CALCULATE THE SIZE OF BATTERY BANK & INVERTOR

Electrical Load Details


Sr.No Equiment Name No Watt Using Hr/Day Watt Hr./Day
1 1 100 1 100.0 ###
AC 1 1500 5 7500.0 ###
AC-2 1 1750 7 12250.0 ###
LIGHT 6 100 8 4800.0 ###
FAN 3 40 8 960.0 ###
PERSONAL COMPUTER 6 250 8 12000.0 ###
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0
0.0 0

Total Load 37610.0 ###Watt.Hr/Day


ERY BANK & INVERTOR
Jignesh.Parmar www.electricalnotes.wordpress.com
Battery Bank's Voltage 12 Volts DC

Reaserve Day: (How many days Do you want


2.5 Days
to get Power from battery Banks)
Loose Connection/Wire Loss Factor: 20 % 0.2
Battery Efficiency 100 % 1
Battery Aging: 20 % 0.2
Depth of Discharge:(DOD) 50 % 0.5
Battery Operating Temp: 46 C°
The Battery Bank Required: 22566.0 Amp.Hr
###
If You are Selecting Battery 150 Amp.Hr @ 12 volts ###
Batteries connection for Battery Bank Parral

:Battery Bank Detail :


Type of Connection For Batteries Parral Connection
Selection of Batteries Connection: O.K
Selection of Each Battery Voltage O.K
Number of String for Battry Bank 150 Nos
Total Amp.Hr of Each String 150 Amp.Hr
Total No of Battery in Each String 1 Nos

Total Battery Bank Amp.Hr 22500 Amp.Hr


Total Nos of Batteries in Battery Bank 150 Nos

:Size of Invertor:
Calculate Additional Future Load 20 %
Effieciency of Invertor 80 %
Size of Invertor 8355 KW

CALCULATIONS:
Total KW.Hr/Day 37610.0 Watt.Hr/Day
Total Amp.Hr 3134.2 Amp.Hr
Average Load 3761.0 Amp.Hr
Storage Required 9402.5 Amp.Hr
Battery Aging 11283.0 Amp.Hr
Including Operating Temp 11283.0 Amp.Hr
Depth of Discharge 22566.0 Amp.Hr

Watt.Hr/Day