AREVA T&D
APPLICATION > MiCOM P992 Multi-finger Test Plug
The P990 series allows easy wiring verification and Access to the circuits connected to the P991 test block
aids commissioning of relays and instruments. It can be is provided by the P992 multi-finger test plug. The P992
used as a test facility either for individual relays or a is compatible with any configuration of the P991.
protection scheme. The P991 test block offers facilities
for monitoring and secondary injection testing of power The P992 enables convenient wiring of the test
system protection schemes and measurement equipment prior to insertion into the test block.
schemes when used with the P992 multi-finger test
plug. Use of the P992 ensures that the circuits operate in a
predetermined sequence, according to the application,
Access to current transformers (CT), voltage before breaking the connection between the circuit and
transformers, auxiliary supply, plant status and trip line connection.
circuits is possible without the need to disturb the relay Each socket is numbered at the front and relates to the
or instrument wiring. corresponding terminal on the rear of the test block.
> MiCOM P991 Test Block > MiCOM P993 Single-finger Test Plug
The P991 test block houses fourteen cassettes. The P993 single-finger test plug is provided for the
verification of CT circuits. It has been designed solely
The cassettes are of modular construction. The for use with the CT cassette of the P991 test block.
cassettes contain contact pairs that allow circuits to be
completed via the screw terminals at the rear. Note that For maximum safety, the P993 converts the monitored
blank cassettes are an exception that have no contacts. current into a voltage which can be measured using a
high impedance voltmeter.
There are specific types of cassette to suit any circuit;
these can be configured in any order. The isolation between contact-fingers and 4mm output
sockets is 5kV rms.
2>3
CONFIGURATION CIRCUIT TYPES
Stage I
Stage II
Stage III
CT
CT Shorting
CT
Breaking
Monitoring
Extraction
Stage III
Stage II
Stage I
> Monitoring cassette INSTALLATION AND USE
The two terminals of this cassette are permanently The generic safety guide R4129 and the
isolated from each other. This provides the facility to P990 Service Manual 'Automation-L4-P99x Service
monitor two independent parameters eg. + and - manual-0689-EN' should be read before installing or
auxiliary supply terminals. using the P990 series test block or test plugs.
When connected to the positive and negative terminals
of the auxiliary power supply this provides access for
monitoring and the supply of power to test equipment. > Test block
Caution should be exercised when using No cassettes other than CT cassettes shall be used for
this cassette type, since between Stage I connection to CT circuits.
and Stage III, one side of the plug contact Only the odd numbered terminals should be used for
will be momentarily connected with inverse P991 test block line side connections, (e.g. line CT
polarity. connections), to maintain automatic CT shorting.
Even numbered terminals are generally designated as
The Monitoring cassette should only be used for the relay/instrument side of the block.
monitoring purposes. Damage could be caused if it is
used to power any products using EMC input filtering This product must not
or ancillary equipment with an earthed supply input be disassembled.
terminal.
Stage I I White
Stage II II White > Multi-finger test plug
Stage III III White
Do not use P992 to break normally
Blank None White
closed live circuits without a shorting
link in place.
A space is provided for customer defined labels on the
Do not short-circuit the terminals of
cover to identify circuits.
normally open monitor cassettes.
4>5
Before use, the insulation of test leads should be Care must be taken when removing the P992 from the
visually checked for damage. P991 test block to avoid contact bounce, which may be
experienced during rapid withdrawal.
The retaining nuts should be hand tightened after
insertion of the P992, to ensure that the P992 cannot When the P992 is not in use, it should be stored in its
be accidentally withdrawn. See figure 2. protective case to maintain the test plug in a
serviceable condition.
Figure 2
There are two ranges of current measurement on the
single-finger test plug. Each range has a scaling factor
as detailed in Table 1.
To use the extraction stop feature, first centralise the
extraction stops about the nuts (see figure 3). P993 Setting Range (A) Scaling factor
for 2V range*.
1 0-2 1V = 1A
2 2-20 1V = 10A
Table 1: Single-finger test plug ranges
Then pull out the P992 until it stops in the stage 1 When the P993 is not in use, it should be stored in its
position, see figure 4. protective case to maintain the test plug in a
serviceable condition.
Figure 4
INFORMATION REQUIRED WITH ORDER
Test block
Cassette position 1
Cassette position 2
Cassette position 3
Cassette position 4
Cassette position 5
Cassette position 6
Cassette position 7
Cassette position 8
Cassette position 9
Cassette position 10
Cassette position 11
Cassette position 12
Cassette position 13
Cassette position 14
Cassette 1 is at the top and cassette 14 at the bottom.
If it is necessary to reconfigure the P991 build after manufacture, then for safety reasons,
the assemblies must be returned to the manufacting plant, for this purpose.
Cassette type numbers used for ordering, these are To achieve IP52 dust/water protection the cover must
used in the P991 test block number : be fitted.
Side view
All dimensions in mm
51.0 31.0
6>7
TECHNICAL DATA SUMMARY TEST BLOCK AND TEST PLUGS
• Less than 10mΩ on both setting ranges Type M4 ring 90° Straight
Supplier JST JST/AMP
> Current withstands Terminal 2 0
connector 1 1
• 20A continuous (UL 5A nominal)
combinations 0 1
150A for 10s
Pre-insulated connectors Wire range 0.25mm² -
500A for 1s
(red) 1.65mm²
Pre-insulated connectors Wire range 1.04mm² -
(blue) 2.63mm²
Post insulated (sleeved) Wire range 2.64mm² -
connectors 6,64mm²
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
AUTOMATION-L3-P99x-BR-01.05-0799-GB - © - AREVA - 2005. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
AREVA T&D Worldwide Contact Centre: Our policy is one of continuous development. Accordingly the
http://www.areva-td.com/contactcentre/ design of our products may change at any time. Whilst every
effort is made to produce up to date literature, this brochure
Tel.: +44 (0) 1785 250 070 should only be regarded as a guide and is intended for
information purposes only. Its contents do not constitute an offer
for sale or advise on the application of any product referred to in
www.areva-td.com it. We cannot be held responsible for any reliance on any
decisions taken on its contents without specific advice.