Beruflich Dokumente
Kultur Dokumente
1, JANUARY 2010
Abstract—Current differential protection relays are widely ap- the same busbar in a substation [2]. This causes difficult situ-
plied to the protection of electrical plant due to their simplicity, ations when relay engineers coordinate reach or operate time
sensitivity and stability for internal and external faults. The pro- among distance relays. To cope with this, current differential
posed idea has the feature of unit protection relays to protect large
power transmission grids based on phasor measurement units. The protection which utilizes wide-area current data would be effec-
principle of the protection scheme depends on comparing posi- tive for wide-area backup protection although such protection
tive sequence voltage magnitudes at each bus during fault condi- needs system-wide timing synchronism for the simultaneous
tions inside a system protection center to detect the nearest bus to current sampling at all remote terminals and data exchanges
the fault. Then the absolute differences of positive sequence cur- among them.
rent angles are compared for all lines connecting to this bus to
detect the faulted line. The new technique depends on synchro- In this area, an adaptive Phasor Measurement Unit (PMU)
nized phasor measuring technology with high speed communica- based protection scheme for both transposed and un-transposed
tion system and time transfer GPS system. The simulation of the in- parallel transmission lines is given [3]. The development of the
terconnecting system is applied on 500 kV Egyptian network using scheme is based on the distributed line model and the synchro-
Matlab Simulink. The new technique can successfully distinguish nized phasor measurements at both ends of lines. By means of
between internal and external faults for interconnected lines. The
new protection scheme works as unit protection system for long eigenvalue/eigenvector theory to decouple the mutual coupling
transmission lines. The time of fault detection is estimated by 5 effects between parallel lines, the fault detection and location
msec for all fault conditions and the relay is evaluated as a back indexes are derived.
up relay based on the communication speed for data transferring. A fault detection/location technique with consideration of
Index Terms—Digital protection, discreet Fourier transform, arcing fault discrimination based on phasor measurement units
(GPS) system, synchronized phasor measurement, time synchro- for extremely high voltage/ultra-high voltage transmission lines
nization. is presented in [4]. The proposed arcing fault discriminator
can discriminate between arcing and permanent faults within
four cycles after fault inception. Some techniques presented
I. INTRODUCTION fault location algorithm based on phasor measurement units for
series compensated lines [5].
Authorized licensed use limited to: M Eissa. Downloaded on January 18, 2010 at 06:17 from IEEE Xplore. Restrictions apply.
EISSA et al.: A NOVEL BACK UP WIDE AREA PROTECTION TECHNIQUE FOR POWER TRANSMISSION GRIDS USING PHASOR MEASUREMENT UNIT 271
Fig. 1. Three zones of operation for each stand alone relay. Fig. 2. The new protected zones of the proposed relay.
Authorized licensed use limited to: M Eissa. Downloaded on January 18, 2010 at 06:17 from IEEE Xplore. Restrictions apply.
272 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010
Authorized licensed use limited to: M Eissa. Downloaded on January 18, 2010 at 06:17 from IEEE Xplore. Restrictions apply.
EISSA et al.: A NOVEL BACK UP WIDE AREA PROTECTION TECHNIQUE FOR POWER TRANSMISSION GRIDS USING PHASOR MEASUREMENT UNIT 273
Authorized licensed use limited to: M Eissa. Downloaded on January 18, 2010 at 06:17 from IEEE Xplore. Restrictions apply.
274 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010
Authorized licensed use limited to: M Eissa. Downloaded on January 18, 2010 at 06:17 from IEEE Xplore. Restrictions apply.
EISSA et al.: A NOVEL BACK UP WIDE AREA PROTECTION TECHNIQUE FOR POWER TRANSMISSION GRIDS USING PHASOR MEASUREMENT UNIT 275
Authorized licensed use limited to: M Eissa. Downloaded on January 18, 2010 at 06:17 from IEEE Xplore. Restrictions apply.
276 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010
Fig. 10. Three phase current signals for all lines connected to the faulted area
(area “2”).
Fig. 9. Three phase voltage signals at each area.
X. CASE STUDY
An extensive series of study is examined on the power system Fig. 11 shows the output from the five PMUs, the graph
given in Fig. 8. All fault events are studied and a sample of the shows the five positive sequence voltage magnitudes (PSVM)
results is given here. More details about the different cases of for five different areas during fault. The minimum value is
faults can be given in [15]. As mentioned above, the studied selected which indicates the nearest area to the fault (area “2”).
network is classified into 5 neighboring areas. The 5 areas are The next step is used to identify the faulted line. Fig. 12 shows
connected with each others by six lines. Three phases to ground the absolute diffrences of positive sequance current angles
fault are located on line 1 which connecting area “1” with area (PSCA) for all lines connecting the faulted area (area “2”) with
“2”, see Fig. 8. all other neighboring areas (areas “1”, “3”, “4”). The graph
Fault location is placed away from area “1” and area “2” by shows the maximum absolute difference of positive sequence
100 and 45 km respectively. The three phase voltage signals at currrent angle (about 175 ) that refers to line 1. The time taken
each area are recorded and displayed in Fig. 9. The three phase to reach the threshold voltage is about 4 ms. While the time
current signals for all lines connected to the faulted area are taken to reach the threshold angle is 3 ms, then the fault can
recorded and displayed in Fig. 10 as: be detected in about 4 ms. A single phase to ground fault is
• line 1 connecting area 2 with area 1; located on transmission line TL3, see Fig. 8, which connecting
• line 3 connecting area 2 with area 3; area “2” (Kurimat) with area “3” (Cairo 500). The distance
• Line 5 connecting area 2 with area 4. between fault location on the transmission line and the nearest
Authorized licensed use limited to: M Eissa. Downloaded on January 18, 2010 at 06:17 from IEEE Xplore. Restrictions apply.
EISSA et al.: A NOVEL BACK UP WIDE AREA PROTECTION TECHNIQUE FOR POWER TRANSMISSION GRIDS USING PHASOR MEASUREMENT UNIT 277
Fig. 14. Positive sequence current angles (absolute difference) for all lines con-
Fig. 12. Positive sequance current angle absolute differences for all lines con- nected to area “2”.
nected to the faulted area (area “2”).
Fig. 15. Positive sequence voltage magnitudes measured from five places on
the network.
Fig. 13. Positive sequence voltage magnitudes measured from five places on
the network.
Authorized licensed use limited to: M Eissa. Downloaded on January 18, 2010 at 06:17 from IEEE Xplore. Restrictions apply.
278 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010
170 . This means that the current is reversed from one terminal [7] S. H. Horowitz and A. G. Phake, Power System Relaying. Taunton,
only. It is clear that the fault is internal and the transmission Somerset, U.K.: Research Studies Press, 1992.
[8] M. M. Eissa, “New principle for transmission line protection using
line must be isolated. Figs. 15 and 16 show also the threshold phase portrait plane,” IET Gener. Transm. Distrib., vol. 3, no. 1, pp.
boundary with time estimated by 3 msec. 49–56, 2009.
[9] D.-Q. Wang, S.-H. Miao, X.-N. Lin, P. Liu, Y.-X. Wu, and D. Yang,
“Design of a novel wide-area backup protection system,” in Proc.
XI. CONCLUSION IEEE/PES Transm. Distrib. Conf. Exhib.: Asia Pac. Dalian, China,
2005, pp. 1–6.
The paper presents a new protection technique for transmis- [10] B. Naduvathuparambil, M. C. Valenti, and A. Feliachi, Communication
delays in wide area measurement systems Lane Dept. of Comp. Sci. &
sion grids using phasor synchronized measuring technique in a Elect. Eng., West Virginia University, Morgantown, WV, 26506-6109,
wide area system. The protection scheme has successfully iden- 2002.
tified the faulted line allover the interconnect system. The relay [11] R. Klump and R. E. Wilson, “Visualizing real-time security threats
using hybrid SCADA/PMU measurement displays,” in Proc. 38th
descried in this paper represents a new state-of-art in the field Hawaii Int. Conf. System Sci., 2005, p. 55c.
of interconnected grid protection for many reasons. [12] M. M. Eissa, “Development and investigation of a new high-speed di-
• The relay is based on sharing data from all areas. rectional relay using field data,” IEEE Trans. Power Del., vol. 23, no.
3, pp. 1302–1309, Jul. 2008.
• One relay is used instead of many stand alone relays with [13] M. M. Eissa, “A new digital feed circuit protection using directional
different complexity coordination. element,” IEEE Trans. Power Del., vol. 24, no. 2, pp. 531–537, Apr.
• The relay has the feature of unit protection in identifying 2009.
[14] M. M. Eissa, “Evaluation of a new current directional protection tech-
the faulted zone. nique using field data,” IEEE Trans. Power Del., vol. 20, no. 2, pp.
• One and only one trip decision is issued from the protection 566–572, Jul. 2005.
center. [15] , “Protection of Interconnected Electrical Networks Using Phasor Syn-
chronized Measuring Technique,” Ph.D. dissertation, Helwan Univer-
The relay has a very fast detection time estimated by 5 msec sity-Faculty of Engineering at Helwan, Cairo, Egypt.
for all fault cases. In the near future and with a very fast com-
munication links the relay can be considered as a main relay on
the interconnected grids. M. M. Eissa (M’96–SM’01) was born in Helwan, Cairo, Egypt, on May 17,
1963. He received the B.Sc. and M.Sc. degrees in electrical engineering from
Helwan University, Cairo, Egypt, in 1986 and 1992, respectively, and the Ph.D.
REFERENCES degree from the Research Institute for Measurements and Computing Tech-
niques, Hungarian Academy of Science, Budapest, Hungary, in 1997.
[1] Wide Area Protection and Emergency Control, 2002, IEEE Members, He is a Professor at Helwan University. In 1999, he was invited to be a Vis-
Working Group C-6. iting Research Fellow at the University of Calgary, Calgary, AB, Canada. His
[2] U. Serizawa, M. Myoujin, K. Kitamura, and N. Sugaya, “Wide area research interests include digital relaying, application of widearea networking
current differential backup protection employing broadband commu- to power systems, power quality and energy management, and wide-area
nication and time transfer systems,” IEEE Trans. Power Del., vol. 13, protection.
no. 4, pp. 427–433, Oct. 1998. Dr. Eissa received the Egyptian State Encouragement Prize in advanced
[3] C.-S. Chen, C.-W. Liu, and J.-A. Jiang, “A new adaptive PMU based science in 2002 and the Best Research in advanced engineering science from
protection scheme for transposed/untransposed parallel transmission Helwan University in 2005.
lines,” IEEE Trans. Power Del., vol. 17, no. 2, pp. 395–404, Apr. 2002.
[4] Y.-H. Lin, C.-W. Liu, and C.-S. Chen, “A new PMU-based fault
detection/location technique for transmission lines with consideration
of arcing fault discrimination—Part I: Theory and algorithms,” IEEE
Trans. Power Del., vol. 19, no. 4, pp. 1587–1593, Oct. 2004. M. E. Masoud, photograph and biography not available at the time of
[5] C.-S. Yu, C.-W. Liu, S.-L. Yu, and J.-A. Jiang, “A new PMU-based publication.
fault location algorithm for series compensated lines,” IEEE Trans.
Power Del., vol. 17, no. 1, pp. 33–46, Jan. 2002.
[6] J. Tang and P. G. McLaren, “A wide area differential backup protection
scheme for Shipboard application,” IEEE Trans. Power Del., vol. 21, M. M. M. Elanwar, photograph and biography not available at the time of
no. 3, Jul. 2006. publication.
Authorized licensed use limited to: M Eissa. Downloaded on January 18, 2010 at 06:17 from IEEE Xplore. Restrictions apply.