Current Derated

Required

Efficiency
Power Full Load rating of Current

AC / DC

PHASE
Sin Length Derating Current Checking for Running
CABLE LOAD factor     current Cable Size Cable size the rating of > Result
Φ (M) factor Rating - full voltage drop
(Cos Φ) (A) cable   the
Load (A)
(A) cable  (A)

FROM TO
%
    No. of % Estimated Allowable
kW  or                   No. of Size
VOLTS runs/Ph Running Running
KVA Cores Sq.mm
EQUIPMET TAG No. Run Run . Voltage drop voltage
PLATFORM PLATFORM drop

631-004-MCC-009 1039.20 kVA 480 AC 3 0.83 0.56 1 300 1250.00 6 3 185 3C X 185 420 0.63 1587.6 > 1250.00 3.52 3.7 OK

631-004-MCC-010 665.09 kVA 480 AC 3 0.83 0.56 1 300 800.00 4 3 185 3C X 185 420 0.63 1058.4 > 800.00 3.38 3.7 OK
AUX
PLAT
631-004-MCC-011 1039.20 kVA 480 AC 3 0.83 0.56 1 300 1250.00 6 3 185 3C X 185 420 0.63 1587.6 > 1250.00 3.52 3.7 OK
PROD
PLAT
631-004-MCC-012 665.09 kVA 480 AC 3 0.83 0.56 1 300 800.00 4 3 185 3C X 185 420 0.63 1058.4 > 800.00 3.38 3.7 OK

631-004-MCC-011 523.76 kVA 480 AC 3 0.86 0.51 1 450 630.00 5 3 185 3C X 185 420 0.63 1323 > 630.00 3.19 3.7 OK
EDP
631-004-MCC-012 523.76 kVA 480 AC 3 0.86 0.51 1 450 630.00 5 3 185 3C X 185 420 0.63 1323 > 630.00 3.19 3.7 OK

631-002-MCC-005 1039.20 kVA 480 AC 3 0.83 0.56 1 361 1250.00 7 3 185 3C X 185 420 0.63 1852.2 > 1250.00 3.63 3.7 OK

631-002-MCC-006 1039.20 kVA 480 AC 3 0.83 0.56 1 361 1250.00 7 3 185 3C X 185 420 0.63 1852.2 > 1250.00 3.63 3.7 OK
EDP TIE-IN
631-002-MCC-007 665.09 kVA 480 AC 3 0.86 0.51 1 361 800.00 5 3 185 3C X 185 420 0.63 1323 > 800.00 3.25 3.7 OK

631-002-MCC-008 665.09 kVA 480 AC 3 0.86 0.51 1 361 800.00 5 3 185 3C X 185 420 0.63 1323 > 800.00 3.25 3.7 OK

631-004-MCC-021 1662.72 kVA 480 AC 3 0.93 0.37 1 311 2000.00 10 3 185 3C X 185 420 0.63 2646 > 2000.00 3.42 3.7 OK

631-004-MCC-022 1662.72 kVA 480 AC 3 0.93 0.37 1 311 2000.00 10 3 185 3C X 185 420 0.63 2646 > 2000.00 3.42 3.7 OK

631-004-MCC-023 1039.20 kVA 480 AC 3 0.93 0.37 1 311 1250.00 6 3 185 3C X 185 420 0.63 1587.6 > 1250.00 3.56 3.7 OK

631-004-MCC-024 1039.20 kVA 480 AC 3 0.93 0.37 1 311 1250.00 6 3 185 3C X 185 420 0.63 1587.6 > 1250.00 3.56 3.7 OK
AUX ACCOM
PLAT PLAT
631-004-MCC-025 1039.20 kVA 480 AC 3 0.86 0.51 1 311 1250.00 6 3 185 3C X 185 420 0.63 1587.6 > 1250.00 3.64 3.7 OK

631-004-MCC-026 1039.20 kVA 480 AC 3 0.86 0.51 1 311 1250.00 6 3 185 3C X 185 420 0.63 1587.6 > 1250.00 3.64 3.7 OK

631-004-MCC-027 1039.20 kVA 480 AC 3 0.86 0.51 1 311 1250.00 6 3 185 3C X 185 420 0.63 1587.6 > 1250.00 3.64 3.7 OK

631-004-MCC-028 1039.20 kVA 480 AC 3 0.86 0.51 1 311 1250.00 6 3 185 3C X 185 420 0.63 1587.6 > 1250.00 3.64 3.7 OK

Geethanjali/ Arun,

Please note,
- Below are the cable sizes w.r.to 3.7% of Voltage drop
- Sized based on bus bar rating for both Cable ampacity & Voltage drop calculation.
- YELLOW Highlighted cables  - CHN Scope
- Cables from EDP to Prod & Tie-in Platform shall be confirmed by DXB
- GCP MCCs Incomer cable sizes shall be provided by DXB as the bus rating is unknown as of now.
- Better keep 3.0 % Voltage drop in bridges, add to use 0.7% at Lighting DB and Power DB. This is help to use single run cable at outdoor Distribution Board. (Oher wise suggest alternate method)