LZM1(-4) BPF-NZM7 10 off Included as standard in main switch
W Z L3 T3 PE LZM2(-4) 217294 assembly kit

Large U X
V Y
L1 T1 N PEN
L2 T2
LZM3(-4) BPF-NZM10 10 off
W Z L3 T3 PE LZM4(-4) 231363
Ordering 61
Accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM...-XDZ, NZM...-XBR, NZM...-X...

For use with Part no. Price Std. pack Notes


Article no. when see price list
ordered separately

Add-on handle
Enables switching when the control panel door is open

Circuit-breakers
LZM1(-4) NZM1/2-XDZ 1 off Push-fits on to the extension shaft
LZM2(-4) 266621 100 mm free extension shaft required.
Cannot be combined with NZM...-XT...-60
LZM3(-4) NZM3/4-XDZ 1 off door coupling rotary handles as well as
LZM4(-4) 266622 NZM...-XT...-0.

Insulating surrounds
For toggle lever, rotary handle with rotary drive and remote operator.
Degree of protection IP40

LZM1(-4) NZM1-XBR 1 off For oblong cut-out on doors and


260195 enclosures with material thicknesses of
1.5 – 5 mm.
External warning plate/designation label
LZM2(-4) NZM2-XBR can be clipped on
260197 NZM4-XBR cannot be combined with
LZM3(-4) NZM3-XBR rotary handle with rotary drive.
284645
LZM4(-4) NZM4-XBR
284646
Toggle lever locking device
Off position lockable using up to 3 padlocks (hasp thickness 4 – 8 mm)
LZM1(-4) NZM1-XKAV 1 off Cannot be combined with insulating
260199 surround.
LZM2(-4) NZM2/3-XKAV 1 off
LZM3(-4) 260201

Spacers
Enables fast and low-priced adjustment of differing frame sizes with/
without rotary handle to the same front depth
LZM1(-4) NZM1/2-XAB 1 set Grid depth 17.5 mm, M4 thread
LZM2(-4) 260203 Type contains 4 off spacer
Maximum component capacity:
LZM1: 4 units per fixing screw,
LZM2: 2 units per fixing screw
2 (LZM1) or 4 (LZM2) fixing screws
contained per circuit-breaker
LZM3(-4) NZM3-XAB 1 set Grid depth 17.5 mm, M5 thread
LZM4(-4) 260211 One set contains 4 spacers
LZM3, LZM4: 1 off per fixing screw
4 fixing screws per switch included

Clip plate
Enables snap-fit of the circuit-breaker to a DIN rail
LZM1(-4) NZM1-XC35 1 off For top-hat rail 35 mm
260213

LZM2 NZM2-XC75 1 off For top-hat rail 75 mm


260215 Not suitable for circuit-breakers with
remote operator.
62 Ordering
Mechanical interlock
NZM...XMV(R)(L), NZM-XBZ... Moeller SK1230-1176GB http://catalog.moeller.net

For use with Part no. Price Std. pack Notes


Article no. when see price
ordered separately list

Mechanical interlocking of (door coupling) rotary handles

LZM1(-4) NZM1-XMV 1 off Rotary handles on switches or door coupling


Circuit-breakers

281581 rotary handles are additionally required.


Cannot be combined with paralleling
mechanisms, side wall operators and remote
operator as well as NZM4-XBR insulating
surrounds.
LZM2(-4) NZM2-XMV In order to establish a mechanical interlock at
281582 least 2 interlock modules are required.
Possible combinations and interlock variants
a engineering
Order Bowden cable separately

LZM3(-4) NZM3-XMV
281583
LZM4(-4) NZM4-XMV
281584

Bowden cables
For mechanical interlocking of (door coupling) rotary handles

LZM1(-4) NZM-XBZ225 1 off


LZM2(-4) 281585
LZM3(-4) NZM-XBZ600
LZM4(-4) 281586
NZM-XBZ1000
281587
Mechanical interlock for remote operator
For 2 switches of the same or next frame size with each other.
Mounting beside one another.

LZM2(-4) NZM2-XMVR 1 off Type contains parts for both switches.


+LZM2(-4) 104543 Remote operator also required.
LZM2(-4) NZM2/3-XMVR Maximum switching distance a
+LZM3(-4) 104544 engineering
Cannot be combined with rotary handles,
LZM3(-4) NZM3-XMVR door coupling rotary handles and early-make
+LZM3(-4) 104545 auxiliary contacts.
LZM3(-4) NZM3/4-XMVR
+LZM4(-4) 104546
LZM4(-4) NZM4-XMVR
+LZM4(-4) 104547

For 2 switches of the same or different type with opposed operation.


Extra long Bowden cable for mounting one above the other or in
adjacent enclosures.

LZM2(-4) NZM2-XMVRL 1 off Type contains parts for both switches.


+LZM2(-4) 104548 Remote operator also required.
LZM2(-4) NZM2/3-XMVRL Maximum switching distance a
+LZM3(-4) 104549 engineering
Cannot be combined with rotary handles,
LZM3(-4) NZM3-XMVRL door coupling rotary handles and early-make
+LZM3(-4) 104550 auxiliary contacts.
LZM3(-4) NZM3/4-XMVRL
+LZM4(-4) 104551
LZM4(-4) NZM4-XMVRL
+LZM4(-4) 104552
Ordering 63
Multi-function device adapter
http://catalog.moeller.net Moeller SK1230-1176GB NZM...-XAD..., NZM...-XKR...
For use with Rated current Part no. Price Std. pack Notes
Article no. when see price
ordered list
separately
Ie
A

Component adapter for circuit-breakers and switch-

Circuit-breakers
disconnectors for 60 mm busbar system
For installation on flat copper busbars 12 … 30 x 5 … 10,
double T and triple T profile
Rated operational voltage Ue: 690 V
• Halogen free
• Temperature resistant to 120 °C
• Self-extinguishing to UL 94
• Approved for feeder branch circuits to UL508A up to 600 V
• 3 pole
LZM1 160 NZM1-XAD160 1 off For breakers with box terminal as standard connection
104554 Connection to system at top using the supplied
connection cable
In conjunction with IP2X protection against contact
with a finger
Enhancement of the protection against direct contact
on the switch outgoer side possible
LZM2 250 NZM2-XAD250 Connection to the system possible at top or bottom via
104555 connection on rear (+)NZM2-XKR4…
Mounting using clamp and screw fixing.

LZM3 550 NZM3-XAD550 Connection to the system possible at top via connection
104556 on rear (+)NZM3-XK13…
Mounting using clamp and screw fixing.

For use with Rated current Part no. suffix Price Part no. Price Std. pack
Article no. when ordered see price Article no. when ordered see price
with basic unit list separately list

Ie
A

Connection on rear for component adapters


For component adapters for LZM2, LZM3

LZM2 250 +NZM2-XKR4O NZM2-XKR4 1 off


281664 281666
LZM2 250 +NZM2-XKR4U NZM3-XKR13
281665 281668
LZM3 550 +NZM3-XKR13O
281667

Notes Part no. and part no. suffix include parts for one switch side at top or bottom (with LZM3 top only). Required with component adapter and
switch with connection on rear, see for example component adapter 104555 and 104556.
O = for fitting at the top
U = for fitting at the bottom
64 Ordering Ordering 65
Accessories Accessories
LZM2, LZM3, LZM4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM2, LZM3, LZM4
For use with Rated control voltage Part no. Price Std. pack
Article no. when ordered see price list Notes
separately
Us
V

Remote operator
For remote switching of circuit-breakers and switch-disconnectors.
Circuit-breakers

Circuit-breakers
ON and OFF switching and resetting by means of 2-wire or 3-wire control.
Can be synchronized.
Local switching by hand possible
Lockable in the 0 position of the remote operator with up to 3 padlocks (hasp thickness: 4 – 8 mm)
LZM2(-4) 110 – 130 V 50/60 Hz NZM2-XR110-130AC 1 off
A standard auxiliary contact (HIN) for the switch position detection is supplied.
259830
When installing the NZM2-XR… and NZM3-XR… remote operators on 4 pole switches, an additional 4 pole NZM2-XAVPR or NZM3-XAVPR shroud is necessary.
208 – 240 V 50/60 Hz NZM2-XR208-240AC
259832 3-wire control
380 – 440 V 50/60 Hz NZM2-XR380-440AC1) L1 Terminal 70/71:
259834 (L1+)
0 I Please note during engineering:
H1
24 – 30 V DC NZM2-XR24-30DC Full current flows though the contact during make and break!
259836 70 71 72 RMQ series contact elements can be used for the NZM2(3,4)-XR… remote operators.
110 – 130 V DC NZM2-XR110-130DC 75
259840 74
N
220 – 250 V DC NZM2-XR220-250DC (L1–, L2)
259842
LZM3(-4) 110 – 130 V 50/60 Hz NZM3-XR110-130AC
259848 2-wire control
208 – 240 V 50/60 Hz NZM3-XR208-240AC L1 Terminal 75:
(L1+) 0 I
259850 S Operational readiness signal when the cover is closed, and not locked.
H1
380 – 440 V 50/60 Hz NZM3-XR380-440AC1) AC-15: 400 V; 2 A
259852 70 71 72 DC-13: 220 V; 0.2 A
24 – 30 V DC NZM3-XR24-30DC 75
259854 74
N
110 – 130 V DC NZM3-XR110-130DC (L1–, L2)
259858 Three-wire control with automatic reset to the 0 position after the switch has tripped
220 – 250 V DC NZM3-XR220-250DC L1
259860 (L1+)
0 I
LZM4(-4) 110 – 130 V 50/60 Hz NZM4-XR110-130AC HIA H1
266684
70 71 72
208 – 240 V 50/60 Hz NZM4-XR208-240AC 75
266685 74
N
380 – 440 V 50/60 Hz NZM4-XR380-440AC1) (L1–, L2)
266686
24 – 30 V DC NZM4-XR24-30DC Switching cycle:
266691 NZM2-XR
110 – 130 V DC NZM4-XR110-130DC 60 ms t>3s 60 ms
266693 r r r r
220 – 250 V DC NZM4-XR220-250DC OFF ON ON OFF OFF ON
266694
NZM3-XR
Shroud for 4th pole
80 ms t>3s 80 ms
Additional shroud for mounting the NZM2-XR... and NZM3-XR... on a 4-pole switch. r r r r
LZM2-4 NZM2-XAVPR 1 off OFF ON ON OFF OFF ON
266677
LZM3-4 NZM3-XAVPR 1 off NZM4-XR
266678 100 ms t>3s 100 ms
Clamp terminal springloaded clamp r r r r
OFF ON ON OFF OFF ON
Control circuit terminal springloaded terminals
NZM...-XR... NZM-XRC 1 off The time interval between OFF and ON is 3 seconds.
266696
On commands received during the time interval are ignored within the first 3 seconds after switch off.

Protective cover for door cutout


Transparent protective shroud to increase the degree of protection to IP54
– RTR-NZM10 1 off Electrical remote switching and manual tripping (push to trip) are still possible.
034825
66 Ordering Ordering 67
Insulated enclosures Insulated enclosures
NZM...-XCI... Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB NZM...-XCI...

Max. rated For use with Part no. Price Std. pack Insulated enclosure Retrofit terminals with 3-pole switches: for 4th and 5th (if Notes
uninterrupted Article no. when ordered see price list description required) conductor (N, PE-conductor), with 4-pole
current separately switches: for 5th conductor (PE conductor)
Iu
A

Insulated enclosures
Circuit-breakers

Circuit-breakers
With door coupling rotary handle
Complete incl. all necessary functional parts
Degree of protection IP65
not UL/CSA approved
Standard, black/grey
Lockable on the 0 position on the handle F 63 A NZM1 NZM1-XCI23-TVD 1 off CI23-150 K10/1, K25/1 Suitable for installation of circuit-breakers and switch-disconnectorsEnclosure
using up to 3 padlocks. Additionally with 271522 for separate mounting with top and bottom cable entry.
cover interlock. F 125 A NZM1(-4) NZM1-XCI43-TVD CI43-150 K10/1, K25/1, K50/1, K95/1N/BR Include fixing straps for wall mounting.
271523 Short-circuit resistance at 415 V 50/60 Hz to 10 kA.
F 160 A NZM1(-4) NZM1-XCI43/2-TVD CI43-200 K10/1, K25/1, K50/1, K95/1N/BR Cannot be used in combination with NZM…-XR… remote operator…,
104645 NZM…-XSV plug-in unit or NZM…-XAV withdrawable unit.
F 200 A NZM2(-4) NZM2-XCI43-TVD CI43-200 K10/1, K25/1, K50/1, K95/1N/BR, K150/1/BR, K240/1/BR Insulated additional terminal for 4th or 5th pole should be ordered separately.
271524
F 250 A NZM2(-4) NZM2-XCI45-TVD CI45-200 K10/1, K25/1, K50/1, K95/1N/BR, K150/1/BR, K240/1/BR CI23 enclosure with flanges
280418 CI43, CI45 and CI48 feature gland plates.
F 400 A NZM3(-4) NZM3-XCI48-TVD CI48-250 K95/1N/BR, K150/1/BR, K240/1/BR, K2X240/1/BR Only for switches with tunnel clamps for direct connection of cables.
271525
Red-yellow for Emergency-Stop
Lockable on the handle and on the switch F 63 A NZM1 NZM1-XCI23-TVDVR 1 off CI23-150 K10/1, K25/1
using up to 3 padlocks each. Lockable in 271527
0 position on handle. Cover interlock as F 125 A NZM1(-4) NZM1-XCI43-TVDVR CI43-150 K10/1, K25/1, K50/1, K95/1N/BR
additional feature, locking facility on 271528
circuit-breaker in 0 position.
F 160 A NZM1(-4) NZM1-XCI43/2-TVDVR CI43-200 K10/1, K25/1, K50/1, K95/1N/BR
104646
F 200 A NZM2(-4) NZM2-XCI43-TVDVR CI43-200 K10/1, K25/1, K50/1, K95/1N/BR, K150/1/BR, K240/1/BR
271529
F 250 A NZM2(-4) NZM2-XCI45-TVDVR CI45-200 K10/1, K25/1, K50/1, K95/1N/BR, K150/1/BR, K240/1/BR
279356
F 400 A NZM3(-4) NZM3-XCI48-TVDVR CI48-250 K95/1N/BR, K150/1/BR, K240/1/BR, K2X240/1/BR
271530

Rated Terminal capacities Part no. Price Std. pack


uninterrupted Article no. when ordered see price list
current separately
Iu
A mm2

Additional insulated terminals


For looping through the neutral and protective conductor
1-pole
32 Flexible, 1 x (1.5 – 6) K10/1 10 off
093827
63 Flexible, 1 x (6 – 16), stranded, 1 x (16 – 25 ) K25/1
096200
100 Flexible, 1 x (10 – 35), stranded, 1 x (16 – 50) K50/1
098573
160 Stranded, 1 x (16 – 95) K95/1N/BR 1 off
012336
250 Stranded, 1 x (35 – 150), 2 x (16 – 70) K150/1/BR
014709
400 Stranded, 1 x (50 – 240), 2 x (25 – 120) K240/1/BR
017082
630 Stranded, 1 x (240 – 300), 2 x (50 – 240) K2X240/1/BR
019455
68 Ordering
Residual-current release frequency response
NZM...XFI... Moeller SK1230-1176GB http://catalog.moeller.net

For use with Part no. Price Std. Notes


Order number for see price pack
separate orders list

Earth-fault release
Suitable for use in three- and single-phase systems
Pulse current sensitive according to core-balance principle
Circuit-breakers

For 3- and 4 pole LZM1(-4) circuit-breakers


dependant on mains power Ue = 200 … 415 V 50/60 Hz,
Rated fault current NZM1 3 pole NZM1-XFI30R 1 off IEC/EN 60947-2
IDn = 0.03 A 104603 With Idn = 0.03 A: delay time tv always
NZM1-4 4 pole NZM1-4-XFI30R fixed settings at 10 ms.
104606 Alarm message > 30 % Idn via yellow
LED.
Rated fault current NZM1 3 pole NZM1-XFI300R Trip indication max. 2 auxiliary contacts
IDn = 0.3 A 104604 (HIAFI) can be fitted by user: N/O =
NZM1-4 4 pole NZM1-4-XFI300R M22-K01, N/C = M22-K10 are reset via
104607 the reset toggle lever.
Rated fault current NZM1 3 pole NZM1-XFIR If the trip-indicating auxiliary contact in
IDn = 0.03 – 0.1 – 0.3 – 0.5 – 1 – 3 A, 104605 the fault current block is used, the N/C
delay time contacts operates as a N/O contact and
NZM1-4 4 pole NZM1-4-XFIR the N/C contact operates as an N/O
tv = 10 – 60 – 150 – 300 – 450 ms. 104608 contact (see HIAFI marking).
Not in combination with insulated
Bottom mounting up to 100 A enclosure or main switch assembly kit
Rated fault current NZM1 3 pole NZM1-XFI30U1) for side panel mounting with mounting
IDn = 0.03 A 104609 bracket
NZM1-4 4 pole NZM1-4-XFI30U NZM1-XFI…U not in combination with
104612 shunt or undervoltage relase.
Rated ultimate short-circuit breaking
Rated fault current NZM1 3 pole NZM1-XFI300U capacity is determined by the fitted
IDn = 0.3 A 104610 LZM1.
NZM1-4 4 pole NZM1-4-XFI300U
104613
Rated fault current NZM1 3 pole NZM1-XFIU
IDn = 0.03 – 0.1 – 0.3 – 0.5 – 1 – 3 A, 104611
delay time NZM1-4 4 pole NZM1-4-XFIU
tv = 10 – 60 – 150 – 300 – 450 ms. 104614
Pulse current sensitive according to core-balance principle

For 4 pole circuit-breaker LZM2-4 IEC/EN 60947-2


independent of mains voltage Ue = 280 – 690 V 50/60 Hz Auxiliary contacts (1 N/O, 1N/C
bottom mounting up to 250 A integrated) are reset via the reset
Rated fault current NZM2-4 4 pole NZM2-4-XFI30 1 off button.
IDn = 0.03 A 292343 Not in combination with plug-in units,
insulated enclosure or main switch
Rated fault current NZM2-4 4 pole NZM2-4-XFI 1 off assembly kit for side panel mounting
IDn 0.1 - 0.3 - 1 - 3 A, 292344 with mounting bracket.
delay time Rated ultimate short-circuit breaking
tv = 60 - 150 - 300 - 450 ms capacity is determined by the fitted
LZM2.
Core-balance principle with AC/DC current sensitivity (in
range 0 – 100 kHz)

For 4 pole LZM2-4 circuit-breakers IEC/EN 60947-2


internal power supply Ue = 50 … 400 V, Observe response threshold
bottom mounting up to 250 A dependence on frequency!
Rated fault current NZM2-4 4 pole NZM2-4-XFIA30 1 off See “Frequency response”
IDn = 0.03 A 292345 characteristic curve
Auxiliary contacts (1 N/O, 1N/C
Rated fault current NZM2-4 4 pole NZM2-4-XFIA 1 off integrated) are reset via the reset
IDn 0.1 - 0.3 - 1 A, 292346 button.
delay time Not in combination with plug-in units,
tv = 60 - 150 - 300 - 450 ms insulated enclosure or main switch
assembly kit for side panel mounting
with mounting bracket.
Rated ultimate short-circuit breaking
capacity is determined by the fitted
LZM2.
Notes 1) Suitable for use in three-phase systems
Ordering 69
Residual-current release frequency response
http://catalog.moeller.net Moeller SK1230-1176GB NZM3, NZM4, PFR-...
For use with Part no. Price Std. pack Notes
Article no. when see price list
ordered with
basic unit

Earth-fault release, 3-pole, 4-pole


Not dependent on mains and control voltages LZM3 +NZM3-XT 1 off Only suitable for use in conjunction with
Ig = 0.35 – 0.4 – 0.5 – 0.6 – 0.7 – 0.8 – 0.9 – 1.0 x In 260756 circuit-breakers having electronic

Circuit-breakers
tg = 0 – 20 – 60 – 100 – 200 – 300 – 500 – 750 – 1000 ms LZM3-4 +NZM3-4-XT releases.
260757
LZM4 +NZM4-XT
266721
LZM4-4 +NZM4-4-XT
266722

Description Part no. Price Std. pack Notes


Article no. see price list

Residual current relay


Pulse-current sensitive
Rated control supply voltage: Us = 230 V AC (50/60Hz)
Integrated auxiliary contact (1 C/O)
Ring-type transformer must also be ordered
Rated fault current IdN = 0.03 A PFR-003 1 off
285555
Rated fault current IdN = 0.3 A PFR-03
285556
Rated fault current IdN = 0.03 – 5 A PFR-5 Adjustable fault current: 0.03, 0.1, 0.3,
Adjustable fault current and delay time 285557 0.5, 1, 3, 5 A
Fault current early warning by flashing, red LED Adjustable delay time: 0.02, 0.1, 0.3, 0.5,
1, 3, 5 A

Ring-type transformer
Rated operational voltage: 690 V (50/60 Hz)
Internal diameter: 20 mm PFR-W-20 1 off incl. fixing clip for DIN rail mounting
285558
Internal diameter: 30 mm PFR-W-30
285559

Internal diameter: 35 mm PFR-W-35 incl. screw fixing


285600 Alternative: fixing clip for DIN mounting
Internal diameter: 70 mm PFR-W-70 rail
285601 Design note:
Internal diameter: 105 mm PFR-W-105 The current transformer diameter must
285602 be selected 1.5 times larger than the
envelope diameter of the passed through
Internal diameter: 140 mm PFR-W-140 conductor.
285603
Internal diameter: 210 mm PFR-W-210
285604
Magnetic shielding
PFR-W-35 PFR-WMA-35 1 off Necessary for a load circuit with high
286001 inrush currents > 4 x In, such as for
example motors and
PFR-W-70 PFR-WMA-70
286002
PFR-W-105 PFR-WMA-105
286003
PFR-W-140 PFR-WMA-140
286004
PFR-W-210 PFR-WMA-210
286005
Fixing clip
for the DIN rail mounting of the PFR-W-35 PFR-WC 1 off 1 set = 2 pieces
current transformer and all larger 286006
70 Engineering Engineering 71
Selectivity: incoming circuit-breaker, outgoing circuit-breaker Selectivity: incoming circuit-breaker, outgoing circuit-breaker
LZM, FAZ-B(C), PKZ Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM, FAZ-B(C), PKZ
Selectivity 415 V AC
Incoming between circuit-breakers enables separate shut-down of faulty system sections.
1 circuit-breaker
Selectivity (discrimination) exists between incoming breaker 1 and outgoing breaker 2 if,
2 3 4 Outgoing only outgoing breaker 2 trips at position 2 during a short-circuit.
circuit-breaker System sections 3 and 4 continue to operate.
Incoming circuit-breaker (S1) Incoming circuit-breaker (S1)
LZM...1-A... LZM...2-A... LZM...2-A... LZM...3-AE... LZM...3-VE... LZM...4-AE... LZM...4-VE...
Circuit-breakers

Circuit-breakers
Icu [kA] 25(36)(50)(70) 25(36)(50)(70) 25(36)(50)(70) 50(70) 50(70) 50(70) 50(70)
In [A] 20...40 50 63 80 100 125 160 20...40 50 63 80 100 125 160 200 250 300 400 630 400 630 800 1000 1250 1600 800 1000 1250 1600
Outgoing circuit- In Icu(415V) Selectivity threshold Is [kA] for selectivity between S2 and S1, overload and short-circuit release set to max. value Selectivity threshold Is [kA] for selectivity between S2 and S1, overload and short-circuit release set to max. value
breaker (S2) [A] [kA]
FAZ–B(C) 0.5 15 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1 15 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
2 15 2 T T T T T T 3 T T T T T T T T T T T T T T T T T T T T T
3 15 1.2 2 3 3 10 T T 1.5 1.5 3 5 T T T T T T T T T T T T T T T T T T
4 15 1.2 2 3 3 8 T T 1.2 1.5 3 4 T T T T T T T T T T T T T T T T T T
6 15 1.2 2 2.5 3 5 10 10 1.2 1.5 2.5 3 T T T T T T T T T T T T T T T T T T
10 15 1.2 1.5 2 2 4 10 10 1 1.5 2.5 3 10 10 10 10 10 10 T T T T T T T T T T T T
13 15 1 1.5 2 2 4 10 10 1 1.2 2 3 10 10 10 10 10 10 T T T T T T T T T T T T
16 15 1 1.2 1.5 2 3 8 8 1 1.2 1.5 2.5 10 10 10 10 10 10 T T T T T T T T T T T T
20 15 0.8 1.2 1.5 1.5 3 8 8 1 1.2 1.5 2.5 10 10 10 10 10 10 T T T T T T T T T T T T
25 15 0.7 1.2 1.5 1.5 3 7 7 0.8 1 1.5 2 10 10 10 10 10 10 T T T T T T T T T T T T
32 15 – 1.2 1 1.5 2 6 6 – 1 1.5 2 8 8 8 8 10 10 T T T T T T T T T T T T
40 15 – – 1 1.5 2 5 5 – – 1.2 1.5 7 7 7 7 10 10 T T T T T T T T T T T T
50 15 – – – 1.2 1.5 4 4 – – – 1.5 6 6 6 6 10 10 T T T T T T T T T T T T
63 15 – – – – 1.5 3 3 – – – – 6 6 6 6 10 10 T T T T T T T T T T T T
PKZM0-... 0.16 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
0.25 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
0.4 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
0.63 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1.6 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
2.5 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
4 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
6.3 100 4 5 5 T T T T 2 3 4 5 T T T T T T T T T T T T T T T T T T
10 100 3 4 5 6 25 T T 1.5 2.5 4 4 T T T T T T T T T T T T T T T T T T
12 50 3 4 5 6 25 T T 1.5 2.5 4 4 T T T T T T T T T T T T T T T T T T
16 50 1.5 1.5 2 3 5 7 T 1 1.6 2 2.5 T T T T T T T T T T T T T T T T T T
20 50 0.8 1.5 1.5 2 3 5 T 0.8 1.2 1.5 2 T T T T T T T T T T T T T T T T T T
25 50 – 1 1.5 1.5 2.5 4 T – 1 1.5 2 10 T T T T T T T T T T T T T T T T T
32 50 – – 1 1 2 3.5 T – – 1 1.5 8 40 T T T T T T T T T T T T T T T T
PKZ2/ZM-... 0.6 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1.0 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
1.6 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
2.4 100 1.2 2 2.5 10 T T T 1.2 2 2.5 10 T T T T T T T T T T T T T T T T T T
4 100 1 1.5 2 2.5 2.5 4 10 1 1.5 2 2.5 2.5 10 10 10 T T T T T T T T T T T T T T
6 100 0.6 0.8 1 1.2 2 3 8 0.6 0.8 1 1.2 2 8 8 8 10 10 T T T T T T T T T T T T
10 100 0.5 0.7 0.8 1 1.2 2 4 0.5 0.7 0.8 1 1.2 4 4 4 5 5 13 T 13 T T T T T T T T T
16 100 0.5 0.6 0.7 0.8 1.2 1.5 3 0.5 0.6 0.7 0.8 1.2 3 3 3 4 4 7 T 7 T T T T T T T T T
25 30 – 0.6 0.7 0.7 1.2 1.5 2 – 0.6 0.7 0.7 1.2 2 2 2 3 3 5 20 5 20 T T T T T T T T
32 30 – – 0.6 0.7 1.2 1.5 2 – – 0.6 0.7 1.2 2 2 2 3 3 3.5 15 3.5 15 T T T T T T T T
40 30 – – 0.6 0.7 1 1.5 2 – – 0.6 0.7 1 2 2 2 2 2 3.5 15 3.5 15 T T T T T T T T
PKZM4 16 100 0.5 0.8 0.8 0.8 2 5 5 0.5 0.8 0.8 0.8 2 5 5 5 5 5 16 45 16 45 T T T T T T T T
25 100 – 0.7 0.8 0.8 1.5 5 5 – 0.7 0.8 0.8 1.5 5 5 5 5 5 10 25 10 25 42 T T T 42 T T T
32 50 – – 0.8 0.8 1.5 4 4 – – 0.8 0.8 1.5 4 4 4 4 4 8 18 8 18 30 45 T T 30 45 T T
40 50 – – – 0.8 1.5 3 3 – – – 0.8 1.5 3 3 3 3 3 8 18 8 18 30 45 T T 30 45 T T
50 50 – – – – 1 2.5 2.5 – – – – 1 2.5 2.5 2.5 2.5 2.5 8 18 8 18 30 45 T T 30 45 T T
58 50 – – – – – 2.5 2.5 – – – – – 2.5 2.5 2.5 2.5 2.5 6.5 15 6.5 15 25 40 T T 25 40 T T
63 50 – – – – – 2 2 – – – – – 2 2 2 2 2 6.5 15 6.5 15 25 40 T T 25 40 T T
Notes T: full selectivity
72 Engineering Engineering 73
Selectivity: incoming circuit-breaker, outgoing circuit-breaker Selectivity: incoming circuit-breaker, outgoing circuit-breaker
LZM Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM
Selectivity 415 V AC
Incoming between circuit-breakers enables separate shut-down of faulty system sections.
1 circuit-breaker Selectivity (discrimination) exists between incoming breaker 1 and outgoing breaker 2 if,
only outgoing breaker 2 trips at position 2 during a short-circuit.
2 3 4 Outgoing System sections 3 and 4 continue to be operational.
circuit-breaker
Incoming circuit-breaker (S1) Incoming circuit-breaker (S1)
LZM...1-A... LZM...2-A... LZM...2-A... LZM...3-AE... LZM...3-VE... LZM...4-AE... LZM...4-VE...
Circuit-breakers

Circuit-breakers
Icu[kA] 25(36)(50)(70) 25(36)(50)(70) 25(36)(50)(70) 50(70) 50(70) 50(70) 50(70)
In[A] 20...40 50 63 80 100 125 160 20...40 50 63 80 100 125 160 200 250 300 400 630 400 630 800 1000 1250 1600 800 1000 1250 1600
Outgoing circuit- In Icu(415V) Prospective short-circuit current (kA). Set the overload and short-circuit release of the incoming Prospective short-circuit current (kA). Set the overload and short-circuit release of the incoming circuit-breaker to the max. value.
breaker (S2) [A] [kA] circuit-breaker to the max. value.
LZM...1-A... 20...40 25...100 – – 0.5 0.7 0.8 1.5 1.5 – – 0.6 0.8 1.5 1.5 1.5 2 3 3 20 20 25 25 T T T T T T T T
50 25...100 – – – 0.6 0.8 1.5 1.5 – – – 0.8 1.5 1.5 1.5 2 3 3 20 20 25 25 T T T T T T T T
63 25...100 – – – – 0.8 1.5 1.5 – – – – 1.5 1.5 1.5 2 3 3 15 15 20 20 T T T T T T T T
80 25...100 – – – – – 1.5 1.5 – – – – – 1.5 1.5 2 3 3 15 15 20 20 T T T T T T T T
100 25...100 – – – – – – 1.5 – – – – – – 1.5 2 3 3 15 15 20 20 T T T T T T T T
125 25...100 – – – – – – – – – – – – – – 2 3 3 15 15 20 20 T T T T T T T T
160 25...100 – – – – – – – – – – – – – – 2 3 3 15 15 20 20 T T T T T T T T
LZM...2-A... 20...40 25...150 – – 0.5 0.6 0.8 1 1 – – 0.5 0.6 0.8 1 1.2 1.6 2 2 15 15 20 20 T T T T T T T T
50 25...150 – – – 0.6 0.8 1 1 – – – 0.6 0.8 1 1.2 1.6 2 2 15 15 20 20 T T T T T T T T
63 25...150 – – – – 0.8 1 1 – – – – 0.8 1 1.2 1.6 2 2 15 15 20 20 T T T T T T T T
80 25...150 – – – – – 1 1 – – – – – 1 1.2 1.6 2 2 15 15 20 20 T T T T T T T T
100 25...150 – – – – – – 1 – – – – – – 1.2 1.6 2 2 15 15 20 20 T T T T T T T T
125 25...150 – – – – – – – – – – – – – – 1.6 2 2 15 15 20 20 T T T T T T T T
160 25...150 – – – – – – – – – – – – – – – 2 2 10 10 15 15 T T T T T T T T
200 25...150 – – – – – – – – – – – – – – – – – 10 10 15 15 T T T T T T T T
250 25...150 – – – – – – – – – – – – – – – – – 10 10 15 15 T T T T T T T T
LZM...2-VE... 100 50...150 – – – – – – – – – – – – – 1.2 1.6 2 2 7 10 8 11 20 50 T T 20 50 T T
160 50...150 – – – – – – – – – – – – – – – – – 7 10 8 11 20 50 T T 20 50 T T
250 50...150 – – – – – – – – – – – – – – – – – 7 10 8 11 20 50 T T 20 50 T T
LZM...3-AE... 250 50...150 – – – – – – – – – – – – – – – – – 5 7.5 10 12 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80
400 50...150 – – – – – – – – – – – – – – – – – – 7.5 – 12 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80
630 50...150 – – – – – – – – – – – – – – – – – – – – – T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80
LZM...3-VE... 250 50...150 – – – – – – – – – – – – – – – – – 3.5 4 10 12 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80
400 50...150 – – – – – – – – – – – – – – – – – – 4 – 12 T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80
630 50...150 – – – – – – – – – – – – – – – – – – – – – T/80 T/80 T/80 T/80 T/80 T/80 T/80 T/80
LZM...4-AE... 630 50...100 – – – – – – – – – – – – – – – – – – – – – 10 15 20 20 10 15 20 20
800 50...100 – – – – – – – – – – – – – – – – – – – – – – – 20 20 – – 20 20
1000 50...100 – – – – – – – – – – – – – – – – – – – – – – – 20 20 – – 20 20
1250 50...100 – – – – – – – – – – – – – – – – – – – – – – – – 20 – – – 20
1600 50...100 – – – – – – – – – – – – – – – – – – – – – – – – – – – – –
LZM...4-VE... 630 50...100 – – – – – – – – – – – – – – – – – – – – – 10 15 20 20 10 15 20 20
800 50...100 – – – – – – – – – – – – – – – – – – – – – – – 20 20 – – 20 20
1000 50...100 – – – – – – – – – – – – – – – – – – – – – – – 20 20 – – 20 20
1250 50...100 – – – – – – – – – – – – – – – – – – – – – – – – 20 – – – 20
1600 50...100 – – – – – – – – – – – – – – – – – – – – – – – – – – – – –
Notes T: total selectivity
74 Engineering
MCB, back-up protection
LZM1, LZM2, LZM3 Moeller SK1230-1176GB http://catalog.moeller.net
Protection of PVC insulated cables against thermal overload with short-circuits
According to VDE 0100 part 430 cables and Short-circuit protection is provided by adjustable The tables indicate the minimum conductor cross-
conductors must be protected against short-circuit instantaneous releases, which open the main contacts section reliably protected by circuit-breakers during a
and overload. The overload protection is obtained by in less than 25 ms. The short-circuit total opening short-circuit. (Operating voltage UN = 415 V)
using LZM circuit-breakers with settable, current- time restricts the temperature rise of the cable to a
dependent, delayed overload release. minimum.

Min. protected cross-section mm2 copper


Circuit-breakers

LZM...1(-4)-...20 6
LZM...1(-4)-...25 … 160 10
LZM...2(-4)-...20 … 300 10
LZM...3(-4)-...250 … 630 16
LZM...4(-4)-...630 … 1600 95

Back-up protection
between LZM(N)(S) incoming circuit-breaker and LZMB(C)(N)(S) outgoing circuit-breaker
Incoming circuit-breaker a
LZM1 LZM2 LZM3
In up to 160 A up to 300 A up to 630 A
Icu(415 V) 25 kA 36 kA 50 kA 70 kA 25 kA 36 kA 50 kA 70 kA 50 kA 70 kA
a Outgoing circuit-breaker b
Icu(415 V) In
LZMB1 25 kA up to 160 A 25 36 50 70 25 36 50 70 50 70
LZMC1 36 kA up to 160 A – 36 50 70 36 50 70 50 70
b LZMN1 50 kA up to 160 A – – 50 70 – – 50 70 50 70
LZMS1 70 kA up to 160 A – – – 70 – – – 70 – 70
LZMB2 25 kA up to 300 A 25 36 50 70 25 36 50 70 50 70
LZMC2 36 kA up to 300 A – 36 50 70 – 36 50 70 50 70
LZMN2 50 kA up to 300 A – – 50 70 – – 50 70 50 70
LZMS2 70 kA up to 300 A – – – – – – – 70 – 70
LZMN3 50 kA up to 630 A – – – – – – – – 50 70
LZMS3 70 kA up to 630 A – – – – – – – – – 70

Where the prospective fault current at the point of The table shows which current-limiting circuit-breaker The selectivity limit is determined by the response
installation of circuit-breakers is very high, it is LZMN(S) in combination with LZMB(C)(N) are to be current of the non-delayed short-circuit release in the
conventional to use LZMN(S) current-limiting circuit- used to provide protection at the network locations upstream incoming circuit-breaker. In many
breakers. An attractively priced alternative is to fit a with high short-circuit capacities. applications this is sufficient.
LZMN(S) current-limiting circuit-breaker upstream of
LZMB(C)(N) standard circuit-breakers, if the fault level is
too high for LZMB(C)(N) switches.

between LZM...1-A... incoming circuit-breaker and FAZ-B(C)/PLSM-B(C)... outgoing circuit-breaker


Icc Outgoing circuit- Outgoing circuit-breaker
breaker LZM(B)(C)2-A... LZMC(N)(S)1-A...
LZM...
FAZ-B(C)...
PLSM 0,5 – 16 25 kA 30 kA
20 – 40 20 kA 20 kA
50, 63 15 kA 15 kA
PLSM-B(C)...(/...)
0,5 – 16 25 kA 30 kA
20 – 40 20 kA 20 kA
50, 63 15 kA 15 kA

between LZM...2-A... incoming circuit-breaker and FAZ-B(C)/PLSM-B(C)... outgoing circuit-breaker


Icc Outgoing circuit- Incoming circuit-breaker
breaker LZMB(C)2-A... LZMN(S)2-A...
LZM...
FAZ-B(C)...
PLSM 0,5 – 10 25 kA 50 kA
13 – 32 25 kA 30 kA
40 – 63 20 kA 20 kA
PLSM-B(C)...(/...)
0,5 – 10 25 kA 50 kA
13 – 32 25 kA 30 kA
40 – 63 20 kA 20 kA
Engineering 75
Direction of blow-out, minimum clearances, tube cable lugs
http://catalog.moeller.net Moeller SK1230-1176GB LZM1, LZM2, LZM3, LZM4
Direction of blow-out
Top, front Bottom,
rear
LZM1 X –
LZM21) X X
LZM3 X X
LZM4 X –

Circuit-breakers
1) LZM2B(C) – A … as LZM1

Minimum clearances
between two adjacently mounted switches
Minimum clearance a in mm
c

LZM1 LZM2 LZM3 LZM4


LZM1 0 5 5 15
LZM2 5 5 5 15
LZM3 5 5 5 15
d

LZM4 15 15 15 15
b a b
between switch and other parts
Minimum clearances in mm
b c d
F 690 V 1000 V F 690 V 1000 V F 690 V 1000 V
LZM1 0 – 60 – 0 –
LZM21) 5 5 35 35 35 35
LZM3 5 5 60 60 60 60
LZM4 15 15 100 200 0 0

1) LZM2B(C) – A … C= 60 mm, d = 0 mm

Dimensions
For pressing the cable lugs a press tool K22, HK60/22 or EK22
from the company Klauke is necessary with the following press inserts:
R22/95 for 95 mm2
h

R22/120 for 120 mm2


R22/150 for 150 mm2
i

R22/185 for 185 mm2


g
R22/240 for 240 mm2

d e
b

c
f

Cable lug For use with Rated cross Terminal bolt Dimensions in mm
section
mm2 o a b c d e f g h i
KS95-NZM7 LZM2 95 M8 53+2 23g0.5 18g0.2 10g1 19 8,5 25 13,5 4,4
KS120-NZM7 LZM2 120 M8 56+2 23g0.5 19.5g0.2 10g1 19 8,5 26 15 4,4
KS150-NZM7 LZM2 150 M8 61+2 23g0.5 21g0.2 10g1 19 8,5 30 16,5 4,4
NZM2-XKS185 LZM2 185 M8 65g1.5 22g1 24g0.3 9+1
–0,5 19+2,5
–0,5 8.5+0,05
–0,1 30g2 19g0.4 7
NZM3-XKS185 LZM3, LZM4 185 M10 65 24,5 24 11,5 18 10,5 30 19 7.0g0.8
NZM3-XKS240 LZM3, LZM4 240 M10 72 31 26 11,5 19 10,5 35 21 5.0g0.8
76 Engineering
Auxiliary switches, trip-indicating auxiliary contacts
LZM1, LZM2, LZM3, LZM4 Moeller SK1230-1176GB http://catalog.moeller.net
Front cut-out
Cut-out a Cut-out b
toggle lever rotary handle,
remote operator
Circuit-breakers

Y Y

X X X

e
e

f f

c
d

Distance from mounting plate and Cut-out a Cut-out b


door cutout
c d e f e f
mm mm mm mm mm mm
LZM1 68 73 40 23 46 91
LZM2 103 108 79 36 96 101
LZM3 120.5 125.5 79 36 96 136
LZM4 138 146 101 105 118 204

Standard auxiliary contact Early-make auxiliary contact (HIV) Trip-indicating auxiliary


(HIN) contact (HIA)
I LZM 1, 2, 3 LZM 4 I
+ I I +
L1L2L3 + + L1L2L3
L1L2L3 L1L2L3
HIN HIA
HIV HIV
I I
+ I I +
L1L2L3 + + L1L2L3
L1L2L3 L1L2L3
HIN HIA
HIV HIV

+ I + I
+ + I + I +
L1L2L3 + + L1L2L3
L1L2L3 L1L2L3
HIN HIA
HIV HIV

0lI Switching on Q Contact closed


q Contact open
0mI Switching off

+mI Trip

Notes If early-make contacts are required in combination with shunt or undervoltage releases,
please select the combination type in the “Release” section.
Engineering 77
Mechanical interlock for (door-coupling) rotary handles
http://catalog.moeller.net Moeller SK1230-1176GB LZM, NZM…-XBZ-…

Interlocking variants and combination options


A B
OFF OFF
A B ON/TRIP ON

ON ON/TRIP

A B C

Circuit-breakers
OFF OFF OFF
A B C ON ON/TRIP ON

ON/TRIP ON ON/TRIP

A B C
OFF OFF OFF
ON/TRIP ON ON
A B C
ON ON/TRIP ON

ON ON ON/TRIP

A B C D
OFF OFF OFF OFF
ON/TRIP ON ON/TRIP ON
A B C D
ON ON/TRIP ON ON/TRIP

x4P x4P
= Switch clearance 3 pole
x3P x3P = Switch clearance 4 pole

NZM-XBZ225 right switch


max. switch clearance LZM1 LZM2 LZM3 LZM4
X3P X4P X3P X4P X3P X4P X3P X4P
left switch mm mm mm mm mm mm mm mm
LZM1 3/4 pole 135 105 120 85 135 90 125 80
LZM2 3/4 pole 135 105 120 85 135 90 125 80
LZM3 3/4 pole 90 75 75 35 85 40 80 45
LZM4 3/4 pole 50 35 40 15 25 – 15 –

NZM-XBZ600 right switch


max. switch clearance LZM1 LZM2 LZM3 LZM4
X3P X4P X3P X4P X3P X4P X3P X4P
left switch mm mm mm mm mm mm mm mm
LZM1 3/4 pole 510 480 495 460 510 465 475 405
LZM2 3/4 pole 510 480 495 460 510 465 475 405
LZM3 3/4 pole 460 430 450 410 460 415 460 390
LZM4 3/4 pole 400 370 380 340 400 375 390 320

NZM-XBZ1000 right switch


max. switch clearance LZM1 LZM2 LZM3 LZM4
X3P X4P X3P X4P X3P X4P X3P X4P
left switch mm mm mm mm mm mm mm mm
LZM1 3/4 pole 910 880 895 860 910 865 865 795
LZM2 3/4 pole 910 880 895 860 910 865 865 795
LZM3 3/4 pole 820 790 850 810 860 815 860 790
LZM4 3/4 pole 750 720 730 700 800 775 790 720
78 Engineering
Mechanical interlock for remote operator, residual-current relay
NZM…-XMVR(L) Moeller SK1230-1176GB http://catalog.moeller.net
XMVR mechanical interlock
(Mounting adjacent)
NZM...-XMVR
Max. switch clearance right switch
LZM2 LZM3 LZM4
X3p X4p X3p X4p X3p X4p
left switch mm mm mm mm mm mm
Circuit-breakers

LZM2 3/4 pole 130 95 95 50 – –


LZM3 3/4 pole – – 135 90 155 85
LZM4 3/4 pole – – – – 120 50

x4P

3P

X3p = max. switch clearance 3 pole


X4p = max. switch clearance 4 pole

XMVRL mechanical interlock


Mounting in adjacent enclosures
NZM...-XMVRL
Max. switch clearance right switch
LZM2 LZM3 LZM4
X3p X4p X3p X4p X3p X4p
left switch mm mm mm mm mm mm
LZM2 3/4 pole 350 315 420 385 – –
LZM3 3/4 pole – – 400 365 460 390
LZM4 3/4 pole – – – – 420 350

XMVRL mechanical interlock


(Mounting one above the other)
NZM…-XMVRL
Max. switch clearance Switch top
LZM2 LZM3 LZM4
3/4 pole 3/4 pole 3/4 pole
Y Y Y
Switch bottom mm mm mm
LZM2 3/4 pole 220 225 –
LZM3 3/4 pole – 220 230
LZM4 3/4 pole – – 230

Y = max. switch clearance

Ring-type transformer
Maximum rated current [A] Diameter
Power Motor/capacitor Transformer part Max. conductor
distribution no. circumference
PFR-W-… (mm)
d1 d2
50 50 20 13 d2
150 100 30 20 d1 f 1.5 x d2
150 100 35 23
400 200 70 47
600 250 105 70
1200 630 140 93
1800 800 210 140
Engineering 79
Sizes 1, 2: tripping characteristics
http://catalog.moeller.net Moeller SK1230-1176GB LZM1, LZM2
System and line protection with LZM1 Motor protection with LZM1
2.5 h 8000 LZM1(-4)-A... 2.5 h 8000 LZM1-S...
6000 6000
Tripping time [s]

4000

Tripping time [s]


4000

2000 2000

1000 1000
800 800
(10 min) 600 (10 min) 600
400 400

Circuit-breakers
200 200

100 100
80 80
(1 min) 60 (1 min) 60
40
Tolerance tr [s]

40

20 20
10 10
8 8
6 6
4 4

2 2
1 Setting range Setting range
1
0.8 0.8
0.6 0.6
0.4 0.4
Ii = 6 10x In Ii = 8 14x In
0.2 0.2
0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04

0.02 0.02
0.01 0.01
0.008 0.008
0.006 0.006
0.004 0.004

0.002 0.002

0.001 0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100 1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir x Ir

System and line protection with LZM2 Motor protection with LZM2
2.5 h 8000 LZM2(-4)-A... 2.5 h 8000
LZM2-S...
6000 6000
Tripping time [s]

4000 4000
Tripping time [s]

2000 2000

1000 1000
800 800
(10 min) 600 (10 min) 600
400 400

200 200

100 100
80 80
(1 min) 60 (1 min) 60
40 40
Tolerance tr [s]

20 20

10 10
8 8
6 6
4 4

2 2

1 Setting range 1 Setting range


0.8 0.8
0.6 0.6
0.4 0.4
Ii = 6 10x In Ii = 8 14x In
0.2 0.2

0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04

0.02 0.02

0.01 0.01
0.008 0.008
0.006 0.006
0.004 0.004

0.002 0.002

0.001 0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100 1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir x Ir
80 Engineering
Sizes 2, 3: tripping characteristics
LZM2, LZM3 Moeller SK1230-1176GB http://catalog.moeller.net
Systems, cable, selectivity and generator protection with LZM2

2.5 h 8000 LZM2(-4)-VE...


6000
Characteristics for Ir = 1,0 x In
Tripping time [s]

4000

2000

1000
800
(10 min) 600
Circuit-breakers

400

200

100
80
(1 min) 60
40
tr [s]
20 20
17
14
10 10
8 8
6 6
4 4

2 2
tsd [ms]
1 1000
0.8 750
0.6 500
0.4
300
200
0.2
100
0.1
0.08 60
0.06 20
0.04 Isd = 2 3 4 5 6 7 8 9 10 x Ir
0
0.02 Ii = 12 x In
0.01
0.008
0.006
0.004

0.002

0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir

System and line protection with LZM3 Systems, cable, selectivity and generator protection with LZM3

2.5 h 8000 2.5 h 8000 LZM3(-4)-VE...


LZM3(-4)-AE...
6000 6000
Characteristics for Ir = 1,0 x In 4000 Characteristics for Ir = 1,0 x In
Tripping time [s]

4000
Tripping time [s]

2000 2000

1000 1000
800 800
(10 min) 600 (10 min) 600
400 400

200 200

100 100
80 80
(1 min) 60 (1 min) 60
40 40
tr [s]
20 20
20 17
14
10 10 10
8 8 8
6 6 6
4 4 4

2 2 2
tsd [ms]
1 1 1000
0.8 0.8 750
0.6 0.6 500 without “I2t = constant” function
0.4 0.4 300
Ii = 2 2.5 3 3.5 4 5 6 7 8 x In 630 A 200
0.2 0.2 Isd = 1.5 2 2.5 3 3.5 4 5 6 7 x Ir 630 A
Ii = 2 3 4 5 6 7 8 9 11 x In 250 A, 400 A 100
0.1 0.1
0.08 60
0.08
0.06 0.06 20
0.04 0.04
0
0.02 Isd = 2 3 4 5 6 7 8 9 10 x Ir 250 A, 400 A
0.02

0.01 0.01
0.008 0.008
0.006 0.006 Ii = 2 2.5 3 3.5 4 5 6 7 8 x In 630 A
0.004 0.004
Ii = 2 3 4 5 6 7 8 9 11x In 250 A, 400 A
0.002 0.002

0.001 0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100 1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100

x Ir x Ir
Engineering 81
Sizes 3, 4: tripping characteristics
http://catalog.moeller.net Moeller SK1230-1176GB LZM3, LZM4
Systems, cable, selectivity and generator protection with LZM3 Systems, cable, selectivity and generator protection with NZM4

2.5 h 8000 2.5 h 8000


LZM3(-4)-VE... LZM4(-4)-VE...
6000 6000
Characteristics for Ir = 1,0 x In
Tripping time [s]

4000 Characteristics for Ir = 1,0 x In 4000

Tripping time [s]


2000 2000

1000 1000
800 800
(10 min) 600 (10 min) 600

Circuit-breakers
400 400

200 200

100 100
80 80
(1 min) 60 (1 min) 60
40 40
tr [s] tr [s]
20 20 20 20
17 17
14 14
10 10 10 10
8 8 8 8
6 6 6 6
4 4 4 4

2 2 2 2
1 1
0.8 0.8
0.6 0 0.6
00 I2t = constant 00
0 I2t = constant
0.4
......1 0.4 ...1
0.. .......
0.2 =
2
0.2 20..
s]
[m s] =
0.1 t sd 0.1 d
[m
0.08 ts
0.08
0.06 Isd = 1.5 2 2.5 3 3.54 5 6 7 x Ir 630 A 0.06
0.04 Isd = 2 3 4 5 6 7 8 910 x Ir 250 A, 400 A 0.04
Isd = 2 3 4 5 6 7 8 9 10 x Ir
0.02 0.02
0.01 0.01 Ii = 2 3 4 5 6 7 8 10 12 x In
0.008 0.008
0.006 0.006
Ii = 2 2.5 3 3.5 4 5 6 7 8 x In 630 A
0.004 0.004

0.002
Ii = 2 3 4 5 6 7 8 9 11 x In 250 A, 400 A
0.002

0.001 0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100 1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir x Ir

System and line protection with LZM4 Systems, cable, selectivity and generator protection with LZM4

2.5 h 8000 LZM4(-4)-AE... 2.5 h 8000 LZM4(-4)-VE...


6000 6000
4000 Characteristics for Ir = 1,0 x In 4000 Characteristics for Ir = 1,0 x In
Tripping time [s]

Tripping time [s]

2000 2000
1000 1000
800 800
(10 min) 600 (10 min) 600
400 400

200 200

100 100
80 80
(1 min) 60 (1 min) 60
40 40
tr [s]
20 20 20
17
14
10 10 10
8 8 8
6 6 6
4 4 4

2 2 2
tsd [ms]
1 1 1000
0.8 0.8 750
0.6 0.6 500
0.4 without “I2t = constant” function
0.4 300
200
0.2 0.2
100
0.1 Ii = 2 3 4 5 6 7 8 10 12x In 60
0.1
0.08 0.08 20
0.06 0.06 0
0.04 0.04

0.02 Isd = 2 3 4 5 6 7 8 9 10 x Ir
0.02
0.01 0.01 Ii = 2 3 4 5 6 7 8 10 12 x In
0.008 0.008
0.006 0.006
0.004 0.004

0.002 0.002

0.001 0.001
1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100 1 2 3 4 5 6 7 8 910 15 20 30 40 50 60 70 80 100
x Ir x Ir
82 Engineering
Frame size 1: let-through characteristics
LZM1 Moeller SK1230-1176GB http://catalog.moeller.net
Let-through current xD

ÎD 200 LZMB1(-4)-A(S)15...160 ÎD 200 LZMC1-A20...160


[kA] [kA]

100 100
80 80
60 60
c

c
Circuit-breakers

Ic

Ic
2x

2x
40 40

20 20
415 V
415 V+440 V 440 V
10 10
525 V
8 8
6 6
690 V
4 4
3 3

1 1
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

ÎD 200 LZMN1(-4)-A(S)15...160 ÎD 200 LZMS1(-4)-A20...160


[kA] [kA]

100 100
80 80
60 60

40 40
c
c

Ic
Ic

2x
2x

20 20

415 V 415 V
10 10
525 V 8 525 V
8
690 V 6 690 V
6

4 4
3 3

1 1
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]
Engineering 83
Frame size 2: let-through characteristics
http://catalog.moeller.net Moeller SK1230-1176GB LZM2
Let-through current xD

ÎD 200 LZMB2(-4)-A(S)1,6...300 ÎD 200 LZMC2-A160...300


[kA] [kA]

100 100
80 80
60 60
c

c
Ic

Circuit-breakers
Ic
2x

2x
40 40

440 V
20 NZMB2-A160...250 20

10 10
8 8 440 V
6 6

4 415 V+440 V 4
NZMB2(-4-A)-M20...250 525 V
3 NZMB2...-(C)NA 3 690 V

1 1
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

ÎD 200 LZMN2(-4)-A(S,VE)1,6...250 ÎD 200 LZMS2(-4)-A(M,VE)15...250


[kA] [kA]

100 100
80 80
60 60

40 40
c

c
Ic

Ic
2x

2x

20 20 415 V
415 V 525 V
525 V
690 V
10 10
8 8 690 V
6 6

4 4
3 3

1 1
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]
84 Engineering
Sizes 1, 3: let-through characteristics
LZM1, LZM3 Moeller SK1230-1176GB http://catalog.moeller.net
Let-through current xD

ÎD 200 LZMN3(-4)-AE(VE)400...630 ÎD 200 LZMS3(-4)-AE(VE)400...630


[kA] [kA]

100 100
80 80
60 60
525 V
Circuit-breakers

690 V
40 40

415 V

c
c

Ic
690 V
Ic

2x
2x

20 20
525 V

415 V
10 10
8 8
6 6

4 4
3 3

1 1
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

Let-through energy J

7 7
Zy 10 Zy 10
8 LZMB1(-4)-A(S)15...160 8 LZMC1-A20...160
[A2 s] 6 [A2 s] 6

4 4

a a 525 V
2 2
440 V

106 106
8 8
6 440 V 6 415 V
4 4

415 V 690 V
2 2

105 105
8 8
6 6
4 4

2 2

104 104
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

7 7
Zy 10 Zy 10
8 LZMN1(-4)-A(S)15...160 8 LZMS1(-4)-A20...160
[A2 s] 6 [A2 s] 6

4 4

a a
2 2

106 106
8 8
6 6
415 V 415 V
4 525 V 4
525 V
690 V 690 V
2 2

105 105
8 8
6 6
4 4

2 2

104 104
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

a 1 half-cycle a 1 half-cycle
Engineering 85
Sizes 2, 3: let-through characteristics
http://catalog.moeller.net Moeller SK1230-1176GB LZM2, LZM3
Let-through energy J

7 7
Zy 10 Zy 10
8 LZMB2(-4)-A(S)15...250 8 LZMC2-A160...250
[A2 s] 6 [A2 s] 6

4 4
440 V
a LZMB2-A160...250 a 525 V
2 2

Circuit-breakers
106 106
8 8
6 6
440 V
4 4

690 V
2 2
415 V+440 V
LZMB2(-4-A)S20...250
105 105
8 8
6 6
4 4

2 2

104 104
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

7 7
Zy 10 Zy 10
2
8 LZMN2(-4)-A(S)15...250 2
8 LZMS2(-4)-A(S,VE)15...250
[A s] 6 [A s] 6

4 4

a a
2 2

106 106
8 8
6 6
4 415 V 4 415 V
525 V 525 V
2 2
690 V 690 V

105 105
8 8
6 6
4 4

2 2

104 104
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

a 1 half-cycle

7 7
Zy 10 Zy 10
8 LZMN3(-4)-AE(VE)400...630 8 LZMS3(-4)-AE(VE)400...630
[A2 s] 6 [A2 s]
6
4 4

a a
2 2
690 V

106 690 V
525 V 106
8 8
6 6
525 V
415 V
4 4
415 V
2 2

105 105
8 8
6 6
4 4

2 2

104 104
1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150 1 2 3 4 5 6 8 10 15 20 30 40 5060 80100 150
Icc rms [kA] Icc rms [kA]

a 1 half-cycle a 1 half-cycle
86 Engineering
Frame size 2: residual-current release frequency response
NZM2-4-XFIA Moeller SK1230-1176GB http://catalog.moeller.net
Frequency response
NZM2-4-XFIA30 NZM2-4-XFIA
30 mA 100 mA
IDn 10000 IDn 10000
[mA] [mA]
Circuit-breakers

1000 1000

100 100

10 10
1 10 100 1000 10000 100000 1 10 100 1000 10000 100000
f [Hz] f [Hz]

NZM2-4-XFIA
300 mA 1000 mA
IDn 10000 IDn 100000
[mA] [mA]

1000 10000

100 1000

10 100
1 10 100 1000 10000 100000 1 10 100 1000 10000 100000
f [Hz] f [Hz]
Notes 87

http://catalog.moeller.net Moeller SK1230-1176GB

Circuit-breakers
88 Technical data Technical data 89
Circuit-breakers Circuit-breakers
LZM…1, LZM…2, LZM…3, LZM…4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM…1, LZM…2, LZM…3, LZM…4
Rated uninterrupted current Rated uninterrupted current Rated uninterrupted current Rated uninterrupted current
max. 160 A max. 250 A max. 630 A max. 1600 A
LZMB1 LZMC1 LZMN1 LZMS1 LZMB2 LZMC2 LZMN2 LZMS2 LZMC3 LZMN3 LZMS3 LZMN4 LZMS4

General
Standards IEC/EN 60947, CCC IEC/EN 60947, CCC
Protection against direct contact Finger and back of hand proof to VDE 0106 Part 100 Finger and back of hand proof to VDE 0106 Part 100
Circuit-breakers

Circuit-breakers
Climatic proofing Damp heat, constant, according to IEC 60068-2-78 Damp heat, constant, according to IEC 60068-2-78
Damp heat, cyclical to IEC 60068-2-30 Damp heat, cyclical to IEC 60068-2-30
Ambient temperature
Storage °C –25…+70 –25…+70
Operation °C –25…+70 –25…+70
Mechanical shock resistance (IEC/EN 60068-2-27) 20 (half-sinusoidal shock 20 ms) 20 (half-sinusoidal shock 20 ms) NZM4: (half-sinusoidal shock 11 ms)
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between auxiliary contacts and main contacts V AC 500 500
between the auxiliary contacts V AC 300 300
Mounting position Vertical and 90° in all directions Vertical and 90° in all directions
With residual-current release With plug-in adapter LZM2: with residual current release, LZM2: vertical and 90°
LZM1: Vertical and 90° in all direc- vertical, 90° right/left to all directions
tions
90˚ 90˚ With withdrawable unit, LZM3: vertical, 90°
left, LZM4: vertical, with remote operator:
LZM2, LZM3, LZM4: vertical and 90° to all
90˚ 90˚ directions
90˚ 90˚
90˚ 90˚
Direction of incoming supply As required As required
Degree of protection
Device In the operating controls area: IP20 (basic degree of protection) In the operating controls area: IP20 (basic degree of protection)
Enclosures With insulating surround: IP40, with door coupling rotary handle: IP66 With insulating surround: IP40, with door coupling rotary handle: IP66

Terminals Tunnel terminal: IP10 Tunnel terminal: IP10


Phase isolator and strip terminal: IP00 Phase isolator and strip terminal: IP00
Circuit-breakers
Rated impulse withstand voltage Uimp
Main contacts V 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000
Auxiliary contacts V 6000 6000 6000 6000 6000 6000 6000 6000 6000 6000 6000 6000 6000
Rated operational voltage Ue V AC 690 690 690 690 440 690 690 690 690 690 690 690 690
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage Ui V 690 690 690 690 690 690 1000 1000 690 1000 1000 1000 1000
For use in IT electrical power networks V 440 690 690 690 440 690 690 690 690 690 690 525 525
90 Technical data Technical data 91
Circuit-breakers Circuit-breakers
LZM…1, LZM…2, LZM…3, LZM…4 Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM…1, LZM…2, LZM…3, LZM…4
Rated uninterrupted current max. 160 A Rated uninterrupted current max. 300 A Rated uninterrupted current max. 630 A Rated uninterrupted current max. 1600 A
LZMB1 LZMC1 LZMN1 LZMS1 LZMB2 LZMC2 LZMN2 LZMS2 LZMC3 LZMN3 LZMS3 LZMN4 LZMS4
Switching capacity
Rated short-circuit making capacity
240 V Icm kA 63 121 187 220 63 121 187 220 121 187 220 105 275
400/415 V Icm kA 53 76 105 220 53 76 105 154 76 105 154 105 187
440 V Icm kA 53 63 74 74 53 63 74 143 63 74 143 74 187
Circuit-breakers

Circuit-breakers
525 V Icm kA – 24 40 40 – 24 53 76 24 53 76 53 143
690 V Icm kA – 14 17 17 – 9 40 53 14 40 53 40 105
Rated short-circuit breaking capacity Icn
Icu to IEC/EN 60947 operating sequence O-t- 240 V 50/60 Hz Icu kA 30 55 85 100 30 55 85 100 55 85 100 50 125
CO 400/415 V 50/60 Hz Icu kA 25 36 50 100 25 36 50 70 36 50 70 50 85
440 V 50/60 Hz Icu kA 25 30 35 35 25 30 35 65 30 35 65 35 85
525 V 50/60 Hz Icu kA – 12 20 20 – 12 25 35 12 25 35 25 65
690 V 50/60 Hz Icu kA – 8 10 10 – 8 20 20 8 20 25 20 50
Icu to IEC/EN 60947 operating sequence O-t- 240 V 50/60 Hz Ics kA 30 55 85 100 30 55 85 100 55 85 100 50 125
CO-t-CO 400/415 V 50/60 Hz Ics kA 25 36 50 50 25 36 50 70 36 50 70 50 85
440 V 50/60 Hz Ics kA 18.5 22.5 35 35 18.5 22.5 35 65 22.5 35 65 35 85
525 V 50/60 Hz Ics kA – 6 10 10 – 6 25 36 9 13 18 25 65
690 V 50/60 Hz Ics kA – 4 7.5 7.5 – 4 5 5 4 5 6 20 50
Maximum low-voltage h.b.c. fuse9) A gG/gL LZM.1-…20…100: 200 355 355 355 355 LZMN3-…400: 400 LZMN4-…800…1250: 2 x 630
LZM.1-…125, 160: 315 LZMN3-…630: 630 LZMN4-…1600: 2 x 800

Utilization category to IEC/EN 60947-2 A A A A A A A A A A A B B


Rated short-time withstand current
t = 0.3 s Icw kA – – – – – – 1.9 1.9 3.3 3.3 3.3 19.2 19.2
t=1s Icw kA – – – – – – 1.9 1.9 3.3 3.3 3.3 19.2 19.2
Rated making and breaking capacity
Rated operational current AC-1 400/415 V 50/60 Hz Ie A 160 160 160 160 250 250 250 250 500 630 630 2000 2000
690 V 50/60 Hz Ie A 160 160 160 160 250 250 250 250 500 630 630 2000 2000
AC-3 400/415 V 50/60 Hz Ie A 160 160 160 160 250 250 250 250 500 630 630 16002) 16002)
690 V 50/60 Hz Ie A 160 160 160 160 250 250 250 250 500 630 630 16002) 16002)
Lifespan, mechanical Operations 20000 20000 20000 20000 20000 20000 20000 20000 15000 15000 15000 10000 10000

Maximum operating frequency


Max. operating frequency Ops/h 120 120 120 120 120 120 120 120 60 60 60 60 60
Lifespan, electrical
AC-1 400/415 V 50/60 Hz Operations 100008) 10000 10000 10000 100008) 10000 10000 10000 5000 5000 5000 3000 3000
690 V 50/60 Hz Operations – 7500 7500 7500 – 7500 7500 7500 3000 3000 3000 2000 2000
AC-34) 400/415 V 50/60 Hz Operations – – 7500 7500 65004) – 6500 6500 2000 2000 2000 2000 2000
690 V 50/60 Hz Operations – – 5000 5000 – 5000 5000 5000 2000 2000 2000 1000 1000
Current heat loss per pole at Iu6) W 16.7 16.7 16.7 16.7 19 19 19 19 31 40 40 97 97
Total opening delay at short-circuit ms < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 25 F 415 V; < 35 > 415 V < 25 F 415 V; < 35 > 415 V
Notes 2) For AC-3 rated operational current with LZM4 the following applies: 400 V: max. 650 kW; 690 V: max. 600 kW
4) For 3-pole system protection circuit-breaker the AC-3 specification is not applicable
6) For current heat loss per pole the specification refers to the maximum nominal current of the frame size.

7) For 3-pole system protection circuit-breaker the following applies: 400/415 V 7500 switching operations

8) Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker.

9) F 1600 A
92 Technical data
Temperature influence
Moeller SK1230-1176GB http://catalog.moeller.net
Response values of the overload release at temperatures deviating from the
reference temperatures
Device Type Release Temperature compensation coefficient
type
20 °C 30 °C 40 °C 50 °C 60 °C 65 °C 70 °C
Thermomagnetic release (TM)
System protection Protection of systems (reference temperature 40 °C)
LZM...1(-4)-A15…80 TM 1.14 1.07 1 0.93 0.86 0.83 0.79
Circuit-breakers

LZM...1(-4)-A90…125 TM 1.14 1.07 1 0.93 0.86 0.83 0.79


LZM...1(-4)-A160 TM 1.08 1.04 1 0.96 0.92 0.90 0.88
LZM...2(-4)-A15…200 TM 1.04 1.02 1 0.98 0.96 0.95 0.94
LZM...2(-4)-A250 TM 1.04 1.02 1 0.98 0.96 0.95 0.94
LZM...2(-4)-A20…200 + XSV TM with XSV 1.04 1.02 1 0.98 0.96 0.95 0.94
LZM...2(-4)-A250 + XSV TM with XSV 1.04 1.02 1 0.98 0.96 0.95 0.94
Short-circuit / motor protection Motor protection (reference temperature 20 °C)
LZM...1-S40…80 TM 1 0.98 0.95 0.93 0.90 0.89 0.88
LZM...1-S100 TM 1 0.98 0.95 0.93 0.90 0.89 0.88
LZM...2-S20…200 TM 1 0.98 0.96 0.94 0.92 0.91 0.90
LZM...2-S20…200 + XSV TM with XSV 1 0.98 0.96 0.94 0.92 0.91 0.90

Notes With temperatures which deviate from the reference temperature, a slight change of the overload protection properties occurs. In order to determine the
release time using the tripping characteristics the temperature compensation coefficient in accordance with the table must be considered.
Example: An LZM1-A100 is calibrated for a reference temperature of 40 °C.
What happens when it is operated at an ambient temperature of 60 °C ?
At 60 °C, the temperature compensation coefficient of 0.86 results in a reduced operating current of Ir = 100 A x 0.86 = 86 A. In other words
at an ambient temperature of 60 °C the LZM1-A100 trips as if it were set to 86 A.

Reduction of the rated operational current (derating) under particular ambient


conditions (according to IEC 947)
Device Type Release Derating coefficient
type
20 °C 30 °C 40 °C 50 °C 60 °C 65 °C 70 °C
Thermomagnetic release (TM)
System protection Protection of systems (reference temperature 40 °C)
LZM...1(-4)-A15…80 TM 1 1 1 1 1 1 1
LZM...1(-4)-A90…125 TM 1 1 1 1 0.86 0.83 0.8
LZM...1(-4)-A160 TM 1 1 1 0.95 0.9 0.85 0.8
LZM...2(-4)-A15…200 TM 1 1 1 1 1 1 1
LZM...2(-4)-A250 TM 1 1 1 1 0.9 0.85 0.8
LZM...2(-4)-A20…200 + XSV TM with XSV 1 1 1 1 1 1 1
LZM...2(-4)-A250 + XSV TM with XSV 1 0.97 0.92 0.87 0.81 – –
Short-circuit / motor protection Motor protection (reference temperature 20 °C)
LZM...1-S40…80 TM 1 1 1 1 1 1 1
LZM...1-S100 TM 1 1 1 1 0.86 0.83 0.8
LZM...2-S20…200 TM 1 1 1 1 1 1 1
LZM...2-S20…200 + XSV TM with XSV 1 1 1 1 1 1 1

Notes The derating coefficient must be considered in accordance with the following table in order to determine the maximum permissible current loading at
different ambient temperatures.
Example: An LZM2-A250 should be operated at an ambient temperature of 65 °C.
How high is the permissible rated operational current Ie?
At 65 °C the derating coefficient is 0.85, this means Ie = 250 A x 0.85 = 212.5 A.
The LZM2-A250 may be operated at an ambient temperature of 65 °C with a maximum Ie = 212.5 A.

Part no. Weight Part no. Weight


kg kg
Circuit-breaker Plug-in adapter elements
LZM...1-... 1.046 +NZM2-XSV 4.7
LZM...1-4-... 1.325 +NZM2-4-XSV 5.9
LZM...2-... 2.345 Withdrawable unit
LZM...2-4-... 3.5 +NZM3-XAV 21
LZM...3-... 6.34 +NZM3-4-XAV 27
LZM...3-4-... 8.4 +NZM4-XAV 52
LZM...4-... 21 +NZM4-4-XAV 65
LZM...4-4-... 27
Technical data 93
Temperature influence
http://catalog.moeller.net Moeller SK1230-1176GB
Reduction of the rated operational current (derating) under particular ambient
conditions (according to IEC 947)
Device Type Release Derating coefficient
type
20 °C 30 °C 40 °C 50 °C 60 °C 65 °C 70 °C
Electronic release (E)
System protection
LZM...3(-4)-AE400...500 E 1 1 1 1 1 1 1

Circuit-breakers
LZM...3(-4)-AE550...630 E 1 1 1 1 0.9 0.85 0.8
LZM...3(-4)-AE400 + XAV E with XAV 1 1 1 1 1 1 1
LZM...3(-4)-AE630 + XAV E with XAV 0.96 0.92 0.87 0.83 0.78 0.75 0.73
LZM...4(-4)-AE600...1250 E 1 1 1 1 1 1 1
LZM...4(-4)-AE1600 E 1 1 1 1 0.87 0.85 0.82
LZM...4(-4)-AE800...1250 + XAV E with XAV 1 1 1 1 1 1 1
LZM...4(-4)-AE1600 + XAV E with XAV 1 0.98 0.93 0.89 0.85 0.83 0.8
Systems protection, cable protection, selectivity and generator protection
LZM...3(-4)-VE400...500 E 1 1 1 1 1 1 1
LZM...3(-4)-VE550...630 E 1 1 1 1 0.9 0.85 0.8
LZM...3(-4)-VE400 + XAV E with XAV 1 1 1 1 1 1 1
LZM...3(-4)-VE630 + XAV E with XAV 0.96 0.92 0.87 0.83 0.78 0.75 0.73
LZM...4(-4)-VE600...1250 E 1 1 1 1 1 1 1
LZM...4(-4)-VE1600 E 1 1 1 1 0.87 0.85 0.82
LZM...4(-4)-VE630...1250 + XAV E with XAV 1 1 1 1 1 1 1
LZM...4(-4)-VE1600 + XAV E with XAV 1 0.98 0.93 0.89 0.85 0.83 0.8

Notes The derating coefficient must be considered in accordance with the following table in order to determine the maximum permissible current loading at
different ambient temperatures.
Example: An LZM3-VE630 should be operated at an ambient temperature of 65 °C.
How high is the permissible rated operational current Ie?
At 65 °C the derating coefficient is 0.85, this means Ie = 630 A x 0.85 = 535.5 A.
The LZM3-VE630 may be operated at an ambient temperature of 65 °C with a maximum Ie = 535.5 A.
94 Technical data
Effective power loss
LZM1, LZM2 Moeller SK1230-1176GB http://catalog.moeller.net

LZM up to 250 A with thermomagnetic release (3- and 4-pole)


Fixed mounting Fixed mounting
LZM1- LZM2-
A... S... A... S...
In [A] P R P R P R P R
[W] [μOhm] [W] [μOhm] [W] [μOhm] [W] [μOhm]
1.2 – – – – – – – –
Circuit-breakers

1.6 – – – – – – – –
2 – – – – – – – –
2.4 – – – – – – – –
3 – – – – – – – –
5 – – – – – – – –
8 – – – – – – – –
12 – – – – – – – –
15 – – – – – – – –
18 – – – – – – – –
20 9.8 8180 – – 5.1 4250 5.1 4250
25 8.8 4680 – – 8 4250 8 4250
26 – – – – – – – –
30 – – – – – – – –
32 9.1 3030 – – 10 3140 10 3140
33 – – – – – – – –
35 – – – – – – – –
40 11 2220 13.5 2810 13 2800 13 2800
45 – – – – – – – –
50 13.5 1760 15 1880 18 2270 18 2270
60 – – – – – – – –
63 14 1190 16.7 1250 20 1700 20 1700
70 – – – – – – – –
80 15.5 850 21.1 1085 22 1070 22 1070
90 – – – – – – – –
100 24 730 25 795 28 855 28 855
110 – – – – – – – –
125 38 570 – – 29 589 29 589
150 – – – – – – – –
160 50 460 – – 40 427 40 427
175 – – – – – – – –
200 – – – – 48 332 48 332
225 – – – – – – – –
250 – – – – 57 310 – –
Note: The values stated in the table apply for 3- and 4-pole fixed mounted devices with an equal load distribution.
On 4-pole devices the current in the N-conductor is equal to zero.
The total resistive load is the measured value for a 3-pole or a 4-pole switch.
The total heat dissipation is the value measured at In, 50/60Hz for a 3-pole or 4-pole switch.
The heat dissipation can be calculated with the formula: P = 3 x R x I²

LZM up to 1600 A with electronic release (3- and 4-pole)


Fixed mounting Supplementary Fixed mounting Supplementary Fixed mounting Supplemementary
LZM2- Plug-in units LZM3 Withdrawable units LZM4 Withdrawable units
R R R R R R
[μOhm] [μOhm] [μOhm] [μOhm] [μOhm] [μOhm]
275 100 100 70 37 10
Note: The values stated in the table apply for 3- and 4-pole devices with an equal load distribution.
On 4-pole devices the current in the N-conductor is equal to zero.
The total resistive load is the measured value for a 3-pole or a 4-pole switch
(independent of In and the type of release).
The total resistive load for a plug-in or withdrawable switch results from:
the resistive value for fixed mounted + resistive value for plug-in or withdrawable.
The heat dissipation can be calculated with the formula: P = 3 x R x I²
Notes 95

http://catalog.moeller.net Moeller SK1230-1176GB

Circuit-breakers
96 Technical data Technical data 97
Terminal capacities Terminal capacities
LZM… Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB LZM…
LZM1 In1) LZM2 In1) LZM3 In1) LZM4 In1)
160 A A 250 A A 630 A A 1600 A A

Terminal capacities
Standard equipment Box terminal Screw terminal Screw terminal Screw terminal
Accessories Screw connection Box terminal Box terminal Tunnel terminal
Tunnel terminal Tunnel terminal Tunnel terminal Connection on rear
Connection on rear Connection on rear Connection on rear Strip terminal
Circuit-breakers

Circuit-breakers
Rated power of coil
Box terminal Solid mm2 1 x (10 – 16) 160 1 x (4 – 16) 250 2 x 16 500
2 x (6 – 16) 2 x (4 – 16)
Stranded mm2 1 x (25 – 70) 1 x (25 – 185) 250 1 x (35 – 240)
2 x 25 2 x (25 – 70) 2 x (25 – 120)
Tunnel terminal Solid mm2 1 x 16 160 1 x 16 250
Stranded Single hole mm2 1 x (25 – 95) 1 x (25 – 185) 1 x (25 – 185) 350
Double hole fitting mm2 – – – – 1 x (50 – 240) 630 – –
2 x (50 – 240) 2 x 185
4-hole mm2 – – – – – – 4 x (50 – 240) 1400
Bolt terminal and rear-side connection
Direct on the switch Solid mm2 1 x (10 – 16) 160 1 x (4 – 16) 250 1 x 16 630
2 x (6 – 16) 2 x (4 – 16) 2 x 16 2 x 185
Stranded mm2 1 x (25 – 70)3) 1 x (25 – 185) 1 x (25 – 240) 1 x (120 … 185) 1250
2 x 25 2 x (25 – 70) 2 x (25 – 240) 4 x (50 … 185)
Module plate Single hole min. mm2 – – – – – – 1 x (120 – 300) 1000
max. mm2 – – – – – – 2 x (95 – 300)
Module plate Double hole min. mm2 – – – – – – 2 x (95 – 185) 1400
max. mm2 – – – – – – 4 x (35 – 185)
Connection width extension mm2 2 x 300 630 4 x 300 1600
2 x 185 6 x (95 – 240) 4 x 240
Al conductors, Al cable
Tunnel terminal Solid mm2 1 x 16 160 1 x 16 250 1 x 16 350 – –
Stranded Single hole mm2 1 x (25 – 95) 1 x (25 – 185)2) 1 x (25 – 185)2) – –
Double hole fitting mm2 – – – – 1 x (50 – 240) 630 – –
2 x (50 – 240)
4-hole mm2 – – – – – – 4 x (50 – 240) 1400
Bolt terminal and rear-side connection
Direct on the switch Solid mm2 1 x (10 – 16) 160 1 x (10 – 16) 250 1 x 16 400 – –
2 x (10 – 16) 2 x (10 – 16) 2 x (10 – 16)
Stranded mm2 1 x (25 – 35) 1 x (25 – 50) 1 x (25 – 120) – –
2 x (25 – 35) 2 x (25 – 50) 2 x (25 – 120)
Module plate Single hole min. mm2 – – – – – – 1 x (185 – 240) pleaes inquire
Single hole max. mm2 – – – – – – 2 x (70 – 185) pleaes inquire
Module plate Double hole mm2 – – – – – – 4 x 50 –
Connection width extension mm2 2 x 240 pleaes inquire
6 x (70 – 240)
Cu strip (number of segments x width x segment thickness)
Box terminal min. mm 2 x 9 x 0.8 160 2 x 9 x 0.8 250 6 x 16 x 0.8 630 – –
max. mm 9 x 9 x 0.8 10 x 16 x 0.8 10 x 24 x 1.0 – –
+ 5 x 24 x 1.0
(2 x) 8 x 24 x 1.0
Flat conductor terminal min. mm 6 x 16 x 0.8 1100
max. mm (2 x) 10 x 32 x 1.0
Module plate Single hole mm – – – – – – (2 x) 10 x 50 x 1.0 1250
(2 x ) 10 x 40 x 1.0
Bolt terminal and rear-side connection
Flat copper strip, with holes min. mm 2 x 16 x 0.8 250 6 x 16 x 0.8 630 (2 x) 10 x 50 x 1.0 1600
Flat copper strip, with holes max. mm 10 x 16 x 0.8 10 x 32 x 1.0 + 5 (2 x) 10 x 50 x 1.0
x 32 x 1.0
Connection width extension mm2 – – – – (2 x) 10 x 50 x 1.0 (2 x) 10 x 80 x 1.0 1600
2 x (10 x 50 x 1.0)
Copper busbar (width x thickness)
Bolt terminal and rear-side connection
Screw connection M6 M8 M10 M10
Direct on the switch min. mm 12 x 5 160 16 x 5 250 20 x 5 630 25 x 5 1600
max. mm 16 x 5 20 x 5 30 x 10 2 x (50 x 10) 2000
+30 x 5 2 x (80x 10)
Module plate Single hole min. mm – – – – – – 25 x 5 1250
max. mm – – – – – – 2 x (50 x 10) 2 x (40 x 10)
Module plate Double hole mm – – – – – – 2 x (50 x 10) 1500
Connection width extension min. mm – – – – – 630 60 x 10 1600
max. mm – – – – 2 x (10 x 50) 10 x 40 2 x (80 x 10) 2 x (50 x 10)

Notes 1) The rated currents In have been determined conform to IEC/EN 60947 (switchgear standard) and generally relate
to the max. defined cross-sections and are intended for the purpose of orientation. The engineering standards which apply in
each case must be observed.
2) depending on the cable manufacturer up to 240 mm2 can be connected.
3) depending on the cable manufacturer up to 95 mm2 can be connected.
98 Technical data
Auxiliary contacts
M22-K…, XHI(V) Moeller SK1230-1176GB http://catalog.moeller.net

at AC = 50/60 Hz M22-K… NZM-XHIV NZM-XHI

Auxiliary contacts
Rated operational voltage
AC Ue V AC 500 500 500
DC Ue V DC 220 220 220
Circuit-breakers

Conventional thermal current Ith = Ie A 4 4 4


Rated operational current
AC–15 115 V Ie A 4 4 4

230 V Ie A 4 4 4
400 V Ie A 2 2 2
500 V Ie A 1 1 1
DC-13 24 V Ie A 3 3 3
42 V Ie A 1.7 1.5 –

60 V Ie A 1.2 0.8 1.2

110 V Ie A 0.8 0.5 0.5

220 V Ie A 0.3 0.2 0.2

Short-circuit protection
max. fuse A gG/gL 10 10 10
Max. miniature circuit-breaker A PKZM0-10/FAZ-B6 FAZ-B6 FAZ-B6
Early-make time compared to the main contacts ms LZM1: approx. 20
during switch on and off (switching times with LZM2: approx. 20
manual operation) LZM3: approx. 20
LZM4: approx. 90
With LZM4/N(S)4 the HIV
does not feature early break.

Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.75 – 2.5) 1 x (0.75 – 2.5) 1 x (0.75 – 2.5)
2 x (0.75 – 2.5) 2 x (0.75 – 2.5) 2 x (0.75 – 2.5)
AWG 1 x (18 – 14) 1 x (18 – 14) 1 x (18 – 14)
2 x (18 – 14) 2 x (18 – 14) 2 x (18 – 14)
Technical data 99
Equipping with auxiliary contacts, time differences
http://catalog.moeller.net Moeller SK1230-1176GB LZM…

Maximum equipment and position of the internal accessories


c b a
-XHIV(2S) HIA HIN Contacts per slot with
or -XA HIA and HIN
or -XU

LZM1 1 1 1 1 N/O

Circuit-breakers
a LZM2 1 1 2 1 N/C
b LZM3 1 1 3 2 N/O
c LZM4 1 2 3 2 N/C
N/O = normally open contact
N/C = normally closed
contact

Time differences ON-OFF

Main contact

Auxiliary contact, early make


a b

Auxiliary contact, normal (HIN)


a b

Time difference a (ms) Time difference b (ms)


Manual operation Motor operators Manual operation Motor operators
HIV HIN HIV HIN HIV HIN HIV HIN
K10 K01 K10 K01 K10 K01 K10 K01

LZM1 202) 0 2.5 – – – 202) 0 2.5 – – –

LZM2 202) 3.5 6.5 Not 2.5 4.5 202) 3 4.5 Not 3 4
permissible permissible
LZM3 202) 4 8 Not 2 4 202) 3.5 8 Not 3 6.5
permissible permissible
LZM4 902) 7 11 Not on request on request 01)2) 12 15 Not on request on request
permissible permissible

Notes 1) With LZM4/N(S)4 the HIV does not feature early break.
2) Minimum value, as it is dependent on the switching speed
100 Technical data
Undervoltage releases, shunt releases
NZM…-XU, NZM…-XA… Moeller SK1230-1176GB http://catalog.moeller.net

NZM1(2/3)-XU... NZM4-XU…

Undervoltage release
Rated control voltage
Alternating voltage at 50/60 Hz Us V AC 24…600 24…600
DC Us V DC 12…250 12…250
Operating range
Circuit-breakers

Drop-out voltage x Us 0.35 – 0.7 0.35 – 0.7


Pick-up voltage x Us 0.85 – 1.1 0.85 – 1.1
Power consumption
AC
Pick-up AC VA 1.5 3.6
Sealing AC VA 1.5 3.6
DC
Pick-up DC W 0.8 2.5
Sealing DC W 0.8 2.5
Max. opening delay ms 19 23
(response time until the main circuits open)
Minimum command time ms 10 – 15 10 … 15
Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.75 … 2.5) 1 x (0.75 … 2.5)
2 x (0.75 … 2.5) 2 x (0.75 … 2.5)
AWG 1 x (18 … 14) 1 x (18 … 14)
2 x (18 … 14) 2 x (18 … 14)

UVU-NZM

Undervoltage releases, off-delayed


Rated operational voltage
Alternating voltage at 50/60 Hz Ue V AC 24, 220 – 550
DC Ue V DC 24
Inrush current (peak value) Ie mA < 500
Power consumption VA 50
Delay time tsd ms 70 – 4000
With additional external capacitor, 90.000 μF f 35 V s To 16

With additional external capacitor, 30.000 μF f 35 V s To 8

Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.5 – 2.5)
2 x (0.5 – 1.5)

NZM1(2/3)-XA... NZM4-XA... NZM2/3-XA...-MNS NZM4-XA…-MNS

Shunt release
Rated control voltage
AC Us V AC 12…440 12…440 230 230
DC Us V DC 12…440 12…440
Frequency range Hz 0 – 400 0 – 400 50/60 50/60
Operating range
AC x Us 0.7…1.1 0.7…1.1 0.1…1.1 0.1…1.1
DC x Us 0.7…1.1 0.7…1.1
Power consumption
Pick-up AC/DC VA/W 2.5 2.5 – –
Sealing AC/DC VA/W 2.5 2.5 – –
Maximum current consumption at 110% Us (230 V 50 Hz) A – – 0.5 1
Max. opening delay (response time until the main circuits ms 20 22 20 22
open)
Duty factor ms L L 1000 ms 1000 ms
Minimum command time ms 10 … 15 10 … 15 10 … 15 10 … 15
Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.75 … 2.5) 1 x (0.75 … 2.5) 1 x (0.75 … 2.5) 1 x (0.75 … 2.5)
2 x (0.75 … 2.5) 2 x (0.75 … 2.5) 2 x (0.75 … 2.5) 2 x (0.75 … 2.5)
AWG 1 x (18 … 14) 1 x (18 … 14) 1 x (18 … 14) 1 x (18 … 14)
2 x (18 … 14) 2 x (18 … 14) 2 x (18 … 14) 2 x (18 … 14)
Technical data 101
Remote operator, capacitor units
http://catalog.moeller.net Moeller SK1230-1176GB NZM-XCM, NZM…-XR…

NZM-XCM

Capacitor unit for shunt release


Rated operational voltage Ue V AC 230
Rated operational current Ie mA < 10
Inrush current (peak value) Ie A 3

Circuit-breakers
Terminal capacities
Solid or flexible conductor with ferrule mm2 1 x (0.5 – 2.5)
2 x (0.5 – 1.5)
AWG 1 x (20 – 14)
2 x (20 – 16)

NZM2-XR... NZM3-XR... NZM4-XR…

Remote operator
Rated control voltage
AC Us V AC 110…440 110…440 110…440
DC Us V DC 24…250 24…250 24…250
Operating range
AC Us 0.85…1.1 0.85…1.1 0.85…1.1
DC Us 0.85…1.1 0.85…1.1 0.85…1.1
Motor rating
AC 110 … 130 V AC VA 350 350 350
208 … 240 V AC VA 350 350 350
380 … 440 V AC VA 350 350 350
DC 24 … 30 V DC W 250 250 250
110 … 130 V DC W 250 250 250
220 … 250 V DC W 250 250 250
Rated power of coil
AC 110 … 130 V AC VA 270 270 270
208 … 240 V AC VA 270 270 270
380 V … 440 V AC VA 270 270 270
DC 24 … 30 V DC W 210 210 210
100 … 130 V DC W 210 210 210
220 … 250 V DC W 210 210 210
Total make time ms 60 80 100
Total opening delay ms 300 1000 3000
Minimum signal duration
with switch on ms 30 30 30
with switch off ms 150 250 500
Lifespan, mechanical Operations 20000 15000 10000
Maximum operating frequency Ops./h 120 60 20
Terminal capacities
Solid or flexible conductor with ferrule mm2 0.75 … 2.5 0.75 … 2.5 0.75 … 2.5
AWG 18 … 14 18 … 14 18 … 14
102 Technical data
Residual-current relay
PFR-… Moeller SK1230-1176GB http://catalog.moeller.net

PFR-003 PFR-03 PFR-5

Electrical
Standards IEC/EN 60947-2, IEC 755, IEC 1008, IEC 1009
Sensitivity Pulse current sensitive, type A
Rated control voltage Us V AC 230 g20 % (50/60 Hz)
Motor rating Pe W 3 3 3
Circuit-breakers

Rated fault currents IDn mA 0.03 0.3 0.03, 0.1, 0.3, 0.5, 1, 3, 5
Delay time tv s 0.02 (non-delayed) 0.02 (non-delayed) 0.02, 0.1, 0.3, 0.5, 1, 3, 5
Relay contacts 1 integrated changeover 1 integrated changeover 1 integrated changeover
contact contact contact
Rated voltage of the relay contact V AC/DC 250/100 250/100 250/100
Rated current of the relay contact A 6 6 6
Fault current warning Hz – – 0.5 = 25% – 50% IDn
1 = 50% – 75% IDn
2 = 75% – 100% IDn
Mechanical
Standard front dimension mm 45 45 45
Device height mm 85 85 85
Device width mm 45 45 45
Mounting Snap fixing, top-hat rail DIN 46277, IEC/EN 60715
Terminals top and bottom Box terminals
Terminal protection Finger/back-of-hand proof to BGV A2, VDE 106 part 100

Terminal capacities mm2 2 x 0.75 – 2.5 solid, 2 x 0.75 – 1.5 flexible/with ferrules
Sealability – yes
Notes 103

http://catalog.moeller.net Moeller SK1230-1176GB

Circuit-breakers
104 Technical Data Technical Data 105
Residual-current releases Residual-current releases
NZM…-XFI… Moeller SK1230-1176GB http://catalog.moeller.net http://catalog.moeller.net Moeller SK1230-1176GB NZM…-XFI…

NZM1(-4)-XFI30R NZM1(-4)-XFI300R NZM1(-4)-XFIR NZM1(-4)-XFI30U NZM1(-4)-XFI300U NZM1(-4)-XFIU +NZM2-4-XFI30 +NZM2-4-XFI +NZM2-4-XFIA30 +NZM2-4-XFIA

Electrical
Standards IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2 IEC/EN 60947-2
Sensitivity Pulse current sensitive according to core-balance principle Pulse current sensitive according to core-balance Pulse current sensitive Pulse current sensitive Sensitive to AC/DC (type Sensitive to AC/DC (type
principle according to core- according to core- B) B)
balance principle balance principle
Circuit-breakers

Circuit-breakers
Min. operating voltage
or detection of fault currents type A/ 80 V (dependent on 80 V (dependent on 80 V (dependent on 80 V (dependent on 80 V (dependent on 80 V (dependent on independent of mains independent of mains 0 V independent of 0 V independent of
AC mains voltage) mains voltage) mains voltage) mains voltage) mains voltage) mains voltage) voltage voltage mains voltage mains voltage
or detection of fault currents type B 50 V (dependent on 50 V (dependent on
mains power) mains voltage)
Suitability for the application In three- and single-phase systems In single-phase In single-phase In three- and single-phase systems
Rated operational voltage Ue V AC 200…415 (3~) 200…415 (3~) 200…415 (3~) 200…415 (3~) 200…415 (3~) 200…415 (3~) 280…690 280…690 50…400 (3~) 50…400 (3~)

Rated frequency f Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Number of poles 3/4 3/4 3/4 3/4 3/4 3/4 4 4 4-pole 4-pole
Rated current range In A 15…125 15…125 15…125 15…100 15…100 15…100 15…250 15…250 15…250 15…250

Rated fault currents IDn A 0.03 0.3 0.03…0.1…0.3… 0.03 0.3 0.03…0.1…0.3… 0.03 0.1…0.3…1…3 0.03 0.1…0.3…1
0.5…1…3 0.5…1…3
Detection range of the fault current 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz with AC voltage: 0 – 100 with AC voltage: 0 – 100
kHz kHz
with pulsed DC voltage: with pulsed DC voltage:
50 Hz 50 Hz
Rated ultimate short-circuit making IDm A = ICU = ICU = ICU = ICU = ICU = ICU = ICU = ICU = ICU = ICU
capacity and -rated ultimate short-circuit
breaking capacity
Fault current warning f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn f 0.3 x IDn – – – –

Mechanical shock resistance (IEC 60068-2-27) 20 (half-sinusoidal shock 20 ms) 20 (half-sinusoidal shock 20 ms)
Lifespan, mechanical (50 % with fault Operations 20000 20000 20000 20000 20000 20000 f 2000 f 2000 f 2000 f 2000
current)
Mechanical
Standard front dimension mm 45 45 45 45 45 45 96 96 96 96
Mounting on the right side sidewise on the right Bottom Bottom Bottom Bottom Bottom Bottom Bottom Bottom
Mounting position Vertical and 90° in all directions Vertical and 90° in all directions
Supply LZM1 from above LZM1 from above LZM1 from above LZM1 from above LZM1 from above LZM1 from above As required As required Bottom Bottom
Degree of protection IP20 in the operating component area IP20 in the operating component area
Ambient temperature °C –5…+40 –5…+40 –5…+40 –5…+40 –5…+40 –5…+40 –25…+70 –25…+70 –25…+70 –25…+70
Sealability yes, setting buttons yes, setting buttons yes, setting buttons yes, setting buttons

Terminal capacity
Flexible without ferrule mm2 such as LZM1 standard terminal such as LZM1 standard terminal with LZM2 standard connection

flexible with ferrules mm2 such as LZM1 standard terminal such as LZM1 standard terminal with LZM2 standard connection
106 Dimensions
Size 1: basic units
LZM1 Moeller SK1230-1176GB http://catalog.moeller.net
Circuit-breaker 84.5
3 pole 68
LZMB1 NZM...1-...-(C)NA

LZMC1 a
30 21

f 60
10.2
LZMN1 57

9.5
LZMS1

16
Circuit-breakers

41.5
64

04
R1
112
126
145

F
45

90
°
63

162

SW4 M4 x 50/10
30 44.6
90

a Blow out area, minimum clearance to other parts f 60 mm

Circuit-breaker 84.5
4 pole 68
LZMB1-4
LZMC1-4 a
60 21
f 60
9.5

LZMN1-4
LZMH1-4
16

89
5
41.5
64

04
R1
112
126
145

N
45
63

SW4 M4 x 50
30 44.6
120

a Blow out area, minimum clearance to other parts f 60 mm

Covers 21
NZM1(-4)-XKSA 16 4
Screw connection
NZM1(-4)-XKS IP2X

IP2X protection against


contact with a finger SW 4 M6 x 14
for shroud
34
26

NZM1(-4)-XIPA
Screw connection
64
296

158
80

90 a 59
120 b

a 3 pole
b 4 pole
Dimensions 107
Size 1: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM1…-XK…, NZM1…XIPK, NZM-XSTK
Tunnel terminal
NZM1(-4)-XKA
20 20 a 3 pole
b 4 pole

SW 5
48

SW 4 M6 x 14

Circuit-breakers
32
64

90 a
120 b

Connection on rear
NZM1(4)-XKR
30 30 30
30 15

SW 4 M6 x 14 o 22
64

63

102
126
128

10 10 50
18

o 6.6 M4
30
90 2–5
120

30
15
M6 x 20
o 22
6

63

126
128

M4
15

Control circuit terminal IP2X protection against contact with a finger


NZM1-XIPK, NZM-XSTK NZM1(-4)-XIPK
46 10
13
91
108

76
64
89

90 a
90 a
120 b
120 b

a 3 pole
b 4 pole
108 Dimensions
Size 1: accessories
NZM1-XDV…, NZM1-XTVD… Moeller SK1230-1176GB http://catalog.moeller.net
Rotary drive
Rotary handle on circuit-breaker
NZM1-XDV NZM1-XDTV
NZM1-XDVR

a
Circuit-breakers

80.3

F 43

36
54
45

45
90
120

d
b

d=4–8
b f 34
a Up to 3 padlocks

Door coupling rotary handle


NZM1-XTVD(V)(R)
73.5
27.5
8

ZFS...-NZM7
o8
23

40
85

71
o
R4
6

71
85
2–5

a
35

d
b

d=4–8
b f 34
a Up to 3 padlocks
Dimensions 109
Size 1: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM1-XTVD…
Door coupling rotary handle with extension shaft
NZM1-XTVD(V)(R)
NZM1/2-XV4(6)
2–5 73
210 – 400(400 – 600) 27

Circuit-breakers
55
o 45
8

NZM1/2-XV4(NZM1/2-XV6) 36 23g0.5

NZM1-XTVD(V)(R)-60 NZM1-XTVD(V)(R)-0
41 – 75
16 – 60

NZM1/2-XV...

167 – 210 23g0.5


a

128 – 167 23g0.5

a Special tip

Minimum door coupling rotary handle clearance from door pivot point

NZM...1-... f 130
110 Dimensions
Size 1: accessories
NZM1-XS, NZM1…HIV Moeller SK1230-1176GB http://catalog.moeller.net
Main switch assembly kit for side panel mounting
NZM1-XS(R)-L NZM1-XS(R)-R
41

51.5
Circuit-breakers

2-5 12 129
12 2-5 129 15
73.5 95-310 90
90 95-310 73.5

Main switch assembly kit for side panel mounting with mounting bracket
NZM1-XS(R)M-L NZM1-XS(R)M-R
NZM1/2-XZB

145
145

NZM1/2-XZB

12 2-5 131.4
2-5 12 131.4
57.2 73.5 176
73.5 57.2 176
163 178.5
163 178.5
195.5
195.5

Undervoltage release
Shunt release
Early-make auxiliary contacts
20 20 23.2 a
NZM1-XA(HIV)
NZM1-XU(HIV)(20)
NZM1-XHIV
39.3

39.3

b
NZM1-XA(HIV)(L)
38.6

a c NZM1-XU(V)(HIV)(L)(20)
NZM1-XHIV(L)
b c
NZM1-XHIVR

Spacers Clip plate


NZM1/2-XAB NZM1-XC35
103
9.5

35
17.5
126
145
157

30 1.5

90 8.4
Dimensions 111
Size 1: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM…-X…
Insulating surrounds
NZM1-XBR a Mounting aperture
9.5
1.5 – 5
ZFS...-NZM7

Circuit-breakers
53
64

82

132

117 23 11.5
148.5 19

Rotary handle on switch with door interlock


NZM1-XDTV(R) a Mounting aperture
32
9.5
1.5 – 5
14.4
9
o4
11
40

53

132

11.5
19

Rear drive Toggle lever locking device


NZM1-XRAV(R) NZM-XKAV
NZM1-4-XRAV(R)
45 32
1

a
46.3
145

F 80
117 a 115

148 b

a NZM1-XRAV(R)
d
b NZM1-4-XRAV(R)
b

d=4–8
b f 34
a Up to 3 padlocks
112 Dimensions
Size 1: accessories
NZM1-XMV, NZM1-XTV… Moeller SK1230-1176GB http://catalog.moeller.net
Mechanical interlock
NZM1-XMV + NZM1-XDV(R)

29.2
Circuit-breakers

80.3

51
27
45
22.5

31
7
45 5
90 40
120 143 40

NZM1-XMV + NZM1-XTVD(V)(R)
Part no. x
NZM1/2-XV4 (NZM1/2-XV6)
NZM1/2-XV4 245 – 400
NZM1/2-XV6 400 – 600

245 – 400 (400 – 600)

NZM1-XMV + NZM1-XTVD(V)(R)-60 NZM1-XMV + NZM1-XTVD(V)(R)-0

NZM1/2-XV... a

163 – 202

202 – 245

a Special tip
Dimensions 113
Size 1: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM1-XCI…, NZM1-XAD
Insulated enclosures
NZM1-XCIK5-T... NZM1-XCI23-T...
280

250
8

Circuit-breakers
200 160
187.5 175
231
246

NZM1-XCI43-T... NZM1-XCI43/2-T...

60
60
495
375

375
495
8
8

80 60 80 60

250 175 250 225

246 296

Component adapter
NZM1-XAD160
200

90 65.5
114 Dimensions
Size 1: accessories
NZM1…-XFI…, PFR-… Moeller SK1230-1176GB http://catalog.moeller.net
Residual-current relay
PFR-003 5 6 7 8

PFR-03
PFR-5 a

85
67
45

1 2 3 4
Circuit-breakers

36 44
68
73

Current transformer
PFR-W-20…30 PFR-W-35...210
F Part no. A B C D E F
PFR-W-35 100 79 26 48.5 35 35
I PFR-W-70 130 110 32 66 70 52
G
J

E PFR-W-105 170 146 38 94 105 72


B
H

PFR-W-140 220 196 48.5 123 140 97


PFR-W-210 299 284 69 161 210 141
A 33

F G H I J
PFR-W-20 32 60 24 46 21
46

PFR-W-30 32 70 30 59 30
6.5

F
C D

Fixing clip
PFR-WC PFR-WMA
Part no. A ØB ØC A1 A2
PFR-WMA-35 91 28 40 35 28
oB
oC

PFR-WMA-70 105 62 75 35 35
51.7
32.7

PFR-WMA-105 153 98 110 35 60


A1 A2
PFR-WMA-140 153 133 145 35 60
A PFR-WMA-210 153 203 215 35 60
6.0
12.5

Residual-current release
NZM1(-4)-XFI...R
– 80.1
68
145
145
220

45
220

42.5

135 105

NZM1(-4)-XFI...U
80.1
68
23.1
145

145

45
42.5

120 90.15
Dimensions 115
Size 2: Basic units
http://catalog.moeller.net Moeller SK1230-1176GB LZM2
Circuit-breaker 149
3 pole 103
LZMB2 35
NZM...2-...(C)NA 25 5
b
LZMC2
a

f 35
LZMN2 M8 x 22

11
LZMS2

19.5

24.5
3

Circuit-breakers
4
80

R 12

95
184
145
135
100
64

72.5
217

M4 x 85/20
f 35

a SW5 b 78.7
35
f5 105 f 5 NZM...2-...-(C)NA(> 480 V)
NS2-...-NA
a Blow out area, minimum distance to other parts f 35 mm
b Minimum distance to adjacent parts f 5 mm

Circuit-breaker 149
4 pole 103
LZMB2-4
LZMC2-4 b a
70 25 5
f 35

LZMN2-4 M8 x 22
LZMS2-4
19.5

24.5

3
80

24
R1

95

N
145
135

184

100
72.5

SW5 M4 x 85/20
f 35

35 78.7
a b
f5 140 f5

a Blow out area, minimum distance to other parts f 35 mm


b Minimum distance to adjacent parts f 5 mm
116 Dimensions
Size 2: accessories
NZM2…-XK…, NZM2…-XIP…, NZM2-XST… Moeller SK1230-1176GB http://catalog.moeller.net
Box terminal Tunnel terminal
(+)NZM2(-4)-...-XKC(O)(U) NZM2(-4)-XKA
IP2X protection against contact with a finger
NZM2(-4)-XIPK
65 25 30
25
19 F 22.1
Circuit-breakers

SW 8
M10

55
37
SW 5 M8 x 22
20
111

80
80

SW 5

105 a
140 b
105 a
140 b

a 3 pole
b 4 pole
Covers Control circuit terminal
NZM2(-4)-XKSA NZM2-XSTS
Cable lug NZM-XSTK
NZM2-XKS185
IP2X protection against contact with a finger for shroud
NZM2(-4)-XIPA
100

SW 5 M8 x 22
80

105
337

105 a
175

140 b
81

105 a 87
140 b

a 3 pole
b 4 pole
Dimensions 117
Size 2: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM2…-XKR…, NZM2-XDV…, NZM2-XDTV…
Connection on rear
(+)NZM2(-4)-XKR(O)(U)
35 35 35

SW 4 o 22
80

80
72

Circuit-breakers
160
145
100
10 10 48
18

M4
105 3–5 17.5
o 8.6
140 70

35 35
M8 x 30
o 30
o 20
6

80
72
145

160

M4
18
35

Rotary drive
Rotary handle on circuit-breaker
NZM2-XDV NZM2-XDTV
NZM2-XDVR NZM2-XDTV2 d
b

a d=4–8
b f 34
a Up to 3 padlocks
F 67
75

59
100
95
R4
6

52
104
140
118 Dimensions
Size 2: accessories
NZM2-XTV…, NZM1/2-XV4(6) Moeller SK1230-1176GB http://catalog.moeller.net
Door coupling rotary handle
NZM2-XTVD(V)(R)...

73.5
d
27.5

b
d=4–8
8 b f 34
a Up to 3 padlocks
ZFS...-NZM7
Circuit-breakers

o8
23

40
85

71
o
R4
6

71
85
2–5

a
35

Door coupling rotary handle with extension shaft


NZM2-XTVD(V)(R)
NZM1/2-XV4(6)
2–5 73
245 – 400(400 – 600) 27
8

55
o 45
17

NZM1/2-XV4(NZM1/2-XV6) 36 23g0.5
Dimensions 119
Size 2: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM2-XTVD…, NZM2-XS…
Door coupling rotary handle with extension shaft
NZM2-XTVD(V)(R)-60 NZM2-XTVD(V)(R)-0 Minimum door coupling rotary handle clearance from door
pivot point
16 – 60 41 – 75

Circuit-breakers
NZM...2-... f 130

NZM1/2-XV...

205 – 249 23g0.5 a

172 – 205 23g0.5

a Special tip

Main switch assembly kit for side panel mounting


NZM2-XS(R)-L

2-5 0.5
73.5 95-310 105 170.5

NZM2-XS(R)-R
41
51.5

0.5 2-5 15
105 95-310 73.5 170.5
120 Dimensions
Size 2: accessories
NZM2-XS…, NZM2…-XRAV… Moeller SK1230-1176GB http://catalog.moeller.net
Main switch assembly kit for side panel mounting with mounting bracket
NZM2-XS(R)M-L

NZM1/2-XZB

185
Circuit-breakers

2-5 0.5 172.1


73.5 47.2 216
168 218.5
200.5

NZM2-XS(R)M-R
185

NZM1/2-XZB
0.5 2-5 172.1
47.2 73.5 216
168 218.5
200.5

Rear drive
NZM2-XRAV
184

133 a 145

168 b

a NZM2-XRAV(R)
b NZM2-4-XRAV(R)
Dimensions 121
Size 2: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM…-XAB, NZM2-XBR, NZM2-XDTV…
Spacers Clip plate
NZM1/2-XAB NZM2-XC75
17.5 2

Circuit-breakers
130
169
NZM1/2-XAB
35 17
120.5 105

Insulating surrounds
NZM2-XBR
9.5 a Mounting aperture
1.5 – 5
ZFS...-NZM7

103
132
64

142

127
10
158.5 23
17.5

Rotary handle on switch with door interlock


NZM2-XDTV(R)
32 a Mounting aperture
9.5 10.4
1.5 – 5 9

NZM2-XDTV(R) o4
a
9
63

103

142
10
17.5
122 Dimensions
Size 2: accessories
NZM2…-XKAV Moeller SK1230-1176GB http://catalog.moeller.net
Toggle lever locking device
NZM2/3-XKAV
a 50
d

b
d=4–8
b f 34
1.3

a Up to 3 padlocks
Circuit-breakers

a
92.5

F 88

Part no. a
LZM2 52.5
LZM3 70
Dimensions 123
Size 2: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM2-XMV, NZM2-XTVD…, NZM2-XD
Mechanical interlock
NZM2-XMV + NZM2-XD

36

Circuit-breakers
73
75

50
95
47.5

50
50 9.6

52.5 6

105 41

140 180 46

NZM2-XMV + NZM2-XTVD(V)(R)

NZM1/2-XV4(6)

Mechanical interlock
NZM2-XMV + NZM2-XTVD(V)(R)-60 NZM2-XMV + NZM2-XT(V)D(V)(R)-0

a
NZM1/2-XV...

240 – 284 207 – 240

a Special tip
124 Dimensions
Size 2: accessories
NZM2-XR… Moeller SK1230-1176GB http://catalog.moeller.net
Remote operator
NZM2-XR...
322.8 a Up to 3 padlocks
235.5 b Remote operator hinged
35 135
d
NZM2-XAVPR

b
d=4–8
b f 34
7.2

21.5
Circuit-breakers

F 13.7

105
a

250
105 52.5
b
105
140
Dimensions 125
Size 2: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM2-XCI…, NZM2-XAD, NZM2…-XSV
Insulated enclosures
NZM2-XCI43-T... NZM2-XCI45-T...
60

80
17
375
495

Circuit-breakers
17
500
660
187.5

250
80 60
250 225
296
190 60
375 225
296

Component adapter
NZM2-XAD250
20

145

190
145

20

35 63
35 35
106

Plug-in units
+NZM2(-4)-XSV
190.5
92.3
87.5 148.3
35 25
15.7

M8 x 22
67.1

NZM2(-4)-XSVS
57.5

109.7
396

184
241
237
205

NZM2(-4)-XSVE

M4 x 93

SW5
M4 x 85

35 78.7
105
140
126 Dimensions
Size 2: accessories
NZM2(-4)-XFI, NZM-XDMI…, UVU-NZM Moeller SK1230-1176GB http://catalog.moeller.net
Residual-current release
NZM2(-4)-XFI...
Circuit-breakers

252
265
291

29.5 22
22
22

22
29.5

29.5

87.7

70 6 103
35 108
140 149

Undervoltage releases, off-delayed


UVU-NZM
Capacitor unit
NZM-XCM
M5 X 16
78

60
50

M4 X 16

100 115 85
Dimensions 127
Size 3: Basic units
http://catalog.moeller.net Moeller SK1230-1176GB LZM3
Circuit-breaker
3 pole 166
LZMC3 120.5
NZM...3-...-4(C)NA
LZMN3
b
a
LZMS3 45 31 5

f 60
20.5
11
M10 x 30

Circuit-breakers
28 29.5
135

R 205
123.5

95
216
234
275

315.5
117

SW5 M5 x 75
f 60

45 69.7
b
a

f5 140 f5

a Blow-out space, minimum distance to other parts f 60 mm


b Minimum distance to adjacent parts f 5 mm

Circuit-breaker
4 pole 166
LZMC3-4 120.5
LZMN3-4
b a
LZMS3-4 90 31 5
f 60
20.5

M10 x 30
28 29.5

135
123.4

R 205

N
95
234
216

275

117

SW5 M5 x 75
45
f 60

69.7
a b

f5 185 f5

a Blow-out space, minimum distance to other parts f 60 mm


b Minimum distance to adjacent parts f 5 mm
128 Dimensions
Size 3: accessories
NZM3…-XK, NZM3…-XIP…, NZM3-XST… Moeller SK1230-1176GB http://catalog.moeller.net
Box terminal Tunnel terminal
(+)NZM3(-4)-XKC(O)(U) NZM3(-4)-XKA1(2)
IP2X protection against contact with a finger
NZM3(-4)-XIPK
75 54
26.5 31 F 18.7 25 32 27
Circuit-breakers

M12
SW 8

25

35 25
SW 8 SW 8

80
M10 x 30
172
124

124
SW 5
140
185

140
185

Covers Control circuit terminal


NZM3(-4)-XKSA NZM3/4-XSTS
Cable lug NZM-XSTK
NZM3-XKS185
IP2X protection against contact with a finger
NZM3(-4)-XIPA

M10 x 30
148

SW 8
124

149
459

140 a
253

185 b
96

140 103
185

a 3 pole
b 4 pole
Dimensions 129
Size 3: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM3…XK…
Connection width extension
NZM3(-4)-XKV70
Terminals 70 70
NZM3(-4)-XK22X21 45 26.5 37 24
NZM3(-4)-XK300 33 70 70 70 6
43 20 50 18 50 6
o 13

Circuit-breakers
a
M10 x 30
o 6.4
5.75
11.5
28

123.5
401

616

295
401
433

433
295

200
b

45 45 45 45 45 49
140 24 185 36.5
188 258
255 325

a NZM3(-4)-XK22X21
b NZM3(-4)-XK300
Connection on rear
(+)NZM3(-4)-XKR(O)(U)
45 45 45
SW 8 o 30
123.5

124
117

247
234

112
11 11 57
22

140 3–5 M5
o 11 90
185

M10 x 35 45 45
o 28

o 30
10

124
117
234

247

M5
22
45
130 Dimensions
Size 3: accessories
NZM3…-XKP, NZM3-XAB, NZM3-XBR Moeller SK1230-1176GB http://catalog.moeller.net
Phase isolators
NZM3-4-XKP
Circuit-breakers

616
599
200

161.6

3.5 100

45
90
210
255

Spacers Insulating surrounds


NZM3-XAB NZM3-XBR a Mounting aperture

138 9.5
17.5 1.5 – 5
ZFS...-NZM7

110
132
64

NZM3-XAB
177

162
193.5 23

10
17.5
Dimensions 131
Size 3: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM3-XDV…, NZM3-XTVD…
Rotary drive
Rotary handle on circuit-breaker
NZM3-XDV
NZM3-XDVR a
d

b
d=4–8
b f 34
a Up to 3 padlocks
105

F82.6
7
R8

Circuit-breakers
124
95

140
185

Door coupling rotary handle


NZM3-XTVD(V)(R)...
95
27.5

ZFS...-NZM7

o8
23

40
85

71
o

R87

71
85

2–5
35

d
b

d=4–8
b f 34
a Up to 3 padlocks
132 Dimensions
Size 3: accessories
NZM3-XTVD… Moeller SK1230-1176GB http://catalog.moeller.net
Door coupling rotary handle with extension shaft
NZM3-XTVD(V)(R)
NZM3/4-XV4(6)

2–5 95
X 27
8
Circuit-breakers

59
o 60
32.5

36 23g0.5
NZM3/4-XV4(6)

29

Part no. x
NZM3/4-XV4 270 – 400
NZM3/4-XV6 400 – 600

NZM3-XTVD(V)(R)-60 NZM3-XTVD(V)(R)-0

18 – 60
42 – 77.5

NZM3/4-XV... a

199.5 – 235 23g0.5


235 – 277 23g0.5

a Special tip

Minimum door coupling rotary handle clearance from door pivot point

NZM...3-... f 180
Dimensions 133
Size 3: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM3-XS…
Main switch assembly kit for side panel mounting
NZM3-XS(R)-L

105

Circuit-breakers
2–5 86 – 433 195
95 2–5

NZM3-XS(R)-R

105

39.1 24.1

86 – 433 2–5 195


95 2–5
134 Dimensions
Size 3: accessories
NZM3-XMV, NZM3-XTVD…, NZM3-XDV Moeller SK1230-1176GB http://catalog.moeller.net
Mechanical interlock
NZM3-XMV + NZM3-XDV(R)

34.5
Circuit-breakers

105

73.2
50
95
47.5

50
96.5

20
99 5

140 40
185 196 69

NZM3-XMV + NZM3-XTVD(V)(R)

NZM3/4-XV4(NZM3/4-XV6)

305 – 400(400 – 600)

NZM3-XMV + NZM3-XTVD(V)(R)-60 NZM3-XMV + NZM3-XTVD(V)(R)-0

a
NZM3/4-XV...

270 – 312 235 – 270

a Special tip
Dimensions 135
Size 3: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM3-XCI…, NZM3-XAD…
Insulated enclosures Component adapter
NZM3-XCI48-TD NZM3-XAD550
80

270
229

Circuit-breakers
32.5

910
750

45 45 38
375

140 63

29 60
190 275
375 369
136 Dimensions
Size 3: accessories
NZM3-X… Moeller SK1230-1176GB http://catalog.moeller.net
Remote operator
NZM3-XR...
358
d

b
260.5 d=4–8
b f 34
60.5 143.5
a Up to 3 padlocks
NZM3-XAVPR
5.5

10
Circuit-breakers

17

28
F 13

140
a

95

291.5
b

140 70
140
185

Withdrawable unit
+NZM3(-4)-XAV
309 d
299 e
271 f

225.5 5
91
25

175.8

171

30
R1
200

341.6
313.5
170.8

130
151.8

c
25

SW 8 M10 x 30
45 31
96 400
200 a 520
227 a
250 b
272 b

a 3-pole d withdrawn
d
b

b 4-pole d=4–8 e test


b f 34 f connected
c Up to 3 padlocks
Dimensions 137
Size 4: Basic units
http://catalog.moeller.net Moeller SK1230-1176GB LZM4
Circuit-breaker
3 pole
LZMN4 207
LZMS4 204 138
70 33 8

ba

Circuit-breakers
f 100

44
108

119
171.5
180

313
401

117
21
87.5

F
15

o 10.5 M5 x 110
b
15

45 25 100 100
f 15 70 f 15
210

a Blow out area, minimum distance to other parts f 100 mm up to 690 V


b Minimum distance to adjacent parts f 15 mm
138 Dimensions
Size 4: accessories
LZM4, LZM4…-XK Moeller SK1230-1176GB http://catalog.moeller.net
Circuit-breaker
4 pole
LZMN4-4 207
LZMS4-4 138
33 8
140

b
a
Circuit-breakers

f 100

44
108

119
171.5
180

21
117
313
401

N
87.5
15

M5 x 110
o 10.5
b
15

100 100
45 70 25
f 15 f 15
280

a Blow out area, minimum distance to other parts f 100 mm up to 690 V


b Minimum distance to adjacent parts f 15 mm

Covers Tunnel terminal


NZM4(-4)-XKSA NZM4-4-XKA
c 60
128
f 100

53 32

c
108.5

f 100

4 x SW8
73.5

25

M10 x 60
2 x SW16
30.5
531

171.5

210 a
280 b

210 a
280 b

a 3 pole
b 4 pole
c Clearance from conductive parts f 100 mm up to 690 V
Dimensions 139
Size 4: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM4…-XKM
Screw connection
Module plate Flat cable terminal Part no. a b
Single hole NZM4(-4)-XKB NZM4(-4)-XKM1 36 47
NZM4(-4)-XKM1 NZM4(-4)-XKM2 32 40
2-hole NZM4(-4)-XKB – 47
NZM4(-4)-XKM2
43 40 50 a 3 pole

Circuit-breakers
43 b 4 pole
25
c Clearance from conductive parts f 100 mm up to
690 V

NZM4-XKM2 NZM4(-4)-XKB NZM4(-4)-XKB


o 11 SW5
M10 × 50
b

SW16
a

NZM4-XKM1
171.5

210 a
280 b

Module plate
2 holes, vertical
NZM4(-4)-XKM2S...
33
o 13
70 70 70 70 70 x
o 13
16

16

M 10 x 50
32
32

SW16
171.5
486
518
486
518

50 50

210 280

Part no. x
NZM4(-4)-XKM2S-1250 12
NZM4(-4)-XKM2S-1600 20
140 Dimensions
Size 4: accessories
NZM4-XKV… Moeller SK1230-1176GB http://catalog.moeller.net
Connection width extension
NZM4-XKV95 NZM4-XKV110
95 95 107.5 107.5 48
50 77 18 50 77 30.5 15
o 11 o 11

M10 x 50
15

15
Circuit-breakers

SW16

171.5
543
573
543
573

30 30
210 28.5 210 41
267 292

NZM4-4-XKV95 NZM4-4-XKV120
95 47.5 47.5 95
18 18 18 122 122 122
48
50 77 80 42 42 42
o 11 15
30 o 11 50

M10 x 50
15
15

171.5
543
573

595
625

30 18 30
41 280 83
362 446
Dimensions 141
Size 4: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM4(-4)-XKP, NZM4(-4)-XKR
Connection on rear
NZM4(-4)-XKR Fitting on mounting plate
278
139 Rear connection possible also with
rotation by 90°.
SW16
a 3 pole
M10 x 30
b 4 pole

72

Circuit-breakers
172

180
411
88
30
15
M5

206
9.5

210 a 16
70
280 b 3-5
140

208
o 11
104
25
45

72

180
411
87.5

M5
205.5

35
70

Phase isolators
NZM4-4-XKP
190

3.5 114
70
140
142 Dimensions
Size 4: accessories
NZM4-XDV…, NZM4-XTVD… Moeller SK1230-1176GB http://catalog.moeller.net
Rotary handle on circuit-breaker
NZM4-XDV(R)
57 69
204 5
33
Circuit-breakers

221.5
a

f 89.5
73.5

R 137
117
58.5

60.5

162
210
280

d
b

d=4–8
b f 34
a Up to 3 padlocks

Door coupling rotary handle


NZM4-XTVD(V)(R)...
70

ZFS...-NZM7 18
o8
23

40

71
85

85 R1
37 71

a
a Up to 3 padlocks
d
b

d=4–8
b f 34
Dimensions 143
Size 4: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM4-XTVD…, NZM4…-XV, NZM4-XS…
Door coupling rotary handle with extension shaft
NZM4-XTVD(V)(R)
NZM3/4-XV4(6)
300 – 400(400 – 600)
2–5 95
5 27
59 8

Circuit-breakers
o 60
21

36 23g0.5

NZM3/4-XV4(NZM3/4-XV6)

57

NZM4-XTVD(V)(R)-60 NZM4-XTVD(V)(R)-0

18 – 60 42 – 77.5

NZM3/4-XV... a
270 – 312 23g0.5 234.5– 270 23g0.5

a Special tip
Minimum door coupling rotary handle clearance from door pivot point

NZM...4-... f 180

Main switch mounting kits for side-wall mounting


NZM4-XS(R)-L
NZM4-XS(R)-R
229

86 – 433 34.1
2–5 24.1
221.5

100
144 Dimensions
Size 4: accessories
NZM4-XBR, NZM4-XMV, NZM4-X… Moeller SK1230-1176GB http://catalog.moeller.net
Insulating surrounds
NZM4-XBR
9.5 a Mounting aperture
1.5 – 5
Circuit-breakers

ZFS...-NZM7

a
154

125
64

246
231 23
262.5

10
17.5

Mechanical interlock
NZM4-XMV + NZM4-XDV(R)
34.5
221.5

73.2
50
95

50
47.5

20
5
162 40
210 230 69
280

NZM4-XMV + NZM4-XTVD(V)(R) NZM4-XMV + NZM4-XTVD(V)(R)-60

NZM3/4-XV4(NZM3/4-XV6)
NZM3/4-XV...

335 – 400(400 – 600) 305 – 347


Dimensions 145
Size 4: accessories
http://catalog.moeller.net Moeller SK1230-1176GB NZM4-XMV, NZM4-X…
Mechanical interlock
NZM4-XMV + NZM4-XTVD(V)(R)-0

Circuit-breakers
270 – 305

a Special tip

Remote operator
NZM4-XR…
435.2
313.4
175.4

12.5
204 F13.4

19.4

306.4
45.5
55.6

189

454.4
117

a
84.4

189.5 189.5
208 208
210 280

d
b

d=4–8
b f 34
a Up to 3 padlocks
Remote operator folded
146 Dimensions
Size 4: accessories
NZM4…-XAV Moeller SK1230-1176GB http://catalog.moeller.net
Withdrawable unit
+NZM4-4-XAV

353.5 d
341 e
313 f
243 8
Circuit-breakers

M6 x 12
25 25

217
274.5

30
R1
300

509
451

c
25 25

70 131 33
275 560
297 a 680
350
367 b

a 3-pole d Disconnected
d
b 4-pole e Test
b

d=4–8
b f 34
f Connected
c Up to 3 padlocks

Das könnte Ihnen auch gefallen