Beruflich Dokumente
Kultur Dokumente
Service instructions
1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Please observe these notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Important notes on commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 Cleaning the control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.6 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
10 Module selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
11 Boiler data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
11.1 Set the number of boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
11.2 Select Hydraulic design for single boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
11.3 Select hydraulic design for cascade systems . . . . . . . . . . . . . . . . . . . . . . . . 45
11.4 Setting to alt. heat sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
11.5 Select the boiler type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
11.6 Limit boiler output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
11.7 Setting the maximum boiler temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
11.8 Selecting the type of sequence control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
2 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Index
13 DHW data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
13.1 Select DHW cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
13.2 Set temperature range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
13.3 Select switching optimisation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
13.4 Heat over run to DHW cyclinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
13.5 Set hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
13.6 Select the primary LAP circuit (currently not available in the UK) . . . . . . . . . . . . 93
13.7 Increase boiler temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
13.8 External fault indication (WF1/WF2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
13.9 External contact (WF1/WF3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
13.10 Selection and set up of thermal disinfection . . . . . . . . . . . . . . . . . . . . . . . . 100
13.11 Select the circulation pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
13.12 Switching off the DHW circulation pump during DHW loading . . . . . . . . . . . . . 107
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 3
Index
17 Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
17.1 Fault displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
17.2 Supplementary fault messages for boilers with EMS . . . . . . . . . . . . . . . . . . . 117
17.3 Maintenance messages on boilers with EMS (only Oil) . . . . . . . . . . . . . . . . . . 119
18 Low loss header monitor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
18.1 Low loss header monitor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
18.2 Boiler monitor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
18.3 Heating circuit monitor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
18.4 DHW monitor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
21 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
21.1 Resetting control unit parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
21.2 Reset the error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
21.3 Resetting the maintenance message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
22 Sensor curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
22.1 Sensor curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
22.2 Heating curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
23 Keyword Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
4 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Safety 1
1 Safety
These service instructions contain important information Make sure that you have isolated the
on the safe and appropriate commissioning and servic- mains power supply by switching the
ing of the Logamatic 4121, 4122 and 4126 control panels. mains off.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 5
1 Safety
1.6 Disposal
6 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Setting parameters and display data 2
Some options are only displayed with certain modules and depending on prior settings.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 7
3 Logamatic 412x control unit – controls
Pos 1 Pos 2
ON/OFF switch
The Logamatic 4122 control unit can also The system flow temperature is displayed
be supplied with the MEC 2. on the boiler display.
MEC2
Heating circ 2 – mixed
CM431
Pos A for module
FM 455 KSE1
8 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Modules and their functions 4
Logamatic
Module
4121 4122 4126
MEC 2 programming unit O O
Boiler display ZM 435 X X
Controller module CM 431 O O O
Central module ZM 424
O – –
2 heating circuits + 1 DHW circuit
Function module FM 441
– X –
1 heating circuit + 1 DHW circuit
Function module FM 442
X X –
2 heating circuits
Function module FM 443
X X –
Solar heating circuit*
Function module FM 445
X X O
LAP/LSP (loading system)*
Function module FM 446
X X X
Interface EIB*
Function module FM 448
X X X
Central fault message
Function module FM 455
O – –
KSE 1 (only with ZM 424)*
Function module FM 456
X X X
KSE 2 (cascade - 2 boilers)
Function module FM 457
X X X
KSE 4 (cascade – 4 boilers)
USER NOTE
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 9
4 Modules and their functions
Module CM 431
Setting the control unit address for cascade
systems
– 2 control units
setting for control unit 1: address 1
Module ZM 424 or FM 456 / FM 457 must be fitted
into control unit 1 (master).
setting for control unit 2: address 2 (substation)
– 3 control units
setting for control unit 1: address 1
Module ZM 424 or FM 456 / FM 457 must be fitted
into control unit 1 (master).
setting for control unit 2: address 2 (substation)
setting for control unit 3: address 3 (substation)
– Maximum settings: 15 addresses
USER NOTE
10 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Modules and their functions 4
WARNING!
mains power supply by switching the
mains off.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 11
4 Modules and their functions
Fig. 6 ZM424
Display
8 Heating circuit pump operational
Display
x DHW Cylinder load pump active
Display
y DHW circulation pump active
12 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Modules and their functions 4
3+X The heating circuit pump and the load pump are
switched ON if "4000 cylinder" has been set in
the "DHW" menu (see page 86).
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 13
4 Modules and their functions
Only fit this module into the Logamatic 4122 control unit.
Fig. 7 FM441
14 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Modules and their functions 4
3
The positions 0 and manual ( ) are special settings
reserved for qualified personnel only.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 15
4 Modules and their functions
Fig. 8 FM442
Display
8 Heating circuit pump operational
16 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Modules and their functions 4
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 17
4 Modules and their functions
Plug into the r.h. slot (slot 2) of the control unit; this
ensures the power supply to all other modules. You can
only use this module if no other FM 441 has already
been installed in the control unit.
18 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Modules and their functions 4
DHW function
Manual DHW switch
USER NOTE
RISK OF SCALDING
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 19
4 Modules and their functions
Output for multiple fault messages: Display General fault, e.g. site error,
All control unit faults cause this output to be switched. A 0 sensor error, external faults,
lamp may, for example, be switched ON via the volt-free internal wiring fault module error,
contacts of this output. manual mode.
The manual switches on the modules, only have service The fault messages appear as plain
and maintenance functions, and affect only the 230 V text in the MEC 2.
outputs. Indicators for the following functions:
Display
If the manual switches are not set to Auto, a a Operational burner
corresponding message appears on the MEC 2 and the
0 Display Heating circuit without valve in
fault indicator illuminates. 1 summer mode
Never use the manual switches to switch OFF the Display
system when you have to temporarily leave the 8 Heating circuit pump active
installation. Display DHW operates via wall-mounted
| boiler
Use the holiday function for this purpose (see operating
Display
instructions for Logamatic 4121, 4122 and 4126). Q Boiler in flue gas test mode
Input voltage in V
20 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Modules and their functions 4
Jumper block
The module is configured using the jumper block:
Setting Function
open
The module is registered as a
(factory
new FM455/456/457 module
setting)
USER NOTE
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 21
5 Burner control and basic controls
Buderus wall-mounted boilers are fitted with a UBA 1.x Wall- Floor-
or UBA 3 universal burner control. The UBA 1.x is Wall-
mounted standing
mounted boiler
equipped with an independent programming unit. boiler boiler
with EMS
without EMS with EMS
As with floor-standing boilers with EMS (Energy Man-
agement System), wall-mounted boilers with UBA 3 are EMS burner
Burner
operated the same via the BC10 base controller. UBA 1.x UBA 3 control unit
control
SAFe
The table on the right you can see the description of boi-
Basic
ler types and burner control units. UBA 1.x BC10 base controller
controls
See page 94 for all the individual boiler types. Code "UBA" "EMS/UBA 3" "EMS/SAFe"
22 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Burner control and basic controls 5
1 11 10 9 8 7
Restricting output
The boiler output can be restricted to 11 kW (or 50 kW
with higher boiler outputs) using a jumper on the rear of
the base controller.
z Remove base controller.
z If necessary, remove jumper (Fig. 15, Item 1)
if you want to restrict boiler output.
Output restricted to
Not inserted 11 kW (50 kW) (only
for boilers with UBA3)
Output unrestricted
Inserted
(factory setting) 1
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 23
6 MEC 2 programmer
6 MEC 2 programmer
MEC 2
Temperature flow
Display
45°C
Dial
Outdoor temp.
10°C
Set time
Enter weekdays
Enter holidays
Modify temperature
Select standard display settings
Summer/winter change
over
Back to the next higher
level
Selecting a program
Fig. 16 MEC 2
USER NOTE
24 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Commissioning the MEC 2 Programmer 7
You can use the MEC 2 for all Logamatic 4000 control
units.
USER NOTE
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 25
7 Commissioning the MEC 2 Programmer
After the MEC 2 has been installed in the control unit, the
two adjacent displays will initially be redisplayed.
MEC is
initialised
Connection with
ctrl panel
address XX
established
Data is
taken
from ctrl panel
26 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Commissioning the MEC 2 Programmer 7
Data is
sent
to ctrl. panel
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 27
7 Commissioning the MEC 2 Programmer
Data is
sent
to ctrl. panel
28 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Calling up and modifying settings 8
USER NOTE
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 29
8 Calling up and modifying settings
– General data
– ...
Turn the dial. You reach all sub-menus by turning
– automatic maintenance message the control dial.
– General data
Press and hold down the Modification of parameter settings.
button. Select function/temperature.
Press once and release. Back to the next higher level.
USER NOTE
30 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Calling up and modifying settings 8
– Type of building
– Remote adjustment
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 31
9 General data
9 General data
Turn the dial. – Minimum outdoor temp Under the heading "General Data",
these settings may be set relating to
The adjacent settings are – Type of building the heating system and to the building
displayed in sequence! characteristics.
– Summer/Winter clock ac.
– Remote adjust.
– Heat consumption
– Automatic maintenance
message
32 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
General data 9
Press and release the button. The first sub-menu item is "Minimum
GENERAL DATA outdoor temp".
Press and hold down the The setting (here: -10 °C) flashes.
button.
Turn the dial to the required
setting (here: -12 °C). GENERAL DATA
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 33
9 General data
Type of building
medium
Press and hold down the The setting (here: medium) flashes.
button.
Turn the dial to the required
type of building (here: heavy). GENERAL DATA
Type of building
Release the dial to store the heavy
setting.
Press once and release. Back to the next higher level.
34 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
General data 9
USER NOTE
IMPORTANT NOTE
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 35
9 General data
Press and hold down the The setting (here: Yes) flashes.
button.
Turn the dial to "Yes" or "No".
GENERAL DATA
USER NOTE
36 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
General data 9
Remote adjust.
Yes
Press and hold down the The setting (here: Yes) flashes.
button.
Turn the dial to "Yes" or "No".
GENERAL DATA
Remote adjust.
Release the dial to store the No
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 37
9 General data
Press and hold down the but- The setting (here: No) flashes.
ton.
Turn the dial to the desired
setting. GENERAL DATA
Release the dial to store the Fault message
setting. Manual control
Fault message
USER NOTE
38 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
General data 9
Press and hold down the but- The setting (here: No) flashes.
ton.
Turn the dial
to the desired setting. GENERAL DATA
Release the dial Automatic
to store the setting. maintenance mess.
Hours run
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 39
9 General data
Press and hold down the but- The setting (here: 6000 h) flashes.
ton.
Turn to change the setting General data
(date or operating hours). Maintenance acc.
to hours run
6000h
Release the dial to store the
setting.
USER NOTE
USER NOTE
40 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Module selection 10
10 Module selection
The modules are automatically recognised and their However, these modules can also be set manually.
information downloaded on starting the Logamatic 41xx
control unit or after resetting the unit.
Module selection
Press and release the button. The display shows that boiler module
MODULE SELECTION FM 455 is installed in slot A.
Pos. A
Boiler module
FM 455
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 41
11 Boiler data
11 Boiler data
You can, if the control unit contains a cascade module, e.g. KSE module FM 456 or FM 457, setup the boiler data with
this menu.
Boiler data
No. of boilers
1
Turn the dial until the required Here you set the number of boilers to
setting is shown. BOILER DATA be run.
You may set the maximum number of
No. of boilers boilers = 8, e.g. if two FM457 multi-
4 boiler modules are used in one
Logamatic 4122 control panel.
If you set the number of boilers = 0,
Release the dial to store the
the control unit will operate as control
setting.
1 heating circuit.
Press once and release. Back to the next higher level.
42 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Boiler data 11
Boiler data
Press and release the button. The display shows the first menu point
BOILER DATA "No. of boilers". At least one boiler
must be displayed.
No. of boilers
1
Press and hold down the The setting (here: with boiler circ.
button. P/with low loss he) flashes.
Turn the dial until the required
setting is shown. BOILER DATA
Schematic
with boiler shunt P
Release the dial to store the no low loss head
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 43
11 Boiler data
44 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Boiler data 11
Boiler data
Press and release the button. The display shows the first menu point
BOILER DATA "No. of boilers". Must be greater
than 1.
No. of boilers
1
Press and hold down the The setting (here: none) flashes.
button.
Turn the dial until the required
setting is shown. BOILER DATA
Alt. ht off
Release the dial to store the +10 °C
setting.
Press once and release. Back to the next higher level.
Example:
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 45
11 Boiler data
Boiler data
Press and release the button. The display shows the first menu point
BOILER DATA "No. of boilers".
No. of boilers
1
Press and hold down the The settings (here: none) flashes.
button.
Turn the dial until the required
setting is shown. BOILER DATA
Alt. ht off
Release the dial to store the 10 °C
setting.
Press once and release. Back to the next higher level.
Example:
46 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Boiler data 11
Boiler data
Press and release the button. The display shows the first menu
BOILER DATA point "No. of boilers".
No. of boilers
1
Boiler type
Condensing boil.
Press and hold down the The setting (here: Condensing boil)
button. flashes.
Turn the dial until the required
type of boiler is shown. BOILER DATA
USER NOTE
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 47
11 Boiler data
USER NOTE
48 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Boiler data 11
Boiler data
Press and release the button. The display shows the first menu
BOILER DATA point "No. of boilers". At least one
boiler must be displayed.
No. of boilers
1
Boiler output
100%
Press and hold down the The setting (here: 100 %) flashes.
button.
Turn the dial until the required
setting is shown. BOILER DATA
Boiler output
Release the dial to store the 50 %
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 49
11 Boiler data
Boiler data
Press and release the button. The display shows the first menu
BOILER DATA point "No. of boilers".
No. of boilers
1
Press and hold down the The setting (here: 85 °C) flashes.
button.
Turn the dial until the required
temperature is shown. BOILER DATA
Max.
boiler temp.
Release the dial to store the 50 °C
setting.
Press once and release. Back to the next higher level.
50 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Boiler data 11
Boiler data
Press and release the button. The display shows the first menu
BOILER DATA point "No. of boilers".
No. of boilers
2
Sequence contrl
Automatic
Press and hold down the The setting (here: Automatic) flashes.
button.
Turn the dial until the required
setting is shown. BOILER DATA
Sequence contrl
Release the dial to store the Fixed
settings.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 51
11 Boiler data
Sequence contrl
1—2—3—4
USER NOTE
52 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
– Base point
The level of the flow temperature is a linear
consequence of the outside temperature. The
resulting heating curve connects as a straight line the
Base point with a second point, which depends on
the design temperature.
– Constant
Use this system for controlling a swimming pool
heating system or to pre-control air conditioning. If
the heating must always provide the same, set flow
temperature, independent of the outside
temperature. You cannot install a remote control for
this heating circuit if you have selected this system.
– Room controller
The set level of the flow temperature is only
dependent on the actual room temperature. For this
purpose, you must install a remote control inside the
room.
The heating system is switched OFF, if the room
becomes too hot.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 53
12 Heating circuit data
Example:
Press and release the button. The display shows the first menu
HEAT CIRC. point "Heating system" for the
selected heating circuit.
Heating system
Radiators
Press and hold down the The setting (here: Radiator) flashes.
button.
Turn the dial to the required
heating system (here: Under- HEAT CIRC.
floor).
Heating system
Release the dial to store the Under-floor
setting.
Press once and release. Back to the next higher level.
54 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Press and hold down the The setting (here: Heating circ.)
button. flashes.
Turn the dial until the required
description is displayed (here: HEAT CIRC. DATA2
Under-floor).
Name heat circ.
Release the dial to store the Under-floor
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 55
12 Heating circuit data
Press and release the button. The display shows the first menu
HEAT CIRC. DATA2 point "Heating system" for the
selected heating circuit.
Press and hold down Heating system The setting (here: Radiators) flashes.
Radiators
Heating system
Release the dial to store the Base point
setting.
Turn the dial until the
submenu "Base point temp." HEAT CIRC. DATA2
appears.
Base point temp.
Press and hold down the 30 °C The setting (here: 30 °C) flashes.
button.
Turn the dial until the required
setting (here: 32 °C) appears. HEAT CIRC. DATA2
56 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Design temp.
75°C
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 57
12 Heating circuit data
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Press and hold down the The setting (here: 5 °C) flashes.
button.
Turn dial and set design This setting sets the temperature,
temperature. HEAT CIRC. DATA2 below which the flow temperature
Min. must not drop.
flow temp.
10°C
Release the dial to store the
setting.
Press once and release. Back to the next higher level.
58 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Press and hold down the The setting (here: 75 °C) flashes.
button.
Turn dial and set design The set design temperature
temperature. HEAT CIRC. DATA2 determines the setting, above which
Maximum the flow temperature must not rise.
flow temp.
60 °C
Release the dial to store the
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 59
12 Heating circuit data
– Automatic adjustment
– Optimisation
60 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Turn the dial until "Remote This function is not available for
control" appears. HEAT CIRC. DATA2 heating circuits from modules FM 456
and 457.
Remote control
None
Press and hold down the The settings (here: None) flashes.
button.
Turn the dial and set the Turn the dial to "with display", when
required setting. HEAT CIRC. DATA2 the selected heating circuit has been
allocated to the MEC 2.
Remote control
Release the dial to store the with display
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 61
12 Heating circuit data
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
62 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
USER NOTE
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 63
12 Heating circuit data
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Set-back type
Outdoor setback
Press and hold down the The setting (here: Outdoor setback)
button. flashes.
Turn the dial and set the You set the required type of setback
required setting. HEAT CIRC. DATA2 with the dial.
Set-back type
Release the dial to store the OFF
setting.
Press once and release. Back to the next higher level.
64 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Outdoor from
5°C
Press and hold down the The setting (here: 5 °C) flashes.
button.
Turn the dial and set the You set the outside stop temperature
required setting. HEAT CIRC. DATA2 with the dial.
Outdoor from
Release the dial to store the 1°C
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 65
12 Heating circuit data
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Press and hold down the The setting (here: Radiators) flashes.
button.
Turn the dial until "Constant"
appears. HEAT CIRC. DATA2
Heating system
Release the dial to store the Constant
setting.
Turn the dial until the
submenu "Flow setback by" HEAT CIRC. DATA2
appears. Flow
setback by
30K
66 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Press and hold down the The setting (here: 0 °C) flashes.
button.
Turn the dial and set the Correct the set room temperature
required setting. HEAT CIRC. DATA2 by –2 °C.
Room temperature
Offset
Release the dial to store the -2°C
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 67
12 Heating circuit data
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Autom adaptation
No
Press and hold down the The setting (here, No) flashes.
button.
Turn the dial and set the Turn the dial to "Yes".
required setting. HEAT CIRC. DATA2
Autom adaptation
Release the dial to store the Yes
setting.
Press once and release. Back to the next higher level.
68 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
USER NOTE
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 69
12 Heating circuit data
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Press and hold down the The setting (here: None) flashes.
button.
Turn the dial and set the Turn the dial until the required
required setting. HEAT CIRC. DATA2 optimising variant appears
Optimisation (here: Switch OFF).
for
Release the dial to store the Switch OFF
setting.
Press once and release. Back to the next higher level.
70 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Press and hold down the The setting (here: None) flashes.
button.
Turn the dial and set the Turn the dial until the required
required setting. HEAT CIRC. DATA2 optimising variant appears: Switch
Optimisation OFF or Switch ON/OFF (here: Switch
for ON/OFF).
Release the dial to store the switch on/off
setting.
Turn the dial until "Switch off
optim. time" appears. HEAT CIRC. DATA2
Switch off
optim. time
60 mins.
Press and hold down the The setting (here: 60 min) flashes.
button.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 71
12 Heating circuit data
72 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Press and hold down the The setting (here: 1 °C) flashes.
button.
Turn the dial and set the Change the frost protection
required setting. HEAT CIRC. DATA2 temperature to -2 °C.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 73
12 Heating circuit data
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
DHW priority
Yes
Press and hold down the The setting (here: Yes) flashes.
button.
Turn the dial and set the Turn the dial until "No" appears.
required setting. HEAT CIRC. DATA2
DHW priority
Release the dial to store the No
setting.
Press once and release. Back to the next higher level.
74 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Actuator
Yes
Press and hold down the The setting (here: Yes) flashes.
button.
Turn the dial and set the Turn the dial until "No" appears.
required setting. HEAT CIRC. DATA2
Actuator
Release the dial to store the No
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 75
12 Heating circuit data
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Press and hold down the The setting (here: 120 s) flashes.
button.
Turn the dial and set the Turn the dial until the required setting
required setting. HEAT CIRC. DATA2 appears (here: 90 s).
Actuator
running time
Release the dial to store the 90 sec
setting.
Press once and release. Back to the next higher level.
76 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Radiators
Increasing boil.
5 °C
Press and hold down the The setting (here: 5 °C) flashes.
button.
Turn the dial and set the Turn the dial until the required setting
required setting. HEAT CIRC. DATA2 (here: 10 °C) appears.
Increasing boil.
Release the dial to store the 10 °C
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 77
12 Heating circuit data
Disinfection
USER NOTE Rise by Setback by
Hold
the
"Under-floor" must be set as heating max.
temp.
system.
Days
Rise Setback
every day every 2 days
Press and release the button. The display shows the first menu point
HEAT CIRC. DATA2 "Heating system" for the selected
heating circuit.
Heating system
Under-floor
Cement drying
No
Press and hold down the The setting (here: No) flashes.
button.
Turn the dial and set the Turn the dial until "Yes" appears.
required setting. HEAT CIRC. DATA2
Cement drying
Release the dial to store the Yes
setting.
The menu items on the following pages enable you to USER NOTE
select the temperatures and settings for the drying time.
Screed drying only takes place on heating
The setting reverts automatically to "No", as soon as the circuits with a valve.
drying process has been completed.
78 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 79
12 Heating circuit data
Heat-up time
Press and hold down the The setting (here: every day) flashes.
button.
Turn the dial and set the Set the required setting,
required setting. HEAT CIRC. DATA2 (here: every 5th day).
Cement drying
Rise
Release the dial to store every 5 days
the setting.
80 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Press and hold down the The setting (here: 45 °C) flashes.
button.
Turn the dial and set the Set the required setting (here: 25 °C).
required setting. HEAT CIRC. DATA2
Cement drying
Max. temp.
Release the dial to store the 25 °C
setting.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 81
12 Heating circuit data
Press and hold down the The setting (here: 4 days) flashes.
button.
Turn the dial and set the Set the required setting,
required setting. HEAT CIRC. DATA2 (here: 20 days).
Cement drying
Hold max. temp.
Release the dial to store the 20 days
setting.
82 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Heating circuit data 12
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 83
12 Heating circuit data
Press and hold down the The setting (here: every day) flashes.
button.
Turn the dial and set the Set the required setting,
required setting. HEAT CIRC. DATA2 (here: every 5th day).
Cement drying
Setback
Release the dial to store the every 5 days
setting.
Press once and release. Back to the next higher level.
84 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
13 DHW data
DHW
Press and release the button. The first menu item "4000 cylinder"
DHW DATA appears.
Select this setting when DHW sensor
DHW and DHW cylinder load pump are
4000 cylinder connected to the Logamatic 4000
control panel.
Press and hold down the The setting (here: 4000 cylinder)
button. flashes.
Turn the dial. Select the required cylinder
DHW DATA (here: UBA cylinder).
DHW
Release the dial to store the UBA cylinder
setting.
Press once and release. Back to the next higher level.
USER NOTE
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 85
13 DHW data
RISK OF SCALDING
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000 cylinder
Range to
60 °C
Press and hold down the The setting (here: 60 °C) flashes.
button.
Turn the dial to the required Set the required setting (here: 80 °C).
setting. DHW DATA
Range to
Release the dial to store the 80 °C
setting.
Press once and release. Back to the next higher level.
86 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000 cylinder
Press and hold down the The setting (here: No) flashes.
button.
Turn the dial. Set the required setting (here: Yes).
DHW DATA
Optimisation
for switch-on
Release the dial to store the Yes
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 87
13 DHW data
If you select "Heat over run, no", you will only utilise
a small amount of residual heat. The burner runs until
the set domestic hot water temperature is reached. The
cylinder load pump runs on for 3 minutes after the burner
is switched OFF.
88 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
Press and hold down the The setting (here: Yes) flashes.
button.
Turn the dial. Set the required setting (here: No).
DHW DATA
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 89
13 DHW data
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
Hysteresis
-5 K
Hysteresis
Release the dial to store the -20 K
setting.
Press once and release. Back to the next higher level.
90 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
Yes
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 91
13 DHW data
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
Yes
92 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
13.6 Select the primary LAP circuit (currently not available in the UK)
If you selected the LAP module FM 445 during RISK OF SCALDING
module selection, you can with the "LAP primary"
function determine the type of primary circuit control. through overheating the system.
Only use the settings "UBA" or "EMS" if:
WARNING!
– the boiler used and the KIM number/BIM
number are approved for this purpose
(see page 85),
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
Yes
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 93
13 DHW data
USER NOTE
setting type KIM-Nr. Boiler type setting type BIM-Nr. Boiler type
74 Logamax plus GB112 - 11/s 5001 Logano G135 - 18
76 Logamax plus GB112 - 19/s 5002 Logano G135 - 25
94 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
Yes
Press and hold down the The setting (here: 120 s) flashes.
button.
Turn the dial. Set the required setting (here: 10 s).
DHW DATA
Actuator
running time
Release the dial to store the 10 secs
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 95
13 DHW data
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
Boiler increase
40 K
Boiler increase
Release the dial to store the 10 K
setting.
Press once and release. Back to the next higher level.
96 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
Press and hold down the The fault indicator (here: None)
button. flashes.
Turn the dial. Set the required fault indication
DHW DATA (here: Pump).
External fault
indicator WF1/2
Release the dial to store the Pump
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 97
13 DHW data
"Single load"
"Disinfection"
98 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
Press and hold down the The setting (here: None) flashes.
button.
Turn the dial. Set the required contact
DHW DATA (here: Single charge).
External contact
WF1/3
Release the dial to store the Single charge
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 99
13 DHW data
USER NOTE
USER NOTE
100 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
Press and hold down the The setting (here: No) flashes.
button.
Turn the dial. Set the required setting (here: Yes).
DHW DATA
Thermal
disinfection
Release the dial to store the Yes
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 101
13 DHW data
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
Press and hold down the The setting (here: 70 °C) flashes.
button.
Turn the dial. Set the required setting (here: 75 °C).
DHW DATA
Disinfection
temperature
Release the dial to store the 75 °C
setting.
Press once and release. Back to the next higher level.
102 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
You can set the day of the week when disinfection USER NOTE
should be carried out via the "Disinfection weekday"
function. The "Disinfection weekday" function will
not be displayed, if thermal disinfection
has previously been set via the "External
contact WF 1/3" function.
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
Press and hold down the The setting (here: Tuesday) flashes.
button.
Turn the dial. Set the required day (here: Sunday).
DHW DATA
Weekday
Disinfection
Release the dial to store the Sunday
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 103
13 DHW data
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
Press and hold down the The fault indicator (here: 1.00)
button. flashes.
Turn the dial. Set the required fault indication
DHW DATA (here: 18.00 h).
Disinfection
time
Release the dial to store the 18:00
setting.
Press once and release. Back to the next higher level.
104 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
DHW circulat
No
Press and hold down the The setting (here: No) flashes.
button.
Turn the dial. Set the required setting (here: Yes).
DHW DATA
DHW circulat
Release the dial to store the Yes
setting.
Press once and release. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 105
13 DHW data
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
4000-cylinder
Press and hold down the The setting (here: twice ON) flashes.
button.
Turn the dial. Set the required setting (here: OFF).
DHW DATA The DHW circulation pump will now
DHW circulat only operate during single loading.
per hour
Release the dial to store the Off
setting.
Press once and release. Back to the next higher level.
106 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
DHW data 13
13.12 Switching off the DHW circulation pump during DHW loading
If the LAP module FM445 is installed, you can switch the USER NOTE
circulation on/off during DHW loading.
The function "circulation OFF DHW
charging" can only be used if the LAP
module FM445 is installed.
DHW
Press and release the button. The first menu item "DHW" appears.
DHW DATA
DHW
yes
Press and hold down the but- The setting (here: Yes) flashes.
ton.
Turn the dial. Set the required setting (here: No).
DHW DATA
Release the dial to store the Circulation OFF
setting. DHW charging
no
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 107
14 Heating Parameters
14 Heating Parameters
Heating charact.
Press and release the button. The first menu item "Heating circ. 1"
Heating charact. appears.
Heating circ. 1
constant
Turn the dial until the required The settings for the selected heating
heating circuit appears. Heating charact. circuit are displayed.
Heating circ 2
AT: 10 / 0 / -10
Press once. VL: 45 / 62 / 75
Back to the next higher level.
108 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Testing the relay 15
You can check with the "Relay test" menu, whether you Relay test example:
have correctly connected the external components
(e.g. pumps). You may call up the following relays:
Relay test
Press and release the button. The first menu item "Heating circ. 1"
RELAY TEST appears.
Heating circ. 1
Turn the dial until the required The first menu item appears
menu item appears. RELAY TEST (here: Heating circ. 2).
Heating circ. 2
Press and hold down. The first setting (here: OFF) flashes.
RELAY TEST
Heating circ. 2
Circ. pump
Off
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 109
15 Testing the relay
Turn the dial until the required The setting of the selected relay
setting appears. RELAY TEST (here: ON) flashes.
Heating circ. 2
Circ. pump
Release the dial to store the ON
setting.
Press once. Back to the next higher level
(relay test).
Press once. Back to the next higher level
(service level).
USER NOTE
110 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Carrying out an LCD test 16
Using the "LCD test" menu, you can check, whether all
symbols are fully displayed.
LCD test
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 111
17 Error
17 Error
Using the "Error" menu you can display the last four fault
messages for the heating system.
Error
Press and release the button. The fault message will then be
Fault displayed.
Flow sensor 2
from 23:20h 13.10 USER NOTE
until 23:45h 13.10
The display will show "No
Turn the dial and scroll fault" if the connected
through the last fault control unit has not
messages. recorded any faults.
112 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Error 17
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 113
17 Error
114 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Error 17
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 115
17 Error
116 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Error 17
DC: Display code (status) Fig. 18 Reading off display and service code (e.g. Logamatic
SC: Service code MC10 control panel/BC10 base controller)
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 117
17 Error
EMS faults
USER NOTE
118 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Only for Oil Boilers – Error 17
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 119
17 Only for Oil Boilers – Error
120 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Low loss header monitor data 18
Using the "Monitor" menu you can display the set and You can display data for the following components:
actual settings. The display depends on which modules
– Low loss header
are installed.
– Boiler
Some display settings are separated by a slash (/). The
number in front of the slash determines the setting of – Heating circ.
each respective parameter and the figure behind the
slash is the actual setting. – DHW
Monitor
Press and release the button. The first menu item "Low loss header"
MONITOR appears.
Press and release the button. The low loss header data are then
MONITOR SWITCH displayed.
Outdoor 5 The "Time del." setting describes the
Time del. 4
outdoor temperature, taking the type
Flow 55 / 55
of building into consideration which
has already been entered, and with
which the heating curves were
calculated.
Press once. Back to the next higher level.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 121
18 Low loss header monitor data
Monitor
Press and release the button. The first menu item "Low loss
MONITOR header" appears.
Boiler 1
Press and release the button. The "Time del." setting describes the
MONITOR BOILER 1 outdoor temperature, taking the type
Outdoor 5 of building into consideration which
Time del. 4 has already been entered, and with
ext. request. 0 which the heating curves were
calculated.
Turn the dial to scroll through Other boiler monitor data is displayed
the boiler monitor data. according to the boiler type.
122 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Low loss header monitor data 18
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 123
18 Low loss header monitor data
}
Flame current actual flame current µA >100, if less
change the flame
ignition
Oil Boilers
Ignition Ignition on/off
}
Flame Flame on/off
Valve 1 Burner valve stage 1 open/closed
Oil Boilers
Valve 2 Burner valve stage 2 open/closed
}
Air actual combustion air temperature °C
Pressure actual heating system operating pressure bar
Flame current actual flame current µA
Ignition
Flame
Ignition
Flame }Oil Boilers on/off
on/off
Valve 1 Burner valve stage 1 open/closed
Oil Boilers
Valve 2 Burner valve stage 2 open/closed
Tab. 9 Boiler monitor data for boilers with EMS/SAFe
124 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Low loss header monitor data 18
Monitor
Press and release the button. The first menu item "Low loss header"
MONITOR appears.
Heating circ. 2
Press and release the button. The setting and the actual setting for
MONITOR HK2 the flow room temperature are
Flow 30/ 29 displayed.
Room 21/ 21
The last line displays one of the
Perm. night
following operating modes:
– Perm. night
– Perm. day
– Auto night
– Auto day
– Holiday
– Summer
– ON optimisation
– OFF optimisation
– Cement (screed)
– DHW priority
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 125
18 Low loss header monitor data
Switch-ON optimisation
Switch-OFF optimisation
– 50 % = valve is commanded in a
cycle of 10 seconds, i.e.
5 seconds towards "Open valve"
(hotter).
Pump
126 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Low loss header monitor data 18
Using the Monitor menu "DHW" you can display the data
relating to the DHW settings.
Monitor
Press and release the button. The first menu item "Low loss header"
MONITOR appears.
DHW
Optimise
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 127
18 Low loss header monitor data
Turn the dial to scroll through The position of the valve indicates
the DHW monitor data. MONITOR DHW a setting between 0 % (closed) and
Primary pump 80% 100 % (open).
Second. pump 100%
Mix. valve pos. 100%
USER NOTE
128 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Display version 19
19 Display version
Version
Press and release the button. The version no. for the MEC and the
SERVICE LEVEL control unit are displayed.
MEC 6.xx
Control panel 6.xx
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 129
20 Selecting the control unit
Control panel
Logamatic
4211
Logamatic
Release the dial to store the 41xx
setting.
Press once. Back to the next higher level.
130 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Reset 21
21 Reset
Reset
Press and hold down the The blocks in the last line disappear
button. RESET one after the other. All settings are
Settings reset after the final block has
Control panel disappeared.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 131
21 Reset
Reset
Error
Press and hold down the The blocks in the last line disappear
button. RESET one after the other. The error log is
reset after the final block has
Error disappeared.
132 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Reset 21
Reset
Maintenance message
Press and hold down the The blocks in the last line disappear
button. RESET one after the other. The maintenance
message is reset after the final block
Maintenance message has disappeared.
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 133
22 Sensor curves
22 Sensor curves
Resistance (kΩ)
134 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Sensor curves 22
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 135
22 Sensor curves
4
3
2
136 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Keyword Index 23
23 Keyword Index
A FM 441 . . . . . . . . . . . . . . . . . . . . . . . 14
FM 442 . . . . . . . . . . . . . . . . . . . . . . . 16
Actual room temperature . . . . . . . . . . . . . 67
FM 445 . . . . . . . . . . . . . . . . 18, 91, 92, 93
Adjusting the setting . . . . . . . . . . . . . . . . 60
FM 456 . . . . . . . . . . . . . . . . . . . . . . . 20
FM 457 . . . . . . . . . . . . . . . . . . . . . . . 20
B
Frost protection temp. . . . . . . . . . . . . . . . 73
Base point . . . . . . . . . . . . . . . . . . . . . 53
Basic equipment . . . . . . . . . . . . . . . . . . 12 G
Boiler temperature . . . . . . . . . . . . . . . 50, 96
General Data . . . . . . . . . . . . . . . . . . . . 32
Boiler type . . . . . . . . . . . . . . . . . . . . . 47
Boiler type codes . . . . . . . . . . . . . . . . . 22
H
C Heating charact. . . . . . . . . . . . . . . . . . 108
Heating circ. no . . . . . . . . . . . . . . . . . . . 55
Cellar . . . . . . . . . . . . . . . . . . . . . . . . 55
Heating circ. valve . . . . . . . . . . . . . . . . . 75
Cement (screed) . . . . . . . . . . . . . . . . . . 78
Heating circ., apartment . . . . . . . . . . . . . . 55
Changeover between summer and winter . . . . . 60
Heating circ., bath . . . . . . . . . . . . . . . . . 55
Changing the operating mode . . . . . . . . . . . 60
Heating circ., building . . . . . . . . . . . . . . . 55
Circulation pump intervals . . . . . . . . . . . . 106
Heating circ., swimming pool . . . . . . . . . . . . 55
CM 431 . . . . . . . . . . . . . . . . . . . . . . 10
Heating circuit functions . . . . . 13, 15, 17, 19, 21
Constant . . . . . . . . . . . . . . . . . . . . . . 53
Heating circulate data . . . . . . . . . . . . . . . 53
Control device address . . . . . . . . . . . . . . 10
Heating system . . . . . . . . . . . . . . . . . . . 53
Control panel . . . . . . . . . . . . . . . . . . . 130
Holiday function . . . . . . . . . . . . . . . . . . 60
Controls . . . . . . . . . . . . . . . . . . . . . . . 8
Hysteresis . . . . . . . . . . . . . . . . . . . . . 90
Convector heater . . . . . . . . . . . . . . . . . 53
I
D
Increasing boil. . . . . . . . . . . . . . . . . . . . 77
Design temperature . . . . . . . . . . . . . . . . 57
Input 0 - 10V . . . . . . . . . . . . . . . . . . . . 20
DHW . . . . . . . . . . . . . . . . . . . . . . . . 85
Inserted modules . . . . . . . . . . . . . . . . . . 8
DHW circulation pump . . . . . . . . . . . .105, 107
DHW functions . . . . . . . . . . . . . . . . . . . 19
J
DHW priority . . . . . . . . . . . . . . . . . . . . 74
Disinfection . . . . . . . . . . . . . . . . . . . . 98 Jumper block . . . . . . . . . . . . . . . . . . . . 21
Disinfection temperature . . . . . . . . . . . . . 102
Domestic hot water functions . . . . . . . . . 13, 15 L
LCD test . . . . . . . . . . . . . . . . . . . . . 111
E Low loss header . . . . . . . . . . . . . . . . . 121
EMS/SAFe . . . . . . . . . . . . . . . . . . . . . 22
EMS/UBA 3 . . . . . . . . . . . . . . . . . . . . 22 M
Error . . . . . . . . . . . . . . . . . . . . .112, 132 Manual control fault message . . . . . . . . . . . 38
Max flow temp. . . . . . . . . . . . . . . . . . . . 59
F Max room infl . . . . . . . . . . . . . . . . . . . . 62
Faults . . . . . . . . . . . . . . . . . . . . . . 113 MEC 2 programmer . . . . . . . . . . . . . . . . 25
Flow setback . . . . . . . . . . . . . . . . . . . . 66 Module selection . . . . . . . . . . . . . . . . . . 41
Flow temperature . . . . . . . . . . . . . . . . . 59 Monitor data . . . . . . . . . . . . . . . . . . . 121
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 137
23 Keyword Index
N U
Night setback with room temperature stop . . . . . 60 UBA . . . . . . . . . . . . . . . . . . . . . . . . 22
No. of boilers . . . . . . . . . . . . . . . . . . . . 42 Under . . . . . . . . . . . . . . . . . . . . . . . 53
Under floor . . . . . . . . . . . . . . . . . . . . 55
O Under floor heating . . . . . . . . . . . . . . 53, 55
Offset . . . . . . . . . . . . . . . . . . . . . . . . 67 Universal burner control . . . . . . . . . . . . . 22
Optimisation . . . . . . . . . . . . . . . . . . . . 69
Optimisation, DHW . . . . . . . . . . . . . . . . . 87
V
Valve . . . . . . . . . . . . . . . . . . . . . . . 75
P Version . . . . . . . . . . . . . . . . . . . . . . 129
Party function . . . . . . . . . . . . . . . . . . . . 60
Password . . . . . . . . . . . . . . . . . . . . . . 29
W
Pause function . . . . . . . . . . . . . . . . . . . 60 Water connection . . . . . . . . . . . . . . . . . 85
R Z
Radiator . . . . . . . . . . . . . . . . . . . . . . 53 ZM 424 . . . . . . . . . . . . . . . . . . . . . . 12
RC30 . . . . . . . . . . . . . . . . . . . . . . . . 24
Relay test . . . . . . . . . . . . . . . . . . . . . 109
Reload the cylinder . . . . . . . . . . . . . . . . . 90
Remote control . . . . . . . . . . . . . . . . . . . 60
Remote control without display (BFU) . . . . . . . 60
Remote system . . . . . . . . . . . . . . . . . . . 37
Rename the heating circuit . . . . . . . . . . . . . 55
Reset . . . . . . . . . . . . . . . . . . . . . . . 131
Reset all settings. . . . . . . . . . . . . . . . . . 131
Rest heat use . . . . . . . . . . . . . . . . . . . . 88
Room . . . . . . . . . . . . . . . . . . . . . . . . 53
Room controller . . . . . . . . . . . . . . . . . . . 53
S
Select the heating system . . . . . . . . . . . . . 53
Select the remote control . . . . . . . . . . . . . . 60
Sensor curves . . . . . . . . . . . . . . . . . . 134
Sequence contrl . . . . . . . . . . . . . . . . . . 51
Set the low end . . . . . . . . . . . . . . . . . . . 56
Set the outside stop temperature . . . . . . . . . . 65
Setback type . . . . . . . . . . . . . . . . . . . . 63
Setting parameters . . . . . . . . . . . . . . . . . 7
Single load . . . . . . . . . . . . . . . . . . . . . 98
T
Thermal disinfection . . . . . . . . . . . . . . . 100
Type of building . . . . . . . . . . . . . . . . . . . 32
Type of setback, outside stop . . . . . . . . . . . 65
138 Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004
Notes
Service instructions Logamatic 4121, 4122 and 4126 control devices • Issue 03/2004 139
Your installer: