Beruflich Dokumente
Kultur Dokumente
3
the supply frequency allow detecting unbalance problems.
2f
A similar analysis can be used to study the effects of 2
e
voltage distortion over the instantaneous power, torque and
vibrations. As an example, frequency components at 4ωe 1
P0
in order to determine if the perturbation is produced by a 3
sequence voltages and currents. This relationship depends, in Fig. 2. Instantaneous active power spectrum for 3.6% voltage unbalance,
turn, on voltage unbalance, the motor operation condition, 6% THD and 75% load. (Simulation)
and its parameters, among others.
Assuming an electrically balanced motor, i.e. a motor 5
without faults, the analysis of voltage unbalance can be 100%
performed using an induction motor model in q - d variables 4
Power 100 Hz (kW)
fully loaded motor) are presented in Figs. 1 to 3. Data and Fig. 3. Amplitude of the 100 Hz instantaneous active power component.
parameters of the simulated motor are shown in the (Simulation)
Appendix.
The instantaneous active power spectrum is shown in Fig.
1 for a motor operating at 75% load, supplied by source with
Autotransformers Accelerometer 5
3∅ IM
(under test)
3∅ 4
Power (kW)
3 P0
IM
kv IM Drive 2
(Load)
Filter
1
Encoder 2 fe 4f
Torque e
Ref. 0
PC Recorder 0 50 100 150 200 250
Frequency (Hz)
Fig. 4. Experimental setup. (a)
5
Power (kW)
P0
V. EXPERIMENTAL RESULTS 3
( kv ) . 25
Two phase currents and two line voltages were measured
Torque (Nm)
20
in order for the instantaneous power to be calculated and the T0
motor torque to be estimated. The measured signals were 15
0.8
8
fr
0.6
Amplitude (mm/s)
6 Closed slots
4 fr
Zn (Ω)
0.4 2 fe 4
0.2
2
4 fe Open slots
0
0 50 100 150 200 250 0
0 20 40 60 80 100
Frequency (Hz)
Load (%)
(a) (a)
0.8
8
fr
0.6 2f
Amplitude (mm/s)
e
6
Amplitude (Ω)
XL
0.4 4 fr
4
0.2
4f 2
e
R
0 0
0 50 100 150 200 250 0 20 40 60 80 100
Frequency (Hz)
Load (%)
(b) (b)
Fig. 7. Vibration velocity spectrum for the motor operating at 75% load. Fig. 9. Negative-sequence impedance as a function of the motor load:
(a) Balanced voltages. (b) 3.6% voltage unbalance (a) Modulus. (b) Real (resistance, R) and imaginary (reactance, XL) parts.
Open rotor slots (solid); closed rotor slots (dashed).
5 5
100% 75%
4 4
Power 100Hz (kW)
0% 50%
3 3
25%
2 2
0%
1 1
0 0
0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8
Voltage unbalance (%) Voltage unbalance (%)
(a) (a)
25 25
100% 75%
20 100%
50%
15 0% 15
25%
10 10
0%
5 5
0 0
0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8
Voltage unbalance (%) Voltage unbalance (%)
(b) (b)
2.5 2
100% 100%
Velocity 100 Hz (mm/s)
2 1.6 75%
Velocity 100 Hz (mm/s)
50%
1.5 1.2
0% 25%
1 0.8
0.5 0.4 0%
0 0
0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8
Voltage unbalance (%) Voltage unbalance (%)
(c) (c)
Fig. 10. Motor with open rotor slots. Amplitude of the 100 Hz component Fig. 11. Motor with closed rotor slots. Amplitude of the 100 Hz component
of: (a) instantaneous active power, (b) torque and (c) vibrations. of: (a) instantaneous active power, (b) torque and (c) vibrations.
The behavior of the 2 f e component of the As mentioned in section II, predictive maintenance
electromagnetic torque is very similar to the one of the programs usually use the RMS value of the vibration
instantaneous power, as it can be appreciated in Fig. 10(b). velocity as an indicator of the motor condition. The RMS
The 100 Hz component of the vibration velocity is shown value of the vibration velocity as a function of the voltage
in Fig. 10(c), where it can be seen that it significantly grows unbalance is shown in Fig. 12, for different motor loads.
with the voltage unbalance, while being practically This result was obtained for the motor with closed rotor
independent of the load level, the same as the instantaneous slots.
active power and torque. According to the ISO 10816-1 standard [19], vibration
velocities between 0-0.71 mm/s (zone A) correspond to
B. IM with closed rotor slots machines just put into operation. Values between 0.71-1.8
Fig. 11 shows the amplitude of the 2 f e component of the mm/s (zone B) correspond to equipment which can operate
continuously without any restrictions. Finally, values
power, torque and vibrations, for different values of voltage between 1.8 and 4.5 mm/s (zone C) indicates that the
unbalance and motor load, for the motor with closed rotor condition is acceptable only for a limited period of time.
slots. As it can be seen, the component of both the power As it can be appreciated in Fig. 12, voltage unbalance
and the torque (Fig. 11(a) and (b), respectively) significantly produce an increase of the RMS vibration velocity, due to
vary with the motor load. This important difference with
the grow of the 2 f e component. For the motor with closed
respect to the motor with open rotor slots is principally due
to the negative-sequence impedance grows for low load rotor slots, this value also depends on the motor load and
levels. This produce a diminution of the negative-sequence machine defects or constructive parameters. Thus, it is
current for a given voltage unbalance. Since this effect important to note that, if the motor vibration at a given
predominates at low load levels, the behavior of the two operation condition are close to the established limits,
types of motor from 50% load is similar. transient supply voltage unbalances could produce false
The component of vibration velocity at 2 f e also grows alarms when the RMS velocity vibration value is used as an
indicator of the motor condition. A more complete vibration-
with the voltage unbalance and, different from the motor based condition monitoring system should take into account
with open rotor slots, also changes with the motor load. The
the variation of the 2 f e component to improve the motor
reason is the variation of the negative-sequence impedance,
as explained before. protection.
2
C [5] NEMA Standard MG1 - Motor and Generators, 1993.
1.8 [6] P. Pillay, P. Hofmann and M. Manyage, “Derating of induction
100%
1.6 Motors Operating with a Combination of Unbalanced Voltages and
Velocity (mm/s− rms)