Sie sind auf Seite 1von 14

• 3 • Fundamental Theory

Introduction 3.1

Vector algebra 3.2

Manipulation of complex quantities 3.3

Circuit quantities and conventions 3.4

Impedance notation 3.5

Basic circuit laws, 3.6


theorems and network reduction

References 3.7
• 3 • Fundamental Theor y
3.1 INTRODUCTION
The Protection Engineer is concerned with limiting the
effects of disturbances in a power system. These
disturbances, if allowed to persist, may damage plant
and interrupt the supply of electric energy. They are
described as faults (short and open circuits) or power
swings, and result from natural hazards (for instance
lightning), plant failure or human error.
To facilitate rapid removal of a disturbance from a power
system, the system is divided into 'protection zones'.
Relays monitor the system quantities (current, voltage)
appearing in these zones; if a fault occurs inside a zone,
the relays operate to isolate the zone from the remainder
of the power system.
The operating characteristic of a relay depends on the
energizing quantities fed to it such as current or voltage,
or various combinations of these two quantities, and on
the manner in which the relay is designed to respond to
this information. For example, a directional relay
characteristic would be obtained by designing the relay
to compare the phase angle between voltage and current
at the relaying point. An impedance-measuring
characteristic, on the other hand, would be obtained by
designing the relay to divide voltage by current. Many
other more complex relay characteristics may be
obtained by supplying various combinations of current
and voltage to the relay. Relays may also be designed to
respond to other system quantities such as frequency,
power, etc.
In order to apply protection relays, it is usually necessary
to know the limiting values of current and voltage, and
their relative phase displacement at the relay location,
for various types of short circuit and their position in the
system. This normally requires some system analysis for
faults occurring at various points in the system.
The main components that make up a power system are
generating sources, transmission and distribution
networks, and loads. Many transmission and distribution
circuits radiate from key points in the system and these
circuits are controlled by circuit breakers. For the
purpose of analysis, the power system is treated as a
network of circuit elements contained in branches
radiating from nodes to form closed loops or meshes.
The system variables are current and voltage, and in

Network Protection & Automation Guide • 17 •


steady state analysis, they are regarded as time varying The representation of a vector quantity algebraically in
quantities at a single and constant frequency. The terms of its rectangular co-ordinates is called a 'complex
network parameters are impedance and admittance; quantity'. Therefore, x + jy is a complex quantity and is
these are assumed to be linear, bilateral (independent of the rectangular form of the vector |Z|∠θ where:
current direction) and constant for a constant frequency.
Z= (x+ y2 
2

)
y 
3 . 2 V E C TO R A L G E B R A θ = tan −1 
x 
A vector represents a quantity in both magnitude and 
x = Z cos θ
direction. In Figure 3.1 the vector OP has a magnitude 
|Z| at an angle θ with the reference axis OX. —
y = Z sin θ 
 …Equation 3.2

Figure
Y 3.1 From Equations 3.1 and 3.2:

Z = |Z| (cos θ + jsin θ) …Equation 3.3

P
and since cos θ and sin θ may be expressed in
exponential form by the identities:
|Z|
y e jθ − e − jθ
sin θ =
q 2j
X
0 x e jθ − e − jθ
cosθ =
2
Figure3.1:
Figure 3.1: Vector
VectorOP
OP —
it follows that Z may also be written as:
Fundamental Theor y


It may be resolved into two components at right angles Z = |Z|e jθ …Equation 3.4
to each other, in this case x and y. The magnitude or Therefore, a vector quantity may also be represented
scalar value of vector Z is known as the modulus |Z|, and trigonometrically and exponentially.

the angle θ is the argument, and is written as arg. Z.

The conventional method of expressing a vector Z is to
write simply |Z|∠θ. 3 . 3 M A N I P U L AT I O N
This form completely specifies a vector for graphical OF COMPLEX QUANTITIES
representation or conversion into other forms. Complex quantities may be represented in any of the
For vectors to be useful, they must be expressed four co-ordinate systems given below:

algebraically. In Figure 3.1, the vector Z is the resultant a. Polar Z∠ θ
of vectorially adding its components x and y;
• 3• algebraically this vector may be written as: b. Rectangular x + jy
c. Trigonometric |Z| (cos θ + jsin θ)

Z = x + jy …Equation 3.1
d. Exponential |Z|e jθ
where the operator j indicates that the component y is The modulus |Z| and the argument θ are together known
perpendicular to component x. In electrical as 'polar co-ordinates', and x and y are described as
nomenclature, the axis OC is the 'real' or 'in-phase' axis, 'cartesian co-ordinates'. Conversion between co-
and the vertical axis OY is called the 'imaginary' or ordinate systems is easily achieved. As the operator j
'quadrature' axis. The operator j rotates a vector anti- obeys the ordinary laws of algebra, complex quantities in
clockwise through 90°. If a vector is made to rotate anti- rectangular form can be manipulated algebraically, as
clockwise through 180°, then the operator j has can be seen by the following:
performed its function twice, and since the vector has — —
Z1 + Z2 = (x1+x2) + j(y1+y2) …Equation 3.5
reversed its sense, then: — —
Z1 - Z2 = (x1-x2) + j(y1-y2) …Equation 3.6
j x j or j2 = -1
(see Figure 3.2)
whence j = √-1

• 18 • Network Protection & Automation Guide


Z1Z2 = Z1 Z2 ∠θ1 + θ2  3.3.2 Complex Numbers
 A complex number may be defined as a constant that
Z1 Z1 
= ∠θ1 − θ2  represents the real and imaginary components of a
Z2 Z2  …Equation 3.7 physical quantity. The impedance parameter of an
electric circuit is a complex number having real and
imaginary components, which are described as resistance
Y and reactance respectively.
Confusion often arises between vectors and complex
numbers. A vector, as previously defined, may be a
complex number. In this context, it is simply a physical
|Z2| quantity of constant magnitude acting in a constant
y2
direction. A complex number, which, being a physical
quantity relating stimulus and response in a given
|Z1|
operation, is known as a 'complex operator'. In this
y1 context, it is distinguished from a vector by the fact that
X it has no direction of its own.
0 x1 x2
Because complex numbers assume a passive role in any
Figure 3.2: Addition of vectors calculation, the form taken by the variables in the
Figure 3.2: Addition of vectors problem determines the method of representing them.

3.3.1 Complex variables 3.3.3 Mathematical Operators


Some complex quantities are variable with, for example, Mathematical operators are complex numbers that are
time; when manipulating such variables in differential used to move a vector through a given angle without
equations it is expedient to write the complex quantity changing the magnitude or character of the vector. An

Fundamental Theor y
in exponential form. operator is not a physical quantity; it is dimensionless.
When dealing with such functions it is important to The symbol j, which has been compounded with
appreciate that the quantity contains real and imaginary quadrature components of complex quantities, is an
components. If it is required to investigate only one operator that rotates a quantity anti-clockwise through
component of the complex variable, separation into 90°. Another useful operator is one which moves a
components must be carried out after the mathematical vector anti-clockwise through 120°, commonly
operation has taken place. represented by the symbol a.
Example: Determine the rate of change of the real Operators are distinguished by one further feature; they
component of a vector |Z|∠wt with time. are the roots of unity. Using De Moivre's theorem, the
|Z|∠wt = |Z| (coswt + jsinwt) nth root of unity is given by solving the expression:

= |Z|e jwt 11/n = (cos2πm + jsin2πm)1/n


where m is any integer. Hence: • 3•
The real component of the vector is |Z|coswt.
Differentiating |Z|e jwt with respect to time: 2 πm 2 πm
11/ n = cos + j sin
n n
d
Z e jwt = jw Z e jwt where m has values 1, 2, 3, ... (n-1)
dt
= jw|Z| (coswt + jsinwt) From the above expression j is found to be the 4th root
and a the 3rd root of unity, as they have four and three
Separating into real and imaginary components: distinct values respectively. Table 3.1 gives some useful
functions of the a operator.
d
dt
( )
Z e jwt = Z ( − w sin wt + jw cos wt )

Thus, the rate of change of the real component of a


vector |Z|∠wt is:
-|Z| w sinwt

Network Protection & Automation Guide • 19 •


For example, the instantaneous value, e, of a voltage
2π varying sinusoidally with time is:
1 3 j
a=− + j =e 3
2 2 e=Emsin(wt+δ) …Equation 3.8

1 3 j
a2 = − − j =e 3 where:
2 2
1=1+ j0 = e j0 Em is the maximum amplitude of the waveform;
ω=2πf, the angular velocity,
1+ a + a2 = 0 δ is the argument defining the amplitude of the
voltage at a time t=0
1−a = j 3a2
At t=0, the actual value of the voltage is Emsin δ. So if
1−a2 = − j 3a Em is regarded as the modulus of a vector, whose
argument is δ, then Emsin δ is the imaginary component
a −a2 = j 3
of the vector |Em|∠δ. Figure 3.3 illustrates this quantity
a −a2 as a vector and as a sinusoidal function of time.
j=
3
Y e
Figure 3.3
Table 3.1: Properties of the a operator
|Em|
Em

3.4 CIRCUIT QUANTITIES


t
AND CONVENTIONS X' 0 X

Circuit analysis may be described as the study of the


response of a circuit to an imposed condition, for
example a short circuit. The circuit variables are current Y' t=0
and voltage. Conventionally, current flow results from
Fundamental Theor y

the application of a driving voltage, but there is Figure 3.3: Representation of a sinusoidal function
Figure 3.3: Representation
complete duality between the variables and either may of a sinusoidal function
be regarded as the cause of the other.
When a circuit exists, there is an interchange of energy; The current resulting from applying a voltage to a circuit
a circuit may be described as being made up of 'sources' depends upon the circuit impedance. If the voltage is a
and 'sinks' for energy. The parts of a circuit are described sinusoidal function at a given frequency and the
as elements; a 'source' may be regarded as an 'active' impedance is constant the current will also vary
element and a 'sink' as a 'passive' element. Some circuit harmonically at the same frequency, so it can be shown
elements are dissipative, that is, they are continuous on the same vector diagram as the voltage vector, and is
sinks for energy, for example resistance. Other circuit given by the equation
elements may be alternately sources and sinks, for
Em
example capacitance and inductance. The elements of a i= sin (wt + δ − φ )
• 3• circuit are connected together to form a network having Z …Equation 3.9

nodes (terminals or junctions) and branches (series where:


groups of elements) that form closed loops (meshes).
In steady state a.c. circuit theory, the ability of a circuit Z = R2 + X 2 

1  
to accept a current flow resulting from a given driving

voltage is called the impedance of the circuit. Since X =  ωL − 
 ωC  
current and voltage are duals the impedance parameter

must also have a dual, called admittance. φ = tan −1 X
R  …Equation 3.10

3.4.1 Circuit Variables


From Equations 3.9 and 3.10 it can be seen that the
As current and voltage are sinusoidal functions of time,
angular displacement φ between the current and voltage
varying at a single and constant frequency, they are
vectors and the current magnitude |Im|=|Em|/|Z| is
regarded as rotating vectors and can be drawn as plan —
dependent upon the impedance Z . In complex form the
vectors (that is, vectors defined by two co-ordinates) on —
impedance may be written Z=R+jX. The 'real
a vector diagram.
component', R, is the circuit resistance, and the

• 20 • Network Protection & Automation Guide


'imaginary component', X, is the circuit reactance. When steady state terms Equation 3.12 may be written:
the circuit reactance is inductive (that is, wL>1/wC), the
current 'lags' the voltage by an angle φ, and when it is ∑E = ∑I Z …Equation 3.13
capacitive (that is, 1/wC>wL) it 'leads' the voltage by an
and this is known as the equated-voltage equation [3.1].
angle φ.
It is the equation most usually adopted in electrical
When drawing vector diagrams, one vector is chosen as
network calculations, since it equates the driving
the 'reference vector' and all other vectors are drawn
voltages, which are known, to the passive voltages,
relative to the reference vector in terms of magnitude
which are functions of the currents to be calculated.
and angle. The circuit impedance |Z| is a complex
operator and is distinguished from a vector only by the In describing circuits and drawing vector diagrams, for
fact that it has no direction of its own. A further formal analysis or calculations, it is necessary to adopt a
convention is that sinusoidally varying quantities are notation which defines the positive direction of assumed
described by their 'effective' or 'root mean square' (r.m.s.) current flow, and establishes the direction in which
values; these are usually written using the relevant positive voltage drops and voltage rises act. Two
symbol without a suffix. methods are available; one, the double suffix method, is
used for symbolic analysis, the other, the single suffix or
Thus:
diagrammatic method, is used for numerical
calculations.
I = Im 2 
 In the double suffix method the positive direction of
E = Em 2  …Equation 3.11 current flow is assumed to be from node a to node b and
The 'root mean square' value is that value which has the the current is designated Iab . With the diagrammatic
same heating effect as a direct current quantity of that method, an arrow indicates the direction of current flow.
value in the same circuit, and this definition applies to The voltage rises are positive when acting in the
non-sinusoidal as well as sinusoidal quantities. direction of current flow. It can be seen from Figure 3.4
— — —
that E1 and Ean are positive voltage rises and E2 and

Fundamental Theor y
Ebn are negative voltage rises. In the diagrammatic
3.4.2 Sign Conventions method their direction of action is simply indicated by an
— —
In describing the electrical state of a circuit, it is often arrow, whereas in the double suffix method, Ean and Ebn
necessary to refer to the 'potential difference' existing indicate that there is a potential rise in directions na and nb.
between two points in the circuit. Since wherever such Figure 3.4 Methods or representing a circuit
a potential difference exists, current will flow and energy
will either be transferred or absorbed, it is obviously
necessary to define a potential difference in more exact Z3
terms. For this reason, the terms voltage rise and voltage I
drop are used to define more accurately the nature of the Z1 Z2
potential difference.
E1 E2
Voltage rise is a rise in potential measured in the
direction of current flow between two points in a circuit. • 3•
Voltage drop is the converse. A circuit element with a
E1-E2=(Z1+Z2+Z3)I
voltage rise across it acts as a source of energy. A circuit
(a) Diagrammatic
element with a voltage drop across it acts as a sink of
energy. Voltage sources are usually active circuit a
Zab
b
elements, while sinks are usually passive circuit Iab
elements. The positive direction of energy flow is from Zan Zbn
sources to sinks.
Ean Ebn
Kirchhoff's first law states that the sum of the driving
voltages must equal the sum of the passive voltages in a
closed loop. This is illustrated by the fundamental n
equation of an electric circuit: Ean-Ebn=(Zan+Zab+Zbn)Iab
(b) Double suffix
Ldi 1
dt C ∫
iR + + idt = e …Equation 3.12
Figure 3.4 Methods of representing a circuit
Figure 3.4: Circuit representation methods
where the terms on the left hand side of the equation are
voltage drops across the circuit elements. Expressed in

Network Protection & Automation Guide • 21 •


Voltage drops are also positive when acting in the component of current, and is known as 'reactive power'.
direction of current flow. From Figure 3.4(a) it can be
— — — — As P and Q are constants which specify the power
seen that ( Z1+ Z2+ Z3) I is the total voltage drop in the
exchange in a given circuit, and are products of the
loop in the direction of current flow, and must equate to —
— — current and voltage vectors, then if S is the vector
the total voltage rise E1- E2. In Figure 3.4(b), the voltage —— —
— product E I it follows that with E as the reference vector
drop between nodes a and b designated Vab indicates — —
and φ as the angle between E and I :
that point b is at a lower potential than a, and is positive —
— S = P + jQ
when current flows from a to b. Conversely Vba is a …Equation 3.16
negative voltage drop. —
The quantity S is described as the 'apparent power', and
Symbolically: is the term used in establishing the rating of a circuit.

— — — S has units of VA.
VV Vanan-−VVbnbn 
abab==V
— — — 
VV = =V
V −
bnbn V
- V anan 
baba  …Equation 3.14
3.4.4 Single-Phase and Polyphase Systems
where n is a common reference point. A system is single or polyphase depending upon whether
the sources feeding it are single or polyphase. A source
3.4.3 Power is single or polyphase according to whether there are one
or several driving voltages associated with it. For
The product of the potential difference across and the example, a three-phase source is a source containing
current through a branch of a circuit is a measure of the three alternating driving voltages that are assumed to
rate at which energy is exchanged between that branch reach a maximum in phase order, A, B, C. Each phase
and the remainder of the circuit. If the potential driving voltage is associated with a phase branch of the
difference is a positive voltage drop, the branch is system network as shown in Figure 3.5(a).
passive and absorbs energy. Conversely, if the potential
difference is a positive voltage rise, the branch is active If a polyphase system has balanced voltages, that is,
and supplies energy. equal in magnitude and reaching a maximum at equally
Fundamental Theor y

displaced time intervals, and the phase branch


The rate at which energy is exchanged is known as impedances are identical, it is called a 'balanced' system.
power, and by convention, the power is positive when It will become 'unbalanced' if any of the above
energy is being absorbed and negative when being conditions are not satisfied. Calculations using a
supplied. With a.c. circuits the power alternates, so, to balanced polyphase system are simplified, as it is only
obtain a rate at which energy is supplied or absorbed, it necessary to solve for a single phase, the solution for the
is necessary to take the average power over one whole remaining phases being obtained by symmetry.
cycle.
If e=Emsin(wt+δ) and i=Imsin(wt+δ-φ), then the power The power system is normally operated as a three-phase,
equation is: balanced, system. For this reason the phase voltages are
equal in magnitude and can be represented by three
p=ei=P[1-cos2(wt+δ)]+Qsin2(wt+δ) vectors spaced 120° or 2π/3 radians apart, as shown in
…Equation 3.15 Figure 3.5(b).
where:
• 3• P=|E||I|cos φ and
A A'
Q=|E||I|sin φ Ean
Phase branches
Ecn N Ebn N'
From Equation 3.15 it can be seen that the quantity P C B C' B'
varies from 0 to 2P and quantity Q varies from -Q to +Q
in one cycle, and that the waveform is of twice the (a) Three-phase system
periodic frequency of the current voltage waveform. Ea
The average value of the power exchanged in one cycle Direction
is a constant, equal to quantity P, and as this quantity is 120° 120° of rotation
the product of the voltage and the component of current
which is 'in phase' with the voltage it is known as the
Ec=aEa 120° Eb=a2Ea
'real' or 'active' power.
(b) Balanced system of vectors
The average value of quantity Q is zero when taken over
a cycle, suggesting that energy is stored in one half-cycle
Figure 3.5: Three-phase systems
and returned to the circuit in the remaining half-cycle. Figure 3.5: Three-phase systems
Q is the product of voltage and the quadrature

• 22 • Network Protection & Automation Guide


Since the voltages are symmetrical, they may be system impedances may be converted to those base
expressed in terms of one, that is: quantities by using the equations given below:
— = —a 
EEaa= E Ea  Zb 2 = Zb1 ×
MVAb 2 
— = a 22 —  MVAb1 
EEbb= a EEaa 
— —  2
Eaa 
EEc c== aE  kVb1  

…Equation 3.17
Zb 2 = Zb1 ×  
 kVb 2   …Equation 3.20
where a is the vector operator e j2π/3. Further, if the phase
where suffix b1 denotes the value to the original base
branch impedances are identical in a balanced system, it
follows that the resulting currents are also balanced. and b2 denotes the value to new base
The choice of impedance notation depends upon the
complexity of the system, plant impedance notation and
3.5 IMPEDANCE NOTATION
the nature of the system calculations envisaged.
It can be seen by inspection of any power system
If the system is relatively simple and contains mainly
diagram that:
transmission line data, given in ohms, then the ohmic
a. several voltage levels exist in a system method can be adopted with advantage. However, the
b. it is common practice to refer to plant MVA in per unit method of impedance notation is the most
terms of per unit or percentage values common for general system studies since:

c. transmission line and cable constants are given in 1. impedances are the same referred to either side of
ohms/km a transformer if the ratio of base voltages on the
two sides of a transformer is equal to the
Before any system calculations can take place, the transformer turns ratio
system parameters must be referred to 'base quantities'
and represented as a unified system of impedances in 2. confusion caused by the introduction of powers of
either ohmic, percentage, or per unit values. 100 in percentage calculations is avoided

Fundamental Theor y
The base quantities are power and voltage. Normally, 3. by a suitable choice of bases, the magnitudes of
they are given in terms of the three-phase power in MVA the data and results are kept within a predictable
and the line voltage in kV. The base impedance resulting range, and hence errors in data and computations
from the above base quantities is: are easier to spot
Most power system studies are carried out using
Zb =
(kV )
2

ohms …Equation 3.18


software in per unit quantities. Irrespective of the
MVA method of calculation, the choice of base voltage, and
and, provided the system is balanced, the base unifying system impedances to this base, should be
impedance may be calculated using either single-phase approached with caution, as shown in the following
or three-phase quantities. example.
The per unit or percentage value of any impedance in the
system is the ratio of actual to base impedance values. • 3•
11.8kV 11.8/141kV 132/11kV
Hence:
132kV 11kV
MVAb 
Z ( p.u .) = Z (ohms ) × Overhead line Distribution

(kVb )2  Wrong selection of base voltage



Z (% ) = Z ( p.u .) ×100  …Equation 3.19 11.8kV 132kV 11kV

Right selection
where MVAb = base MVA 11.8kV 141kV 141 x 11=11.7kV
132
kVb = base kV
Simple transposition of the above formulae will refer the Figure 3.6: Selection of base voltages
ohmic value of impedance to the per unit or percentage
values and base quantities. Figure 3.6: Selection of base voltages
Having chosen base quantities of suitable magnitude all

Network Protection & Automation Guide • 23 •


From Figure 3.6 it can be seen that the base voltages in 3 . 6 B A S I C C I R C U I T L AW S ,
the three circuits are related by the turns ratios of the THEOREMS AND NETWORK REDUCTION
intervening transformers. Care is required as the
Most practical power system problems are solved by
nominal transformation ratios of the transformers
using steady state analytical methods. The assumptions
quoted may be different from the turns ratios- e.g. a
made are that the circuit parameters are linear and
110/33kV (nominal) transformer may have a turns ratio
bilateral and constant for constant frequency circuit
of 110/34.5kV. Therefore, the rule for hand calculations
variables. In some problems, described as initial value
is: 'to refer an impedance in ohms from one circuit to
problems, it is necessary to study the behaviour of a
another multiply the given impedance by the square of
circuit in the transient state. Such problems can be
the turns ratio (open circuit voltage ratio) of the
solved using operational methods. Again, in other
intervening transformer'.
problems, which fortunately are few in number, the
Where power system simulation software is used, the assumption of linear, bilateral circuit parameters is no
software normally has calculation routines built in to longer valid. These problems are solved using advanced
adjust transformer parameters to take account of mathematical techniques that are beyond the scope of
differences between the nominal primary and secondary this book.
voltages and turns ratios. In this case, the choice of base
voltages may be more conveniently made as the nominal
voltages of each section of the power system. This 3.6.1 Circuit Laws
approach avoids confusion when per unit or percent In linear, bilateral circuits, three basic network laws
values are used in calculations in translating the final apply, regardless of the state of the circuit, at any
results into volts, amps, etc. particular instant of time. These laws are the branch,
For example, in Figure 3.7, generators G1 and G2 have a junction and mesh laws, due to Ohm and Kirchhoff, and
sub-transient reactance of 26% on 66.6MVA rating at are stated below, using steady state a.c. nomenclature.
11kV, and transformers T1 and T2 a voltage ratio of 3.6.1.1 Branch law
11/145kV and an impedance of 12.5% on 75MVA. — —
Choosing 100MVA as base MVA and 132kV as base The current I in a given branch of impedance Z is
Fundamental Theor y


voltage, find the percentage impedances to new base proportional to the potential difference V appearing
— ——
quantities. across the branch, that is, V = I Z .

a. Generator reactances to new bases are: 3.6.1.2 Junction law


The algebraic sum of all currents entering any junction
26 ×
100
×
(11) =0.27% 2
(or node) in a network is zero, that is:
66.6 (132 )2
∑ I =0
b. Transformer reactances to new bases are:
3.6.1.3 Mesh law
100 (145 )
2

12.5 × × = 20.1% The algebraic sum of all the driving voltages in any
75 (132 )2 closed path (or mesh) in a network is equal to the
algebraic sum of all the passive voltages (products of the
• 3• NOTE: The base voltages of the generator and circuits
impedances and the currents) in the components
are 11kV and 145kV respectively, that is, the turns
ratio of the transformer. The corresponding per unit branches, that is:
values can be found by dividing by 100, and the ohmic
value can be found by using Equation 3.19. ∑ E = ∑Z I
Alternatively, the total change in potential around a
Figure 3.7 closed loop is zero.
T1
G1
132kV 3.6.2 Circuit Theorems
overhead
lines From the above network laws, many theorems have been
G2
derived for the rationalisation of networks, either to
T2 reach a quick, simple, solution to a problem or to
represent a complicated circuit by an equivalent. These
theorems are divided into two classes: those concerned
Figure 3.7: Section of a power system with the general properties of networks and those

Figure 3.7: Section of a power system


• 24 • Network Protection & Automation Guide
concerned with network reduction. 3.6.3 Network Reduction
Of the many theorems that exist, the three most The aim of network reduction is to reduce a system to a
important are given. These are: the Superposition simple equivalent while retaining the identity of that
Theorem, Thévenin's Theorem and Kennelly's Star/Delta part of the system to be studied.
Theorem.
For example, consider the system shown in Figure 3.9.
3.6.2.1 Superposition Theorem The network has two sources E ’ and E ’’, a line AOB
(general network theorem) shunted by an impedance, which may be regarded as the
reduction of a further network connected between A and
The resultant current that flows in any branch of a
B, and a load connected between O and N. The object of
network due to the simultaneous action of several
the reduction is to study the effect of opening a breaker
driving voltages is equal to the algebraic sum of the
at A or B during normal system operations, or of a fault
component currents due to each driving voltage acting
alone with the remainder short-circuited. at A or B. Thus the identity of nodes A and B must be
retained together with the sources, but the branch ON
3.6.2.2 Thévenin's Theorem can be eliminated, simplifying the study. Proceeding, A,
(active network reduction theorem) B, N, forms a star branch and can therefore be converted
Any active network that may be viewed from two to an equivalent delta.
terminals can be replaced by a single driving voltage
acting in series with a single impedance. The driving
voltage is the open-circuit voltage between the two Figure 3.9
2.55Ω
terminals and the impedance is the impedance of the
1.6Ω 0.4Ω
network viewed from the terminals with all sources A B
short-circuited. 0
0.75Ω 0.45Ω
3.6.2.3 Kennelly's Star/Delta Theorem
E' E''
(passive network reduction theorem) 18.85Ω

Fundamental Theor y
Any three-terminal network can be replaced by a delta or
star impedance equivalent without disturbing the N
external network. The formulae relating the replacement
of a delta network by the equivalent star network is as Figure 3.9: Typical power system network
Figure 3.9: Typical power system network
follows (Figure 3.8):
— — — — — —
Zco = Z13 Z23 / (Z12 + Z13 + Z23)
Z AO Z NO
and so on. Z AN = Z AO + Z NO +
Z BO
Zao O Zbo Z12 0.75 ×18.85
a b 1 2 = 0.75 +18.85 +
0.45
Zco Z13 Z23 = 51 ohms

c
3
• 3•
Z BO Z NO
(a) Star network (b) Delta network Z BN = Z BO + Z NO +
Z AO
Figure 3.8:Star-Delta
Figure 3.8: Star/Delta network
network reduction
transformation
0.45 ×18.85
Figure 3.8: Star-Delta network transformation
= 0.45 +18.85 +
The impedance of a delta network corresponding to and 0.75
replacing any star network is: =30.6 ohms
— —
— — — Zao Zbo
Z12 = Zao + Zbo + ————————

Zco Z AO Z BO
Z AN = Z AO + Z BO +
and so on. Z NO
= 1.2 ohms (since ZNO>>> ZAOZBO)

Figure 3.10

Network Protection & Automation Guide • 25 •


Most reduction problems follow the same pattern as the
2.5Ω example above. The rules to apply in practical network
1.6Ω 1.2Ω 0.4Ω reduction are:
A B a. decide on the nature of the disturbance or
disturbances to be studied
E' 51Ω 30.6Ω E''
b. decide on the information required, for example
the branch currents in the network for a fault at a
N particular location
Figure 3.10: Reduction using c. reduce all passive sections of the network not
star/delta transform directly involved with the section under
The network is now reduced as shown in Figure 3.10. examination
By applying Thévenin's theorem to the active loops, these d. reduce all active meshes to a simple equivalent,
can be replaced by a single driving voltage in series with that is, to a simple source in series with a single
an impedance as shown in Figure 3.11. impedance
With the widespread availability of computer-based
1.6 x 51 power system simulation software, it is now usual to use
Figure 3.111.6Ω Ω
52.6 such software on a routine basis for network calculations
A A without significant network reduction taking place.
However, the network reduction techniques given above
51
E' 51Ω E' are still valid, as there will be occasions where such
52.6
software is not immediately available and a hand
calculation must be carried out.
N N
(a) Reduction of left active mesh In certain circuits, for example parallel lines on the same
towers, there is mutual coupling between branches.
Fundamental Theor y

0.4 x 30.6
Ω Correct circuit reduction must take account of this
0.4Ω 31
B B coupling.

30.6Ω E'' 30.6 E''


31 Figure 3.13 Ia Zaa

I
N N P Zab Q
(b) Reduction of right active mesh Ib
Zbb
Figure
Figure 3.11:3.11: Reduction
Reduction of active
of active meshes: Thévenin's Theorem
meshes:
(a) Actual circuit
Thévenin's Theorem

The network shown in Figure 3.9 is now reduced to that I


P Q
• 3• shown in Figure 3.12 with the nodes A and B retaining Z Z -Z2
their identity. Further, the load impedance has been Z= aa bb ab
Zaa+Zbb-2Zab
completely eliminated. (b) Equivalent when Zaa≠Zbb
The network shown in Figure 3.12 may now be used to
I
study system disturbances, for example power swings P Q
with and without faults. Z= 1 (Zaa+Zbb)
2
(c) Equivalent when Zaa=Zbb
2.5Ω
Figure 3.12
1.55Ω 0.39Ω Figure 3.13: Reduction of two branches
A B Figure 3.13: Reduction of two branches with mutual
withcoupling
mutual coupling
1.2Ω

0.97E' 0.99E''
Three cases are of interest. These are:
a. two branches connected together at their nodes
b. two branches connected together at one node only
N
c. two branches that remain unconnected
Figure 3.12:3.12:
Figure Reduction of typical
Reduction of typical power system network
power system network

• 26 • Network Protection & Automation Guide


Considering each case in turn: The assumption is made that an equivalent star
network can replace the network shown. From
a. consider the circuit shown in Figure 3.13(a). The
inspection with one terminal isolated in turn and a
application of a voltage V between the terminals P
voltage V impressed across the remaining terminals
and Q gives:
it can be seen that:
V = IaZaa + IbZab
Za+Zc=Zaa
V = IaZab + IbZbb
Zb+Zc=Zbb
where Ia and Ib are the currents in branches a and
Za+Zb=Zaa+Zbb-2Zab
b, respectively and I = Ia + Ib , the total current
entering at terminal P and leaving at terminal Q. Solving these equations gives:
Solving for Ia and Ib :
Za = Zaa − Zab 

Ia =
(Zbb − Zab )V Zb = Zbb − Zab 
Zaa Zbb − Zab
2 
Zc = Zab  …Equation 3.23
from which
-see Figure 3.14(b).
Ib =
(Zaa − Zab )V
Zaa Zbb − Zab
2
c. consider the four-terminal network given in Figure
and 3.15(a), in which the branches 11' and 22' are
electrically separate except for a mutual link. The
V (Zaa + Zbb −2 Zab ) equations defining the network are:
I = Ia +Ib =
Zaa Zbb − Zab
2
V1=Z11I1+Z12I2
so that the equivalent impedance of the original
circuit is: V2=Z21I1+Z22I2

Fundamental Theor y
I1=Y11V1+Y12V2
V Zaa Zbb − Zab2
Z= = I2=Y21V1+Y22V2
I Zaa + Zbb − 2 Zab …Equation 3.21
where Z12=Z21 and Y12=Y21 , if the network is
(Figure 3.13(b)), and, if the branch impedances are
assumed to be reciprocal. Further, by solving the
equal, the usual case, then:
above equations it can be shown that:
1
Z=
2
(Zaa + Zab ) …Equation 3.22 Y11 = Z22 ∆ 

(Figure 3.13(c)). Y22 = Z11 ∆ 

Y12 = Z12 ∆ 
b. consider the circuit in Figure 3.14(a). 
∆ = Z11Z22 − Z122  …Equation 3.24

Zaa There are three independent coefficients, namely • 3•


A Z12, Z11, Z22, so the original circuit may be
replaced by an equivalent mesh containing four
Zab C
external terminals, each terminal being connected
to the other three by branch impedances as shown
B
Zbb in Figure 3.15(b).
(a) Actual circuit

Za=Zaa-Zab Z11
Z11
A 1 1' 1 1'

Z12 Z12 Z12 Z21 Z12


C
Zc=Zab
2 2' 2 2'
B Z22 Z22
Zb=Zbb-Zab (a) Actual circuit (b) Equivalent circuit

(b) Equivalent circuit Z11


1 Figure 3.15
1 : Equivalent circuits for 1'
Figure 3.14: Reduction of mutually-coupled branches Z12 mutual coupling
four terminal network with
with a common terminal Z11 Z12 Z12 -Z12 -Z12
Figure 3.14: Reduction of mutually-coupled branches with a common terminal Z12
C 2 2'
Network Protection & Automation Guide • 27 • Z12
(c) Equivalent with all (d) Equivalent circuit
nodes commoned
In order to evaluate the branches of the equivalent defining the equivalent mesh in Figure 3.15(b), and
mesh let all points of entry of the actual circuit be inserting radial branches having impedances equal
commoned except node 1 of circuit 1, as shown in to Z11 and Z22 in terminals 1 and 2, results in
Figure 3.15(c). Then all impressed voltages except Figure 3.15(d).
V1 will be zero and:
I1 = Y11V1
3.7 REFERENCES
I2 = Y12V1
3.1 Power System Analysis. J. R. Mortlock and
If the same conditions are applied to the equivalent M. W. Humphrey Davies. Chapman & Hall.
mesh, then:
3.2 Equivalent Circuits I. Frank M. Starr, Proc. A.I.E.E.
I1 = V1Z11 Vol. 51. 1932, pp. 287-298.
I2 = -V1/Z12 = -V1/Z12
These relations follow from the fact that the branch
connecting nodes 1 and 1' carries current I1 and
the branches connecting nodes 1 and 2' and 1 and
2 carry current I2. This must be true since branches
between pairs of commoned nodes can carry no
current.
By considering each node in turn with the
remainder commoned, the following relationships
are found:
Z11’ = 1/Y11
Z22’ = 1/Y22
Fundamental Theor y

Z12’ = -1/Y12
Z12 = Z1’ 2’ = -Z21’ = -Z12’

Hence:
Z Z −Z 2 
Z ' = 11 22 2 12 
= Z11
Z11’ 11 Z22Z-Z 22 12
_______________ 
Z22 2 
Z11Z22 − Z12 
=' Z=11
Z22’Z22 Z22-Z212 
_______________
Z 
Z1111
=Z ZZ11 Z 22 −2Z 
2
Z12Z12 = 11 22-Z 1212 
_______________
ZZ1212
 …Equation 3.25
A similar but equally rigorous equivalent circuit is
• 3• shown in Figure 3.15(d). This circuit [3.2] follows
from the fact that the self-impedance Z11
of any circuit
Z11
1 is independent
1' of all other circuits. Therefore,
1 1' it
need not appear in any of the mutual branches if it
Z12 Z12 Z12 Z21 Z12
is lumped as a radial branch at the terminals. So
2 putting Z11 and
2' Z22 equal2 to zero in Equation 2'3.25,
Z22 Z22
(a) Actual circuit (b) Equivalent circuit
Z11
1 1 1'
Z12
Z11 Z12 Z12 -Z12 -Z12
Z12
C 2 2'
Z12
(c) Equivalent with all (d) Equivalent circuit
nodes commoned
except 1

Figure 3.15: Equivalent circuits for


four terminal network with mutual coupling
Figure 3.15: Equivalent circuits for four terminal network with mutual coupling

• 28 • Network Protection & Automation Guide

Das könnte Ihnen auch gefallen