Beruflich Dokumente
Kultur Dokumente
Paper 0185
PCC
External Grid
Transmission
LAT 300/50 mm2- 10 Km
T 132 / 33 / 13.2 kV T 13.2 / 0.4 kV
r = 0.094 Ohm/ Km ro = 0.245 Ohm/ Km Distribution S = 1 MVA
x = 0.388 Ohm/ Km xo = 1.164 Ohm/ Km
b = 2.951 uS/ Km bo = 1.968 uS/ Km
Zcc = 5 % Load A
50 mm2 - 4.5 km
Skk 3fhi = 1500 MVA
Skk 1fhi = 1400 MVA
RN
starting from the impossibility of fulfilling their design current were considered negligible, when the fault takes
Paper 0185
Figure 2. Simple circuit model. It is observed that besides a change in the magnitude, a
phase jump appears. In the simplified method this change
I1 doesn't appears because all the resistive losses were
Z S1 ZF1
rejected. For short circuits in sub-transmission or
+ distribution systems, this simplification can give important
E V1 errors, due to the high resistance values for small cross
− section conductors. Also, the difference of impedance of the
high and low voltage conductors can introduce phase jumps
Figure 3. Sequence nets connection for three-phase faults. higher than those studied up to now. The cited errors are
The direct sequence impedance of the external equivalent acceptable, for what the simplified method can provide very
circuit can be obtained by: good results with minimum calculations. This is important
in cases where the study is done without specialized
programs. This sag was classified by Bollen as Type A [1].
Paper 0185
2- Single Phase short circuit: Type B 4- Two phase to ground short circuit: Type E
For this fault type the sequence nets are connected in series. In this case, the direct, inverse and zero sequence nets are
The three windings transformer will be studied for the connected in parallel. The results of the manual
connection group more commonly used in power systems. calculations and simulations are the following ones:
The presence of the delta winding allows the circulation of
Manual Simulation
the necessary harmonic component for the magnetic circuit,
excitation without important voltage distortions. The high ⎡V A ⎤ ⎡1 . 028 ∠ 0 º ⎤ ⎡V A ⎤ ⎡1 . 028 ∠ 0 .08 º ⎤
⎢ ⎥ ⎢ 0 . 547 ∠ − 125 . 4 º ⎥ ⎢ ⎥ ⎢ 0 . 532 ∠ − 132 . 30 º ⎥
voltage windings are connected in star to ground, which ⎢V B ⎥ = ⎢ ⎥ ⎢V B ⎥ = ⎢ ⎥
allows lower insulation level. It was decided to include in ⎢V C ⎥ ⎢⎣ 0 . 547 ∠ 125 . 4 º ⎥⎦ ⎢V C ⎥ ⎢⎣ 0 . 510 ∠ 123 . 38 º ⎥⎦
⎣ ⎦ ⎣ ⎦
the circuit the existence of neutral reactor, although it
doesn't participate in the calculations. For the analysis of the This voltage sag type has been proposed as sag Type E. In
circulation of the zero sequence components, it should be this case the not failed phase it is not affected and a
kept in mind that the delta coil allows the current decrease of the remaining two phases magnitude is verified
contribution coming from earth toward the fault, through the but the phase change can be disregarded with little
transformer primary neutral. In consequence this path calculation error, which notably simplifies the mathematical
should be included in the net of zero sequence, adding a expressions. The following table is a summary of the types
branch in parallel with the sum of the external impedance of of PCC voltage sags, according to the faults that originated
the equivalent one and the line L1. The impedance between them.
primary and third is taken in the common base of 100 Table 1. PCC voltage sags types
MVA. In general equals impedances of direct and inverse
sequence are adopted. This is acceptable in the case of Type of fault Star with neutral
faults electrically far from rotating machines. The results of Three phase A
the manual calculations and the simulations are:
Single phase B
Manual Simulation
Two phase C
⎡V A ⎤ ⎡ 0 . 572 ∠ 0 º ⎤ ⎡V A ⎤ ⎡ 0 . 579 ∠ − 3 .74 º ⎤
⎢ ⎥ ⎢1 . 018 ∠ − 121 . 7 º ⎥ ⎢ ⎥ ⎢1 . 019 ∠ − 121 .69 º ⎥ Grounded two phase E
⎢V B ⎥ = ⎢ ⎥ ⎢V B ⎥ = ⎢ ⎥
⎢V C ⎥ ⎢⎣1 . 018 ∠ 121 . 7 º ⎥⎦ ⎢V C ⎥ ⎢⎣1 . 017 ∠ 121 .78 º ⎥⎦
⎣ ⎦ ⎣ ⎦ TRANSFER AMONG DIFFERENT VOLTAGE
This event type has been defined as voltage sag Type B. In LEVELS
fact in the classification proposed by Bollen the presence of To connect the transmission net with the rest of the system,
the voltage sag only affects the failed phase, rejecting for the existence of a 132/33/13.2 kV transformer station has
the healthy phases so much the voltage elevation like the been supposed in the bar 132 B that provides the electric
phase change (although small) that is evidenced in the energy to the subtransmission and distribution nets. These
calculated values and also in the results of the simulation nets extend the feeding to the low voltage systems where it
that are given next. is supposed that the sensitive equipment is connected. The
transformers can have diverse connection forms, but in
3- Two phase short circuit: Type C order to explain the voltage sags transfers is enough to
classify them in three types.
To maintain the phase A as symmetry reference, it is
supposed that the fault takes place in the phases B and C. Type I: Transformers that don't change the voltages
For this fault type the direct and inverse sequence nets are between primary and secondary. For this type the voltages
connected in parallel, while the zero sequence net is opened in pu in both sides are the same, this means that the
by not being included the contact to ground. The results of transformer type I doesn't produce any change in the voltage
the manual calculations and simulations, applying the same sag type when transferring the voltages between levels. The
methodology of the previous examples, are: transformation matrix is the identity. Example YNyn
Manual Type II: Transformers that remove the zero sequence. The
Simulation
voltages of both sides are the same except for the
⎡V A ⎤ ⎡1 ∠ 0 º ⎤ ⎡V A ⎤ ⎡1 ∠ 0 . 006 º ⎤
⎢ ⎥ ⎢ 0 . 643 ∠ − 141 º ⎥ ⎢ ⎥
component of zero sequence. Example Yy Dd
⎢ 0 . 677 ∠ − 142 . 74 º ⎥
⎢V B ⎥ = ⎢ ⎥ ⎢V B ⎥ = ⎢ ⎥
⎢V C ⎥ ⎢V C ⎥ Type III: Transformers that eliminate the zero sequence
⎣ ⎦ ⎣⎢ 0 . 643 ∠ 141 º ⎦⎥ ⎣ ⎦ ⎣⎢ 0 . 617 ∠ 138 . 4 º ⎦⎥ and that exchange line by phase voltages. For these
This event type has been classified by Bollen as voltage transformers each secondary voltage is the difference
sag Type C. It can be observed that the not failed phase between two primary voltages. YNd Yd Dyn Dy
doesn't modify, while the two phases that participate in the In matrix form: V abc = [TR 2 ] V ABC . Where TR 2 indicate the
short circuit suffer a magnitude decrease and a phase
change. transformation matrix.
Paper 0185
TipoI TR 1 TipoII TR 2 TipoIII TR 3 In table 2 the types of sags that can be obtained by transfer
⎡1 0 0⎤ ⎡2 −1 − 1⎤ ⎡0 1 − 1⎤ from high to medium voltage and from medium to low
⎢0 0 ⎥⎥
1⎢
− 1⎥⎥
j ⎢
⎢ 1 −1 2 −1 0 1 ⎥⎥ voltage are summarized, with the consideration of the group
3⎢ 3⎢ obtained by means of the multiplication of transformation
⎣⎢ 0 0 1 ⎦⎥ ⎣⎢ − 1 −1 2 ⎦⎥ ⎣⎢ 1 −1 0 ⎥⎦
matrixes. As it is not very probable in the real world the
To maintain the phase “A” as reference with angle 0º, had presence of two type I transformers in cascade I, only
to rotate the values 90º multiplying the matrix given by j. equivalents of the group TR2 or TR3 are possible. In
3 is included so that the secondary values in pu are consequence the sags type B and E do not take place in low
similar to those of the primary one. If it is wanted to voltage nets, since zero sequence component is blocked.
analyze the transfer toward the low voltage sensitive loads, Table 2. Summary of different voltage sags types
it can be considered the connection of the transformers in
cascade by means of the multiplication of the Primary Secondary
transformation matrix, in way of obtaining an equivalent Sag Group TR1 Group TR2 GroupTR3
group. A A A A
TR 1 . TR 1 = TR 1 TR 2 .TR 2 = TR 2 B B D* C*
TR 1 . TR 2 = TR 2 TR 2 .TR 3 = TR 3 C C C D
E E G F
TR 1 .TR 3 = TR 3 TR 3 .TR 3 = TR 2