Sie sind auf Seite 1von 26

ICC-ES Evaluation Report ESR-2262*

Reissued July 1, 2012


This report is subject to renewal August 1, 2014.

www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ®

DIVISION: 03 00 00—CONCRETE The Hilti HIT-HY 150 MAX Adhesive Anchoring System
Section: 03 16 00—Concrete Anchors may be used with continuously threaded rod, Hilti HIS-N
and HIS-RN internally-threaded inserts or deformed
DIVISION: 05 00 00—METALS reinforcing bar. The primary components of the Hilti
Section: 05 05 19—Post-Installed Concrete Anchors Adhesive Anchoring System are shown in Figure 3 of this
report.
REPORT HOLDER:
The manufacturer’s printed installation instructions
(MPII), as included with each adhesive unit package, are
HILTI, INC.
shown in Figure 5 of this report.
5400 SOUTH 122ND EAST AVENUE
TULSA, OKLAHOMA 74146 3.2 Materials:
(800) 879-8000 3.2.1 Hilti HIT-HY 150 MAX Adhesive: Hilti HIT-HY 150
www.us.hilti.com MAX Adhesive is an injectable hybrid adhesive combining
HiltiTechEng@us.hilti.com urethane methacrylate resin, hardener, cement and water.
The resin and cement are kept separate from the hardener
EVALUATION SUBJECT: and water by means of a dual-cylinder foil pack attached to
a manifold. The two components combine and react when
HILTI HIT-HY 150 MAX ADHESIVE ANCHORING SYSTEM dispensed through a static mixing nozzle attached to the
IN UNCRACKED CONCRETE manifold. Hilti HIT-HY 150 MAX is available in 11.1-ounce
(330 ml), 16.9-ounce (500 ml), and 47.3-ounce (1400 ml)
1.0 EVALUATION SCOPE foil packs. The manifold attached to each foil pack is
Compliance with the following codes: stamped with the adhesive expiration date. The shelf life,
® as indicated by the expiration date, applies to unopened
 2009 and 2006 International Building Code (IBC) foil packs that are stored in accordance with the MPII, as
®
 2009 and 2006 International Residential Code (IRC) illustrated in Figure 5 of this report.

Property evaluated: 3.2.2 Hole Cleaning Equipment: Hole cleaning


equipment comprised of steel wire brushes and air nozzles
Structural is illustrated in Figure 5 of this report.
2.0 USES 3.2.3 Dispensers: Hilti HIT-HY 150 MAX must be
dispensed with manual dispensers, pneumatic dispensers,
The Hilti HIT-HY 150 MAX Adhesive Anchoring System is
or electric dispensers provided by Hilti.
used to resist static, wind, or earthquake (Seismic Design
Categories A and B only) tension and shear loads in 3.2.4 Anchor Elements:
uncracked normal-weight concrete having a specified 3.2.4.1 Threaded Steel Rods: The threaded steel rods
compressive strength, f′c, of 2,500 psi to 8,500 psi must be clean, continuously threaded rods (all-thread) in
(17.2 MPa to 58.6 MPa). diameters as described in Tables 2 and 3 of this report.
The anchor system is an alternative to cast-in-place Steel design information for common grades of threaded
anchors described in Sections 1911 and 1912 of the 2009 rod and associated nuts are provided in Tables 7 and 10,
and 2006 IBC. The anchor systems may also be used and instructions for use are shown in Figure 5. Carbon
where an engineered design is submitted in accordance steel threaded rods must be furnished with a 0.0002-inch-
with Section R301.1.3 of the IRC. thick (0.005 mm) zinc electroplate coating in accordance
with ASTM B633 SC 1; or must be hot-dipped galvanized
3.0 DESCRIPTION in accordance with ASTM A153, Class C or D. Threaded
3.1 General: rods must be straight and free of indentations or other
defects along their length. The ends may be stamped with
The Hilti HIT-HY 150 MAX Adhesive Anchoring System is identifying marks and the embedded end may be blunt cut
comprised of the following components: or cut on the bias (chisel point).
 Hilti HIT-HY 150 MAX adhesive packaged in foil packs. 3.2.4.2 Steel Reinforcing Bars: Steel reinforcing bars
are deformed reinforcing bars as described in Table 6 of
 Adhesive mixing and dispensing equipment.
this report. Table 19, Table 22 and Table 25, along with the
 Hole cleaning equipment. instructions for use shown in Figure 5 of this report,
*Revised January 2014

ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000

Copyright © 2014 Page 1 of 25


ESR-2262 | Most Widely Accepted and Trusted Page 2 of 24

summarize reinforcing bar size ranges. The embedded accordance with ACI 318 D.5.1.2 and the associated
portions of reinforcing bars must be straight, and free of strength reduction factors, , in accordance with ACI 318
mill scale, rust, mud, oil, and other coatings that may D.4.3 are provided in the tables outlined in Table 1 for the
impair the bond with the adhesive. Reinforcing bars must corresponding anchor steel.
not be bent after installation except as set forth in Section
7.3.2 of ACI 318, with the additional condition that the bars 4.1.3 Static Concrete Breakout Strength in Tension:
must be bent cold, and heating of reinforcing bars to The nominal static concrete breakout strength of a single
facilitate field bending is not permitted. anchor or group of anchors in tension, Ncb or Ncbg, must be
calculated in accordance with ACI 318 D.5.2 with the
3.2.4.3 HIS-N and HIS-RN Inserts: Hilti HIS-N and following addition:
HIS-RN inserts have a profile on the external surface and
are internally threaded. Tensile properties for HIS-N and The basic concrete breakout strength of a single anchor
HIS-RN inserts are provided in Table 4 of this report. The in tension, Nb, must be calculated in accordance with ACI
inserts are available in diameters as shown in Table 13 318 D.5.2.2 using the values of kc,uncr as provided in Tables
and Table 16, and the instructions for use are shown in 8, 11, 14, 17, 20, 23, and 26of this report. Where analysis
Figure 5 of this report. HIS-N inserts are produced from indicates no cracking in accordance with ACI 318 D.5.2.6,
carbon steel and furnished either with a 0.0002-inch-thick Nb must be calculated using kc,uncr and Ψc,N = 1.0. See
(0.005 mm) zinc electroplated coating complying with Table 1. For anchors in lightweight concrete, see ACI
ASTM B633 SC 1, or a hot-dipped galvanized coating 318-11 D.3.6. The value of f′c used for calculation must be
complying with ASTM A153, Class C or D. The stainless limited to 8,000 psi (55 MPa) in accordance with ACI 318
steel HIS-RN inserts are fabricated from X5CrNiMo17122 D.3.7. Additional information for the determination of
K700 steel complying with DIN 17440 (EN 10088). nominal bond strength in tension is given in Section 4.1.4
Specifications for common bolt types that may be used in of this report.
conjunction with HIS-N and HIS-RN inserts are provided in 4.1.4 Static Bond Strength in Tension: The nominal
Table 5. Bolt grade and material type (carbon, stainless) static bond strength of a single adhesive anchor or group
must be matched to the insert. Strength reduction factors, of adhesive anchors in tension, Na or Nag, must be
, corresponding to brittle steel elements must be used for calculated in accordance with ACI 318-11 D.5.5. Bond
HIS-N and HIS-RN inserts. strength values are a function of the concrete compressive
3.2.4.4 Ductility: In accordance with ACI 318 D.1, in strength, the concrete temperature range, and the
order for a steel element to be considered ductile, the installation conditions (dry or water-saturated concrete).
tested elongation must be at least 14 percent and The resulting characteristic bond strength shall be
reduction of area must be at least 30 percent. Steel multiplied by the associated strength reduction factor nn as
elements with a tested elongation of less than 14 percent follows:
or a reduction of area less than 30 percent, or both, are
considered brittle. Values for various steel materials are ASSOCIATED
PERMISSIBLE
provided in Tables 2 through 6 of this report. Where values CONCRETE BOND STRENGTH
INSTALLATION
TYPE STRENGTH REDUCTION
are nonconforming or unstated, the steel must be CONDITIONS
FACTOR
considered brittle.
Dry uncr d
3.3 Concrete:
Uncracked
Normal-weight concrete must comply with Sections 1903 Water-saturated uncr ws
and 1905 of the IBC. The specified compressive strength
of the concrete must be from 2,500 psi to 8,500 psi Figure 2 of this report presents a bond strength design
(17.2 MPa to 58.6 MPa). selection flowchart. Strength reduction factors for
determination of the bond strength are given in Tables 9,
4.0 DESIGN AND INSTALLATION
12, 15, 18, 21, 24 and 27. See Table 1. Adjustments to the
4.1 Strength Design: bond strength may also be made for increased concrete
4.1.1 General: The design strength of anchors under the compressive strength as noted in the footnotes to the
2009 and 2006 IBC, as well as the 2009 and 2006 IRC, corresponding tables.
must be determined in accordance with ACI 318-11 (ACI 4.1.5 Static Steel Strength in Shear: The nominal static
318) and this report. steel strength of a single anchor in shear as governed by
A design example according to the 2009 IBC based on the steel, Vsa, in accordance with ACI 318 D.6.1.2 and
ACI 318-11 is given in Figure 4 of this report. strength reduction factor,, in accordance with ACI 318
D.4.3 are given in the tables outlined in Table 1 of this
Design parameters are based on the ACI report for the corresponding anchor steel.
318-11 for use with the 2009 and 2006 IBC unless noted
otherwise in Sections 4.1.1 through 4.1.11 of this report. 4.1.6 Static Concrete Breakout Strength in Shear: The
nominal static concrete breakout strength of a single
The strength design of anchors must comply with ACI
anchor or group of anchors in shear, Vcb or Vcbg, must be
318 D.4.1.
calculated in accordance with ACI 318 D.6.2 based on
Design parameters are provided in Table 7 through information given in the tables outlined in Table 1 of this
Table 27. Strength reduction factors, , as given in ACI report for the corresponding anchor steel.
318-11 D.4.3 must be used for load combinations
The basic concrete breakout strength of a single anchor
calculated in accordance with Section 1605.2.1 of the 2009
in shear, Vb, must be calculated in accordance with ACI
or 2006 IBC or Section 9.2 of ACI 318. Strength reduction
318 D.6.2.2 using the values of d given in the tables
factors, , as given in ACI 318-11 D.4.4 must be used for outlined in Table 1 for the corresponding anchor steel in
load combinations calculated in accordance with ACI 318 lieu of da (2009 IBC) and do (2006 IBC). In addition, hef
Appendix C. must be substituted for ℓe. In no case must ℓe exceed 8d.
4.1.2 Static Steel Strength in Tension: The nominal The value of f′c must be limited to a maximum of 8,000 psi
static steel strength of a single anchor in tension, Nsa, in (55 MPa) in accordance with ACI 318 D.3.7.
ESR-2262 | Most Widely Accepted and Trusted Page 3 of 24

4.1.7 Static Concrete Pryout Strength in Shear: The dimensions, hole cleaning procedures, anchor spacing,
nominal static pryout strength of a single anchor or group edge distances, concrete thickness, anchor embedment,
of anchors in shear, Vcp or Vcpg, shall be calculated in tightening torque and adherence to the manufacturer’s
accordance with ACI 318 D.6.3. printed installation instructions. The special inspector
must verify the initial installations of each type and size
4.1.8 Interaction of Tensile and Shear Forces: For
of adhesive anchor by construction personnel on-site.
designs that include combined tension and shear, the
Subsequent installations of the same anchor type and size
interaction of tension and shear loads must be calculated
by the same construction personnel shall be permitted to
in accordance with ACI 318 D.7.
be performed in the absence of the special inspector. Any
4.1.9 Minimum Member Thickness, hmin, Anchor change in the anchor product being installed or the
Spacing, smin, and Edge Distance, cmin: In lieu of ACI personnel performing the installation requires an initial
318 D.8.1 and D.8.3, values of smin and cmin described in inspection. For ongoing installations over an extended
this report must be observed for anchor design and period, the special inspector shall make regular inspections
installation. In lieu of ACI 318 D.8.5, the minimum member to confirm correct handling and installation of the product.
thicknesses, hmin, described in this report must be
Continuous special inspection of adhesive anchors
observed for anchor design and installation. For adhesive
installed in horizontal or upwardly inclined orientations to
anchors that will remain untorqued, ACI 318 D.8.4 applies.
resist sustained tension loads shall be performed in
For the edge distance cai and anchor spacing sai, the accordance with ACI 318 D.9.2.4.
maximum torque T′max shall comply with the following
Under the IBC, additional requirements as set forth in
requirements:
Sections 1705, 1706, or 1707 must be observed, where
REDUCED INSTALLATION TORQUE Tmax,red applicable.
FOR EDGE DISTANCES cai < (5 X da) 5.0 CONDITIONS OF USE
Minimum Anchor Maximum The Hilti HIT-HY 150 MAX Adhesive Anchoring System
Edge Distance cai
Spacing, sai Torque, Tmax,red described in this report is a suitable alternative to what is
specified in, those codes listed in Section 1.0 of this report,
5 x da ≤ sai < 16 in. 0.3 x Tmax subject to the following conditions:
1.75 in. (45 mm) ≤
cai < 5 x da
sai ≥ 16 in. (406 mm) 0.5 x Tmax 5.1 The Hilti HIT-HY 150 MAX Adhesive Anchoring
System must be installed in accordance with the
4.1.10 Critical Edge Distance cac: In lieu of ACI 318 manufacturer’s printed installation instructions as
D.8.6, cac must be determined as follows: included in the adhesive packaging and illustrated in
Figure 5 of this report.
5.2 Anchors are limited to installation in concrete that is
τuncr 0.4 h uncracked and may be expected to remain uncracked
cac =hef · · 3.1-0.7 (D-43)
1160 hef for the service life of the anchor. The anchors must be
where installed in uncracked normal-weight concrete having
a specified compressive strength f′c = 2,500 psi to
need not be taken as larger than 2.4; and 8,500 psi (17.2 MPa to 58.6 MPa).
5.3 The values of f′c used for calculation purposes must
τuncr = characteristic bond strength stated in the table of not exceed 8,000 psi (55 MPa).
this report where by τuncr need not be taken as larger than:
5.4 Anchors must be installed in concrete base materials
in holes predrilled in accordance with the instructions

provided in Figure 5 of this report.

4.1.11 Requirements for Seismic Design: The anchors 5.5 Loads applied to the anchors must be adjusted in
may be used to resist seismic loads for structures accordance with Section 1605.2 of the IBC for
classified as Seismic Design Categories A and B under the strength design.
IBC or IRC only. 5.6 Hilti HIT-HY 150 MAX adhesive anchors are
4.2 Installation: recognized for use to resist short- and long-term
loads, including wind and earthquake (Seismic Design
Installation parameters are illustrated in Figure 1 of this Categories A and B only), subject to the conditions of
report. Installation must be in accordance with ACI 318-11 this report.
D.9.1 and D.9.2. Anchor locations must comply with this
5.7 Strength design values must be established in
report and the plans and specifications approved by the
accordance with Section 4.1 of this report.
code official. Installation of the Hilti HIT-HY 150 MAX
Adhesive Anchor System must conform to the 5.8 Minimum anchor spacing and edge distance as well
manufacturer’s printed installation instructions (IFU) as minimum member thickness must comply with the
included in each unit package as provided in Figure 5 of values given in this report.
this report.
5.9 Prior to anchor installation, calculations and details
4.3 Special Inspection: demonstrating compliance with this report must be
submitted to the code official. The calculations and
Periodic special inspection must be performed where
details must be prepared by a registered design
required in accordance with Sections 1704.4 and 1704.15
professional where required by the statutes of the
of the 2009 IBC or Section 1704.13 of the 2006 IBC and
jurisdiction in which the project is to be constructed.
this report. The special inspector must be on the jobsite
initially during anchor installation to verify anchor type, 5.10 Anchors are not permitted to support fire-resistive
anchor dimensions, concrete type, concrete compressive construction. Where not otherwise prohibited by the
strength, adhesive identification and expiration date, hole code, the Hilti HIT-HY 150 MAX Adhesive Anchoring
ESR-2262 | Most Widely Accepted and Trusted Page 4 of 24

System is permitted for installation in fire-resistive 5.16 Installation of anchors in horizontal or upwardly
construction provided that at least one of the following inclined orientations to resist sustained tension loads
conditions is fulfilled: shall be performed by personnel certified by an
applicable certification program in accordance with
 Anchors are used to resist wind or seismic forces
ACI 318 D.9.2.2 or D.9.2.3.
only
 Anchors that support gravity load–bearing 5.17 Hilti HIT-HY 150 MAX adhesive is manufactured by
structural elements are within a fire-resistive Hilti GmbH, Kaufering, Germany, under a quality
envelope or a fire-resistive membrane, are control program with inspections by ICC-ES.
protected by approved fire-resistive materials, or 5.18 Hilti HIS-N and HIS-RN inserts are manufactured by
have been evaluated for resistance to fire exposure Hilti (China) Ltd., Guangdong, China, under a quality
in accordance with recognized standards control program with inspections by ICC-ES.
 Anchors are used to support nonstructural 6.0 EVIDENCE SUBMITTED
elements.
Data in accordance with the ICC-ES Acceptance Criteria
5.11 Since an ICC-ES acceptance criteria for evaluating for Post-installed Adhesive Anchors in Concrete Elements
data to determine the performance of adhesive (AC308), dated February 2013, including but not limited to
anchors subjected to fatigue or shock loading is tests under freeze–thaw conditions (Table 4.2, test series
unavailable at this time, the use of these anchors 6).
under such conditions is beyond the scope of this
report. 7.0 IDENTIFICATION
5.12 Use of zinc-plated carbon steel threaded rods, 7.1 The adhesives are identified by packaging labeled
zinc-plated HIS-N inserts, or steel reinforcing bars is with the manufacturer’s name (Hilti, Inc.) and address,
limited to dry, interior locations. anchor name, anchor size, evaluation report number
5.13 Use of hot-dipped galvanized carbon steel rods, or (ESR-2262), and the name of the inspection body
hot-dipped galvanized carbon steel or stainless steel (ICC-ES).
HIS-RN inserts, is permitted for exterior exposure or 7.2 HIS-N and HIS-RN inserts are identified by packaging
damp environments. labeled with the manufacturer’s name (Hilti, Inc.) and
5.14 Steel anchoring materials in contact with preservative- address, anchor name, and evaluation report number
treated and fire-retardant treated wood must be of (ESR-2262).
zinc-coated carbon steel or stainless steel. The 7.3 Threaded rods, nuts, washers, bolts, cap screws, and
minimum coating weights for zinc-coated steel must deformed reinforcing bars are standard elements and
comply with ASTM A153. must conform to applicable national or international
5.15 Periodic special inspection must be provided in specifications as set forth in Tables 2 through 6.
accordance with Section 4.3 of this report. Continuous
special inspection for anchors installed in horizontal or
upwardly inclined orientations to resist sustained
tension loads must be provided in accordance with
Section 4.3 of this report.

c BOLT OR
STUD Tmax
HILTI HIS-N/HIS-RN
ALL-THREAD Tmax INTERNALLY
OR REBAR s THREADED
INSERT

c
hs
d
hef d
hef
h h

do
do

THREADED ROD / REINFORCING BAR HIS-N AND HIS-RN INSERTS


FIGURE 1—INSTALLATION PARAMETERS
ESR-2262 | Most Widely Accepted and Trusted Page 5 of 24

TABLE 1—DESIGN TABLE INDEX


1
DESIGN STRENGTH THREADED ROD HILTI HIS INTERNALLY DEFORMED REINFORCEMENT
THREADED INSERT
Fractional Metric Fractional Metric USA EU Canadian
Steel Nsa, Vsa Table 7 Table 10 Table 13 Table 16 Table 19 Table 22 Table 25
Concrete Ncb, Ncbg, Vcb, Vcbg, Vcp, Vcpg Table 8 Table 11 Table 14 Table 17 Table 20 Table 23 Table 26
2
Bond Na, Nag Table 9 Table 12 Table 15 Table 18 Table 20 Table 24 Table 27
1
Design strengths are as set forth in ACI 318 D.4.1.1.
2
See Section 4.1 of this report for bond strength information.

FIGURE 2—FLOWCHART FOR ESTABLISHMENT OF DESIGN BOND STRENGTH

1
TABLE 2—TENSILE PROPERTIES OF COMMON CARBON STEEL THREADED ROD MATERIALS

THREADED ROD SPECIFICATION MINIMUM MINIMUM fUTA/fYA MINMUM MINIMUM SPECIFICATION


6
SPECIFIED SPECIFIED ELONGATION, REDUCTION FOR NUTS
5
ULTIMATE YIELD PERCENT OF AREA,
STRENGTH STRENGTH PERCENT
fUTA 0.2%
OFFSET, fYA
2
ASTM A193 Grade B7 psi 125,000 105,000 ASTM A563 Grade
1 1.19 16 50
≤ 2 /2 in. (≤ 64 mm) (MPa) (860) (725) DH
3 DIN 934 (8-A2K)
ASTM F568M Class 5.8
1 MPa 500 400
M5 ( /4 in.) to M24 (1 in.) 1.25 10 35 ASTM A563 Grade
(psi) (72,500) (58,000) 7
(equivalent to ISO 898-1) DH
4 MPa 500 400
ISO 898-1 Class 5.8 1.25 22 - DIN 934 (8-A2K)
(psi) 72,500) (58,000)
4 MPa 800 640
ISO 898-1 Class 8.8 1.25 12 52 DIN 934 (8-A2K)
(psi) (116,000) (92,800)
1
Hilti HIT-HY 150 MAX adhesive may be used in conjunction with all grades of continuously threaded carbon steel rod (all-thread) that
comply with the code reference standards and that have thread characteristics comparable with ANSI B1.1 UNC Coarse Thread Series or
ANSI B1.13M M Profile Metric Thread Series. Values for threaded rod types and associated nuts supplied by Hilti are provided here.
2
Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials for High-Temperature Service
3
Standard Specification for Carbon and Alloy Steel Externally Threaded Metric Fasteners
4
Mechanical properties of fasteners made of carbon steel and alloy steel – Part 1: Bolts, screws and studs
5
Based on 2-in. (50 mm) gauge length except ASTM A193, which are based on a gauge length of 4d and ISO 898 which is based on 5d.
6
Nuts of other grades and styles having specified proof load stresses greater than the specified grade and style are also suitable. Nuts must
have specified proof load stresses equal to or greater than the minimum tensile strength of the specified threaded rod.
7
Nuts for fractional rods.
ESR-2262 | Most Widely Accepted and Trusted Page 6 of 24
1
TABLE 3—TENSILE PROPERTIES OF COMMON STAINLESS STEEL THREADED ROD MATERIALS

THREADED ROD SPECIFICATION MINIMUM MINIMUM fUTA/fYA MINIMUM MINIMUM SPECIFICATION


4
SPECIFIED SPECIFIED ELONGATION, REDUCTION FOR NUTS
ULTIMATE YIELD PERCENT OF AREA,
STRENGTH STRENGTH PERCENT
fUTA 0.2%
OFFSET, fYA
2 psi 100,000 65,000
ASTM F593 CW1 (316)
1 5 1.54 20 — F 594
/4 to /8 in. (MPa) (690) (450)
2 psi 85,000 45,000
ASTM F593 CW2 (316)
3 1 1.89 25 — F 594
/4 to 1 /2 in. (MPa) (585) (310)
3 MPa 700 450
ISO 3506-1 A4-70
1.56 40 — ISO 4032
M8 – M24 (psi) (101,500) (65,250)
3 MPa 500 210
ISO 3506-1 A4-50
2.38 40 — ISO 4032
M27 – M30 (psi) (72,500) (30,450)
1
Hilti HIT-HY 150 MAX may be used in conjunction with all grades of continuously threaded stainless steel rod (all-thread) that comply with
the code reference standards and that have thread characteristics comparable with ANSI B1.1 UNC Coarse Thread Series or ANSI B1.13M
M Profile Metric Thread Series. Values for threaded rod types and associated nuts supplied by Hilti are provided here.
2
Standard Steel Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
3
Mechanical properties of corrosion-resistant stainless steel fasteners – Part 1: Bolts, screws and studs
4
Nuts of other grades and styles having specified proof load stresses greater than the specified grade and style are also suitable. Nuts must
have specified proof load stresses equal to or greater than the minimum tensile strength of the specified threaded rod.

TABLE 4—TENSILE PROPERTIES OF FRACTIONAL AND METRIC HIS-N AND HIS-RN INSERTS

MINIMUM SPECIFIED ULTIMATE MINIMUM SPECIFIED


HILTI HIS-N AND HIS-RN INSERTS
STRENGTH, futa YIELD STRENGTH, fya
Carbon Steel MPa 490 410
DIN EN 10277-3 11SMnPb30+c or DIN
1561 9SMnPb28K (psi) (71,050) (59,450)
3
/8 and M8 to M10
Carbon Steel MPa 460 375
DIN EN 10277-3 11SMnPb30+c or DIN
1561 9SMnPb28K (psi) (66,700) (54,375)
1 3
/2 to /4 and M12 to M20
Stainless Steel MPa 700 350
DIN 17440 (EN 10088-3)
X5CrNiMo 17-12-2 (psi) (101,500) (50,750)

TABLE 5—TENSILE PROPERTIES OF COMMON BOLTS, CAP SCREWS AND STUDS


1,2
FOR USE WITH HIS-N AND HIS-RN INSERTS

BOLT, CAP SCREW OR STUD MINIMUM MINIMUM futa/fya MINIMUM MINIMUM SPECIFICATION
6
SPECIFICATION SPECIFIED SPECIFIED ELONGATION, REDUCTION FOR NUTS
ULTIMATE YIELD PERCENT OF AREA,
STRENGTH, futa STRENGTH 0.2% PERCENT
OFFSET, fya
3 psi 120,000 92,000
SAE J429 Grade 5 1.30 14 35 SAE J995
(MPa) (830) (635)
psi 120,000 92,000 A563 C, C3, D,
4 1
ASTM A325 /2 to 1-in. 1.30 14 35 DH, DH3 Heavy
(MPa) (830) (635) Hex
5
ASTM A193 Grade B8M psi 110,000 95,000
7
(AISI 316) for use with 1.16 15 45 F594
HIS-RN (MPa) (760) (655)
5
ASTM A193 Grade B8T psi 125,000 100,000
7
(AISI 321) for use with 1.25 12 35 F594
HIS-RN (MPa) (860) (690)

1
Minimum Grade 5 bolts, cap screws or studs must be used with carbon steel HIS inserts.
2
Only stainless steel bolts, cap screws or studs are permitted with HIS-RN inserts.
3
Mechanical and Material Requirements for Externally Threaded Fasteners
4
Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength
5
Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials for High-Temperature Service
6
Nuts must have specified minimum proof load stresses equal to or greater than the specified minimum full-size tensile strength of the
specified stud.
7
Nuts for stainless steel studs must be of the same alloy group as the specified stud.
ESR-2262 | Most Widely Accepted and Trusted Page 7 of 24

TABLE 6—TENSILE PROPERTIES OF COMMON REINFORCING BARS

REINFORCING BAR SPECIFICATION MINIMUM SPECIFIED MINIMUM SPECIFIED YIELD


ULTIMATE STRENGTH, futa STRENGTH, fya
1 psi 90,000 60,000
ASTM A615 Gr. 60
(MPa) (620) (415)
1 psi 60,000 40,000
ASTM A615 Gr. 40
(MPa) (415) (275)
2 MPa 550 500
DIN 488 BSt 500
(psi) (79,750) (72,500)
3 MPa 540 400
CAN/CSA-G30.18 Gr. 400
(psi) (78,300) (58,000)
1
Standard Specification for Deformed and Plain Carbon Steel Bars for Concrete Reinforcement
2
Reinforcing steel; reinforcing steel bars; dimensions and masses
3
Billet-Steel Bars for Concrete Reinforcement

1
TABLE 7—STEEL DESIGN INFORMATION FOR FRACTIONAL THREADED ROD

DESIGN INFORMATION SYMBOL UNITS NOMINAL ROD DIAMETER (inches)


3 1 5 3 7 1
/8 /2 /8 /4 /8 1 1 /4
in. 0.375 0.5 0.625 0.75 0.875 1 1.25
Rod O.D. d
(mm) (9.5) (12.7) (15.9) (19.1) (22.2) (25.4) (31.8)
2
Rod effective cross-sectional in. 0.0775 0.1419 0.2260 0.3345 0.4617 0.6057 0.9691
Ase 2
area (mm ) (50) (92) (146) (216) (298) (391) (625)
lbf 5,620 10,290 16,385 24,250 33,470 43,910 70,260
Nsa
ISO 898-1 Class 5.8

Nominal strength as (kN) (25.0) (45.8) (72.9) (107.9) (148.9) (195.3) (312.5)
governed by steel
strength lbf 2,810 6,175 9,830 14,550 20,085 26,345 42,155
Vsa
(kN) (12.5) (27.5) (43.7) (64.7) (89.3) (117.2) (187.5)
Strength reduction
 - 0.65
factor  for tension
2

Strength reduction
 - 0.60
factor  for shear
2

lbf 9,690 17,740 28,250 41,810 57,710 75,710 121,135


Nominal strength as Nsa
(kN) (43.1) (78.9) (125.7) (186.0) (256.7) (336.8) (538.8)
ASTM A193 B7

governed by steel
strength lbf 4,845 10,640 16,950 25,090 34,630 45,425 72,680
Vsa
(kN) (21.5) (47.3) (75.4) (111.6) (154.0) (202.1) (323.3)
Strength reduction
 - 0.75
factor  for tension
3

Strength reduction
 - 0.65
factor  for shear
3

lbf 7,750 14,190 22,600 28,430 39,245 51,485 82,370


Nominal strength as Nsa
(kN) (34.5) (63.1) (100.5) (126.5) (174.6) (229.0) (366.4)
ASTM F593, CW

governed by steel
lb 3,875 8,515 13,560 17,060 23,545 30,890 49,425
Stainless

strength Vsa
(kN) (17.2) (.37.9) (60.3) (75.9) (104.7) (137.4) (219.8)
Strength reduction
 - 0.65
factor  for tension
2

Strength reduction
 - 0.60
factor  for shear
2

For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897 MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Values provided for common rod material types based on published strengths and calculated in accordance with ACI 318-11 Eq. (D-2) and
Eq. (D-29). Other material specifications are admissible, subject to the approval of the code official. Nuts and washers must be appropriate
for the rod strength.
2
For use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If the load combinations of
ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4. Values correspond to a brittle
steel element.
3
For use with the load combinations of IBC Section 1605.2.1 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If the load combinations of
ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4. Values correspond to a
ductile steel element.
ESR-2262 | Most Widely Accepted and Trusted Page 8 of 24

TABLE 8—CONCRETE BREAKOUT DESIGN INFORMATION FOR FRACTIONAL THREADED ROD


1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS NOMINAL ROD DIAMETER (inches)


3 1 5 3 7 1
/8 /2 /8 /4 /8 1 1 /4
Effectiveness factor for in-lb 24 24 24 24 27 27 30
kc,uncr
uncracked concrete (SI) (10) (10) (10) (10) (11.3) (12.6) (12.6)
7 1 3 3 3 1
4 in. 1 /8 2 /2 3 /8 3 /4 4 /8 5 6 /4
Min. anchor spacing smin
(mm) (48) (64) (79) (95) (111) (127) (159)
7 1 1 3 3 1
4 in. 1 /8 2 /2 3 /8 3 /4 4 /8 5 6 /4
Min. edge distance cmin
(mm) (48) (64) (79) (95) (111) (127) (159)
1
in. hef + 1 /4 (3)
Minimum member thickness hmin hef + 2d0
(mm) (hef + 30)
Critical edge distance –
splitting cac - See Section 4.1.10 of this report.
(for uncracked concrete)
Strength reduction factor for
tension, concrete failure  - 0.65
2
modes, Condition B
Strength reduction factor for
shear, concrete failure modes,  - 0.70
2
Condition B
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897 MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
For additional setting information, see installation instructions in Figure 5.
2
Values provided for post-installed anchors with category as determined from ACI 355.4 given for Condition B. Condition B applies without
supplementary reinforcement or where pullout (bond) or pryout govern, as set forth in ACI 318 D.4.3, while condition A requires supplemental
reinforcement. Values are for use with the load combinations of IBC Section 1605.2.1 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If
the load combinations of ACI 318 Appendix Care used, the appropriate value of must be determined in accordance with ACI 318 D.4.4.
3
d0 = hole diameter.
4 3
For installations with 1 /4-inch edge distance, refer to Section 4.1.9 for spacing and maximum torque requirements.

TABLE 9—BOND STRENGTH DESIGN INFORMATION FOR FRACTIONAL THREADED ROD


1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS NOMINAL ROD DIAMETER (IN.)


3 1 5 3 7 1
/8 /2 /8 /4 /8 1 1 /4
Characteristic bond psi 1,985 1,985 1,850 1,710 1,575 1,440 1,175
A k,uncr
Temperature

strength (MPa) (13.7) (13.7) (12.7) (11.8) (10.9) (9.9) (8.1)


2
Range

Characteristic bond psi 1,610 1,610 1,495 1,385 1,275 1,170 950
B
strength
k,uncr
(MPa) (11.1) (11.1) (10.3) (9.6) (8.8) (8.1) (6.6)
Characteristic bond psi 930 930 865 805 740 675 550
C
strength
k,uncr
(MPa) (6.4) (6.4) (6.0) (5.5) (5.1) (4.7) (3.8)
3 3 1 1 1
Minimum anchor embedment in. 2 /8 2 /4 3 /8 3 /2 3 /2 4 5
hef,min
depth (mm) (60) (70) (80) (89) (89) (102) (127)
1 1 1
Maximum anchor embedment in. 7 /2 10 12 /2 15 17 /2 20 25
hef,max
depth (mm) (191) (254) (318) (381) (445) (508) (635)

Anchor
Permissible

- 1 2
Installation
Conditions

Category
Dry concrete & Water-
saturated concrete
d & ws 0.65 0.55

For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897 MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Bond strength values correspond to concrete compressive strength range 2,500 psi ≤ f′c ≤ 4,500 psi. For 4,500 psi < f′c ≤ 6,500 psi, tabulated
characteristic bond strengths may be increased by 6 percent. For 6,500 psi < f′c ≤ 8,000 psi, tabulated characteristic bond strengths may be
increased by 10 percent.
2
Temperature range A: Maximum short term temperature = 104°F (40°C), maximum long term temperature = 75°F (24°C).
Temperature range B: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
Temperature range C: Maximum short term temperature = 248°F (120°C), maximum long term temperature = 162°F (72°C).
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete
temperatures are roughly constant over significant periods of time.
ESR-2262 | Most Widely Accepted and Trusted Page 9 of 24
1
TABLE 10—STEEL DESIGN INFORMATION FOR METRIC THREADED ROD

DESIGN INFORMATION SYMBOL UNITS NOMINAL ROD DIAMETER (mm)


8 10 12 16 20 24 27 30
mm 8 10 12 16 20 24 27 30
Rod O.D. d
(in.) (0.31) (0.39) (0.47) (0.63) (0.79) (0.94) (1.06) (1.18)
2
Rod effective cross-sectional mm 36.6 58 84.3 157 245 353 459 561
Ase 2
area (in. ) (0.057) (0.090) (0.131) (0.243) (0.380) (0.547) (0.711) (0.870)
kN 18.3 29.0 42.2 78.5 122.5 176.5 229.5 280.5
Nsa
ISO 898-1 Class 5.8

Nominal strength as (lb) (4,115) (6,520) (9,475) (17,650) (27,540) (39,680) (51,595) (63,060)
governed by steel
strength kN 9.2 14.5 25.3 47.1 73.5 105.9 137.7 168.3
Vsa
(lb) (2,060) (3,260) (5,685) (10,590) (16,525) (23,810) (30,955) (37,835)
Strength reduction factor
 - 0.65
 for tension2
Strength reduction factor
 - 0.60
 for shear2
kN 29.3 46.4 67.4 125.6 196.0 282.4 367.2 448.8
Nsa
ISO 898-1 Class. 8.8

Nominal strength as (lb) (6,580) (10,430) (15,160) (28,235) (44,065) (63,485) (82,550) (100,895)
governed by steel
strength kN 14.6 23.2 40.5 75.4 117.6 169.4 220.3 269.3
Vsa
(lb) (3,290) (5,215) (9,100) (16,940) (26,440) (38,090) (49,530) (60,540)
Strength reduction factor
 - 0.65
 for tension2
Strength reduction factor
 - 0.60
 for shear2
kN 25.6 40.6 59.0 109.9 171.5 247.1 183.1 223.8
3

Nsa
ISO 3506-1 Class A4 SS

Nominal strength as (lb) (5,760) (9,130) (13,263) (24,703) (38,555) (55,550) (41,135) (50,335)
governed by steel
strength kN 12.8 20.3 35.4 65.9 102.9 148.3 109.9 134.3
Vsa
(lb) (2,880) (4,565) (7,960) (14,825) (23,135) (33,330) (24,680) (30,200)
Strength reduction factor
 - 0.65
 for tension2

Strength reduction factor


 - 0.60
 for shear2

For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897 MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Values provided for common rod material types based on published strengths and calculated in accordance with ACI 318-11 Eq. (D-2) and
Eq. (D-29). Other material specifications are admissible, subject to the approval of the code official. Nuts and washers must be appropriate
for the rod strength.
2
For use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If the load combinations of
ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4. Values correspond to a brittle
steel element.
3
A4-70 Stainless (M8 - M24 diameters); A4-502 Stainless (M27 - M30 diameters)
ESR-2262 | Most Widely Accepted and Trusted Page 10 of 24

TABLE 11—CONCRETE BREAKOUT DESIGN INFORMATION FOR METRIC THREADED ROD


1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS NOMINAL ROD DIAMETER (mm)


8 10 12 16 20 24 27 30
Effectiveness factor for SI 10 10 10 10 10 11.3 11.3 12.6
kc,uncr
uncracked concrete (in-lb) (24) (24) (24) (24) (24) (27) (27) (30)
4 mm 40 50 60 80 100 120 135 150
Min. anchor spacing smin
(in.) (1.6) (2.0) (2.4) (3.2) (3.9) (4.7) (5.3) (5.9)
4 mm 40 50 60 80 100 120 135 150
Min. edge distance cmin
(in.) (1.6) (2.0) (2.4) (3.2) (3.9) (4.7) (5.3) (5.9)
mm hef + 30 (3)
Minimum member thickness hmin hef + 2d0
(in.) (hef + 1¼)
Critical edge distance –
splitting cac - See Section 4.1.10 of this report.
(for uncracked concrete)
Strength reduction factor for
tension, concrete failure  - 0.65
2
modes, Condition B
Strength reduction factor for
shear, concrete failure modes,  - 0.70
2
Condition B
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897 MPa
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
For additional setting information, see installation instructions in Figure 5.
2
Values provided for post-installed anchors with category as determined from ACI 355.4 given for Condition B. Condition B applies without
supplementary reinforcement or where pullout (bond) or pryout govern, as set forth in ACI 318 D.4.4, while condition A requires supplemental
reinforcement. Values are for use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If
the load combinations of ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4.
3
d0 = drill bit diameter.
4 3
For installations with 1 /4-inch edge distance, refer to Section 4.1.9 for spacing and maximum torque requirements.

TABLE 12—BOND STRENGTH DESIGN INFORMATION FOR METRIC THREADED ROD


1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS NOMINAL ROD DIAMETER (mm)


8 10 12 16 20 24 27 30
Characteristic bond MPa 13.7 13.7 13.7 12.7 11.8 10.9 9.9 8.1
A k,uncr
Temperature

strength (psi) (1,985) (1,985) (1,985) (1,850) (1,710) (1,575) (1,440) (1,175)
2
Range

Characteristic bond MPa 11.1 11.1 11.1 10.3 9.6 8.8 8.1 6.6
B k,uncr
strength (psi) (1,610) (1,610) (1,610) (1,500) (1,390) (1,275) (1,170) (950)
Characteristic bond MPa 6.4 6.4 6.4 6.0 5.5 5.1 4.7 3.8
C k,uncr
strength (psi) (930) (930) (930) (865) (805) (740) (675) (550)
Minimum anchor embedment mm 60 60 70 80 90 96 108 120
hef,min
depth (in.) (2.4) (2.4) (2.8) (3.1) (3.5) (3.8) (4.3) (4.7)
Maximum anchor embedment mm 160 200 240 320 400 480 540 600
hef,max
depth (in.) (6.3) (7.9) (9.4) (12.6) (15.7) (18.9) (21.3) (23.6)
Permissible

Anchor
Installation
Conditions

- 1 2
Category
Dry concrete & Water-
saturated concrete
d & ws - 0.65 0.55

For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.


For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Bond strength values correspond to concrete compressive strength range 2,500 psi ≤ f′c ≤ 4,500 psi. For 4,500 psi < f′c ≤ 6,500 psi,
tabulated characteristic bond strengths may be increased by 6 percent. For 6,500 psi < f′c ≤ 8,000 psi, tabulated characteristic bond
strengths may be increased by 10 percent.
2
Temperature range A: Maximum short term temperature = 104°F (40°C), maximum long term temperature = 75°F (24°C).
Temperature range B: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
Temperature range C: Maximum short term temperature = 248°F (120°C), maximum long term temperature = 162°F (72°C).
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete
temperatures are roughly constant over significant periods of time.
ESR-2262 | Most Widely Accepted and Trusted Page 11 of 24
1
TABLE 13—STEEL DESIGN INFORMATION FOR FRACTIONAL HILTI HIS-N AND HIS-RN INSERTS

DESIGN INFORMATION SYMBOL UNITS NOMINAL BOLT/CAP SCREW DIAMETER (inch)


3 1 5 3
/8 /2 /8 /4
in. 0.65 0.81 1 1.09
HIS insert O.D. d
(mm) (16.5) (20.5) (25.4) (27.6)
2
Bolt effective cross-sectional in. 0.0775 0.1419 0.2260 0.3345
Ase 2
area (mm ) (50) (92) (146) (216)
2
HIS insert effective cross- in. 0.178 0.243 0.404 0.410
Ainsert 2
sectional area (mm ) (115) (157) (260) (265)
lb 9,690 17,740 28,250 41,815
Nominal strength as Nsa
governed by steel (kN) (43.1) (78.9) (125.7) (186.0)
strength – ASTM A193 lb 5,815 10,645 16,950 25,090
3
ASTM A193 B7

B7 bolt/cap screw Vsa


(kN) (25.9) (47.3) (75.4) (111.6)
Nominal strength as lb 12,650 16,195 26,925 27,360
governed by steel Nsa
strength – HIS-N insert (kN) (56.3) (72.0) (119.8) (121.7)
Strength reduction factor
 - 0.65
 for tension2
Strength reduction factor
 - 0.60
 for shear2
Nominal strength as lb 8,525 15,610 24,860 36,795
governed by steel Nsa
(kN) (37.9) (69.4) (110.6) (163.7)
ASTM A193 Gr. B8M SS

strength – ASTM A193


Grade B8M SS bolt/cap lb 5,115 9,365 14,915 22,075
Vsa
screw (kN) (22.8) (41.7) (66.3) (98.2)
Nominal strength as lb 17,165 23,430 38,955 39,535
governed by steel Nsa
strength – HIS-RN insert (kN) (76.3) (104.2) (173.3) (175.9)
Strength reduction factor
 - 0.65
 for tension2
Strength reduction factor
 - 0.60
 for shear2

For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.


For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Values provided for common rod material types based on published strengths and calculated in accordance with ACI 318-11 Eq. (D-2) and
Eq. (D-29). Other material specifications are admissible, subject to the approval of the code official. Nuts and washers must be appropriate
for the rod strength.
2
For use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If the load combinations of
ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4. Values correspond to a brittle
steel element.
For the calculation of the design steel strength in tension and shear for the bolt or screw, the  factor for ductile steel failure according to ACI
3

318 D4.3 may be used.


ESR-2262 | Most Widely Accepted and Trusted Page 12 of 24
1
TABLE 14—CONCRETE BREAKOUT DESIGN INFORMATION FOR FRACTIONAL HILTI HIS-N AND HIS-RN INSERTS

DESIGN INFORMATION SYMBOL UNITS NOMINAL BOLT/CAP SCREW DIAMETER (inch)


3 1 5
/8 /2 /8 ¾
3 1
in. 4 /8 5 6¾ 8 /8
Effective embedment depth hef
(mm) (110) (125) (170) (205)
Effectiveness factor for in-lb 24
kc,uncr
uncracked concrete (SI) (10)
1 1
3 in. 3 /4 4 5 5 /2
Min. anchor spacing smin
(mm) (83) (102) (127) (140)
1 1
3 in. 3 /4 4 5 5 /2
Min. edge distance cmin
(mm) (83) (102) (127) (140)
in. 5.9 6.7 9.1 10.6
Minimum member thickness hmin
(mm) (150) (170) (230) (270)
Critical edge distance –
splitting cac - See Section 4.1.10 of this report.
(for uncracked concrete)
Strength reduction factor for
tension, concrete failure  - 0.65
2
modes, Condition B
Strength reduction factor for
shear, concrete failure modes,  - 0.70
2
Condition B
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
For additional setting information, see installation instructions in Figure 5.
2
Values provided for post-installed anchors with category as determined from ACI 355.4 given for Condition B. Condition B applies without
supplementary reinforcement or where pullout (bond) or pryout govern, as set forth in ACI 318 D.4.3, while condition A requires supplemental
reinforcement. Values are for use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If
the load combinations of ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4.
3 3
For installations with 1 /4 inch edge distance, refer to Section 4.1.9 for spacing and maximum torque requirements.

TABLE 15—BOND STRENGTH DESIGN INFORMATION FOR FRACTIONAL HILTI HIS-N AND HIS-RN INSERTS
1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS NOMINAL BOLT/CAP SCREW DIAMETER (inch)


3 1 5
/8 /2 /8 ¾
3 3 1
in. 4 /8 5 6 /4 8 /8
Effective embedment depth hef
(mm) (110) (125) (170) (205)
in. 0.65 0.81 1 1.09
HIS insert O.D. d
(mm) (16.5) (20.5) (25.4) (27.6)
Characteristic bond psi 1,565 1,440 1,255 1,170
A k,uncr
Temperature

strength (MPa) (10.8) (9.9) (8.7) (8.1)


2
range

Characteristic bond psi 1,270 1,170 1,020 950


B k,uncr
strength (MPa) (8.7) (8.1) (7.0) (6.5)
Characteristic bond psi 735 675 590 550
C k,uncr
strength (MPa) (5.1) (4.7) (4.1) (3.8)
Permissible
Installation

Anchor
Conditions

- 1 2
Dry concrete & Water- Category
saturated concrete
d & ws - 0.65 0.55

For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.


For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Bond strength values correspond to concrete compressive strength range 2,500 psi ≤ f′c ≤ 4,500 psi. For 4,500 psi < f′c ≤ 6,500 psi, tabulated
characteristic bond strengths may be increased by 6 percent. For 6,500 psi < f′c ≤ 8,000 psi, tabulated characteristic bond strengths may be
increased by 10 percent.
2
Temperature range A: Maximum short term temperature = 104°F (40°C), maximum long term temperature = 75°F (24°C).
Temperature range B: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
Temperature range C: Maximum short term temperature = 248°F (120°C), maximum long term temperature = 162°F (72°C).
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete
temperatures are roughly constant over significant periods of time.
ESR-2262 | Most Widely Accepted and Trusted Page 13 of 24
1
TABLE 16—STEEL DESIGN INFORMATION FOR METRIC HILTI HIS-N AND HIS-RN INSERTS

DESIGN INFORMATION SYMBOL UNITS NOMINAL BOLT/CAP SCREW DIAMETER (mm)


8 10 12 16 20
mm 12.5 16.5 20.5 25.4 27.6
HIS insert O.D. d
(in.) (0.49) (0.65) (0.81) (1.00) (1.09)
2
Bolt effective cross-sectional mm 36.6 58 84.3 157 245
Ase 2
area (in. ) (0.057) (0.090) (0.131) (0.243) (0.380)
2
HIS insert effective cross- mm 51.5 108 169.1 256.1 237.6
Ainsert 2
sectional area (in. ) (0.080) (0.167) (0.262) (0.397) (0.368)
kN 29.3 46.4 67.4 125.6 196.0
Nominal strength as Nsa
governed by steel (lb) (6,580) (10,430) (15,160) (28,235) (44,065)
ISO 898-1 Class 8.8

strength – ISO 898-1 kN 17.6 27.8 40.5 75.4 117.6


Class 8.8 bolt/cap screw Vsa
(lb) (3,950) (6,260) (9,100) (16,940) (26,440)
Nominal strength as kN 25.2 52.9 77.8 117.8 109.3
governed by steel Nsa
strength – HIS-N insert (lb) (5,670) (11,895) (17,490) (26,485) (24,575)
Strength reduction factor
 - 0.65
 for tension2
Strength reduction factor
 - 0.60
 for shear2
Nominal strength as kN 25.6 40.6 59.0 109.9 171.5
governed by steel Nsa
(lb) (5,760) (9,130) (13,265) (24,705) (38,555)
ISO 3506-1 Class A4-70

strength – ISO 3506-1


Class A4-70 Stainless kN 15.4 24.4 35.4 65.9 102.9
Vsa
bolt/cap screw (lb) (3,455) (5,475) (7,960) (14,825) (23,135)
Stainless

Nominal strength as kN 36.0 75.6 118.4 179.3 166.3


governed by steel Nsa
strength – HIS-RN insert (lb) (8,100) (16,990) (26,610) (40,300) (37,395)
Strength reduction factor
 - 0.65
 for tension2
Strength reduction factor
 - 0.60
 for shear2
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Values provided for common rod material types based on published strengths and calculated in accordance with ACI 318-11 Eq. (D-2) and
Eq. (D-29). Other material specifications are admissible, subject to the approval of the code official. Nuts and washers must be appropriate
for the rod strength.
2
For use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If the load combinations of
ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4. Values correspond to a brittle
steel element.
ESR-2262 | Most Widely Accepted and Trusted Page 14 of 24
1
TABLE 17—CONCRETE BREAKOUT DESIGN INFORMATION FOR METRIC HILTI HIS-N AND HIS-RN INSERTS

DESIGN INFORMATION SYMBOL UNITS NOMINAL BOLT/CAP SCREW DIAMETER (inches)


8 10 12 16 20
mm 90 110 125 170 205
Effective embedment depth hef
(in.) (3.5) (4.3) (4.9) (6.7) (8.1)
Effectiveness factor for SI 10
kc,uncr
uncracked concrete (in-lb) (24)
3 mm 63 83 102 127 140
Min. anchor spacing smin
(in.) (2.5) (3.25) (4.0) (5.0) (5.5)
3 mm 63 83 102 127 140
Min. edge distance cmin
(in.) (2.5) (3.25) (4.0) (5.0) (5.5)
mm 120 150 170 230 270
Minimum member thickness hmin
(in.) (4.7) (5.9) (6.7) (9.1) (10.6)
Critical edge distance –
splitting cac - See Section 4.1.10 of this report.
(for uncracked concrete)
Strength reduction factor for
tension, concrete failure  - 0.65
2
modes, Condition B
Strength reduction factor for
shear, concrete failure modes,  - 0.70
2
Condition B
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
For additional setting information, see installation instructions in Figure 5.
2
Values provided for post-installed anchors with category as determined from ACI 355.4 given for Condition B. Condition B applies without
supplementary reinforcement or where pullout (bond) or pryout govern, as set forth in ACI 318 D.4.3, while condition A requires
supplemental reinforcement. Values are for use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI
318 D.4.3. If the load combinations of ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI
318 D.4.4.
3 3
For installations with 1 /4-inch edge distance, refer to Section 4.1.9 for spacing and maximum torque requirements.

TABLE 18—BOND STRENGTH DESIGN INFORMATION FOR METRIC HILTI HIS-N AND HIS-RN INSERTS
1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS NOMINAL BOLT/CAP SCREW DIAMETER (inches)


8 10 12 16 20
mm 90 110 125 170 205
Effective embedment depth hef
(in.) (3.5) (4.3) (4.9) (6.7) (8.1)
mm 12.5 16.5 20.5 25.4 27.6
HIS insert O.D. d
(in.) (0.49) (0.65) (0.81) (1.00) (1.09)
Characteristic bond MPa 10.8 10.8 9.9 8.7 8.1
A k,uncr
Temperature

strength (psi) (1,565) (1,565) (1,440) (1.255) (1,170)


2
Range

Characteristic bond MPa 8.7 8.7 8.1 7.0 6.5


B k,uncr
strength (psi) (1,270) (1,270) (1,170) (1,020) (950)
Characteristic bond MPa 5.1 5.1 4.7 4.1 3.8
C k,uncr
strength (psi) (735) (735) (675) (590) (550)
Permissible
Installation
Conditions

Anchor
- 1 2
Dry concrete & Water- Category
saturated concrete
d & ws - 0.65 0.55

For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.


For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Bond strength values correspond to concrete compressive strength range 2,500 psi ≤ f′c ≤ 4,500 psi. For 4,500 psi < f′c ≤ 6,500 psi, tabulated
characteristic bond strengths may be increased by 6 percent. For 6,500 psi < f′c ≤ 8,000 psi, tabulated characteristic bond strengths may be
increased by 10 percent.
2
Temperature range A: Maximum short term temperature = 104°F (40°C), maximum long term temperature = 75°F (24°C).
Temperature range B: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
Temperature range C: Maximum short term temperature = 248°F (120°C), maximum long term temperature = 162°F (72°C).
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete
temperatures are roughly constant over significant periods of time.
ESR-2262 | Most Widely Accepted and Trusted Page 15 of 24
1
TABLE 19—STEEL DESIGN INFORMATION FOR USA REINFORCING BARS

DESIGN INFORMATION SYMBOL UNITS BAR SIZE


No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No. 10
3 1 5 3 7 1 1
in. /8 /2 /8 /4 /8 1 1 /8 1 /4
Nominal bar diameter d
(mm) (9.5) (12.7) (15.9) (19.1) (22.2) (25.4) (28.6) (31.8)
2
Bar effective cross-sectional in. 0.11 0.2 0.31 0.44 0.6 0.79 1.0 1.27
Ase 2
area (mm ) (71) (129) (200) (284) (387) (510) (645) (819)
lb 6,600 12,000 18,600 26,400 36,000 47,400 60,000 76,200
Nominal strength as Nsa
ASTM A615 Gr. 40

(kN) (29.4) (53.4) (82.7) (117.4) (160.1) (210.9) (266.9) (339.0)


governed by steel
strength lb 3,960 7,200 11,160 15,840 21,600 28,440 36,000 45,720
Vsa
(kN) (17.6) (32.0) (49.6) (70.5) (96.1) (126.5) (160.1) (203.4)
Strength reduction factor
 - 0.65
 for tension2
Strength reduction factor
 - 0.60
 for shear2
lb 9,900 18,000 27,900 39,600 54,000 71,100 90,000 114,300
Nominal strength as Nsa
ASTM A615 Gr. 60

(kN) (44.0) (80.1) (124.1) (176.2) (240.2) (316.3) (400.4) (508.5)


governed by steel
strength lb 5,940 10,800 16,740 23,760 32,400 42,660 54,000 68,580
Vsa
(kN) (26.4) (48.0) (74.5) (105.7) (144.1) (189.8) (240.2) (305.1)
Strength reduction factor
 - 0.65
 for tension2
Strength reduction factor
 - 0.60
 for shear2
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Values provided for common rod material types based on published strengths and calculated in accordance with ACI 318-11 Eq. (D-2) and
Eq. (D-29). Other material specifications are admissible, subject to the approval of the code official. Nuts and washers must be appropriate
for the rod strength.
2
For use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If the load combinations of
ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4. Values correspond to a brittle
steel element.

TABLE 20—CONCRETE BREAKOUT DESIGN INFORMATION FOR FRACTIONAL REINFORCING BARS


1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS BAR SIZE


No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No. 10
Effectiveness factor for in-lb 24 24 24 24 24 24 27 30
kc,uncr
uncracked concrete (SI) (10) (10) (10) (10) (10) (10) (11.3) (12.6)
7 1 1 3 3 5 1
4 in. 1 /8 2 /2 3 /8 3 /4 4 /8 5 5 /8 6 /4
Min. bar spacing smin
(mm) (48) (64) (79) (95) (111) (127) (143) (159)
7 1 1 3 3 5 1
4 in. 1 /8 2 /2 3 /8 3 /4 4 /8 5 5 /8 6 /4
Min. edge distance cmin
(mm) (48) (64) (79) (95) (111) (127) (143) (159)
in. hef + 1¼ (3)
Minimum member thickness hmin hef + 2d 0
(mm) (hef + 30)
Critical edge distance –
splitting cac - See Section 4.1.10 of this report.
(for uncracked concrete)
Strength reduction factor for
tension, concrete failure  - 0.65
2
modes, Condition B
Strength reduction factor for
shear, concrete failure modes,  - 0.70
2
Condition B
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
For additional setting information, see installation instructions in Figure 5.
2
Values provided for post-installed anchors with category as determined from ACI 355.4 given for Condition B. Condition B applies without
supplementary reinforcement or where pullout (bond) or pryout govern, as set forth in ACI 318 D.4.3, while condition A requires supplemental
reinforcement. Values are for use with the load combinations of IBC Section 1605.2.1 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If
the load combinations of ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4.
3
d0 = drill bit diameter.
4 3
For installations with 1 /4-inch edge distance, refer to Section 4.1.9 for spacing and maximum torque requirements.
ESR-2262 | Most Widely Accepted and Trusted Page 16 of 24

TABLE 21—BOND STRENGTH DESIGN INFORMATION FOR FRACTIONAL REINFORCING BARS


1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No. 10


Characteristic bond psi 1,290
A k,uncr
Temperature

strength MPa (8.9)


2
Range

Characteristic bond psi 1,045


B k,uncr
strength MPa (7.2)
Characteristic bond psi 605
C k,uncr
strength MPa (4.2)
3 3 1 1 1 1
Minimum anchor embedment in. 2 /8 2 /4 3 /8 3 /2 3 /2 4 4 /2 5
hef,min
depth (mm) (60) (70) (80) (89) (89) (102) (114) (127)
1 1 1 1
Maximum anchor embedment in. 7 /2 10 12 /2 15 17 /2 20 22 /2 25
hef,max
depth (mm) (191) (254) (318) (381) (445) (508) (572) (635)
Permissible
Installation
Conditions

Anchor
- 1 2
Dry concrete & Category
Water-saturated
concrete
d & ws - 0.65 0.55

For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.


For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Bond strength values correspond to concrete compressive strength range 2,500 psi ≤ f′c ≤ 4,500 psi. For 4,500 psi < f′c ≤ 6,500 psi, tabulated
characteristic bond strengths may be increased by 6 percent. For 6,500 psi < f′c ≤ 8,000 psi, tabulated characteristic bond strengths may be
increased by 10 percent.
2
Temperature range A: Maximum short term temperature = 104°F (40°C), maximum long term temperature = 75°F (24°C).
Temperature range B: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
Temperature range C: Maximum short term temperature = 248°F (120°C), maximum long term temperature = 162°F (72°C).
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete
temperatures are roughly constant over significant periods of time.

1
TABLE 22—STEEL DESIGN INFORMATION FOR EU METRIC REINFORCING BARS

DESIGN INFORMATION SYMBOL UNITS BAR SIZE


8 10 12 14 16 20 25 28 32
mm 8.0 10.0 12.0 14.0 16.0 20.0 25.0 28.0 32.0
Nominal bar diameter d
(in.) (0.315) (0.394) (0.472) (0.551) (0.630) (0.787) (0.984) (1.102) (1.260)
2
Bar effective cross-sectional mm 50.3 78.5 113.1 153.9 201.1 314.2 490.9 615.8 804.2
Ase 2
area (in. ) (0.078) (0.122) (0.175) (0.239) (0.312) (0.487) (0.761) (0.954) (1.247)
kN 27.6 43.2 62.2 84.7 110.6 172.8 270.0 338.7 442.3
DIN 488 BSt 550/500

Nominal strength as Nsa


(lb) (6,215) (9,710) (13,985) (19,035) (24,860) (38,845) (60,695) (76,135) (99,440)
governed by steel
strength kN 16.6 25.9 37.3 50.8 66.4 103.7 162.0 203.2 265.4
Vsa
(lb) (3,730) (5,830) (8,390) (11,420) (14,915) (23,310) (36,415) (45,680) (59,665)
Strength reduction factor
 - 0.65
 for tension2
Strength reduction factor
 - 0.60
 for shear2
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Values provided for common rod material types based on published strengths and calculated in accordance with ACI 318-11 Eq. (D-2) and
Eq. (D-29). Other material specifications are admissible, subject to the approval of the code official. Nuts and washers must be appropriate
for the rod strength.
2
For use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If the load combinations of
ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4. Values correspond to a brittle
steel element.
ESR-2262 | Most Widely Accepted and Trusted Page 17 of 24

TABLE 23—CONCRETE BREAKOUT DESIGN INFORMATION FOR EU METRIC REINFORCING BARS


1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS BAR SIZE


8 10 12 14 16 20 25 28 32
Effectiveness factor for SI 10 12.6
kc,uncr
uncracked concrete (in-lb) (24) (30)
4 mm 40 50 60 70 80 100 125 140 160
Min. bar spacing smin
(in.) (1.6) (2) (2.4) (2.8) (3.1) (3.9) (4.9) (5.5) (6.3)
4 mm 40 50 60 70 80 100 125 140 160
Min. edge distance cmin
(in.) (1.6) (2) (2.4) (2.8) (3.1) (3.9) (4.9) (5.5) (6.3)
mm hef + 30 (3)
Minimum member thickness hmin hef + 2d0
(in.) (hef + 1¼)
Critical edge distance –
splitting cac - See Section 4.1.10 of this report.
(for uncracked concrete)
Strength reduction factor for
tension, concrete failure  - 0.65
2
modes, Condition B
Strength reduction factor for
shear, concrete failure  - 0.70
2
modes, Condition B
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
For additional setting information, see installation instructions in Figure 5.
2
Values provided for post-installed anchors with category as determined from ACI 355.4 given for Condition B. Condition B applies without
supplementary reinforcement or where pullout (bond) or pryout govern, as set forth in ACI 318 D.4.3, while condition A requires supplemental
reinforcement. Values are for use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If
the load combinations of ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4.
3
d0 = drill bit diameter.
4 3
For installations with 1 /4-inch edge distance, refer to Section 4.1.9 for spacing and maximum torque requirements.

TABLE 24—BOND STRENGTH DESIGN INFORMATION FOR EU METRIC REINFORCING BARS


1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS BAR SIZE


8 10 12 14 16 20 25 28 32
Characteristic bond MPa 8.9
A k,uncr
Temperature

strength (psi) (1,290)


2
Range

Characteristic bond MPa 7.2


B
strength
k,uncr
(psi) (1,045)
Characteristic bond MPa 4.2
C
strength
k,uncr
(psi) (605)
Minimum anchor embedment mm 60 60 70 75 80 90 100 112 128
hef,min
depth (in.) (2.4) (2.4) (2.8) (2.9) (3.1) (3.5) (3.9) (4.4) (5.0)
Maximum anchor embedment mm 160 200 240 320 400 440 500 560 635
hef,max
depth (in.) (6.3) (7.9) (9.4) (12.6) (15.7) (17.3) (19.7) (22.0) (25)
Permissible
Installation
Conditions

Anchor
- 1 2
Dry concrete & Category
Water-saturated
concrete
d & ws - 0.65 0.55

For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.


For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Bond strength values correspond to concrete compressive strength range 2,500 psi ≤ f′c ≤ 4,500 psi. For 4,500 psi < f′c ≤ 6,500 psi, tabulated
characteristic bond strengths may be increased by 6 percent. For 6,500 psi < f′c ≤ 8,000 psi, tabulated characteristic bond strengths may be
increased by 10 percent.
2
Temperature range A: Maximum short term temperature = 104°F (40°C), maximum long term temperature = 75°F (24°C).
Temperature range B: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
Temperature range C: Maximum short term temperature = 248°F (120°C), maximum long term temperature = 162°F (72°C).
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete
temperatures are roughly constant over significant periods of time.
ESR-2262 | Most Widely Accepted and Trusted Page 18 of 24
1
TABLE 25—STEEL DESIGN INFORMATION FOR CANADIAN METRIC REINFORCING BARS

DESIGN INFORMATION SYMBOL UNITS BAR SIZE


10 M 15 M 20 M 25 M 30 M
mm 11.3 16.0 19.5 25.2 29.9
Nominal bar diameter d
(in.) (0.445) (0.630) (0.768) (0.992) (1.177)
2
Bar effective cross-sectional mm 100.3 201.1 298.6 498.8 702.2
Ase 2
area (in. ) (0.155) (0.312) (0.463) (0.773) (1.088)
kN 54.2 108.6 161.3 269.3 379.2
Nominal strength as Nsa
(lb) (12,175) (24,410) (36,255) (60,550) (85,240)
governed by steel
strength kN 32.5 65.1 96.8 161.6 227.5
G30CSA

Vsa
(lb) (7,305) (14,645) (21,755) (36,330) (51,145)
Strength reduction factor
 - 0.65
 for tension2
Strength reduction factor
 - 0.60
 for shear2
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Values provided for common rod material types based on published strengths and calculated in accordance with ACI 318-11 Eq. (D-2) and
Eq. (D-29). Other material specifications are admissible, subject to the approval of the code official. Nuts and washers must be appropriate
for the rod strength.
2
For use with the load combinations of IBC Section 1605.2or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If the load combinations of
ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4. Values correspond to a brittle
steel element.

TABLE 26—CONCRETE BREAKOUT DESIGN INFORMATION FOR CANADIAN METRIC REINFORCING BARS
1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS BAR SIZE


10 M 15 M 20 M 25 M 30 M
Effectiveness factor for SI 10 10 10 11.3 12.6
kc,uncr
uncracked concrete (in-lb) (24) (24) (24) (27) (30)
4 mm 57 80 98 126 150
Min. bar spacing smin
(in.) (2.2) (3.1) (3.8) (5.0) (5.9)
4 mm 57 80 98 126 150
Min. edge distance cmin
(in.) (2.2) (3.1) (3.8) (5.0) (5.9)
mm hef + 30 (3)
Minimum member thickness hmin hef + 2d0
(in.) (hef + 1¼)
Critical edge distance –
splitting cac - See Section 4.1.10 of this report.
(for uncracked concrete)
Strength reduction factor for
tension, concrete failure  - 0.65
2
modes, Condition B
Strength reduction factor for
shear, concrete failure  - 0.70
2
modes, Condition B
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
For additional setting information, see installation instructions in Figure 5.
2
Values provided for post-installed anchors with category as determined from ACI 355.4 given for Condition B. Condition B applies without
supplementary reinforcement or where pullout (bond) or pryout govern, as set forth in ACI 318 D.4.3, while condition A requires supplemental
reinforcement. Values are for use with the load combinations of IBC Section 1605.2 or ACI 318 Section 9.2 as set forth in ACI 318 D.4.3. If
the load combinations of ACI 318 Appendix C are used, the appropriate value of must be determined in accordance with ACI 318 D.4.4.
3
d0 = drill bit diameter.
4 3
For installations with 1 /4-inch edge distance, refer to Section 4.1.9 for spacing and maximum torque requirements.
ESR-2262 | Most Widely Accepted and Trusted Page 19 of 24

TABLE 27—BOND STRENGTH DESIGN INFORMATION FOR CANADIAN METRIC REINFORCING BARS
1
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT

DESIGN INFORMATION SYMBOL UNITS BAR SIZE


10 M 15 M 20 M 25 M 30 M
Characteristic bond MPa 8.9
A k,uncr
Temperature

strength (psi) (1,290)


2
Range

Characteristic bond MPa 7.2


B k,uncr
strength (psi) (1,045)
Characteristic bond MPa 4.2
C k,uncr
strength (psi) (605)
Minimum anchor embedment mm 60 80 90 101 120
hef,min
depth (in.) (2.4) (3.1) (3.5) (4.0) (4.7)
Maximum anchor embedment mm 226 320 390 504 598
hef,max
depth (in.) (8.9) (12.6) (15.4) (19.8) (23.5)
Permissible
Installation
Conditions

Anchor
- 1 2
Dry concrete & Category
Water-saturated
concrete
d & ws - 0.65 0.55

For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897MPa.


For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi.
1
Bond strength values correspond to concrete compressive strength range 2,500 psi ≤ f′c ≤ 4,500 psi. For 4,500 psi < f′c ≤ 6,500 psi, tabulated
characteristic bond strengths may be increased by 6 percent. For 6,500 psi < f′c ≤ 8,000 psi, tabulated characteristic bond strengths may be
increased by 10 percent.
2
Temperature range A: Maximum short term temperature = 104°F (40°C), maximum long term temperature = 75°F (24°C).
Temperature range B: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
Temperature range C: Maximum short term temperature = 248°F (120°C), maximum long term temperature = 162°F (72°C).
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete
temperatures are roughly constant over significant periods of time.

FIGURE 3—HILTI HIT-HY 150 MAX ANCHORING SYSTEM AND ANCHOR ELEMENTS
ESR-2262 | Most Widely Accepted and Trusted Page 20 of 24

Specifications / Assumptions:
ASTM A193 Grade B7 threaded rod
Normal weight concrete, f’c = 4,000 psi
Seismic Design Category (SDC) B
No supplementary reinforcing in accordance with
ACI 318-11 D.1 will be provided.
Assume maximum short term (diurnal) base
material temperature < 100° F.
Assume maximum long term base material
temperature < 75° F.
Assume installation in dry concrete and hammer-
drilled holes.
Assume concrete will remain uncracked for
service life of anchorage.
Dimensional Parameters:
hef = 9.0 in.
s = 4.0 in.
ca,min = 2.5 in.
h = 12.0 in.
d = 1/2 in.

Calculation in accordance with ACI 318-11 Appendix D and this report ACI 318 Code Ref. Report Ref.
Step 1. Check minimum edge distance, anchor spacing and member thickness:
cmin = 2.5 in. < ca,min = 2.5 in. OK
Table 8
smin = 2.5 in. ≤ s = 4.0 in. OK -
Table 9
hmin = hef + 1.25 in. = 9.0 + 1.25 = 10.25 in. ≤ h = 12.0 OK
hef,min ≤ hef ≤ hef,max = 2.75 in. ≤ 9 in. ≤ 10 in. OK
Step 2. Check steel strength in tension:
2
Single Anchor: Nsa = Ase • futa = 0.1419 in • 125,000 psi = 17,738 lb.
D.5.1.2 Table 2
Anchor Group:  Nsa =  • n • Ase • futa = 0.75 • 2 • 17,738 lb. = 26,606 lb.
Eq. (D-2) Table 7
Or using Table 7:  Nsa = 0.75 • 2 • 17,735 lb. = 26,603 lb.
Step 3. Check concrete breakout strength in tension:
D.5.2.1
ANc -
Ncbg   ec ,N  ed ,N  c ,N  cp ,N  Nb Eq. (D-4)
ANc 0
2
ANc = (3 • hef + s)(1.5 • hef + ca,min) = (3 • 9 + 4)(13.5 + 2.5) = 496 in - -
2 2
ANc0 = 9 • h ef = 729 in D.5.2.1 and Eq. (D-5) -

ec,N = 1.0 no eccentricity of tension load with respect to tension-loaded anchors D.5.2.4 -

ca ,min 2.5
 ed,N  0.7  0.3   0.7  0.3   0.76 D.5.2.5 and Eq. (D-10) -
1.5 hef 1.5  9

c,N = 1.0 uncracked concrete assumed (kc,uncr = 24) D.5.2.6 Table 8

Determine cac:
From Table 9: uncr = 1,985 psi
k c,uncr 24
 uncr  hef  f 'c  9.0  4,000  2,899 psi > 1,985 psi  use 1,985 psi -
Section 4.1.10
 d   0 .5 Table 9
0 .4 0 .4
   h   1,985   12  = 24.2 in.
cac  hef   uncr   3.1  0.7    9     3.1  0.7 
 1,160   hef   1,160   9 

max ca ,min ;1.5  hef max 2.5 ;1.5  9


For ca,min < cac   0.56
cp,N   D.5.2.7 and Eq. (D-12) -
cac 24 .2

Nb  kc,uncr   
1.5
f 'c  hef  24  1.0  4,000  91.5 = 40,983 lb. D.5.2.2 and Eq. (D-6) Table 8

496
Ncbg  1.0  0.76 1.0  0.56  40,983  11,867 lb. - -
729
Ncbg = 0.65 • 11,867 = 7,713 lb. D.4.3(c) Table 8

FIGURE 4—SAMPLE CALCULATION


ESR-2262 | Most Widely Accepted and Trusted Page 21 of 24

Step 4. Check bond strength in tension:


D.5.5.1
ANa -
Nag   ec ,Na  ed ,Na  cp ,Na  Nba  Eq. (D-19)
ANa0

ANa = (2cNa + s)(cNa + ca,min)

cNa = 10 d  uncr  10  0.5  1,985 = 6.72 in. D.5.5.1


Table 9
a Eq. (D-21)
1,100 1,100
2
ANa = (2 • 6.72 + 4)(6.72 + 2.5) = 160.8 in
2 2 2
ANa0 = (2cNa) = (2 • 6.72) = 180.6 in D.5.5.1 and Eq. (D-20) -

ec,Na = 1.0 no eccentricity – loading is concentric D.5.5.3 -

 c   2.5  = 0.81
 ed ,Na   0.7  0.3  a, min    0.7  0.3   D5.5.4 -
 cNa   6.72 

max c a , min ; c Na max 2 .5 ;6 .72


 cp , Na    0.28 D.5.5.5 -
c ac 24 .2

Nba = • uncr • • d • hef = 1.0 • 1,985 • • 0.5 • 9.0 = 28,062 lb. D.5.5.2 and Eq. (D-22) Table 9

160.8
Nag  1.0  0.81  0.28  28 ,062  5,667 lb. - -
180.6

Nag = 0.65 • 5,667 = 3,684 lb. D.4.3(c) Table 9


Step 5. Determine controlling strength:
Steel Strength Nsa = 26,603 lb.
D.4.1 -
Concrete Breakout Strength Ncbg = 7,713 lb.
Bond Strength Nag = 3,684 lb. CONTROLS

FIGURE 4—SAMPLE CALCULATION (Continued)


ESR-2262 | Most Widely Accepted and Trusted Page 22 of 24

FIGURE 5—INSTRUCTIONS FOR USE (IFU) AS PROVIDED WITH PRODUCT PACKAGING


ESR-2262 | Most Widely Accepted and Trusted Page 23 of 24

Tmax

FIGURE 5—INSTRUCTIONS FOR USE (IFU) AS PROVIDED WITH PRODUCT PACKAGING (Continued)
ESR-2262 | Most Widely Accepted and Trusted Page 24 of 24

FIGURE 5—INSTRUCTIONS FOR USE (IFU) AS PROVIDED WITH PRODUCT PACKAGING (Continued)
ICC-ES Evaluation Report ESR-2262 FBC Supplement*
Reissued July 1, 2012
This report is subject to renewal August 1, 2014.

www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ®

DIVISION: 03 00 00—CONCRETE
Section: 03 16 00—Concrete Anchors

DIVISION: 05 00 00—METALS
Section: 05 05 19—Post-Installed Concrete Anchors

REPORT HOLDER:

HILTI, INC.
5400 SOUTH 122ND EAST AVENUE
TULSA, OKLAHOMA 74146
(800) 879-8000
www.us.hilti.com
HiltiTechEng@us.hilti.com

EVALUATION SUBJECT:

HILTI HIT HY 150 MAX ADHESIVE ANCHOR SYSTEM IN UNCRACKED CONCRETE

1.0 REPORT PURPOSE ANDSCOPE


Purpose:
The purpose of this evaluation report supplement is to indicate that the Hilti HIT-HY 150 MAX Adhesive Anchor System in
Uncracked Concrete, recognized in ICC-ES master evaluation report ESR-2262, has also been evaluated for compliance
with the codes noted below.
Applicable code editions:
 2010 Florida Building Code—Building
 2010 Florida Building Code—Residential
Property Evaluated:
Structural
2.0 CONCLUSIONS
The Hilti HIT HY 150 MAX Adhesive Anchor System in Uncracked Concrete, described in Sections 2.0 through 7.0 of the
master evaluation report ESR-2262, complies with the 2010 Florida Building Code—Building and the 2010 Florida Building
Code—Residential, provided the design and installation are in accordance with the International Building Code® (IBC)
provisions noted in the master report and the following conditions apply:

• Design wind loads must be based on Section 1609 of the 2010 Florida Building Code—Building or Section 301.2.1.1 of
the 2010 Florida Building Code—Residential, as applicable.

• Load combinations must be in accordance with Section 1605.2 or Section 1605.3 of the 2010 Florida Building Code—
Building, as applicable.

• The modifications to ACI 318 as shown in 2009 IBC Sections 1908.1.9 and 1908.1.10, as noted in 2009 IBC Section
1912.1, do not apply to the 2010 Florida Building Code.
Use of the Hilti HIT HY 150 MAX Adhesive Anchor System in Uncracked Concrete for compliance with the High-Velocity
Hurricane Zone provisions of the 2010 Florida Building Code—Building has not been evaluated, and is outside the scope of
this supplemental report.

ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000

Copyright © 2014 Page 1 of 2


ESR-2262 FBC Supplement | Most Widely Accepted and Trusted Page 2 of 2

For products falling under Florida Rule 9N-3, verification that the report holder’s quality assurance program is audited by a
quality assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the
responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by
the Commission).
This supplement expires concurrently with the master report reissued July 1, 2012, revised January 2014.

Das könnte Ihnen auch gefallen