Sie sind auf Seite 1von 2

TECHNICAL SPECIFICATION

Mobile Rect 110 / 48 – 100 A

Manufacturer ENERMILD INDONESIA


Merk / Type MOBILE RECT 110/48 - 100 A
Control Method Full Bridge Thyristor Controlled
Input Voltage Three Phase, 380 Vac (nominal) range : -15% / +15%
Input Frequency 50 Hz (nominal) range : ± 10 % (45 ~ 66 Hz)
Output Voltage Dual Voltage 110 / 48 Vdc (nominal)
Output Ripple Voltage ± 1 % Vpp, without battery
Output Voltage Adjustment
110 VDC SYSTEM Adjustment: 89 - 157 Vdc

48 VDC SYSSTEM Adjustment: 36 - 70 Vdc

Output Current Capacity 100 Adc (max)


Battery Current Limit Adjustment Battery Current Limit Adjustment : 0 - 100 A
Input Protections Phasa fail , Magnetic Circuit Breaker (MCB)
Output Protections Over temperature, MCB protection
Battery Protections limit current adjusment, MCB protection
Metering Ampere meter DC output Analog, Voltage meter DC output Digital
Status Indicators & Alarms RST Lamp , 110 Vdc On, 48 Vdc On, Rectifier Fail
Rectifier Mode Indicators (no alarm) Float , Boost, Equalize, Rectifier fail
Selector Switch 110Vdc - 48Vdc
Enclosures Steel construction with Indoor Service NEMA 12 Std
Front side mounting for all Switches, Meters and Indicator Lamps.
Corrosion resistant materials or treatment (galvanized) for handles,
screws, hinges
Powder Coating Painting for Enclosure
Altitude 1000 Meters
Humidity 95%
Ambient Temperature 10 - 60 ºC
Wearing & Accessories Marking cable & cable capacity standard
Tested Form test / Check list / Test Report
Grounding Ground Connector available
Dimension 800 x 600 x 600 mm
Weight +/- 120 Kg
Warranty 3 year / 36 month