Compact controller
Easy controller
ED
VD
I 6022
Tested to VDI 6022
Type Page
LVC General information LVC – 2
Function LVC – 4
Technical data LVC – 5
Quick sizing LVC – 6
Specification text LVC – 7
Order code LVC – 8
Attachments LVC – 9
Dimensions and weight LVC – 10
Product details LVC – 11
Installation details LVC – 12
Basic information and nomenclature LVC – 14
– Casing air leakage to EN 1751, class C materials are not subject to wear
Maintenance
– Maintenance-free as construction and
① ②
③
⑥ ⑤
Volume flow rate ranges depend on the nominal size and on the control
The minimum differential pressure of VAV terminal component (attachment) that is installed. The
units is an important factor in designing the table gives the minimum and maximum values for
ductwork and in rating the fan including speed a VAV terminal unit. Some control components
control. may only have a limited volume flow rate range.
Sufficient duct pressure must be ensured for all This applies in particular to control components
operating conditions and for all control units. The with a static differential pressure transducer. For
measurement points for fan speed control must be volume flow rate ranges for all control components
selected accordingly. refer to our Easy Product Finder design
The volume flow rates given for VAV terminal units programme.
Circular VAV terminal units for variable air volume – Nominal sizes: 125 to 250 mm
systems with low airflow velocities, suitable for – Volume flow rate range: 8 to 300 l/s or
supply or extract air, available in four nominal 30 to 1080 m³/h
sizes. – Volume flow rate control range:
Measurement and control of low volume flow rates approx. 10 – 100 % of the nominal volume flow
based on a new measurement principle. Plastic rate
nozzle with damper blade for measuring the – Minimum differential pressure: 5 – 30 Pa
differential pressure upstream and downstream of – Maximum differential pressure: 600 Pa
the damper blade (effective pressure). The
relation between damper blade position and Attachments
differential pressure is stored as a characteristic Variable volume flow control with electronic Easy
relationship in the Easy or Compact controller. controller to connect an external control signal;
This results in high control accuracy even in case actual value signal can be integrated into the
of unfavourable upstream conditions. central BMS.
Selection based on nominal size determination. – Supply voltage 24 V AC/DC
Ready-to-commission unit which consists of the – Signal voltages 0 – 10 V DC
mechanical parts and the electronic control – Possible override controls with external
components. Units are equipped with a plastic switches using volt-free contacts: CLOSED,
nozzle with integral damper blade. OPEN, min and max
The averaging differential pressure sensor is – Potentiometers with percentage scales to set
resistant to dust and pollution. the volume flow rates min and max
Spigot with lip seal, for circular connecting ducts – The actual value signal relates to the nominal
to EN 1506 or EN 13180. volume flow rate such that commissioning and
Position of the damper blade indicated externally subsequent adjustment are simplified
at shaft extension. Damper blade is factory set to – Volume flow rate control range:
open position which allows ventilation airflow even approx. 10 – 100 % of the nominal volume flow
without control. rate
Closed blade air leakage to EN 1751, at least – Clearly visible external indicator light for
class 1. signalling the functions: Set, not set, and power
Casing air leakage to EN 1751, class C. failure
Electrical connections with screw terminals.
Special features Double terminals for looping the supply voltage,
– Optimised for low airflow velocities from i.e. for the simple connection of voltage
0.6 to 6 m/s transmission to the next controller.
– High control accuracy even in case of
unfavourable upstream conditions Sizing data
– Any installation orientation – _____________ _______________________
– Volume flow rate control with Easy or Compact [m³/h]
controller – Δpst___________ _______________________
– Casing length of only 310 mm [Pa]
Air-regenerated noise
Materials and surfaces – LPA____________ _______________________
– Casing made of galvanised sheet steel [dB(A)]
– Nozzle, damper blade, and plain bearings Case-radiated noise
made of ABS plastic, UL 94, flame retardant (V- – LPA____________ _______________________
0) [dB(A)]
– Damper blade seal made of TPV (plastic)
Technical data
LVC
LVC
310
20
ØD
~80
LVC
ØD m
Nominal size
mm kg
125 124 1.5
160 159 1.9
200 199 2.1
250 249 2.7
Upstream conditions
The volume flow rate accuracy Δ applies to a
straight upstream section of the duct. Bends,
junctions or a narrowing or widening of the duct
cause turbulence that may affect measurement.
Duct connections, e.g. branches off the main duct,
must comply with EN 1505. Some installation
situations require straight duct sections upstream.
Bend
1D
Δp M
Junction
D
Δp M
Space required
① ② ③
Attachments
mm
VARYCONTROL
Easy controller 370 200 300
Compact controller 370 200 200
Definition of noise
② ①
LPA
① Air-regenerated noise
② Case-radiated noise
max [m³/h] and [l/s] Δ [± %]
Upper limit of the operating range for the VAV Volume flow rate tolerance from setpoint value
terminal unit that can be set by customers
Δwarm [± %]
– max can only be smaller than or equal to nom
Volume flow rate tolerance for the warm air flow of
– In case of analog signalling to volume flow
dual duct terminal units
controllers (which are typically used), the set
maximum value (max) is allocated to the
∆pst
covers, are usually made of galvanised sheet – Parts in contact with the airflow are powder-
steel coated or made of stainless steel
– External parts, e.g. mounting brackets or
Stainless steel (A2) covers, are usually made of galvanised sheet
– Casing made of stainless steel 1.4201