Sie sind auf Seite 1von 7

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/261260327

Centralized substation level protection for determination of faulty feeder in


distribution network

Conference Paper · July 2012


DOI: 10.1109/PESGM.2012.6345484

CITATIONS READS
4 127

5 authors, including:

Jan Izykowski E. Rosolowski


Wroclaw University of Science and Technology Wroclaw University of Science and Technology
122 PUBLICATIONS   1,516 CITATIONS    128 PUBLICATIONS   1,775 CITATIONS   

SEE PROFILE SEE PROFILE

Piotr Pierz
Wroclaw University of Science and Technology
21 PUBLICATIONS   59 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Mathematical modeling of electric power systems View project

All content following this page was uploaded by Jan Izykowski on 05 May 2014.

The user has requested enhancement of the downloaded file.


1

Centralized Substation Level Protection for


Determination of Faulty Feeder in Distribution
Network
P. Balcerek Member IEEE, M. Fulczyk Member, IEEE, J. Izykowski Senior Member, IEEE,
E. Rosolowski Senior Member, and P. Pierz

and property in the event of faults and transient phenomena


Abstract-- This paper presents a novel approach to design of a resulting from switching operations. Another reason for
centralized substation level protection aimed at determining the adequate grounding of the network is to allow high sensitivity
faulty feeder in a distribution network. In opposite to phase-to- of the relays operation.
ground faults in the transmission networks (HV), impedance of
Fault detection and location invariably relies on the
phase-to-ground fault-loops in MV distribution networks is
usually high. From all of these reasons, detection of ground-fault presence of sufficiently high fault current and this is met in
and determination of a faulty feeder at a bus-bar with many the solidly grounded networks or when the grounding
outgoing feeders arises as serious problem. However, during the impedance is small – as far as a fault between one or more
ground-fault the transient component which provides important phases and ground is considered. Such conditions are not
information about the disturbance in the system appears. Such accomplished in MV networks with low ground-fault current,
signals consist of different frequency components, which result
as in isolated or compensated networks. Detection of ground-
from charging or discharging of the network capacitances. In this
paper new approach which is based on checking a phase fault and determination of a faulty feeder at a bus-bar with
displacement between a fundamental frequency component of many outgoing feeders arises as serious problem.
zero sequence current and a voltage directly after the fault This paper describes a novel method for ground fault
inception is presented. Provided simulation experiments in detection and selection of a faulty feeder at the substation in
ATP/EMTP software package confirm the effectiveness of the ungrounded, compensated and high-resistance grounded
proposed technique for selection of a faulty feeder during phase-
networks.
to-ground fault in different and under different fault scenarios-
different fault inception angles, including random mechanism
and high resistance faults. II. CHARACTERISTICS OF GROUND FAULTS
Regarding the method of the neutral grounding, the MV
Index Terms-- Distribution network, Fault detection, networks can be divided into the following categories:
Grounding, EMTP, Simulation. • directly or solidly grounded;
I. INTRODUCTION • network grounded through impedance; and

T HE method of power system grounding has the


fundamental influence on a phase-to-ground fault loop
impedance and consequently, on the value of fault current.
• isolated (ungrounded) network.
Solid neutral grounding is cheaper as it requires no extra
equipment but can lead to high ground-fault currents that may
System grounding, or the intentional connection of a phase or
cause damage and high step or touch voltages. On the other
neutral conductor to ground, is used for the purpose of
hand, this solution establishes a low-impedance path for
controlling the voltage to ground, within predictable limits. It
ground-fault currents and hence satisfactory operation of relay
also provides for a flow of current that will allow detection of
protection.
an unwanted connection between system conductors and
There are two types of impedance grounding:
ground (a phase-to-ground fault). The question of how the
• grounding through resistor; and
network neutral shall be grounded is determined by particular
regulations [1]. Local utility practice also influences the • grounding through arc-suppressing coil (Petersen coil),
choice of the neutral-grounding arrangement on the MV called also as resonant or compensated network.
circuits. The general purpose of grounding is to protect life Resistance grounding is broadly dividing into two
categories: high-resistance (when the fault current is limited to
Przemyslaw Balcerek (e-mail: przemyslaw.balcerek@pl.abb.com) and about 20 - 150 A) and low-resistance grounding (with fault
Marek Fulczyk (e-mail: marek.fulczyk@pl.abb.com) are with ABB Corporate current of some hundreds of amps) [2]. Generally, the high
Research Center, 31-038 Krakow, Poland.
grounding resistance decreases selectivity of the protective
Jan Izykowski (e-mail: jan.izykowski@pwr.wroc.pl), Eugeniusz
Rosolowski (e-mail: eugeniusz.rosolowski@pwr.wroc.pl) and Piotr Pierz (e- relays because the fault detection and the fault-location
mail: piotr.pierz@pwr.wroc.pl) are with Wroclaw University of Technology, estimation are less accurate. High resistance grounding is well
50-370 Wroclaw, Poland.

978-1-4673-2729-9/12/$31.00 ©2012 IEEE


2

known for its many advantages over low-impedance and faulted line [1].
solidly grounded systems. A ground fault on the high- a b c

resistance grounded system draws a small current and,


therefore, does not require immediate clearing [3]. High-
IC01
resistance grounding also minimizes fault arcing that damages
electrical apparatus and lowers personnel safety hazards ICc1 ICb1 ICa1
associated with high fault currents. From the power quality
perspective, high-resistance grounding allows for continuous N
service to loads after a ground fault.
Grounding the neutral point through the Petersen coil is
used for reducing the capacitive current in isolated networks F
IC0k
[1]. The adequate inductance in the neutral is selected for IF
compensation of the capacitive current during a phase-to- IC0km ICck ICbk ICak

ground fault; thus this method is also known as the ground- RF


fault compensation method. The equivalent scheme for this
arrangement is shown in Fig. 1.
The coil reactance is adjustable in relatively coarse steps, to Fig. 2. Equivalent scheme of the isolated network; dotted lines show path for
allow for changes in network zero-sequence capacitance the fault current
resulting from the switching out of lines. If the coil inductance
exactly matches the system capacitance, the fault current has The most frequent fault type in the electrical distribution
resistive character and may be insufficient for selective relay networks is the single phase to ground fault. It is known that
operation. Frequently, the grounding equipment is completed 50%-80% of all faults are of this type [3], [4]. Ground faults
with a resistor (resistor Rg in Fig. 1) that, with some delay, are common in the distribution networks. Determination of the
automatically paralleling the coil what permits fault current faulty feeder of ungrounded and compensated MV networks is
sufficient for correct relay operation. more challenging than the fault detection. The detection is
a b c based on the neutral voltage change, however, the faulty
feeder determination should be carried out using the feeder
currents which have small changes during the ground faults.
High impedance faults often draw small currents which
cannot be detected by conventional relays. When these faults
N
persist, it is hazardous for both human beings and electrical
equipment, especially when the faults are associated with arcs.
IN Such faults are very common in distribution networks. So,
F
many protection algorithms have been introduced to detect
IF
ICc1 ICb1 ICa1 these faults.
Rg
jXg Different solutions for determination of phase-to-ground
RF
faults are proposed by many researchers. Some of the methods
are based on modern signal processing approaches as wavelet
transformation [5]-[7], application of artificial neural
Fig. 1. Equivalent scheme of the network grounding through a Petersen coil networks [8] or even modification of the classical Fourier
algorithm [9]. It is also proposed to support the final decision
An isolated network is one in which there is no intentional of the algorithm with using the fuzzy logic technique [10] or
connection between the circuit and ground (Fig. 2). The probabilistic-based technique [11].
currents during single phase-to-ground faults are low and Recently, recorded field data have been used to enhance
depend mostly on the phase to ground capacitances of the protection relay performance [2], [10]. These data are used for
lines. practical investigation of network abnormal conditions or to
The voltage between faulted equipment and ground is test the relay reliability and its security. However, they are not
small, which improves safety. However, transient and power- suitable for modeling faults, especially high impedance faults.
frequency over-voltages can be higher than those obtained for That is due to the fact that the fault characteristics cannot be
other type of neutral grounding. Moreover, an one-phase managed using measurements at the network terminals.
grounding results in the full line-to-line voltage appearing on Furthermore, the fault scenario is not well-known and such
the other two sound phases. This situation can frequently data do not provide a dependable basis on which to base
cause failures in motors and transformers, due to insulation protection functions. Consequently, many researchers have
breakdown. There are known difficulties in detecting and performed actual fault events on real networks and have
locating the first line-to-ground fault: the over-current captured fault data from ultimately known events and
principle is not suitable here because the capacitive current in locations [3], [12]. It is worthy to introduce practical
a sound line may be even greater than that measured at the
3

protection functions using such data, especially if the fault • select the feeder with maximum of ϕ0m, m=1, ..., M.
event is recorded at both the fault branch and the measurement
For proper and reliable operation this algorithm should be
terminals. However, it imposes a high and severe risk on the
additionally adjusted. This includes the following limits:
electrical networks and there are restrictions against further
• if the magnitude of power fulfills the condition:
use of staged faults. On the other hand, experimental work is
|S0m|>S0min, otherwise ϕ0m=0;
still used to determine the characteristics of the high
impedance faults associated with arcs [12], [13]. However, • if the zero-sequence current magnitude is greater than
these investigations are insufficient for managing situations some limit: |I0m|>I0min;
where several faults simultaneously occur at a number of • the selected maximum value calculated phase should
locations in the network. be greater than some setting (threshold) value ϕ0t.
Generally, all these methods for ground-fault detection are
nonselective. The faulted phase is identified, but the fault So, the algorithm has two settings: S0min and ϕ0t, which
could be anywhere in the network [12]. Because the fault should be adequately selected.
current in high-impedance fault-loop can be similar in In the above algorithm the power components are
magnitude to the charging currents, it is difficult to distinguish calculated from zero-sequence voltage and current orthogonal
between the two. Thus, determination of a faulty feeder during components. The last are estimated by using the standard full-
the ground fault is difficult and needs further investigation. period Fourier algorithm:
The presented algorithm for selection of a faulty feeder
N −1
during phase-to-ground fault utilizes the fault signals transient 2
component, which provides very fast information about the
X R (k ) =
N
∑ x( k − i ) h
i =0
R (i)
possible disturbance in the system. N −1
(1)
2
X I (k ) =
N
∑ x(k − i)h (i)
i =0
I k = 0,1...
III. ALGORITHM DESCRIPTION
The main idea of the algorithm is based on the analysis of
the polarity between a current and a voltage changes directly where: hR (i) = cos(ν (i + 0.5)) , hI (i) = sin(ν (i + 0.5)) , ν = 2π/N,
after the fault inception. The described algorithm is designed N – number of s/c, applied for zero-sequence voltage and
for centralized substation level protection and therefore current.
utilizes the zero sequence bus-bar voltage and residual Next, having these orthogonal components the active and
currents from all outgoing feeders for detection a faulty reactive power may be calculated:
feeder. A criteria phase is calculated for each feeder as an
angle between active and reactive power determined for zero- 1
sequence component. The full-period Fourier algorithm is P0 (k ) = (V0 R (k ) I 0 R (k ) + V0 I (k ) I 0 I (k ))
2
used for adequate voltage and current phasors determination. (2)
1
Figure 3 shows the general concept of the algorithm. Q0 (k ) = (V0 I (k ) I 0 R (k ) − V0 R (k ) I 0 I (k ) )
Excepting details the algorithm can be split into the following 2
steps:
Finally, the power angle is calculated:
• calculate the zero-sequence power S0m for each feeder
m = 1, ..., M (for M feeders);
⎛ Q0 (k ) ⎞
• calculate the power angle ϕ0m for each feeder m = 1, ..., ϕ o (k ) = atan⎜⎜ ⎟⎟ (3)
M; ⎝ P0 (k ) ⎠

i01(t) i01(k)
S/H I01=I01R+jI01I
ϕ01(k)
S01=P01+jQ01 ϕ01=atan2(Q01,P01)
v0(t) v0(k)
S/H V0=V0R+jV0I
ϕ0mx result
ϕ0m>ϕ0t
...

...

Max

i08(t) i08(k) ϕ0t


S/H I08=I08R+jI08I
S08=P08+jQ08 ϕ08=atan2(Q08,P08)
v0(t) v0(k) ϕ08(k)
S/H V0=V0R+jV0I

Fig. 3. Flow-chart of the selection algorithm


4

In the above relation the angle should be determined in the capacitances, so the zero-sequence capacitive current changes
range of ±2π. from 0.5A to 40A, what is shown in Table 1. There is also
The physical structure of the considered relay is as follows: bus-bar capacitance included with the value of: C0S = 0.0153
• At each m feeder of the MV network there is installed μF. All these capacitances give zero-sequence capacitive
a box which function is to calculate a phase φm(k) at current: I0C ≈ 100 A for V0 = V1f. The neutral grounding
each time-step k. impedance equals ZN = (2+j240)Ω and corresponds for
• Signals containing calculated phases φm(k) from all M compensation factor XCs/XLN = 1.08. Faults are represented as
feeders are collected in a central box where the feeder permanent or intermittent. The last one is modeled with
with the maximum value of phase φm(k) is determined. random characteristics. The fault transients performance
Moreover, for accurate calculation of the angle (3), some depend on fault inception angle, which can be initiated by
limited (minimum) absolute value of power |P0(k) + jQ0(k)|, to changing of the fault-time inception or by changing of the
avoid inaccurate calculation, should be determined. voltage source angle.
The decision is ready if the condition: TABLE I
FEEDER CAPACITIVE PARAMETERS
ϕ0im (k ) > ϕ 0t , ϕ0im (k ) = max(ϕ 01 (k ), ϕ 02 (k ),L, ϕ0M (k ) ) (4) Parameter Zero-sequence Capacitive
capacitance/phase for one current, A
section, μF
where φ0t – setting threshold for angle value, Feeder 1, C011 .. C014 0.0153 0.5
is fulfilled for assumed ks consecutive samples for the same ith Feeder 2, C021 .. C024 0.0460 1.5
feeder. Feeder 3, C031 .. C034 0.0919 3.0
Feeder 4, C041 .. C044 0.1532 5.0
Feeder 5, C051 .. C054 0.3064 10.0
IV. SIMULATION EXAMPLES Feeder 6, C061 .. C064 0.4597 15.0
The discussed above algorithm for detection of faulty Feeder 7, C071 .. C074 0.770 25.0
Feeder 8, C081 .. C084 1.2258 40.0
feeder has been evaluated with using the fault data obtained Total values 4×3.0683=12.2732 100.0
from ATP-EMTP. Versatile simulations of faults in the
distribution (MV) system considering different fault resistance Two different cases were chosen for illustration of the
place and fault inception angle have been simulated. Step- algorithm. In both situations the phase-to-ground fault was
down transformer connects 110 kV system with 15 kV MV initiated in phase a of Feeder 1 (with minimum capacitive
network. The modeled MV distribution network consist of current) at tF = 0.04s.
eight feeders with different zero sequence capacitance. In the first example it is considered isolated network (high
Scheme of the considered network is presented in Fig. 4. impedance between nodes GR_N and GR_G in Fig. 4). The
I01 fault resistance is: RF=2500Ω. Waveforms of zero-sequence
110 kV
I
currents at faulty feeder (Feeder 1) and Feeder 8 and zero-
V sequence power angles (3) are presented in Fig. 5 and Fig. 6,
Y Y
SAT

I02
respectively.
STATION BUS

GR_N
ZN I03
I

I
GR_G

I04
I

V0
VABC
V0

V_0F
I05
I

STATION
COMPUTER

Fig. 5. Zero-sequence currents at Feeder 1 and Feeder 8


FLT_IT

SWITCH
FAULT MODEL
It can be seen from Fig. 6 that, generally, faulty and
healthy feeders have opposite signs of the calculated zero-
Fig. 4. EMTP model of the considered system sequence power angle. Influence of some passing deviations
may be removed by adequate setting of the minimum positive
All feeders are represented by four identical serial value of the angle (Fig. 6). Moreover, it was observed that
connected circuits with longitudinal impedance: these deviations do not appear at the beginning of a fault
Zl1=(1.085+j0.915)Ω. Feeders have different zero-sequence period.
5

3
faulty feeder: Feeder 1
Fig. 10 presents the calculated angle of zero-sequence
threshold power for all eight feeders. Again, one can observe clear
2 separation of decision areas determined by zero-sequence
power angles with the exception of small deviations which
1
can be handled by adequate setting of φ0t (threshold).
0 Fig. 11 presents final selection of the faulted feeder. The
algorithm properly selects the faulty line. No decision periods
-1 are observed in segments when a fault disappears.

-2

-3
0.0 0.1 0.2 0.3 0.4 time, s 0.5

Fig. 6. Waveforms of zero-sequence power angle at all feeders

V 0, V
Consequently, for the considered example, the algorithm
can make the final decision during time periods for which the
condition (4) is fulfilled (high level for Feeder 1 in Fig. 7).

Fig. 9. Bus-bar zero sequence voltage


feeder number

, rad
angle

Fig. 7. Decision periods for selecting Feeder 1 as faulty feeder

The second case provides results of the proposed algorithm


for compensated (resonant) network with compensation factor
1.08. Figs 8 - 9 present the input signals for faulty feeder in Fig. 10. Angle of zero-sequence power (faulty feeder –red)
case of phase-to-ground fault at Feeder 1, RF=2500Ω. 8

4
I0, A

0
0.0 0.1 0.2 0.3 0.4 time, s 0.5

Fig. 11. Selected Feeder number


Fig. 8. Zero-sequence current at faulty Feeder 8 (red) and Feeder 1 (green)
For proper operation of the algorithm and its stabilization,
To make the picture more legible at Fig 8 only the zero the following two settings need to be determining:
sequence currents form Feeder 1 and Feeder 8 are presented. - minimum absolute value of power (starting point) to
Fig. 9 presents the bus-bar zero sequence voltage with avoid inaccurate calculation;
characteristic waveforms. - setting threshold for angle value (4).
6

V. CONCLUSION [10] J. Lorenc, K. Musierowicz, Z. Marcinkowski, “Discrimination of


damaged line during intermittent earth faults”, in Proc. Power System
This papers provides an analysis of a transient phenomenon Protection Conference, Bled 2004, Slovenia, pp. 211 - 216.
related to a fault-to-ground faults in a typical distribution [11] N.I. Elkalashy, N.G. Tarhuni, M.F. Abdel-Fattah, M. Lehtonen,
“Evaluation of Probabilistic-Based Selectivity Technique for Earth Fault
networks with consideration of the network neutral grounding Protection in MV Networks,” in Proc. IEEE Bucharest Power Tech
method. The analysis is intended to determine a reliable Conference, June 28th - July 2nd, Bucharest, Romania.
algorithm for detection of the faulty feeder in a Medium [12] T. Baldwin, F. Renovich, “Analysis of Fault Locating Signals for High-
Voltage (MV) substation. Impedance Grounded Systems.” IEEE Transactions on Industry
Applications, vol. 38, pp. 810-817, May/June 2002.
The developed algorithm is based on the use of
[13] D. Bąk, S-J Lee, S-H Kang, M-S Choi and W. Rebizant, “New
fundamental frequency zero-sequence voltage at the Approach to Arcing High Impedance Faults Detection in Medium
substation and zero-sequence current at each substation Voltage Distribution Network,” in Proc. APAP2009, October 18~21,
2009 Jeju, Korea.
feeder. The scope is restricted to radial distribution systems.
[14] Alternative Transients Program (ATP) - Rule Book, Canadian/American
The presented algorithm is based on determination of an angle EMTP User Group, 1987-1998.
of the zero-sequence power in all outgoing feeders at the MV [15] L. Dube, I. Bonfanti, “Models: A new simulation tool in the EMTP.”
substation. The feeder with maximum value of this angle is European Trans. on Electric Power, vol. 2, no. 1, pp.45-50, Jan./Feb.
1992.
selected to be the faulty feeder. For stabilization of the
criterion two general settings were proposed.
The provided analysis in ATP-EMTP software indicate that VII. BIOGRAPHIES
the presented concept is an adequate proposition for the faulty Przemyslaw Balcerek received his M.Sc. and Ph.D
feeder in MV detection and can be applied to a real system. In degrees in Electrical Eng. from the Wroclaw University of
the attached simulation examples there was shown the general Technology in 2000, 2004 respectively. Fault location,
instrument transformers and ATP-EMTP simulation of
approach for selection of the algorithm settings. However, power system transients are in the scope of his research
further investigations are needed for proper selection of these interests. Presently he is with ABB Corporate Research
settings for different types of network. Center in Krakow/Poland, as a research scientist.

VI. REFERENCES Marek Fulczyk (M’04) received the M.Sc. and Ph.D.
degree in Electrical Eng. from the Wroclaw University of
[1] IEEE Recommended Practice for Grounding of Industrial and
Technology/Poland in 1993 and 1997, respectively. In 1997
Commercial Power Systems. IEEE Std 142-2007, Aug. 2007.
he joined ABB as a research scientist. Now he is a group
[2] S. Hänninen, 2001. Single phase earth faults in high impedance leader of Electrical & Engineering Systems at ABB
grounded networks - Characteristics, indication and location. Espoo. 78 Corporate Research in Krakow/Poland. His fields of
p. + app. 61 p. (VTT Publications No. 453), [Online]. Available: interests include power system protection, power
http://www.inf.vtt.fi/pdf/ system/voltage stability, and simulations of phenomena in
[3] S. Hänninen, M. Lehtonen, T. Hakola, E. Antila, J. Strom and S. power systems.
Ingman, “Characteristics of Earth Faults in Power Systems with a
Compensated or an Unearthed Neutral,” in Proc. CIRED. 14th Jan Izykowski (M’97, SM’04) received his M.Sc., Ph.D.
International Conference on Electricity Distribution (IEE Conf. Publ. and D.Sc. degrees in Electrical Eng. from the Faculty of
No. 438), 2-5 June 1997, pp. 16/1-16/5. Electrical Engineering of Wroclaw University of
Technology (WrUT) in 1973, 1976 and in 2001,
[4] J. Lorenc, K. Musierowicz, A. Kwapisz, “Detection of the Intermittent
respectively. In 1973 he joined Institute of Electrical
Earth Faults in Compensated MV Network, “ in Proc. 2003 IEEE
Bologna Power Tech Conference, June 23-26, Bologna, Italy, IEEE Engineering of the WrUT. Presently he is a Professor and
Catalogue No. 0-7803-7967-5/03 Director of this Institute. His research interests are in power
system simulation, power system protection and control,
[5] M. Michalik, W. Rebizant, M. Lukowicz, S-J Lee and S-H Kang, “High- and fault location.
Impedance Fault Detection in Distribution Networks With Use of
Wavelet-Based Algorithm," IEEE Trans. Power Delivery, vol. 21, pp. Eugeniusz Rosolowski (M’1997, SM’00) received his
1793-1802, Oct. 2006. M.Sc. degree in Electrical Eng. from the Wroclaw
[6] H. Belka, M. Michalik, “Application of the continuous wavelet University of Technology in 1972. From 1974 to 1977, he
transform to intermittent high impedance ground fault detection in MV studied in Kiev Politechnical Institute and received Ph.D. in
networks,” in Proc. Eighth IEE International Conference on Electrical Eng. in 1978. In 1993 he received D.Sc. in
Developments in Power System Protection, Amsterdam, 5-8 April 2004, Electrical Eng. from the WrUT. Presently he is a Professor
pp. 473-476. in the Institute of Electrical Engineering. His research
[7] N.I. Elkalashy, M. Lehtonen, H.A. Darwish, A-M Taalab I. Izzularab, interests are in power system analysis and relaying
“DWT-Based Detection and Transient Power Direction-Based Location algorithms.
of High-Impedance Faults Due to Leaning Trees in Unearthed MV
Networks.” IEEE Trans. Power Delivery, vol. 3, pp. 94-101, Jan. 2008. Piotr Pierz received his M.Sc. degrees in Electrical Eng.
[8] S. Hänninen, M. Lehtonen, 2001. ”Earth fault distance computation with and Biomedical Eng. from the Wroclaw University of
artificial neural network trained by neutral voltage transients, in Proc. of Technology (WrUT) in 1998, 2002 respectively. His area
IEEE PES SM2001. Vancouver, Canada, July 15-19. CD-ROM of interests are power system simulation, power system
01CH37262C. 6p. protection and power quality. Currently he is with WrUT
[9] M.F., Abdel-Fattah, M. Lehtonen, “Transient Fault Detection Technique where he is finishing his Ph.D.
with Varying Fault Detection Window of Earth Modes in Unearthed MV
Systems” in Proc. Power Quality and Supply Reliability Conference, PQ
2008, IEEE Catalogue No. 978-1-4244-2501-3/08, pp. 181-186.

View publication stats

Das könnte Ihnen auch gefallen