Sie sind auf Seite 1von 1

5/8” CONDENSATE DRAIN LINE

PUMPED TO EXTERIOR
WALL MOUNTED EXHAUST FAN TERMINATES AT 5-GALLON PRV TERMINATES 6”
BROAN-NUTONE #509 270 CFM GROUND LEVEL GRAVEL SUMP ABOVE GROUND
(1” EXTERIOR RECESS MAY BE REQ)
TOP EDGE @ 8’-6”

24 3/4” DIAMETER
80 GALLON
(ELECTRIC BACKUP)
DISCONNECT SUNEARTH SU80HE
WALL MOUNTED
EXHAUST FAN BROAN- 10x10 10x10

RESIDENCE for AMY GRAHAM & SCOTT DREISBACH


NUTONE #508 270 CFM TYPE “B” GAS
TOP @ 8’-6” HEIGHT FURNACE & AIR VENT TO ROOF HIGH & LOW MAKE UP AIR
(1” EXTERIOR RECESS HANDLER (2) 8”x12”VERT DUCTS OR
10x10 10x10
MAY BE REQ) 100 IN2 MIN EACH W/
SCREENED ROOF CAP
SHW
8” 8”

16560 S.MANN AVE, SAHUARITA, AZ 85629


8” 8x8

20x10 16x10
TYPE “X” SHEETROCK
IN MECHANICAL CLOSET
8” 8” 6” LINE RISERS T 8”
6” BROAN-NUTONE XB110
6” EXHAUST FAN 110 CFM W/ 6”
A DUCT TO WALLCAP
13 SHIELED RISER TO
TRUSS SPACE
CONDENSER/
COMPRESSOR
ON PAD
180 CFM 6x6 6x6
TYP. OF 4
10x10 10x10
8x8 W

D 10x10

2 REFRIGERANT LINES W/
1 CONTROL LINE
WALL CAP @
DRYER VENT
2 REFRIGERANT LINES W/
1 CONTROL LINE BROAN- NUTONE XB80
EXHAUST FAN 80 CFM W/ 4”
DUCT TO WALLCAP
N
HOUSE MECHANICAL PLAN
7 HALL FURNACE & AIR HANDLER: 1/4” = 1’-0”
TEMPSTAR MODEL # FMV1102120A VS80 SERIES “SMARTCOMFORT”
OPEN TO NANO 115V, 20 AMP DEDICATED CIRCUIT 15, 89,000 BTUH HEAT CAPACITY,
BREWERY 15 SEER, 80% AFUE, #12 WIRE FURNACE
DIMENSIONS- 21” WIDTH, 29 DEPTH, 33 1/4” HEIGHT
MASTER
BEDROOM COMPRESSOR & CONDENSOR:
T4A348GKD 4 TON RATING, 13 SEER, Drawn by AB & RG
Date 11/2/12
DIMENSIONS-31 3/16” WIDTH, 31 3/16” DEPTH, 35 1/2” HEIGHT

20”x10” Revisions
RET.AIR 1.
60” x 12”
RET.AIR 2.

A HALL WALL @ UTILITY CLOSET 3.


13 1/4” = 1’-0” LOOKING NORTH Radius Project # 10-781

MECHANICAL NOTES
1. Kitchen and bathroom ventilation shall be routed to an exterior wall or roof, and shall provide the flow rate called out on with
each exhaust fan on the Mechanical and/or Electrical Plans.
2. Air conditioning and heat are provided by the Tempstar split system.
3. Furnace & Air Handler-
Tempstar model # FMV1102120A - VS80 series “Smartcomfort”
115V, 20 AMP dedicated circuit 15, #12 wire
89,000 BTUH heat capacity, 15 SEER 80% AFUE
Furnace Dimensions- 21” Width, 29 Depth, 33 1/4” Height
4. Compressor & Condenser:
T4A348GKD 4 Ton Rating, 13 SEER,
Dimensions-31 3/16” Width, 31 3/16” Depth, 35 1/2” Height

5. Condensate drain to be installed per manufacturer’s installation specifications. HOUSE


6. An online source for this equipment is http://www.gotempstar.com/go/index.asp
7. Because of the provision of a window in each bathroom, of 3 SF or more, per 2006 IRC Section R 303.3, mechanical ventilation MECHANICAL
is optional for both bathrooms. PLAN
REQUIREMENTS from MODEL ENERGY CODE
Note: Other energy-related requirements are found in other Notes – such as the water-flow requirements for various fixtures, as found
on the Plumbing Notes that are with the Plumbing Plan.

1. AIR LEAKAGE. Joints, penetrations, and all other such openings in the building envelope that are sources of air leakage must
be caulked, gasketed, weatherstripped, or otherwise sealed. Recessed lights must be type IC rated and installed with no
penetrations or installed inside an appropriate air-tight assembly with a 0.5-in. clearance from combustible materials and 3-in.
clearance from insulation.

13
2. ENERGY INFORMATION AND MAINTENANCE. Manufacturer’s specifications and manuals for all installed heating and
cooling equipment and service water heating equipment will be
a. available onsite during construction, then
b. provided to the owners in a binder.