Beruflich Dokumente
Kultur Dokumente
net/publication/261260327
CITATIONS READS
4 127
5 authors, including:
Piotr Pierz
Wroclaw University of Science and Technology
21 PUBLICATIONS 59 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Jan Izykowski on 05 May 2014.
known for its many advantages over low-impedance and faulted line [1].
solidly grounded systems. A ground fault on the high- a b c
protection functions using such data, especially if the fault • select the feeder with maximum of ϕ0m, m=1, ..., M.
event is recorded at both the fault branch and the measurement
For proper and reliable operation this algorithm should be
terminals. However, it imposes a high and severe risk on the
additionally adjusted. This includes the following limits:
electrical networks and there are restrictions against further
• if the magnitude of power fulfills the condition:
use of staged faults. On the other hand, experimental work is
|S0m|>S0min, otherwise ϕ0m=0;
still used to determine the characteristics of the high
impedance faults associated with arcs [12], [13]. However, • if the zero-sequence current magnitude is greater than
these investigations are insufficient for managing situations some limit: |I0m|>I0min;
where several faults simultaneously occur at a number of • the selected maximum value calculated phase should
locations in the network. be greater than some setting (threshold) value ϕ0t.
Generally, all these methods for ground-fault detection are
nonselective. The faulted phase is identified, but the fault So, the algorithm has two settings: S0min and ϕ0t, which
could be anywhere in the network [12]. Because the fault should be adequately selected.
current in high-impedance fault-loop can be similar in In the above algorithm the power components are
magnitude to the charging currents, it is difficult to distinguish calculated from zero-sequence voltage and current orthogonal
between the two. Thus, determination of a faulty feeder during components. The last are estimated by using the standard full-
the ground fault is difficult and needs further investigation. period Fourier algorithm:
The presented algorithm for selection of a faulty feeder
N −1
during phase-to-ground fault utilizes the fault signals transient 2
component, which provides very fast information about the
X R (k ) =
N
∑ x( k − i ) h
i =0
R (i)
possible disturbance in the system. N −1
(1)
2
X I (k ) =
N
∑ x(k − i)h (i)
i =0
I k = 0,1...
III. ALGORITHM DESCRIPTION
The main idea of the algorithm is based on the analysis of
the polarity between a current and a voltage changes directly where: hR (i) = cos(ν (i + 0.5)) , hI (i) = sin(ν (i + 0.5)) , ν = 2π/N,
after the fault inception. The described algorithm is designed N – number of s/c, applied for zero-sequence voltage and
for centralized substation level protection and therefore current.
utilizes the zero sequence bus-bar voltage and residual Next, having these orthogonal components the active and
currents from all outgoing feeders for detection a faulty reactive power may be calculated:
feeder. A criteria phase is calculated for each feeder as an
angle between active and reactive power determined for zero- 1
sequence component. The full-period Fourier algorithm is P0 (k ) = (V0 R (k ) I 0 R (k ) + V0 I (k ) I 0 I (k ))
2
used for adequate voltage and current phasors determination. (2)
1
Figure 3 shows the general concept of the algorithm. Q0 (k ) = (V0 I (k ) I 0 R (k ) − V0 R (k ) I 0 I (k ) )
Excepting details the algorithm can be split into the following 2
steps:
Finally, the power angle is calculated:
• calculate the zero-sequence power S0m for each feeder
m = 1, ..., M (for M feeders);
⎛ Q0 (k ) ⎞
• calculate the power angle ϕ0m for each feeder m = 1, ..., ϕ o (k ) = atan⎜⎜ ⎟⎟ (3)
M; ⎝ P0 (k ) ⎠
i01(t) i01(k)
S/H I01=I01R+jI01I
ϕ01(k)
S01=P01+jQ01 ϕ01=atan2(Q01,P01)
v0(t) v0(k)
S/H V0=V0R+jV0I
ϕ0mx result
ϕ0m>ϕ0t
...
...
Max
In the above relation the angle should be determined in the capacitances, so the zero-sequence capacitive current changes
range of ±2π. from 0.5A to 40A, what is shown in Table 1. There is also
The physical structure of the considered relay is as follows: bus-bar capacitance included with the value of: C0S = 0.0153
• At each m feeder of the MV network there is installed μF. All these capacitances give zero-sequence capacitive
a box which function is to calculate a phase φm(k) at current: I0C ≈ 100 A for V0 = V1f. The neutral grounding
each time-step k. impedance equals ZN = (2+j240)Ω and corresponds for
• Signals containing calculated phases φm(k) from all M compensation factor XCs/XLN = 1.08. Faults are represented as
feeders are collected in a central box where the feeder permanent or intermittent. The last one is modeled with
with the maximum value of phase φm(k) is determined. random characteristics. The fault transients performance
Moreover, for accurate calculation of the angle (3), some depend on fault inception angle, which can be initiated by
limited (minimum) absolute value of power |P0(k) + jQ0(k)|, to changing of the fault-time inception or by changing of the
avoid inaccurate calculation, should be determined. voltage source angle.
The decision is ready if the condition: TABLE I
FEEDER CAPACITIVE PARAMETERS
ϕ0im (k ) > ϕ 0t , ϕ0im (k ) = max(ϕ 01 (k ), ϕ 02 (k ),L, ϕ0M (k ) ) (4) Parameter Zero-sequence Capacitive
capacitance/phase for one current, A
section, μF
where φ0t – setting threshold for angle value, Feeder 1, C011 .. C014 0.0153 0.5
is fulfilled for assumed ks consecutive samples for the same ith Feeder 2, C021 .. C024 0.0460 1.5
feeder. Feeder 3, C031 .. C034 0.0919 3.0
Feeder 4, C041 .. C044 0.1532 5.0
Feeder 5, C051 .. C054 0.3064 10.0
IV. SIMULATION EXAMPLES Feeder 6, C061 .. C064 0.4597 15.0
The discussed above algorithm for detection of faulty Feeder 7, C071 .. C074 0.770 25.0
Feeder 8, C081 .. C084 1.2258 40.0
feeder has been evaluated with using the fault data obtained Total values 4×3.0683=12.2732 100.0
from ATP-EMTP. Versatile simulations of faults in the
distribution (MV) system considering different fault resistance Two different cases were chosen for illustration of the
place and fault inception angle have been simulated. Step- algorithm. In both situations the phase-to-ground fault was
down transformer connects 110 kV system with 15 kV MV initiated in phase a of Feeder 1 (with minimum capacitive
network. The modeled MV distribution network consist of current) at tF = 0.04s.
eight feeders with different zero sequence capacitance. In the first example it is considered isolated network (high
Scheme of the considered network is presented in Fig. 4. impedance between nodes GR_N and GR_G in Fig. 4). The
I01 fault resistance is: RF=2500Ω. Waveforms of zero-sequence
110 kV
I
currents at faulty feeder (Feeder 1) and Feeder 8 and zero-
V sequence power angles (3) are presented in Fig. 5 and Fig. 6,
Y Y
SAT
I02
respectively.
STATION BUS
GR_N
ZN I03
I
I
GR_G
I04
I
V0
VABC
V0
V_0F
I05
I
STATION
COMPUTER
SWITCH
FAULT MODEL
It can be seen from Fig. 6 that, generally, faulty and
healthy feeders have opposite signs of the calculated zero-
Fig. 4. EMTP model of the considered system sequence power angle. Influence of some passing deviations
may be removed by adequate setting of the minimum positive
All feeders are represented by four identical serial value of the angle (Fig. 6). Moreover, it was observed that
connected circuits with longitudinal impedance: these deviations do not appear at the beginning of a fault
Zl1=(1.085+j0.915)Ω. Feeders have different zero-sequence period.
5
3
faulty feeder: Feeder 1
Fig. 10 presents the calculated angle of zero-sequence
threshold power for all eight feeders. Again, one can observe clear
2 separation of decision areas determined by zero-sequence
power angles with the exception of small deviations which
1
can be handled by adequate setting of φ0t (threshold).
0 Fig. 11 presents final selection of the faulted feeder. The
algorithm properly selects the faulty line. No decision periods
-1 are observed in segments when a fault disappears.
-2
-3
0.0 0.1 0.2 0.3 0.4 time, s 0.5
V 0, V
Consequently, for the considered example, the algorithm
can make the final decision during time periods for which the
condition (4) is fulfilled (high level for Feeder 1 in Fig. 7).
, rad
angle
4
I0, A
0
0.0 0.1 0.2 0.3 0.4 time, s 0.5
VI. REFERENCES Marek Fulczyk (M’04) received the M.Sc. and Ph.D.
degree in Electrical Eng. from the Wroclaw University of
[1] IEEE Recommended Practice for Grounding of Industrial and
Technology/Poland in 1993 and 1997, respectively. In 1997
Commercial Power Systems. IEEE Std 142-2007, Aug. 2007.
he joined ABB as a research scientist. Now he is a group
[2] S. Hänninen, 2001. Single phase earth faults in high impedance leader of Electrical & Engineering Systems at ABB
grounded networks - Characteristics, indication and location. Espoo. 78 Corporate Research in Krakow/Poland. His fields of
p. + app. 61 p. (VTT Publications No. 453), [Online]. Available: interests include power system protection, power
http://www.inf.vtt.fi/pdf/ system/voltage stability, and simulations of phenomena in
[3] S. Hänninen, M. Lehtonen, T. Hakola, E. Antila, J. Strom and S. power systems.
Ingman, “Characteristics of Earth Faults in Power Systems with a
Compensated or an Unearthed Neutral,” in Proc. CIRED. 14th Jan Izykowski (M’97, SM’04) received his M.Sc., Ph.D.
International Conference on Electricity Distribution (IEE Conf. Publ. and D.Sc. degrees in Electrical Eng. from the Faculty of
No. 438), 2-5 June 1997, pp. 16/1-16/5. Electrical Engineering of Wroclaw University of
Technology (WrUT) in 1973, 1976 and in 2001,
[4] J. Lorenc, K. Musierowicz, A. Kwapisz, “Detection of the Intermittent
respectively. In 1973 he joined Institute of Electrical
Earth Faults in Compensated MV Network, “ in Proc. 2003 IEEE
Bologna Power Tech Conference, June 23-26, Bologna, Italy, IEEE Engineering of the WrUT. Presently he is a Professor and
Catalogue No. 0-7803-7967-5/03 Director of this Institute. His research interests are in power
system simulation, power system protection and control,
[5] M. Michalik, W. Rebizant, M. Lukowicz, S-J Lee and S-H Kang, “High- and fault location.
Impedance Fault Detection in Distribution Networks With Use of
Wavelet-Based Algorithm," IEEE Trans. Power Delivery, vol. 21, pp. Eugeniusz Rosolowski (M’1997, SM’00) received his
1793-1802, Oct. 2006. M.Sc. degree in Electrical Eng. from the Wroclaw
[6] H. Belka, M. Michalik, “Application of the continuous wavelet University of Technology in 1972. From 1974 to 1977, he
transform to intermittent high impedance ground fault detection in MV studied in Kiev Politechnical Institute and received Ph.D. in
networks,” in Proc. Eighth IEE International Conference on Electrical Eng. in 1978. In 1993 he received D.Sc. in
Developments in Power System Protection, Amsterdam, 5-8 April 2004, Electrical Eng. from the WrUT. Presently he is a Professor
pp. 473-476. in the Institute of Electrical Engineering. His research
[7] N.I. Elkalashy, M. Lehtonen, H.A. Darwish, A-M Taalab I. Izzularab, interests are in power system analysis and relaying
“DWT-Based Detection and Transient Power Direction-Based Location algorithms.
of High-Impedance Faults Due to Leaning Trees in Unearthed MV
Networks.” IEEE Trans. Power Delivery, vol. 3, pp. 94-101, Jan. 2008. Piotr Pierz received his M.Sc. degrees in Electrical Eng.
[8] S. Hänninen, M. Lehtonen, 2001. ”Earth fault distance computation with and Biomedical Eng. from the Wroclaw University of
artificial neural network trained by neutral voltage transients, in Proc. of Technology (WrUT) in 1998, 2002 respectively. His area
IEEE PES SM2001. Vancouver, Canada, July 15-19. CD-ROM of interests are power system simulation, power system
01CH37262C. 6p. protection and power quality. Currently he is with WrUT
[9] M.F., Abdel-Fattah, M. Lehtonen, “Transient Fault Detection Technique where he is finishing his Ph.D.
with Varying Fault Detection Window of Earth Modes in Unearthed MV
Systems” in Proc. Power Quality and Supply Reliability Conference, PQ
2008, IEEE Catalogue No. 978-1-4244-2501-3/08, pp. 181-186.